HomeMy WebLinkAboutE800.6.pdfSUPPORT STRUCTURE NOTE: FOR STEEL STRUCTURAL SYSTEM COMBINATION BEAM CLAMP AND CONDUIT HANGER OR EQUIVALENT NOTE: 1.FOR STEEL STRUCTURAL SYSTEM. 2.PROVIDE SEISMIC BRACING MINIMUM 40' ON CENTER WHEN THE CONDUITS SUPPORT IS BELOW 12" FROM STRUCTURE. UNISTRUT CHANNEL OR EQUIVALENT CONDUIT CLAMP OR EQUIVALENT SIZE AS REQUIRED THREADED ROD SIZE AS REQUIRED BEAM CLAMP STRUTCLAMP OR EQUIVALENT BEAM CLAMP STEEL CABLE AIRCRAFT HANGER WIRE STEEL CABLE AIRCRAFT HANGER WIRE LAY-IN CEILING LAY-IN CEILING FLEXIBLE CONDUIT W/#14 WIRE (6' MAX.) LAY-IN CEILING JUNCTION BOX LAY-IN CEILING 12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE SUPPORT CONNECTED TO STRUCTURE ABOVE SEISMIC CLIP WALL CONDUIT VANITY SINK LIGHT FIXTURE MIRROR 4"x4" BOX: VERIFY MOUNTING AHEIGHT AND EXACT LOCATION PRIOR TO ROUGH-IN 6" . CADDY SCREW GUN BRACKET NOTE: FOR METAL STUD WALL CONSTRUCTION ONLY. 4" SQUARE BOX METAL STUDS CONDUIT BOX MOUNTING BRACKET J FUSIBLE DISCONNECT SWITCH. PROVIDE FUSING PER MANUFACTURER'S RECOMMENDATIONS TERMINAL BOX / FAN POWERED BOX REFER TO HVAC SCHEDULES 480V, 4W, CKT TO PANEL REFER TO FLOOR PLANS 9365 Counselors Row Indianapolis, IN 46240-1478 ph 317.819.7878 fx 317.819.7288 www.bsalifestructures.com SCALE DATE COORD DRAWN APPROVED FILE NAME CLIENT NO. : PROJECT NO. TM WOMEN'S CENTER CARMEL, IN NO SCALE 04610082 04610082-MEP_BSALS_CENTRAL_v2012.rvt BDH TMH JCP E800.6 ELECTRICAL DETAILS 0461 BP #6 DESIGN DOCUMENTS OCTOBER 10, 2014 NO SCALE12" AND SMALLER CONDUIT SUPPORT DETAIL NO SCALE22-1/2" AND LARGER CONDUIT SUPPORT DETAIL NO SCALE3LAY-IN FIXTURE DETAIL NO SCALE4OVER MIRROR LIGHT FIXTURE INSTALLATION DETAIL NO SCALE5WALL BOX INSTALLATION DETAIL MARKDATEDESCRIPTION NO SCALE6HVAC TERMINAL BOX / FAN POWERED BOX WITH ELECTRIC HEATING COILS - BP6