HomeMy WebLinkAboutA010-6 - WALL TYPES GENERAL NOTES AND DETAILS.pdfXX
DIMENSION PLAN SYMBOLS
NEW COLUMN LINE
DETAIL INDICATORAREA OF
DETAIL DETAIL NUMBER
SHEET NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
PLAN NOTE DESIGNATION
DOOR NUMBER DESIGNATION
FLOOR DRAIN
CURTAIN TRACK W/ CURTAIN
F.D.
A101
1 SIM SIMILAR
ROOM
000
10
1
1
XX EXISTING COLUMN LINE
H.
O
.
A
U
T
O
NEW DOOR
NEW WALL
DOOR WITH MAGNETIC HOLD OPEN DEVICES
DOOR WITH AUTOMATIC DOOR OPERATOR
NEW DOOR
NEW WALL
PUSH PLATE FOR AUTO DOOR OPERATOR
CARD READER FOR ELECTRIC DOOR LATCH
KEYPAD FOR ELECTRIC DOOR LATCH
KEY FOB
TOUCHLESS ACTUATOR
CR
PP
TA
KF
KP
2-HOUR RATED FIRE BARRIER- 2H
WALL RATINGS
GENERAL DIM. PLAN NOTES
3-HOUR RATED FIRE BARRIER- 3H
1-HOUR RATED FIRE BARRIER- 1H
C.
ALL INTERIOR GYPSUM DRYWALL WALLS SHALL BE TYPE 'B3' UNLESS NOTED
OTHERWISE.
D.
E.
ALL DIMENSIONS ARE TO CENTER OF COLUMN LINES, FACE OF DRYWALL OR
TO FACE OF EXISTING WALL FINISH, UNLESS NOTED OTHERWISE.
REFER TO 'IF' SHEET SERIES FOR ADDITIONAL INTERIOR FINISH INFORMATION.
REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL
INFORMATION.
F.
G.
ALL INTERIOR GYPSUM DRYWALL COLUMN SURROUNDS SHALL BE WALL TYPE
'A2' UNLESS NOTED OTHERWISE.
H.
CONTRACTOR SHALL VERIFY ALL EXISTING CONSTRUCTION AND NOTIFY THE
ARCHITECT/ENGINEER OF ANY DISCREPANCIES.
A.
B.REFER TO SHEET A500.6 FOR OPENING SCHEDULE AND TYPICAL INTERIOR
DOOR OPENING DETAILS.
REFER TO SHEET A010.6 FOR WALL TYPES.
PROVIDE 5/8" GYPSUM DRYWALL ON INSIDE OF ALL TENANT SPACE WALLS.
GYPSUM DRYWALL TO BE FOIL FACED AT ALL EXTERIOR WALL LOCATIONS.
I.
ALL COLUMN SURROUNDS SHALL BE 1'-0" FROM CENTERLINE OF COLUMN TO
EXTERIOR FACE OF DRYWALL IN ALL DIRECTIONS, UNLESS NOTED OTHERWISE.
J.
WALL TYPE
WALL TYPE SUFFIXXX.#
DOOR FRAMES SHALL BE TYPICALLY 6" FROM PERPENDICULAR CORNER TO
DOOR OPENING (INSIDE OF FRAME), ULESS NOTED OTHERWISE.
K.
1
A000 2
3
4
XX
ARCH. PLAN SYMBOLS
NEW COLUMN LINE
DETAIL INDICATORAREA OF
DETAIL DETAIL NUMBER
SHEET NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
PLAN NOTE DESIGNATION
EQUIPMENT DESIGNATION. REFER
TO EQUIPMENT SCHEDULE.
ELEVATION TAG
GENERAL ARCH. PLAN NOTES
A.
B.
A101
1 SIM SIMILAR
000
ROOM
000
1
REFER TO SHEET A010.6 FOR TOILET ACCESSORIES SCHEDULE.
PAINTING CONTRACTOR SHALL LABEL, ABOVE CEILING, ALL FIRE RATED
WALL CONSTRUCTION AND SMOKE BARRIER WALL CONSTRUCTION IN
ACCORDANCE WITH SPECIFICATION.
C.REFER TO SHEET A010.6 FOR EQUIPMENT SCHEDULE. REFER TO M/E/P
DRAWINGS TO COORDINATE CONNECTIONS.
