HomeMy WebLinkAboutE001.6.pdf1. REFER TO SHEET `HPE' SERIES DRAWINGS FOR ADDITIONAL ELECTRICAL SCOPE.
2. ALL CONDUITS SHALL BE RUN ABOVE FINISHED FLOOR OF WHICH IT IS SERVING UNLESS
OTHERWISE NOTED. CONDUITS ARE NOT PERMITTED, UNDER ANY CIRCUMSTANCES, TO BE RUN
IN CONCRETE SLAB.
3. PLAN NOTES SHOWN OUTSIDE OF AREA MATCH LINES FOR EACH PROJECT SHEET SHALL NOT BE
APPLICABLE TO SAID SHEET.
4. REFER TO ARCHITECTURAL SCHEDULES, DETAILS, ELEVATIONS FOR DEVICE MOUNTING HEIGHTS
AND ADDITIONAL INFORMATION ON DEVICE LOCATIONS PRIOR TO ROUGH-IN.
5. ALL INTERRUPTIONS OF ELECTRICAL SYSTEMS SHALL BE COORDINATED AND SCHEDULED IN
ADVANCE WITH THE CONSTRUCTION MANAGER AND OWNER. REFER TO SPECIFICATIONS FOR
RESTRICTIONS AND ADVANCE NOTICE REQUIREMENTS.
6. VERIFY TYPE OF CEILING, GRID SYSTEM SPECIFICATIONS (IF APPLICABLE), AND MOUNTING
RESTRICTIONS WITH ARCHITECTURAL DISCIPLINE PRIOR TO ORDER FOR LUMINAIRES.
7. MOUNTING OF JUNCTION BOXES BACK-TO-BACK IS NOT PERMITTED UNDER ANY CIRCUMSTANCES.
8. ELECTRICAL DEVICES INSTALLED ON VERTICAL FIRE RESISTIVE ASSEMBLIES CLASSIFIED AS
FIRE/SMOKE PARTITIONS SHALL BE INSTALLED WITH OPENING ON ONE SIDE ONLY IN EACH FRAMING
SPACE, AND THAT OPENING SHALL NOT EXCEED 16 SQUARE INCHES. ALL CLEARANCES BETWEEN
SUCH DEVICES AND THE GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND OR
OTHER UL APPROVED MATERIALS.
9. WHERE SPACE ALLOCATIONS WITH REGARD TO ELECTRICAL EQUIPMENT ARE NOT ADEQUATE FOR
THE SPECIFIED ELECTRICAL EQUIPMENT, THE ENGINEER SHALL BE CONSULTED BEFORE ORDERING
THE EQUIPMENT AND ANY INSTALLATION IS PERFORMED.
10. COORDINATE LOCATIONS OF ALL CEILING MOUNTED ELECTRICAL AND MECHANICAL EQUIPMENT
INCLUDING-BUT NOT LIMITED TO-LUMINAIRES, PAGING SPEAKERS, SMOKE DETECTORS, ETC. WITH
THE ARCHITECTURAL REFLECTED CEILING PLAN. REFER TO SPECIFICATIONS FOR RESTRICTIONS OF
PARTICULAR DEVICE PLACEMENT.
11. MAINTAIN AND SUBMIT AS-BUILT DRAWINGS SHOWING ALL MODIFICATIONS (BOTH IN THE FIELD AND
AS DIRECTED BY OWNER OR ENGINEER) TO LIGHTING, POWER, AND SYSTEMS PLAN TO
CONSTRUCTION MANAGER AT PROJECT OR PHASE COMPLETION.
12. PROVIDE NEW, TYPED PANELBOARD CIRCUIT DIRECTORIES IN EXISTING AND NEW PANELBOARDS
MODIFIED BY THIS PROJECT.
13. REFER TO SITE PLANS LOCATED ON `C' SERIES SHEETS FOR ADDITIONAL ELECTRICAL SCOPE.
14. CONDUIT FLOOR SLEEVES SHALL BE INSTALLED 2" ABOVE FINISHED FLOOR AND SHALL BE FIRE
PROOFED USING APPROVED FIRE RESISTIVE MATERIAL.
15. REFER TO ARCHITECTURAL PHASING PLAN FOR SPECIFIC PHASING CONSTRAINTS. ADJUST
ELECTRICAL WORK ACCORDINGLY AND ENSURE THAT ALL SERVICES REMAIN ACTIVE IN ALL ACTIVE
AND OCCUPIED AREAS THROUGHOUT THE PROJECT.
16. TO PROVIDE ORGANIZATION AND ACCESS, ALL CONDUIT, PIPING, DUCTWORK, ETC. ABOVE THE
CEILING SHALL BE INSTALLED USING THE FOLLOWING CRITERIA:
(A) ITEMS SHALL BE CLOSEST TO THE CEILING: SANITARY, STORM AND VENT PIPING, DOMESTIC
COLD, HOT, HOT WATER RETURNS, CHILLED WATER SUPPLY AND RETURNS, STEAM AND FIRE
PROTECTION.
(B) MEDICAL GAS PIPING SHALL BE ABOVE ITEMS NOTED IN (A).
(C) ELECTRICAL CONDUIT SHALL BE ABOVE ITEMS NOTED IN (B).
(D) DUCTWORK SHALL BE ABOVE ITEMS NOTED IN (C) AND TO BE CLOSEST TO THE METAL DECK.
DUCTWORK WHICH IS BELOW PIPING SHALL HAVE NO PIPE JOINTS ABOVE THE DUCTWORK.
17. ALL J-BOX IN CEILING SPACE SHALL HAVE ACCESS, TO COMPLY WITH NEC CLEARANCE REQUIRED.
18. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH ARCHITECTURAL
ELEVATIONS PRIOR TO ROUGH-IN, AND ADJUST ROUGH-IN LOCATION ACCORDINGLY.
19. CONTRACTOR SHALL BE RESPONSIBLE TO FIRE PROOF PENETRATIONS AT SMOKE WALL, FIRE/SMOKE
WALL, AND ROOF PENETRATIONS.
20. CONNECT ALL EXIT AND EGRESS LIFE SAFETY LIGHTING WITH #10 WIRING.
21. PRIOR TO INSTALLATION OF ALL TVS, MONITORS, OR FLAT SCREEN PANELS ROUGH-INS (TV, DATA,
OR POWER RECEPTACLES), CONFIRM MOUNTING HEIGHT OF UNIT.
22. WALL AND CEILING MOUNTED EXIT SIGNS ARE NOT DISTINGUISHED DIFFERENTLY ON THE ELECTRICAL
LIGHTING PLANS. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING MOUNTED
DEVICES. COORDINATE EXACT LOCATION WITH BULKHEADS, SOFFITS, WALL WASHING LIGHT
FIXTURES, OTHER WALL-MOUNTED DEVICES PRIOR TO INSTALLATION AND ORDERING OF UNITS AND
ADJUST LOCATION AS REQUIRED WHILE STILL MAINTAINING DESIGN INTENT OF EGRESS SIGNAGE.
COORDINATE ROUGH-IN LOCATIONS WITH ALL OTHER TRADES.
23. VOLTAGE DROP REQUIREMENTS: BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
VOLTAGE DROP OF 3 PERCENT TO COMPLY WITH THE REQUIREMENTS OF ASHRAE STANDARD
90.1-2007. THE FOLLOWING ARE MINIMUM ALLOWABLE CONDUCTOR SIZES BASED ON CIRCUIT
LENGTH. THE CIRCUIT LENGTH SHALL BE MEASURED FROM THE BRANCH PANELBOARD TO THE
FARTHEST DEVICE IN THAT CIRCUIT. THE PHASE AND NEUTRAL CONDUCTORS SHALL BE SIZED AS
INDICATED THE ENTIRE LENGTH OF THAT CIRCUIT UNLESS A LARGER SIZE CONDUCTOR IS INDICATED
ON THE DRAWINGS. BASED ON COPPER CONDUCTORS INSTALLED IN CONDUIT.
