HomeMy WebLinkAbout127_P601 (Const Issue 7-22-2010).PDFPLUMBING PUMP SCHEDULE
DESIGN DESIGN PUMP MOTOR DATA SPECIFICATION MANUFACTURER WITH
MARK LOCATION SYSTEM TYPE CAPACITY CAPACITY (FT. MIN EFF. SUCT. DISCH. SECTION MODEL NUMBER NOTES
(GPM) HD.) (IN.) (IN.) HP RPM VOLTS PH
HWRP-1 MECHANICAL ROOM 206 DOMESTIC HOT WATER INLINE 4 10 - 3/4" 3/4" � 2650 115 1 221123 B&G #PL-30B 1
NOTES:
1. PUMP IS CONTROLLED BY A STRAP ON AQUASTAT AND BY AN AUTOMATIC TIMER.
PLUMBING FIXTURE ROUGH-IN SCHEDULE
ROUGH-IN SIZES
MARK FlXTURE TYPE WASTE VENT CW HW FIXTURE MOUNTING HEIGHT SPECIFlCATION NOTES
SECTION
SIZE SIZE SIZE SIZE
WC-1 WATER CLOSET 4" 2" 1" - SEE SPECIFICATION 224000 1, 3
WC-2 WATER CLOSET, ADA COMPLIANT 4" 2" 1" - SEE SPECIFICATION 224000 1, 3, 4
WC-3 WATER CLOSET, ADA COMPLIANT 4" 2" 1" _ SEE SPECIFICATION 224000 1, 2, 4
WC-4 WATER CLOSET, ADA COMPLIANT 4" 2" 1" - SEE SPECIFICATION 224000 1, 3, 15
UR-1 URINAL 2" 1 1/2" 3/4" - SEE SPECIFICATION 224000 1, 6
UR-2 URINAL, ADA COMPLIANT 2" 1 1/2" 3/4" - SEE SPECIFICATION 224000 1, 6
L-1 LAVATORY, ADA COMPLIANT 1 1/2" 1 1/2" 1/2" 1/2" COUNTER MOUNTED 224000 1, 8, 9, 10, 11, 12
L-2 LAVATORY, ADA COMPLIANT 1 1/2" 1 1/2" 1/2" 1/2" SEE SPECIFICATION 224000 1, 8, 9, 10, 12
L-3 LAVATORY, ADA COMPLIANT 1 1/2" 1 1/2" 1/2" 1/2" SEE SPECIFICATION 224000 1, 7, 9, 10, 12
EWC-1 BI-LEVEL ELECT. WATER COOLER, ADA COMPLIANT 1 1/2" 1 1/2" 1/2" - SEE SPECIFICATION 224000 1
SK-1 SINGLE COMPARTMENT STAINLESS STEEL SINK 1 1/2" 1 1/2" 1/2" 1/2" COUNTER MOUNTED 224000 1, 11, 13
MB-1 MOP SERVICE BASIN 3" 2" 1/2" 1/2" FLOOR MOUNTED 224000 1
SU-1 SHOWER UNIT, ADA COMPLIANT - - 1/2" 1/2" SEE SPECIFICATION 224000 1
IB-1 ICE MAKER SUPPLY UNIT BOX - - 1/2" - VARIES REFER TO DETAIL #7/P501 224000 1
HB-1 HOSE BIBB - - 3/4" - �$" 221116 1
WH-1 WALL HYDRANT - - 3/4" - - 221116 14
NOTES:
1. MOUNTING HEIGHT IS FROM FINISHED FLOOR.
2. WALL MOUNTED WATER CLOSET WITH MANUAL OPERATED FLUSH VALVE.
3. WALL MOUNTED WATER CLOSET WITH ELECTRONIC SENSOR OPERATED FLUSH VALVE.
4. INSTALL FLUSH VALVE HANDLE AT WIDE SIDE OF COMPARTMENT.
5. WALL MOUNTED URINAL WITH MANUAL OPERATED FLUSH VALVE.
6. WALL MOUNTED URINAL WITH ELECTRONIC SENSOR OPERATED FLUSH VALVE.
7. MANUAL OPERATED HAND WASHING FAUCET.
8.. ELECTRONIC SENSOR OPERATED HAND WASHING FAUCET, PROVIDED WITH UNDER LAVATORY THERMOSTATIC MIXING VALVE WITH SINGLE TEMPERED HOT WATER SUPPLY.
9. INSULATE DRAIN AND WATER SUPPLIES WITH INSULATION KIT.
10. 2g" MINIMUM KNEE CLEARANCE.
11. PROVIDE THE CABINET SUPPLIER WITH APPROVED SHOP DRAWINGS SHOWING THE SIZE OF THE REQUIRED OPENING IN THE CABINET ENCLOSURE FOR THE PROPER INSTALLATION OF THE
LAVATORY, TRIM, OR SINK.
12. OFF SET P TRAP AND WASTE PIPING UNDER ADA COMPLIANT SINKS.
13. ADA COMPLIANT FOR SIDE APPROACH.
14. MOUNTING HEIGHT OF 24" FROM FINISHED GRADE, UNLESS INDICATED DIFFERENT ON ARCHITECTURAL DRAWINGS.
15. FLOOR MOUNTED WATER CLOSET WITH MANUAL OPERATED FLUSH VALVE.
BACKFLOW PREVENTER SCHEDULE
DESIGN PRESS. SIZE SPECIFICATION MANUFACTURER WITH
MARK LOCATION SYSTEM TYPE CAPACITY DROP (IN) SECTION MODEL NUMBER NOTES
(GPM) (PSIG)
BFP-1 SPRINKLER/WATER MAIN CW SYSTEM REDUCED PRESSURE ZONE 110 13 3 22 1116 WA�S 1, 2, 3, 4
RISER ROOM 128 ASSEMBLY 909-NRS-S-FDA
BFP-2 SPRINKLER/WATER MAIN CW SYSTEM REDUCED PRESSURE ZONE 110 13 3 22 1116 WA�S 1, 2, 3, 4
RISER ROOM 128 ASSEMBLY 909-NRS-S-FDA
NOTES:
1. USC APPROVED, FDA EPDXY COATED STRAINER, 7.5 FPS FLOW.
2. IN-LINE, INDEPENDENT CHECK VALVES WITH AN INTERMEDIATE RELIEF VALVE, NON-RISING STEM RESILIENT SEATED GATE VALVES.
3. PROVIDE UNIT WITH AIR GAP DRAIN ASSEMBLY, PIPE DRAIN TO NEAREST FLOOR DRAIN OR SINK.
4• MAXIMUM MOUNTING HEIGHT OF 5'-0" ABOVE FLOOR.
5. IN-LINE, INDEPENDENT CHECK VALVES WITH AN INTERMEDIATE RELIEF VALVE, FULL PORT QUARTER-TURN RESILIENT SEATED BALL VALVES.
6. BRONZE STRAINER.
WATER HAMMER ARRESTOR SCHEDULE
TYPE FIXTURE UNIT RATING I.P.S. J. R. SMITH NUMBER SPECIFICATION SECTION NOTES
WHA—A 1-11 3/4" 5005 221116 1
WHA—B 12-32 1" 5010 221116 1
WHA—C 33-60 1" 5020 221116 1
WHA—D 61-113 1" 5030 221116 1
WHA—E 114-154 1" 5040 221116 1
WHA—F 155-330 1" 5050 221116 1
NOTES:
1• WATER HAMMER ARRESTORS SHALL BE SIZED AND INSTALLED PER THE PLUMBING DRAINAGE INSTITUTE (STANDARD PDI—WH 201) REQUIREMENTS IN ACCESSIBLE LOCATIONS ON THE COLD
WATER AND HOT WATER PIPING AND WHERE FLUSH VALVES AND ANY OTHER QUICK CLOSING VALVES ARE USED.
