FIRE RISER
� i: \ ► ►
T.S.
INDICATING TYPE FLOOR CONTROL
VALVE WITH SUPERVISORY SWITCH.
PRESSURE GAUGE
WATERFLOW SWITCH
� SIZE PER HYDRAULIC
� � CALCULATIONS
FEED MAIN
INSTALL ASSEMBLY IN
RECESSED CABINET
� ���TEST AND DRAIN ASSEMBLY
' WITH CORROSION RESISTANT
� ORIFICE GIVING FLOW EQUIVALENT
TO THE SMALLEST SPRINKLER
ORIFICE IN THE SYSTEM.
2" DRAIN LINE, ROUTE TO EXTERIOR
OF THE BUILDING.
CLASS I, 2-1/2" FIRE HOSE VALVE
�, WITH CAP AND CHAIN.
INDICATING TYPE FLOW CONTROL VALVE
WITH SUPERVISORY SWITCH AT RISER BASE
COMBINATION CLASS I STANDPIPE
�
SPRINKLER RISER AND DRAIN DETAIL
SCALE: NONE
DETAIL NOl
1. 6" PIPING FROM
2. PREACTION SYSTI
3. 6" TO STANDPIPE
4. WET PIPE RISER
�
FI RE PROTECTION RISER
PIPING DETAIL
3 SCALE: NONE
C
MARK
FP-1
JP-1
LOCATION
SPRINKLER/WATER RISER ROOM 128
SPRINKLER/WATER RISER ROOM 128
SYSTEM
FIRE PROTECTION
FIRE PROTECTION
NOTES:
1. FIRE PUMP CONTROLLER; FIRETROL MODEL FTA1930-AM506, FIRETROL M
CHECK VALVE
�(TYPICAL) FULL LINE SIZED AUTOMATIC BALL DRIP,
� � BY-PASS DRAIN THRU WALL
� i r ,.
r , �
CHECK VALVE
TO BUILDING FIRE (TYPICAL)
PROTECTION SYSTEM
Q
PUMP SUCTION HEAD PRESSURE
CONTROL VALVE
FIRE PUMP (FP-1) ON
CONCRETE PAD
TYPICAL PRESSURE GAUGE
JOCKEY PUMP (JP-1) ON �
CONCRETE PAD
—_
� _ -- _
_�-
° � =�1=
. -��
TANK MOUNTED
AIR COMPRESSOR
TYPE
INLINE VERTICAL
MULTISTAGE CENTRIFUGAL
FI RE PU M P SCH EDU LE
DESIGN DESIGN PUMP
CAPACITY CAPACITY (FT. MIN EFF. SUCT. DISCH.
(GPM) HD.) (IN.) (IN.) HP
750 192 - 6 6 50
8 219 - 1 1 1
MOTOR DATA
RPM VOLTS PH
3600 460 3
- 460 3
SPECIFICATION MANUFACTURER WITH
SECTION MODEL NUMBER
21 30 00
21 30 00
PEERLESS #
GRUNDFOS #CR1-9
NOTES
1
2
BACKFLOW PREVENTER SCHEDULE
DESIGN PRESS. SIZE SPECIFICATION MANUFACTURER WITH
MARK LOCATION SYSTEM TYPE CAPACITY DROP (IN) SECTION MODEL NUMBER NOTES
(GPM) (PSIG)
DCV-1 SPRINKLER/WATER MAIN FIRE SERVICE DOUBLE CHECK VALVE 6 21 13 00 AMES �, 2
RISER ROOM 128 ASSEMBLY COLT SERIES 200
NOTES:
�• PROVIDED WITH GATE OR UL/FM BUTTERFLY VALVES WITH TAMPER SWITCH.
2• MAXIMUM MOUNTING HEIGHT OF 5'-0" ABOVE FLOOR.