XX EXISTING COLUMN LINE
D.ALL FURNITURE SHOWN FOR REFERENCE ONLY.
E.REFER TO INTERIOR FINISH PLANS FOR LOCATIONS OF HANDRAILS,
BUMPRAILS, CORNER GUARDS, AND WALL PROTECTION.
TOILET ACCESSORY NOTE DESIGNATION1
F.REFER TO INTERIOR FINISH PLANS FOR WINDOW SHADE TYPES AND
LOCATIONS.
G.REFER TO A010.6/1 FOR TYPICAL ADA TOILET ROOM INFORMATION.
REFER TO M/E/P DRAWINGS TO COORDINATE CONNECTIONS.
H.PROVIDE (1) COAT HOOK CENTERED ON BACK SIDE OF DOOR IN EACH TOILET
ROOM. PROVIDE (2) COAT HOOKS CENTERED ON BACK SIDE OF DOOR IN
EACH CLINIC ROOM. ALL COAT HOOKS TO BE MOUNTED AT 5'-6" A.F.F.
GENERAL RC PLAN NOTES
A.ALL LAY-IN ACOUSTICAL CEILINGS SHALL BE INSTALLED AT 9'-0" ABOVE FINISH
FLOOR, UNLESS NOTED OTHERWISE.
B.
REF. CEILING PLAN SYMBOLS
ACT - 1
SUSPENDED LAY-IN CEILING SYSTEM
RECESSED "CAN" TYPE LIGHT FIXTURE OR PENDANT
CEILING MOUNTED EXIT LIGHT
CUBICLE CURTAIN TRACK AND CURTAIN
2'x4' LIGHTING FIXTURE
2'x2' LIGHTING FIXTURE
RETURN AIR GRILLE
SUPPLY AIR GRILLE
SUPPLY AIR GRILLE
CEILING HEIGHT ABOVE FINISH FLOOR
DRYWALL BULKHEAD/CEILING
1'x4' LIGHTING FIXTURE
ACOUSTICAL CEILING TILE - TYPE
EXHAUST AIR GRILLE
+9'-0"
LOBBY LIGHT FIXTURE (EXISTING)
CHAIN HUNG LIGHT FIXTURE
ALL LAY-IN ACOUSTICAL CEILINGS SHALL BE TYPE 3, UNLESS NOTED
OTHERWISE.
C.ALL GYPSUM DRYWALL BULKHEADS SHALL BE INSTALLED AT 8'-6" ABOVE
FINISHED FLOOR, UNLESS NOTED OTHERWISE. ALL GYPSUM DRYWALL
BULKHEADS ABOVE CASEWORK SHALL BE INSTALLED AT 7'-2" ABOVE FINISHED
FLOOR.
D.REFER TO INTERIOR FINISH PLANS FOR GYPSUM DRYWALL BULKHEAD
FINISHES.
E.FIRE RATINGS NOT SHOWN ON REFLECTED CEILING PLANS. REFER TO LIFE
SAFETY PLANS OR DIMENSION PLANS FOR WALL RATING LOCATIONS.
INT. ELEV. SYMBOL LEGEND
GENERAL INT. ELEV. NOTES
A.REFER TO SHEET A010.6 FOR THE EQUIPMENT LIST AND TOILET
ACCESSORIES SCHEDULE. REFER TO M/E/P DRAWINGS TO COORDINATE
CONNECTIONS.
C.
ALL DIMENSIONS ARE TAKEN TO THE FACE OF FINISHED MATERIAL.
D.
COORDINATE BULKHEAD HEIGHTS INDICATED ON INTERIOR ELEVATIONS WITH
THAT SHOWN ON THE REFLECTED CEILING PLAN. CONFIRM ANY
DISCREPANCIES WITH THE ARCHITECT PRIOR TO CONSTRUCTION.
E.
PROVIDE A 4" HIGH INTEGRAL BACK SPLASH ON ALL COUNTERS WITH
RECESSED SINKS. INSTALL SIDE SPLASHES WHERE THESE COUNTERS
ABUT A WALL, UNLESS NOTED OTHERWISE.
F.
PROVIDE ADJUSTABLE SHELVING WITHIN ALL WALL AND BASE CABINETRY AS
SHOWN BY DASHED LINE.
