HomeMy WebLinkAbout198_SVC-011-SYMBOLLEGEND (Const Issue 7-22-2010).PDF�
3
�a
�
�p Z
W
� W
� J
J
0
m
�
�
�
�
0
U
�
DEVICE IDENTIFICATION NUMBER
DEVICE DESIGNATION
ZONE DESIGNATION (IF APPLICABLE)
NOTE: SEE DEVICE DETAIL AND WIRE ROUTING SCHEDULE FOR DETAILS
SYMBOL DESCRIPTION
MICROPHONE LEVEL — GROUP A
M2 Microphone Receptacle — 2 circuit
MMP Monitor Microphone — 1 circuit
LINE LEVEL — GROUP B
PS 1 Powered Loudspeaker Receptacle— 1 circuit
Note: Provide one 120V 20A AC IG ckt adjacent
to each �PS 1 � device
Note: Switching of AC circuits for "PS1 � devices will
be controlled by SCC—supplied equipment within ARR
VIDEO AND R/F LEVEL — GROUP D
IRE Infrared Emitter Receptacle— 1 Circuit (loop—through)
Note: All °IR° receptacles shall have an adjacent 120V 15A
non—isolated Ground Circuit
Power consumption per �IR� device < 40w
MV Modulated Video System Reciever Receptacle
Note: All �MV� receptacles shall have an adjacent 120V 15A
non—isolated Ground Circuit
Power consumption per "MV" device < 80w
CV2 Closed Circut Video System Receptacle — 2 Ckt
Note: All �CV2� receptacles shall have an adjacent 120V 15A
non—isolated Ground Circuit
Power consumption per "MV" device < 80w
CV4 Closed Circut �deo System Receptacle — 4 Ckt
Note: All �CV4� receptacles shall have an adjacent 120V 15A
non—isolated Ground Circuit
Power consumption per "MV" device < 80w
INTERCOM LEVEL — GROUP E
H4 Intercom Receptacle— 4 circuit
HM House Manager's Panel
SOUND SYSTEM LOUDSPEAKER LEVEL — GROUP F
S 1 Sound System Loudspeaker Receptacle— 1 connector
2 circuit
S2 Sound System Loudspeaker Receptacle— 2 connector
4 circuit
S4 Sound System Loudspeaker Receptacle— 4 connector
8 circuit
UBS Under—Balcony Loudspeaker— 8� Recessed Mount
70.7 VOLT COMMUNICATION SYSTEM LOUDSPEAKER LEVEL — GROUP G
SCA Monitor/Page Speaker (70V)— 8n Recessed
#—(indicates paging zone) Mount
Electrical Enclosure: AMK Innovations BC8-7
SCB Monitor/Page Speaker (70V)— 8� Surface Ceiling
#—(indicates paging zone) Mount
Electrical Enclosure: Atlas Sound SE175-4
SSW Monitor/Page Speaker (70V)— 8" Surface Wall
#—(indicates paging zone) Mount
Electrical Enclosure: Atlas Sound SE175-4
SSA Monitor/Page Speaker Receptacle (70V)
#—(indicates paging zone)
V Monitor/Paging Volume Control (70V)
VC Monitor/Paging Volume Control (70V) w/Paging
Disable Switch
NOTE: ALL DEVICES IN THIS CATEGORY ARE TO BE LOOPED THROUGH
DEVICES IN THE SAME ZONE, THEN TO COMMUNICATIONS RACK ROOM.
SYMBOL DESCRIPTION
SOUND & COMMUNICATION SYSTEM MULTIPLE LEVEL PANELS — VARIOUS
TE: SEE DEVICE DETAIL AND WIRE ROUTING SCHEDULE FOR PANEL DETAILS
R##
Sound & Communication Combination Panel
Recording System Microphone Input Panel
SYMBOL DESCRIPTION
SOUND & COMMUNICATION SYSTEM A—C POWER RECEPTACLES
SHOWN FOR REFERENCE ONLY — ALL DETAILS PER ELECTRICAL SPEC
L/50q A—C NEMA L5-20 Duplex 1 ckt, 20A, Receptacle—
IG S&C Isolated Ground
Type L/ Surface Mounted Adjacent to an S&C Device
Type M/ On Self—Powered Loudspeaker Panel
A—C QUAD Receptacle— 1 ckt, 20A S&C Isolated Ground
Type A/ Surface Mounted adjacent to an S&C Device
Type B/ Flush Mounted adjacent to an S&C Device
A—C DUPLEX Receptacle— 1 ckt, 20A S&C Isolated Ground
Type C/ Surface Mounted adjacent to an S&C Device
Type D/ Flush Mounted adjacent to an S&C Device
Type E/ Surface Mounted with Waterproof Cover
Type F/ Recessed adjacent to an S&C Device in Floor Box
A—C DUPLEX Receptacle— 1 ckt. Standard Safety Ground
Note: These ckts may originate from any Power Panel
Note: See "MVr »CV2 ; �CV4n & �IRE;
above for power requirements
Type G/ Surface Mounted adjacent to an S&C Device
Type H/ Flush Mounted adjacent to an S&C Device
Type I/ Recessed for use with LCD TVs
JUNCTION BOXES
Type J/ 20A IG Circuit in Junction Box
adjacent to S&C Device or Rack
Type K/ 20A Std Circuit in Junction Box
adjacent to S&C Device or Rack
DIVERSITY DESIGNATION
100q [20A Typical Load]
50� 10A Typical Load]
25q 5A Typical Load
10q 2A Typical Load
TYPE DESCRIPTION MFG / CAT No. O.D. (in.) AREA (in.) NOTES
MICROPHONE LEVEL — GROUP A
A 1 1x24 AWG twisted quad. copper strand shield Mogami 2820 0.197 0.030 (1 ch.)
(16x37 stranding)
LINE LEVEL — GROUP B
B 1 1 x22 AWG twisted quad. mylar shield Belden 1800B 0.135 0.014 (1 ch.)
(7x30 strand�ng)
SPARE — SOUND SYSTEM — GROUP C
Empty conduit only.
VIDEO & RF LEVEL — GROUP D
D 1 4x24 AWG twisted pair skew—free UTP cable Belden 7989R 0.365 0.060 RF Video Receiver System Line (MAN)
D2 75 ohm Precision Video Coaxial Cable Belden 9116 0.270 0.057 Production Video Line (CCTV)
(18 AWG solid center cond. &
double copper braided shield)
D3 75 ohm RG-6/U Type Low Belden 1694A 0.275 0.059 Word Clock / MADI / HD—SDI
Loss Digital Coax�al Cable
(18 AWG and Copper Braid Shield)
D5 50 ohm RG-58A/U Type B'cast Coaxial Cable Belden 9311 0.195 0.030 Infrared Emitter (RF signal only)
(20 AWG stranded cntr. cond.(19x32)
& mylar w/ copper braid shield)
D6 50 ohm RG-8/U Type B'cast Coaxial Cable Belden 9914 0.405 0.129 RF Microphone System Antenna
(10 AWG solid center cond. &
mylar w/ copper braid shield)
INTERCOM LEVEL & DC CONTROL — GROUP E
E4 4x20 AWG twisted .pair, mylar shield Belden 1815A 0.384 0.116 Production Intercom (4 ch.)
(7x30 stranding)
E20 4x22 AWG twisted pair, unshielded Belden 9746 .281 0.062 Sequential Power System Voltage
chrome PVC 'acket 7x30 strandin
J � 9)
E22 2x22 AWG twisted pair, unshielded Belden 9744 .244 0.047 Sequential Power System Switching
chrome PVC 'acket 7x30 strandin Control S stem Volta e
J � 9) Y 9
LOW VOLT/IMPEDANCE LOUDSPEAKER LEVEL — GROUP F
F1 12 AWG THHN—THWN stranded copper TBD 0.13 0.013 Low Volt/Impedance Loudspeaker 1 cond.)
bu�ld�n w�re, one conductor (Used �n pa�rs only — DO NOT IST)
65x30 stranding)
70.7 VOLT LOUDSPEAKER LEVEL — GROUP G
G 1 2x 18 AWG multiconductor cable Alpha 1897 0.2 0.031 70.7 Volt Communication System
(16x30 stranding) Loudspeaker (1 ckt.)
G2 3x18 AWG multiconductor cable Alpha 1898 0.21 0.035 70.7 Volt Volume Control (1 ckt.)
(16x30 stranding)
SPARE — COMMUNICATION SYSTEM — GROUP H
Empty conduit only
FIBER OPTIC LEVEL — GROUP J
J 1 Fiber Optic Cable Multi—Mode Belden PTD6002 .184 0.051 Digital Audio
J2 Fiber Optic Cable Single—Mode Belden M9D042 .255 0.051 Digital Audio
J3 4x24 AWG twisted pair, category 6 Belden 1872A 0.200 0.031 Digital Audio
ALLOWABLE CONDUIT TYPES:
1. ELECTRIC METALLIC CONDUIT (EMT)
2. GALVANIZED RIGID STEEL CONDUIT (GRS)
3. PVC—COATED RIGID STEEL CONDUIT IN CONCRETE SLAB
NOTE: PVC CONDUIT SHALL NOT BE ALLOWED FOR ANY SOUND & COMMUNICATION SYSTEMS WIRING. NO EXCEPTIONS !
MINIMUM SEPARATION REQUIRED BETWEEN SOUND & COMMUNICATION SYSTEM CONDUIT SIGNAL LEVELS
SPARE — INTERCOM SOUND SYSTM 70.7 VOLT SPARE — FIBER ISOLATED
WIRING MICROPHONE LINE SOUND R/F LEVEL & LOUDSPEAKER LOUDSPEAKER COMM. OPTIC GROUND
SIGNAL LEVEL LEVEL LEVEL SYSTEM LEVEL DC CONTROL LEVEL LEVEL SYSTEM LEVEL A—C POWER
GROUP — A GROUP — B GROUP — C GROUP — D GROUP — E GROUP — F GROUP — G GROUP — H GROUP — J LEVEL
MICROPHONE LEVEL
GROUP — A ADJACENT 6" 6" 9" 12" 15" 18" 18" ADJACENT 24"
LINE LEVEL
GROUP — B 6" ADJACENT ADJACENT 3" 6" 9" 12" 12" ADJACENT 18"
SPARE — SOUND SYSTEM
GROUP — C 6" ADJACENT ADJACENT 3" 6" 9" 12" 12" ADJACENT 18"
R/F LEVEL
GROUP — D 9" 3" 3" ADJACENT 3" 6" 9" 9" ADJACENT 15"
INTERCOM LEVEL &
DC CONTROL 12" 6" 6" 3" ADJACENT 3" 6" 6" ADJACENT 12"
GROUP — E
SOUND SYSTEM
LOUDSPEAKER LEVEL 15" 9" 9" 6" 3" ADJACENT 3" 3" ADJACENT 9"
GROUP — F
70.7 VOLT
LOUDSPEAKER LEVEL 18" 12" 12" 9" 6" 3" ADJACENT ADJACENT ADJACENT 6"
GROUP — G
SPARE — COMM. SYSTEM
GROUP — H 18" 12" 12" 9" 6" 3" ADJACENT ADJACENT ADJACENT 6"
FIBER OPTIC LEVEL
GROUP — J ADJACENT ADJACENT ADJACENT ADJACENT ADJACENT ADJACENT ADJACENT ADJACENT ADJACENT ADJACENT
ISOLATED GROUND
A—C POWER LEVEL 24" 18" 18" 15" 12" 9" 6" 6" ADJACENT ADJACENT
MINIMUM SEPARATION REQUIRED BETWEEN SOUND & COMMUNICATION SYSTEM CONDUIT AND ALL OTHER CONDUIT
— PRODUCTION LIGHTING — --------------- AC POWER ---------------
WIRING CONDUIT 120 VOLT 277 VOLT DIMMED ALL 277/480 VOLT
SIGNAL LEVEL TYPE COMPOSITE SIGNAL / BRANCH BRANCH LIGHTING MOTOR FEEDER
VIDEO TTL VIDEO CIRCUITS CIRCUITS CIRCUITS CIRCUITS CIRCUITS
EMT/IMC/GRSC 9" 12" 36" 36" 36" 36" 36"
MICROPHONE LEVEL
GROUP — A
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH MICROPHONE LEVEL WIRING! --------
EMT/IMC/GRSC 3" 6" 24" 24" 24" 24" 24"
LINE LEVEL
GROUP — B
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH LINE LEVEL WIRING! --------
EMT/IMC/GRSC 3" 6" 24" 24" 24" 24" 24"
SPARE — SOUND SYSTEM
GROUP — C
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE AS MICROPHONE LEVEL SPARE CONDUIT! --------
EMT/IMC/GRSC ADJACENT 3" 15" 15" 15" 15" 15"
RF LEVEL
GROUP — D
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH RF LEVEL WIRING! --------
ROUTING
EMT/IMC/GRSC 3" ADJACENT 12" 12" 12" 12" 12"
INTERCOM LEVEL &
DC CONTROL
GROUP — E
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH INTERCOM & DC CONTROL WIRING! --------
EMT/IMC/GRSC 6" 3" 12" 12" 12" 12" 12"
LOW VOLT LOUDSPEAKER
GROUP — F PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH LOW VOLT LOUDSPEAKER WIRING! --------
EMT/IMC/GRSC 9" 6" 9" 12" 12" 12" 12"
70.7 VOLT LOUDSPEAKER
GROUP — G
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH 70.7 VOLT LOUDSPEAKER WIRING! --------
EMT/IMC/GRSC 15" 12" ADJACENT ADJACENT 12" 12" 12"
ISO GND AC POWER
PVC IN SLAB -------- PVC CONDUIT IS NOT ACCEPTABLE FOR USE WITH ISO GROUND WIRING! --------
ARTEC
DESIGN AND PLANNING SERVICES FOR PERFORMING ARTS FACILITIES
114 WEST 2GTH STREET 12TH FLOOR NEW YORK NEW YORK USA 10001-6812
TEL: +1(212) 242 0120 FAX: +1(212) 645 8635 www.ArtecConsultants.com
i��•����
FOR INFORMATI4N
ONLY. REFER TO
ELECTRICAL AND
ARCH ITECTU RAL
DRAWI NGS
DATE:
REVISIONS:
DRAWN BY: SDP
SCALE: NTS
PROJECT NUMBER: 3796
oATE: 11 J U N 10
CHECKED BY: PSP
PRo�ECT: CARMEL THEATER
CARMEL, IN
No.
TiT�E: SOUND & VIDEO COMMUNICATION
DEVICE LEGEND AND
CONDUIT SEPARATION
DRAWING NUMBER:
SVC-011