� EXTERIOR WALL
FIRE DEPARTMENT
��CONNECTION
FIRE PUMP
�� TEST H EAD
PIPE SLEEVE (TYPICAL) �
SEE DETAIL
- - FLOOR LINE
� `� DOUBLE CHECK
�� VALVE ASSEMBLY
(DCV-1)
TYPICAL OS&Y GATE VALVE WITH
SUPERVISORY TAMPER SWITCH
TYPICAL OS&Y GATE VALVE OR
INDICATING BUTTERFLY VALVE WITH
SUPERVISORY TAMPER SWITCH
NOTE:
I I INSTALL FIRE PUMP, ACCERORIES AND DEVICES AS REQUIRED
r—INCOMING FIRE SERVICE gY CODE AND PUMP MANUFACTURES RECOMMENDATIONS.
FIRE PUMP PIPING DETAIL
SCALE: NONE
� �
W
J
>
Y
U
W
2
U
a
�
M
�
�E DEVICE
3/4"
�
GALV
�� 6"DRIP LEG WITH
DRAIN VALVE & PLUG
PRE-ACTION SYSTEM AI R
COM PRESSOR PI PI NG DETAI L
SCALE: NONE
PIPE VA.
A.
B.
C.
E.
F.
G.
H.
L.
M.
N.
�
T.
S.
2.
3.
4.
5.
6.
GENERAL FIRE PROTECTION NOTES
REFER TO DRAWING M001 FOR MECHANICAL AND PLUMBING SYMBOLS AND ABBREVIATIONS.
ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE TRADE, AND
SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND STANDARDS. THE SAME
ARE MADE A PART OF THESE CONTRACT DOCUMENTS, THE SAME AS IF REPEATED HEREIN.
CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND DRAWINGS, AND BOTH
ARE INTENDED TO BE COMPLEMENTARY - ANYTHING APPEARING ON EITHER MUST BE EXECUTED
THE SAME AS IF SHOWN ON BOTH.
THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS REQUIRED TO COMPLETELY
AND PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT, AND SHALL EXAMINE THE
SCOPE OF WORK OF OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, HOWEVER,
SYSTEMS HAVE BEEN SHOWN DIAGRAMATICALLY AND IN SOME CASES, ENLARGED FOR CLARITY.
ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE A
COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE CONTRACTOR.
CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS PRIOR TO BIDDING OR BEGINNING WORK ON
THIS PROJECT.
PROVIDE AND INSTALL VALVES IN ALL SYSTEMS AS REQUIRED TO FACILITATE THE OPERATION OF
VARIOUS SYSTEMS DURING CONSTRUCTION.
ALL PIPING IN CEILING SPACE SHALL BE INSTALLED AND ROUTED IN A MANNER TO AVOID
DUCTWORK, LIGHT FIXTURES, JOIST, BEAMS, ETC.
ALL PIPING IN PIPE CHASES AND TUNNELS SHALL BE RUN AS CLOSE TO WALLS AS POSSIBLE
TO ALLOW MAXIMUM ACCESS.
INSTALL THE SPRINKLER ZONE INSPECTOR TEST DRAIN LINE PARALLEL WITH THE FIRE SERVICE
LINE AND ROUTE TO THE EXTERIOR OF THE BUILDING.
PROVIDE CEILING ACCESS PANELS FOR ACCESS TO SHUT-OFF VALVES, CONTROL VALVES, DRAIN
VALVES, ETC. LOCATED ABOVE NON-ACCESSIBLE CEILING. COORDINATE ALL ACCESS PANELS
WITH ARCHITECTURAL DRAWINGS.
ALL ELECTRICAL AND MECHANICAL ROOMS SHALL BE SPRINKLED WITH HIGH TEMPERATURE
SPRINKLER HEADS.
THE FIRE PROTECTION PIPE ROUTING SHOWN IS PROVIDED AS A GUIDE TO THE FIRE
PROTECTION CONTRACTOR. THE SUCCESSFUL BIDDER SHALL DESIGN THE AUTOMATIC FIRE
PROTECTION SYSTEMS IN ACCORDANCE WITH THE INSTRUCTIONS IN THE SPECIFICATIONS AND
DRAWINGS.
THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION SYSTEMS SHALL CONFORM TO THE
NATIONAL FIRE PROTECTION ASSOCIATION CODES (NFPA), STANDARDS AND RECOMMENDED
PRACTICES, LATEST EDITIONS ADOPTED BY THE STATE OF INDIANA. ALL APPLICABLE STATE AND
LOCAL FIRE PREVENTION BUREAU'S STATUES AND CODES, AND REQUIREMENTS OF OWNER'S
INSURANCE UNDERWRITER. INCLUDE ALL PIPE AND FITTINGS, APPROVED WATER FLOW
DETECTING ALARM DEVICES, PRESSURE GAUGES, SPRINKLER HEADS, INDICATING VALVES, FIRE
DEPARTMENT CONNECTIONS, AND OTHER MATERIALS NEED TO PROVIDE A COMPLEfE AND
OPERABLE CODE COMPLIANT SYSTEM.
THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN LAYOUT OF THE
SPRINKLER SYSTEMS AS REQUIRED FOR ALL NEW AREAS. THE ENTIRE BUILDING SHALL BE
SPRINKLED PER NFPA 13, LATEST ENFORCED EDITION AND BUILDING CODE, PROVIDING A
COMPLETE, CERTIFIED SYSTEM AND FINAL CONSTRUCTION COORDINATION.
THE WATER FLOW TEST INFORMATION SHOWN ON THE DRAWINGS IS THE LATEST INFORMATION
AVAILABLE FROM THE CITY AT THIS TIME, THIS FLOW TEST SHALL BE USED FOR BID
PREPARATION, THE FIRE PROTECTION CONTRACTOR SHALL PERFORM HIS OWN FLOW TEST AND
SUBMIT THE RESULTS TO THE ENGINEER PRIOR TO START OF WORKING PLANS.
FLOW TEST DATA: IT SHALL BE THIS CONTRACTOR'S RESPONSIBILITY TO ENSURE ADEQUACY OF
FLOW AND PRESSURE FROM THE CITY'S WATER DISTRIBUTION SYSTEM. COST OF TEST SHALL
BE BORNE BY THIS CONTRACTOR.
FIRE PROTECTION DESIGN NOTES
THE CONTRACTOR SHALL PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC FIRE SPRINKLER
SYSTEM DESIGNED AND INSTALLED TO PRODUCE DISCHARGE DENSITIES OF NOT LESS THAN 0.10
GPM/SQUARE FOOT OVER THE HYDRAULICALLY MOST REMOTE 1500 SQUARE FEEf WITH A
MAXIMUM OF 225 SQUARE FEET PER HEAD THROUGHOUT ALL LIGHT HAZARD OCCUPANCY AREAS
PLUS 100 GPM OUTSIDE FIRE HOSE STREAM. QUICK RESPONSE (QR) SPRINKLERS REQUIRED
FOR LIGHT HAZARD (QR SPRINKLERS MAY REDUCE DESIGN AREA);
a) ASSEMBLY
b) LOBBY
c) OFFICE
d) REST ROOMS/TOILETS
e) CORRIDORS
f) STAIRS
g) GENERAL PUBLIC AREAS
THE CONTRACTOR SHALL PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC FIRE SPRINKLER
SYSTEM DESIGNED AND INSTALLED TO PRODUCE DISCHARGE DENSITIES OF NOT LESS THAN 0.15
GPM/SQUARE FOOT OVER THE HYDRAULICALLY MOST REMOTE 1500 SQUARE FEET WITH A
MAXIMUM OF 130 SQUARE FEET PER HEAD THROUGHOUT ORDINARY HAZARD GROUP 1
OCCUPANCIES PLUS 250 GPM OUTSIDE FIRE HOSE STREAM;
a) MECHANICAL / ELECTRICAL ROOMS
b) RECEIVING / LOADING
c) STORAGE ROOMS
THE CONTRACTOR SHALL PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC FIRE SPRINKLER
SYSTEM DESIGNED AND INSTALLED TO PRODUCE DISCHARGE DENSITIES OF NOT LESS THAN 0.2
GPM/SQUARE FOOT OVER THE HYDRAULICALLY MOST REMOTE 1500 SQUARE FEET WITH A
MAXIMUM OF 130 SQUARE FEEf PER HEAD THROUGHOUT ORDINARY HAZARD GROUP 2
OCCUPANCIES PLUS 250 GPM OUTSIDE FIRE HOSE STREAM;
a) STAGE
INCREASE PRE-ACTION PIPE SYSTEMS OPERATING AREAS BY 30� WITHOUT INCREASING THE
DENSITY.
