HomeMy WebLinkAboutC 507 Sanitary Sewer DetailO-RING GASKET BETWEEN ALL. RISERS AND CONE SECTIONS PLUS 1/2' EXTRUDABLE GASKET MATERIAL (KENT SEAL OR EQUAL) BASIC MANHOLE IS THE SAME AS THE PRECAST MANHOLE 48" DIA. z ' N - BENCH WALL N =I n ID t. c6; ''J n o o 0 n POLYPROPYLENE OR PLASTIC COATED STEPS CONC. DAM ADJUST TO SUIT PIPE DIAMETER AND FLOW C REBAR 0 12" o.c. HWAYS 6 12 STONE BEDDING PRECAST DROP MANHOLE SA-8 NO SCALE SANITARY SEWER BENCH SLOPE = 1/2" PER FOOT ', STANDARD MANHOLE BENCHES ce_ ;, v� NO SCALE SANITARY PIPES AND LATERALS I 5' MIN. I PROPOSED EDGE OF PAVEMENT THE CONTRACTOR SWILL BE AWARE THAT IF THE TOP OF THE TRENCH IS WITHIN 5 FEET (5') OF THE PROPOSED FUTURE BACK OF CURB THAT GRANULAR BACKFILL SHALL BE PLACED IN THE EXCAVATION AND COMPACTED PER INDOT SPECIFICATIONS FOR SUCH AREAS. THIS DISTANCE WILL BE CHECKED AT RANDOM INTERVALS DURING THE CONSTRUCTION. EXISTING GRADE 4a. rjQ , C:1� 0 -20' X 60 SAFETY BOX 60' `TRENCH DETAIL WITH SAFETY BOXDETAIL WITH SAFETY BOX cA_ 1A NO SCALE FLOWLINE or SEWER BENCH/ G NO SCALE ( CARMEL CLAY DISTRICT ) ICE EXCAVATED MATERIAL MATERIAL TO BE COMPACTED #8 CRUSHED STONE 'OR ROCK OR OTHER INCOMPRESSIBLE THE TRENCH SHOULD BE OVER EXCAVATED A MINIMUM OF 6" AND REFILLED W /f/8 CRUSHED STONE. ALL FILL IS TO MEET CLAY TWP. REGIONAL WASTE DISTRICT STANDARD. FLEXIBLE PIPE BEDDING DETAIL NO SCALE SANITARY SEWER WATER MAIN PLAN VY MIN. 10 MIN. 0 i ? I WATFR MAIN + 0 O SANITARY SEWER 7 `CLASS 22 MECH. JOINT C.I. OR CLASS 2 D.I. PIPE LIk!CONC. COLLAR k COUPLINGS FLEXIBI F C;OI1Pt_ING OR ADAPTOR USED WHEN LESS THAN 18" OR IN CASES WHERE WATER IS BELOW SAN SEWER ELEVATION NOTES: Water and sewer crossings and seperotions sholl be in accordance with Ten State Standards and local codes. There sholl be no physical connections between a public or private water supply system and a sanitary sewer or appurtenances thereto which would permit the passage of any polluted water into the potable supply. Sanitary sewers shall be laid ten (10) feet horizontally from any existing or proposed water line. The distance shall be measured edge to edge. In cases where it is not practical to maintain a ten (10) foot seperation, the appropriate reviewing agency may allow deviation on a case- by -cose basis if supported by data from the design engineer. Such deviation may allow installation of the sewer closer to a water main provided that the water main is in a separate trench or on an undisturbed earth shelf located to one side of the sewer, and at an elevation so the bottom of the water main is at least 18 inches above the top of the sewer. Sanitary sewers crossing water mains shall be laid to provide a minimum vertical seperation distance of 18 inches between the outside of water main and the outside of the sewer. This shall be the case where the water main is either above or below the sewer. The crossing sholl be arranged so that the sewer joints will be equidistant and as for as possible from the water main joints. Where a water main crosses under a sewer, adequate structural support sholl be provided for the sewer to prevent damage to the water main. When it is impossible to obtain proper horizontal and vertical seperotion as stipulated above, the sewer shot[ be designed and constructed equal to water pipe. and sholl be pressure tested to assure water tightness prior to backfilling. MIN. CROSSOVER & SEPARATION CROSSOVER & SEPARATION cA_i^, r / NO SCALE (WATER MAINS & .SANI. SEWERS) 2" LETTERS, RECESSED. FLUSH WITH SURFACE 'SELF - APPI BUILDING SETBACK OR EASEMENT NEENAH R -1642 OR EQUIVALENT, LINE. SEE PLAN FOR LATERAL LOCATIONS. W/ SELF- SEALING APPLICATION. WATERPROOF CASTINGS