HomeMy WebLinkAbout135_E001 (Const Issue 7-22-2010).PDFFI RE ALARM I DENTITY
SYMBOLS
� CONTROL RELAY
� CONTROL RELAY
❑F Q HORN AND STROBE
� HORN UNIT ONLY
� STROBE UNIT ONLY
F s SPEAKER AND STROBE
❑F MANUAL PULL STATION
sO SMOKE DETECTOR
� DUCT SMOKE DETECTOR WITH TWO AUXILIARY CONTACTS
RTs REMOTE STATION FOR DUCT DETECTOR USED AT DUCT
WORK OPENING
DA AREA TYPE SMOKE DETECTOR USED AT DUCT WORK
OPENING
� ELEVATOR RECALL WITH AUXILIARY CONTACTS
Q,� SELF CONTAINED SMOKE DETECTOR-SINGLE STATION TYPE
Q, SMOKE DETECTOR-VISUAL AND AUDIBLE SIGNAL
� BEAM SMOKE DETECTOR, "R"-INDICATES RECEIVER
Q5 BEAM SMOKE DETECTOR, "S" INDICATES SENDING UNIT
� CARBON MONOXIDE DETECTOR. LINE VOLTAGE WITH
BATTERY BACKUP
� FLAME DEfECTOR
� AUTOMATIC HEAT DETECTOR, "R" INDICATES RATE OF RISE
� AUTOMATIC HEAT DETECTOR, "F" INDICATES FIXED
TEMPERATURE 190'F
� HYDROGEN DETECTOR
� MOTOR OPERATED FIRE/SMOKE DUCT DAMPER
Fs WATER FLOW SWITCH, BY DIVISION 15
� LOW PRESSURE SWITCH, BY DIVISION 15
❑Ts TAMPER SWITCH, BY DIVISION 15
P�v POST INDICATOR VALVE, BY DIVISION 15
Eo� END-OF-LINE RESISTOR
FIRE ALARM COMM
I DENTITY SYM BOLS
� FIRE ALARM MASTER BOX
� FIRE FIGHTER'S PHONE
FT CODE TRANSMITTER
� DRILL KEY SWITCH
� KEY REPOSITORY (KNOX BOX)
FA FIRE ALARM ANNUNCIATOR PANEL, 2 LINES OF 4'
CHARACTERS LCD DISPLAY
FACP FIRE ALARM CONTROL PANEL
EVA VOICE EVACUATION PANEL
FATC FIRE ALARM TERMINAL CABINET
BAn BATTERY PACK AND CHARGER
As� AIR SAMPLING CONTROL/DETECTOR PANEL WITH
ASSOCIATED AIR SAMPLING PIPING NETWORK
�R TRANSPONDER
IAM INDIVIDUALLY ADDRESSABLE MODULE- MONITOR (PROVIDES
ADDRESS FOR CONTACT)
� INDIVIDUALLY ADDRESSABLE MODULE- RELAY (PROVIDES
CONTACT CLOSURE)
ONE-LINE IDENTITY
SYMBOLS
CAPACITOR
� CIRCUIT BREAKER (OPEN), "xxAF" INDICATES FRAME SIZE,
yyAT "yyAT" INDICATES TRIP SIZE
,oc� CIRCUIT BREAKER (ENCLOSED), "xxAF" INDICATES FRAME
»'�`T SIZE, "yyAT" INDICATES TRIP SIZE
� PRIMARY DRAW OUT TYPE CIRCUIT BREAKER, "xxAF"
yyAT INDICATES FRAM SIZE, "yyAT" INDICATES TRIP SIZE
,ou� LOW VOLTAGE DRAW OUT TYPE CIRCUIT BREAKER, "xxAF"
�T INDICATES FRAM SIZE, "yyAT" INDICATES TRIP SIZE
,� LOW VOLTAGE DRAW OUT TYPE CIRCUIT BREAKER. WITH
yyAT CURRENT LIMITING FUSES, "xxAF" INDICATES FRAME SIZE,