THERM4STATIC MIXING VALVE SCHEDULE
CAPACITY PRESSURE CONNECTION SIZES ��� W �
DROP AT z v � o'` �� Z� SPECIFICATION MANUFACTURER
MAX MIN HW CW TEMPER � > o Y�
M A R K L O C A T I O N M A X F L O W E X T E R I O R F I N I S H m o �„ S Q � c, � SECTION W I T H M O D E L N O T E S
FLOW FLOW INLEf INLET OUTLET Q c� _> � o c�
(GPM) (GPM) (PSI) (IN) (IN) (IN) " Z J `�' W J'�' NUMBER
w Q � �
3
TMV-1 MECH. ROOM 206 25 1 10 3/4' 3/4" 1" BRONZE NO YES YES YES NA 221116 �`WLER VALVE �
#801 SERIES
NOTES:
1. HIGH—LOW FLOW UNIT.
ELECTRIC WATER HEATER SCHEDULE
ELECTRICAL DATA RECOVERY NOMINAL �N� MANUFACTURER
STORAGE SPECIFICATION
MARK LOCATION CAPACITY W�BSHT SECTION WI UM EREL NOTES
HP KW VOLTS PHASE GPH/GPM RISE 'F ��.� � )
EWH-1 MECH. ROOM 206 - 15 480 3 62 GPH 100 80 1000 223301 LOCHINVAR
HC 15-80A
EWH-2 GREEN ROOM 124 - 9 277 1 1 GPM 61 NA NA 223301 EEMAX SP90 INSTANT FLOW
EWH-3 LOUNGE 200 - 9 277 1 1 GPM 61 NA NA 223301 EEMAX SP90 INSTANT FLOW
NOTES:
,.
PLUMBING EQUIPMENT SCHEDULE
ITEM MAKE AND MODEL N0. DESCRIPTION CAPACITY SPECIFICATION SECTION NOTES
DIAPHRAGM-TYPE PRE-PRESSURIZED 4.7 GALLON, .51 MAX. ACCEPT.
EXT-1 AMTROL THERM-X-TROL #ST-12-C EXPANSION TANK FACTOR, 150 PSI MAX WORKING 223301 1
PRESSURE
NOTES:
1. PRE-CHARGED THERMAL EXPANSION ABSORBER DESIGNED AND CONSTRUCTED PER ASME CODE - SECTION VIII, FOR WORKING PRESSURE OF 150 PSI. ALL INTERNAL WETTED PARTS SHALL
COMPLY WITH FDA REGULATIONS AND APPROVALS.
ROOF OVERFL�W DRAI N SCH EDU LE
DRAIN BODY STRAINER � o �'
w � � z a MANUFACTURER
MARK DESCRIPTION �,��-, o �� Z=� SPECIFICATION
OUTLET OUTLET N � z o W SECTION WITH MODEL NOTES
MATERIAL S I Z E T Y P E MATERIAL SIZE TYPE �� ��� � NUMBER
RD-1 GERNERAL PURPOSE CAST IRON AS NO-HUB CAST IRON AS TWIST YES YES NO YES 22 13 16 J.R. SMITH �
ROOF DRAIN NOTED REQ. LOCK #1010Y SERIES
OFD-1 OVERFLOW ROOF DRAIN CAST IRON AS NO-HUB CAST IRON AS TWIST YES YES NO YES 22 13 16 J.R. SMITH �
NOTED REQ. LOCK #1080Y SERIES
RD-2 GENERAL PURPOSE CAST IRON AS THREADED GALVANIZED CAST AS TWIST YES YES NO YES 22 13 16 J.R. SMITH �
ROOF DRAIN NOTED OR CAULK IRON REQ. LOCK #1340 SERIES
N-1 DOWNSPOUT NOZZLE NICKEL AS THREADED -- -- -- -- -- -- -- 22 13 16 J.R. SMITH
BRONZE NOTED #1770 SERIES
NOTES:
�. ALL ROOF DRAINS AND OVERFLOW DRAINS SHALL BE OF THE 4 BOLT PATTERN.
FLOOR DRAIN SCHEDULE
DRAIN BODY STRAINER �� a o�� ; MANUFACTURER
MARK DESCRIPTION �, � o o��c z SPECIFICATION
OUTLET OUTLET W Z� o� � SECTION WI UM EREL NOTES
MATERIAL SIZE TYPE MATERIAL SIZE TYPE Z�> a w m
FD-1 FLOOR DRAIN CAST IRON AS NO-HUB NICKEL BRONZE AS ROUND YES YES NO NO 22 13 16 J.R. SMITH FIG. �
NOTED REQ. #2041-A
FD-2 FLOOR DRAIN CAST IRON AS NO-HUB NICKEL BRONZE AS ROUND NO YES NO NO 22 13 16 J.R. SMITH FIG. 2� 4
NOTED REQ. #2005Y-A
FD-3 FLOOR DRAIN CAST IRON AS NO-HUB CAST IRON AS ROUND NO NO YES NO 22 13 16 J.R. SMITH FIG. 2� 3
NOTED REQ. #2230Y
FD-4 FLOOR DRAIN CAST IRON AS NO-HUB CAST IRON AS ROUND NO NO YES NO 22 13 16 J.R. SMITH FIG. 2
NOTED REQ. #2230Y
NOTES:
1. INTEGRAL TRAP WITH FLOOR LEVEL CLEANOUT.
2. DEEP SEAL TRAP.
3. FLOOR LEVEL CLEANOUT.
4. WATER PROOFING MEMBRANE: FLASHING CONSTRUCTED IN PLACE USING 40 MIL CHLORINATED POLYETHYLENE SHEETS (CHLORALOY 240).
Owner:
CARMEL THEATER
DEVELOPMENT COMPANY
11711 North Pennsylvania Street, Suite 200
Carmel, Indiana 46032
317.573-6050
Architect:
. . � : � �, 4 ,
PEDCOR DESIGN GROUP
Architecture / Project Management:
355 City Center Drive
Carmel, Indiana 46032
317.705.7979 (phone)
317.705.7980 (fax)
Engineer:
L'AC UIS
CONSULTING ENGINEERS
9229 DELEGATES ROW, SUTTE 550
INDIANAPOLIS, IN 46240
317.706.2075
WWW.LACQUIS.COM
KEY PLAN
SCALE+ NTS
PLAN I�ORTH
Project:
COPYRIGHT & OWNERSHIP OF DOCUMENTS
THIS DOCUMENT IS AN INSTRUMENT OF SERVICES AND IS THE
SOLE PROPERTY OF THE ARCHITECT AND PEDCOR DESIGN GROUP,
ALL INFORMATION CONTAINED HEREIN IS CONFIDENTIAL, ITS
SUBMISSION AND DISTRIBUTION TO OTHER PARTIES IS NOT TO BE
CONSTRUED AS PUBLICATIDN IN DEROGATION OF COMMON LAW
COPYRIGHT, INTELLECTUAL PROPERTY RIGHTS OR OTHER
RESERVED RIGHTS, ALL INFORMATIDN CONTAINED HEREIN
CONSTITUTES THE ORIGINAL AND UNPUBLISHED WORK OF THE
ARCHITECT, JAMES R, STUTZMAN, AND PEDCOR DESIGN GRDUP, LLC,
NO PART OR WHOLE OF THIS DESIGN, THESE DRAWINGS, OR THE
RESULTING BUILDING OR BUILDINGS, OR PORTIONS OF THE
RESULTING BUILDING OR BUILDINGS MAY BE DUPLICATED, COPIED,
EXHIBITED,PHOTOGRAPHED,PUBLISHED,MODIFIED OR OTHERWISE
DISTRIBUTED IN ANY WAY WITHOUT THE SPECIFIC AND PRIOR
WRITTEN CONSENT OF THE ARCHITECT, JAMES R, STUTZMAN AND
PEDCOR DESIGN GROUP, LLC, c COPYRIGHT 2006, 2007, 2008,
2009 JAMES R, STUTZMAN, AIA, INDIANAPOLIS,
BID PACKAGE N0. 3
CONSTRUCTION ISSUE SET
rin a e Sheet Issue Date
07/22/10 04/01 /10
Drawn By Checked By
GMR AJM
Last Revision Date:
0
O
O
O
O
O
Project Number:
Parcel 7C-1
Sheet Title:
PLUMBING
SCHEDULES
Sheet Number: