Gentlemen:
We are requesting your review and approval for variances to the
building code for this project as follows:
1 . Delete one hour floor assembly and open center stair at all
levels <Stair enclosure Section 3308(a)>. Provide supervised
automatic sprinklers throughout the entire building tied to
local fire department.
2. Delete requirement for rated corridor walls including elevator
lobby vestibules <Section 3304(8&h)>. Provide supervised
smoke detectors in all public corridors. Tie supervision to
local fire department.
The leasable office space market is so competitive that building
owners need to offer greater flexibility for interior office
development conventional codes will allow in this proposed
building location on the meridian corridor. Alternative systems
proposed actually improve life safety features of the project by
greatly improving response time to stopping fires and protecting
occupants.
Two separate checks for $150.00 each are submitted along with this
letter. Checks are made out to "State Building Commissioner
Fund".
Five sets of plans for the proposed building are submitted. Plans
for supervised sprinkler system and smoke detection system will be
submitted on contractor's shop drawings for review by agency
staff.
ARCHITECTS
PLANNERS
INTERIOR DESIGNERS
8900 Keystone Crossing
Suite 1150
Indianapolis,Indiana 46240
(317)848-7800
MEMBERS OF
AMERICAN INSTITUTE OF ARCHITECTS
Wainwright Meridian Plaza
January 17, 1985
Page Two
CSO
ARCHITECTS
INCORPORATED
Enclosed please find a copy of a letter from the building owner
acknowledging these requests.
Copies of this letter have been sent to the Carmel Fire Dept. and
the Carmel Dept. of Community Development for their information.
ry truly yours,
s
Michael F. Conly, A.I.A.
Executive Vice President
djw
enclosures
cc: R. Richardson
C. Kiphart
S. Couts
J. Wheeler
R. Gerdes
M. Conly
M. Cope
file •
/ -.
January 9, 1985
Mr. Michael F. Conly
CSO Architects, Inc.
8900 Keystone Crossing, Suite 1150
Indianapolis, IN 46240
WAINWRIGHT FINANCIAL CENTER
Dear Mike:
In summarizing our January 7th meeting with Mr. Frank M. Deal, Jr. , we reviewed
the open center stair proposed for the Wainwright Building. As discussed, it is
now probable that this center stair will serve as a required exit due to leasing
considerations. Use of this stair as an exit means compliance or variance with
several specific code requirements.
Based on our meeting with Frank Deal, some design options available are:
1 . Open stair at first floor, stair enclosed at second and third floors,
provide supervised automatic sprinklers throughout the first floor,
provide supervised smoke detectors in first floor public corridors, with
all supervision tied to local fire department or approved central alarm
station. Building would have 1-hour fire resistive floor ceiling
assembly throughout. We would need to obtain, a variance on the stair
enclosure [Section 3308 (a)] and we could apply for a variance on first
floor corridor walls [Section 3304 (g&h)]. The issue of elevator lobby
vestibules on the second and third floors needs to be resolved.
2. Open center stair at all levels, provide supervised automatic sprinklers
throughout the entire building , with supervision tied to local fire
department or approved central alarm station, and provide a 1-hour fire
resistive floor ceiling assembly throughout (Type II 1-hour construc-
tion) . We could obtain variances on stair enclosure [Section 3308 (a)]
and corridor walls [Section 3304 (g&h)] including all elevator lobby
vestibules.
,-r 0
"
..r 4.?_ r . - `" .•a v.4 .. . .r 4 _,n. . rAs - -,[''t.....i 3i;. to ,,J ' Ralph Gerdes and Associates, Inc. Building Codes
'i..' 105 E. Michigan St. Fire Protection
-` Indianopolis, IN 46204 (317) 636-4700
Mr. Michael F. Conly January 9, 1985
Page 2
3. Open center stair at all levels, provide supervised automatic sprinklers
ilk 3 IS° throughout the entire building, provide supervised smoke detectors in
i®i is all public corridors with supervision tied to the local fire department
® or approved centre alarm system, and delete the 1-hour floor assembly.
D IRR® We would need to obtain a variance on the stair enclosure [Section 3308
(a) ] and we could apply for a variance on corridor walls including
elevator lobby vestibules [Section 3304 (g&h)].
4. Enclose the center stair and provide a 1-hour exit passageway from the
stair to the exterior of the building. Corridors would comply with
Section 3304 (Oh) . Elevator lobby vestibules could be required.
° If you have any questions, please call,
Very truly ours, -
R_ 1 :!d , , .
, . .
- RP:rj :_ rte'.
- Cc: • Frank Deal .. - - -
-Chief Couts :. y, _ _. .. - _ - •- - . .._
— - - .--- Mary Trietsch ----= ---=- ----:----
: . ;, _
-•- • - - V 1.5") ;,' j 3 r 'j �'7 ,-�
1138 - ~
• • : • J.L-1 ii 0 -- L.Y.)
►,': 3
. • • • ,. 'r'Ts !A►n
•
no-- •,.;..t +, .`.f4 .Y" cY... .� :-:,-',,---:4.-:;-'1,-..•'i ;."i...4, .i y s S '.!7..-4-4-.21,,'4-:-. - . y- I-}i�', -y .t: 3 ..+ i-=:_ ',4` '.t`;,•-s -
11 it
: :::::;::
Eaton & Lauth
Developers Managers Realtors
December 27, 1984
Department o,6 Fine Prevention
and Bu,i2d.ing Sa.fyety
Dtivis.ton o4 Techn.ica.E Senvices 8 Research
1099 North Men id ian S.neet
Suite 900
- - - Ind ianapo ;—IN 462 04 -
RE: Wa,inwnight Men,id an Ptaza
To Whom I.t May Concern:
P1ea,e aloes .Getters to 6e/we aus out ac noweedgment o{y a deviation
Prom min%mum nequvicements the appZicab.2e code, -" a va'zJ.ance .ins
gran ted Eno the Wa-i.nwn,i.gh- Me' id,ian P.Q.aza 066-ice &Lad.ing. The vatci-ance
wooed a-U.ow an open is.taL't cucea in the entky .lobby the bu,ied.ing. CSO
A' ch i tec tis w%Pe ,ubmi t {yon youh review the 6 pee i.6-icatiovis {yon the van iance.
Yours appnovat oiy the van lance ishcJtt not ne,?i.eve any pa ,t. es 4nom nonmat
nu pon6-ib-i! t i-e/s on
Thank. you {yon your cmsidutation oA -thiz ma .ten.
S-inceneey, yowo,
MERIDIAN ONE COMPANY
R. D. Richardon, Pantne't
RDR/mab
Metroplex Office &Conference Center
8320 Craig Street Indianapolis, IN 46250 317/842-0020
•
December 13, 1984
CS®
ARCHITECTS
SPECIAL DELIVERY INCORPORATED
Mr. Chuck Kiphart `-• u'� William C Schubert, AIA
Lester S Olds, AIA
Carmel City Building , Michael F Conly,.AIA
40'E,. Main St.
" ., Thomas L. Whitaker, AIA
Carmel , IN 46032 j[, Anita Linegar Barnett, IBD
4
RE': Wainwright Meridian Plaza
Dear Mr. Kiphart:
We, as architects for the Wainwright Meridian Plaza project at
106th and U.S. 31 , are filing for a variance with the Dept.
of Fire Prevention & ' Building Safety. We would appreciate.
your review of the plans enclosed and our summary of variance
items being requested as stated below:
1 . We would like to delete the enclosure wall on 3 sides of
the central stair. Two additional stairs are enclosed.
The owner wishes a more pleasing and inviting central stair.
2. We would like to delete the one hour wall requirement at
the north end of the 1st floor corridor where the entry
to the branch bank exists. One hour construction destroys
the aesthetic intent of the bank entry.
In order to provide equivalent or better life safety conditions,
we are proposing the use of sprinklers around the open sides of the
center stair plus sprinklers throughout the first floor lobby and
core area. Sprinkler heads will also be placed at the bank entry
at the north corridor end where approximately 6 lineal feet of one
hour wall is deleted.
We would appreciate your review of_ this variance proposal so
that we can complete plans by January 1 , 1985. A copy of the
Dept of Fire Prevention and Building Safety variance format is en-
closed also for your reference. We would also appreciate your
helping us obtain a letter as described in Paragraph 1 (f) . from
the appropriate official .
truly your. ,
// � ARCHITECTS
PLANNERS
Michael F. only, A. I ' INTERIOR DESIGNERS
Executive Vice Presid-
8900 Keystone Crossing
djw Suite 1150
Indianapolis,Indiana 46240
(317)848-7800
enclosure
MEMBERS OF
AMERICAN INSTITUTE OF ARCHITECTS
cc: file