�► "yyAT" INDICATES TRIP SIZE, "zzA" INDICATES FUSE
RATING
CONTACT NORMALLY OPEN (NO) ("TC"-WITH TIMED
CLOSING)
CONTACT NORMALLY CLOSED (NC) ("TO"-WITH TIMED
OPENING)
0 CURRENT TRANSFORMER CABINET
1�► FUSED CUTOUTS, "zzA" INDICATES FUSE RATING
�
1 DISCONNECT SWITCH UNFUSED
�
1 »„
DISCONNECT SWITCH AIR BREAK WITH FUSE, zzA
� INDICATES FUSED RATING
�► FUSE, "zzA" INDICATES FUSED RATING
�r OVERLOAD RELAY
� GROUNDING CONNECTION-SYSTEM AND OR EQUIPMENT
K2 KIRK KEY INTERLOCK SYSTEM
LIGHTNING ARRESTER AND GROUNDING TO PROTECT ALL
�o--�r PHASES
3 MOTOR AND LABEL, "3" DENOTES HORSEPOWER
�a-�oc-x-x
Mo MOTOR OPERATOR FOR CIRCUIT BREAKERS OR SWITCH
�� NETWORK PROTECTOR
�
PANEL BOARD
� POTHEAD
� STRESS CONE
�'�✓�/� RESISTOR
O SHUNT TRIP
l�
� MAGNEfIC STARTER WITH NEMA SIZE INDICATED
c�i GROUND FAULT CIRCUIT INTERRUPTER, PERSONNEL
PROTECTION
� XXX �
� XXXv Xo GENERATOR
GENERATOR
n �:,.�
T� TRANSFORMER, DRY TYPE, UNLESS OTHERWISE INDICATED
� rr/�v r r� aee
� POTENTIAL TRANSFORMER, "3" INDICATES QUANTITY
(3)
�3� CURRENT TRANSFORMER, "3" INDICATES QUANTITY,
��,� "400-5A" INDICATED RATIO
Q 3-PHASE, 3-WIRE DELTA CONNECTION
� CORNER GROUNDED DELTA
� 3-PHASE, 4-WIRE WYE CONNECTION (GROUNDED
N EUTRAL)
,� ADJUSTABLE FREQUENCY DRIVE 3 REFERENCES DETAIL
xx-x-x N U M BER
�' �' � BUS DUCT OR BUS WAY
�' �" ""� �"Y WIRE WAY
�"�`�" TRANSFER SWITCH
SWITCH BOARD M ETER
I DENTITY SYM BOLS
CM CUSTOMER MEfER
OD DEMAND METER (UTILITY)
WM WATTHOUR METER (UTILITY)
SECURITY IDENTITY
SYMBOLS
� CCN CAMERA "WP" INDICATES WEATHER-PROOF EXTERIOR
CAMERA
� CCN COAXIAL CABLE OUTLET AND POWER OUTLET
� CCN MONITOR OUTLET
C�a DOORBELL
a0/ DOOR BUZZER
B� DOOR CHIME
� ELECTRIC DOOR OPENER
Es ELECTRIC DOOR STRIKE
ic INTERCOM UNIT - FLUSH MOUNT
M� MASTER INTERCOM AND DIRECTORY UNIT
� MOTION DEfECTOR
� SECURITY DOOR ALARM MAGNETIC LOCK
� SECURITY CARD READER. "WP" INDICATES
WEATHER-PROOF
sc SECURITY CONTROL PANEL
� SECURITY DOOR CONTACTS
O SECURITY EXIT PUSH BUTTON
❑K SECURITY KEYPAD
SWITCH I DENTITY
SYMBOLS
S SINGLE POLE SWITCH
S� SWITCH (EDIT AS NEEDED FOR 2-WAY, 3-WAY, a SWITCH
• LEG ETC.
S� SWITCH (EDIT AS NEEDED FOR 2-WAY, 3-WAY, OR a
' SWITCH LEG ETC.
