HomeMy WebLinkAbout19 M100 Mechanical Plan.pdf�
�
,�
,��
GAS METERII
Q Q O Q O O O O
I I i
ROOF TOP UNR INFORMATION:
ALL UNITS SUPPLIED AND INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTR4CTOR
RTU � CARRIER 48TCEAOSA2G5—OAOAO (4 TON) RTU rJ CARRIER 48TCEAOSA2G5—OAOAO (4 TON)
WITH ECONOMRER WITH ECONOMIZER
208/230/30 208/230/30
No. 10 FEEDER No. 10 FEEDER
No. 10 GROUND No. 10 GROUND
30 AM DISCONNECT 30 AM DISCONNECT
THERMOSTAT: HONEYWELL VISION PRO 8000 THERMOSTAT: HONEYWELL VISION PRO 8000
(� 2 CARRIER 48TCEAO6A2G5—OAOAO (5 TON) �U s CARRIER 48TCEA05A2G5—OAOAO (4 TON)
WITH ECONOMIZER WITH ECONOMIZER
208/230/30 208/230/30
No. 8jj fEEDER No. 10 FEEDER
No. 10# GROUND No. 10 GROUND
60 AMP DISCONNECT 30 AM DISCONNECT
THERMOSTAT: HONEYWELL VISION PRO 8000 THERMOSTAT: HONEri"lELL VISION PRO 5000
RTU 3 CARRIER 48TCEAOSA2G5—OAOAO (4 TON) RTU 7 CARRIER 48TCE407A2G5—OAOAO (6 TON)
WITH ECONOMIZER WITH ECONOMIZER
208/230/30 208/230/30
No. 10� FEEDER No. 8j� fEEDER
Na. 10 GROUND No. 8d� GROUND
30 AM DISCONNECT 60 AA1�P DISCONNECT
THERMOSTAT: HONEYWELL VISION PRO 8000 THERMOSTAT: HONEYWELL VISION PRO 8000
RTU 4 CARRIER 48TCEAOSA2G5—OAOAO (4 TON) UH�
WITH ECONOMIZER
208/230/30
No. 10 FEEDER
Na. 10 GROUND
30 AM DISCONNECT
THERMOSTAT: HONEYWELL VISION PRO 8000
MARKEL 5100 — UH050240
KW: 3.7, BTU: 12.8
208/3� 10.4amps
No. 8 FEEDER
No. 8 GROUND
15 A P BREAKER
HANGING BR4CKET:
UHA5105 3.SKW-5.OKW
7HERMOSTAT:
UHT5100
_�
_�
�
_�
MECHlWICAL PLAN
s�,� ,i8._ � _o..
EGEND
NEW SUPPLY AIR DUCiWORK
--- — NEW GAS SERVICE SUPPLY LINE
� PRICE SCD 24x24 NECK SIZE
AS NOTED
� 24x24 PRICE 80—CORE
OPRICE RCDE
� DAMPER
� THERMOSTAT
O RESTROOM EXHAUST FAN (NRNISHED AND INSTALLED
BY MECH. CONTR4CTOR—WIRED BY ELECT. CONTRACTOR)
75 CFM GREENHECK, SP—B90 120/60/10
MECHANICAL NOTES
1. ALL MECHANICAL EQUIPMENT AND INSTALLATIONS TO BE IN
ACCORDANCE WITH THE LATEST EDITION OF THE UNIFORM
MECHANICAL CODE AND ALL OTHER STATE AND LOCAL CODES.
2. ALL DUC7WORK TO BE INSULATED SHEEf MEfAL WITH
1 1/2" EXTERIOR DUCT WRAP
3. ALL BRANCH DUCTS TO BE FLIX DUCT, GARY STEEL
NUMBER 429 OR EQUAL.
4. ALL HEATING, VENTILATION AND AIR CONDRIONING THERMOSTATS
SHALL BE E�UIPPED WITH PLASTIC LOCK BOXES.
5. ALL LOCATIONS WHERE FLEXIBLE DUCiWORK IS USED, THE
FLIXIBLE DUCT SHALL NOT EXCEED 6'-0"
6. ALL UNITS TO HAVE CURB WITH SMOOTH AND FLUSH
EXTERIOR WALLS.
7. ALL ROOF TOP UNITS TO BE E�UIPPED WITH PHOTOELECTRIC
SMOKE DEfECTORS
N
�
�
�
�
s
VERSATILE
CK�]►[.�l�311�C��1
GROUP, LLC.
sm eon na�r eooa seae sio
a 1610�
P�31]9d535/9 Fox: }p,45.]581
� �� �
�
a
� �r '�
a �' ,�
N
� � �
L7 U �
Job No.:
13039
Drawn By:
Date Stamped:
oz/is/u
Checked By: Scale:
caw ta6 1/a^=t'—o^
CAD FlLE:
G:\13039\m100 mechanirnl plan.dwg
'�-( A. Bq,l' ��ii�
v �cixerr� �� :
N o.
19700309 *
STniE OF �
CERTIFIED BY:
THIS DRAWING IS THE PROPERTY OF
VERSATILE CONSTRUCTION GROUP LLC
AND IS NOT TO BE USED FOR ANY
OTHER PURPOSE THAN THE PROJECT
DESCRIBED HEREIN.
snEEr n.��.
M100