SHALL BE NEENAH R- 1916 -F1 OR EQUIVALENT. ALL CASTINGS TO BE STAMPED "SANITARY SEWER ", �� / _ 2.0'_ BEARING SURFACE 35 7/8' ( DEPENDENT UPON O.D. OF RING SECTION IN USE) SECTION "A -A" SANITARY SEWER NO SCALE MANHOLE FRAME AND COVER PLACE 112- DIA. EXTRU PREFORMED GASKET MA IN EACH KEYWAY -SEE DETAIL PLAN VIEW NOMINAL 1/2" BUYTL RUBBER BASE EXTRUDABLE PREFORMED GASKET MATERIAL TYP. ALL PIPE EXCEPT RISE PIPE SHALL BE AT A MINIMUM GRADE of 1.00% G4" 1. D. 1" 27 3/4" 34" O.D. PRECAST CONCRETE ADJ. GASKET DETAIL RING OR FLANGE OF CASTING. SECTION "A -A" ADJUSTING RING DETAIL SA'-28 NO SCALD CONTRACTOR SHALL PLACE A 5' POST EXPOSED 2' MINIMUM O GRADE DIRECTLY ABOVE LATERAL END. POST TO BE PAINTED RED TO ASSIST IN LOCATING LOCATION. '\ NOTE: DEPTH OF PIPE AT PROPERTY LINE TO BE APPROXIMATELY 9' BELOW ESTABLISHED GRADE EXCEPT WHERE A MIN. GRADE OF 3.0' 1.007E FROM MAIN SEWER FIXES A LESSER , DEPTH 6" PVC PLUG SEALED IN PLACE NOTE: MAGNETIC LOCATOR TAPE TO BE PLACED AT END OF EACH LATERAL. NOTE: BEDDING REQUIREMENTS FOR LATERALS SHALL BE THE SAME AS FOR MAIN SEWER LINE. FLOW CONTRACTOR SHALL PLACE A 5' POST EXPOSED 2' MINIMUM O GRADE DIRECTLY ABOVE LATERAL END. POST TO BE PAINTED RED TO ASSIST IN VISUAL LOCATION. NOTE: DEPTH OF PIPE AT PROPERTY LINE TO 3.0' BE APPROXIMATELY 9' BELOW ESTABLISHED GRADE EXCEPT WHERE A MIN. GRADE OF 1.00% FROM MAIN SEWER FIXES A LESSER DEPTH - 6" PVC PLUG SEALED IN PLACE 6" PVC PIPE PER SANITARY SEWER SPECIFICATIONS (SDR 35) PROPER CURVES SHALL BE USED FOR ALL ABRUPT CHANGES IN LINE AND GRADE. NOTE: BEDDING REOUIREMENTS FOR LATERALS SHALL BE THE SAME AS FOR MAIN SEWER LINE. SEWER MAIN �0 LATERAL ISOMETRIC PLAN /X-5 MAX MIN MAIN D DEEP LATERAL CONNECTION DETAIL A-5A NO SCALE 4"-12" 1/2" CONCRETE MAY BE FLOWABLE MORTER PER IN.DOT SPEC. 213 OR #2500 READY MIX CONCRETE. NOTE: MAGNETIC LOCATOR TAPE TO BE PLACED AT END OF EACH LATERAL. LONG RADIUS CURVE SEWER MAIN FLOW _ THIS TYPE OF CONCRETE ENCASEMENT THIS TYPE OF CONCRETE ENCASEMENT IS USED WHEN STORM SEWER IS IS USED WHEN EXCAVATING IS DW' BELOW SANITARY SEWER WHERE SHOWN JUST ABOVE SANITARY SEWER ME iE ON PROFILE. SHOWN ON PROFILE SANITARY SEWER CONCRETE ENCASEMENT DETAIL CA I I BUILDING SETBACK OR EASEMENT LINE. SEE PLAN FOR LATERAL LOCATIONS. 2.0' MINIMUM GRADE 1.00% 6" PVC PIPE PER SANITARY SEWER SPECIFICATIONS (SDR 35) ISOMETRIC LONG RADIUS CURVE PLAN LATERAL CONNECTION DETAIL NO SCALE J 0 F.{ NO SCALE PLAN NOTE: b MANHOLE CONFORMS TO ASTM C -478 JOINT CONFORMS TO NEENAH R -1642 CASTING W SELF PICK ASTM C -443 SEALING LID & CONCEALED HOLES AND STAMPED "SANITARY SEWER" TC = ELEV. FINISH GRADE TO DRAIN ®UM RUBBER BASE EXTERIOR 11" MAX: AWAY FROM CASTING BACKPLASTER MATERIAL. 1 /4 "t 3" MIN 1/16" MIN. THICKNESS FROM PRECAST CONCRETE ADJUSTER RINGS 4" 2" BELOW TOP OF CONE TO r r � MIN. -12' MAX. SEAL WITH INFI - SHIELD THE BASE OF THE MANHOLE co UNIBAND OR EQUAL. Co Z POLYPROPYLENE OR J 0 PLASTIC CIRAOTNDSTTEPS %MAX--- 16 ECCENTRIC CONE SECTION W LU 0 -RING GASKET BETWEEN SEAL EACH JOINT W /BUTYL RUBBER BASE ALL RISER AND CONE SECTIONS, PLUS 1/2" COATING 6' ABOVE & BELOW EACH JOINT (/� z UJ EXTRUDABLE GASKET (INSIDE JOINTS TO BE FILLED W /"PRECO" w Q (KENT SEAL OR EQUAL) PLUG MATERIAL.) Q z LU 24' MAX. L - ,., n� PRECAST CONCRETE SECTIONS FLOW CHANNELS THROUGH MANUFACTURED GASKET OR MANHOLES SHALL BE U- SHAPED _ a co Q I -. BOOT AROUND PIPES W /BENCHWALLS EXTENDING TO Q rn < ���■��rs��rsaassaaa a CROWN OF PIPES. 