S� CIRCUIT BREAKER SWITCH
SpT SINGLE POLE/DOUBLE THROW SWITCH
S� GLOW SWITCH TOGGLE, GLOWS IN OFF POSITION
SH HORIZONTALLY MOUNTED-WITH ON POSITION TO THE LEFT
SK KEY OPERATED SWITCH
KEY OPERATED SWITCH WITH PILOT LIGHT ON WHEN
SKP SWITCH IS ON
S�� LOW VOLTAGE SWITCH
S� LOW VOLTAGE MASTER SWITCH
SM� MOMENTARY CONTACT SWITCH
SP SWITCH WITH PILOT LIGHT ON WHEN SWITCH IS ON
ST TIMER SWITCH
S� WEATHERPROOF SINGLE POLE SWITCH
� DIMMER SWITCH. RATED 1000W, UNLESS OTHERWISE
INDICATED. "LV" = LOW VOLTAGE "FL" = FLUORESCENT
4 OCCUPANCY SENSOR, WALL MOUNTED WITH OFF-AUTO
OVERRIDE SWITCH
OCCUPANCY SENSOR, CEILING MOUNTED, "P"- INDICATES
O MULTIPLE SWITCHES WIRED IN PARALLEL
COMMUNICATION
I DENTITY SYM BOLS
0 DATA OUTLET
� DATA OUTLEf FLOOR TYPE
� TELEPHONE/DATA OUTLET
� TELEPHONE/DATA OUTLEf FLOOR TYPE
� TELEPHONE OUTLET
�w TELEPHONE OUTLET-WALL MOUNTED
� TELEPHONE OUTLEf FLOOR TYPE
� CALL IN SWITCH
� CABLE ANTENNA SYSTEM OUTLET (CAN)
�M MASTER ANTENNA SYSTEM OUTLEf (MAN)
� MICROPHONE OUTLEf-FLOOR MOUNTED
� MICROPHONE OUTLET-WALL MOUNTED
MONITOR/PAGE SPEAKER-CEILING MOUNTED. SUBSCRIPT
� REPRESENTS ZONE NUMBER. R= RECESSED, S=
SURFACE MTD.
� SPEAKER-WALL MOUNTED
� SPEAKER HORN
�I SPEAKER BI-DIRECTIONAL PAGING-WALL MOUNTED
OI SPEAKER BI-DIRECTIONAL PAGING-CEILING MOUNTED
ic INTERCOM UNIT-FLUSH MOUNTED
M� MASTER INTERCOM AND DIRECTORY UNIT
� VOLUME CONTROL
� EQUIPMENT CABINET
� EQUIPMENT RACK-WALL MOUNTED
� EQUIPMENT RACK-FREE STANDING
�� TERMINAL CABINEf WITH 3/4" PLYWOOD BACKING
� PLYWOOD BACKBOARD
DISTRIBUTION IDENTITY
SYMBOLS
� LIGHTING OR POWER PANEL, RECESSED
� LIGHTING OR POWER PANEL, SURFACE
� DISTRIBUTION PANEL
� LIGHTING OR POWER PANEL ON NORMAL/GENERATOR
FEEDER
� DISTRIBUTION PANEL ON NORMAL/GENERATOR FEEDER
� MOTOR CONTROL CENTER (MCC)
� DRY TYPE TRANSFORMER
. TRANSFORMER-PAD MOUNT
cT CURRENT TRANSFORMER CABINET
c� GENERATOR
OO METER
� METER AND SOCKET
� TRANSFER SWITCH
LIGHTING IDENTITY
SYMBOLS
� SURFACE MOUNTED 2'x4' FIXTURE
� SURFACE MOUNTED 2'x4' EMERGENCY FIXTURE
� RECESSED MOUNTED 2'x4' FIXTURE
� RECESSED MOUNTED 2'x4' EMERGENCY FIXTURE
0 SURFACE MOUNTED 1'x4' FIXTURE
� SURFACE MOUNTED 1'x4' EMERGENCY FIXTURE
� RECESSED MOUNTED 1'x4' FIXTURE
� RECESSED MOUNTED 1'x4' EMERGENCY FIXTURE
O SURFACE MOUNTED FIXTURE
0 SURFACE MOUNTED EMERGENCY FIXTURE
� RECESSED MOUNTED FIXTURE
� RECESSED MOUNTED EMERGENCY FIXTURE
O POLE MOUNTED FIXTURE
0 POLE MOUNTED EMERGENCY FIXTURE
0 SUSPENDED FIXTURE
� SUSPENDED EMERGENCY FIXTURE
i-O WALL MOUNTED FIXTURE
� WALL MOUNTED EMERGENCY FIXTURE
-r�- WALL MOUNTED FIXTURE
� WALL MOUNTED EMERGENCY FIXTURE
I—I LUMINAIRE STRIP TYPE FIXTURE (2 FOOT)
�� LUMINAIRE STRIP TYPE FIXTURE (3 FOOT)
�� LUMINAIRE STRIP TYPE FIXTURE (4 FOOT)
�
�
EXIT LIGHTING FIXTURE, ARROWS AND EXIT FACE AS
� INDICATED ON DWGS (MOUNTING HEIGHTS TO BE
DETERMINED BY JOB SPECIFICATION
�
�
"d
FIXTURE-DOUBLE OR SINGLE HEAD SPOT LIGHT
�4
� EMERGENCY BATTERY UNIT WITH LIGHTING HEADS
�► EMERGENCY BATTERY REMOTE LIGHTING HEADS
� LIGHT TRACK, LENGTH AS INDICATED ON DWGS WITH
NUMBER OF LIGHTS INDICATED ON DWGS AND SCHEDULE
� IN-GROUND OR FLOOR MOUNTED FIXTURE
�-O SINGLE LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
o-❑ SINGLE LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
o-0 SINGLE LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
�o TWIN LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
o-� ROADWAY LUMINAIRE-COBRA HEAD
� BOLLARD TYPE SITE LIGHTING FIXTURE
ABBREVIATIONS AN D TERMS
� PHASE EWC ELECTRIC WATER COOLER OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
'F DEGREES FAHRENHEIT EX EXISTING OL OVERLOAD
A/C AIR CONDITIONING FCU FAN COIL UNIT OZ OUNCE
A AMPERES FLR FLOOR P POLE
ACCU AIR COOLED CONDENSING UNIT FPVAV FAN POWERED VAV UNIT PE PNEUMATIC ELECTRIC
AF AMPERE FUSE FT FOOT, FEET PH PHASE
AFC ABOVE FINISHED COUNTER FURN FURNACE PSI POUNDS PER SQUARE INCH
AFF ABOVE FINISHED FLOOR G GROUND PSIA POUNDS PER SQUARE INCH ABSOLUTE
AHU AIR HANDLING UNIT GC GENERAL CONTRACTOR PSIG POUNDS PER SQUARE INCH GAUGE
AIC AMPERES INTERRUPTING CAPACITY GFI GROUND FAULT INTERRUPTING PTAC PACKAGED TERMINAL AIR CONDITIONER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE HHWP HEATING HOT WATER PUMP RCPT RECEPTACLE
ARCH ARCHITECT HO HUB OUTLET REV REVOLUTIONS
AVG AVERAGE HOA HAND-OFF-AUTOMATIC RM ROOM
B/I BYPASS ISOLATION HORIZ HORIZONTAL RPM REVOLUTIONS PER MINUTE
BE BOTTOM ELEVATION HP HORSEPOWER RPS REVOLUTIONS PER SECOND
BHP BRAKE HORSEPOWER HR HOUR(S) RTU ROOF TOP UNIT
BLDG BUILDING HRTU HEATING ONLY ROOFTOP UNIT SF SQUARE FOOT
BSMT BASEMENT Hz HERTZ SPEC SPECIFICATION
BtuH BRITISH THERMAL UNIT PER HOUR ID INSIDE DIAMEfER SQ SQUARE
C CONDUIT IN INCH, INCHES ST SHUNT TRIP
CB CIRCUIT BREAKER INT INTERIOR STD STANDARD
CCW COUNTERCLOCKWISE INV INVERT SW SWITCH
CH CHILLER K KELVIN TBI TO BE INSTALLED
CHWP CHILLED WATER PUMP kW KILOWATT TBR TO BE REMOVED
CLG CEILING LBS POUNDS TR TO REMAIN
COMPR COMPRESSOR LTG LIGHTING TE TOP ELEVATION
COND CONDENSER MAX MAXIMUM TEMP TEMPERATURE
CONV CONVECTOR MBH THOUSAND Btu PER HOUR TF TRANSFER FAN
CT COOLING TOWER MC MECHANICAL CONTRACTOR TRANS TRANSITION
CU CONDENSING UNIT MCA MINIMUM CIRCUIT AMPS TYP TYPICAL
CUH CABINEf UNIT HEATER MCC MOTOR CONTROL CENTER UH UNIT HEATER
CUV CLASSROOM UNIT VENTILATOR MFR MANUFACTURER UON UNLESS OTHERWISE NOTED
CW CLOCKWISE MIN MINIMUM UV UNIT VENTILATOR
CWP CONDENSER WATER PUMP MISC MISCELLANEOUS V VOLTS
DC DIRECT CURRENT MTD MOUNTED VAV VARIABLE AIR VOLUME
DED DEDICATED CIRCUIT MV MEDIUM VOLTAGE VB VACUUM BREAKER
DS DISCONNECT SWITCH NA NOT APPLICABLE VERT VERTICAL
DWG DRAWING NEC NATIONAL ELECTRIC CODE VF VENTILATION FAN
EA EACH NIC NOT IN CONTRACT VFD VARIABLE FREQUENCY DRIVE
EC ELECTRICAL CONTRACTOR NL NON-LINEAR W WIRE, WATT
EF EXHAUST FAN NOM NOMINAL WP WEATHERPROOF
EFF EFFICIENCY NTS NOT TO SCALE W/ WITH
EL ELEVATION OD OUTSIDE DIAMETER, OVERFLOW DRAIN W/0 WITHOUT
ETR EXISTING TO REMAIN
POWER I DENTITY
SYM BO LS
� SINGLE CONVENIENCE RECEPTACLE
� DUPLEX CONVENIENCE RECEPTACLE. 20A 125V. WALL
MOUNT DEVICE
� DOUBLE DUPLEX CONVENIENCE RECEPTACLE.
� SINGLE CONVENIENCE RECEPTACLE ON
EMERGENCY/STANDBY CIRCUIT
� DUPLEX CONVENIENCE RECEPTACLE ON
EMERGENCY/STANDBY CIRCUIT
� DOUBLE DUPLEX CONVENIENCE RECEPTACLE ON
EMERGENCY/STANDBY CIRCUIT
� SPECIAL RECEPTACLE
a CLOCK HANGER OUTLET RECESSED MOUNTED 8'-0" AFF
� OR 8" BELOW CEILING AS INDICATED
� MULTI-OUTLET ASSEMBLY
� MULTI-OUTLET ASSEMBLY
� FLOOR DUPLEX CONVENIENCE RECEPTACLE.
� FLUSH MOUNT FLOOR BOX, ADJUSTABLE, WITH BOTH
POWER AND VOICE/DATA RECEPTACLES
Q JUNCTION BOX
� MOTOR
� PUSH-BUTTON
� ON/OFF PUSH-BUTTON STATION
.
aTHREE FUNCTION PUSH-BUTTON SWITCH
� (UP/DOWN/STOP)
$,� MOTOR STARTER SWITCH
� TOGGLE DISCONNECT SWITCH
�
THERMAL MOTOR SWITCH WITH HANDLE GUARD AND
PADLOCK CAPABILITY, "P"-INDICATES PILOT LIGHT
�P
� DISCONNECT SWITCH, UNFUSED TYPE
� DISCONNECT SWITCH, FUSED TYPE
� ENCLOSED CIRCUIT BREAKER
❑� MAGNETIC CONTACTOR
� MAGNETIC MOTOR STARTER
� COMBINATION MAGNETIC STARTER AND DISCONNECT
SWITCH
.- PHASE, NEUTRAL, GROUND
; PHASE, PHASE, NEUTRAL, GROUND
= PHASE, PHASE, PHASE, NEUTRAL, GROUND
.
- PHASE, PHASE, NEUTRAL, NEUTRAL, GROUND
.
: PHASE, PHASE, GROUND
= PHASE, PHASE, PHASE, GROUND
.-
� HOMERUN
PHASE, NEUTRAL, GROUND, HOMERUN
• GROUND
♦ CONNECTION
GENERAL ELECTRICAL NOTES
A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE
APPROXIMATE. ALL LOCATIONS SHALL BE FIELD VERIFIED.
B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL
ELECTRICAL CODE - LATEST EDITION ADOPTED BY INDIANA, THE
INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL/MUNICIPAL CODES,
AND THE AUTHORITY HAVING JURISDICTION.
C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR
VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT LESS
THAN 12" IN LENGTH, NOR GREATER THAN 36" IN LENGTH.
D. ALL CONDUIT PENEfRATIONS SHALL BE SEALED WITH APPROPRIATE
CONDUIT SEALING MATERIAL.
E. ALL CABLE SIZES SHALL UTILIZE COPPER CONDUCTORS.
FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN
ROUTING CONDUIT. ALL CONDUITS CROSSING EXPANSION JOINTS
SHALL BE INSTALLED WITH EXPANSION FITTINGS. EXPANSION FITTINGS
SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND
MANUFACTURER'S WRITTEN RECOMMENDATIONS.
FEEDERS FROM PANEL BOARDS BACK TO MAIN SWITCHBOARD, BETWEEN
AUTO TRANSFER SWITCHES AND THEIR SOURCES/LOADS, BETWEEN
DRY-TRANSFORMERS AND THEIR SOURCES/LOADS. ARE NOT INDICATED
ON THE FLOOR PLAN DRAWINGS. FEEDERS ARE PART OF THE WORK,
AND SHALL BE SIZED AS INDICATED ON THE ONE LINE DIAGRAM.
CABLE TRAY IS SHOWN ON THE PLANS. IF PORTIONS OF CABLE TRAY
CANNOT BE INSTALLED DUE TO CONFLICT WITH STRUCTURE OR OTHER
EQUIPMENT, THE CONTRACTOR SHALL PROVIDE (2) 4" C. WITH
INSULATED BUSHINGS THAT OVERLAP 1" INTO THE TRAY TO AVOID
CONFLICTS IN THESE LOCATIONS.
HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN
ON THE CONTRACT DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME
RUNS MAY BE COMBINED AT THE CONTRACTOR'S DISCRETION NOT
GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL CONDUCTORS,
AND A GROUNDING CONDUCTOR.
EACH SINGLE PHASE BRANCH CONDUCTOR SHALL HAVE A DEDICATED
NEUTRAL BACK TO THE PANEL.
CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL
USE LINK-SEALS.
WHERE LOW VOLTAGE (CONTROL) CABLING IS ALLOWED TO BE
INSTALLED WITHOUT A RACEWAY, IT SHALL BE SUPPORTED PER
SECTION 260523 NOT EXCEEDING INTERVALS OF 48 INCHES, AND NOT
MORE THAN 6 INCHES FROM CABINETS, BOXES, FITTINGS, OUTLETS,
RACKS, FRAMES AND TERMINALS.
NOTATION DE IGNATOR
GENERAL NOTES: NOTES THAT APPLY EQUALLY TO ALL DISCIPLINES
WITHIN THE DRAWING SET.
GENERAL ELECTRICAL NOTES THAT APPLY EQUALLY TO ALL SHEETS WITHIN
NOTES: THE DISCIPLINE.
GENERAL SHEET NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET ON
NOTES: WHICH THEY APPEAR.
SHEET KEYNOTES: NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET ON
WHICH THEY APPEAR AND USE A KEYNOTE INDICATOR
TO IDENTIFY ITEMS.
SUBSET DESIGNATORS
G-000 GENERAL
A-000 ARCHITECTURAL
F-000 FIRE PROTECTION
P-000 PLUMBING
M-000 MECHANICAL
E-000 ELECTRICAL
T-000 TELECOMMUNICATION
SHEETTYPE DESIGNATORS
E-000 GENERAL (SYMBOLS, ABBREVIATIONS, NOTES)
E-100 PLANS (DEMOLITION, SITE, FOUNDATION)
E-200 PLANS (POWER)
E-300 PLANS (LIGHTING)
E-400 LARGE SCALE VIEWS (PLANS, SECTIONS)
E-500 DETAILS
E-600 SCHEDULES
E-700 SHORT SPECIFICATIONS
E-800 DIAGRAMS (CONTROLS, RISERS, ONE-LINES)
E-900 3D REPRESENTATIONS (ISOMETRICS)
REFERENCE SYM BOLS
SECTION INDICATOR: REFERENCE SECTION LOCATION THROUGH AN AREA FOR KEYNOTE INDICATOR: REFERENCE SHEET KEYNOTE LOCATION FOR ADDITIONAL
ADDITIONAL INFORMATION. INFORMATION.
SECTION LOCATION BEYOND AREA KEYNOTE INDICATORS
IN DRAWING MODULE EXTENSION NUMERICAL CHARACTER
PLAN RELATES TO ITEM
A1 POINT LEADER 1 1 1
E-301
AREA LEADER
SECTION LOCATION AT SUBSET SHEET LINE LEADER
DETAIL INDICATOR: REFERENCE DETAIL LOCATION FOR ADDITIONAL DRAWING BLOCK REFERENCE DRAWING MODULE LOCATION FOR
INFORMATION. TITLE INDICATOR: ADDITIONAL INFORMATION.
LARGE SCALE VIEW LOCATION DETAIL LOCATION IN DRAWING MODULE LOCATION
IN DRAWING MODULE DRAWING MODULE (IDENTIFYING LOWER LEFT OF MULTIPLE MODULES)
� � ^ � aL
A1 A1 � DRAWING BLOCK TITLE
E-401 I E-501 � �� SCALE: �/s" _ �'-o" 0 4' s' �s'
�_I `�
NUMERIC SCALE GRAPHIC SCALE NORTH ARROW
LARGE SCALE VIEW LOCATION DEfAIL LOCATION AT
AT SUBSET SHEEf SUBSEf SHEEf
MATCH LINE REFERENCE SHEEf LOCATION FOR ADDITIONAL REVISION INDICATOR: REFERENCE TITLE BLOCK LOCATION FOR ADDITIONAL
INDICATOR: INFORMATION. INFORMATION.
FLOOR PLAN OVERLAP B�OND AREA REVISION INDICATOR
� EXTENSION n
SEE E-102 �
� �� �
REFER TO ADDITIONAL PLAN
SHEEf FOR CONTINUATION
REVISION CLOUD
LIGHTING INDICATOR: REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
A "A" = FIXTURE TYPE, REFER TO FIXTURE SCHEDULE,
a� "2" = CIRCUIT NUMBER, "a" = SWITCH IDENTIFICATION
J
�
•
J
■1
�
■1
J
J
Owner:
CARMEL THEATER
DEVELOPMENT COMPANY
117ll North Pennsylvania Street, Suite 200
Carmel, Indiana 46032
317.573-6050
Architect:
. � rt �,
PEDCOR DESIGN GROUP
Architecture / Project Management:
355 City Center Drive
Carmel, Indiana 46032
317.705.7979 (phone)
317.705.7980 (fax)
Engineer:
L'AC UI S
CONSULTING ENGINEERS
9229 DELEGATES ROW, SUITE 550
INDIANAPOLIS, IN 46240
317.706.2075
WWW.LACQUIS.COM
�� -°{�r���+ '
� �.
7-C-4
E.C.
OFFICE
BLDG.7-C-2
PARKING 7- -9
GARAGE
7-C-3
— — — —
7-C-11
KEY PLAN
sc��� �s
PLAN N�RTH
Project:
COPYRIGHT & OWNERSHIP OF DOCUMENTS
THIS DOCUMENT IS AN INSTRUMENT OF SERVICES AND IS THE
SOLE PROPERTY OF THE ARCHITECT AND PEDCOR DESIGN GROUP.
ALL INFORMATION CONTAINED HEREIN IS CONFIDENTIAL, ITS
SUBMISSION AND DISTRIBUTION TO OTHER PARTIES IS NOT TO BE
CONSTRUED AS PUBLICATIDN IN DEROGATION OF COMMON LAW
COPYRIGHT,INTELLECTUAL PROPERTY RIGHTS OR OTHER
RESERVED RIGHTS, ALL INFORMATION CONTAINED HEREIN
CONSTITUTES THE ORIGINAL AND UNPUBLISHED WORK OF THE
ARCHITECT, JAMES R, STUTZMAN, AND PEDCOR DESIGN GRDUP, LLC,
NO PART OR WHOLE OF THIS DESIGN, THESE DRAWINGS, OR THE
RESULTING BUILDING OR BUILDINGS, OR PORTIONS OF THE
RESULTING BUILDING OR BUILDINGS MAY BE DUPLICATED, COPIED,
EXHIBITED,PHOTOGRAPHED,PUBLISHED,MODIFIED OR OTHERWISE
DISTRIBUTED IN ANY WAY WITHOUT THE SPECIFIC AND PRIOR
WRITTEN CONSENT OF THE ARCHITECT, JAMES R, STUTZMAN AND
PEDCOR DESIGN GROUP, LLC, c COPYRIGHT 2006, 2007, 2008,
2009 JAMES R, STUTZMAN, AIA, INDIANAPOLIS,
BID PACKAGE N0. 3
CONSTRUCTION ISSUE SET
Print Date Sheet Issue Date
07/22/10 04/01 /10
Drawn By Checked By
MAR PCB
Last Revision Date:
O
O
O
O
O
O
Project Number:
Parcel 7C-1
Sheet Title:
ELECTRICAL SYMBOLS
AND ABBREVIATIONS
SHEET
Sheet Number: