HomeMy WebLinkAboutE800.5.pdfSUPPORT STRUCTURE
NOTE: FOR STEEL STRUCTURAL SYSTEM
COMBINATION BEAM CLAMP AND
CONDUIT HANGER OR EQUIVALENT
NOTE:
1. FOR STEEL STRUCTURAL SYSTEM.
2. PROVIDE SEISMIC BRACING MINIMUM 40' ON
CENTER WHEN THE CONDUITS SUPPORT IS
BELOW 12" FROM STRUCTURE.
UNISTRUT CHANNEL
OR EQUIVALENT
CONDUIT CLAMP OR
EQUIVALENT SIZE
AS REQUIRED
THREADED ROD
SIZE AS REQUIRED
BEAM CLAMP
STRUTCLAMP
OR EQUIVALENT
BEAM CLAMP
STEEL CABLE
AIRCRAFT
HANGER WIRE
STEEL CABLE
AIRCRAFT
HANGER WIRE
LAY-IN CEILING
LAY-IN CEILING
FLEXIBLE CONDUIT
W/#14 WIRE (6' MAX.)
LAY-IN CEILING
JUNCTION BOX
LAY-IN CEILING
12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
SUPPORT CONNECTED TO STRUCTURE ABOVE
SEISMIC CLIP
WALL
CONDUIT
VANITY SINK
LIGHT FIXTURE
MIRROR
4"x4" BOX: VERIFY MOUNTING
AHEIGHT AND EXACT LOCATION
PRIOR TO ROUGH-IN 6"
.
CADDY SCREW GUN BRACKET
NOTE: FOR METAL STUD WALL CONSTRUCTION ONLY.
4" SQUARE BOX
METAL STUDS
CONDUIT
BOX MOUNTING BRACKET
9365 Counselors Row
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
SCALE
DATE
COORD
DRAWN
APPROVED
FILE NAME
CLIENT NO. :
PROJECT NO.
TM
WOMEN'S CENTER
CARMEL, IN
NO SCALE
04610082
04610082-MEP_BSALS_CENTRAL_v2012.rvt
BDH
TMH
JCP E800.5
ELECTRICAL
DETAILS
0461
BP #5 DESIGN
DOCUMENTS
SEPTEMBER 12, 2014
NO SCALE 1 2" AND SMALLER CONDUIT SUPPORT DETAIL
NO SCALE 2 2-1/2" AND LARGER CONDUIT SUPPORT DETAIL
NO SCALE 3 LAY-IN FIXTURE DETAIL
NO SCALE 4 OVER MIRROR LIGHT FIXTURE INSTALLATION DETAIL
NO SCALE 5 WALL BOX INSTALLATION DETAIL
MARK DATE DESCRIPTION