PROVIDE COVERAGE UNDER ALL OBSTRUCTIONS OVER 48" WIDE.
UNENCLOSED STAIRWAYS SHALL BE PROVIDED WITH 18" DRAFT CURTAIN WITH CLOSED-SPACED
SPRINKLERS.
WET PIPE SYSTEM
PRE-ACTION SYSTEM
Owner:
CARMEL THEATER
DEVELOPMENT COMPANY
11711 North Pennsylvania Street, Suite 200
Carmel, Indiana 46032
317.573-6050
Architect:
. . � : � �, 4 ,
PEDCOR DESIGN GROUP
Architecture / Project Management:
355 City Center Drive
Carmel, Indiana 46032
317.705.7979 (phone)
317.705.7980 (fax)
Engineer:
L'AC UIS
CONSULTING ENGINEERS
9229 DELEGATES ROW, SUTTE 550
INDIANAPOLIS, IN 46240
317.706.2075
WWW.LACQUIS.COM
KEY PLAN
SCALE+ NTS
PLAN I�tTH
Project:
r
1
U
1
�
J M
.
W �
Z
U
� �
� �
Q c� � N
� 1 � M
1 U � �
Z � � �
� � �
�..�..� (n ..
�..�..� � Z
._
� m �
� �
� �� J
� V W
W - � �
_� +�-+ �/
. — (n I..L
� � � Q
� Q
z � U
U
O �
�--+
W �
�
� �
� �
J
J
—
�
COPYRIGHT & OWNERSHIP OF DOCUMENTS
THIS DOCUMENT IS AN INSTRUMENT OF SERVICES AND IS THE
SOLE PROPERTY OF THE ARCHITECT AND PEDCOR DESIGN GROUP,
ALL INFORMATION CONTAINED HEREIN IS CONFIDENTIAL, ITS
SUBMISSION AND DISTRIBUTION TO OTHER PARTIES IS NOT TO BE
CONSTRUED AS PUBLICATIDN IN DEROGATION OF COMMON LAW
COPYRIGHT, INTELLECTUAL PROPERTY RIGHTS OR OTHER
RESERVED RIGHTS, ALL INFORMATIDN CONTAINED HEREIN
CONSTITUTES THE ORIGINAL AND UNPUBLISHED WORK OF THE
ARCHITECT, JAMES R, STUTZMAN, AND PEDCOR DESIGN GRDUP, LLC,
NO PART OR WHOLE OF THIS DESIGN, THESE DRAWINGS, OR THE
RESULTING BUILDING OR BUILDINGS, OR PORTIONS OF THE
RESULTING BUILDING OR BUILDINGS MAY BE DUPLICATED, COPIED,
EXHIBITED,PHOTOGRAPHED,PUBLISHED,MODIFIED OR OTHERWISE
DISTRIBUTED IN ANY WAY WITHOUT THE SPECIFIC AND PRIOR
WRITTEN CONSENT OF THE ARCHITECT, JAMES R, STUTZMAN AND
PEDCOR DESIGN GROUP, LLC, c COPYRIGHT 2006, 2007, 2008,
2009 JAMES R, STUTZMAN, AIA, INDIANAPOLIS,
BID PACKAGE N0. 3
CONSTRUCTION ISSUE SET
rin a e Sheet Issue Date
07/22/10 04/01 /10
Drawn By Checked By
GMR AJM
Last Revision Date:
0
�
0
O
O
0
Project Number:
Parcel 7C-1
Sheet Title:
� FIRE PROTECTION
DETAILS
Sheet Number: