S CAL E: 3/ 16" = 1'-0"
GENERAL NaTES:
1. SEE H0.01 FOR MECHANICAL SYMBOLS,
ABBREVIATIONS ANQ PROJECT GENERAL NOTES.
PLAN NOTES:
� PROVIDE LOAD BEARING NON PENETRATION
SUPPORT PEIRS AT EACH CORNER OF EACH ACCU
AND GALVANIZED SLOTTED STRUT CHANNEL
SHAPED FRAMING TO DISTRIBUTE THE COMBINED
WEIGHT EVENLY. TOP OF UNITS MOUNTING NOT TO
EXCEED 46" ABOVE ROOF.
2 PROVIDE 12" TALL, U.V. STABILIZED, RECYCLED
RUBBER RAILS WITH SPREAD FOOTING. ANCHOR
REFRIGERANT PIPE TO INTEGRAL GALVANIZED
STEEL OR ALUMINUM SLOTTED STRUT CHANNELS
AND NON FERROUS CLAMPING HARDWARE.
PRODUCT SIMILAR OR EQUAL TD "B-LINE DUR-BLOC"
SUPPORT AT CHANGE OF DIRECTIONS AND 8' O.C.
3 REFRIGERANT LINES - SUCTION ONE {1-1 /8"}, LIQUID
(5 /8") AC UNIT MANUFACTGURER TO VERIFY LINE
SIZES. PROVIDE ONE LINE SET FOR EACH FURNACE,
SLEE PIPING ROOF PENETRATION DETAIL.
4 3� PVC COMBUSTION AIR INTAKE AND 2-1/2� CPVC
EXHAUST FLUE PIPNG. ROUTE FR4M FURNACE TO
ROOF OUTLET. TERMINATE WITH CONCENTRIC
ADAPTER ON ROOF FQLLOWING MFRS INSTALLATION
I NSTRUCTIONS AN D PAI NT TO MATCH BUI LDI NG.
5
COORDINATE PIER PLACEMENT WITH ROOF JOIST
LOCATIONS AND ROOFING CONTRACTOR FOR
MEMBRANE ROOFING PROTECTION.
6 EXHAUST FAN ON ROOF, TOP OF FAN <36" ABOVE
ROOFING.
7 COORDINATE PLUMBING VENT, EXHAUST FAN
LOCATIONS TO BE >10' FROM AIR INTAKE HOOD.
ROOF PENETRATION LOCATION T4 BE C�ORDINATED
WITH SCREEN PERAPIT WALL KNEE BRACE
LOCATOI NS.
,;; ECTOR CONSULTIN�
��;>;�;' � L L C Mechanical & E/ectrical Engineering
� ijtitr,jjjiiij.
' 5�Y��:ii:.i
j?'^j3:�
�"''' 9005 North Senate Avenue
��;,,,,:,;:,; :
���,,:.
lndianapolis, lndiana 46202
ph. 3 �7. 632.4444
fax 317. 632.4960
\`\����\111�0 111//���i/
%� /
���\G � o0000000000/V %/
�� (� �\/oo oo�/ /�
`�� V o , ^ oo (� �/
�► //
\` `Oo O O a o�/
•� t �
o � L� o i
_�o� � 2o J,
_ �t�,� o � _
-
_�°~ � O W a°Q-
� �
-
= o%� Z 0 Q Oo =
�� o� N n =o ��
� ° v�
� o d. O o �
. 4//� ,o�°oo � oo° Go \/ �
�/� //�/� �OO000000°° O` ♦
��/ " � o � �\
%,, P ����
//I►��������� �. _