3" MIN. LU _ CONC. BASE - 1 12" MINIMUM LATERALS ENTERING MANHOLE SHALL V DIA. BE PLACED AT BENCH LEVEL w 8" FOR GREATER TFUW 4' �r J �����aaaaaaaa�s /a BARS 0 12' O.C. -B.W. GROUT BENCH 12' c 5" 4' -0" DIA. MIN. 1/2" PER FOOT SLOPE 18 CRU SHED STONE BEDDING ��s���asaaaas_a TC. = TOP OF CASTING ELEVATION NOTE : ALL MANHOLE SECTIONS WILL BE WATER PROOFED ON THE OUTSIDE WITH SPARYED BITUMINOUS COATING. SANITARY SEWER MANHOLE (`A h• r �u nu G NO SCALE ( CARMEL CLAY DISTRICT ) ICE EXCAVATED MATERIAL MATERIAL TO BE COMPACTED #8 CRUSHED STONE 'OR ROCK OR OTHER INCOMPRESSIBLE THE TRENCH SHOULD BE OVER EXCAVATED A MINIMUM OF 6" AND REFILLED W /f/8 CRUSHED STONE. ALL FILL IS TO MEET CLAY TWP. REGIONAL WASTE DISTRICT STANDARD. FLEXIBLE PIPE BEDDING DETAIL NO SCALE SANITARY SEWER WATER MAIN PLAN VY MIN. 10 MIN. 0 i ? I WATFR MAIN + 0 O SANITARY SEWER 7 `CLASS 22 MECH. JOINT C.I. OR CLASS 2 D.I. PIPE LIk!CONC. COLLAR k COUPLINGS FLEXIBI F C;OI1Pt_ING OR ADAPTOR USED WHEN LESS THAN 18" OR IN CASES WHERE WATER IS BELOW SAN SEWER ELEVATION NOTES: Water and sewer crossings and seperotions sholl be in accordance with Ten State Standards and local codes. There sholl be no physical connections between a public or private water supply system and a sanitary sewer or appurtenances thereto which would permit the passage of any polluted water into the potable supply. Sanitary sewers shall be laid ten (10) feet horizontally from any existing or proposed water line. The distance shall be measured edge to edge. In cases where it is not practical to maintain a ten (10) foot seperation, the appropriate reviewing agency may allow deviation on a case- by -cose basis if supported by data from the design engineer. Such deviation may allow installation of the sewer closer to a water main provided that the water main is in a separate trench or on an undisturbed earth shelf located to one side of the sewer, and at an elevation so the bottom of the water main is at least 18 inches above the top of the sewer. Sanitary sewers crossing water mains shall be laid to provide a minimum vertical seperation distance of 18 inches between the outside of water main and the outside of the sewer. This shall be the case where the water main is either above or below the sewer. The crossing sholl be arranged so that the sewer joints will be equidistant and as for as possible from the water main joints. Where a water main crosses under a sewer, adequate structural support sholl be provided for the sewer to prevent damage to the water main. When it is impossible to obtain proper horizontal and vertical seperotion as stipulated above, the sewer shot[ be designed and constructed equal to water pipe. and sholl be pressure tested to assure water tightness prior to backfilling. MIN. CROSSOVER & SEPARATION CROSSOVER & SEPARATION cA_i^, r / NO SCALE (WATER MAINS & .SANI. SEWERS) 2" LETTERS, RECESSED. FLUSH WITH SURFACE 'SELF - APPI BUILDING SETBACK OR EASEMENT NEENAH R -1642 OR EQUIVALENT, LINE. SEE PLAN FOR LATERAL LOCATIONS. W/ SELF- SEALING APPLICATION. WATERPROOF CASTINGS SHALL BE NEENAH R- 1916 -F1 OR EQUIVALENT. ALL CASTINGS TO BE STAMPED "SANITARY SEWER ", �� / _ 2.0'_ BEARING SURFACE 35 7/8' ( DEPENDENT UPON O.D. OF RING SECTION IN USE) SECTION "A -A" SANITARY SEWER NO SCALE MANHOLE FRAME AND COVER PLACE 112- DIA. EXTRU PREFORMED GASKET MA IN EACH KEYWAY -SEE DETAIL PLAN VIEW NOMINAL 1/2" BUYTL RUBBER BASE EXTRUDABLE PREFORMED GASKET MATERIAL TYP. ALL PIPE EXCEPT RISE PIPE SHALL BE AT A MINIMUM GRADE of 1.00% G4" 1. D. 1" 27 3/4" 34" O.D. PRECAST CONCRETE ADJ. GASKET DETAIL RING OR FLANGE OF CASTING. SECTION "A -A" ADJUSTING RING DETAIL SA'-28 NO SCALD CONTRACTOR SHALL PLACE A 5' POST EXPOSED 2' MINIMUM O GRADE DIRECTLY ABOVE LATERAL END. POST TO BE PAINTED RED TO ASSIST IN LOCATING LOCATION. '\ NOTE: DEPTH OF PIPE AT PROPERTY LINE TO BE APPROXIMATELY 9' BELOW ESTABLISHED GRADE EXCEPT WHERE A MIN. GRADE OF 3.0' 1.007E FROM MAIN SEWER FIXES A LESSER , DEPTH 6" PVC PLUG SEALED IN PLACE NOTE: MAGNETIC LOCATOR TAPE TO BE PLACED AT END OF EACH LATERAL. NOTE: BEDDING REQUIREMENTS FOR LATERALS SHALL BE THE SAME AS FOR MAIN SEWER LINE. FLOW CONTRACTOR SHALL PLACE A 5' POST EXPOSED 2' MINIMUM O GRADE DIRECTLY ABOVE LATERAL END. POST TO BE PAINTED RED TO ASSIST IN VISUAL LOCATION. NOTE: DEPTH OF PIPE AT PROPERTY LINE TO 3.0' BE APPROXIMATELY 9' BELOW ESTABLISHED GRADE EXCEPT WHERE A MIN. GRADE OF 1.00% FROM MAIN SEWER FIXES A LESSER DEPTH - 6" PVC PLUG SEALED IN PLACE 6" PVC PIPE PER SANITARY SEWER SPECIFICATIONS (SDR 35) PROPER CURVES SHALL BE USED FOR ALL ABRUPT CHANGES IN LINE AND GRADE. NOTE: BEDDING REOUIREMENTS FOR LATERALS SHALL BE THE SAME AS FOR MAIN SEWER LINE. SEWER MAIN �0 LATERAL ISOMETRIC PLAN /X-5 MAX MIN MAIN D DEEP LATERAL CONNECTION DETAIL A-5A NO SCALE 4"-12" 1/2" CONCRETE MAY BE FLOWABLE MORTER PER IN.DOT SPEC. 213 OR #2500 READY MIX CONCRETE. NOTE: MAGNETIC LOCATOR TAPE TO BE PLACED AT END OF EACH LATERAL. LONG RADIUS CURVE SEWER MAIN FLOW _ THIS TYPE OF CONCRETE ENCASEMENT THIS TYPE OF CONCRETE ENCASEMENT IS USED WHEN STORM SEWER IS IS USED WHEN EXCAVATING IS DW' BELOW SANITARY SEWER WHERE SHOWN JUST ABOVE SANITARY SEWER ME iE ON PROFILE. SHOWN ON PROFILE SANITARY SEWER CONCRETE ENCASEMENT DETAIL CA I I BUILDING SETBACK OR EASEMENT LINE. SEE PLAN FOR LATERAL LOCATIONS. 2.0' MINIMUM GRADE 1.00% 6" PVC PIPE PER SANITARY SEWER SPECIFICATIONS (SDR 35) ISOMETRIC LONG RADIUS CURVE PLAN LATERAL CONNECTION DETAIL NO SCALE J 0 F.{ NO SCALE Table I: Time in Seconds Required For Pressure Drop From 3.5 PSIG to 2.5 PSIG (Based on 0.003 cfm per sq. ft. and 2.0 cfm) AIR TEST SCHEDULE NO SCALE 6� 5 3' TYPICAL SANITARY SEWER SPECIFICATIONS TO BE USED FOR PRIVATE SEWER DEVELOPMENT WITHIN CLAY TOWNSHIP REGIONAL WASTE DISTRICT REVISED SEPTEMBER, 1999 1. Standard specifications of the Clay Waste District and Indiana Deportment of Highways sholl apply for all work and materials. Pipe sholl be installed in accordance with Section 715, 2. Sanitary sewer pipe sholl be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321. PVC pipe shall have grooved bell and gasket. The pipe sholl be mode of PVC plastic having a cell classification of 12454B. 3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in sizes through 8" shall be molded in one piece with elostomeric joints and minimum socket depths as specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of fittings shall be SDR 26 as defined in section 7.4.1 of the specifications. Gaskets for elostomeric joints shall be molded with a minimum cross - sectional area of 0.20 square inches and conform to ASTM F -477 specification. Fittings shall be manufactured by Harco or equal. 4. All sdnitor'y manholes sholl be "precast concrete" manholes in accordance with ASTM C -478 and Section 720. 0 -rings sholl conform to C -443. Kent Seal or equivalent shall also be applied to all joints and between riser rings and castings. Manhole step spacing shalt be no more than 16- inches. Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test. A. Installation and operation of vacuum equipment and indicating devices must be in accordance with manufacturer's recommendations and performance specifications which have been provided by the manufacturer and accepted by the Engineer. B. With the vacuum tester set in place: 1. Inflate the compression bond to forty (40) psi to effect a seal between the vacuum base and the structure. 2. Connect the vacuum pump to the outlet port with the valve open. 3. Draw a vacuum of ten (10) inches of Hg. and close the valve. C. Accepted standards for leakage will be established from the elapsed time for a negative pressure change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate for a four -(4) foot diameter manhole must be in accordance with the following: Minimum Elapsed Time for a Manhole Depth Pressure Change of 1 Inch Hg. 10 feet or less 60 seconds >10 feet but <15 feet 75 seconds >15 feet but <25 feet 90 seconds For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six (6) feet in diameter, add on additional thirty (30) seconds to the time requirements for four (4) foot diameter manholes. For all manholes deeper than twenty -five (25) feet, engineer will determine the applicable minimum elapsed time. D. If the manhole foils the test, necessary repoirs must be made and the vacuum test and repairs must be repeated until the manhole passes the test. E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be disassembled and the joint sealants replaced. F. Manholes will be subject to visual inspection with all visual leaks being repaired. 5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches below each joint. The appropriate primer sholl be applied prior to applying the rubber coating. Inside joints to be filled with precoot plug material. 6. The manhole chimney's including all riser rings shall be sealed using Infi- Shield " Uniband" or approved equal. Prior to placement, the top 4- inches of the manhole cone and casting frame shall be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section to 2- inches over the flange of the manhole costing frame. 7. The costing elevations are set by plan. However, the castings are to be adjusted in the field by the Engineer s representative, should a discrepancy occur between plan grade and existing grode. New manhole ring and cover shall be installed to establish grode. Maximum height of adjusting rings shall be 12- inches. 8. Bockfill around all structures and all cuts under paved areas with granular material. Trenches opening with 5 -feet of paved roadways shall be backfilled with granular material in accordance with Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum of six months after backfill has been in- place. 9. The Contractor shall be responsible for verifying that oil state highways, city and county permits have been obtained by the developer prior to start of construction. 10. The Contractor shall be required to furnish the developer's Engineer with a set of prints, marked in red pencil, showing actual sewer location and invert, to include lateral location, depth and length. Such 'as- built" prints must be received by the Engineer before the final contract payment can be authorized. The sonitory sewer laterals and stubs termination shall be indicated on the surface with a metal fence post set immediately above said termination point. 11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a representative of the Cloy Waste District. The testing shall be in accordance with Table 1. 12. Deflection tests shall be performed on all flexible* pipe after the final bockfill has been in -place at least 30 days. No pipe shall exceed a vertical deflection of five percent (5%) deflection test results. ( *The following are considered non - flexible pipes: concrete pipe, ductile iron pipe and cast iron pipe.) The deflection test shall be performed with a nine -point mandrel. Proving rings shall be available. 13. All mandrel testing sholl be observed by a Professional Engineer for certification and a representative of the Clay Waste District. 14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of withstanding a low pressure air test without leakage. 15. Bedding for flexible pipe sholl be No. 8 crushed stone from 6- inches below the pipe to 12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below the pipe to the spring line of the pipe and from this point to 12- inches above shall be fill sand or equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding. 16. Water and sewer line crossings and separations sholl be in accordance with Ten States Standards. 17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstructions, and shall be property protected and /or barricaded when left unattended. 18. No water shall be permitted to flow into the sanitary sewer system during construction. Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be directed to a storm outlet. Any pipe entering existing sewers shall be plugged, with screw type mechanical, braced plug, until such time as all tests on the sewers have been completed and the lines have passed all punch lists. 19. All sewer laterals installed by the mainline Contractor shall be bedded the some as the main line sewer. 20. Forty -eight (48) hours notice sholl be given to the Clay Regional Waste District prior to the start of sewer construction. Also, 48 -hours notice sholl be given prior to any testing done on the sewer. 21. Manhole costings shall be stomped "SANITARY SEWER" (Neenah Costing R 1642 or equal) and be self - sealing type. Waterproof castings shall be Neenah R- 1916 -F1 and stamped "SANITARY SEWER 22. The minimum slope for sewer acceptance by the Clay Township Regional Waste District are: Size of Pipe Minimum Constructed Slope 8 -inch 0.40% 10 -inch 0.28% 12 -inch 0.22% 15 -inch 0.15% 18 -inch 0.12% 23. The Contractor shall provide measurements of the slope of the sewer for each manhole section as construction progresses. Such measurements sholl be certified by a Registered Land Surveyor or Engineer and be available on -site for observation by the District s Inspector. No more than three manhole sections can be constructed in advance of such measurements. 24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other affected sewer sections shall be reconstructed to meet such minimum slopes. t b N r- xr Z r r -1 co Co Z J 0 W LU 0­1- (/� z UJ r,, sr�■�s�s�n�s����r�s�r��sa w Q 0 Q z LU L - ,., n� 0 a co Q I -. Q rn < ���■��rs��rsaassaaa a `, LU - 1 �■IIIIIIIXIIIIII�■saaa�aa V w ,�; I� �r J �����aaaaaaaa�s c , I ��s���asaaaas_a 71 c� m •' s��sssaaasaaa �s��aaasasaaaaa • s��aaasaaaaaa ., ���aaaaaaaassa f r. srsssaaaaaaasasaa �■�ssaaaassaasa ., �=�Iaasaaaaaasaaa .: �Iaasaaaaaaaaaa .00 �aa_asaaasaaaa . e 11111iti�ii���ii,����i������i Table I: Time in Seconds Required For Pressure Drop From 3.5 PSIG to 2.5 PSIG (Based on 0.003 cfm per sq. ft. and 2.0 cfm) AIR TEST SCHEDULE NO SCALE 6� 5 3' TYPICAL SANITARY SEWER SPECIFICATIONS TO BE USED FOR PRIVATE SEWER DEVELOPMENT WITHIN CLAY TOWNSHIP REGIONAL WASTE DISTRICT REVISED SEPTEMBER, 1999 1. Standard specifications of the Clay Waste District and Indiana Deportment of Highways sholl apply for all work and materials. Pipe sholl be installed in accordance with Section 715, 2. Sanitary sewer pipe sholl be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321. PVC pipe shall have grooved bell and gasket. The pipe sholl be mode of PVC plastic having a cell classification of 12454B. 3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in sizes through 8" shall be molded in one piece with elostomeric joints and minimum socket depths as specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of fittings shall be SDR 26 as defined in section 7.4.1 of the specifications. Gaskets for elostomeric joints shall be molded with a minimum cross - sectional area of 0.20 square inches and conform to ASTM F -477 specification. Fittings shall be manufactured by Harco or equal. 4. All sdnitor'y manholes sholl be "precast concrete" manholes in accordance with ASTM C -478 and Section 720. 0 -rings sholl conform to C -443. Kent Seal or equivalent shall also be applied to all joints and between riser rings and castings. Manhole step spacing shalt be no more than 16- inches. Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test. A. Installation and operation of vacuum equipment and indicating devices must be in accordance with manufacturer's recommendations and performance specifications which have been provided by the manufacturer and accepted by the Engineer. B. With the vacuum tester set in place: 1. Inflate the compression bond to forty (40) psi to effect a seal between the vacuum base and the structure. 2. Connect the vacuum pump to the outlet port with the valve open. 3. Draw a vacuum of ten (10) inches of Hg. and close the valve. C. Accepted standards for leakage will be established from the elapsed time for a negative pressure change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate for a four -(4) foot diameter manhole must be in accordance with the following: Minimum Elapsed Time for a Manhole Depth Pressure Change of 1 Inch Hg. 10 feet or less 60 seconds >10 feet but <15 feet 75 seconds >15 feet but <25 feet 90 seconds For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six (6) feet in diameter, add on additional thirty (30) seconds to the time requirements for four (4) foot diameter manholes. For all manholes deeper than twenty -five (25) feet, engineer will determine the applicable minimum elapsed time. D. If the manhole foils the test, necessary repoirs must be made and the vacuum test and repairs must be repeated until the manhole passes the test. E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be disassembled and the joint sealants replaced. F. Manholes will be subject to visual inspection with all visual leaks being repaired. 5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches below each joint. The appropriate primer sholl be applied prior to applying the rubber coating. Inside joints to be filled with precoot plug material. 6. The manhole chimney's including all riser rings shall be sealed using Infi- Shield " Uniband" or approved equal. Prior to placement, the top 4- inches of the manhole cone and casting frame shall be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section to 2- inches over the flange of the manhole costing frame. 7. The costing elevations are set by plan. However, the castings are to be adjusted in the field by the Engineer s representative, should a discrepancy occur between plan grade and existing grode. New manhole ring and cover shall be installed to establish grode. Maximum height of adjusting rings shall be 12- inches. 8. Bockfill around all structures and all cuts under paved areas with granular material. Trenches opening with 5 -feet of paved roadways shall be backfilled with granular material in accordance with Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum of six months after backfill has been in- place. 9. The Contractor shall be responsible for verifying that oil state highways, city and county permits have been obtained by the developer prior to start of construction. 10. The Contractor shall be required to furnish the developer's Engineer with a set of prints, marked in red pencil, showing actual sewer location and invert, to include lateral location, depth and length. Such 'as- built" prints must be received by the Engineer before the final contract payment can be authorized. The sonitory sewer laterals and stubs termination shall be indicated on the surface with a metal fence post set immediately above said termination point. 