-- '- ~ ----TProject number
CONSTRUCTION DESIGN RELEASE 313134
State Form 41 t 91 (R9/5-98) ~'~o~e
Report Printed on: November 1 2005
Indiana Department of Homeland Security
DIVISION OF FIRE SAFETY / PLAN REVIEW
402 W. Washington St., Room E245
ndianapotis. IN 46204
To: Owner / Architect / Engineer
LAMSON & CONDON INC
JOHN T LAMSON 4041
151 N DELAWARE ST STE 151
INDIANAPOLIS iN 46204
..t~i DANA 02~
SUPPORT HOOSIER SAFETY
Fax &e-mail: 3172660468. mlamson@lamsoncondon,com
F Release date
l 11/01/05
Occupancy classification
Scope of release
ARCH FDN
STR,
-~e of release Partia
OFFICE PARK EXPANSION
Street address
479 - 785 GRADLE DR
City County
CARMEL HAMILTON
The plans specifications and appl~cauon submitted for the above referenced project ne ]e been reviewed fo~ce w~tn tne applicable rules of
the Fire Prevention and Building Safety Commission, The project is released for construction subject to, but not necessarily, limited to. the conditions
listed below. THIS IS NOT A BUILDING PERMIT, All required local-permits and ~tcenses must oe oatamed prior to begmmng construction work, All
construction work must be in full compliance with all applicable State rules, Any changes ~n me releaseq plans and/or specifications must be filed with
and released by this Office before any wor~ is~altered. ,¢¢hie, [eleqse nay be ~uspended er revoked if it is delermieed Io be issued in error, in violation
ef any ru es of the Commission or if it is base,be ibco~ect ~ i~u~i~t idf~p~4iJon iThjs release shall expire by lin~tatibn and become null and
voic if the work authorized is not commenceawghih ot~e (1),~/~r f~lm:~e above:date,
CONDITIONS
Note :(A1A & AIB): In accordance~ the affidavit swor~ under psaalbes of perjury in the application for censtrucbon design re~ease me plans
and specifications filed in conjunci~l with this projeci: shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission, Providing false information constitutes an act of perjury, which is a Class D felony punishable by a pdson term and a fine up to $10,000.
in accordance w h Section 19 of the General Adm nistra ive Rules (675 lAC 12-6-19) a complete set of plans axed specifications that conform
exactly to the design that was reteased by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
4G0615A This is a part~ally submitted and released project. Subsequent submittals shall be accompanied by a
c~)mpleted standard / partial form (ACDR) and proper fees in accordance with 675 lAC 12-6-15(c).
3B0705C One or re'ore fre wa s are beng provided for the purposes of allowabe area and minimum
construction type in accordance with Section 705.1, IBC (675 lAC 13-2.4)
4G0412AE The proposed building or addition may not put the existing building in noncompliance or into further
noncompliance in accordance with 675 lAC 12-4-12(f)~
3B03113 Buildings classified as S-2 occupancies shall include buildings, structures, or portions thereof,
used for the storage bfnohconibUstible materials such as products on wood pallets or in paper
cartons with or without single-thickness divisions: or in paper wrappings in accordance with Section
31! .3. IBC (675 lAC 13-2.4).
4G0623A Storage of some commodities at a height of si~ feet or more may be high*piled storage as defined in
675 lAC 22-2.3. Section 202 Improper use ,,f this structure for high-~)iled storage will subject the
project design release to revocation in accordance w~th 675 lAC 12-6-23,
3B0602 Exterior walls shall have fire-resistance ratings in accordance with Table 602. IBC (675 lAC 13-2.4).
( NORTH WALL )
3B0703A Existing and new walls being used as fire barriers or fire walls shall be of tested assemblies in
accordance w~th Section 703,2. iBC f675 lAC 13-2.4].
4G0603AE Detailed plans and seecifications of the fire suppression system shall be filed with the required
application ano appropnate fees in accoraance witt' 675 lAC 12-6~3(a) and 675 lAC 13-1-8.
fN.F.P.A. 13)
3C0502H1 For a slab-on-grade floor, the perimeter insulation shall ex[ena downward from the top of the slab to
rne top of the inverted tee of a spread footing In accordance with Section 502.3.1.4. IECC (675 lAC
19-3-1 ).
Page 1/2
Would you like to reduce your turnaround time?
ELECTRONICALLY FILE YOUR ~ROJEC'r WITH STATE OF INDIANA AT
efile24-7@dhs.state,in.us. Or VISI,r OUR WEB SITE AT www.~n.gov/dhs/osbc
Please be advtsed that ~f an aom~ms[ra[~ve review of this action is des[red, a written petition for rewew must be filed at the above address w~tn tee
Fire Prevention and Sui 3 ng Safety Commission identifyin§ the mat er for wh ch a review is sought no later titan eighteen 18 dais from the above -
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Suiidieg Services is closed during normal business hours. In the latter case, the filing deadfine will be the first working day thereaffer~ if you
choose to pet tion and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission If a ~etition for review is not filed this Order will
befina and you must comply with its requirements
Filed By Code review official
IN PHILLIPS
Address (name,[ide of local officia street,city.state and ZIP code
DEPT OF COMMUNITY SERVICE
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL IN 46032
F~blanchard armeLin, ov
~C~'e Enforcement & Plan Review Branch Director
Page 2/2