HomeMy WebLinkAbout0866.2002 Certificate of Occupancy ENCOMPASS NOTEPAD - 09/17/03 PAGE 1
NOTES FOR: 020866B 08 2 - PI
DATE TIME NOTE TEXT OPERATOR "
---------- ------- -------------------------------------- --------
2003-09-17 09 : 19 : 02 Temo C/O is issued for 30 davs . jochs
A S 93 . 50 reinsoection fee apolies .
1 Secure the. ovc conduit next to the
meter base on the rear of the buildina.
2 Provide manufactures installation
instructions for all terminations and
intake of a11 furnaces .
3 The 12 x 12 electrical iunction boxes
are blocked and must be ooened for
insoection.
9 The maximum lenath of fnmc conduit
is 6 feet . Install aooroved exterior
' conduit for a11 iunction boxes and ac
units . Per IEC 356. 10
5 Romex mav be used in exterior conduit
�~� brovided that the conduit and �uction
boxes are water tiaht .
6 Level and raise the ac oads so that
the ac unit is a min, of 2 inches above
the around.
7 Show weeo holes on all exterior b=ick
faces at base of walls, windows .
8 Al1 white eonductors used as hot
conductors must be marked as hot .
9 Close a11 holes in exterior at all
suoplv chases to ac units and electrical
units .
10 All flex conduit and all conduits
must be secured next to the iunetion
boxes oer code.
11 Pack and tool all mortar ioints at
the self suoportina arches .
�---• --- 12 Install code aporoved auard rails - - —��
for the accessible ramo on both sides
and install auards on the landina .
13 Install auards max 4 inch soacina
on the well at the rear of the' buildina .
14 Install h"andrail from well on rear.
15 Inst'a11 blanks to cover all missina
soaces on pan'el boards .
16 Insfall covers on hiah limit boxes
or show manufactures install instruction
s that it is not necessarv .
17 Provide clear soace for finaers on
handrail from ist floor to basement .
18 Close all holes in the ceilinas of
the mechanical r`ooms .
19 Install a aasketed and bolted lid
for the sewaae e�ector .
. 20 Install lables at the main
discon�ect for all sub-banels on all
floors .
� 21 Install liqht for rear we11 exit 6n
� exterior .
22 Provide afci protection for
basement focd orep area .
23 Clear gfci at basement bathroom.
TOTAL LINES OF NOTES : 57
_ ;
INSPECTION WORK LOG - ONE PER PAGE DETAIL FORMAT PAGE-001
PRINTED ON 09/16/03
PERMIT �UMBER: 020866B 931 RANGE LINE RD S CARMEL
PERMIT TYPE : ZCOMNS06 G�M-NEWST-06
USAGE CLASS : COM COMMERCIAL
SPECIAL : STEWART & STEWART OFFICE BLDG RE-BOILD
PERMIT : This building suffered extensive fire damaqe and
CONDITIONS : has been demo ' ed. . . see permit 715 . 02 . It will be
AND NOTES : re-built using most of the existing foundation .
PARCEL ZD: 1610310108016000
LOT : 16 BLOCK:
S�BDIVISION : 359 NEWARK
OWNER: PHILLIP L & JUDITH E STEWART 931 RANGELINE RD S
GF_V CONTRACTOR: ANDECOR THE ANDERSON CORPORATION (317 ) 848-5000
CONTRAC_OR NAME :
INSPECT�ON TYPE: 08 FINAL
INSPECTION AREA: s��
SCHED DATE : 09/16/03 INSPECT TIME :
CONTACT INFO: RANDY STEELE 753-4122 � �/� � ��� /
INSPECTOR: �
INSTRUCTIONS :
COMMENTS :
RESULTS : PASS FAIL CAP]CEL RE-FEE FAIL CODE :
� �� �
_. _�, ..;_ _._, ,.�,_
-�NOTES�:-;x-�..__3_.. _,,..- . -.�. . - - - • _ — -- �- -- -
_� - /i-•-_ ____-- - �
n N� y � , I �
PRIOR INSPECTION .RESULTS :
00 PROJECT NOTES 10/22/02 STILL ON DO NOT ISSOE C/0
INS'PECTION NOTES,: We still have unresolved drainage
issues with this pro]ect . Kate has
been and will be working with the
design engineer to resolve the issues .
We are requesting that a C.O. not be
issued for this project until these
issues are resolved and drawings are
approved by this office . From Dick Hill .