G.
PROVIDE 12" CLEAR INTERIOR DIMENSION ON ALL UPPER WALL CABINETS
UNLESS NOTED OTHERWISE.
H.
COORDINATE ALL WALL OUTLETS TO AVOID CONFLICT WITH CASEWORK.
I.
INSTALL WOOD BLOCKING TO STUDS TO SUPPORT ALL WALL-MOUNTED
CABINETRY AND EQUIPMENT AS REQUIRED.
J.
ALL CASEWORK SHALL BE FINISHED WOOD UNLESS NOTED OTHERWISE.
K.
CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTING
CABINETRY.
L.
PROVIDE FILLER PANELS AT ALL LOCATIONS WHERE CABINETRY ABUTS A
WALL.
ALL BASE CABINETS SHALL BE 2'-0" DEEP UNLESS NOTED OTHERWISE.
XX NEW COLUMN LINE
SECTION INDICATOR
DETAIL INDICATORAREA OF
DETAIL DETAIL NUMBER
SHEET NUMBER
ELEVATION NOTE DESIGNATION
A101
1 SIM SIMILAR
1
A101
SIM
1
TOILET ACCESSORY#
B.
ABBREVIATION LIST
A.F.F.ABOVE FINISHED FLOOR
ALT. ALTERNATE
ALUM.ALUMINUM
APP.APPLICABLE
ARCH.ARCHITECTURAL
AXON.AXONOMETRIC DRAWING
B.C.BRICK COURSE /
BRICK COURSES
B.O.BOTTOM OF
CL.CENTERLINE
CLR.CLEAR
C.M.U.CONCRETE MASONRY UNIT
CONFIG.CONFIGURATION
CONT.CONTINUOUS / CONTINUED
C.F.C.I.CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
C.J.CONTROL JOINT
DIMS.DIMENSIONS
E.J.EXPANSION JOINT AT
BRICK VENEER
ELEC.ELECTRICAL
ELEV.ELEVATION
EQ.EQUAL
E.W.C.ELECTRIC WATER COOLER
EXT.EXTERIOR
F.E.FIRE EXTINGUISHER
F.E.C.FIRE EXTINGUISHER CABINET
F.R.T.FIRE RETARDANT TREATED
GA.GAUGE
GALV.GALVANIZED
G.S.F.GROSS SQUARE FEET
GYP.GYPSUM
HORIZ.HORIZONTAL / HORIZONTALLY
INT.INTERIOR
L.C.C.LEAD COATED COPPER
JT.JOINT
MAX.MAXIMUM
MECH.MECHANICAL / MECHANICALLY
MER.MOLDED EPOXY RESIN
MFGR.MANUFACTURER/S
MIN.MINIMUM
M.O. MASONRY OPENING
O.C.ON CENTER
O.H.OPPOSITE HAND
O.F.O.I.OWNER FURNISHED, OWNER
INSTALLED
O.F.C.I.OWNER FURNISHED,
CONTRACTOR INSTALLED
P.PLASTIC
RAD./R/RADIUS
REF.REFER / REFERENCE
R.O.ROUGH OPENING
SIM.SIMILIAR
S.F.SQUARE FEET
S.S.STAINLESS STEEL
S.S.G.STRUCTURAL SILICON GLAZED
STRUC.STRUCTURAL
T.O.TOP OF
U.N.O.UNLESS NOTED OTHERWISE
V.VARIES
VERT.VERTICAL / VERTICALLY
V.I.F.VERIFY IN FIELD
W/WITH
DIAMETER
GENERAL WALL TYPE NOTES
A.DIMENSIONS IN PLAN AND ELEVATION ARE TAKEN TO THE FACE OF FINISH
DRYWALL OR CENTER LINE OF COLUMN, UNLESS NOTED OTHERWISE.
B.ALL INTERIOR WALLS SHALL BE TYPE 'B3' UNLESS NOTED OTHERWISE. ALL
COLUMN SURROUNDS SHALL BE WALL TYPE 'A2' UNLESS NOTED
OTHERWISE.
C.PROVIDE FULL HEIGHT STRUCTURAL STUDS TO THE STRUCTURE ABOVE
AT ALL CORNERS, AT DOOR AND BORROWED LIGHT FRAMES, JAMBS,
AND BEHIND ALL WALL MOUNTED EQUIPMENT AND/ OR CASEWORK.
