HomeMy WebLinkAboutStructural0 3 4 1. 2. 3. 4. 5. 6. 7. 8. 9. EXISTING CONSTRUCTION The Contractor shall field verify the dimensions, elevations, etc. necessary for the proper construction and alignment of the new portions of the work to the existing work. The Contractor shall make all necessary measurements for fabrication and erection of the structural members. Any discrepancy shall be brought to the attention of the Structural Engineer of Record (SER). Before proceeding with any work within the existing facility, the Contractor shall familiarize himself with existing structural and other conditions. Any shoring shown or noted on the Plans is a partial and schematic representation of that required. It shall be the Contractor's responsibility to provide al) necessary bracing, shoring, and other safeguards to maintain all parts of the work in a safe condition during the progress of demolition and construction, and to protect from damage those portions of the existing work which are to remain. Shoring shall remain in place until the structural work is complete, has been inspected by the Testing Agency, and is certified to be in substantial compliance with the Contract Documents. When required by the Specifications or by Plan Note, the Contractor shall submit for the SER's review, a"Proposed Shoring Plan", induding, but not limited to: plans, sections, details, notes, description of proposed sequence of work, and calculations prepared by, or under the supervision of a Specialty Structural Engineer (SSE). The SSE shall be registered in the State where the project is located. Welding to and within an existing facility presents potential hazards including: A. Fire Nazard-Due to the existing construction and building contents. B. Structural Liquifaction-Due to welding across the full section of the structural members. Recommendations to prevent these hazards include: A. Fire Hazard-Protect existing combustibles prior to welding. Keep a separate watchman and several fire extinguishers on hand. B. Structural Liquifaction-weld in small increments. Allow welds to harden before continuing to the next increment. C. Do not leave the site until satisfied that no fire hazard exists. D. Preference should be given to the use of beam clamps, mechanical fasteners, or bolted connections in lieu of welding within existing facilities, whenever possible. Do not field-drill existing structural members without the written permission of the SER. COORDINATION WIT�-I OTHER TRADES The Contractor shall coordinate and check all dimensions relating to Architec- tural finishes, mechanical equipment and openings, elevator shafts and overrides, etc. and notify the Architect/Engineer of any discrepancies before proceeding with any work in the area under question. The Structural Drawings shall be used in conjunction with the Drawings of all other disciplines and the Specifications. The Contractor shall verify the requirements of other trades as to sleeves, chases, hangers, inserts, anchors, holes, and other items to be placed or set in the Structura) Work. There shall be no vertical or horizontal sleeves set, or holes cut or drilled in any beam or column unless it is shown on the Structural Drawings or approved in writing by the SER. Mechanical and electrical openings through supported slabs and walls, 8" diameter, or larger not shown on the Structura) Drawings must be approved by the SER. Openings less than 8" diameter shall have at least 1'-0" clear between openings, unless approved in writing by the SER. Verify locations and dimensions of inechanical and electrica) openings through supported slabs and walls shown on the Structural Drawings with the Mechanical and Electrical Contractors. Do not install conduit in supported slabs, slabs on grade, or concrete walls unless ex licitl shown or noted on the Structural Drawin s. P Y 9 Do not suspend any items, such as ductwork, mechanical or electrical fixtures, ceilings, etc. from steel roof deck or wood roof sheathing. The Mechanical Contractor shall verify that mechanical units supported by steel framing are capable of spanning the distance between the supporting members indicated on the Structural Drawings. The Mechanical Contractor shall supply additional support framing as required. If the Drawings and Specifications are in conflict, the most stringent restrictions and requirements shall govern. GE�EI�:AL NOTES 1. The Contractor shall be responsible for complying with all safety precautions and regulations during the work. The SER will not advise on, nor issue direction as to safety precautions and programs. 2. The Structural Drawings herein represent the finished structure. The Contractor shall provide all temporary guying and bracing required to erect and hold the structure in proper alignment until all Structural Work and connections have been completed. The investigation, design, safety, adequacy and inspection of the bracing, shoring, temporary supports, etc. is the sole responsibility of the Contractor. 3. The SER shall not be responsible for the methods, techniques, and sequences of procedures to perform the Work. The supervision of the Work is the sole responsibility of the Contractor. 4. The Drawings indicate general and typical details of construction. Where conditions are not specifically shown, similar details of construction shall be used, subject to approval of the SER. 5. All structural systems which are to be composed of components to be field erected shall be supervised by the Supplier during manufacturing, delivery, handling, storage, and erection in accordance with the Supplier's instructions and requirements. 6. Loading applied to the structure during the process of construction shal) not exceed the safe load-carrying capacity of the structural members. The live loads used in the design of this structure are indicated in the "Design Criteria Notes". Do not apply any construction loads until structural framing is properly connected together and until all permanent bracing is in place. 7. All ASTM and other referenced standards and codes are for the latest editions of these publications, unless noted otherwise. 8. Shop Drawings and other items shall be submitted to the SER for review prior to fabrication. All shop drawings shall be reviewed by the Contractor before submittal. The SER's review is to be for conformance with the design concept and general compliance with the relevant Contract Documents. The SER's review does not relieve the Contractor of the sole responsibility to review, check, and coordinate the Shop Drawings prior to submission. The Contractor remains solely responsible for errors and omissions associated with the preparation of Shop Drawings as they pertain to member sizes, details, dimensions, etc. 9. Submit Shop Drawings in the form of blueline/blackline prints (min. 2 sets/ max. 5 sets), unless the use of electronic submittals has been addressed in the Specifications or approved by the SER in writing. In no case shall reproductions of the Contract Documents be used as Shop Drawings. As a minimum, submit the following items for review: A. Concrete Mix Design(s). B. Reinforcing Steel Shop Drawings. C. Structural Steel Shop Drawings. D. Steel Joist Shop Drawings. E. Steel Deck Shop Drawings. F. Pre-Engineering Cold-Formed Steel Truss Systems. G. Cold-Formed Steel Framing Systems. 10. Resubmitted Shop Drawings: Resubmitted shop drawings are reviewed only for responses to comments made in the previous submittal. 11. When calculations are included in the submittal for components of Work designed and certified by a Specialty Structural Engineer (SSE), the review by the Structural Engineer of Record (SER� shall be for conformance with the relevant Contract Documents. The SER's review does not relieve the SSE from responsibility for the design of their system(s) and the coordination with the elements of the structure under the certification of the SER, or other SSE's. The SER's review does not constitute a warrant of the accuracy or completeness of the SSE's design. 12. Contractors shall visit the site prior to bid to ascertain conditions which may adversely affect the Work or cost thereof. 13. No structural member may be cut, notched, or otherwise reduced in strength without written direction from the SER. 14. When modifications are proposed to structural elements under the design and certification of a SSE, written authorization by the SSE must be obtained and submitted to the SER for review prior to performing the proposed modifications. 1 7 3 DESIGN CRITERIA DESIGN STANDARDS: The intended design standards are as follows: General The 2014 Indiana Code (2012 International Building Code [IBC] with Indiana Amendments) Concrete ACI 318 Masonry TMS 402 Steel AISC Manual, Allowable Stress Design (ASD) Steel Joists Steel Joist Institute (SJI) Steel Deck Steel Deck Institute (SDI) Cold-Formed Metal AISI-ASD All referenced standards and codes, as well as ASTM numbers, are for the editions of these publications referenced in the Building Code listed above, unless noted otherwise. DEAD �OADS: Gravity dead loads used in the design of the structure are as computed for the materials of construction incorporated into the building, including but not limited to walls, floors, roofs, ceilings, stairways, fixed partitions, finishes, cladding, and other similar architectural and structural items, as well as mechanical, electrical and plumbing equipment and fixtures, and material handling and fixed service equipment, including the weight of cranes. LIVE LOADS: Gravity live loads used in the design of the structure meet, or exceed the following table (IBC 2012, 1607.1): OCCUPANCY OR USE UNIFORM (PSF) CONCENTRATED (LB) A. Equipment Platform 125 -- B. Stairs & Exits 1. Typical 100 300 on A=4 sq. in. 4. COLLATERAL LOAD: Unless otherwise noted, a minimum uniform collateral load of 10 PSF has been used to account for ductwork, ceilings, sprinklers, lighting, etc. The collatera) load is in addition to the weight of inechanical unites, larger piping (greater than 4" diameter) and suspended fixtures or equipment that have been specifically accounted for in the design. 5. CONCENTRATED �OADS: All single panel points of the lower chord of exposed roof trusses or any point along the primary structural members supporting roofs over all other occupancies shall be capable of carrying safely a suspended concentrated load of not less than 200 LBS in addition to dead load, unless noted. 6. HANDRAIL AND GUARDS: A. Handrail Assemblies and Guards 50 PLF applied in any direction 200 LB concentrated load applied in any direction (non- concurrent with 50 PLF load) B. Components, Intermediate Rails, 50 LBS horizontally applied Balusters, Fillers, etc. normal load on an area not to exceed 1 SF, not superimposed with those of handrail assem's. 7. ROOF �IVE/SNOW LOADS: Gravity live loads used in the design of the roof structure meet or exceed the following table: A. Snow Load Ground Snow Load, Pg 20 PSF Flat Roof Snow Load, Pf 22 PSF Snow Exposure Factor, Ce 1.0 Risk Category (IBC Table 1604.5) III Snow Importance Factor, Is 1.1 Thermal Factor, Ct 1.0 B. Minimum Roof Live Load 20 PSF C. Overhanging Eaves & Projections 30 PSF 1. Sloped roof snow loads calculated in accordance with Sec. 7.4, ASCE 7. 2. Unbalanced roof snow loads calculated in accordance with Sec. 7.6, ASCE 7. Structural Specialty Engineers (SSE) must consider unbalanced snow loads in the design of pre-engineered trusses, frames, skylights, curtain walls, cold-formed stee) framing, canopies, etc. 3. Drift loads calculated in accordance with Section 7.7, ASCE 7. 8. LATERAL LOADS: Lateral loads were computed using the following criteria: A. Wind Load Ultimate Design Wind Speed, Vult 120 MPH Nominal Design Wind Speed, Vasd 93 MPH Wind Exposure Category B Risk Category (IBC Table 1604.5) III Internal Pressure Coefficient, GCpi ±0.18 B. Seismic Load Site Class C Risk Category (IBC Table 1604.5) III Seismic Importance Factor, le 1.25 Mapped Spectral Response Acceleration, Ss 0.147g Mapped Spectral Response Acceleration, S1 0.082g Design Spectral Response Acceleration, Sds 0.118g Design Spectral Response Acceleration, Sd1 0.093g Seismic Design Category, SDC B Response Modification Factor, R 3 Seismic Response Coefficient, Cs 0.0492 Analysis Procedure Equivalent Lateral Force Basic Seismic Force-Resisting System Steel Systems not Specifically Detailed for Seismic Resistance 9. SAFETY FACTORS: This structure has been designed with 'Safety Factors' in accordance with accepted principles of structural engineering. The fundamental nature of the 'Safety Factor' is to compensate for uncertainties in the design, fabrication, and erection of structural building components. It is intended that 'Safety Factors' be used such that the load-carrying capacity of the structure does not fall below the design load and that the building will perform under design load without distress. While the use of 'Safety Factors' implies some excess capacity beyond design load, such excess capacity cannot be adequately predicted and SHALL NOT BE RELIED UPON. 0 7 3. 4. 5. REINFORCED 11�IASONRY NOTES All construction of reinforced masonry walls to be in accordance with the Building Code Requirements for Concrete Masonry Structures (ACI 530) and Commentary. A) f'm = 2000 PSI B) Maximum height of masonry lift: 5'-0" C) Maximum height of grout lift: 5'-0" D) See the Specifications for additional masonry wall information. CONCRETE BLOCK: Minimum compressive test strength on the net cross- sectional area: 2800 PSI. MORTAR: Type S required. GROUT: ASTM C476, 2500 PSI with a slump of 8" min. and 10" max. REINFORCING: fy = 60000 PSI with a min. lap of 48 bar diameters. 0 2. Ki 4 5 7 : FOUNDATIONS Proofroll slab on grade areas with a medium-weight roller or other suitable equipment to check for pockets of soft material hidden beneath a thin crust of better soil. Any unsuitable materials thus exposed should be removed and replaced with compacted, engineered fill as outlined in the specifications. Proofrolling operations shall be monitored by the Geotechnical Testing Agency. All engineered fill beneath slabs and over footings should be compacted to a dry density of at least 93� of the Modified Proctor maximum dry density (ASTM D-1557). All fill which shall be stressed by foundation loads shall be approved granular materials compacted to a dry density of at least 95% (ASTM D-1557). Coordinate all fill and compaction operations with the Specifications and the Subsurface Investigation. Compaction shall be accomplished by placing fill in approximate 8" lifts and mechanically compacting each lift to at (east the specified minimum dry density. For large areas of fill, field density tests shall be performed for each 2,000 square feet of building area for each lift as necessary to insure adequate compaction is being achieved. Column footings and wall footings to bear on firm natural soils or well- compacted engineered fill with allowable bearing pressure of 2,500 PSF and 2,000 PSF for column and wall footings respectively. It is essential that the foundations be inspected to ensure that all loose, soft, or otherwise undesirable material (such as organics, existing uncontrolled fill, etc.) is removed and that the foundations will bear on satisfactory material. The Geotechnical Testing Agency shall inspect the subgrade and perform any necessary tests to ensure that the actual bearing capacities meet or exceed the design capacities. The Geotechnical Testing Agency shall verify the bearing capacity at each spread column footing and every 10 feet on center for strip footings prior to placement of concrete. Place footings the same day the excavation is performed. If this is not possible, the footings shall be adequately protected against any detrimental change in condition, such as from disturbance, rain, or freezing. It is the responsibility of the Contractor and each Sub-Contractor to verify the location of all utilities and services shown, or not shown; and establish safe working conditions before commencing work. The Contractor shall layout the entire building and field verify all dimensions prior to excavation. For information regarding subsurface conditions, refer to the Subsurface Investigation & Foundation Recommendation Report prepared by Alt & Witzig Engineering, Inc., A&W Project No. 151N0178. CONCRETE REINFORCING 1. Reinforcement, other than cold drawn wire for spirals and welded wire fabric, shall have deformed surfaces in accordance with ASTM A305. 2. Reinforcing steel shall conform to ASTM A615, Grade 60, unless noted. 3. Welded wire fabric shall conform to ASTM A185, unless noted. 4. Where hooks are indicated, provide standard hooks per ACI and CRSI for all bars unless other hook dimensions are shown on the plans or details. 5. Reinforcement in footings, walls and beams shall be continuous. Lap bars a minimum of 36 bar diameters, unless noted otherwise. 6. Reinforcement shall be supported and secured against displacement in accordance with the CRSI 'Manual of Standard Practice'. 7. Details of reinforcing steel fabrication and placement shall conform to ACI 315 'Details and Detailing of Concrete Reinforcement' and ACI 315R 'Manual of Engineering and Placing Drawings for Reinforced Concrete Structures', unless otherwise indicated. 8. Spread reinforcing steel around small openings and sleeves in slabs and walls, where possible, and where bar spacing will not exceed 1.5 times the normal spacing. Discontinue bars at all large openings where necessary, and provide an area of reinforcement, equal to the interrupted reinforcement, in full length bars, distributing one-half each side of the opening. Where shrinkage and temperature reinforcement is interrupted, add (2) �5 x opening dimension + 4' 0" on each side of the opening. Provide �5 x 4' 0" long diagonal bars in both faces, at each corner of openings larger than 12" in any direction. 9. Provide standees for the support of top reinforcement for footings, pile caps, and mat foundations. 10. Provide individual high chairs with support bars, as required for the support of top reinforcement for support slabs. Do not provide standees. 11. Provide snap-on plastic spacer wheels to maintain required cover for vertical wall reinforcement. 12. Where walls sit on column footings, provide dowels for the wall. Dowels shall be the same size and spacing as the vertical wall reinforcement, unless noted otherwise, with lap splices as shown on the applicable sections. Install dowels in the footing forms before concrete is placed. Do not stick dowels into footings after concrete is placed. 13. Field bending of reinforcing steel is prohibited, unless noted on the drawings. 14. Minimum concrete cover over reinforcing steel shall be as follows, unless noted otherwise on plan, section or note: MINIMUM COVER FOR RElNFORCEMENT MINIMUM COVER, IN SLABS AND JOISTS TOP & BOTfOM BARS FOR DRY CONDITIONS: � 11 BARS & SMALLER 3/" � 14 &� 18 BARS 1 12" FORMED CONCRETE SURFACES EXPOSED TO EARTN, WATER, OR WEATHER, AND OVER OR IN CONTACT WITN SEWAGE AND FOR BOTTOMS BEARING ON WORK MAT, OR SLABS SUPPORTING EARTH COVER: #5 BARS & SMALLER 1 %" �6 THROUGH �18 BARS 2" BEAMS & COLUMNS, FORMED FOR DRY CONDITIONS: STIRRUPS, SPIRALS & TIES 1 %" PRINCIPAL REINFORCEMENT 2" EXPOSED TO EARTH, WATER, SEWAGE, OR WEATHER: STIRRUPS & TIES 2" PRINCIPAL REINFORCEMENT 2 %" WA�LS FOR DRY CONDITIONS: � 11 BARS & SMALLER 3/" �14 & #18 BARS 1 y" FORMED CONCRETE SURFACES EXPOSED TO EARTH, WATER, SEWAGE, WEATNER, OR IN CONTACT WITH 2" GROUND FOOTINGS & BASE SLABS AT FORMED SURFACES & B0ITOMS BEARING ON 2» CONCRETE WORK MAT AT UNFORMED SURFACES & BOTfOMS IN CONTACT 3» WITH EARTH TOP OF FOOTINGS SAME AS SLABS OVER TOP OF PI�ES 2" 0 2. 3. 4 5. CAST IN PLACE CONCRETE Details of fabrication of reinforcement, handling, and placing of the concrete, construction of forms and placement of reinforcement not otherwise covered by the Plans and Specifications, shall comply with the ACI Code requirements of the latest revised date. Cold weather concreting shall be in accordance with ACI 306. Cold weather is defined as a period when for more than 3 successive days the average daily air temperature drops below 40F and stays below 50F. The Contractor shall maintain a copy of this publication on site. Not weather concreting shall be in accordance with ACI 305. Hot weather is defined as any combination of the following conditions that tends to impair the quality of the freshly mixed or hardened concrete: high ambient temperature, high concrete temperature, low relative humidity, wind speed, or solar radiation The Contractor shall maintain a copy of this publication on site. A certified Testing Agency shall be retained to perform industry standard testing including measurement of slump, air temperature, concrete cylinder testing, etc. to insure conformance with the Contract Documents. Submit reports to the Architect/Engineer. FINISHING OF SLABS: After screeding, bull floating and floating operations have been completed, apply final finish as indicated below, and as described in the Division 3 Cast In Place Concrete Specification of the Project Manual. A. Floor Slabs Trowel Finish B. Ramps, Stairs, & Sidewalks Broom Finish C. Surfaces to Receive Topping Slabs Float Finish D. Surfaces to receive thick-set mortar Float Finish beds or similar cementitious materials Sample Finishes: See the Specifications for sample and mockup requirements, if any. Floor Tolerances: See the Specifications for specified Ff and FI tolerances. Ff and FI testing shall be performed by the Testing Agency in accordance with ASTM E 1155. Results, including acceptance or rejection of the work will be provided to the Contractor and the Architect/Engineer within 48 hours after data collection. Remedies for out-of-tolerance work shall be in accordance with the Specifications. When approved by the SER, measurement of the gaps beneath a 10-foot straightedge may be used in lieu of Ff and FI testing. Approval must be obtained in writing prior to the beginning of concrete operations. 6. FINISHING OF FORMED SURFACES: Finish formed surfaces as indicated below, and as described in the Division 3 Cast In Place Concrete Specification of the Project Manual. A. Sides of Footings & Pile Caps Rough Form Finish B. Sides of Grade Beams Rough Form Finish C. Surfaces not exposed to public view Rough Form Finish D. Surfaces exposed to public view Smooth Form Finish 7. The Contractor shall consult with the Engineer before starting concrete work to establish a satisfactory placing schedule and to determine the location of construction joints so as to minimize the effects of shrinkage in the floor system. 8� Sawn or tooled control/contraction joints shall be provided in all slabs on grade. For a framed structure, joints shall be located on all column lines. If the column spacing exceeds 20'-0", provide intermediate joints. Exterior slabs, and interior slabs without columns shall have joints spaced a maximum of 12'-0" apart. Layout joints so that maximum aspect ratio (ratio of long side to short side) does not exceed 1.5. 9. Where vinyl composition tile, vinyl sheets goods, thin-set epoxy terrazzo, or other similar material is the specified finish floor material, the Contractor shall coordinate the locations of control/contraction and construction joints with the Finish Flooring Contractor. Submit a dimensioned plan showing joint locations and proposed sequence of floor pours. 10. Unless specifically noted on the Plans, composite and non-composite supported slabs on metal deck, and supported cast-in-place concrete slabs do not require sawn control joints. 11. Joints in slabs to receive a finish floor may remain unfilled, unless required by the Finish Flooring Contractor. All exposed slabs shall be filled with sealant as specified in Division 7, or as follows: All slabs in industrial, manufacturing, or warehouse applications subject to wheeled traffic shall be filled with specified epoxy resin sealant, all other joints shall be filled with specified elastomeric sealant. Defer filling of joints as long as possible, preferably a minimum of 4 to 6 weeks after the slab has been cured. Prior to filling, remove all debris from the slab joints, then fill in accordance with the manufacturer's recommendations. 12. Refer to the Architectural Drawings for locations and details of reveals (1" maximum depth) in exposed walls. 13. Refer to the Architectural Drawings for chamfer requirements for corners of concrete. Where not indicated, provide 4" chamfers on exposed corners of concrete except those abutting masonry. 14. Refer to the Architectural Drawings for exact locations and dimensions of recessed slabs, ramps, stairs, thickened slabs, etc. Slope slabs to drains where shown on the Architectural and Plumbing Drawings. 15. Sidewalks, stoops, aprons, drives, exterior retaining walls, and other site concrete are not indicated on the Structural Drawings. Refer to the Site/Civil and Architectural Drawings for locations, dimensions, elevations, jointing and finishing details. 1 2 POST-INSTALLED DOWELS & ANCI�OR BOLTS/RODS All reinforcing steel and threaded rod anchors to be installed in 2-part chemical anchoring system shall be treated as follows: A) Drill holes larger than bar or rod to be embedded. Coordinate hole diameter with Manufacturer's requirements. B) Holes must be cleaned and prepared in accordance with Manufac- turer's requirements. C) When reinforcing steel is encountered during drilling for installation of anchors; stop drilling, use a sensor to locate the reinforcing in the surrounding area and install anchor(s) as close as possible to the original location. Contact the Structural Engineer of Record for direction when the revised location is more than 2" from the original location, or when the original function of the anchorage is significantly altered. When in doubt, contact the SER for direction. D) Drill the hole to a depth as shown on the drawings with a minimum of 15 bar diameters. E) Use a 2-part adhesive anchoring system, Hilti HIT-HY 200, or approved equal. F) For anchorage into hollow substrate, use Hilti HIT-HY 70, or approved equal. G) Reinforcing steel dowels shall be ASTM A615, Grade 60, unless noted. N) Anchor rods shall be ISO 898 5.8 (Nilti NAS-E), unless noted. Provide finish as noted on the Drawings. If not noted, provide zinc-coated finish for interior applications. Provide stainless steel finish for exterior applications, unless noted. When column anchor bolts/rods have been omitted, or damaged by construction operations, the Contractor must obtain the written approval of the SER prior to repair and/or replacement. A) As a precaution, the affected column must be guyed and braced after repair for the balance of the erection period. B) As an alternate to guying and bracing, the Contractor may at his option, employ a Testing Agency to perform a tensile pull test to confirm the strength of the repaired or replaced anchor bolt/rod. The tensile proof load must exceed 1.33 x the design load of the original anchor without causing distress of the anchor bolt/rod or the surrounding concrete. Refer to the following table for the minimum proof loads: a" diameter: 11.6 kips 8" diameter: 16.0 kips 1" diameter: 20.9 kips Note: Values listed above are for ASTM F-1554, Grade 36 material. When higher grade or strength materials are specified, refer to the AISC Manual of Steel Construction for minimum allowable loads to be multiplied by 1.33. C} When affected anchor bolts/rods are part of a fixed moment- resisting column base, such as those in moment-resisting space frames, canopies, or fixed base installations, the repaired anchor bolts/rods must be proof-loaded, or the affected column footing and/or pier replaced in its entirety. D� When affected anchor bolts/rods are 1 Y" diameter or larger, the affected column footing and/or pier must be replaced in its entirety. E) When affected anchor bolts/rods are part of a braced frame, the affected column footing and/or pier must be replaced in its entirety. F) Prior to erection, the controlling Contractor must provide written notification to the Steel Erector if there has been a repair, replacement or modification of the anchor bolts/rods for that column. 1 2 3 ►, � CONCRETE MIX CLASSES FOOTINGS COMPRESSIVE STRENGTH 3000 PSI MAXIMUM WATER/CEMENT RATIO 0.58 AIR CONTENT 0-3 PERCENT WATER-REDUCING ADMIXTURE REQUIRED SLUMP 5" TO 6 1/2" FOUNDATION WALLS & PIERS COMPRESSIVE STRENGTH 4000 PSI MAXIMUM WATER/CEMENT RATIO 0.45 AIR CONTENT 0-3 PERCENT WATER-REDUCING ADMIXTURE REQUIRED SLUMP 5" TO 6 1/2" INTERIOR CONCRETE SLABS COMPRESSIVE STRENGTN 4000 PSI MINIMUM CEMENTITIOUS MATERIAL CONTENT 517 LB/CU YD AIR CONTENT 0-3 PERCENT WATER-REDUCING ADMIXTURE REQUIRED SLUMP 5" TO 6 1/2" EXTERIOR CONCRETE SUBJECT TO FREEZE-THAW COMPRESSIVE STRENGTH 4000 PSI MINIMUM CEMENTITIOUS MATERIAL CONTENT 564 LB/CU YD AIR CONTENT 6+/- 1 PERCENT WATER-REDUCING ADMIXTURE REQUIRED SLUMP 5" TO 6 1/2" COARSE AGGREGATE CRUSHED STONE �EAN CONCRETE FILL COMPRESSIVE STRENGTH 2O00 PSI MAXIMUM WATER/CEMENT RATIO 0.65 AIR CONTENT OPTIONAL WATER-REDUCING ADMIXTURE NOT REQUIRED SLUMP 4" TO 7" SLUMP: MIXES CONTAINING TYPE A WRDA 5 IN. MAXIMUM MIXES CONTAINING MID-RANGE WRDA 5-6 %" IN. MIXES CONTAINING HIGH-RANGE WRDA 5-8 IN. SPECIFIED MINIMUM CEMENTITIOUS MATERIAL CONTENTS ARE BASED ON THE USE OF WATER REDUCING ADMIXTURES. INCLUDE AN AIR-ENTRAINING ADMIXTURE FOR ALL CONCRETE EXPOSED TO FREEZING AND THAWING IN SERVICE AND FOR ALL CONCRETE EXPOSED TO CO�D WEATHER DURING CONSTRUCTION, BEFORE ATTAINING ITS SPECIFIED DESIGN COMPRESSIVE STRENGTN. REF. ACI 306 FOR DEFINITION OF COLD WEATHER. CLASS C OR F FLY ASH MAY BE USED AS A CEMENT SUBSTITUTE WITH A MAXIMUM 20% SUBSTITUTION RATE ON A LB. PER LB. BASIS. PROPORTION CONCRETE MIXES TO PROVIDE WORKABILITY AND CONSISTENCY TO PERMIT CONCRETE TO BE WORKED READILY INTO THE CORNERS AND ANGLES OF THE FORMS AND AROUND REINFORCEMENT BY THE METNODS OF PLACEMENT AND CONSOLIDATION TO BE EMPLOYED, WITHOUT SEGREGATION AND EXCESSIVE BLEEDING. ADJUSTMENTS TO THE APPROVED MIX DESIGNS MAY BE REQUESTED BY THE CONTRACTOR WHEN JOB CONDITIONS, WEATHER, TEST RESULTS, OR OTHER CIRCUMSTANCES WARRANT. THESE REVISED MIX DESIGNS SHALL BE SUBMITTED TO THE ARCNITECT/ENGINEER FOR APPROVAL PRIOR TO USE. LI1`1TEL SC�EDITLE 1. Where lintels are not specifically shown or noted on the Structural or Architectural Drawings, provide the following lintels over all openings and recesses in both interior and exterior, non-load bearing walls. A) Brick: Masonry Opening Angle Size Up to 5'-0" L4 x 4 x 5/s Over 5'-0" & up to 7'-0" L6 x 4 x 5�6 Over 7'-0" U x 4 x% All angles are LLV (long leg vertical), unless noted otherwise. Provide 1" of bearing per foot of span each end with minimum 8". B) Block: For openings up to 8'-0" long exposed in the finished room, use lintel block filled with grout. Grout all exposed joints and reinforce as follows: 1) For 6" thick block: 1-�5 bar 2) For 8" thick block: 2-�5 bars 3) For 10" thick block: 2-#6 bars 4) For 12" thick block: 2-#6 bars C) Block: For openings Over 8'-0° & up to 12'-0" long exposed in the finished room, use lintel block filled with grout. Grout all exposed joints and reinforce per the "Long Masonry Lintel Detail" on the Typical Masonry Detail Drawing. STRUCTURAL STEEL NOTES 1. Structural steel construction shall conform to the American Institute of Steel Construction "Specification for Structural Steel Buildings". 2. All structural wide flange members shall be ASTM A992, Fy=50 ksi. 3. AIl plates, channels, bars, angles, and rods shall be ASTM A36, unless noted. 4. All structural tube members shall be ASTM A500, Grade B, unless noted. 5. Details for design, fabrication and erection of all structural steel shall be in accordance with the latest AISC Standards, unless otherwise noted or specified. 6. Provide temporary erection guying and bracing as required. 7. Unless otherwise shown or noted on the Drawings, provide 8" minimum bearing each end for all loose lintels and beams. 8. For loose lintels, masonry shelf angles and other such items generally not shown on the Structural Drawings, refer to the Architectural Drawings. See general notes on lintels this sheet for sizes, reinforcing, etc. 9. Steel columns below grade shall be encased in a minimum of 4" concrete or painted with 2 coats of asphaltum paint, unless otherwise shown. 10. Fabricate simple span beams not specifically noted to receive camber so that after erection, any minor camber due to rolling or shop assembly be upward. 11. Refer to the Division 5 Structural Steel Specification of the Project Manual for structural steel surface preparations and prime painting requirements. 12. The Erector shall shim between parallel roof beams and joists with differential mill and induced cambers for (evel deck bearing. 13. Provide cap plates/end plates to close off exposed, open ends of all tubular members, unless noted. Seal weld with partial penetration square groove welds for watertight condition. STEEL COI�TNECTION NOTES 1. Typical beam-to-beam and beam-to-column connections shall be bearing type using A325 bolts, unless noted otherwise. 2. Shop connections unless otherwise shown, may be either bolted or welded. All field connections shall be bolted unless otherwise shown on the Structural Drawings. 3. Connections shall be designed by the Steel Fabricator to support the reactions shown on the framing plan(s). Simple span connections without reactions listed on the Structural Drawings shall be designed by the Steel Fabricator in accordance with Table 3-6 of the AISC "Manual of Steel Construction, 14th Edition". For composite beams where reactions are not indicated, design connections for 75% of the Maximum Total Uniform Load ASD value for the applicable beam size and span given in Table 3-6. For non-composite beams, design connections for 50% of the tabulated ASD value. 4. Submit calculations for connections not detailed on the Structural Drawings and not covered by the AISC Tables. 5. All beam-to-beam connections shall be double angle, unless shown or noted otherwise. 6. All beam-to-column connections shall be at the column centerline, unless shown or noted otherwise. Shear tab connections to tube columns are permitted unless otherwise noted or detailed. 7. Typical bearing-type beam-to-beam, and beam-to-column field-bolted connections may be tightened to the snug-tight condition, unless otherwise shown or noted. 8. Bolted connections in moment frames, bracing connections, hangers and stub columns, crane connections, and those designated PT (pretensioned) on the Drawings shall be pretensioned joints utilizing tension-control (TC) bolts or direct tension indicators. Holes for PT bolts shall be %6" larger than the bolt diameter. All pretensioned joints must be inspected by the Testing Agency. 9. Connect bracing members for two components of stress unless otherwise approved by the SER. Provide a minimum 2-bolt or welded field connection. 10. Locate centerlines of all vertical bracing members on column centerlines in vertical plane and on column and beam centerlines in horizontal plane, unless otherwise shown on the Structural Drawings. 11. All welding shall be in conformance with AWS D1.1, using E70XX electrodes, unless shown or noted otherwise. Welding, both shop and field, shall be performed by welders certified for the weld types and positions involved according to the current edition of AWS D1.1. Perform all AESS welds with care to provide a clean, uniform appearance. 12. Backup bars required for welded connections shall be continuous. 13. Holes in steel shall be drilled or punched. All slotted holes shall be provided with smooth edges. Burning of holes in structural steel shall not be allowed without approval of the SER. 14. The minimum thickness of all connection material shall be is", unless noted. 15. Continuous bent plate and angle slab closures, roof edges, diaphragm chords, etc. around the perimeter of the floor and roof, as well as around openings shall be welded with a minimum %" fillet weld x 3" long at 12" o.c., top & bottom, unless noted otherwise. Butt weld joints in continuous diaphragm chords for continuity. For continuous perimeter angles and bent plates perpendicular-to and connected to the top chords of joists, provide a minimum 3" of %" weld at each joist. Continuous angle and bent plate dosures may be shop-applied to the supporting structural members only when requested and approved in writing by the SER. 16. A qualified independent Testing Agency shall be retained to perform inspection and testing of structural steel field weldments as follows: WELD INSPECTION SCI-�EDULE WELD TYPE VT MT UT PT RT COMMENTS FILLET 25% ROOT PASS AND (SINGLE PASS) FINISNED WELD FILLET 50� 25� (MULTIPLE PASS) ° F�ARE BEVEL FLARE V / 25� GROOVE (PARTIA� REFERENCE NOTE PENETRATION) 100% - 100% - - 'E' BELOW GROOVE (FULL 100% 100� ALL FULL PENE- PENETRATION) TRATION WELDS A) Test procedures: VT = Visual Test (inspection) MT = Magnetic Particle Test: ASTM E109, cracks or incomplete fusion or penetration not acceptable. UT = Ultrasonic Test: ASTM E164. PT = Penetrant Test, ASTM E165. RT = Radiographic Test, ASTM E94 and ASTM E142, min. quality level 2-21. B� Acceptance standards in AWS D1.1 shall be followed for each test procedure. C) Test procedures may be substituted to meet feasibility requirements of test based upon weld geometry or other factors with the approval of the SER. D) Samples shall occur at random locations; additional tests may be required at locations noted on the Drawings. E) Groove welds include square, bevel, V, U, and J grooves including single and double pass types. F) Partial penetration square groove welds at end seal plates of tubular members do not require inspection. G) Weld Procedure Specifications (WPS) shall be produced and maintained in accordance with AWS D1.1. The independent Testing Agency shall have access to all WPS's during the course of testing and inspection. H} For highly-restrained welded joints, especially in thick plates and/or heavy structural shapes, detail the welds so that shrinkage occurs as much as possible in the direction the steel was rolled. Refer to the AISC Manual for preferred welded-joint arrangements that reduce the possibility for lamellar tearing. Members scheduled to receive highly-restrained connections shall be tested by the independent Testing Agency by Ultrasonic Testing prior to commencing welding. I) In addition to inspection requirements for fillet welds in Table above, 100� of field welding of diagonal bracing members to gusset plates shall be visually inspected (VT). STEEL STAIRS 1. Refer to the Design Criteria notes for live load and handrail requirements. 2. All stair designs shall be provided by the Stair Manufacturer�Fabricator's SSE and shall be stamped by a Professional Engineer registered in the State of Indiana. Stair designs shall be in accordance with all applicable code provisions of the IBC. 3. The Stair Manufacturer/Fabricator's SSE shall provide the SER with drawings showing location, direction and magnitudes of all stair load reactions on the building structure for approval, prior to fabrication. 4. The Stair Manufacturer/Fabricator shall coordinate the transition between the supported structural floor slab and the stair structure with the Structural Steel Fabricator, prior to fabrication. 5. Refer to the Architectural Drawings for stair width, rise, run, tread and riser geometry, handrail and guardrail design, shaft wall construction, etc. � U w � O � a ��'���� y}� � � � �� r r ' �' ri cc�i �t ���� ; �� wj �� r� r: �� � �_ �,... r r : 3 , .� M C� `-a� c� 0 � N � � � �' , Qz � .� ' 'c o -� a c� > _ c� o� , �,�, ; , �,s��; � c O � � � � �G ' v M v O � � > � t!{ = Z ti? � �O � O `- r U SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 JRV PAB DRAWING TIT�E: GENERAL STRUCTURAL NOTES CERTIFIED BY: �����iii���i� \\����� P . BR Utij��!��i�. � QQ��a •�F,G\STER� °�°so0 ��` �i = No. 890277 - � � e: STATE OF :• � ^- � o � i �.C`�°a.,oND�ANP,m°���\\�� ��//,/ s/O N W L � \\\\ � �ii *i�i� STEEL JOIST NOTES �, All steel joists shall be designed, fabricated, and erected in accordance with the SJI Standard Specifications. 2. Joist bridging (if shown) is schematically indicated. Provide all bridging necessary to conform to SJI Specifications. 3, The ends of all bridging lines terminating at walls or beams shall be anchored to the wall or beam. 4. Joist bridging and connections shall be completely installed prior to placing any construction loads on the joists. Construction loading shall not exceed the joist design load. 5. All roof joists shall be capable of resisting the net uplift as noted on the Structural Drawings (min. 15 psf net). Provide an additional row of continuous horizontal bottom chord bridging at the first panel point location at each end of all roof joists. 6. Special joists (SP) shall be designed for the load designations specified on the Structural Drawings. Designs shall properly account for the distribution of concentrated loads, live loads, and for the effect of openings. Designs are to meet the requirements of SJI. 7, Joists shall meet the following deflection criteria per SJI. Maximum live load deflection shall not exceed: 8. 9. 10 11 A) Roofs without suspended ceilings: L/240 B) Roofs with suspended ceilings: L/360 C) Floors: L/360 The Joist Manufacturer shall submit calculations for all specia) joists to the SER for record purposes, prior to fabrication. These calculations shall bear the seal and signature of a Professional Engineer registered in the State of Indiana. Joists on column centerlines shall have extended bottom chord connections for erection stability, unless otherwise noted. Do not connect bottom chord extensions, unless otherwise noted or shown. Joists on, or near column centerlines shall have field-bolted connections for erection stability, unless otherwise noted. The Joist Manufacturer shall coordinate with the Structura) Steel Fabricator for the design of all connections to supporting columns, beams, bearing seats, etc. prior to submittal of shop drawings. 12. All steel joists shall be furnished with standard SJI camber, unless noted otherwise. 13. All items suspended from joists such as catwalks, basketball goals, operable partitions, etc. should be installed after all dead loads of roofing, flooring, ceilings, etc. are installed. 14. All joists shall be shop primed in accordance with SJI requirements, unless noted otherwise. Color to match structural steel primer, unless approved in writing by the SER. 15. Provide sloped bearing ends where joist slope exceeds %" per foot. 16. Do not field cut or alter joists without the written approval of the Joist Manufacturer. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10 11 12 0 2. 3. 4 5. All steel deck material, fabrication and installation shall conform to the Steel Deck Institute "SDI SPECIFICATIONS AND COMMENTARY" and °CODE OF RECOMMENDED STANDARD PRACTICE", current edition, unless noted otherwise. Provide members for deck support at all deck span changes. Provide L3x3x%6 deck support at all columns where required. All deck shall be provided in a minimum of 3-span lengths where possible. All welding of steel deck shall be in conformance with AWS Specification D1.3. Provide welding washers for all floor decks less than 22 gauge in thickness. Mechanical fasteners may be used in lieu of welding, providing fasteners meet, or exceed the strength of the specified welds. Submit fastener design data to the SER for review. Substitution of fiber secondary reinforcement for welded wire fabric on supported slabs is prohibited. Do not suspend any items, such as ductwork, mechanical and electrical fixtures, ceilings, etc. from steel deck. Roof deck sidelaps shall be attached at ends of cantilevers and at a maximum spacing of 12" o.c. from cantilevered deck ends. The roof deck must be completely fastened to the supports and at sidelaps before any loads is applied to the cantilever. Submit shop drawings for general conformance to the design concept in accordance with Specifications in the Project ManuaL Erection drawings shall show type of deck, shop finish, accessories, method of attachment, edge details, deck openings and reinforcement, and sequence of installation. Installation holes shall be sealed with a closure plate 2 gauges thicker than deck and mechanically fastened to the deck. Steel deck holes visible from below will be rejected. Deck units that are bent, warped or damaged in any way which would impair the strength and appearance of the deck shall be removed from the site. Where gauge metal pourstops are indicated, supply pourstops designed to meet, or exceed the gauges listed in the SDI Pourstop Selection Table (min. 18 ga.) as required or slab depth, concrete weight, and cantilever distance, unless noted otherwise. The Erector shall shim between parallel roof beams and joists with differential mill and induced cambers for level deck bearing. SPECIALTY STRUCTURAL ENGINEERIl`1G (SSE) A Specialty Structural Engineer (SSE} is defined as a Professional Engineer licensed in the State of Indiana, not the Structural Engineer of Record (SER), who performs Structural Engineering functions necessary for the structure to be completed and who has shown experience and/or training in the specific specialty. It is the SSE's responsibility to review the Construction Drawings and Specifications to determine the appropriate scope of engineering. It is the intent of the Drawings and Specifications to provide sufficient information for the SSE to perform his design and analysis. If the SSE determines there are details, features, or unanticipated project limits which conflict with the engineering requirements as described in the project documents, the SSE shall in a timely manner contact the SER for resolution of conflicts. The SSE shall forward documents to the SER for review. Such documents shall bear the stamp of the SSE and include: A) Drawings introducing engineering input, such as defining the configuration or structural capacity of structural components and/or their assembly into structural systems. B) Calculations. C) Computer printouts which are an acceptable substitute for manual calculations provided they are accompanied by sufficient design assumptions and identified input and output information to permit their proper evaluation. Such information shall bear the stamp of the SSE as an indication that said SSE has accepted responsibility for the results. Contractors are referred to the specific technical specification sections and the structural drawings for those elements requiring Specialty Structural Engineering. Examples of components requiring Specialty Structural Engineering include, but are not limited to the following: A) Structural Steel Connections. B) Steel Joist Systems. C) Cold-Formed Steel Framing. D) Cold-Formed Steel Trusses When modifications are proposed to elements under the design and certification of the SSE, written authorization by the SSE must be obtained and submitted to the SER for review prior to performing the proposed modification. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24 25. 26. COLD-FORMED (LIGHT GA.) STEEL FRAMING NOTES All cold-formed steel framing members, their design, fabrication, and erection shall conform to the "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" of the latest edition of the AISI. All framing members shall be formed from steel conforming to ASTM A653, with a minimum yield strength as follows: A) 12, 14 & 16 gauge members: Fy=50 ksi B) 18, 20 gauge members: Fy=36 ksi All framing members shall be galvanized with a G60 coating meeting the requirements of ASTM A653, unless otherwise indicated. Members shall be the Manufacturer's standard 'C-Shaped studs/joists of the size, flange width, and gauge indicated. All members shall have a minimum flange lip return of %" and satisfy the minimum properties in accordance with the Steel Stud Manufacturers Association (SSMA). The gauge of all tracks shall match the gauge of the associated stud or joists, unless otherwise noted. All welding shall be in accordance with AWS Specification D1.3. No welding of members less than 14 gauge in thickness is permitted without the approval of the SER. All welding shall be performed by certified welders. All welds shall be touched up with zinc rich paint in accordance with ASTM A780. Provide bridging for all load-bearing studs at a maximum spacing of 48" o.c. Provide bridging for all non load-bearing curtain wall studs at a maximum spacing of 54" o.c. Locate one row of bridging within 18" of the top track when a single deep-leg deflection track is utilized. Provide bridging for joists and rafters at midspan and at a maximum spacing of 6'-0" o.c., unless noted otherwise. All bridging shall be installed prior to the application of any loading. Connect bridging to each member by clip angles, or other approved method per the Manufacturer's requirements. Provide web stiffeners at joist and rafter bearings in accordance with the Manufacturer's requirements. All axially-loaded studs shall have full bearing against the track web, prior to stud and track alignment. Splices in axially loaded studs are not permitted. Provide the Manufacturer's standard track, clip angles, bracing, reinforcement, fasteners, and accessories as recommended by the Manufacturer for the application indicated and as needed to provide a complete framing system. Unless otherwise indicated, install the metal framing system in accordance with the Manufacturer's shop drawings, written instructions and recommendations. Install supplementary framing, blocking, and bracing in metal framing system wherever walls or partitions are indicated to support fixtures, equipment, services, casework, heavy trim and furnishings, and similar work requiring attachment to the wall or partition. Where type of supplementary support is not otherwise indicated, comply with the stud manufacturer's recommendations and industry standards in each case, considering weight or loading resulting from the item supported. All field-cutting of studs must be down by sawing or shearing. Torch-cutting of cold-formed members is not allowed. No notching or coping of studs is allowed, unless explicitly shown on the design or shop drawings. All field-cut holes must be reinforced. The Framing Contractor is to ensure punch out alignment when assembling lateral bracing/bridging and field-cutting studs to length. Lateral bracing/ bridging must be installed at the time the wall is erected. Temporary bracing shall be provided and remain in place until work is completely stabilized. Use a minimum of three studs at the corners of all exterior walls. Use a minimum of three studs at the corners and intersections of all load- bearing walls. All headers and built-up beams must be constructed of UNPUNCHED materia) only. Install insulation in built-up exterior framing members, such as headers, sills, boxed joists, and multiple stud jambs at openings, that are inaccessible upon completion of framing work. Shop Drawings: Show layout, spacings, sizes, thicknesses, and types of cold- formed metal framing; and fastening and anchorage details, including mechanical fasteners. Show reinforcing channels, opening framing, supplemental framing, strapping, bracing, bridging, splices, accessories, connection details, and attachment to adjoining work. For cold-formed metal framing indicated to comply with design loads, include structural analysis data signed and sealed by the qualified professional engineer (SSE) responsible for their preparation. Structural Performance: Provide cold-formed metal framing capable of withstanding design loads within limits and under conditions indicated. A) Design Loads: Reference the Design Criteria Notes. B) Deflection �imits: Design framing systems to withstand the design loads without deflections greater than the following: 1. Wall Framing: Horizontal deflection of %40 of the wall height for walls with flexible finishes, e.g. metal siding, wood siding, EIFS, etc. 2. Wall Framing: Norizontal deflection of Yso of the wall height for walls with cementitious finishes, e.g. cement plaster. 3. Wall Framing: Horizontal deflection of %oo of the wall height for walls with masonry veneer finishes. 4. Floor Joist Framing: Vertical deflection of %ao of the span under live load. Limit deflection under total load (dead + live) to to %so of the span. 5. Roof Framing: Vertical deflection of �60 of the span under live/snow load. Limit deflection under total load (dead + live) to %ao of the span. Design framing systems to provide for movement of framing members without damage or overstressing, sheathing failure, undue strain on fasteners and anchors, or other detrimental effects when subject to an ambient temperature change of not less than 120 degrees F. Design framing system to maintain clearances at openings, to allow for construction tolerances, and to accommodate live and/or snow load deflection of primary building structure as follows: Upward and downward movement of % inch. Design exterior non load-bearing curtain wall framing to accommodate horizontal deflection without regard for contribution of sheathing materials. ABBREVIATION LEGEND ABBR DEFINITION AB ANCNOR BOLT ABV ABOVE ACI AMERICAN CONCRETE INSTITUTE ACIP AUGERED CAST IN PLACE PILE ADDL ADDITIONAL ADDM ADDENDUM ADJ ADJUSTABLE AESS ARCHITECTURALLY EXPOSED STRUCT. STL. AFF ABOVE FINISNED FLOOR AGG AGGREGATE AISC AMERICAN INSTITUTE OF STEEL CONSTR'N. AISI AMERICAN IRON & STEEL INSTITUTE ALT ALTERNATE ANCH ANCHORAGE ANSI AMERICAN NATIONAL STANDARDS INSTITUTE APA AMERICAN PLYWOOD ASSOCIATION APPROX APPROXIMATE ARCH ARCHITECT(URAL) ASSY ASSEMBLY ASTM AMERICAN SOCIETY FOR TESTING & MATLS. AVG AVERAGE AWS AMERICAN WELDING SOCIETY B/'X' BOTTOM OF REFERENCED ITEM BB BOND BEAM BFF BELOW FINISNED FLOOR BLDG BUILDING BLKG BLOCKING BLW BELOW BM BEAM BOT BOTTOM BP BASE PLATE BRDG BRIDGING BRG BEARING BS BOTH SIDES BTWN BETWEEN C/C CENTER TO CENTER CAIS CAISSON CAPY CAPACITY CANT CANTILEVER CB CONCRETE BEAM CC CONCRETE COLUMN CFS COLD-FORMED STEEL CIP CAST IN PLACE CJ CONTROL JOINT CNJ CONSTRUCTION JOINT CL CENTERLINE CLR CLEAR(ANCE) CMU CONCRETE MASONRY UNIT COL COLUMN COLL COLLATERAL CONC CONCRETE CONSTR CONSTRUCTION CONT CONTINUOUS CRSI CONCRETE REINFORCING STEEL INSTITUTE CTR CENTER CTRD CENTERED CW CONCRETE WALL D DEEP (DEPTH) DBA DEFORMED BAR ANCHOR DEG DEGREE DIA DIAMETER DIAG DIAGONAL DIM DIMENSION DL DEAD LOAD DN DOWN DP DRILLED PIER DT DOUBLE TEE DTL DETAIL DWG DRAWING DWL DOWEL EA EACH ECC ECCENTRIC EF EACN FACE EIFS EXTERIOR INSULATION & FINISH SYSTEM EJ EXPANSION JOINT EL ELEVATION ELEC ELECTRICAL ELEV ELEVATOR ENG ENGINEER EQ EQUAL EQ SPA EQUALLY SPACED (EQUAL SPACING) EQUIV EQUIVALENT ES EACN SIDE EW EACH WAY EX EXISTING EXC EXCAVATE (EXCAVATION) EXT EXTERIOR FABR FABRICATE (FABRICATOR) FD F�OOR DRAIN FDN FOUNDATION FIN FINISH FF FINISHED FLOOR FLG FLANGE FS FAR SIDE FT FOOT (FEET) FTG FOOTING FV FIELD VERIFY ABBR DEFINITION GA GAGE (GAUGE) GALV GALVANIZED GB GRADE BEAM GC GENERAL CONTRACTOR GLULAM GLUE LAMINATED WOOD GRAN GRANULAR GWB GYPSUM WALL BOARD H HIGH (HEIGHT) HAS NEADED ANCNOR STUD HC HOLLOW CORE HD NOLD DOWN HK HOOK HORIZ NORIZONTAL HP HIGH POINT IBC INTERNATIONAL (INDIANA) BUILDING CODE ID INSIDE DIAMETER IF INSIDE FACE INCR INCREASE INFO INFORMATION INDOT INDIANA DEPARTMENT OF TRANSPORTATION INSUL INSULATE (INSULATION) INT INTERIOR INV INVERT ISO ISOLATION IT INVERTED TEE BEAM JBE JOIST BEARING ELEVATION JST JOIST JT JOINT KIP 1,000 POUNDS KO KNOCK OUT KSF KIPS PER SQUARE FOOT KSI KIPS PER SQUARE INCH L LONG (LENGTH) Ld TENSION DEVELOPMENT LENGTH LB 'L' BEAM LBS POUNDS LGSF LIGHT GAUGE STEEL FRAMING LL LIVE LOAD LLH LONG-LEG HORIZONTAL LLO LONG-LEG OUTSTANDING LLV LONG-LEG VERTICAL LNTL LINTEL LONG LONGITUDINAL LP LOW POINT LVL LAMINATED VENEER LUMBER LW LONG WAY LWC LIGHTWEIGNT CONCRETE MATL MATERIAL MAX MAXIMUM MC MOMENT CONNECTION MECH MECHANICAL MEZZ MEZZANINE MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MO MASONRY OPENING MOM MOMENT MTL METAL NDS NATIONAL DESIGN SPEC'N. FOR WOOD NIC NOT IN CONTRACT NO NUMBER NOM NOMINAL NRC NOISE REDUCTION COEFFICIENT NS NEAR SIDE NTS NOT TO SCALE NWC NORMAL WEIGNT CONCRETE 0/0 OUT TO OUT OA OVERALL OC ON CENTER OD OUTSIDE DIAMETER OF OUTSIDE FACE ON OPPOSITE HAND OPNG OPENING OPP OPPOSITE OSB ORIENTED STRAND BOARD ABBR DEFINITION PAF POWDER-ACTUATED FASTENER PARTN PARTITION PC PRECAST CONCRETE PCF POUNDS PER CUBIC FOOT PCI PRECAST CONCRETE INSTITUTE PDF POWER-DRIVEN FASTENER PERIM PERIMETER PL PLATE PLBG PLUMBING PLF POUNDS PER LINEAL FOOT PLYWD PLYWOOD PNL PANEL PREFAB PREFABRICATED PROJ PROJECTION PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PSL PARALLEL STRAND LUMBER PPT PRESSURE PRESERVATIVE TREATED PSC PRESTRESSED CONCRETE PT POST TENSIONED PTD PAINTED PRTN PARTITION PVMT PAVEMENT QTR QUARTER QTY QUANTITY R RADIUS RB RECTANGULAR BEAM (PRECAST) REF REFER TO (REFERENCE) REQD REQUIRED REV REVISION (REVISED) RF ROOF RO ROUGH OPENING RTU ROOF TOP UNIT RTN RETURN RW RETAINING WALL SBCA STRUCTURAL BUILDING COMPONENTS ASSN. SCT STRUCTURAL CLAY TILE SCNED SCHEDULE SDI STEEL DECK INSTITUTE SE SLAB EDGE SER STRUCTURAL ENGINEER OF RECORD SECT SECTION SHT SNEET SIM SIMILAR SJI STEEL JOIST INSTITUTE SL SLOPE SOG S�AB ON GRADE SPA SPACE (S)(D}(ING) SPECS SPECIFICATIONS SQ SQUARE SS STAINLESS STEEL SSE SPECIALTY STRUCTURAL ENGINEER STD STANDARD STIFF STIFFENER STL STEEL STR STRENGTH STRUCT STRUCTURAL SW SHORT WAY SW SHEAR WALL (OCCASIONAL) SYMM SYMMETRICAL T/'X' TOP OF REFERENCED ITEM T&B TOP AND BOITOM T&G TONGUE & GROOVE TB TIE BEAM TD TRENCH DRAIN TEMP TEMPERATURE TF TRENCH FOOTING TNK THICK(NESS) TOPG TOPPING TPI TRUSS PLATE INSTITUTE TRANSV TRANSVERSE TYP TYPICAL UNO UNLESS NOTED OTHERWISE UNEXC UNEXCAVATED VERT VERTICAL W WIDE (WIDTH) W/ WITN WD WOOD WF WALL FOOTING WP WORKING POINT WPS WELD PROCEDURE SPECIFICATION WRDA WATER REDUCING ADMIXTURE WTCA WOOD TRUSS COUNCIL OF AMERICA WWF WELDED WIRE FABRIC � U w � O � a ��'���� y}: � � � �� r r ''' ri cc�i �t ���� ; �� wj �� r� r: �� �.. r r 3 , .� M C� `-�� c� 0 � N � � � �' , Qz � .� 'c o �� a � '> c cti o� � ��,,,.. �; r,.r��:: � c 0 -p O � � �G ' v M v O � � > � t!{ = Z ti? � O � r U SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 JRV PAB DRAWING TIT�E: CERTIFIED BY: �����iii���i� `\\\���� P . BR Utij��!��i�. � QQ��a•�F,G\STER�°�°soo��` �i = No. 890277 - � � e: STATE OF :• � ^- � i �.C`��'.,oND�ANP,mo���\�� ��//,/ s/O N W L � \\\\ � ui *���� � ----�� � ' � --------- - � :1 I !� ' 3� � : :i � -=�--- - ---- ---- -_�� �., _ � � �I '.. ''.. ,.. � - ��1 _-�""�---� =-� � _-. ---� """ _ - ` � � �--.��'�-.-:='✓ , - - ` � ----= � __�-=--' '-= - - l 1 � � ��I ' � � �- -� � - � � �1 � ( � ;> 1 � � 1 1 C ( � �� I � � 1 ( ( _-_---- � �------�`` ; _ �- � � ��_� - -- y._._ _ � � �� � _ : : �-- =� " i ;, A _� _�,-� __ B ' -- � 21'-1%" 17'-4%" : • ICi 33'-0" �'� 33'-0" � 33'-0" � 20'-0" � 12'-10%" z l � 'I 'I g/„ �I 'I �I �I � � � 1'-4" i � i � -� `' ---------------� �' ; � }-- ---- ---- ---- --� '' ( _� �� �„ � ___� ', � `� -- � ~~� �~ _ � �`,� � � J t_ � �`� `�.,, ~� �,r. � � � I I ��� I I ? �``� r� �---J C 1 ~ f � `�. � F5_CISP -1'-4" 1'1 ^� f �� I �7 � � �� � � SCALE: 1/8" = 1'-0" �` 1 ' F5.OE -1'-4" HSS8x8x3/ �-- 4" CONC. SLAB ON C T/SLAB +0'-0" OUTLINE OF SLAB FOR QUARRY TILE, EXACT LOCATIONS w/ ARCH. DWGS. FLOORING SUPPLIE _r- _ � UNDERGROUND PIPES SLEEVE PER TYP. DTL & PLMB'G. DWGS., STEP B�FTG. AS REQ' F3.OE -1'- HSS5x5x% FOLTNDATION NOTES 1. SEE SHEET S001 FOR STRUCTURAL NOTES AND DESIGN DATA. 2 SEE S601 & S603 FOR TYPICAL FOUNDATION & S�AB DETAILS, BASE PLATE AND ANCHOR ROD DETAILS. 3. SEE S602 FOR TYPICAL MASONRY DETAILS. 4. ALL CONTRACTORS ARE REQUIRED TO COORDINATE THEIR WORK WITH ALL DISCIPLINES TO AVOID CONFLICTS. THE MECNANICAL, ELECTRICAL, AND PLUMBING ASPECTS ARE NOT IN THE SCOPE OF THESE DRAWINGS. HEREFORE, ALL REQUIRED MATERIA�S AND WORK ARE NOT INDICATED. 5. ALL ELEVATIONS ARE REFERENCED FROM THE EXISTING FIRST FLOOR ELEVATION +0'-0". REF. SITE/CIVIL DWGS. FOR USGS ELEV. 6. ALL WALLS SHALL BE LAID OUT FROM ARCHITECTURAL DWGS. 7. NOTE: PERIMETER WALL AND COLUMN FOOTINGS SNALL BE DEEPENED TO ACCOMMODATE SLEEVES FOR PLUMBING LINES (LE. SANITARY & STORM SEWERS, WATER LINES, ETC). ALL INFORMATION REGARDING UNDERSLAB UTILITIES IS BASED ON PRELIMINARY INFORMATION AND MUST BE VERIFIED. SET ALL SLEEVES FROM MEP DRAWINGS. 8. GROUT AL� CORES OF CMU BELOW F.F. ELEVATION SOLID. 9. COORDINATE REINFORCING DOWELS AT CMU WALLS WITH CMU REINF. NOTED ON PLANS & SECTIONS. PROVIDE �5 @ 48" O.C. MIN. VERT. REINF. FOR ALL WALLS WITNOUT REINF. NOTED. 10. COORD. EXACT SIZE & LOCATION OF ANY MECH. OPENINGS IN S�ABS AND/OR FOUNDATION WALLS WITN THE MECH. CONTR. 11. PROVIDE THICKENED SLAB UNDER ALL INTERIOR MASONRY WALLS PER TYPICAL DETAIL 14/S601 U.N.O. �AYOUT ALL WA��S FROM DIMENSIONS ON ARCNITECTURAL FLOOR PLANS. 12. ALL S�AB RECESSES SNALL BE LOCATED PER ARCH. DWGS. COORDINATE DEPTHS OF ALL SLAB RECESSES WITN ARCH. DWGS. REF. 18/S601 FOR TYPICA� DETAIL. 13. EARTH-FORMED FOOTINGS ARE ACCEPTABLE WHERE SOIL CONDITIONS PERMIT (i.e. WHERE THE BANKS OF THE EXCAVATION WILL HOLD WITHOUT CAVING AND SLOUGNING). HOWEVER, THE PLAN DIMENSION OF EARTH- FORMED FOOTINGS MUST BE INCREASED BY 2" A�ONG ALL EDGES TO ACCOUNT FOR INACCURACIES ASSOCIATED WITH EARTH-FORMING (i.e. 2'-0" WIDE WALL FOOTINGS SHALL BE 2'-4" WIDE AND 5'-0" SQUARE COLUMN FOOTINGS SHA�� BE 5'-4" SQUARE). 14. PROVIDE 1/8" WIDE x 1/4 SLAB DEPTH SAWN CONTROL/ CONTRACTION JOINTS IN ALL SLABS ON GRADE. JOINTS TO BE SPACED 20 FT. O.C. MAX IN EACN DIRECTION. 15. A�� NEW CO�UMN/WALL FOOTINGS ABUTTING EX. FTGS. (REF. 'SP' FTG. LABE� ON PLAN) SNA�L BE SIZED PER THE FOOTING SCNEDULE SUCN THAT HALF THE FOOTING SIZE SHALL BE TAKEN FROM TNE CENTER OF THE COLUMN/WALL IN ALL DIRECTIONS NOT LIMITED BY TNE ADJACENT EX. FDNS. BOTTOM OF 'SP' FTG. TO MATCH EX. ADJACENT B/FTG ELEVATION. REF. SPECIFIC SECTIONS & FOOTING SCHEDULES FOR DOWELING & REINF. INFORMATION. 16. PLAN LEGEND: F.F. DENOTES FINISH FLOOR T/'X' DENOTES TOP OF FTG., SLAB, PIER, ETC. B/'X' DENOTES BOTTOM OF FTG., STEEL, ETC. F6.0 -1'-4" DENOTES COLUMN FOOTING SIZE & TOP OF FOOTING E�EVATION (SEE SCHEDULE) F6.OE -1'-4" "E" DENOTES EXTERIOR - SEE SCHED. BELOW WF24 -1'-4° DENOTES WALL FOOTING MARK & TOP OF FTG. ELEVATION (SEE SCHEDULE). WF24E -1'-4" "E" DENOTES EXTERIOR - SEE SCHED. BELOW COLUI���T FOOTING SCHEDULE FOOTING FOOTING SIZE REINFORCING MARK WIDTH x LENGTH x DEPTN (EACH WAY) F3.0 3'-0 3'-0 1'-2 (3) �5 x 2'-6 F3.OE 3'-0 3'-0 2'-4 (4) �5 x 2'-6 F4.0 4'-0 4'-0 1'-2 (4) #5 x 3'-6 F4.OE 4'-0 4'-0 2'-4 (6) #5 x 3'-6 F5.0 5'-0 5'-0 1'-2 (5) �5 x 4'-6 F5.OE 5'-0 5'-0 2'-4 (8) �5 x 4'-6 F6.0 6'-0 6'-0 1'-2 (7) �5 x 5'-6 F6.OE 6'-0 6'-0 2'-4 (10} #5 x 5'-6 F7.0 7'-0 7'-0 1'-6 (7) #6 x 6'-6 F7.OE 7'-0 7'-0 2'-4 (8) �6 x 6'-6 F8.0 8'-0 8'-0 1'-8 (7) �7 x 7'-6 F8.OE 8'-0 8'-0 2'-4 (8) �7 x 7'-6 F4.Ox8.0E 4'-0 8'-0 2'-4 �4) #6 x 7'-6 LONGITUDINAL (9} �5 x 3'-6" TRANSVERSE NOTES: 1. CENTER FOOTINGS BENEATH COLUMNS, U.N.O. 2. INCREASE FOOTING DEPTN WNERE REQ'D. TO ENCASE CO�UMN ANCNOR RODS IN CONCRETE (3" MINIMUM COVER). 3. 'SP' FOOTING DEPTH SHALL BE INCREASED TO MATCH BOTTOM OF ADJ. EX. FTG. (REF. PLAN NOTE ON FOUNDATION PLAN). SCNEDULED REINF. PERPENDICULAR T EXISTING FOUNDATION TO BE DOWELED INTO FACE OF EX. FTG., 6° MIN. EMBED. \ / � NOTE: WF STEEL COLUMN SHOWN, LENGTH P R SCHED. TUBES, PIPES, C.I.P. CON RETE, PRECAST & MASONRY CO UMNS SIM. EQ. EQ. Z � � �w W � � F.F. o � �„ W c� _ W U (/� � d SEE NOTE #2� � o � WALL FOOTING SCHEDULE �� FOOTING SIZE FOOTING REINFORCING MARK W�DTH DEPTH LONGITUDINAL TRANSVERSE WF24 2'-0 1'-0 (3) �5 x CONTINUOUS �4 x 1'-6 @ 96" O.C. WF24E 2'-0 2'-4 (4) �5 x CONTINUOUS �4 x 1'-6 @ 96" O.C. WF36E 3'-0 2'-4 (4) �5 x CONTINUOUS �4 x 1'-6 @ 96" O.C. NOTES: 1. CENTER FOOTINGS BENEATH WALLS, U.N.O. 2. SEE DETAILS 5& 11/S601 FOR TYP. CONSTRUCTION JOINT DETAIL. 3. LAP FOOTING REINFORCING A MINIMUM OF 30 BAR DIAMETERS. 3. REF. FOUNDATION PLAN NOTES FOR 'SP'-TYPE WALL FOOTING INFORMATION. SCHEDULED REINF. PERPENDICULAR TO EXISTING FOUNDATION TO BE DOWELED INTO FACE OF EX. FTG., 6" MIN. EMBED. � U w � O � a O -p O GC � �G ' v M v O � � > � t!{ = Z ti? � �O � O `- � U SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 PAB DRAWING TIT�E: FOUNDATION PLAN UNITA CERTIFIED BY: ����������,�� `\\\���� P . BR Utij��!��i�. � QQ��a•�F,G\STER�°�°soo��` �i = No. 890277 - � � e: STATE OF :• � ^- i o � i �.C` ��a.aoND�ANPomo° ��� �' � �` ,�����s,��N �L F- \��\. � ui *���� DRAWING NUMBER PROJECT NUMBER 12071 G H 12'-10%" � i � F5.OE -1'-4" i HSS8x8x/ I- - - _ �_..........._� _ � _ T � � - - �__J i , i i I � I I � � '� � F6.OE -1'-4" I HSS8x8x% � i � i � -�-- -�- L - - J i � i C � F6.OE -1'-4" � HSS8x8x% �- � s �WF24E -1'-4" - -) F4.OE -1'-4" HSS5x5x% OU LINE OF SLAB RECESS FO QUARRY TILE, COORD. EX CT LOCATIONS & DEPTN w/ ARCN. DWGS. & FL ORING SUPPLIER. � 4" F4.0 -1'-4" � � HSS5x5x% � , I - I----I - 4" U 0 � ;� UNDERGROUND PIPE i � SLEEVE PER TYP. DTLS. � & PLMB'G. DWGS., 1 STEP B/FTG. AS R'D. S701 ' 4.9 � � � � 1 1 I I 1 I I i � ---, � -------- - - - - - - - - --------------- L J � �� I � � ' � ' I � � I � � I I I I- -- I- �- - - -�- ---� �----�- � ( - - _ _ _ _ - - - � I I � �--� T � �J / � r � � � � � ---� �--� , 1 I I � L--- � � _� ( ��� � � � ( � ( ( � � � ( � ( (�� � � � ( ( � � � � �� = � � ( � ( ( ( � � � „ �. ( �_==-_� � ( � � � � � ��. - � �-� - I I � � I ���_. � (--------� --�--=�----------� � ( ( � � � REP�acE EX. EXTERioR � I I � �� ( 2 � I� i �-REF. ETAIL ( � CONC. STOOP ( ( ( � S701 � i 9/S6 1 ( � ( ( ( ( � I �� � � I I � � I s �� �� � �, � ��� ,� I I i i I i ---- WF24E 1 =4" ---- - 5 F4.OE -1'-4" � HSS5x5x% HSS5x5 OLUMNS U `-' ARE ON INE 4.9 0 � � N 7 4" CONC. SLAB ON GRADE T/SLAB +0'-0" OUTLINE OF S�AB RECESS FOR QUARRY TILE, COORD. EXACT LOCATIONS & DEPTN F4.0 -1'-4" m w/ ARCN. DWGS. & NSS5x5x% � FLOORING SUPPLIER. � � -S�_ - � � i � � � I I i i I F4.o -�'-a" , Fa.o -�'-4" ,� I I 1 HSS5x5x% i HSS5x5x% 4" SLA 5" SLAB ( � � ( � � � I,_ � I I I � � � � Wo�- � � ( ( ( ( � ( � o�� �I � �g� � ( , � � � ( � � �� I c����) ( CJ � o+i�� � , ( I I � m � �i ( OUT INE OF� SLAB RECESS ���� I � ( � ( � ' FOR QUAR�Y TILE, COORD. "' o w�, i�_,� i o� � ( ( ( � -�� I EXA T LOC TIONS & DEPTH z m � ,- � � � � ( � , � � w/ RCN. pWGS. & �� W iI FLO RING UPPLIER. ��� � I ( ( ( � REPLACE EX. EXTERIOR � � ( ( � "' � I � � CONC. STOOP .�� I F4.0 -1'-4" i F4.0 -1'-4" i) ( ': ( ( � � � �r,... _ �'� � � Hss5X5X� Nss5X5X� � � ; „= I� � � i , �� „ �.� � � �----------���=-=-� - ---� �--- --- -=-�-" _-------- � o i � � �1 CJ � ----- ------ --------- - �� - �_. _- -- -- - - -- -T -- ---- - --- - - - - �- - - -- - -- � � � ¢ � � � ��' � �-- ' - ------- - ----- -� i - - - - - - - - - 10 5" CONC. SLAB �N GRADE � 1�-0" i � i� �------------------------ -------------- -- --� i � � � i � _ � �,_0„ � � UNDERGROUND PIPES T SLAB -0'-0%"�, COORD. > � � F3. SP -1'-4° F3.OSP -1'-4" F3.OSP -1'-4" F3.OSP -1'-4° F3.OSP -1'-4" F3.OSP -1'-4" �� i S�EEVE PER TYP. DTLS. RECESS DEPTH / QUARRY � HS 5x5x% '11 HSS5x5x% 11 HSS5x5x% 11 HSS5x5x% 11 HSS5x5x% 11 NSS5x5x% � (' 5 -� � & PLMB'G. DWGS., TILE SUPPLIER 701 S70 S70 S7 1 S7 1 S� � i ( N-� S701 0 �--� � I �� I � / i, L -J � �� � � � // i � // � 1 � I 57� CJ ;� � ��ar�,,,! � � 2 � � / � S�701 / � / � / � �, H �/ �/ UNDERGROUND PIPES `� / � SLEEVE PER TYP. DTLS. ' & PLMB'G. DWGS., STEP B/FTG. AS REQ' . x 8 4 � /� o �/ / �/ STEP B FTG. AS REQ'D. UNDERGROUND PIPE 5 CONC. SLA i ON GRADE 11 � �� � � WF24E 1'-4" WF2 E-1'-4° WF24E -1' 4" �� S�EEVE PER TYP. DTLS. T/SLAB -0'-OY"±, COORD. ---- -- ---------� �------ ------- � i Z- --- -- � � � � � � -- I & P�MB'G_DWGS., RECESS DEPTH w/ QUARRY S701 I ---- -- -------- � J-------- ------- i �-- --- i-_- - - - G. AS R - - - - - - - � - - - � � TEP B/FT E(�'9 � TILE SU PLIER � � � S701 � L WF24E -1'-4" � � - - - - - - - - WF24E -1'-4" � � WF24 -1'-4" � - - �� F3.OE -1'-4" F3.OE -1'-4" F3.OE 1'-4" - -� � � � - - - - - � F4.OE -1'y " HSS5x5x% NSS5x5x% ' NSS5x x/ _ _ � � _ _ _ _ _ _ _ _ � � HSS5x5x/ ! -T �- � F24E -1'-4" � L _ _ _ _ � r + s ! _J �' 1 2 1 � 2 F4.Ox8. E -1'-4" F4.OE -1'-4° �, --- � - - - - - - - - _ _ F-�,g�= �'- " - .8x . -1'- ° - i 2 NS 5x5x/ i HSS5 5x% -- ---- HSS5x5x% 2 NSS5 5x/ UNDERGROUND PIPES S701 S701 S701 S701 �� � W 24E -1'-4" Z �� SLEEVE PER TYP DTLS /� �1 � / / /, / � F4.OE -1'-4" �� � NSS8x8x% � �o � � � �� 1 O� S701 _ -1'-4" o 3x8x% � � 29'-6" FV J 26'-0" -0" ��� � : � � � � � �& PLMB'G. DWGS., i � F4.Ox8.0E -1'-4" 2 F4.Ox8.0E -1'-4" � STEP B/�fG. AS REQ'D. S701 (2) NSS5x5x/ , S701 � , (2) NSS5x5x/ S701 i 11 -0" 11'-0' 6'-1%" ' 13'-0" FV � 13'-0" � 22' 0" � 13'-0" ' 13'-0" FV � 1'-7�%6„ L L.7 M N P � Q R S CENTER�INE OF RIDGE AT EXISTING NORTH ROOF , , � • � � � � SCALE: 1/8" = 1'-0" r � �• � � FOLTNDATION NOTES 1. SEE SHEET S001 FOR STRUCTURAL NOTES AND DESIGN DATA. 2 SEE S601 & S603 FOR TYPICAL FOUNDATION & S�AB DETAILS, BASE PLATE AND ANCHOR ROD DETAILS. 3. SEE S602 FOR TYPICAL MASONRY DETAILS. 4. ALL CONTRACTORS ARE REQUIRED TO COORDINATE THEIR WORK WITH ALL DISCIPLINES TO AVOID CONFLICTS. THE MECNANICAL, ELECTRICAL, AND PLUMBING ASPECTS ARE NOT IN THE SCOPE OF THESE DRAWINGS. HEREFORE, ALL REQUIRED MATERIA�S AND WORK ARE NOT INDICATED. 5. ALL ELEVATIONS ARE REFERENCED FROM THE EXISTING FIRST FLOOR ELEVATION +0'-0". REF. SITE/CIVIL DWGS. FOR USGS ELEV. 6. ALL WALLS SHALL BE LAID OUT FROM ARCHITECTURAL DWGS. 7. NOTE: PERIMETER WALL AND COLUMN FOOTINGS SNALL BE DEEPENED TO ACCOMMODATE SLEEVES FOR PLUMBING LINES (LE. SANITARY & STORM SEWERS, WATER LINES, ETC). ALL INFORMATION REGARDING UNDERSLAB UTILITIES IS BASED ON PRELIMINARY INFORMATION AND MUST BE VERIFIED. SET ALL SLEEVES FROM MEP DRAWINGS. 8. GROUT AL� CORES OF CMU BELOW F.F. ELEVATION SOLID. 9. COORDINATE REINFORCING DOWELS AT CMU WALLS WITH CMU REINF. NOTED ON PLANS & SECTIONS. PROVIDE �5 @ 48" O.C. MIN. VERT. REINF. FOR ALL WALLS WITNOUT REINF. NOTED. 10. COORD. EXACT SIZE & LOCATION OF ANY MECH. OPENINGS IN S�ABS AND/OR FOUNDATION WALLS WITN THE MECH. CONTR. 11. PROVIDE THICKENED SLAB UNDER ALL INTERIOR MASONRY WALLS PER TYPICAL DETAIL 14/S601 U.N.O. �AYOUT ALL WA��S FROM DIMENSIONS ON ARCNITECTURAL FLOOR PLANS. 12. ALL S�AB RECESSES SNALL BE LOCATED PER ARCH. DWGS. COORDINATE DEPTHS OF ALL SLAB RECESSES WITN ARCH. DWGS. REF. 18/S601 FOR TYPICA� DETAIL. 13. EARTH-FORMED FOOTINGS ARE ACCEPTABLE WHERE SOIL CONDITIONS PERMIT (i.e. WHERE THE BANKS OF THE EXCAVATION WILL HOLD WITHOUT CAVING AND SLOUGNING). HOWEVER, THE PLAN DIMENSION OF EARTH- FORMED FOOTINGS MUST BE INCREASED BY 2" A�ONG ALL EDGES TO ACCOUNT FOR INACCURACIES ASSOCIATED WITH EARTH-FORMING (i.e. 2'-0" WIDE WALL FOOTINGS SHALL BE 2'-4" WIDE AND 5'-0" SQUARE COLUMN FOOTINGS SHA�� BE 5'-4" SQUARE). 14. PROVIDE 1/8" WIDE x 1/4 SLAB DEPTH SAWN CONTROL/ CONTRACTION JOINTS IN ALL SLABS ON GRADE. JOINTS TO BE SPACED 20 FT. O.C. MAX IN EACN DIRECTION. 15. A�� NEW CO�UMN/WALL FOOTINGS ABUTTING EX. FTGS. (REF. 'SP' FTG. LABE� ON PLAN) SNA�L BE SIZED PER THE FOOTING SCNEDULE SUCN THAT HALF THE FOOTING SIZE SHALL BE TAKEN FROM TNE CENTER OF THE COLUMN/WALL IN ALL DIRECTIONS NOT LIMITED BY TNE ADJACENT EX. FDNS. BOTTOM OF 'SP' FTG. TO MATCH EX. ADJACENT B/FTG ELEVATION. REF. SPECIFIC SECTIONS & FOOTING SCHEDULES FOR DOWELING & REINF. INFORMATION. 16. PLAN LEGEND: F.F. DENOTES FINISH FLOOR T/'X' DENOTES TOP OF FTG., SLAB, PIER, ETC. B/'X' DENOTES BOTTOM OF FTG., STEEL, ETC. F6.0 -1'-4" DENOTES COLUMN FOOTING SIZE & TOP OF FOOTING E�EVATION (SEE SCHEDULE) F6.OE -1'-4" "E" DENOTES EXTERIOR - SEE SCHED. BELOW WF24 -1'-4° DENOTES WALL FOOTING MARK & TOP OF FTG. ELEVATION (SEE SCHEDULE). WF24E -1'-4" "E" DENOTES EXTERIOR - SEE SCHED. BELOW COLUI���T FOOTING SCHEDULE FOOTING FOOTING SIZE REINFORCING MARK WIDTH x LENGTH x DEPTN (EACH WAY) F3.0 3'-0 3'-0 1'-2 (3) �5 x 2'-6 F3.OE 3'-0 3'-0 2'-4 (4) �5 x 2'-6 F4.0 4'-0 4'-0 1'-2 (4) #5 x 3'-6 F4.OE 4'-0 4'-0 2'-4 (6) #5 x 3'-6 F5.0 5'-0 5'-0 1'-2 (5) �5 x 4'-6 F5.OE 5'-0 5'-0 2'-4 (8) �5 x 4'-6 F6.0 6'-0 6'-0 1'-2 (7) �5 x 5'-6 F6.OE 6'-0 6'-0 2'-4 (10} #5 x 5'-6 F7.0 7'-0 7'-0 1'-6 (7) #6 x 6'-6 F7.OE 7'-0 7'-0 2'-4 (8) �6 x 6'-6 F8.0 8'-0 8'-0 1'-8 (7) �7 x 7'-6 F8.OE 8'-0 8'-0 2'-4 (8) �7 x 7'-6 F4.Ox8.0E 4'-0 8'-0 2'-4 �4) #6 x 7'-6 LONGITUDINAL (9} �5 x 3'-6" TRANSVERSE NOTES: 1. CENTER FOOTINGS BENEATH COLUMNS, U.N.O. 2. INCREASE FOOTING DEPTN WNERE REQ'D. TO ENCASE CO�UMN ANCNOR RODS IN CONCRETE (3" MINIMUM COVER). 3. 'SP' FOOTING DEPTH SHALL BE INCREASED TO MATCH BOTTOM OF ADJ. EX. FTG. (REF. PLAN NOTE ON FOUNDATION PLAN). SCNEDULED REINF. PERPENDICULAR T EXISTING FOUNDATION TO BE DOWELED INTO FACE OF EX. FTG., 6° MIN. EMBED. � � NOTE: WF STEEL COLUMN SHOWN, LENGTH P R SCHED. TUBES, PIPES, C.I.P. CON RETE, PRECAST & MASONRY CO UMNS SIM. EQ. EQ. � �o W � � F.F. o � �„ W W U � � � SEE NOTE #2� � o � WALL FOOTING SCHEDULE �� FOOTING SIZE FOOTING REINFORCING MARK W�DTH DEPTH LONGITUDINAL TRANSVERSE WF24 2'-0 1'-0 (3) �5 x CONTINUOUS �4 x 1'-6 @ 96" O.C. WF24E 2'-0 2'-4 (4) �5 x CONTINUOUS �4 x 1'-6 @ 96" O.C. WF36E 3'-0 2'-4 (4) �5 x CONTINUOUS �4 x 1'-6 @ 96" O.C. NOTES: 1. CENTER FOOTINGS BENEATH WALLS, U.N.O. 2. SEE DETAILS 5& 11/S601 FOR TYP. CONSTRUCTION JOINT DETAIL. 3. LAP FOOTING REINFORCING A MINIMUM OF 30 BAR DIAMETERS. 3. REF. FOUNDATION PLAN NOTES FOR 'SP'-TYPE WALL FOOTING INFORMATION. SCHEDULED REINF. PERPENDICULAR TO EXISTING FOUNDATION TO BE DOWELED INTO FACE OF EX. FTG., 6" MIN. EMBED. H U w � O � a O � � �G ' v M M � � � � > � = Z - ti? � O � � U SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 PAB DRAWING TIT�E: FOUNDATION PLAN UNIT B CERTIFIED BY: �����iii���i� `\\\���� P . BR Utij��!��i�. � QQ��a•�F,G\STER�°�°soo��` �i = No. 890277 - � � e: STATE OF °• � ^- � i �.C`��«.aoND�ANPomo���\�� ��//,/ s/O N � L � \\\\ � �ii *i�i� DRAWING NUMBER PROJECT NUMBER 12071 ��:�_1�II�Ct.I��_1�I�C����, 1. SEE SHEET S001 FOR STRUCTURAL NOTES AND DESIGN DATA. 2. SEE S301 & S302 FOR TRUSS & BRACING ELEVATIONS. 3. SEE S602 & S603 FOR TYPICAL FRAMING DETAILS. 4 SEE S602 FOR TYPICAL MASONRY DETAILS. 5. ALL CONTRACTORS ARE REQUIRED TO COORDINATE THEIR THEIR WORK WITN ALL DISCIPLINES TO AVOID CONFLICTS. THE MECNANICAL, ELECTRICAL, AND PLUMBING ASPECTS ARE NOT IN THE SCOPE OF TNESE DRAWINGS. THEREFORE, ALL REQUIRED MATERIALS AND WORK MAY NOT BE INDICATED. 6. ALL ELEVATIONS ARE REFERENCED FROM THE USGS ELEVATION. REF. SITE/CIVI� DWGS. 7. ALL WALLS SHALL BE LAID OUT FROM ARCNITECTURAL DWGS. 8. COORDINATE EXACT SIZE & LOCATION OF ANY MECHANICAL OPENINGS IN FLOOR SLABS OR WALLS WITH THE M.E.P. CONTRACTOR. LOCATION & SIZE OF ALL DUCT OPENINGS, GRILLS, ETC. SHA�L BE VERIFIED PRIOR TO CONSTRUCTION. 9. A�L E�EVATIONS SNOWN ON P�AN INDICATE TOP OF STEE� BEAM UNLESS NOTED OTHERWISE. 10. REF. FOUNDATION PLAN FOR REINFORCING IN CMU WALLS. ALL MASONRY BOND BEAMS SHA�L BE "OPEN-CORE" BOND BEAMS TO ALLOW VERTICAL REINFORCING TO PASS TNROUGH, UNLESS NOTED OTNERWISE. PROVIDE BOND BEAMS AT 8'-0" O.C. MAX. (VERT.) AND AT E�EVATIONS INDICATED ON SECTIONS, AT TOPS OF WALLS, AND AT CHANGES IN CMU THICKNESS. 11. NOTE: ALL HORIZONTAL AND DIAGONAL BRIDGING FOR STEE� JOISTS SNALL BE DESIGNED, LOCATED & PROVIDED BY TNE JOIST SUPPLIER PER S.J.I. SPECIFICATIONS. 12. PROVIDE ANGLE ROOF FRAME @ ALL ROOF DRAINS, ROOF NATCHES, SKYLIGHTS & MECH. OPENINGS IN ROOF PER "TYPICAL ROOF OPENING FRAME" DETAILS 8& 9/S603. COORD. EXACT NUMBERS, LOCATIONS AND SIZES w/ THE APPROPRIATE CONTRACTORS AND THE ARCH. DWGS. 13. ALL EXISTING CONSTRUCTION SNOWN IN PLAN AND/OR SECTION WAS WAS DERIVED FROM EXISTING DWGS. AND SHA�L BE FIELD VERIFIED. IF ANY DISCREPANCIES ARE DISCOVERED BETWEEN INFORMATION SHOWN ON THE DRAWINGS AND ACTUAL CONDITIONS, IMMEDIATELY CONTACT THE ARCHITECT/ENGINEER FOR DIRECTION BEFORE PROCEEDING WITN WORK. 14. PLAN LEGEND: F.F. DENOTES FINISH FLOOR SE DENOTES SLAB EDGE MEASURED FROM CENTERLINE OF BEAM OR COLUMN LINE EX. DENOTES EXISTING CONSTRUCTION T/'X' DENOTES TOP OF STEEL, SLAB, PIER, ETC. KB DENOTES KNEE BRACE, REF. DETAIL 10/S603. ►— DENOTES BEAM-TO-COLUMN MOMENT CONN. � U w � O � a ��'3��� y}: � � �� r r '' ri c�i � t �� � � :: dN' � wj �� r� r: �� �,.. r r 3 , .� M C� � I.L c� 0 � N � � � � , Qz � .� 'c o �� a c� > _ c� o� � ��,,,.. �; r,.r��:: � c � � � � � N ._ — W � SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 PAB DRAWING TIT�E: � i � �1�_1►l � CERTIFIED BY: �����iii���i� \\����� P . BR Utij��!��i�. � QQ��a •�F,G\STER� °�°so0 ��` �i = No. 890277 - � � e: STATE OF :• � ^- � i �.C`��«.aoND�ANPomo���\�� ��//,/ s/O N � L � \\\\ � �ii *i�i� DRAWING NUMBER PROJECT NUMBER 12071 � ROOF FRAl�/II1`�TG PLA1`�T - LT��TIT "B" S221B % scazE: 1�g�� =1�-0,� �' � Q CENTER�INE OF RIDGE AT EXISTING NORTH ROOF FRAMING PLAN NOTES 1. SEE SHEET S001 FOR STRUCTURAL NOTES AND DESIGN DATA. 2. SEE S301 & S302 FOR TRUSS & BRACING ELEVATIONS. 3. SEE S602 & S603 FOR TYPICAL FRAMING DETAILS. 4 SEE S602 FOR TYPICAL MASONRY DETAILS. 5. ALL CONTRACTORS ARE REQUIRED TO COORDINATE THEIR THEIR WORK WITH ALL DISCIPLINES TO AVOID CONFLICTS. THE MECNANICAL, ELECTRICAL, AND PLUMBING ASPECTS ARE NOT IN THE SCOPE OF TNESE DRAWINGS. THEREFORE, ALL REQUIRED MATERIA�S AND WORK MAY NOT BE INDICATED. 6. ALL ELEVATIONS ARE REFERENCED FROM THE USGS ELEVATION. REF. SITE/CIVIL DWGS. 7. ALL WA��S SHALL BE �AID OUT FROM ARCHITECTURAL DWGS. 8. COORDINATE EXACT SIZE & LOCATION OF ANY MECHANICAL OPENINGS IN FLOOR S�P,BS OR WA��S WITH THE M.E.P. CONTRACTOR. LOCATION & SIZE OF ALL DUCT OPENINGS, GRILLS, ETC. SHALL BE VERIFIED PRIOR TO CONSTRUCTION. 9. ALL ELEVATIONS SHOWN ON PLAN INDICATE TOP OF STEEL BEAM UN�ESS NOTED OTHERWISE. 10. REF. FOUNDATION P�AN FOR REINFORCING IN CMU WALLS. ALL MASONRY BOND BEAMS SNALL BE "OPEN-CORE" BOND BEAMS TO ALLOW VERTICAL REINFORCING TO PASS THROUGH, UNLESS NOTED OTNERWISE. PROVIDE BOND BEAMS AT 8'-0" O.C. MAX. (VERT.) AND AT ELEVATIONS INDICATED ON SECTIONS, AT TOPS OF WALLS, AND AT CHANGES IN CMU THICKNESS. 11. NOTE: ALL HORIZONTAL AND DIAGONAL BRIDGING FOR STEEL JOISTS SHALL BE DESIGNED, LOCATED & PROVIDED BY TNE JOIST SUPPLIER PER S.J.I. SPECIFICATIONS. 12. PROVIDE ANGLE ROOF FRAME @ ALL ROOF DRAINS, ROOF NATCHES, SKYLIGHTS & MECH. OPENINGS IN ROOF PER °TYPICAL ROOF OPENING FRAME" DETAILS 8& 9/S603. COORD. EXACT NUMBERS, LOCATIONS AND SIZES w/ THE APPROPRIATE CONTRACTORS AND TNE ARCH. DWGS. 13. ALL EXISTING CONSTRUCTION SNOWN IN PLAN AND/OR SECTION WAS WAS DERIVED FROM EXISTING DWGS. AND SHALL BE FIELD VERIFIED. IF ANY DISCREPANCIES ARE DISCOVERED BETWEEN INFORMATION SHOWN ON THE DRAWINGS AND ACTUAL CONDITIONS, IMMEDIATELY CONTACT THE ARCHITECT/ENGINEER FOR DIRECTION BEFORE PROCEEDING WITN WORK. 14. PLAN �EGEND: F.F. DENOTES FINISN FLOOR SE DENOTES SLAB EDGE MEASURED FROM CENTERLINE OF BEAM OR COLUMN LINE EX. DENOTES EXISTING CONSTRUCTION T/'X' DENOTES TOP OF STEEL, SLAB, PIER, ETC. KB DENOTES KNEE BRACE, REF. DETAIL 10/S603. � DENOTES BEAM-TO-COLUMN MOMENT CONN. � U w � O � a ��'���� y}: � � �� r r ''' ri cc�i � t �� e� ' N N d' d" �j �� r� r: �� �,.. r r 3 , .� M C� � I.L co 0 � N � � �� , Qz � .� 'c o �� a c� > _ c� o� � ��,,,.. �; r,.r��:: � c � � � � � N ._ — W � SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 PAB DRAWING TIT�E: CERTIFIED BY: �����iii���i� `\\\���� P . BR Utij��!��i�. � QQ��a•�F,G\STER�°�°soo��` �i = No. 890277 - � � e: STATE OF °• � ^- � i �.C`��«.aoND�ANPomo���\�� ��//,/ s/O N � L � \\\\ � �ii *i�i� DRAWING NUMBER PROJECT NUMBER 12071 59'-4" y 29'-8" � 29'-8" � I 7 ELEVATION - LOOKING WEST ROOF TRLTSSES OVER SOCIAL I�ALL SCALE: 1/4" = 1'-0° �. 10'-11 4" 59'-4" 10'-113/a" 3.2 18, �» 1 � � • •• '�� ' • ' � ' ' � •' SCALE: 1/4" - 1'-0" T/SLAB +12'-0" � 16'-0" D2 32' 0" 16'-0" n���no'n ��c rnoi r � ELEVATION - LOOKING �OR�IV�EST ROOF TRLTS SES OVER MINISTRY ROOM SCALE: 1/4" = 1'-0° ELEVATION - LOOKING NORT�I ROOF TRI.J S SES OV�R LOBBY SCALE: 1/4" = 1'-0" TRUSS BRG. +15'-10" N I � � � � �D SLOPE & ELEVATION I EXISTING ADJACENT TO THE NORTH, FIELD TRUSS BRG. +13'-�" � �� ; 0 � O �� � � cn o ._ � o � .— � � �� Q� �' Q v M M W � � � t�0 o.�..r � � � a � � =z � _ � � a� N— ._ � o � — .� � ca W C� � O � � . � � SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TIT�E: ROOF TRUSS ELEVATIONS CERTIFIED BY: �����iii���i� \\����� P . BR Utij��!��i�. � QQ��a •�F,G\STER� °�°so0 ��` �i = No. 890277 - � � e: STATE OF :• � ^- � i �.C`�°«.aoND�ANPomo���\�� ��//,/ s/O N � L � \\\\ � �ii *i�i� DRAWING NUMBER PROJECT NUMBER 12071 � � � � � I I I HSS8x8 � � � 0 o � W o � NSS8x8 0 �, N N p N � � I I � � M--i-�i � � ( HSS5x5 � ry- � Vti.r ( ( � y -1� rn r� � I 6'- � o�, `J'J' \ o � ySss�s�j o � �� - � \ � 1 � ` 1 � l 1 ot� I I ot� ` �� I I � I � � � �' � i i � ' � � ` tis S � � r ti`s'ss �' s�-s� O O ` ��� O � � , , � � � � � � � � � i � i � � d � � y � � � , N � r k� � I I I � O i i � i i i � � o O , � HSS8x8 N O � O ___ � � � / � �� � � � �� - �� � � i i ' ' ' ' � �,����� � � � �� O � � � � r � , � � �� ' � � �' y � � , , ,� , � � � o � -- N � � �}c,`��'� NSS5x5 I I .�c,SS �? ��� I I I e��� o � � � � I / � � }��� � � � � �'� 6' ! o � �o � ( ( I I� / I � � +� � � / � I HSS8x8 � � � � i� m � I I I � HSS8x8 I I I ( � � � � � � � � �-, cn o� � D � —' � -I- I� + —' � o � \ \ \ � � IV � � � � n 0 0 � � � V � m + W i + � c�j � o V IV o + 0 - � c� NI� N� � �{ O � � � w �' � � HSS8x8 r r rrn m O7 � � � � �� I I I �' C� � � � �, , i� i o � HSS8x8 � 'o_ � y � � s � � o ` 1 r ysSs�s- � �� � � _ � �—i � Q ii y Q ii � i \ � � � � � � � I I I � � � � �tiss � ����� �' � NSS5x5 � � � � � � � � W � � � � I I I � � 00 I I� � � I � I r � ` � O � i SS� �s O o � O � ��� }� O o O � � � �� ��� � O �� � � � � � ►—i M�1 \ 'S's � U, � , ' \�� � I �-�I1 i � ,C� s�� � - -P I I / ,.` -�j \ � � � HSSSx8 O� � � � � \ I � g ���'�'SS 6'_ � � � � i� � �� O ` ►�-� � / � ,, � - ;; ;� ; � -� � � � � C7 � NSS5x5 ! W + � + � � +o w �, 6, HSS8x8 - � V o o + � _ = �,,, - I I � � —� —� —i o ' \ \ \ m � cn o� c� I � � � CO + W i + w c-�j � � � -P o � c\n � o o + � � � - c.,� + I� I + � NF-', -P O � I- (� - � O I I I NSS5x5 rr1 zn r� � 0 0 0 °� o `'' N N N � �, � HSSgxg �� I I I I I � bd I I I m _ 0 m m .. � .. .. � � /-1 � /-1 HSS8x8 � /-1 '�S,S, �� 1 I I �� 1 � �� 1 s�-s � � � � � W � � I I � I � � SJ��.� 3 �� � � � � ( � b �\ � �� �- � � � � �� � �� O � — --� � O �' O �� - -� � t -- � ; � � � � i � - � i i ' � _ ___ ______ _ - � � � V � N %/ � � � / �� �, � _ � � � � � ' / � � � o i ,������ � o � I I � I � � I I j �1� � ; � - �-- - - � - � Q � � Q � � � � � � ' -- - ' , � � � l s � �% ►-�-� I I ��,� I I -- }��� � � / � ���5 �� � 5�,� � � ' � � � / '°� /'� �I���� � � o � / �-i 1 0 � ; 0 � � I I � i N � I I / � � I ( NSS8x8 � i � _ - - ---- _ o � y ' � HSS8x8 � � '� � � - -- - Ct� I I I NSS5x5 � � � � I I I � � o � � \ \ m \ \ � cn c� �o �o � � � � i � � + + � � � � � � � � �m � -i o � � cs � c\n � � �'"� � O� C7 OJ " ( � -f- I I � � � I D � � � 0 � � � � W -�- O7 + ' � � _ _ � -{- -f- � _ _ I + � + � ^I , � � C� Csl -P O � O ' � � O � � � � � iv NI N\ y � � HSS5x5 � y � � m - — - — � rn HSS5x5 � � � � -P � N -. r r-� � o I � O , v CO CO m � O O7 �7 C'> �(� � Z C7 O� D 07 � D D O D D D � c'� � �7 O r� �l rTl rTl O Z I-Tl � 7J -{ O�l O� �77 �7 C�J � -i Z-� � � �� i c�S� �/SS' � � �� � c-� —i < n cn � m �—i �'-'"' � �� iv c� c m�—� c� ➢ r— m D'�'i �— O �7 � D O a� � _ � � �� �����1 4�-Q� _ �-. �,`_�, � ( ��'�SS� y`ss�,� � � � o0 o�my� z � �oo ➢zc' � y �o -cni c �� m� tT � � � c� - c� m m— r� r� , z cn � � � ~�—�/ ll� ��� � 4 � � � � � z r � m c� � c� �o � O � -o z � � � � m r�T� � � z --- _ / , m � � r,-� j� j� D D \ ` - -- -- N �' vzi��D - o� �c� - ^�i I HSS5x5 �� --- — NSS5x5 - � �� -o�000 � z��� ��x �� �� D � � �� 1�� ,� 1 l I l z c-� p co �- � o � � � o� D 0 � C��� ���� CO �� C� m z O z C7 � z z y r� z�- o �,-� — m z � z o c� ,�— i �O �O � �``�� �``�� ( ( � � �r� —�� n m � iv z � o W c c��zcny � r�-o� c� D cn� �O � m ��O 11'� � l�-� � � �� �� cnc7 D��c7� � �Drn �o� O�m �—ri � � � m� �-0 �t'm�'i�� � c'>rOJ m � � ��7 �D —I 0 � �c/) �/ � � _j z G> z'O � y O<�i> `�.' cn � � �� D� n z C� c,r� �'�-1 � \ \ \ '� � fCTI ��� Z � I-Tl �7 � Z C.D/) D 7J C7 m D N z r z � z cn z '+"� cn OJ -i -I -I � O � z rT� �� z D m m � 0�� m= N m r�_ I ➢ � � 'rt Cn CO D � � � � r � � � _ � � Cp � Z D Z � � O � � � \ \ \ C7 Z (� � Z � � Z m � fTl (� � � C I + ± ! � � D 0 m O z O C n� m � � � _� � O(. /) O D � y -P O �"� � -P � � D �� D➢�0 � O� 00 N � � XD � � ) o iv T� _ i I � O� o r m N yz �� �m �t/� /�/ �.� (J1 N � o X n � m � � V1 o � _ z — = o m _ � o � �{ ' PROJECT: � � "o���� �� �, � m X�s��� ��3� , � i ,.,- n �n � `��`�,���������, � v 6 � p = 70 �0 ��� �j�� � v � �����i r � � tJt � -^ ° `� s � � ; � 1 `k+' � r � � , � � m : �� o . '4(,l �i rn � � D 70 � � � s � � � � �, , ! O D `° � z � �e � a � � O �,.� �I � I � I 4 � � r��v 0 0, 0 0 a o 0 0 � 0 �, � _ _o am= � � ����4-� : � �, � � � �o o�� ���o m a� � eton ����4 ���-1��������:rr � s �_ _ _ _ � n za e nn _ _o _ � -� � z a o -� � � o� - �, z � n � rt � � , �.. � � . �_ �, -�: - � � �n o�� � �v . . . �._ �F,�z. =r�z � �0�- rn � � � � � � _ _ � Soc�al Hall Add�t�on g z z -�;a �� o�e ��\ p � O � o o � o� n 550 Vir inia Avenue P 317.423.1550 y c c °� �' .' ^ : � -< Z � = a- -�° � � � ARCHITECTtTRE • iNTERIQR DE�IGN �� � ',� �� •°°••o•aa 'e,��''>`�. p� o O Z � N o� Q � o��� �, z Indiana polis, IN 46203 F 317.423.1551 �� � m n o �° �rt=� � . .. Z m a �� "�a" t" . � � '///� ������������\\\\\ � F� ��� a� ��� 10655 Haverstick Rd. 8�31 I�e stone �rcassin � Indiana olis, IN 46240 � Y � P a oN � W� °� � Carmel, IN 46033-380� Main 317.848.7800 • Fc�x 317.574.0�57 • c�oinc.net � �o ���. � -^ ^ c� 2007 CSO Architects, Inc. All Rights Reserved NOTE: SLOPE OF EXCAVATION TO CONFORM W/ APPLICABLE REQUIREMENTS OF OSHA AND/OR STATE & LOCAL CODES NOTE: 1. REFER TO TNE SPECIFICATIONS FOR APPLICATION OF UNIT COSTS FOR a a MAX. DEPTH OF UNSHEETED/UNSHORED REMOVAL OF UNSUITABLE BEARING MATERIAL & REPLACEMENT W/ EXCAVATION TO CONFORM W/ THE STRUCTURAL COLUMN OR �OMPACTED, ENGINEERED FI�L. ° APPLICABLE REQUIREMENTS OF OSHA WALL FOOTING 2. REFER TO THE GEOTECHNICAL ENGINEERING REPORT FOR ADDITIONAL ° AND/OR STATE & LOCAL CODES INFORMATION RE: EXPECTED SOIL CONDITIONS, SUITABILITY OF EX. PROPOSED GRADE SOILS FOR USE AS ENGINEERED FILL, GROUNDWATER CONDITIONS, ETC. � STRUCTURAL COLUMN PROPOSED GRADE a OR WALL FOOTING � �%��\�: ��%�%�%�%�%�%�% a � ///�//�//�/ ///�//�//��//�//�//�//� ��\��\��\�� �\��\��\��\��\��\��\� . /\//\//\//\// //\//\//\//\//\//\//\ � , . d , ��j\�j\�j\�j\j \\\�j\�j\�j\�%\�%\�j\�j � . � //�\//�\//�\//�\/ �\//�\//�\//�\//�\//�\//�\//�\ /�/�/�/�/�� �/�/�/�/�/�/�/� a a . ' W ���\���\���\���\���\ \���\���\���\���\���\���\���\ .� 4 a . � a . �: . . . a o j %�\%�\%�\%�\%�\i %�\%�\%�\%�\%�\%�\%�\\ . � � � . � . a . a z o // // // // // , // // // // // // // W ¢ // /// /// /// /// /// % jj /// /// /// /// /// /// ° � /\\/\\/\\/\\/\\/\\/ /\\/\\/\\/\\/\\/\\/\\\ a �1 ��j��/��j��j��/��/�i ��j��j��j��j��j��j��j� BOTTOM/FOOTING ELEVATION � /�\/�\/�\/�\/�\/�\/�\j \/�\/�\/�\/�\/�\/�\/�\/ a � 1 // // // // // // //�i // // // // // // // a � ,�,��,��,��,��,��,��,�� �,��,��,��,��,��,��,��, a aa va �,��,��,��,��,��,��,��,. ��,��,��,��,��,��,��,� a a a � � ,,��,,��,,��,,��,,��,,��,,��,; ,,��,,��,,��,,��,,��,,��,,��, 2 ,��,��,��,��,��,��,��,��, ;��,��,��,��,��,��,�� / i�i�i�i�i�i�i�i�, � a -� � �/��/��/��/��/��/��/��/� �/��/��/��/��/��/��/� ,LEAN CONCRETE FILL . & � / �/�\�/�\�/�\�/�\�/�\�/�\�/�\�/�� �/�\�/�\�/�\�/�\�/�\�/�\�/�\ `(MIN. 2,000 PSI @ 28 DAYS) N' /� ��/���%�%�%�%�%�%�%�%` %�%�%�%�%�%�%�% G a a / � / / //��%��/��/��/��/��%��%��%��%� /��%��/��%��/��/��/��/ aa a aa � /j��jj�jj�jj�jj�jj�jj�jj�jj�jj \jj� //\/�\/�\/�\/�\//\//\ j � � \/\/\/\/\/\/\/\/\/\/� /�/�/�/�/�/�/� a a , � / /�j// /// /// /// /// /// /// /// /// /` /�j// /// /// /// /// /// / ° a . a — ' / . \\�\\j\\j\\� �� � \�\\�\\j� \\� \� � \�\��\\j\\j 4 Q—d d �— — I 1-1 I 1=1 I 1=1 I 1=1 I 1=1 I 1=1 I 1= I 1=1 I 1=1 I 1=1 I 1=1 I �- '=1 I 1=1 I 1=1 I 1= 1= I 1-1 I 1-1 I 1-1 I 1-1 I 1-1 I 1-1 I 1-1 I 1-1 I —I I 1=1 I 1=1 I I—I I I—I I I—I I 1=1 I I—I I 1=1 I I—I I 1- �—I I 1=1 I 1=1 I 1=1 I I- AS =� j I=I I I=I I I=I I I=I I I=I I I=I I I=I I I=I I I= ' I: I I I=I I I=I I I=I SUITAB�E BEARING MATERIAL AS �CY I I 1=1 I 1=1 I 1=1 I 1=1 I 1=1 I 1=1 I 1=1 I 1=1 I 1= ' I 1=1 I 1=1 I 1=1 I 1= DETERMINED BY TESTING AGENCY COM PACTED FI L� �EAN CON CRETE FI �L OVEREXCAVATION DETAILS 1 NOSCALE s(�j SECOND POUR FIRST POUR _ ,,,,— NOTE: SPLICE TRENCH FOOTINGS IN MIDDLE THIRD OF SPAN BTWN. STEEL COLUMNS r�Kiv�tu r��rvvHr TRENCI� FOOTING CONSTR. JOINT s NOS�Az� s6o1 � z � ~ z O o � � � = Q � � W °- � � � z WELDED WIRE FABRIC � � _ � m � � W cn � a °x x-� . x�° �'a x x x x ° x °!� Q a o a. ,� a a a a �������� ������� /1r--�T\r�T1r--�T\r--�T1r--�T\r--�T1 T\r�T\r--�T,\r--�T1r�T1r--�T\r--�T\r--�T\r� II III III III III III III III III III III III III I �) � �� i �� � �� � �) � �� i i� � � � ( �� i i� � �� � �� ( �� I I� � �, � ,� ( � � � �� I �� ( �� � �� � �� i i) ( (, VAPOR BARRIER COMPACTED GRANULAR DRAINAGE FILL PROOF-ROLLED & VERIFIED SUBGRADE 1. LOCATE WELDED WIRE FABRIC IN UPPER TNIRD OF SLAB. SUPPORT ON BOLSTERS, CHAIRS, OR CONCRETE BRICKS. 2. LAP WELDED WIRE FABRIC A MIN. OF ONE FULL MESH SPACING. 3. THE USE OF NYLON OR POLYPROPYLENE FIBER IN LIEU OF WELDED WIRE FABRIC AS A SECONDARY REINFORCEMENT IS PERMISSIB�E, UN�ESS OTHERWISE NOTED. NOTE: FIBER MAY NOT BE SUBSTITUTED FOR W.W.F. IN SUPPORTED SLABS. 4. SEE PLANS, NOTES, AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS SUCH AS FINISH, JOINTING, CURING, ETC. SLAB ON GRADE CONSTRIJCTION lo NOSCALE 56�1 CMU WALL w/ REINF. PER PLAN — 1 /2" ISOLATION JT. CONC. SLAB ON GRADE PER PLAN T/SLAB +0'-0" U.N.O. x x x x > � � o � z i � w J w� w� �„ W _ U c!� �SEE PLAN & SCNEDULE FOR SIZE & REINF. � INTERI OR MA S ONRY WALL FOOTING 1 s NOSCALE SC01 PROVIDE STD. 90 DEGREE CONTINUOUS TRENCH FTG. REINF. HOOKS AT ENDS OF ALL PER SECTIONS BARS _�� ��� �zo ��� °- w � � �w //�\ W U ---------� � U � U w w w � � � Q > -----------i �---- � � � � � � NOTES: � � � � 1. PROVIDE THIS DETAIL AT A�� INTERSECTIONS INCLUDIN � � AT COLUMN PIERS MONOLITHIC W/ TRENCN FOOTINGS � � � � � � � � � � � � TRENCI� FaOTING INTERSECTION 6 NO SCALE SF)O1 1/8" W. X 1/4 SLAB "T" IN UNEXPOSED AREAS WHERE JOINTS WILL NOT BE FILLED. — X X X X 1/4" W. X 1/4 SLAB "T" - z WET SAWCUT - SEE TABLE ~ � BELOW � � � � X X X X > CONTROL JOINTS SHALL BE SAWN NOT LATER THAN THE FOLLOWING TAB�E, OR 16 HOURS A�fER FINAL TROWE�ING (WNICHEVER IS �ESS), WHERE T EQUA�S THE AMBIENT TEMPERATURE IN DEGREES FANRENNEIT AT THE TIME OF FINAL TROWELING. SAWCUTTING SHALL BE SUSPENDED ONLY IF TNE LARGE AGGREGATE IS DISLODGED OR LOOSENED. ALTERNATE: USE PRE-FORMED JOINT FORMER. TEMP, F o G 40 ° 50 ° 60 ° 70 ° 80 ° 90 ° TIME, NOURS 16 14 8 1/2 5 1/2 4 3 SLAB CONTROL/CONTRACTION JOI��TT 11 NOSCALE S(�l STEEL COLUMN PER PLAN CONC. SLAB PER PLAN FINISHED FLOOR ELEV.= 0'-0" x x x x—X x � W � Q > c� z J �� 00 o ,_,_, � _ w � W C� � EXTEND FOOTING DEPTH AS REQUIRED TO MAINTAIN MIN. 3" COVER AROUND BOTTOM OF ANCHOR RODS WHEN FOOTING DEPTN IS LESS TNAN ANCNOR BOLT EMBEDMENT COLUMN BASE PLATE & I ANCNOR RODS - SEE DTLS. I REFERENCE CO�UMN ISOLATION � JOINT DETAILS � � X x—x x X X � . . . . . /��-- --� EQUAL EQUAL SEE SCHEDULE FO SIZE & REINF. INTERIOR COLUMN FOOTI��TG NO SCALE DETAIL 16 5601 REFER TO M.E.P. DRAWINGS & SPECIFICATIONS FOR INFO. RELATING TO TRENCH EXCAVATION, BEDDING, AND BACKFIL�. FOR ANY EXCAVATION THAT MUST EXTEND BEYOND THIS LINE SHORING MUST BE COLUMN OR WALL �'-6" PROVIDED TO KEEP THE EXCAVATION FROM FOOTING UNDERMINING THE FOUNDATIONS. . , . � --��1 _ ' `==i(�ll� _ii����� II � � � ... .. .. . �I_ ������ . r , . .. .. . . '— —��illll— ��� _ IIIIi��— � � -__ . �:. — ' — . — _ . : • _ ������I= _ ,��' �—_ � _ �Trrti���� rrrrrrr--`�I I I I I,— �� � � I I ��—�� — I�- 1.5 NOTE: ANY SNORING SCHEME REQUIRED MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW, PRIOR TO EXCAVATION. EXCAVATION LIMITS DETAIL 2 No Sc�� s6o1 � (y� I\LIIVI . IIV Jf11VIL JILL lX. Q N0. AS TRENCH FTG. > 40 � NOTES: 1. "H" DENOTES HEIGHT OF STEP AS SHOWN ON PLAN. 2. "D" DENOTES FOOTING DEPTH, REFER TO PLANS AND SECTIONS. STEPPED TRENCI� FOOTING NO SCALE 4°� DETAIL � 56�1 TOOL OR CHASE w/ i- Q SAWCUT SIM. TO °- CONTRO� JOINT ¢ � F.F. PER PLAN � — X X X X X X X X FO MED KEYWAY W/—� 3/ " DIA. x 18" LONG SMOOTH DO ELS @ 18" O.C., GREASE ON END FOR BOND BREAK 2'-0" 2'-0" PROVIDE CONSTRUCTION JOINT IN LIEU OF CONTROL JOINT AT TERMINATION OF POUR SLAB CUNSTRUCTION JOINT 12 NOSCALE 56�1 PROVIDE 1-1/2" D. JOINTS IN CURBS. LOCATE DIRECTLY ABOVE JOINTS IN SOG CURB OR HOUSEKEEPING � PAD, SIZE, NO., LOC'N. & NT. PER MEP DWGS. 6" � (1) �3 STIRRUP @ 4'-0" O.C. 4�� (MIN. 1 PER CORNER) 1 /2" RADIUS, TYPICA� SEAL �o z I�OLTSE���PI�G PAD DETAIL 1 � NOSCALE S6O1 "�"'T'"" "" "' TRENCH FOOTING REINF. �" LARGER THAN � ;,N ���h����h��v ������. � V( 1�VIVl.I\LIL TRENCN FOOTING REINF. COVER ALL AROUND, STEP TRENCH FOOTING SIM. TO FTG. WHERE MIN. 6" CAN'T BE MAINTAINED NOTES: 1. REFER TO PLUMBING DRAWINGS FOR INVERT ELEVATION OF ALL UNDERGROUND PIPING. 2. STEP BOTfOM/TRENCH F7G AS SHOWN WHERE PIPE PENETRATION INTERRUPTS BOTfOM REINFORCING, UNLESS WRITTEN PERMISSION IS OBTAINED FROM THE MEP ENGINEER. TRENCI� FOOTING SLE�VE DETAIL 3 No Sc�� s6o1 � MIN. 6" EMBEDMENT . MIN. 30 DIA. LAP EX. FOUNDATION WALL & FOOTING REF. PLAN FOR APPROX. T/FTG ELEV. #5 x 2'-6" �ONG DOWE�S IN SAME N0. AS FOOTING REINF. EPDXY DOWE� TO EX. FOOTING REF. SPECIFIC SECTIONS & WALL FOOTING SCHEDULE � z z � � o� W �� � W= � v � � � � w � � STEP NEW FOOTING AS REQUIRED TO PREVENT UNDERMINING EX. FOOTING OR BEARING ON PREVIOUS BACKFILL NEW-TO-EX. WALL FOOTING NO SCALE DETAIL s 56�1 STAIR STRINGER BY � STAIR MANUF. � ANCHORAGE BY STAIR MANUF. W.W. F. X X X X X X— X X X X � � o O 0 O 2, 6„ (3) - #4 EACH . , WAY BOTTOM STAIR POST BY STAIR MANUF. ANCHORAGE BY BASE PLATE STAIR MANUF. BY STAIR MANUF. W W F x x x x x x—x x x x � � o o • o 2'-6" �3) - �4 EACN WAY BOITOM TI�ICKENED SLAB AT STAIR POSTS 13 NOSCALE SCOl CONCRETE S�AB ON GRADE PER PLAN REFER TO ARCH. PLANS & ROOM FINISH ,� SCEDULES FOR LOCATION, & DEPTH OF � RECESSED SLABS. "' F.F. PER PLAN F.F. PER P�AN x x x x x DEPTH OF RECESS x x x x OR DEPRESSION + SLAB THICKNESS 1'-0" MIN. �N.�N.F. TO BE DEPRESSED OR LAPPED AT DEPRESSIONS � CONCRETE SLAB ON F.F. PER PLAN _� GRADE PER PLAN u u " " " F.F. PER P�AN x x x- � FORMED KEYWAY W/ COLD- 1'-0" MIN. 1'-0" MIN. JOINT WATERSTOP AT BASEMENTS - CONCRETE SLAB ON �� p�R pl ��� GRADE PER PLAN x x- F.F. PER PLAN x x x x�x DEPTH OF RECESS/STEP OR DEPRESSION DEPTH OF RECESS/STEP OR DEPRESSION � FORMED KEYWAY W/ COLD- 1'-0" MIN. 1'-0" MIN. JOINT WATERSTOP AT BASEMENTS REC�SS�D SLAB ON G�:.ADE DETAILS ls NO SCALE SC)O1 �nnrrinu ini ic TRENCN FOOTING REWF. ' , ,. • � z o � � 0 o � J S 4 U U W � � � � MAINTAIN MIN. 6"" OF CONCRETE � � LOOSE INSULATION COVER A�L AROUND, STEP TRENCH FOOTING SIM. TO FTG. WHERE MIN. 6" CAN'T BE MAINTAINED NOTES: 1. REFER TO PLUMBING DRAWINGS FOR INVERT ELEVATION OF ALL UNDERGROUND PIPING. 2. PROVIDE THIS DETAIL WHERE A PENETRATION THROUGN A TRENCH FOOTING IS UNAVOIDABLE. 3. NO SLEEVES IN COLUMN PIERS OR FOOTINGS ARE PERMITTED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER. TRENCI� FOOTING SLEEVE DETAIL 4 No Sc�� s6o1 � MIN. 6" EMBEDMENT _ . MIN. 30 DIA. LAP EX. FOUNDATION WAL� & FOOTING REF. PLAN FOR APPROX. T/FTG ELEV. �5 x 2'-6" LONG DOWELS IN SAME N0. AS FOOTING REINF EPDXY DOWEL TO EX. FOOTING REF. SPECIFIC SECTIONS & WALL FOOTING SCHEDULE STEP NEW FOOTING AS REQUIRED TO PREVENT UNDERMINING EX. FOOTING OR BEARING ON PREVIOUS BACKFILL NEW-TO-EX. WALL FOOTING NO SCALE DETAIL 9 56�1 _�' REINF. PER PLAN CONCRETE SLAB ON GRADE SLAB CONSTRUCTION JOINT PER PLAN SEE TYPICAL DETAIL x x x x x x x x 0 0 °� 3'-0" TYPICAL U.N.O. CNTR'D UNDER MAS. WALL NOTE: PROVIDE 2'-0" DOWELS INTERIOR NON-LOAD BEARING WALL, EPDXY GROUTED INTO CONCRETE TNICKNESS & LOCATION PER THE SLAB W/ 6" MIN. EMBEDMENT ARCHITECTURAL FLOOR PLANS. HILTI HY-150, OR APPROVED EQ. (TYPICAL @ ALL NEW CMU WALLS WITHOUT DOWE� SIZE & SPACING TO MATCN FOOTINGS) SCHEDULED VERTICAL REINF. IF NOT INDICATED ON PLAN OR SCHEDULE, USE �4 DOWELS @ 4'-0" O.C. CONCRETE SLAB ON GRADE PER PLAN X X X X X X X X— o • °� (2) �5 x CONTINUOUS 3'-0" TYPICAL U.N.O. �) CNTR'D UNDER MAS. WALL �� TI�ICKENED SLAB DETAILS 14 No sca1.,E 5601. � U W � 0 � a SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TIT�E: TYPICAL DETAILS CERTIFIED BY: ��\Iilllll/// \\����� P . BR Utij��!��i�. � QQ��a •�F,G\STER� °�°so0 ��` �i = No. 890277 - � � e: STATE OF :• � ^- � i �.C`�°'.,oND�ANP,mo���\�� ��//,/ s/O N W L � \\\\ � ui *���� �, - ��� �, ; �� �. .. ��� ' .� 1 CMU SASN BLOCK W/ CRUCIFORM RUBBER OR PVC CONTROL JOINT (ABOVE GRADE), SEE SPECIFICATIONS. REFER TO ARCHITECTURAL DRAWINGS FOR JOINT LOCATIONS. SEE PLAN & SECTIONS FOR VERTICAL REINFORCING SIZE & SPACING. LAP BARS 48 DIA. AT SPLICES BLOCK CORES W/ REINF. STEEL TO BE FI�LED WITN GROUT THE � FULL HEIGNT OF WALL � GROUT ALL CORES BELOW GRADE/FIN. FLOOR, U.N.O. LADDER—TYPE HORIZONTAL JOINT REINF. @ 16" O.C. VERTICALLY (DISCONTINUOUS AT CONTROL JOINTS) � REDUCE SPA. TO 8" BELOW GRADE & AT PARAPETS REINF'D. CONCRETE FOOTING, REF. P�AN FOR SIZE, REINF. & T/FOOTING E�EVATION FULLY BED MORTAR JOINTS AT NOTE: USE NORMAL WEIGNT CMU BELOW STARTER COURSE OFF FOOTINGS GRADE. REFER TO SPECIFICATIONS & ARCN. WHERE CELLS ARE NOT GROUTED DRAWINGS FOR WT. CLASSIFICATION FOR ABOVE GRADE UNITS. RL�`�TNING BOND - REINFORCED l��IASONRY DETAIL 1 NO SCALE VERTICAL REINF. CONTIN.� THRU BOND BEAM CORES FI��ED SOLID � / WITH GROUT SEE SCHED.� � VERTICAL REINF. CONTIN.�.� THRU BOND BE� CORES FILLED SC WITH GROUT 3 1 /2" % NOTE: USE OPEN CORE BOND BEAMS, TYPICAL EXCEPT FOR LINTELS & OTHER CONDITIONS WHERE BOITOM OF UNITS WILL BE EXPOSED. OPEN CORE CMU BOND BEAM W/ WEB KNOCKOUTS OR CUT FROM STANDARD UNITS SCHEDULE SIZE REINF. 6" (1) #5 8" (2) �5 10" (2) �5 12" 2 5 � CMU BOND BEAM UNITS SEE SCHED. 2 ClVIU BOND BEAlVI DETAILS 6 NO SCALE SFO2 LUBRICATE BTWN. BOTTOM OF BEAM & SURFACE OF BEARING PLATE WITH DRY-FILM LUBRICANT WIDE-FLANGE STEEL BEAM PER PLAN 5602 13/16" x 2" LONG SLOTfED HO�ES IN BEAM FLANGE (ONE EA. SIDE OF WEB W/ GA. = 1 3/4") I ( - MASONRY WA�L STEEL BEARING PLATE—SEE � PER PLAN SCHEDULE. TYPE "B" TYP. U.N.O. (2} 5/8" DIA. BOLTS—TACK WELD TO - ---- BEARING PLATE FOR PLACEMENT 3" BOLT PROJ'N ABOVE TOP/BEARING 6" MIN. EMBEDMENT GROUT 8c REINFORCING—SEE SCNEDULE I I BEAM PARALLEL TO WALL BEARING PLATE SCHEDULE BEARING PLATE SIZE GROUT REQUIREMENTS REINFORCING 1/2 x 6 1/2 x 1'-0 GROUT SOLID TO FTG. x 24" LONG 2 VERTICALS FULL HEIGHT OF WALL. SEE PLANS & DETAILS FOR SIZE. LADDER—TYPE HORIZONTAL CMU SASH UNITS W/ JOINT REINF. CRUCIFORM CONTROL JOINT INSERT, SEE SPECS. DD��:��D P � A N NOTE: VERTICAL WALL REINF. 1. BOND BEAM REINFORCEMENT SHA�L PER PLAN & SECTIONS NOT BE LAPPED WITHIN 8'-0" OF CONTROL JOINT. 2. HORIZ. JOINT REINFORCEMENT TO BE . , . DISCONTINUOUS AT CONTROL JOINTS. ,� 3EAM REINFORCING TO BE CONTINUOUS THRU CONTROL E LE VA TI 0 N BOND BR�EAK)W/ MASTIC FOR RI:�`�NING BOND Cl��IU COI�TTROL DETAILS 2 NO SCAL� 56�2 ��o -a— _�� �� a �� CORNER BARS TO MATCH "la� �") a N0. & SIZE OF CONTIN. BOND BEAM REINFORCING � a�l �� � (a (��� CONTINUOUS REINFORCING CMU BOND BEAM— THICKNESS VARIES I a°a�, CORNER BARS TO MATCH ' � N0. & SIZE OF CONTIN. � ° BOND BEAM REINFORCING �� ��� � (� � � (�a �� I PROVIDE PRE—FABRICATED °L'S" AND "T'S" AT CORNERS OF HORIZONTAL JOINT REINF. CMU BOND BEAM— � Ie II THICKNESS VARIES I � I� oI I CONTINUOUS REINFORCING �� BOND BEAM INTERSECTION DETAILS � NOSCALE SEO2 �UBRICATE BTWN. BOTTOM OF BEAM & SURFACE OF BEARING PLATE WITH DRY-FI�M LUBRICANT WIDE-FLANGE STEEL BEAM PER PLAN STEEL BEARING PLATE - SEE � - SCHEDULE BELOW, TYPE "A" TYP. U.N.O. (2} 5/8" DIA. BO�TS-TACK WELD TO BEARING PLATE FOR PLACEMENT 3" BOLT PROJ'N ABOVE TOP/BEARING 6" MIN. EMBED. FINGER TIGNTEN NUTS & FOUL THREADS GROUT & REINFORCING-SEE SCHEDULE BEAM PERPENDICULAR TO WALL 13%16" x 2" LONG SLOTTED NOLES IN BEAM FLANGE (ONE EA. SIDE OF WEB W/ GA. = 1 3/4") MASONRY WALL PER PLAN BEARING PLATE SCHEDULE BEARING PLATE SIZE GROUT REQUIREMENTS REINFORCING 3/4 x 6 1/2 x 1'-0 MIN. 3 COURSES DEEP x 24" �ONG NONE UN�ESS �OCATED AT DISCONTINUOUS END OF WALL 5 5/8" 7 5/8" 9 5/8" 11 5/8" 1 1/2" CL. �) C~�) �~�� ��--il� � , - � - � � 2„ CL. (� ) #6 (2) �5 �2) �� �2) �8 � TOP & BOT. TOP & BOT. TOP & BOL TOP & BOT. �3 STIRRUPS C� 1 1/2" CL. 8" ON CENTER � ( �'� c� 11 I � C 2" CL. 16" BEARING — LINTEL SPAN—PER ARCH. PLAN � 16" BEARING CMU LINTEL NOTES: 1. FILL SHALL BE 2,500 PSI (MINIMUM) GROUT. 2. AL� REBARS ARE HOOKED AT THE ENDS. 3. REFER TO SPECS. FOR TYPE OF CMU. 4. LINTELS SHALL BEAR ON SOLIDLY GROUTED CMU 5. THIS SCHEDU�E DOES NOT APPLY TO �OAD BEARING WA��S, U.N.O. 6. BOND PATfERN OF LINTEL TO BE RUNNING BOND, U.N.O. 7. BOTTOM OF LINTEL SNALL BE SMOOTN MASONRY WITH NO CORES EXPOSED. 8. CONTRACTOR TO PROVIDE TEMPORARY SHORING UNTIL CMU NAS PROPERLY SET (3 DAY MINIMUM). LONG CMU LINTEL DETAILS 3 No scal,E 5602 GROUT CORES FULL HEIGNT � ^. • / • � a d / � / / � LOAD BEARING OR RAKE JOINT & CAU�K SNEAR WALL—FOOTING— SUPPORTED LOAD BEARING OR — 24 2" NOOK SHEAR WALL EACH END FOOTING SUPPORTED a a ' 1/4"x2"x28" �ONG STRAP � ANCNORS. SPACE AT 48" O.C. AT INTERIOR WALLS & 24" O.C. AT EXTERIOR WALLS TYPICAL AT INTERSECTION BETWEEN FOOTING-SUPPORTED CMU WALLS WALL INTERSECTION DETAILS s NO SCALE SE)OZ CMU CONTROL JOINT-SEE ARCH. DWGS. FOR LOCN. '"„" """ r"" "T OFFSET & �AP JAMB BAR 48 DIA. AT CONTROL JT. � DCHRIIVI� r�R HRI.(l. rLHIVJ ���I:�K������� �-----�— 2 LAYERS OF FLASHING —' LE AT BEARING COAT THIS PORTION OF� BARS W/ GREASE TO PREVENT BOND MASONRY OPENING PER ARCH. PLANS 8" MIN. BEARING �K����� 1► 1 5 5/8" 7 5/8" 9 5/8" 11 5/8" �� �� �� �� `° _ 2„ CL. -- — � —�� `' � 1) #5 (2) �5 (2) �6 (2) �6 � 8" MIN. BRG. 8" MIN. BRG. 2" CL. CMU LINTEL NOTES: 1. FILL IS 2,500 PSI (MINIMUM) GROUT. 2. PROVIDE 1" BRG. PER FOOT OF SPAN WITH 8" MIN. 3. LINTELS SNALL BEAR ON SOLIDLY GROUTED CMU 4. THIS SCNEDULE DOES NOT APP�Y TO LOAD BEARING WALLS, UNLESS NOTED OTNERWISE. 5. BOND PATTERN OF LINTEL TO BE RUNNING BOND, U.N.O. 6. BOTfOM OF LINTEL SHA�L BE SMOOTH MASONRY WITH NO CORES EXPOSED. 7. CONTRACTOR TO PROVIDE TEMPORARY SHORING UNTIL MASONRY HAS PROPER�Y SET (3 DAY MINIMUM). 8. PRECAST LINTELS MAY NOT BE SUBSTITUTED FOR BOND BEAM LINTELS WHERE EXPOSED IN THE FINISNED STRUCTURE. TYPICAL CI��IU LINT�L D�TAILS 4 NOSCALE S6O2 GROUT CORES FULL HEIGHT , � . ad CMU WALL—FOOTING SUPPORTED INTERIOR NON—LOAD BEARING CMU WA��— SLAB SUPPORTED v � , ° RAKE JOINT & CAULK 16 GA. GA�VANIZED WIRE MESH TIES @ 16" O.C. NOHMANN & BARNARD MWT, OR EQUAL TYP. AT INTERSECTION BETWEEN FOOTING-SUP'TD. AND THICKENED SLAB-SUPPORTED CMU WALLS WALL INTERSECTION DETAILS 9 N�O SCALE SCO2 "VERTICAL" BRICK EXPANSION "OFFSET" BRICK EXPANSION JOINT-SEE ARCH. DWGS. JOINT-SEE ARCH. DWGS. FOR LOCATION FOR LOCATION 2 LAYERS OF F�ASHING—' AT BEARING, BOTH ABOVE & BELOW BEARING C�EAR OPENING (, (, 8" MIN. PER ARCH. PLANS BEARING . � . � � �� � � 2 LAYERS OF FLASHING AT BEARING C�EAR OPENING �, (, 8" MIN. PER ARCH. PLANS BEARING . � � � �� � � WIDE-FLANGE BEARING PLATE DETAIL ll WIDE-FLANGE BEARING PLATE DETAIL IZ BOND BEAM BEARING DETAILS 13 ANGLE LINTEL BEARING DETAILS 14 NOSCALE S6O2 NOSCALE S6O2 NOSCALE S6O2 NOSCALE SC)OZ NOTE: NOTE: NOTE: NOTE: PROVIDE LATERAL BRACING FOR ALL INTERIOR PARTITION WALLS WHERE LENGTH BETWEEN PROVIDE LP,TERAL BRACING FOR ALL INTERIOR PARTITION WALLS WNERE LENGTN BETWEEN PROVIDE LATERAL BRACING FOR ALL INTERIOR PARTITION WALLS WHERE LENGTH BETWEEN PROVIDE LATERAL BRACING FOR ALL INTERIOR PARTITION WALLS WHERE LENGTH BETWEEN BONDED OR TIED CROSS WALLS EXCEEDS THE FOLLOWING: BONDED OR TIED CROSS WALLS EXCEEDS THE FOLLOWING: BONDED OR TIED CROSS WA�LS EXCEEDS THE FOLLOWWG: BONDED OR TIED CROSS WALLS EXCEEDS THE FO��OWING: 10 FEET FOR 4" MASONRY WALLS 10 FEET FOR 4" MASONRY WALLS 10 FEET FOR 4" MASONRY WALLS 10 FEET FOR 4" MASONRY WAL�S 12 FEET FOR 6" MASONRY WALLS 12 FEET FOR 6" MASONRY WALLS 12 FEET FOR 6" MASONRY WALLS STEEL JOIST OR BEAM 12 FEET FOR 6" MASONRY WA��S � STEEL JOIST OR BEAM 14 FEET FOR 8" MASONRY WALLS 14 FEET FOR 8" MASONRY WALLS 14 FEET FOR 8" MASONRY WALLS 14 FEET FOR 8" MASONRY WA��S COMPRESSIBLE FILLER, FIRE—SAFING, COMPRESSIB�E FI��ER, FIRE—SAFING, MAINTAIN MIN. 1" CLEAR ETC. REF. ARCN. DRAWINGS ETC. REF. ARCH. DRAWINGS AL� AROUND MUST PROVIDE FOR 3/4" MIN. OF TYP CAL g AT EACH CLIP � MUST PROVIDE FOR 3/4" MIN. OF COMPRESSION COMPRESSION � � � ,; � � I "`� � STEEL JOIST OR BEAM � �� L3x3x1�4 x 0'-6" LONG � ' < SPACED AT EACH ROOF ���,� ��g„ TYPICAL JOIST (MAX. 6'-6" O.C.) '�; �` DO NOT ATTACH TO WALL '��` INTERIOR MASONRY PARTITION WALL REF. ARCH. DRAWINGS WALL EXTENDED TO BOTTOM OF STRUCTURE WALL PERPENDICULAR TO PURLINS PARTITION BR;ACING DETAIL 16 NOSCALE S6OZ I STEEL ROOF DECK ��� ' a W � � �� � � � � � � � L2x2x1�8 FRAME " TYPICAL L2x2x1�8 FRAME � L5x3x1�4 LLV x 0'-6" LONG ���� AT EACH L5x3 � /, � AT EACH L5x3 � �8�� DO NOT A17ACH TO WALL �'' � STEEL JOIST OR BEAM TYPICAL TYPICAL �j" � a �� ;� `% �� L5x3x1 4 ��V x 0'-6" L5x3x1�4 LLV x 0'-6" � � � �%% � TYPICAL %� — SPACE AT MAX 6'-0" 0 C ��8„ SPACED AT EACH ROOF ' '' CEILING LINE—SEE ARCN. DWGS. JOIST (MAX. 6'-6" O.C.) CEILING LINE—SEE ARCH. DWGS. DO NOT ATTACH TO WALL �� � DO NOT ATTACH TO WA�� �� INTERIOR MASONRY PARTITION WALL INTERIOR MASONRY PARTITION WALL INTERIOR MASONRY PARTITION WALL REF. ARCN. DRAWINGS REF. ARCH. DRAWINGS REF. ARCH. DRAWINGS WALL EXTENDED TO BOTTOM OF STRUCTURE WALL EXTENDED TO ABOVE CEILING WALL EXTENDED TO A�OVE CEILING WALL PARALLEL TO PURLINS WALL PERPENDICULAR TO PURLINS WALL PARALLEL TO PURLINS PARTITION BR;ACI��TG DETAIL 1 � PARTITION B�;ACI�G DETAIL 18 PARTITIO� BR;ACING DETAIL 19 NOSCALE S(O2 NOSCALE S(O2 NOSCALE SCOZ CMU WALL PER ARCH. PLANS & DETAI LS NOTE: HORIZ. JOINT REINFORCING NOT SHOWN FOR CLARITY. CONTIN. VERTICAL WALL REINF. PER PLANS & DETAILS. USE REBAR POSITIONERS TO MAINTAIN VERTICAL REINF. IN CORRECT LOCATION WITHIN THE WALL. REF. SPECIFICATIONS FILL ALL REINFORCED CELLS SOLID WITN GROUT. DELAY APPROX. 5 MINUTES (TO AL�OW EXCESS WATER TO BE ABSORBED BY TNE CMU UNITS) AND THEN CONSOLI- DATE BY MECHANICALLY VIBRATING. SEE SPECIFICATIONS FOR ADDNL. REQUIREMENTS. MORTAR CROSS WEBS AT REINFORCED CEL�S MATCHING DOWELS LOW - LIFT WALL CONSTRUCTION s NoscaLE 5602 FILL W/ GROUT 4NCHOR @ 24" O.C. CMLT WALL - STEEL STLTD WALL lo NOSCALE 56�2 �STEEL PER P�AN GROUT COURSE ABOVE — BOND BEAM AS REQUIRED TO ENGAGE ANCHORS ALONG BOTTOM OF BEAM BOND BEAM — PER TYP. DT�. STEEL ROOF DECK PER PLAN STEEL BEAM PER PLAN ' L' CONTIN. BENT PLATE 5/16" x 6» �x 1'-6" w/ (2) 3/4" DIA. ADNE5IVE ANCHORS IN BOTTOM OF 2" VERT. S�OT (FINGER TIGNTED & FOUL THREADS, 6 MIN. EMBEDMENT) CMU WA�L w/ #5 @ 32" O.C. MIN. PER ARCH. DWGS. SHEAR WALL ADJACENT TO BEAM SI�EAR TRANSFER/LATERAL SLTPPORT C01�1NECTION 1 s NOSCALE 56�2 I 1'-0" I MASONRY OPENING - REF. ARCH. DWGS. I 1'-0° I LINTEL I)ETAIL OVER LOUV�R ALONG LI�E G Zo NOSCALE SCO2 �PECT ' SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TIT�E: TYPICAL DETAILS CERTIFIED BY: ��\Iilllll/// `\\\���� P . BR Utij��!��i�. � QQ��a•�F,G\STER�°�°soo��` �i = No. 890277 - � � e: STATE OF :• � ^- � i �.C`��'.,oND�ANP,mo���\�� ��//,/ s/O N W L � \\\\ � ui *���� a- , ; ,, � ,: , ., 1 #4 x 1'-6" LONG DOWELS Q 18" O.C. W/ 2-PART EPDXY ANCHORING SYSTEM. MIN. 6" EMBEDMENT F.F. TO MATCH EX. F.F. PER PLAN x x x x TURN SLAB DOWN 8" MIN. TO TOP OF EX. FOUNDATION �4 x 1'-6" LONG DOWELS @ 18" O.C. W/ 2-PART EPDXY ANCHORING SYSTEM. MIN. 6" EMBEDMENT EX. FOUNDATION WALL OR GRADE BEAM F.F. TO MATCH EX. F.F. PER PLAN x x x TURN SLAB DOWN 8" MIN. TO EX. FOUNDATION TOP OF EX. FOUNDATION WALL OR GRADE BEAM NEW SLAB AT EX. WALL 1 NOSCALE S(�3 STEEL ROOF DECK PER P�AN STEEL JOIST-SIZE PER PLAN NOTE: ATTACNMENT OF JOIST TO SUPPORTING SPANDREL BEAM PER SJI REQUIREMENTS CONTINUOUS PERIMETER ANGLE OR BENT PLATE (DIAPHRAGM CNORD) SIZE PER PLAN NOTE OR SPECIFIC FRAMING SECTION FASTEN DECK TO DIAPNRAGM CHORD W/ FUSION WELDS OR MECHANICAL FASTENERS MAINTAIN FASTENER SPACING TO MATCH ATTACHMENT AT SUPPORTING STRUCTURAL MEMBERS, I.E. 12" O.C. FOR 36/4 PATTERN, 6" O.C. FOR 36/7 PATTERN WELD TO BOTN ANGLES OF JOIST TOP CHORD \ �-I-I-� INSPECT ROOF DIAPI�RAGM CI�ORD DETAIL 6 NoscaLE 5603 � 1-1/2" WIDE RIB STEEL ROOF DECK ( GA. & FINISH PER PLAN � STEEL COLUMN PER -� P�AN OR SCHEDU�E KNEE BRACE DETAIL SCALE : N�ONE 36" COVER 36/4 PATTERN W/ SIDELA FASTENERS @ 24" O.C. M X. �5/16 TyP. EA. END INSPECT HSS4x4x5/16 KNEE BRACE TYPICAL U.N.O. (REF. 'KB' ON FRAMING PLANS) FINISNED CEILING PER ARCH. DWGS. HOLD 6" CL. ABOVE FINISHED CEILING, TYPICAL U.N.O. l� 5603 NOTE: 1. 1 1/2", 20 GA. GALVANIZED 8c PRIME-PTD WIDE RIB STEEL ROOF DECK. 2. DO NOT WE�D DECK TO SUPPORTING STRUCTURE. MECHANICAL FASTENERS MUST BE USED IN LIEU OF WELDS. USE THE FOLLOWING HILTI POWDER ACTUATED FASTENERS: USE X-HSN24 FOR FASTENING TO BAR JOISTS USE X-ENP-19 FOR FASTENING TO STRUCTURAL STEEL ACCEPTABLE ALTERNATE: PNEUTEK AIR-SAFE FASTENING SYSTEM SUBMIT PROPOSED FASTENERS & TECHNICAL DATA FOR REVIEW. USE �10 TEK SCREWS FOR FASTENING TO COLD-FORMED STEEL. SUBMIT PROPOSED FASTENERS & TECHNICAL DATA FOR REVIEW. 3. USE �10 TEK SCREW SIDELAP FASTENERS, U.N.O. 4. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. ROOF DECK PROFILE 14 NoscaLE 5603 1/2" ISOLATION JOINT F.F. TO MATCH EX. - X X X X THICKEN SLAB TO 8" AROUND PERIMTER AT EX. CONSTRUCTION F.F. PER PLAN EX. FOUNDATION WALL OR GRADE BEAM NEW SLAB AT EXISTING WALL 2 No scaz,� 5603 NOTE: ASSUME THAT A�L BENT PLATE SLP,B EDGES SHA�L BE FIELD WELDED AF7ER ADJUSTMENT TO MAINTAIN TOLERANCES AND REQ'D. CLEARANCES. SLAB C�OSURES FOR SNORT MEMBERS, OR FOR SLAB EDGES WHERE TOLERANCES ARE NOT CRITICAL MAY BE SHOP-WELDED PENDING APPROVAL OF TNE ENGINEER. THE FABRICATOR 8c ERECTOR SNALL COORDINATE ALL FIELD WELDING VS. SHOP WELDING AT THE TIME OF BIDDING. LACK OF FIE�D WE�D SYMBOLS ON SPECIFIC SECTIONS DOES NOT RELIEVE THE FABRICATOR/ ERECTOR FROM THE RESPONSIBI�ITY TO MAINTAIN TOLERANCES. � y SE PER PLAN CONT. BENT PL 1 /4" x x x x x � SLAB DEPTH 'X' NOTE: DETAI� SIMILAR FOR *NOTE: NOLD NORIZONTAL LEG OF DECK PARALLEL TO BEAM BENT PLATE CLOSURE 1° LESS TNAN OVERLAP PER SLAB EDGE WHILE MAINTAINING 2" MIN. STEEL BEAM ADJ. NOTE OVER�AP TO ACCOMMODATE FIELD- PER PLAN INSTA��ED COMPOSITE SHEAR STUDS. WHERE BEAM FLANGES ARE LESS THAN 6", OVER�AP MAY BE REDUCED TO 1" MIN. 1/2" DIA. x 8" LONG HEADED ANCHOR STUDS AT 18" O.C. �4 x 4'-0" LONG AT 18" O.C. SE 6" TO 12" w/ 180" STD. HOOK � x� x x x x CONT. BENT PL 1/4" � SLAB DEPTN NOTE: DETAI� SIMILAR FOR X DECK PARALLEL TO BEAM OVERLAP PER STEEL BEAM -����� ADJ. NOTE PER PLAN 1/2" DIA. x 8" LONG HEADED NOTE: INCREASE 't' OF BENT PL TO 3/8° AT ANCHOR STUDS AT 12" O.C. ALL SLAB EDGES SUPPORTING HANDRAIL OR �4 x 4'-0" LONG AT 12" O.C. SE >_ 12" BRICK RELIEF ANGLE. PROVIDE 1/2" DIA. w/ 180" STD. NOOK H.A.S.'s Q 12" O.C. w/ #4 HOOKED REBAR, � REGARDLESS OF S.E. DIMENSION U x __ x _x x �-- CONT. BENT PL 1/4" � SLAB DEPTH NOTE: DETAIL SIMILAR FOR X DECK PARALLEL TO BEAM OV LAP PER STEEL BEAM J. NOTE PER PLAN 1/4" GUSSET PL @ 48" O.C. NOTE: SE = SLAB EDGE PER PLAN BENT PLATE SLAB CLOStJRE DETAILS � NOSCALE 56�3 CONTINUOUS 20 GA. COVER PLATE, SAME STEEL ROOF DECK MATERIAL AS DECK TS2 ,�2 X ��8 DETAIL R WHERE REQUIRED FOR DECK SUPPORT BEAM OR JOIST CONTINUOUS 20 GA. PER PLAN BEAMS PER PLAN COVER PLATE, SAME MATERIAL AS DECK �-rrn nnnr DECK CONTINUOUS 20 GA. COVER PLATE, SAME STEEL ROOF DECK MATERIAL AS DECK BEAMS PER PLAN �2.5x2.5x1/4 FOR DECK SUPPORT DETAIL C BEAM OR JOIST � PER PLAN BEAM PER PLAN CI�ANGE OF ROOF DECK DIRECTION 11 NoscaLE 5603 NEW SLAB ON GRADE EX. SLAB ON GRADE "t" VARIES PER PLAN "t" VARIES F.F. TO MATCH EX. F.F. PER PLAN x x x x x x #4 x 1'-6" LONG DOWELS @ 18" O.C. W/ 2-PART EPDXY ANCHORING SYSTEM. MIN. 6" EMBEDMENT NEW TO EX. SLAB DETAIL 3 NoscaLE 5603 STEEL ROOF DECK PER PLAN GALV. 16 GA. COVER PLATE FOR SQUARE OR ROUND OPENINGS WITN SIZES AS NOTED BELOW #8 TEK SCREWS-FASTEN � � TO EACH RIB %%� � \ rr . � i �. �� \ - , �� .�,' \ ... . ... ...... �.. � NOTE: PROVIDE SIMILAR COVER PLATE DETAIL FOR SINGLE DAMAGED RIB-CONSULT ENGINEER FOR DIRECTION WHERE MORE THAN ONE ADJ. RIB IS DAMAGED 1.5" DECK: NOLES LESS THAN 6" IN WIDTH (ONE RIB REMOVED) DO NOT REQUIRE REINFORCEMENT. REF. TYPICAL ROOF OPENING FRAME DETAIL FOR OPENINGS W/ MAX. DIMENSION EXCEEDING 12". SMALL ROOF OPENING DETAIL s NoscAZE 5603 NOTE: IF THE OPENING IS POST-INSTALLED A�ER THE SLAB IS POURED, THE CLIP ANG�ES MAY BE OMITTED AND THE CHANNELS MAY BE CONNECTED DIRECTLY TO TNE BEAM WEB. COORD. W/ G.C. COORD. W/ G.C. � 1/4" x 7" x CONT. PL POUR STOP � FLOOR OPENING STEEL BEAM- -����- � � = _I SIZE PER PLAN C6x8.2 FRAME L7x4x3/8 x 0'-8 W/ MIN. 3" BRG. ON STEEL BEAM OR GIRDER P.T. 2x4 x 6" MIN. - WEDGE IN RIB UNDER CONCENTRATED LOAD N x Q �� o z i � N N x Q � � o z I � N � W m N -I � � W W z � � Q � = WW ~ c� � � z � � N W � � W � o � � z �_ � o � � i� � 0 o� i� �o � = z U X z � Q ¢ _ o� �� �' z J i o �� z w ,� �, _ - �"� N � � � � �z o � o� cv z c� STEE� COLUMN PER PLAN CONCRETE PIER OR FOOTING HEAVY HEX DOUBLE NUTS w/ PL 5/16" x 2 1/2" x 2 1/2" WASHERS. WELD AFTER ERECTION HEAVY HEX NUT-TACK ��� WELD TO ROD NOTES: 1. LOCATION OF ANCHOR RODS MUST NOT VARY MORE TNAN 1/8" CENTER- TO-CENTER OF ANY TWO BOLTS WITHIN AN ANCHOR BOLT GROUP. 2. HOLD MAX. DEVIATION OF 1/4", CENTER-TO-CENTER OF ADJACENT ANCNOR BOLT GROUPS. 3. HOLD ELEVATION OF TNE TOP OF TNE ANCHOR RODS TO +/- 1/2 INCH. 4. HOLD MAXIMUM DEVIATION OF 1/4" FROM THE CENTER OF ANY ANCHOR BOLT GROUP TO THE ESTABLISHED COLUMN LINE THROUGH THAT GROUP. 5. REFER TO TNE AISC CODE OF STANDARD PRACTICE FOR ADDITIONAL INFORMATION. 6. TESTING AGENCY TO INSPECT TIGHTENING/TENSIONING OF ALL ANCNOR ROD NUTS IN BRACED FRAMES AND MOMENT FRAMES. WELD NUT & WASHER AFTER INSPECTION. 7/8" DIA. ANCI�OR ROD DETAIL 4 No scaz,� 5603 DIA. HO�ES FOR )IA. F1554-36 RODS 't' = 1%" FOR HSS5x5 ' 't' = 1�2" FOR HSS8x8 ' %"x�" WASHERS- ' LD NUT-TO-WASNER ' NER-TO-BASE PL , �NTENING & , )N ' I�SS BASE PLATE DETAIL s NO SCALE 56�3 STEE� JOIST OR BEAM-SIZE PER PLAN NOTES: L4x4x1/4 RAME 1. PROVIDE ANGLE FRAME AS SHOWN FOR ALL ANGLES TO BEAR A MIN. OF 3" ON ROOF OPENINGS IN 1 1/2" WIDE RIB DECK z JOIST TOP CHORD OR BEAM WITH MAXIMUM DIMENSION EXCEEDING 1'-0". Q TOP FLANGE � 2. USE: L4 x 4 x 1/4 TYPICAL. � COPE VERTICAL �EGS OF ANGLES o WITHIN 1" OF EDGE OF JOIST 3. COORDINATE LOCATION OF ROOF OPENINGS WITH ROOF OPENING- z CHORD OR BEAM F�ANGE ROOF OPENING-COORD. SIZE & MECHANICAL AND ARCHITECTURAL DRAWINGS. COORD. SIZE W/ � LOC'N. W/ MECHANICAL TRADES MECH. CONTR. w � ANG�ES TO BEAR A MIN. OF 3" ON JOIST TOP CHORD OR BEAM TOP FLANGE STEEL JOIST OR BEAM-SIZE PER PLAN 1'LAl`1 L4x4x1/4 ANGLE FRAME COORD. W/ MECN. COORD. W/ MECH. PROVIDE FOR A�� OPENINGS W/ MAX. DIMENSION EXCEEDING 12" 1 1/2" WIDE RIB � ROOF DECK ROOF OPENING STEE� JOIST OR BEAM-SIZE �c /� SPACING PER PLAN - -- - - � - STEEL JOIST OR BEAM-SIZE & ISOMETRIC SPACING PER P�AN � L4x4x1/4 FRAME � MAINTAIN COPE OF VERTICAL LEG WITNIN 1" �� OF EDGE OF JOIST CHORD OR BEAM FLANGE SECTION TYPICAL ROOF OP�NING F�:AM� I)�TAIL, 1.5" DECK 9 NOSCALE 56�3 �4 x 1'-6" IN SLAB @ EACH 36" COVER � / �CORNER OF OPNG. � �` FOR CRACK CONTROL ¢ � o � � � � NOTE: 6 FRAME ONLY REQUIRED FOR OPENINGS OVER 12" WIDE �ENDICULAR TO DECK S�AN \ � / C6x8.2 FRAME C�IP �7x4x3/8 x 0'-8" TYPICAL � I i¢ W FLOOR OPENING- m � COORD. SIZE W/ � � GENERAL CONTR. "' � wW c� n- z � N � �„ I � SEE P�AN FOR SPACING SECTION PLA � SLAB-ON-DECK OPENI��TG F�;AME DETAIL IZ NOSCALE 56�3 >200 LBS _> 6" ,_ PROVIDE MOME T CONNECTION WIDE RIB STEEL WHERE REFERE CED ON P�AN ROOF DECK STEEL COLUMN PER � ,--� ,--�I P�AN OR SCHEDULE � 6" ��- 2-L2x2x3/16 ADDNL. DIAGONALS AT EACH CONCENTRATED LOAD STEEL JOIST >200 LBS 1. LOADS LESS THAN 200 LBS. MAY BE LOCATED ANYWNERE ALONG THE TOP OR BOTTOM CHORD OF THE JOIST WITHOUT REQUIRING REINFORCEMENT. 2. PROVIDE TNIS DETAIL WHERE SUSPENDED EQUIPMENT, MECHANICA� UNIT, OR PIPING IMPARTS A CONCENTRATED LOAD OVER 200 LBS. IF THE LOAD IS APP�IED WITHIN 6" OF A TOP OR BOITOM CHORD PANE� POINT, NO REINFORCEMENT IS REQUIRED. 3. NO CONCENTRATED LOADS GREATER THAN 200 LBS. WILL BE AL�OWED WITHOUT THE WRITTEN APPROVAL OF THE ARCNITECT/ENGINEER. JOIST CONCENTRATED L4AD DETAIL 1 s NOSCALE 56�3 � . v� d Q� � � . . � , � ' . a X. � . X Q i� i�� 4a( d' X �- X � X a '� d . p . ' ��' , . � p Q ' . � /��1a ��1 ��1 /%1\ ,(��1 /�� a T T T NOTE: 1. 1 1/2", 20 GA. GALVANIZED COMPOSITE STEEL FLOOR DECK-REF. PLANS & SCHEDULE. 2. WELD DECK TO SUPPORTING STRUCTURE USING 3/4" DIAMETER WE�DS. 3. MECNANICALLY FASTEN SIDELAPS @ 36" O.C. MAX. w/ �10 TEK SCREWS. 4. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 5. SIDELAPS MAY BE NESTING, OR INTERLOCKING AT CONTRACTOR'S OPTION. 6. MAXIMUM UNSHORED CLEAR SPANS SNALL NOT EXCEED THE FOLLOWING: SINGLE SPAN 6'-0" TWO SPAN 8'-1" THREE SPAN 8'-2" NOTE: THE SPANS ABOVE ARE BASED ON THE USE OF VU�CRAFT VL/VLI 20 GA. DECK. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONFIRM THAT ALTERNATE DECK PRODUCTS MEET, OR EXCEED TNE SPANS LISTED ABOVE. CONTRACTOR SNALL SHORE ALL SPANS EXCEEDING THE LIMITS ABOVE UNTIL CONCRETE HAS ACNIEVED ITS SPECIFIED 28 DAY COMPRESSIVE STRENGTN. COMPOSITE SLAB/DECK PROFILE 13 NOSCALE 56�3 � z � � STEEL COLUMN � o �� PER PLAN EX. CONCRETE PIER OR FOOTING �o 00 �� � Qo 0 � w � � SNIM COLUMN BASE �� `'� zv � _ � �� i � � �~ � �� � w O 0 J � O O o�� HEAVY HEX NUTS w� PL 5/16" x 2 1/2' x 2 1/2" STEEL BEAM PER PI�,N - STEEL BEAM PER PLAN N�� WASNERS. WELD AFTER ERECTION NOTES: NQTE: BEAM OR JOIST FRAMING TOP L8x4x3/4 x COLUMN SIZE + 1" INTO WEB OF COLUMN NOT W/ (4) 3/4" DIA. A325 FULLY- 1. DRILL & GROUT THREADED ANCHOR RODS SOLIDLY INTO EX. CONCRETE SHOWN FOR CLARITY TENSIONED (F.T.) BOLTS USING HILTI HY-150, OR APPROVED 2-PART EPDXY ANCHORING SYSTEM. TEST/ 5/16 2. WHERE COLUMNS ARE TO BE INSTALLED BETWEEN TWO FIXED ELEVATIONS, INSPECT SUCH AS BETWEEN THE BOTTOM OF AN EXISTING BEAM AND THE TOP OF T/B PER PLAN AN EXISTING FOUNDATION, THE ANCHORS MAY BE INSTALLED A�fER THE COLUMN IS TEMPORARILY SET IN PLACE. IT IS TNE RESPONSIBILITY OF THE STEEL ERECTOR TO ADEQUATELY BRACE THE COLUMN UNTIL THE 0 ANCHOR BOLTS CAN BE INSTALLED AND TIGNTENED. O O O O 3. THIS DETAI� SNA�L BE USED ONLY FOR CONNECTION OF COLUMNS TO EXISTING FOUNDATIONS AND NOT FOR NEW COLUMNS SUPPORTED ON STEEL BEAM PER PLAN � � STEEL BEAM PER PLAN NEW FOUNDATIONS. I REFA NOT�ESNONTI0001 7/8" DIA. POST-INSTALLED ANCHOR BOLTS STEEL COLUMN PER BOT. L8x4x3/4 x CO�UMN SIZE + 1" P�AN OR SCNEDULE W/ (4) 3/4" DIA. A325 FULLY- TENSIONED (F.T.) BO�TS BEAM-TO-COLUl�'��T 1��I0MENT COI�INECTION 16 ANCI�t�R BOLTS TO EX. FOLT��TDATIONS N�o scaLE 5603 scaLE : NONE l� 5603 ��'���� y}: � � S�--.� ». r r �� M M t � � �` :: d" rl" wj �� r� r: �� � �_ �,... r r : 3 , .� M C� `-a� co 0 � N �� �� Qz � .� 'c o -�, Q � '> c cti O � .s a,sa„ '� „�.rk7s�v:. � G SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TIT�E: TYPICAL DETAILS CERTIFIED BY: �����iii���i� \\����� P . BR Utij��!��i�. � QQ��a •�F,G\STERE `� �oo ��` �i = No. 890277 - � � e: STATE OF :• � ^- � i �.C`��'.,oND�ANP,mo���\�� ��//,/ s/O N W L � \\\\ � ui *���� a- , ;,, � �� ' .� � GAB�E END OR CFS WAI 0 ► i� ��I SCALE: � • � i . � � . • ' ' None �rc� -rrn ic-c- Tnn ni ir�RD CONNECTION �G FRAME I/2" FLANGE FOR ROOF DECK CLIP ANG�E CONN. CAL � NOTES: 1. PROVIDE CFS STUD FRAME FOR A�� ROOF OPENINGS WITH LARGEST DIMENSION EXCEEDING 1'-0". COORD. SIZE & LOCATION W/ MECHANICAL TRADES. 2. ROOF DECK NOT SHOWN FOR CLARITY. IYPICAL 4"-0" TRUSS SPACING Typical Roof �penzn� Detail SCALE: None �ACES AT �. USE DIAGONALS OF EACH RUN OF D AT THE SPACING BOTTOM CHORD BRACING AS REQ'D. BY TRUSS SUPPLIER MECHANICAL UNIT SUPPORT, PI TRAPEZE, ETC. BY MECH/ELEC. CONTRACTOR AS F LATE AT � ' � � � � / � � 5604 % SCALE: None TUBULAR BLOCKING WITHIN BOTTOM CHORD, SEE NOTE #5 BELOW UNISTRUT CHANNEL SPANNING BETWEEN TRUSSES BY MECH. OR ELEC. CONTRACTOR. CONTRACTOR SHALL LAYOUT CHANNELS SO THAT NO CONCENTRATED LOAD TO TRUSS BOITOM CHORD EXCEEDS 204 POUNDS 1. CONTRACTORS SNA�L NOT CUT OR DRILL NO�ES FOR NANGER RODS OR BOLTS 5 IN TRUSS MEMBERS UNLESS SNOWN ON THE APPROVED COLD—FORMED TRUSS SHOP DRAWINGS, OR APPROVED BY THE FABRICATOR IN WRITING. 2. CONTRACTORS MAY SCREW TO TNE SIDES OF CHORD MEMBERS FOR SUPPORT OF LIGHTER (LESS THAN 100 LBS.) LOADS USING �12-16 SCREWS. 6 3. DO NOT SCREW INTO THE BOTfOM OF THE TRUSS CHORDS (I.E. SCREWED CONNECTIONS IN TENSION). L��IIl��►[�1t:11I:1���11�[�k11I:»:i�1��1:ill.`I.'l�i►I�:��il��il:l�:i.`�:3:7UItll�[!i.'�:3:7RIll�[!I �ACES AT . USE DIAGONALS OF EACN RUN OF D AT THE SPACING niAr,n�iAi RRA�F� AT TRIISS UNISTRUT CHANNEL SPANNING BETWEEN TRUSSES BY MECN. OR ELEC. CONTRACTOR. CONTRACTOR SNALL LAYOUT CHANNELS SO THAT NO CONCENTRATED LOAD TO TRUSS BOTTOM CHORD EXCEEDS 200 POUNDS MECHANICAL UNIT SUPPORT, PIPE TRAPEZE, ETC. BY MECH/ELEC. CONTRACTOR THE TRUSS FABRICATOR SNA�L SUPPLY 300 LINEAL FEET OF 1-1/2" x 4" TUBULAR WEB MEMBER MATERIAL FOR USE AS BLOCKING FOR ATTACHMENT BY MECHANICAL, ELECTRICAL & SPRINKLER TRADES. BLOCKING TO BE FASTENED TO TNE BOTTOM CHORD W/ A MIN. OF (2) �12-16 SCREWS PER PIECE OR 16" ON CENTER, WHICHEVER IS GREATER. TRUSSES SHA�� BE DESIGNED TO SUPPORT A 200 POUND CONCENTRATED LOAD LOCATED ANYWHERE A�ONG THE TRUSS BOTTOM CHORD. SEE TRUSS FRAMING NOTES. �� ��� ��� �� � SCALE: None STEEL ROOF DECK SCA�E: None TUBULAR TRUSS WEB MEMBERS UNISTRUT CLIP W/ SCREWS TO TUBULAR BLOCKING WITHIN TRUSS BOTfOM CHORD TUBULAR BLOCKING WITHIN BOTTOM CHORD, SEE NOTE #5 BELOW PRE-ENGINEERED, PRE-FABRICATED COLD-FORMED STEEL TRUSSES 1. Structural Performance: Design, engineer, fabricate and erect cold—formed steel trusses to withstand specified design loads within limits and under conditions required. A. Gravity Loads Top chord �ive load — 22 psf + drift loads Dead load — 10 psf Additional 5 psf at overbuild framing areas Bottom chord Dead load — 8 psf Collateral load — 5 psf In addition to bottom chard uniform dead load, design the bottom chords to support a concentrated, non—concurrent load of 200 pounds located anywhere along the bottom chord. B. Wind Loads Per 2014 Indiana Building Code. See 'Design Criteria Notes' for wind design criteria. C. Seismic Loads Per 2014 Indiana Building Code. See 'Design Criteria Notes' for seismic design criteria. D. Deflections: Roof Trusses Vertical deflection less than or equal to 1 360 of the span under live load, and 1/240 of t e span under total load. 2. See sheet S001 for Structural Notes & Design Data. 3. All Contractors are required to coordinate their work with all disciplines to avoid conflict. The mechanical, electrical and plumbing aspects are not in the scope of these drawings, therefore all required materials and work may not be indicated. 4. All cold formed steel framing (CFS) member sizes, connection, bridging, and bracing is schematically indicated. Fabricator shall engineer, fabricate, and erect cold formed steel framing to withstand design loads within limits and under conditions required. Refer to Spec. 05 45 00 for additional information. 5. Spacing of trusses shall be 4'-0" o.c. max., u.n.o. 6. Provide 2 1/2", CSJ 20 GA. continuous lateral bridging w/ (2) �10-16 screw per intersection at all truss panel points, u.n.o. 7. Provide continuous hat channel bridging across bottom chords of trusses as required (in lieu of ceiling attachment). Size and spacing per truss supplier. � U w � O � a ��'���� y}: � � �� r r r.i M M t � � � dN" ��„ . , �3 t,�1� t� 1� <.a�..� _ �,�_ r r 3 , M C� " � I . L co 0 � N � � � � QZ t� .� �c O -� a c� > _ c� o� � ��,,,.. �; r,.r��:: � c O -p O � � �G ' v M v O � � > � t!{ = Z ti? � �O � O `- � U SCOPE DRAWINGS: These drawings indicate the general scope of the project in terms of architectural deslgn concept, the dimensions of the building, the major architectural elements and the type of strucfural, mechanical and elecfrical systems. The drawings do not necessarily indicofe or describe alI work required for full performonce and completion of ihe requirements of the Contr�ct. On the basis of the general scope indicoted or described, the tr�de controctors shall fumish oIl items required for the proper execution ond completion of Che work. REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TIT�E: TYPICAL DETAILS CERTIFIED BY: �����iii���i� \\����� P . BR Utij��!��i�. � QQ��a •�F,G\STER� °�°so0 ��` �i = No. 890277 - � � e: STATE OF °• � ^- � i �.C`��«.aoND�ANPomo���\�� ��//,/ s/O N � L � \\\\ � �ii *i�i� TYP. U.N.O. @ LINES D3 & DH @LINESM&S MASONRY VENEER PER ARCH. DWGS. FINISHED GRADE PER CIVI� DWGS. T/SLAB PER PLAN �, __."�---.._a.._ .4.�____ ,,,__ _ 6" + 8" CMU, -----__. GROUT CORES SOLID T/WALL FTG. PER P�� N CENTER ON TRENC w � � 0 W _ U � � � � W � 10%" METAL STUD WALL PER ARCH. DWGS. 8" CMU BOND BEAM PER TYPICAL DETAIL Y" EXPANSION MATERIAL SLAB ON GRDAE PER PLAN x x x x x RIGID INSULATION PER ARCH. DWGS. 4 #4 DOWELS w/ 4" HOOKS �., @ 48" O.C. N \i WALL FOOTING PER PLAN REF. �fG. SCH'EDULE SECTI�N 1 3/4" = 1'-0" 57�1. DOOR PER ARCH. DWGS. EXTERIOR SLAB PER CIVIL DWGS� T/SLAB PER PLAN 8" CMU, GROUT CORES SOLID T/WALL FTG. PER PI w � 0 W _ � � � � � W � 'l■! . . . REF. �fG. SCHEDULE Y" EXPANSION MATERIAL SLAB ON GRADE PER PLAN — x x RIGID INSULATION PER ARCH. DWGS. 24" 24" �4 DOWELS @ 16" O.C. � i N WALL FOOTING PER PLAN SECTION 6 3/4" =1'-0" S7� 1. I f EX. CMU & BRICK WA�L ( —x— x— I EX. CONC. FOUNDATION WALL . . T/EX. FTG. —2'-0"± (FV) . EX. WALL FOOTING B/NEW FTG. TO MATCN B/EX. FTG. TYP. U.N.O. 10%" @ LINES D3 & DH 11%" @ LINES M & S 1'-0'' ( � FACE OF MASONRY ►-� VENEER BEYOND ( ( I FINISHED GRADE ( PER CIVIL DWGS. � T�SLAB PER PLAN � .,�-. _ . _____ �______� �._ ___ ( �. 8" CMU, GROUT ( CORES SOLID �-� I � T/WA�� FTG. PER Pf N 11%" w J � 0 W _ U � � � � w � o a STEEL COLUMN PER P�AN Y" EXPANSION MATERIAL SLAB ON GRADE PER PLAN T/SLAB PER PLAN x x x x x PROVIDE %"� POST-INSTALLED ANCHOR BOLTS (PER TYP. DETAI�) T/FTG. PER P�AN SECTION 10 3/4" � 1'-0" 57�1. COL. FTG. REINF. PERP. TO EX. F1G. TO BE EPDXY DOWELED INTO FACE OF EX. FTG. (6" MIN. EMBED.) WINDOW SYSTEM PER ARCH. DWGS. 6" CMU BOND BEAM PER TYPICAL DETAIL %" EXPANSION MATERIAL SLAB ON GRADE PER PLAN x x x x x RIGID INSULATION PER ARCH. DWGS. t�,,, 4 i �' �4 DOWELS w/ 4" HOOKS �,, `o � @ 48" O.C. N C � ■ / � SECTION 2 3/4" = 1'-0" 57�1. MASONRY VENEER PER ARCH. DWGS. EX. CONC. COLUMN EXTERIOR WA�K PER CIVIL DWGS� 6" + 8" CMU, GROUT CORES SOLID WALL FOOTING PER PLAN MASONRY VENEER PER ARCH. DWGS. EXTERIOR WALK PER CIVIL DWGS. T/SLAB PER PLAN 8" CMU, GROUT CORES SO�ID T/WALL FTG. PER P�AN � 2» � 0 W _ � � � w � � — -!-• METAL STUD WALL I / PER ARCN. DWGS. 8° CMU BOND BEAM PER TYPICA� DETAIL %" EXPANSION MATERIAL j SLAB ON GRADE PER PLAN T/SLAB PER PLAN x x x x x �. ol __ f, I I v RIGID INSULATION PER 4 ' ARCH. DWGS. > f I I %; I I ---- �5 DOWELS w/ 4" NOOKS —� I �I, ��/ I� @ 48" O.C. T/EX. FTG. —2'-0"± (FV) `9 EPDXY DOWEL BARS INTO TOP � OF EX. FTG. (6" MIN. EMBED.) I _ EX. COL. FOOTING 1'-0" 3'-0» INTERIOR MASONRY VENEER PER ARCH. DWGS. SLAB ON GRADE PER � PLAN x x x x x TURN SLAB DOWN TO T/FTG. @ INTERIOR � � � '� MASONRY VENEER 4 �4 DOWELS w/ 4" NOOKS � � Q 48" O.C. N ' ��— RIGID INSU�ATION PER ' I ARCH. DWGS. — WALL FOOTING PER PLAN SECTION 3 3/4" = 1'-0" 57�1. SECTION 7 3/4" =1'-0" S7� 1 I - STEEL CO�UMN PER PLAN EX. CMU & BRICK WALL � Y" EXPANSION MATERIAL SLAB ON GRADE PER PLAN T SLAB PER PLAN —x— x x x x x x ( PROVIDE %"4 POST-INSTALLED T/EX. FTG. -1'-0"± (FV) ANCHOR BOLTS (PER TYP. DETAIL) T/FTG. PER PLAN ,,, _,,,,,,,,,, p COLUMN FTG. � PER PLAN COL. F7G. REINF. PERP. TO EX. FTG. TO BE EPDXY DOWELED INTO FACE OF EX. m �fG. (6" MIN. EMBED.) > I EX. WALL FOOTIN B/NEW FTG. TO MATCH � � B/EX. FTG. SECTION 11 3/4" = 1'-0" S7� 1. I 0� n � _ � ,,,,,� -- � � �- __.. .,.- � I I I MASONRY VENEER , ; I , PER ARCH. DWGS. � � � I I EX. CONC. COLUMN — � ( BEYOND ( � ( ( EXTERIOR WA�K PER CIVIL DWGS. � � � I I i I I � I' I I ( #4 DOWELS @ 12" O.C. � I ( I � � MAX. ALONG EDGE OF � NEW COL. �fG. ( . . T/EX. FTG. —2'-0"f (FV) ( � 4„ � EX. COL. FOOTING B/NEW FTG. TO MATCH B/EX. F7G. I I I ( FACE OF MASONRY —� VENEER BEYOND � I I FINISHED GRADE � PER CIVIL DWGS.� ' \ T/SLAB PER PLAN ( ( 8" CMU, GROUT --- � CORES SOLID ( I T/WALL FTG. PER PLAN � 2„ � 0 w _ U (/� � w � � WINDOW SYSTEM PER ARCN. DWGS. 6" CMU BOND BEAM PER TYPICAL DETAIL %" EXPANSION MATERIAL SLAB ON GRADE PER PLAN x x x x x RIGID INSULATION PER ARCH. DWGS. v.; ��� 4 �% #4 DOWELS w/ 4" HOOKS � `9 Q 48" O.C. N WALL FOOTING PER PLAN 3'-0" SECTION 4 3/4" = 1'-0" S']�j METAL STUD WALL PER ARCH. DWGS. STEEL COLUMN PER P�AN %" EXPANSIdN MATERIAL S�AB ON GRADE PER PLAN T/S�AB PER PLAN x x x x x PROVIDE %"� POST-INSTALLED ANCHOR BO�TS (PER TYP. DETAIL) T/F�fG. PER P�AN SECTION s 3/a �� —1,_0,� 5701. I I ;I I I I EX. 1 st FLOOR I I SLAB I I I I I I I I L � 12" CMU LINTEL � NORIZ. IN WAL� BEYOND TO BE DOWELED INTO FACE OF EX. BASEMENT WA�L EX. CONC. BASEMENT WALL EX. BASEMENT SLAB l -a a � o . � —COLUMN FTG. PER PLAN �WALL FTG. PER PLAN � COL FTG. REINF. PERP. TO EX. FTG. TO BE EPDXY DOWELED INTO FACE OF EX. FTG. (6" MIN. EMBED.) 12" CMU w/ �5 @ 24" O.C. MAX. •—MASONRY VENEER PER ARCH. DWGS. 8" CMU w/ #5 @ 24" O.C. MAX. T/CONC. WA�� PER ARCH. DWGS. �ili■ll�i[��i REF. ARCH. DWGS. FOR LOCATION, DIMENSIONS AND ELEVATIONS OF AREAWAY 12" CONC. WALL w/ #5 @ 12" O.C., EACH WAY, EACN FACE T/EX. �fG. FIELD V'FY AREAWAY FOUNDATION . . w/ �5 @ 12" O.C. EACN WAY, TOP & ' =—=— BOTTOM EX. WALL FOOTING F7G. REINF. PERP. TO EX. F�G. TO BE EPDXY DOWELED B/NEW FTG. TO MATCH INTO FACE OF EX. FTG. (6" B/EX. F7G. MIN. EMBED.) AREAWAY DETAIL 12 3/4" = 1'-0" S']O1 DOOR PER ARCH. DWGS. EXTERIOR SLAB PER CIVI� DWGS. T/SLAB PER PLAN ; 6" + 8" CMU, --�__ GROUT CORES SOLID � �r' I I I I <, ! T�WAL� FTG. PER P�,� N ��^ CENTER ON TRENC FTG. 1'-1% w J � 0 W _ U C/) � � w w � a o 0 ( REF. �fG. SCHEDULE ___ _—_ �' ��, ,-- . �. ' _ � I I I I I I I I I EX. CONC. COLUMN � 1 IN FOREGROUND I I SECTION s 3/4" = 1'-0" 57�1. Y" EXPANSION MATERIAL SLAB ON GRADE PER PLAN � x x RIGID INSULATION PER ARCH. DWGS. 24" 24,� �4 DOWE�S @ 16" O.C. � i N WALL FOOTING PER PLAN - STEEL COLUMN PER P�AN %" EXPANSION MATERIAL ( I ( I S�AB ON GRADE PER PLAN ( ( T SLAB PER PLAN x x x x x x x x x x x ' � PROVIDE %"� POST-INSTALLED ( ( ANCHOR BO�TS (PER TYP. DETAIL) �4 DOWELS � 12" O.C. � I ( MAX. ALONG EDGE OF T/F7G. PER P�AN NEW COL FTG. ( . . T�EX. FTG. -2'-0"± (FV) � � 4„ � EX. COL FOOTING B/NEW FTG. TO MATCH B/EX. �fG. SECTION 9 3ia �� —1,_0,� 5701. '� 1�..., COL. FTG. REINF. PERP. TO EX. FTG. TO BE EPDXY DOWELED INTO FACE OF EX. FTG. (6" MIN. EMBED.) w � 0 � a SCOPE DRAWINGS: These araw�ngs �ndicate the general scope of the project In terms of architectural deslqn concept, the dimenslons of the build�ng the major r,rchitectural elements an� the type of sfructural, mechanical and electrical systems. The drewings do not necessarily indicate or describe all work required ,or full performance and completion of the requirements of the Controct. On the basis of the general scope indicated or described, the trade contractors sholl fumish ali Items required for the prc�per execuCic�n and compleClon of the wc�rk REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TITLE: SECTIONS AND DETAILS CERTIFIED BY: ����uiiiiii� \\����� P . B R (ltij��!��i�. � Q�o•��G1STE/?F�'.o��` �i Q = No. 890277 - � � oS STATE OF :e � = � � �.(��amo,e�/MDI�ANP,.°"� ��� F � �� ,�����S,��N •L � ���\. � i�� ii�� �- i� ��� ^j i—�� ��, )1 , � �� � ,� ( �,i ( .� 1 C3x5 VERT. @ 4'-0" O.C.— WITHIN STUD SPACE, SCREW TO ADJACENT STUD L6x4x%6 CONTIN. ---____, T/STEEL PER PLAN � � STEEL BEAM PER PLAN — MASONRY VENEER PER ARCH. DWGS. STEEL ROOF DECK PER PLAN STEEL BEAM PER PLAN STEEL JOISTS PER PLP,N DEEP LEG DEFLECTION TRACK BY CFS SUPPLEIR MASONRY VENEER PER ARCH. DWGS. = CFS STUD WALL PER ARCN. DWGS. S�CTIO� 1 3/4" = 1'-0" S%�2 4„ 10 GA. BENT P�ATE � CONTIN., SCREW TO TOP CHORDS OF CFS TRUSSES MASONRY VENEER PER ARCH. DWGS. 10%" 8» STEEL ROOF DECK PER PLAN -- 12 4 C� . " � II � 0 �CFS TRUSSES PER PLAN WELDED TRUSS CLIP BY TRUSS SUPPLIER STEEL BEAM PER PLAN � DEEP LEG DEFLECTION " TRACK BY CFS SUPPLEIR ''-� CFS STUD WAL� PER _ ARCH. DWGS. SECTION � 3�4 -1-o s�a2 O I C3x5 VERT. @ 4'-0" O.C. WITHIN STUD SPACE, SCREW TO ADJACENT STUD STEEL ROOF DECK PER PLAN DEEP LEG DEFLECTION TRACK BY CFS SUPP�EIR CFS STUD WALL PER ARCH. DWGS. S�CTIO� 2 3/4" = 1'_0" S%�2 4���-- 10 GA. BENT PLATE � � CONTIN., SCREW TO TOP 10" CHORDS OF CFS TRUSSES MASONRY VENEER PER ARCH. DWGS. s�cT1oN 13 3/4" = 1'-0" S%�2 12 � 12 I _ STEEL ROOF DECK � PER PLAN CONTIN. 16 GA. —� STRAP WELDED 10 GA. PLATE ASSEMBLY x CONTIN., 5" 4 10" SCREW TO TOP CHORDS �" OF CFS TRUSSES �STEEL PER PLAN MASONRY VENEER PER ARCH. DWGS. C12x20J CONTIN. IN� DECK FLUTES FOR BRICK SUPPORT STEEL ROOF DECK � PER PLAN STEEL JOIST PER PLAN� JOISTS ALONG LINE D1-� TO BE DESIGNED TO SUPPORT A BRICK POINT LOAD = 625� AS SHOWN g 8„ i 6" 14 GA. SNEAR BRAKE (BETWEEN EVERY OTHER TRUSS) ( 800S200-68 (BETWEEN �" EVERY OTHER TRUSS) CFS TRUSSES PER P�AN STEEL BEAM PER PLAN 3 � DEEP �EG DEFLECTION TRACK BY CFS SUPPLEIR � � CFS STUD WALL PER ARCH. DWGS. � T STEE� PER PLAN 9%„ � STEEL BEAM PER P�AN SECTION 1 s 3/4" = 1'-0" S'J�2 10 GA. BENT PLATE x� CONTIN., SCREW TO TOP CHORDS OF CFS TRUSSES 4"� 10" METAL PANEL PER ARCH. DWGS. STEEL ROOF DECK PER PLAN STEEL JOISTS PER� P�AN T/STEEL BEYOND +11'- SHIM AS REQ'D.—'� 2"� 10�" 8» STEEL ROOF DECK PER PLAN 12 4��. � � 0 � CFS TRUSSES PER PLAN WELDED TRUSS CLIP BY TRUSS SUPPLIER STEEL BEAM PER PLAN DEEP LEG DEFLECTION TRACK BY CFS SUPPLEIR CFS STUD WALL PER ARCH. DWGS. S�CTIOl`1 s 3/4 - 1-0 �'702 SECTION 3 3/4" = 1'-0" S']�2 SECTION 9 3/4 - 1-0 S']�2 P�AN rio� �PPLEIR ER 8%° 6/°° STEEL ROOF DECK PER PLAN -- 12 " 4 � i I � , /\ � 0 L CFS TRUSSES PER P�AN WELDED TRUSS CLIP BY TRUSS SUPPLIER � STEEL BEAM PER PLAN DEEP LEG DEFLECTION TRACK BY CFS SUPPLEIR CFS STUD WA�L PER 2" ARCN. DWGS. �4x4x3�6 CONTIN. _� ` T STEEL PER PLAN c� STEEL BEAM PER PLAN �STEEL BEAM BEYOND PER PLAN SECTION 19 3/4" = 1'-0" S']�2 SECTION 14 3/4" � 1'-0" S']�2 10 GA. BENT PLATE x� CONTIN., SCREW TO TOP CHORDS OF CFS TRUSSES 4" �10" METAL PANEL PER ARCH. DWGS. STEEL ROOF DECK PER PLAN STEEL JOISTS PER PLAN 8%„ 6/�� STEEL ROOF DECK PER PLAN - 12 I 4 �� � , /\ � 0 �CFS TRUSSES PER PLAN WELDED TRUSS CLIP BY TRUSS SUPPLIER STEEL BEAM PER PLAN � DEEP LEG DEFLECTION TRACK BY CFS SUPPLEIR CFS STUD WALL PER 2" ARCH. DWGS. L4x4x3�6 CONTIN. � � T STEEL PER PLAN a � STEEL BEAM PER PLAN SECTION zo 3/4" = 1'-0" S']�2 � � ? EXPANSION JOINT � 11 "± FV PER ARCH. DWGS. ,' , ��, - � STEEL ROOF DECK L4x4x316 CONTIN---�_ ,-' ( PER PLAN � I %' � 10"± FV /,, \ GSTEEL JOIST PER PLAN �STEEL BEAM PER PLAN PLAN �LAN � FACE OF EX. WALL I 1'-0"± FV I STEEL ROOF DECK PER PLAN CONTIN. 16 GA. - STRAP 10 GA. WELDED P�ATE — ASSEMB�Y CONTIN., SCREW 5"4 10" TO TOP CHORDS OF CFS �" TRUSSES MASONRY VENEER PER ARCH. DWGS. C3x5 VERT. @ 4'-0" O.C. WITHIN STUD SPACE, SCREW TO ADJACENT STUD 10 g" i 3 S�CTIO� 4 3/4" = l'-0" S%�2 12 12 / 9%„ i 6" /' � / 14 GA. SHEAR BRAKE (BETWEEN EVERY OTHER TRUSS) 800S200-68 (BETWEEN N EVERY OTHER TRUSS) - CFS TRUSSES PER PLAN WELDED TRUSS CLIP BY TRUSS SUPP�IER STEEL BEAM PER PLAN �"—DEEP LEG DEFLECTION TRACK BY CFS SUPPLEIR CFS STUD WAL� PER ARCH. DWGS. SECTION 10 3/4 - 1 -0 S']�2 STEEL ROOF DECK PER PLAN / JOIST TOP CNORD EXTENSION STEEL BEAM PER PLAN L4x4x% x 0'-5" i L. MASONRY VENEER -/ � CFS STUD WA�L PER PER ARCH. DWGS. ARCH. DWGS. �, � , � / i C4x5.4 VERT. @ 2'-8" O.C. � WITHIN STUD SPACE � � / � � , 3» � �� L3x3� BRACES UP TO L6x4x%6 (LLV) / TOP CHORD EXTENSION CONTIN. @ EACH VERTICAL B/ANGLE PER ARCH. DWGS. J L5x3x% x 0'-4" WINDOW SYSTEM PER ARCN. DWGS. SECTION Is 3!4" = 1'-0" S'J�2 12 I 12 14 GA. STEEL BENT PLATE 5/�� FOR DECK TRANSITION BY DECK SUPPLIER STEEL ROOF DECK PER PLAN 12 ' ' ' N � � � � � � i_ � � �---_ T STEE� PER P�AN —'— CFS TRUSSES PER PLAN BEYOND WELDED TRUSS CLIP BY TRUSS SUPPLIER STEEL BEAM PER PLAN CFS TRUSSES PER PLAN SECTION z 1 3/4" = 1'-0" S']�2 �» 1' � ' EX. SLOPING ROOF I ' EXPANSION JOINT PER ARCH. DWGS. L4x3x3/6 CONTIN. ( STEEL ROOF DECK PER PLAN �STEEL JOIST PER PLAN STEEL BEAM PER PLAN FACE OF EX. WALL I 1'-2 8" I C3x5 VERT. @ 2'-8" O.C. WITHIN STUD SPACE, SCREW TO ADJACENT STUD '¢�� STEEL ROOF DECK L4x4x t6 CONTIN. PER PLAN ( T STEEL PER PLAN , , �4x4x5t6 x 0'-4" AT EACH CNANNEL 'I STEEL BEAMS PER PLAN MASONRY VENEER - CFS STUD WALL PER PER ARCN. DWGS. ARCH. DWGS. SECTION s , , �6x4x t6 (��V) L5x3x% x 0'-4" 3/4" = 1'-0" S'702 CONTIN. B/ANGLE PER ARCH. DWGS. ' � J WINDOW SYSTEM PER - ARCH. DWGS. SECTION 6 3/4" - 1�_�,� S%02 I �/;% �%% � EXPANSION JOINT � % �;� 6%"� FV PER ARCH. DWGS. � �: L6x4x �s (LLN) � ��� � STEEL ROOF DECK � FACE OF EX. WALL CONTIN. PER PLAN T/STEEL PER PLAN ;;; „ ;; EXPANSION JOINT STEEL BEAM PER PLAN ' 6 4"� FV PER ARCH. DWGS. L6x4x%6 (LLH) ;;; ��� � STEEL ROOF DECK ',; CONTIN. ',-�' PER PLAN � T STEEL PER PLAN � T STEEL PER PLAN 1� % % - STEEL BEAM PER PLAN FACE OF EX. WALL 7%��f I.� S�CTIO� 11 3/4° = 1'-0" S%�2 SECTION 16 3l4" = 1'-0" S']�2 CFS TRUSS PER PLAN GROUT CORES TO RECEIVE ADHESIVE ANCHORS 10" CMU WALL— PER PLAN SECTION zz 3/4" = 1'-0" S']�Z STEEL ROOF DECK PER PLAN STEE� BEAM PER PLAN L6x6x%6 CONTIN. w/ %" DIA. ADNESIVE ANCNORS @ 24" O.C. IN BOITOM OF 2" VERT. SLOT (FINGER TIGHTEN & FOUL THREADS, 6" MIN. EMBEDMENT) �/„+ � �STEEL BEAM PER PLAN S�CTIO� 12 3/4° = 1'-0" s%�2 SECTION 1 � 3/4" = 1'-0" S%�2 �� � � : �� r r � ' �' 4 1_ � C'� M � �� � � t " � r r: �; y ri .+ t ,.�,. r r =,1 .i r,.� .e C'� M d W � 0 � N � CO C �' -a'z .� .� �o '� Q � � � � o� :�i,� .a,a��;: � c SCOPE DRAWINGS: These drawings indicate the general scope of the project In terms of architectural deslqn concept, the dimenslons of the building, the major r,rchitectural elements an� the type of sfructural, mechanical and electrical systems. The drewings do not necessarily indicate or describe all work required ;or full performance and completion of the requirements of the Controct. On the basis of the general scope indicated or described, the trade contractors sholl fumish ali Items required for the prc�per execuCic�n and compleClon of the wc�rk REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TITLE: SECTIOIVS AND DETAILS CERTIFIED BY: ��\illliii/// \\\����� P . B R (ltij��!��i�. ` Q�a •��G1STE/?F� °.o��` �i Q = No. 890277 - =�o o�_ � � �S STATE OF :� � �- � � ! �.noamooeaMDIANPo.�"� � � F � �` ,�����S,��N •L � ���\. � i�� ii�� SECTION 1 3!4" = i'-0" 57�3 �4x4x316 CONTIN. � STEEL BEAM PER PLAN MASONRY VENEER PER ARCH. DWGS. 10" CMU WA�L PER PLAN GROUT COURSE ABOVE BOND BEAM AS REQ'D. TO ENGAGE ANCHORS 10" CMU BOND BEAM- PER TYPICAL DETAIL O � � EXPANSION JOINT PER ARCH. DWGS. STEEL ROOF DECK PER P�AN MASONRY VENEER PER ARCH. DWGS. SLAB EDGE PER - TYPICAL DETAIL STEEL BEAM PER PLAN CFS STUD WALL PER ARCH. DWGS. � SLAB ON DECK PER PLAN T SLAB PER PLAN x x x x , ' STEEL ROOF DECK � `"'" � i PER P�AN DEEP LEG DEFLECTION ; TRACK BY CFS SUPPLEIR B/ANGLE PER ARCH. DWGS. - ;; p3' � CFS STUD WALL PER ARCN. DWGS. � „ ( FACE OF EX. WALL L4x4x5�6 CONTIN. 11/ (GALV.) SECTION 2 SECTION 3 3i4�� = l�-o�� 5703 si4�� =1�-0�� 5703 NOTE: ELEVATION AND SLOPE� 12 12 � � � I I I � � � � � I I S�AB EDGE PER TYPICAL DETAIL � I � I I S�P,B ON DECK PER PLAN I I T SLAB PER PLAN I I x x x x I I I 8 8" SE I I I STEEL BEAMS PER PLAN I I I BENT PLATE L8x6x5/6 (LLH) CONTIN. �` ° � w/ %" DIA. ADNESIVE ANCNORS @ 24" O.C. IN BOTTOM OF 2" VERT. I I S�OT (FINGER TIGHTEN & FOUL THREADS, 6" MIN. EMBEDMENT) SECTION � 3!4" = i'-0" 57�3 L3x3� BRACE UP TO TOP FLANGE OF ADJACENT BEAM @ 4'-0" O.C. Ux4x% x 0'-6" (LLH) w/ STIFF. �' %" @ 24" O.C. OF TOP OF TRUSSES TO MATCH TOPS OF EXISTING ADJACENT TRUSSES TO THE NORTH, FIE�D VERIFY STEEL ROOF DECK PER PLAN � CONTIN. 16 GA. � STRAP 10 GA. PLATE x 10" � CONTIN., SCREW TO TOP \ CNORDS OF CFS TRUSSES STEEL ROOF DECK � PER PLAN T/STEEL PER PLAN � 14 GA. STEEL BENT PLATE- FOR DECK TRANSITION BY DECK SUPPLIER TOP PLATE i fi"x9" CONTIN. I� MASONRY VENEEf PER ARCH. DWG`. SLAB EDGE PER TYPICAL DETAIL B/ANGLE PER Af L4x4x5/6 CONTIN. ( GALV. ) 14 GA. SHEAR BRAKE (BETWEEN EVERY OTNER TRUSS) 800S200-68 (BETWEEN EVERY OTHER TRUSS) CFS TRUSSES PER P�AN WELDED TRUSS CLIP BY TRUSS SUPPLIER STEEL BEAM PER PLAN SECT ON 8 3!4" = 1'-0" S']�3 1'-0" SECTION 4 3ia�� = l�_o" 5703 ► ' :► PLAN _LH) w/ STIFF. � %" @ 24" O.C. MASONRY VENEER- PER ARCH. DWGS. STEEL ROOF DECK PER PLAN � L4x4x 16 CONTIN. - STEEL JOIST PER PLAN SLAB EDGE PER TYPICAL DETAIL CFS STUD WALL PER ARCH. DWGS. 4" (. SLAB ON DECK PER PLAN T SLAB PER PLAN � x x x x x � 1'-0" SE SECTION s 3ia�� = l�_o" 5703 SECTION 9 3/4" = 1'-0" S']�3 �r��:��G'�J�.»/:1�1 MASONRY VENEER- PER ARCH. DWGS. STEEL ROOF DECK PER PLAN � L4x4x3/6 CONTIN. — STEEL JOIST PER PLAN P�ATE 3/"x12" CONTIN w/ %" STIFFENER PLATES @ 2'-0" P.C. 4" CFS STUD WALL PER ARCH. DWGS. T/STEE� PER PLAN � � _ STEEL BEAM PER PLAN SECTION 6 3l4" =1'-0" S'J�3 E II �� II �N III ;.�, �� COORD. SHEAR TAB + �� LENGTHS W/ BOLT JOISTS, DECK SUPPORT N INSTALLATION ANGLES, BOLTS, ETC. o �� CLEARANCES NOT SNOWN FOR � II CLARITY II COPE FLANGES AT Ilh INTERFERENCE W16x50 +13'-0 W16x36 +13'-0 11 =-=-= = = —_—_— _ � I� � ���x2 / I � �� R � S �f//�S '0 � �/ � 01 ,��,� REF. ROOF FRAMING �'` I PLAN FOR UPPER � BEAMS PLAN DETAIL 10 3/4" = 1'-0" s7�3 W � 0 � a SCOPE DRAWINGS: These drawings indicate the general scope of the project In terms of architectural deslqn concept, the dimenslons of the building, the major r,rchitectural elements an� the type of sfructural, mechanical and electrical systems. The drewings do not necessarily indicate or describe all work required ;or full performance and completion of the requirements of the Controct. On the basis of the general scope indicated or described, the trade contractors sholl fumish ali Items required for the prc�per execuCic�n and compleClon of the wc�rk REVISIONS: ISSUE DATE DRAWN BY CHECKED BY 04/14/15 MD� PAB DRAWING TITLE: SECTIONS AND DETAILS CERTIFIED BY: ����uiiiiii� \\����� P . B R (ltij��!��i�. � Q�o•��G1STE/?F�'.o��` �i Q = No. 890277 - � � oS STATE OF :e � = � � �.(��amo,e�/MDI�ANP,.°"� ��� F � �� ,�����S,��N •L � ���\. � i�� ii�� �- „ ,� � �-�� ��� i (, ! \ \ )1 >' � ,�� ,.� � ., i