RE: St. Mary and MarkChurch
12174 Shelbourne Rd
Carmel, IN 46032
Plan Review Comments
The undersigned has reviewed the proposed plans for the above listed project
and is forwarding the following comments for your review. All comments are
requirements of the Indiana Fire Code 2008 Edition 675 IAC 22-2.4 unless noted.
1. Two exits or exiY access doorways shall be provided from the Chapel area when the
movable partition is closed. The occupant load for this area is 79. This occupant load
requires 2 exits. (1015.1 Exit or exit access doorways required)
2. All cooking equipment shall be installed per the manufactures instructions and
guidelines. Additionally, all cooking equipment and required Hood, Duct, and Fire
suppression system installations shall comply with the requirements of the Indiana
Mechanical Code, 2008 edition.
3. The exit discharge shall provide a direct and.unobstructed access to a public way.
(1024.6 Access to a public way.) Sidewalks shall be provided from each exit discharge
to a public way.
4. Plans for the following systems shall be submitted to the Carmel Fire Department for
review and comment. 1. Fire Alarm System. 2. Automatic Fire Sprinkler System. 3. All
cooking ventilation, Hood, Grease Duct, and Fire Suppression systems.
,- -
Please respond to the above noted condition(s) in writing and forward this to my attention.
Be advised that no building permits will be approved for release by this office until the
requested response is received. If you have any qaestions I can be contacted directly at
317-571-2621.
Date: 05/20/14 By: Chris Ellison, Deputy Fire Marshal
Carmel Fire Department