11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a representative of the Cloy Waste District. The testing shall be in accordance with Table 1. 12. Deflection tests shall be performed on all flexible* pipe after the final bockfill has been in -place at least 30 days. No pipe shall exceed a vertical deflection of five percent (5%) deflection test results. ( *The following are considered non - flexible pipes: concrete pipe, ductile iron pipe and cast iron pipe.) The deflection test shall be performed with a nine -point mandrel. Proving rings shall be available. 13. All mandrel testing sholl be observed by a Professional Engineer for certification and a representative of the Clay Waste District. 14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of withstanding a low pressure air test without leakage. 15. Bedding for flexible pipe sholl be No. 8 crushed stone from 6- inches below the pipe to 12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below the pipe to the spring line of the pipe and from this point to 12- inches above shall be fill sand or equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding. 16. Water and sewer line crossings and separations sholl be in accordance with Ten States Standards. 17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstructions, and shall be property protected and /or barricaded when left unattended. 18. No water shall be permitted to flow into the sanitary sewer system during construction. Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be directed to a storm outlet. Any pipe entering existing sewers shall be plugged, with screw type mechanical, braced plug, until such time as all tests on the sewers have been completed and the lines have passed all punch lists. 19. All sewer laterals installed by the mainline Contractor shall be bedded the some as the main line sewer. 20. Forty -eight (48) hours notice sholl be given to the Clay Regional Waste District prior to the start of sewer construction. Also, 48 -hours notice sholl be given prior to any testing done on the sewer. 21. Manhole costings shall be stomped "SANITARY SEWER" (Neenah Costing R 1642 or equal) and be self - sealing type. Waterproof castings shall be Neenah R- 1916 -F1 and stamped "SANITARY SEWER 22. The minimum slope for sewer acceptance by the Clay Township Regional Waste District are: Size of Pipe Minimum Constructed Slope 8 -inch 0.40% 10 -inch 0.28% 12 -inch 0.22% 15 -inch 0.15% 18 -inch 0.12% 23. The Contractor shall provide measurements of the slope of the sewer for each manhole section as construction progresses. Such measurements sholl be certified by a Registered Land Surveyor or Engineer and be available on -site for observation by the District s Inspector. No more than three manhole sections can be constructed in advance of such measurements. 24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other affected sewer sections shall be reconstructed to meet such minimum slopes. t CERTIFIED BY: or f N! • PM S K N G 15TE � �J No 160900358', z 1 STATE OF � %sSN V- Draw" W. KMK Checked W. - - - -- - - - -- - - -- - - AS -- Quordy Amrome: ShM- - - -- 0507 Dole 07-16-01 Project Number 960324 -20600 b N r- xr Z r r -1 co Co Z J 0 W LU 0­1- (/� z UJ Z 0 (� w Q 0 Q z LU L - n� 0 a co Q I -. Q rn < a `, LU - 1 V w ,�; I� �r J c 71 c� CERTIFIED BY: or f N! • PM S K N G 15TE � �J No 160900358', z 1 STATE OF � %sSN V- Draw" W. KMK Checked W. - - - -- - - - -- - - -- - - AS -- Quordy Amrome: ShM- - - -- 0507 Dole 07-16-01 Project Number 960324 -20600