HomeMy WebLinkAbout086 IMPA Bid Set 3 - H402.pdfNOTES:
1. FOLLOW MANUFACTURER'S RECOMMENDATIONS
ON ALL PIPE SIZING AND ROUTING.
2. PITCH ALL HORIZONTAL LINES A MINIMUM OF 1/2" IN
10 FEET IN DIRECTION OF REFRIGERANT FLOW.
3. HORIZONTAL DIMENSION OF OIL TRAPS MUST BE
AS SMALL AS POSSIBLE.
4. INSULATE ALL SUCTION LINES.
5. PROPERLY SUPPORT ALL LIQUID AND SUCTION
LINES AS SPECIFIED
THERMOSTATIC
EXPANSION VALVE
SOLE NOI D VALVE
SIGHT GLASS
FILTER-DRIER
,
rANGLE VALVE
EVAPORATOR COIL
OIL TRAP
LOOP TO TOP OF EVAPORATOR
T4 PREVENT LIQUID FROM
DRAINING TO COMPRESSOR
SCALE: NONE
ROOF DECK EXTENDED TO
DUCT QPENING
EXTEND
AS INDICATED ON PLANS
CONDENSATE P-TRAP /
B E LO W ROO F J
ANGLE STEEL
� FRAMING FOR DUCT
RTU
/ AI R-004LE D
CONDENSING UNIT
`LIQUID LINE {SIZE PER PLANS}
SUCTION LINE (SIZE PER PLANS}
5/8" DENSGLASS, 2.5
PCF, 0.13 P/SQ. FT.
(2} WHISPERTONE,
4.75 PCF - (2}X 0.25
P/SQ. FT.
5/8" DENSGLASS, 2.5
PCF, 0.13 P/SQ. FT.
ROOF
DECK
� �� �
� ��
� ��
� ��
� � JOIST
� ��
�� ��
�� ��
� ��
�� � �
�� �
� �' � � SEE DETAIL FOR RTU-1'S ADDITIONAL LAYERS
� �� ON THIS SHEET (ABOVE}
�� ��
�� � ��
�� � �
�� � �
/ ��
�� WRAP VERTICAL DUCT WITH MASS-LOADED
��
�� ' VINYL (MIN 1 LB PER FT2). SEAL ALL SEAMS.
��
��
��
�
��
��
�
�� -
/ ��
�
��
�
��
/ ��
��
��
�� �
� ��
��
/ , „ " �� � LINED DUCT
� �� �
TYPICAL FOR SUPPLY AND RETURN DUCT
SCALE: NONE