00= PROJECT NOTES 10/O1/02 DO NOT ISSUE C/0- SEE ENG
INSPECTION NOTES : C/0 IS NOT TO BE ISSUED ONTIL DRAINAGE
ISSUES ARE RESOLVED WITI1 ENGINEERING/
, KATE. vad
00 PROJECT NOTES O8/28/02 SEE BELOW PROIR TO EURTH JO
_ ;
INSPECTI-0N NOTES : 1 FOUNDATION WALL THICKNESS NEEDS
SPEC ON APPROVED DRAWINGS 2 NO BEAMS
EXISTING AS INDICATED ON PLANS 3 MAY
BE USING USED ELECTRICAL PANELS
INSPECTION WORK LOG - ONE PER PAGE DETAIL FORMAT PAGE-002
PRZNTED ON 09/16/03
*** INSPECTION SHEET - CONTINUED ***
PERMIT i�UMBER: 020866B 931 RANGE LINE RD S CARMEL
INSPECTION TYPE: 08
PRIOR INSPECTION RESULTS (cont �dj :
02 OPPER FOOTING 08/27/02 P 10 AM AS
02 UPPER EOOTING O8/26/02 E PARTIAL NOTES JO
INSPECTION NOTES : • 1 EOOTER NOT COMPLETE, INTERIOR AND
SO�TH 2 OK OT POUR EAST, NORTH AND
WEST 3 CALL EOR ADDITIONAL INSECTION
04 ROUGH-IN 09/29/03 P JEB
09 ROOGH-IN 02/24/03 E JOE 432-523'S ALL THE REST JB
INSPECTION NOTES : Rep�ort, from Alt & Witzig Engineering was
submitted to our offices, dated
3/26/03 . This reort approved the
fillet-welded connections .
Dra'ft stop bulk heads on both floors;
Saddle clamp for vent stack. Blocking
required for 22 ' wall ( ar,ywhere
theres a seam in osb. ) Tempered window
in. landing by final . Laq bolts in steel
cclumn at top plate by front entrance .
Jcist hangers second floor top of
---- ' -�- "-""""-" ' - ' stairs .- Engineer re�ort on welds .
Plenum rated cable in cold air returns .
OK to insulate drywall interior walls
one side only
04 ROUGH-IN O1/31/03 P PARTIAL ZNSPECTION ONLY-N JB
INSPECTION NOTES : Rough of ceilings of both €loors so
they can put in drywall lid. Joe Patch
432=5235 cell
05 METER BASE 03/13/03 F AJS
INSPECTION NOTES : Note added on rough-in ins�Oection about
the report from Alt & Witzig; report
appro�es fillet-welded connections .
l . Bond CT cabnet w/ 1/0 copper per NEC
ta�le 251 . 22 .
2 . Psovide Y;iser pipes ,
• 3 . bond switch cabnet w/ 1/0 copper.
9 . tighten all EMT to bond w/ locknuts
@ switch cabnet .
- 5 . per NEC 312 .,5c (exception) - EMT w/
conduit not to code .
6 . ID white wires as hot in panels .
.
7 . Panel neutral bar lugs may receive
only one neutral .
INSPECTION WORK LOG - ONE PER PAGE DETAIL FORMAT PAGE-003
PRINTED ON 09/16/03
*** INSPECTION SHEET - CONTINUED ***
PERMIT NUMBER: 020866B 931 RANGE LINE RD S CARMEL
INSPECTION TYPE: -08
PRIOR INSPECTION RES[JLTS (cont 'd) :
08 FINAL 03/26/03 C
08- FINAL 09/16/03
13 RO[JGH-IN RE-INSPECTI 03/OS/03 F ONE ITEM SEE NOTE JO
INSPECTION NOTES : JB received en. report on c��elds 4/7
1 site inspection for welds on steel
on west wall and 2nd floor column at nw
wall . photo on s drive
25 METER BASE RE-INSPEC 03/19/03 P JAO
�. _,_'-..,- --�-- -- � _�..._<.� ._-- °"- - --
� . . .'�_ "��.- .(�- � . . . . :_. �. ,,, -r.".' ' - .' . -. .. .. - .. - . -.
��
o� r
j" ��`4MR��4�
;..
� "� This is a TEMPORARY CERTIFICATE OF
OCCUPANCY
,N��•` City of Carmel/Clay Township
_ �, Dept. of Community Services
/� �
- PERMITIt(��Jd'��� �� BUILDER: / ' ^=� �l.s�>J
, �
Location: � r ` /C_ !� '-•�� � ��--
Project Name: �l �{ . � i;t � i
. �
� INCOMPLETE ITEMS: <L�� �v � :, ��- j � /�,.• �� 7
lj �/n ; � 5 !i - �,c % ! F� - ' S ��� f1 %, p . ��� /
, '1^ . �" (
�
t:
r.
. NOTICE: THE ABOVE LISTED INCOMPLETE ITEM(S) SHALL BE
� READY AND SCHEDULED FOR RE-INSPECTION WITHIN 30 DAYS.
This TEMPORARY Certificate of Occupancy is granted with the under-
standing that the above-referenced i(em(s) be completed within 30 days,
:�� and a final re-inspection be scheduled and a permanent Certificate of
Occupancy be issued. If we do not hear from you within 30 days, late fees
` may be assessed and future permits may not be issued.
a' ,
= A$52.00 Residential re-inspection fee is assessed: Yes ❑ No ❑
`� A$93.50 Commercial, Multi-family, Institulional, or
� ,#
Industrial fee is assessed: Yes�u No ❑
�i � � � �i4� � . �l. J _�
?
' Building Inspector, � Date
�' Building & Code Enforcement
�•
�' To schedule your inspection, call 571-2444. Please notify the Building & Code
Enforcement office prior to the deadline date if any items cannot be completed
for any reason.
i•_ *.er*��.*s+�r**�+��xs*��r�*�++**��*.�e***�rr+�+r*++�+��+rr•�s++•
w'
y; S:PERMITSMOI'ICf:OPCORRlCI'IONSQ'orinspcctions)/Ficld'fempCO2003
e�- Rev.12/'02
S'
A
k
5