D.FURNISH AND INSTALL FIRE STOP SEALANT WHERE GYPSUM WALL BOARD
MEETS FIREPROOFING ON COLUMNS, BEAMS, AND METAL DECK AT FIRE
RATED PARTITIONS.
E.ALL PENETRATIONS THROUGH FIRE AND SMOKE RATED WALLS SHALL BE
FIRE STOPPED AS NECESSARY TO MAINTAIN RATINGS.
F.AT FIRE RATED WALLS, PROVIDE TESTED FIRE STOPPING SYSTEM AT
HEAD OF WALL. AT ALL NON-FIRE RATED WALLS, INCLUDING SOUND
RESISITANT WALLS, SMOKE PARTITIONS AND CORRIDOR WALLS, PACK
VOID SPACE BETWEEN METAL DECK FLUTES AND TOP OF PARTITION WITH
FIRE SAFING AND SEAL GAP AT DRYWALL WITH ACOUSTICAL SEALANT.
G.ALL WALLS SHALL BE TREATED AS SOUND RESISTANT WALLS (UNLESS
NOTED OTHERWISE). SEAL AROUND ALL PENETRATIONS AND INSTALL
SOUND ATTENTION BATTS FULL HEIGHT. FIT INSULATION TIGHT AROUND
DUCT AND PIPE PENETRATIONS. ALL SOUND RESISTANT WALLS WITH
SOUND ATTENUATION BATTS SHALL HAVE ACOUSTICAL SEALANT UNDER
BOTTOM RUNNER TRACK.
H.ALL STUDS SHALL BE AT 16" O.C. UNLESS NOTED OTHERWISE.
1.INDICATES ENTIRE WALL CONSTRUCTION TO STOP 6" ABOVE FINISHED
CEILING.
2.INDICATES GYPSUM BOARD ON ONE SIDE TO STOP 6" ABOVE FINISHED
CEILING.
3.INDICATES PARTIAL HEIGHT WALL.
a.INDICATES NO SOUND ATTENUATION BLANKETS
b.INDICATES ADDITIONAL LAYER OF 5/8" GYPSUM BOARD OVER WALL.
c.INDICATES FOIL-FACED GYPSUM BOARD.
WALL TYPE SYMBOL
X1.1x
INDICATES CONSTRUCTION TYPE
NUMERICAL INDICATION OF STUD/MASONRY SIZE
SUFFIX INDICATES MODIFICATIONS TO WALL
CONSTRUCTION HEIGHT
SUFFIX INDICATES HORIZONTAL
MODIFICATIONS
WALL TYPES SUFFIX
Ax WALL PARTITION
1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
Bx WALL PARTITION
1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
Fx WALL PARTITION
1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
01 TYP. METAL STUD PARTITION HEAD DETAIL
1 1/2" = 1'-0" NON-BEARING
PARALLEL TO RIBS OF DECK PERPENDICULAR TO RIBS OF DECK
Dx WALL PARTITION
1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
AX-'X'=METAL STUD SIZE
A2-2 1/2" METAL STUDS
A3-3 5/8" METAL STUDS
A6-6" METAL STUDS
BASE: REFER TO FINISH
DRAWINGS
FLOOR: REFER TO FINISH
DRAWINGS
1/2" SEALANT SPACE
STEEL STUD RUNNER TRACK.
STUDS SCREWED AT BOTTOM
FLOOR SLAB
5/8" GYPSUM WALL BOARD
METAL STUDS (REFER
TO CHART BELOW)
DEFLECTION TRACK
BOTTOM OF STRUCTURE
FASTEN GYPSUM BOARD
TO STUDS NOT TO THE
TOP TRACK
BX-'X'=METAL STUD SIZE
B2-2 1/2" METAL STUDS
B3-3 5/8" METAL STUDS
B6-6" METAL STUDS
BASE: REFER TO FINISH
DRAWINGS
FLOOR: REFER TO FINISH
DRAWINGS
1/2" SEALANT SPACE
(FIRESTOP AT RATED
PARTITIONS)
FLOOR SLAB
STEEL STUD RUNNER
TRACK. STUDS SCREWED
ON EA. SIDE AT BOTTOM
BOTTOM OF STRUCTURE
1/2" SEALANT SPACE
(FIRESTOP SYSTEM AT
RATED PARTITIONS)
DEFLECTION TRACK
FASTEN GYPSUM BOARD
TO STUDS NOT TO THE
TOP TRACK
METAL STUDS (REFER TO
CHART BELOW)
1/2" SEALANT SPACE
BASE: REFER TO FINISH
DRAWINGS
FLOOR: REFER TO FINISH
DRAWINGS
5/8" GYPSUM WALL BOARD
1/2" SEALANT SPACE
FLOOR SLAB
5/8" GYPSUM BOARD
FURRING CHANNEL
(REFER TO CHART BELOW)
ADJACENT WALL
CONSTRUCTION
BOTTOM OF STRUCTURE
FINISH CEILING. REFER
TO REFLECTED CEILING
PLAN.
NON-RATEDNON-RATED 1 HOUR RATED PARTITION; UL #V450
(WHERE NOTED ON PLAN)
SOUND ATTENUATION BATTS
SOUND ATTENUATION
BATTS
METAL DECK. REFER TO STRUCTURAL
DRAWINGS.
METAL EDGE TRIM WHERE
EXPOSED TO VIEW.
FASTEN STEEL RUNNER TO METAL DECK. FRICTION FIT METAL STUDS TO
DEFLECTION TRACK AND FASTEN GYPSUM BOARD TO STUDS. DO NOT
FASTEN TO DEFLECTION TRACK. MAINTAIN GAP BETWEEN STEEL
DEFLECTION TRACK AND METAL STUD/GYPSUM BOARD TO ACCOMMODATE
STRUCTURAL DEFLECTION.
COMPRESSED SAFING INSULATION.
(FIRESTOPPING AT RATED
PARTITIONS)
STEEL RUNNER WITH MIN. 2" FLANGES
CONTINUOUS ACOUSTIC SEALANT
BOTH SIDES. (FIRESTOPPING AT
RATED PARTITIONS)
REFER TO PARTITION TYPES FOR
WALL CONSTRUCTION.
D1- 1 5/8" STUD
D2- 2 1/2" STUD
D3- 3 5/8" STUD
D4- 4" STUD
D5- 6" STUD
BASE: REFER TO FINISH
DRAWINGS
FLOOR: REFER TO FINISH
DRAWINGS
1/2" SEALANT SPACEFLOOR SLAB
5/8" GYPSUM BOARD
METAL STUDS (REFER TO
CHART BELOW)
BOTTOM OF STRUCTURE
NON-RATED WALL
1/8" ALIGNMENT SPACE
(IF APPLICABLE)
ADJACENT WALL
CONSTRUCTION.
CLIP ANGLE AT EACH STUD
FINISH CEILING. REFER
TO REFLECTED CEILING
PLAN.
A2- 3 1/8" WALL
A3- 4 1/4" WALL
A6- 6 5/8" WALL
Fx- "X" =METAL FURRING
SIZE
F1- 7/8" FURRING
CHANNEL
F2- 1 1/2" "Z" FURRING
CHANNEL
F3- 1 -1/2" FURRING
CHANNEL
16 GAUGE HORIZONTAL
STEEL STRAPS AT 32"
O.C. VERTICALLY.
ANCHOR TO EACH STUD.
1
1
/
2
"
1/
2
"
CONTINUOUS 20 GA. SHEET METAL
FILLER FASTENED TO DECK WITH
WIDTH TO SPAN 3 RIBS MIN.
COPE GYPSUM BOARD AROUND
METAL DECK PROFILE.
1/
2
"
1"
VARIES
VARIES
5/8"
1"
5/8" GYPSUM BOARD ON
EACH SIDE OF STUDS
B2- 3 3/4" WALL
B3- 4 7/8" WALL
B6- 7 1/4" WALL
VARIESVARIESVARIES
VARIES 5/8"5/8"
6"
M
I
N
.
VARIES 5/8"D1- 2 3/8" WALL
D2- 3 1/4" WALL
D3- 4 3/8" WALL
D4- 4 3/4" WALL
D5- 6 3/4" WALL
5/8"F1- 1 1/2" WALL
F2- 2 1/8" WALL
F3- 2 1/8" WALL
2 3
1
4
5 6
3'
-
4
"
3'
-
0
"
9" D. WALL CABINET WITH
ADJUSTABLE SHELVES
SHOWN DASHED. (TYPICAL
ALL STAFF TOILET ROOMS
ONLY)
4" H. BASE, REFER
TO INTERIOR FINISH
DRAWINGS
723
1
4
3'
-
0
"
4"
4" H. BASE, REFER
TO INTERIOR FINISH
DRAWINGS
2' - 3"1' - 0"
3'
-
8
"
3' - 0"
7
WALL
PROTECTION
(WP1T)
8 5 A010.4 2
3
4
2
3
1 4
5 7
6
7'
-
2
"
M
I
N
.
8
A010.6 2A010.6
3
A010.6
4
2"10"2"
2"
9
1
/
2
"
2"
1'
-
1
1
/
2
"
1' - 2"
3/4" PARTICLE BOARD WITH
PLASTIC LAMINATE FINISH ON
ALL EXPOSED SURFACES.
WIRE PULL.
HINGED DOOR, BOTH SIDES.
6
A010.6
GROMMET - EXACT
LOCATIONS TO BE
COORDINATED WITH OWNER
6" METAL STUDS AT 16" O.C.
4"H BASE
3/4" PARTICLE BOARD WITH
PLASTIC LAMINATE FINISH 5/8" GYPSUM DRYWALL
VARIES - REFER TO PLAN
1
1
/
2
"
RAKKS SUPPORT BRACKET;
3'-0" O.C. MAX.
COUNTERTOP TO BE PLASTIC
LAMINATE WITH EASED EDGES -
REFER TO ELEVATIONS
1/4" REVEAL ALL SIDES,
PAINTED BLACK, TYP.
4"
EQ
.
EQ
.
EQ
.
SLIDING GLASS WINDOW
FIRE-RATARDANT WOOD
BLOCKING
4" H. BASE
1'
-
1
1
/
2
"
VARIES
2"
9
1
/
2
"
2"
9
1
/
4
"
1 3/4"1 3/4"
3/4" PARTICLE BOARD WITH
PLASTIC LAMINATE FINISH ON
ALL EXPOSED SURFACES.
WIRE PULL.
HINGED DOOR, BOTH SIDES.
METAL STUDS AT 16" O.C. WITH
5/8" GYPSUM DRYALL EACH
SIDE.
GROMMET - EXACT
LOCATIONS TO BE
COORDINATED WITH OWNER
3 5/8" METAL STUDS AT 16" O.C.
RAKKS SUPPORT BRACKET;
3'-0" O.C. MAX.
3/4" SOLID SURFACE
OVER 3/4" PARTICLE
BOARD SUBSTRATE
3/4" PARTICLE BOARD WITH
PLASTIC LAMINATE FINISH
EASED EDGE EA. SIDE
1
1
/
2
"
1
1
/
2
"
5/8" GYPSUM DRYWALL
FIRE-RATARDANT WOOD
BLOCKING
VARIES
VARIES - REFER TO PLAN
COUNTERTOP TO BE PLASTIC
LAMINATE WITH EASED EDGES -
REFER TO ELEVATIONS
4"H BASE4" H BASE
3'
-
1
0
1
/
2
"
3'
-
0
"
GROMMET - EXACT
LOCATIONS TO BE
COORDINATED WITH OWNER
6" METAL STUDS AT 16" O.C.
RAKKS SUPPORT BRACKET;
3'-0" O.C. MAX.
3/4" SOLID SURFACE
OVER 3/4" PARTICLE
BOARD SUBSTRATE
3/4" PARTICLE BOARD WITH
PLASTIC LAMINATE FINISH
EASED EDGE EA. SIDE
1
1
/
2
"
5/8" GYPSUM DRYWALL
FIRE-RETARDANT WOOD
BLOCKING
VARIES
VARIES - REFER TO PLAN
COUNTERTOP TO BE PLASTIC
LAMINATE WITH EASED EDGES -
REFER TO ELEVATIONS
4"H BASE
4" H BASE
1
1
/
2
"
FIRE-RETARDANT WOOD
BLOCKING
3'
-
0
1
/
2
"
4"
3'
-
0
"
SLIDING GLASS WINDOW
GROMMET - EXACT
LOCATIONS TO BE
COORDINATED WITH OWNER
3 5/8" METAL STUDS AT 16" O.C.
4"H BASE
3/4" PARTICLE BOARD WITH
PLASTIC LAMINATE FINISH
5/8" GYPSUM DRYWALL
VARIES - REFER TO PLAN
1
1
/
2
"
RAKKS SUPPORT BRACKET;
3'-0" O.C. MAX.COUNTERTOP TO BE PLASTIC
LAMINATE WITH EASED EDGES -
REFER TO ELEVATIONS
3'
-
0
"
6"
4" H. BASE
9365 Counselors Row
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
CONNECTOR
WOMEN'S
CENTER
KEYPLAN
N
SCALE
DATE
COORD
DRAWN
APPROVED
FILE NAME
CLIENT NO. :
PROJECT NO.
TM
WOMEN'S CENTER
CARMEL, IN
As indicated
04610082
A010.6
WALL TYPES,
GENERAL NOTES
AND DETAILS
0461
BP #6 DESIGN
DOCUMENTS
OCT. 10, 2014
TOILET ACCESSORIES - BP6
1SURFACE MOUNT TOILET TISSUE DISPENSER #1; REFER TO PROJECT MANUAL.
2GRAB BARS: 36" L. GRAB BAR BEHIND TOILET, 42" L. GRAB BAR BESIDE TOILET
318" L. VERTICAL GRAB BAR
4SANITARY NAPKIN DISPOSAL
5SURFACE MOUNTED PAPER TOWEL DISPENSER
624" x 36" MIRROR WITH METAL FRAME
7SURFACE MOUNTED SOAP DISPENSER
8ROBE HOOK
EQUIPMENT SCHEDULE- BP6
NUMBERNAMEREMARKS
401FLAT PANEL TELEVISIONO.F.O.I.
402PATIENT SCALEO.F.O.I.
403EXAM TABLEO.F.O.I.
404COMPUTER MONITORO.F.O.I.
405UNDERCOUNTER REFRIGERATORO.F.O.I.
406DISHWASHERO.F.O.I.
407REFRIGERATORO.F.O.I.
408VENDING MACHINEO.F.O.I.
409PRINTER.O.F.O.I.
410COPIERO.F.O.I.
411MICROWAVEO.F.O.I.
412COFFEE MAKER - KEURIGO.F.O.I.
413ULTRASOUNDO.F.O.I.
414MONITOR - WALL MOUNTEDO.F.O.I.
415BIO-HAZARD WASTE CONTAINERO.F.O.I.
416SOILED HOLDING CONTAINERO.F.O.I.
417WATER COOLERO.F.O.I.
418TRASH CONTAINERO.F.O.I.
419PHLEBOTOMY CHAIRO.F.O.I.
420SPECIMEN LABEL PRINTERO.F.O.I.
421URINALYSIS MACHINEO.F.O.I.
422CENTRIFUGEO.F.O.I.
423ULTRACLAVEO.F.O.I.
424STEAM SPORE TESTING INCUBATORO.F.O.I.
425COLPOSCOPEO.F.O.I.
426LEEP SYSTEMO.F.O.I.
1 1/2" = 1'-0"
ARCH- WALL TYPES - BP6
1/4" = 1'-0"2 TYPICAL ADA TOILET ROOM 1 - BP6
1/4" = 1'-0"3 TYPICAL ADA TOILET ROOM 2 - BP6
1/4" = 1'-0"4 TYPICAL ADA TOILET ROOM 3 - BP6
1/4" = 1'-0"1 TYPICAL ADA TOILET ROOM - BP6
1" = 1'-0"5 PASS-THRU ELEVATION - BP6
1" = 1'-0"7 CASEWORK SECTION 1 - LOW COUNTER - BP6
MARKDATEDESCRIPTION
1" = 1'-0"6 PASS-THRU SECTION - BP6
1" = 1'-0"9 CASEWORK SECTION 3 - HIGH COUNTER - BP6
1" = 1'-0"8 CASEWORK SECTION 2 - HIGH COUNTER - BP6
1" = 1'-0"10 CASEWORK SECTION 4 - LOW COUNTER - BP6