CONDUCTOR SIZES FOR 20A/1-PHASE/120V CIRCUITS SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE:
CIRCUIT LENGTH OF 0 TO 95 FEET: #12 AWG.
CIRCUIT LENGTH OF 96 TO 150 FEET: #10 AWG.
CIRCUIT LENGTH OF 151 TO 235 FEET: #8 AWG.
CIRCUIT LENGTH OF 236 TO 380 FEET: #6 AWG.
CONDUCTOR SIZES FOR 20A/1-PHASE/277V CIRCUITS SHALL BE AS FOLLOWS UNLESS NOTED
OTHERWISE:
CIRCUIT LENGTH OF 0 TO 200 FEET: #12 AWG.
CIRCUIT LENGTH OF 201 TO 350 FEET: #10 AWG.
CIRCUIT LENGTH OF 351 TO 550 FEET: #8 AWG.
GENERAL NOTES:
ST
PC
S
D
S
K
S
P
S4
S3
S
S
SD
HD
FD
DD
AR
RI
BD
M
FS
TS
H
H
C
C
S
S
V
DH
AM
FACP
FAAP
FANP
FATC
FGCC
FT
RA
B
B
M
S
S
S
V
M
M
W
TV
AV
MTV
CCTV
DR
ES
IC
MI
SCP
ML
CR
MD
DC
PB
K
BS
DS
SM
SS
DE
LC
M
OC
J
RT
HEAVY CONTINUOUS LINES INDICATE SPRINKLER ZONESZ
ALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT
LIGHT/SCREENED SOLID OR DASHED LINES INDICATE EXISTING TO REMAIN
HEAVY CONTINUOUS LINES INDICATE NEW WORK
LINE SYMBOLS
HEAVY DASHED LINES INDICATE EXISTING TO BE REMOVED
NOTE:
A.GENERAL NOTE
1 PLAN NOTE
FLOOR PLAN SYMBOLS
ST - 20 AMP, 125VAC, SAFETY TYPE
S - 20 AMP, 125VAC, SURGE GUARD PROTECTION TYPE
WP - 20 AMP, 125VAC, WEATHERPROOF TYPE
TOGGLE SWITCH - 20 AMP, 120/277VAC
LETTER DESIGNATION INDICATES SWITCH LEG
FLOOR BOX (POWER AND DATA)
SPECIAL RECEPTACLE - EMERGENCY CIRCUIT (SEE DRAWINGS
SPECIAL RECEPTACLE - NORMAL CIRCUIT (SEE DRAWINGS AND
TOGGLE SWITCH - KEY OPERATED
TOGGLE SWITCH - 3-WAY
TOGGLE SWITCH - 4-WAY
INDIVIDUAL LIGHT DIMMER
TOGGLE SWITCH - PILOT LIGHT
AND SPECIFICATIONS)
PLUGSTRIP (POWER AND/OR DATA)
SPECIFICATIONS)
HM - 20 AMP, 125VAC, HORIZONTAL MOUNT TYPE
IG - 20 AMP, 125VAC, ISOLATED GROUND TYPE
GFCI - 20 AMP, 125VAC, GROUND FAULT CURRENT INTERRUPTER TYPE
NONE - 20 AMP, 125VAC
ELECTRICAL DEVICES
DUPLEX RECEPTACLE - EMERGENCY CIRCUIT ("X" DENOTES
QUADRAPLEX RECEPTACLE - NORMAL CIRCUIT ("X" DENOTES
QUADRAPLEX RECEPTACLE - EMERGENCY CIRCUIT ("X"
SIMPLEX RECEPTACLE - NORMAL CIRCUIT ("X" DENOTES AS
SIMPLEX RECEPTACLE - EMERGENCY CIRCUIT ("X" DENOTES
DUPLEX RECEPTACLE - NORMAL CIRCUIT ("X" DENOTES AS
DESCRIPTION
DENOTES AS FOLLOWS:)
FOLLOWS:)
AS FOLLOWS:)
FOLLOWS:)
AS FOLLOWS:)
AS FOLLOWS:)
SYMBOL
FLOOR BOX (QUADRAPLEX)
FLOOR BOX (DUPLEX)
QUADRAPLEX - CEILING MOUNTED
DUPLEX - CEILING MOUNTED
DOOR SECURITY SYSTEM
QUANTITY OF CONDUCTORS OR CABLES IN CONDUIT
JUNCTION OR PULL BOX
NEUTRAL
GROUND
RACEWAY SYSTEM
DESCRIPTION
PHASE
CONDUCTORS
SYMBOL
SYMBOL DESCRIPTION
GENERATOR/ALTERNATOR
AUTOMATIC TRANSFER SWITCH
G
PUSHBUTTON OR PUSH PLATE
PAD MOUNTED TRANSFORMER ("X" DENOTES KVA SIZE)
BRANCH PANELBOARD AND CABINET - RECESSED MOUNT
BRANCH PANELBOARD AND CABINET - SURFACE MOUNT
DISTRIBUTION PANELBOARD AND CABINET - SURFACE MOUNT
HORSEPOWER RATED MANUAL MOTOR STARTER TOGGLE SWITCH
WITH THERMAL OVERLOAD PROTECTION
COMBINATION MOTOR CONTROLLER
DISCONNECT SWITCH - NON-FUSED
MOTOR CONTROLLER
DISCONNECT SWITCH - FUSED
MOTOR ("X" DENOTES HORSEPOWER)
GROUND CONNECTION
ELECTRIC THERMOSTAT
CAPACITOR ("X" DENOTES KVAR)
T
X
PAGING/AUDIO SYSTEM
MICROPHONE INPUT RECEPTACLE - WALL MOUNTED
LOUDSPEAKER - WALL MOUNTED
LOUDSPEAKER - CEILING MOUNTED
SYMBOL
VOLUME CONTROL
DESCRIPTION
WALL MOUNTED SPEAKER (ROUGH-IN)
DESCRIPTION
MOLDED CASE CIRCUIT BREAKER
CURRENT TRANSFORMER
ELECTRICAL EQUIPMENT
SYMBOL
FIRE ALARM SYSTEM
SYMBOL DESCRIPTION
TELEVISION SYSTEM
SYMBOL
TV SYSTEM OUTLET
DESCRIPTION
TELECOMMUNICATION SYSTEM
VOICE ONLY OUTLET
VOICE AND DATA OUTLET
SYMBOL DESCRIPTION
SMOKE DETECTOR ("X" DENOTES AS FOLLOWS)
HEAT DETECTOR
FLAME DETECTOR
DUCT DETECTOR ("X" DENOTES AS FOLLOWS)
MANUAL PULL STATION
FLOW SWITCH
TAMPER SWITCH
HORN ONLY
HORN STROBE
CHIME ONLY
CHIME STROBE
SPEAKER ONLY
SPEAKER STROBE
VISUAL ONLY
DOOR HOLD OPEN
ADDRESSABLE MODULE
BEAM DETECTOR
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM NOTIFICATION APPLIANCE PANEL
FIRE ALARM TERMINAL CABINET
S - SUPPLY
R - RETURN
R - RELAY BASE
REMOTE TEST STATION
REMOTE INDICATOR STATION
DOOR BUZZER
SECURITY DOOR ALARM MAGNETIC LOCK
CCTV MONITOR OUTLET
ELECTRIC DOOR OPENER
ELECTRIC DOOR STRIKE
INTERCOM UNIT FLUSH MTD.
MASTER INTERCOM AND DIRECTORY UNIT
MOTION DETECTOR
CCTV COAXIAL CABLE OUTLET AND POWER OUTLET
SECURITY CARD READER
SECURITY CONTROL PANEL
SECURITY DOOR CONTACTS
SECURITY EXIT PUSH BUTTON
SECURITY KEYPAD
BIOSCAN ACCESS PAD
CAMERA
VOICE ONLY OUTLET (WALL OUTLET)
DATA ONLY OUTLET
PHOTO CELL
X
P.F.
ADDRESSABLE RELAY
LIGHTING
DESCRIPTION
12x48 FLUORESCENT FIXTURE
HALF SHADED INDICATES LIFE SAFETY POWER
24x24 FLUORESCENT FIXTURE
24" WALL LIGHTS
36" WALL LIGHTS
48" WALL LIGHTS
24x48 FLUORESCENT FIXTURE ("NL" DENOTES NIGHT LIGHT)
DOWN LIGHT
WALL MOUNTED SCONCE
WALL MOUNTED EMERGENCY BATTERY LIGHT
CEILING MOUNTED EMERGENCY BATTERY LIGHT
EXIT LIGHT DIRECTIONAL ARROWS
CEILING MOUNTED EXIT LIGHT (DUAL FACED)
CEILING MOUNTED EXIT LIGHT
WALL MOUNTED EXIT LIGHT
EXTERIOR POLE LIGHTS (SINGLE HEADS)
EXTERIOR POLE LIGHTS (DOUBLE HEADS)
EXTERIOR POLE LIGHTS (THREE HEADS)
EXTERIOR POLE LIGHTS (FOUR HEADS)
EXTERIOR LIGHTS (BOLLARDS)
24" STEM MOUNTED WALL LIGHTS
36" STEM MOUNTED WALL LIGHTS
48" STEM MOUNTED WALL LIGHTS
FULL SHADED INDICATES EMERGENCY POWER
GROUND POINT
GROUND ROD
a
X
X
FIRE ALARM GRAPHICS COMMAND CENTER
FIREMEN'S TELEPHONE
RESCUE ASSIST STATION
BELL ONLY
BELL STROBE
MICROPHONE INPUT RECEPTACLE - FLOOR MOUNTED
MICROPHONE INPUT RECEPTACLE - CEILING MOUNTED
EXTERIOR POLE LIGHTS (POLE TOP MOUNT)
GROUND FLOOD LIGHT
EXTERIOR FLOOD LIGHT
DUAL BALLAST (NORMAL AND EMERGENCY)
CEILING MOUNTED (DATA, VOICE/DATA)
FLOOR BOX (VOICE, DATA, VOICE/DATA)
TELECOMMUNICATIONS EQUIPMENT RACK
AUDIO/VISUAL CONTROLLER
SECURITY DUTY STATION
SECURITY STAFF STATION
SECURITY MONITOR
SECURITY DOOR EGRESS
LIGHTING CONTROLLER
MOTION DETECTOR (LIGHT SWITCH)
OCCUPANCY SENSOR
FLOOR BOX (BLANK)
WIRELESS ACCESS POINTWA
ABBREV.
A or AMP
AC
A/C
ACP
ACU
ADD
ADJ
AF
AFC
AFF
AFG
AHU
AIC
AL
AM
AMB
APPROX.
ARCH
ATS
AUTO
AVG
BC
BKR
BHP
BL
BLDG
BR
BTM
C
ºC
CAB
CB or C/B
C/C
CCTV
CKT
CL
CLG
COL
COMM
COMP
CONC
CONST
CONT
CONTR
CR
CT
CU
DB
DC
DEPT
DF
DIST
DM
DO
DRS
DWG
EC
EF
ELEC
ELEV
ELV
EMER
ENCL
EP
EQUIP
EWC
EX
EXH
EXP
EXT
ºF
FA
FAAP
FACP
FC
FCU
FFC
FFS
FHC
FIN
FIXT
FL
FLUOR
FLEX-CONN
FPC
FSS
FTG
FVR
FV
FVNR
G or GND
GALV
GC
GEN
GFCI
GFI
GFP
HGT
HH
HID
HO
HOA
HORZ
HP
HPS
HTR
HV
DESCRIPTION
AMPERE
ALTERNATING CURRENT
AIR CONDITIONING
ACCESS PANEL
AIR CONDITIONING UNIT
ADDITION
ADJUSTABLE
AMPERE FRAME
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
AMBIENT
APPROXIMATELY
ARCHITECT
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AVERGE
BARE COPPER
BREAKER
BRAKE HORSEPOWER
BUILDING LINE
BUILDING
BRANCH
BOTTOM
CONDUIT
DEGREES CELSIUS
CABINET
CIRCUIT BREAKER
CENTER TO CENTER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CENTER LINE
CEILING
COLUMN
COMMUNICATION
COMPRESSOR
CONCRETE
CONSTRUCTION
CONTINUOUS
CONTRACTOR
CRITICAL
CURRENT TRANSFORMER
COPPER
DIRECT BURIAL
DIRECT CURRENT
DEPARTMENT
DRINKING FOUNTAIN
DISTRIBUTION
DEMAND METER
DRAWOUT
DOCTORS
DRAWING
ELECTRICAL CONTRACTOR
EXHAUST FAN
ELECTRIC
ELEVATOR
ELEVATION
EMERGENCY
ENCLOSURE
ELECTRIC PNEUMATIC
EQUIPMENT
ELECTRIC WATER COOLER
EXPLOSIONPROOF
EXHAUST
EXPANSION
EXTERIOR
DEGREES FAHRENHEIT
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FLAT CABLE
FAN COIL UNIT
FOOD FACILITY CONTRACTOR
FOOD FACILITY SUPPLIER
FIRE HOSE CABINET
FINISH
FIXTURE
FLOOR
FLUORESCENT
FLEXIBLE CONNECTION
FIRE PROTECTION CONTRACTOR
FUSED SAFETY SWITCH
FOOTING
FILMVIEWER
FULL VOLTAGE
FULL VOLTAGE NON REVERSING
GROUND
GALVANIZED
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CKT. INTERRUPTER
GROUND FAULT INTERRUPTER
GROUND FAULT PROTECTION
HEIGHT
HANDHOLE
HIGH INTENSITY DISCHARGE
HAND OPERATED
HAND-OFF-AUTOMATIC
HORIZONTAL
HORSEPOWER
HIGH PRESSURE SODIUM
HEATER
HIGH VOLTAGE
ABBREV.
HZ
IC
ID
INCAN
INCL
ISG
JB
JT
KEC
KT
KVA
KVAR
KW
LAB
LB
LF
LOC
LS
LT
LTG
LV
MATV
MAX
MC
MCB
MCC
MDP
MECH
MH
MIN
MISC
MLO
MTD
MTG HT
MU
OD
OFCI
OFOI
OPNG
OPP
OR
P
PB
PBOX
PE
PF
PH or Ø
PV
PNL
PL
PREFAB
PRES
PT
PTS
PW
PWR
RACU
RAD
RECEPT
REF or REFR
REINF
RGIP
RM
RPM
SA
SC
SG
SHT
SIG
SN
SPEC
SQ
SS
SSSS
STD
STN
STR
SUSP
SW
SWBD
SWGR
TCC
TELE
TEMP
TMH
TV
TYP
UC
U/C
UH
UV
V
VAC
VB
VC
VEL
VFD
VM
VOL
VP
VSD/VFC
W/
W/O
WTR
WP
WT
XFMR
Z
DESCRIPTION
HERTZ
INTERCOMMUNICATION
INSIDE DIAMETER
INCANDESCENT
INCLUDE
ISOLATED GROUND SURGE GUARD
JUNCTION BOX
JOINT
KITCHEN EQUIPMENT CONTRACTOR
KITCHENETTE
KILOVOLT AMPERE
KILOVOLT AMPERE REACTIVE
KILOWATT
LABORATORY
POUND
LINEAR FEET
LOCATION
LIFE SAFETY
LIGHT
LIGHTING
LOW VOLTAGE
MASTER ANTENNA TELEVISION
MAXIMUM
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MECHANICAL
MANHOLE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MOUNTED
MOUNTING HEIGHT
MEDICINE UNIT
OUTSIDE DIAMETER
OWNER FURNISHED-CONTRACTOR INSTALLED
OWNER FURNISHED-OWNER INSTALLED
OPENING
OPPOSITE
OPERATING ROOM
POLE
PUSHBUTTON
PULL BOX
PNEUMATIC ELECTRIC CONVERTER
POWER FACTOR
PHASE
POST INDICATOR VALVE
PANELBOARD
PILOT LIGHT
PREFABRICATED
PRESSURE
PNEUMATIC TUBE
PNEUMATIC TUBE STATION
PART WINDING
POWER
ROOM AIR CONDITIONING UNIT
RADIATION
RECEPTACLE
REFRIGERATOR
REINFORCED
REMOTE GROUND INDICATING PANEL
ROOM
REVOLUTIONS PER MINUTE
SUPPLY AIR
SHORT CIRCUIT
SURGE GUARD PROTECTION
SHEET
SIGNAL
SOLID NEUTRAL
SPECIFICATIONS
SQUARE
SAFETY SWITCH
SOLID STATE SOFT START
STANDARD
STATION
STRUCTURAL
SUSPENDED
SWITCH
SWITCHBOARD
SWITCHGEAR
TEMPERATURE CONTROL CONTRACTOR
TELECOMMUNICATION
TEMPERATURE
TOP OF MANHOLE
TELEVISION
TYPICAL
UNDER CARPET
UNDER CABINET or UNDER COUNTER
UNIT HEATER
UNIT VENTILATOR
VOLT
VACUUM
VACUUM BREAKER
VACUUM CLEANING
VELOCITY
VARIABLE FREQUENCY DRIVE
VOLTMETER
VOLUME
VAPORPROOF
VARIABLE SPEED DRIVE/CONTROLLER
WITH
WITHOUT
WATER
WEATHERPROOF
WEIGHT
TRANSFORMER
IMPEDANCE
ELECTRICAL ABBREVIATIONS
SYMBOL
SYMBOL DESCRIPTION
OC CEILING OCCUPANCY SENSOR
M
D
S
E
P
CB
CP
L
Z
W
R
A
N
NC
IC
X
PC
PC
P
IR
RF
BS
CL
WL
2X
MO
NURSE ASSIST
NURSE ASSIST/CODE BLUE
DUTY STATION
DESCRIPTION
MASTER STATION
STAFF STATION
STAFF LOCATOR STATION
CODE BLUE STATION
SYMBOL
ROOM READY INDICATOR
REMOTE ANNUNCIATOR
NURSE STATION INPUT JACK
BED CONTROL CABLE/INTERCONNECT JACK
NURSE CALL SYSTEM
PATIENT STATION - SINGLE OUTLET
EMERGENCY/BATH STATION
ZONE LIGHT
WALL MOUNTED DOME LIGHT
CODE PINK STATION
NURSE AUXILARY JACK
TELEMETRY ANTENNA LOCATION
CEILING MOUNTED DOME LIGHT
PULL CORD
PULL CORD WITH AUDIOA
PATIENT STATION - SINGLE OUTLET WITHECODE/STAFF ASSIST BUTTON
TRACKING SENSOR (IR)
TRACKING SENSOR (RF)
WHITE BOARD MONITOR
DOUBLE NURSE AUXILARY JACK
ASCOM BASE STATION
NL
9365 Counselors Row
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
SCALE
DATE
COORD
DRAWN
APPROVED
FILE NAME
CLIENT NO. :
PROJECT NO.
TM
WOMEN'S CENTER
CARMEL, IN
NO SCALE
04610082
04610082-MEP_BSALS_CENTRAL_v2012.rvt
BDH
TMH
JCP E001.6
SYMBOLS AND
ABBREVIATIONS
0461
BP #6 DESIGN
DOCUMENTS
OCTOBER 10, 2014
MARKDATEDESCRIPTION