HomeMy WebLinkAboutResponse to Clay Township Waste 6-10-2013Mr. Ryan Hartman December 12, 2013 Page 1 December 12, 2013 Mr. Ryan Hartman Clay Township Regional Waste District 10701 North College Ave. Indianapolis, IN 46280 Re: Health and Wellness Suites of Carmel – TAC Review Project No. 201300569 Dear Mr. Hartman: American Structurepoint, Inc., has revised the design, construction plans and drainage report for the Health and Wellness Suites of Carmel project per the review comments listed in the letter dated June 10, 2013. Each comment listed from the review letter contains a response addressing each issue. Below are the original comments with the response in italics. 1. We ask that the prefix for the manhole be labeled as MH#MWS1. Manhole labels reflect the naming example and can be found on the Sanitary Sewer Plan & Profiles on sheets C.303 – C.304. 2. Existing MH#S2 should be labeled MH#MC-25 on Sheet C.303. Existing manholes have been renamed. See revised Utility Plan on sheet C.300 and Sanitary Sewer Plan and Profile on sheet C.303. 3. Please show profile view of 8” lateral with all utility crossings. Sanitary laterals have been revised and lateral plan and profiles can be found on the Sanitary Sewer Plan and Profile on sheet C.304. 4. Sheet C.303 plan and profile view please specify length of Jack and Bore and include casing material, thickness and diameter. Typical Boring Detail provided by Clay Township Regional Waste District has been added to sheet C.606. The appropriate notes regarding the jack and bore method, casing mater, thickness and diameter have been added to sheet C.303. Mr. Ryan Hartman December 12, 2013 Page 2 5. If Jack and Bore is utilized, granular backfill callout on profile view is not necessary. A note stating granular backfill is not required if jack and bore method is utilized has been added to Sheet C.303. 6. Min. FFE of the structure must be set 1’ above TC of up or downstream manhole (Min: 856.61) According to agreement made, a manhole structure will be added for each sanitary lateral with a casting grade no higher than 853.50 (one foot lower than the finished floor elevation) 7. Please add a note to grease interceptor to refer to detail drawing sheet C.601 Note added to the grease interceptor keynote #5 on revised Utility Plan, sheet C.300. 8. Please add hardscape/pavement bump out at interceptor location for serviceability. The grease interceptor is now located within the paved drive. 9. Please send to CTRWD a full copy of the IDEM Application and Allocation packet. IDEM Application and Allocation packet will be sent to the Clay Township Regional Waste District next week. Mr. Ryan Hartman December 12, 2013 Page 3 If you have any questions or need clarification on any of these comments, please feel free to contact me at our office (317) 547-5580. Very truly yours, American Structurepoint, Inc. Ross L. Nixon, PE, LEED AP Project Manager RLN: