Loading...
HomeMy WebLinkAbout13110024.18CONNECT TO SIDE OF MAIN. DO NOT CONNECT FROM TOP OR BOTTOM CODE APPROVED VACUUM BREAKER REQUIRED AT ALL ELEVATED W.H. CW � ••• HW • • -.� PRESSURE TEMP. RELIEF ' VALVE DISCHARGE WITHIN WATER WALL CAVITY TO DISCHARGE HEATER ABOVE MOP BASIN. DRAIN VALVE � STAINLESS STEEL DRAIN PAN, 1 1/2" DEEP WITH A 1" MINIMUM DRAIN WATE R H EATE R DETAI L N.T.S. INSTALL THERMAL EXPANSION TANK NO VALVES OR DEVICES TO BE INSTALLED BETWEEN EXPANSION TANK AND THE WATER HEATER AS PER CODE. PROVIDE INTEGRAL HEAT TRAPS 1" PIPE WASTED WITHIN WALL CAVITY TO DISCHARGE ABOVE MOP SINK REFER TO ARCH PLANS FOR WATER HEATER PLATFORM TYPICAL VENT THRU ROOF N.T.S. CONDENSATE DRAIN OPEN PIPE TO ATMOSPHERE PIPE SIZE SAME AS UNIT CONDENSATE DRAIN TO APPROVED RECEPTACLE A. STATIC PRESSURE IN PAN (INCHES) B. 0.5 X STATIC PRESSURE IN PAN (INCHES). NOTE: ALL PIPES FULL SIZE OF UNIT OUTLET TYPICAL UNIT CONDENSATE PIPING � N.T.S. CONNECT TO UNIT GAS CONTROLS WITH GROUND JOINT UNION PROVIDE GROMMET FOR WATER-TIGHT SEAL ( GAS PIPE SIZE TO MATCH UNIT CONNECTION) �-- PLUGGED 1/8"_ NPT TEST GAUGE CONNECTION PRESSURE REDUCING VALVE WITH INTERNAL VENT. VENT ELBOW DOWN GROUND JOINT UNION GAS COCK WITH PLUGGED 1I8" NPT TEST GAUGE CONNECTION ROOF TOP UNIT GAS PIPING - RUN ON ROOF 2"MIN. TYP. TYP. MECH. DIRT POCKETJ i PIPE ROOF PIPESTAN 9 TYP. GAS PIPE ADJUSTMENT AT P-2 ROOF OBSTRUCTIONS TYPICAL NOTE: CONTRACTOR SHALL VERIFY ALL MECHANICAL GAS FIRED EQUIPMENT CONNECTION LOCATIONS IN THE FIELD PRIOR TO INSTALLING ANY GAS PIPE MAINS OR BRANCHES. TYPICAL UNIT GAS PIPING CONNECTION N.T.S. SEDIMENT BUCKET (3) COMPARTMENT SINK DETAIL N.T.S. NO SUBSTITUTI4NS ON ANY FIXTURES. .�„ �� ,���� ..�..BRANE )R MATERIAL FLOOR DRAIN DETAIL N.T.S. 0 DRAIN FROM COOLING UNIT CE MAKER 1' MIN AIR GAP OR AIR BREAK DEEP SEAL TRAP � � -VENT I 1 1 � FLOOR DRAIN � FOR ICE BIN � � � I � TO SAN. WASTE MAIN ICE MAKER DRAINAGE PIPING DETAIL N.T.S. � � 1" MIN. AIR GAP NEW FINISH FLOOR MATERIAL EXISTING SUBFLOOR FUNNEL 4" HIGH FLOOR DRAIN WITH NICKEL BRONZE GRATE 18" RUBBER MEMBRANE FLOOR DRAIN WITH FUNNEL DETAIL N.T.S. SYRUP LINES 3' H�LE— P L U M B I N G F IXT U RE S C H E D U L E� NOTE: THERE WILL BE ABSOLUTELY NO SUBSTITUTIONS A�LOWED FOR ANY PLUMBING PRODUCTS AS SPECIFIED. THIS INCLUDES ALL ZURN PRODUCTS. MARK ITEM MANUFACTURER MODEL NO UTILITIES REMARKS CW HW W VT TEMP OICE/BEVERAGE BY VENDOR 1/2" - INTO FS ' ' UNIT ICE-MAKER HOSHIZAKI KM-280MWH (2)1/2" - - - - WATER COOLED ICE MAKER. PROVIDE W/ HOSHIZAKI �� B-300PF BIN - SEE 3/P2. HAND SINK UNIVERSAL EHS-1 1/2" 1/2" 1-1/2" 1-1/2" 110° SEE NOTE 2 FOR THERMOSTATIC MIXING VALVES 19 STAINLESS REQUIREMENTS. (HS) FAUCET UNIVERSAL CHF-04 GOOSENECK FAUCET. STAI N LESS MOP BASIN ZURN Z1996-24 3/4" 3/4" 3" 2" 140° 20 WALL-MOUNT WITH 1/2" IPS FLANGED FEMALE INLET, VACUUM (MS) FAUCET ZURN Z1996-SF BREAKER SPOUT, PAIL HOOK, 3/4" HOSE THREAD, LEVER HANDLES AND ROUGH CHROME FINISH. PROVIDE HOSE BIB VACUUM BREAKER FOR SPRAYER. 21 3 COMPARTMENT UNIVERSAL #3N1620-2D18-I 1/2" 1/2" INTO ' 140° VERIFY INDIRECT WASTE AND GREASE TRAP - SEE 1/P2. SINK W/ 2-18" STAINLESS FS (3CS) DRAIN BOARDS FAUCET ZURN Z842H1.0002 34 WATER FILTER CUNO #15 1/2" �1 COMPARTMENT UNIVERSAL #1N1620-RD18 1/2" 1/2" INTO ' 140° VERIFY INDIRECT WASTE SINK W/ 1-18" STAINLESS FS (1CS) DRAIN BOARDS FAUCET ZURN Z842H1-15F WC-1 HANDICAP ZURN Z5615 - - 4^ 2�� FURNISH WITH ZURN OPEN FRONT SEAT MODEL Z5955SS. WATER CLOSET FURNISH WITH WALL CARRIER MODEL Z-1204N4. FLUSH VALVE ZURN Z6000-AV-WS1 1" ' - - FLUSH VALVE MOUNTING HEIGHT AT 26-1/2" AFF LAV-1 HANDICAP ZURN MODEL Z5354 1/2" 1/2" 1-1/2" 1-1/2" 110° FURNISH W2URN Z81261 FAUCET WITH VANDAL RESISTANT WALLHUNG AERATOR AND GRID DRAIN. PROVIDE TRU-BRO LAV GUARD. LAVATORY SEE NOTE 2 FOR THERMOSTATIC MIXING VALVES REQUIREMENTS FD-1 FLOOR DRAIN ZURN MODEL ZN415-3NH-6S-P ' - 4^ 2N TYPE "S" STAINER. PROVIDE WITH COMPLETE BODY ASSEMBLY WITH TRAP PRIMER CONNECTION - SEE 21P2. FD-2 FLOOR DRAIN ZURN MODEL ZN415-3NH- ' ' 3" 2" FLOOR DRAIN IS TO BE FLUSH WITH FINISH FLOOR. 6S-CONE GT-1 GREASE ZURN MODEL GT-2700-50 - - 4" 2" 50 G.P.M. FLOW RATE, 100 LBS CAPACITY, T�P FLUSH-WITH-FLOOR INSTALLATION, 4" TAPPED INLET AND OUTLET, HEAVY-DUTY NON-SKID GASKETED COVER SECURED WITH STAINLESS STEEL BOLTS, FLOW CONTROL VALVE. (3C TO VERIFY IF EXTENSION KIT WILL BE REQUIRED PRIOR TO INSTALLATION FCO FLOOR ZURN MODEL ZN1400-3(4)NH-T ' ' - - POLISHED NICKEL BRONZE TOP CLEANOUT PLUMBER MUST FIELD VERIFY 3" OR 4" CONNECTION WCO WALL CLEANOUT ZURN MODEL Z-1441-2 - - - - SMOOTH, STAINLESS STEEL ACCESS COVER FS-1 FLOOR SINK ZURN MODEL Z1901-3NH-2-25 ' ' 3" 2" 12"x12" FLOOR SINK, 3" OUTLET HALF-GRATE, A.R.E. BUCKET, BOTTOM DOME STRAINER. - TOP OF FLOOR SINK IS TO BE FLUSH WITH TOP OF FLOOR TILE. FS-2 FLOOR SINK ZURN MODEL Z1910-3NH-2-25 - - 3" 2" 8"x8" FLOOR SINK, 3" OUTLET HALF-GRATE, A.R.E. BUCKET, BOTTOM DOME STRAINER. - TOP OF FLOOR SINK IS TO BE FLUSH WITH TOP OF FLOOR TILE. TP-1 TRAP PRIMER PPP P1-500 W/ADAPTER 1/2" ' 3" 2" BFP-1 BACKFLOW WATTS 007 1" - INTO - VERIFY BFP TYPE AND INS7ALLATION WITH LOCAL AHJ PREVENTER FD BFP-2 BACKFLOW WATTS 9BD 1/2" - INTO - VERIFY BFP TYPE AND INSTALLATION WITH LOCAL AHJ PREVENTER FD ELECTRIC WATER HEATER SCHEDULE MANUFACTURER STORAGE EWT LWT REC. ELECTRIC ELEMENT MARK AND MODEL NO. CAPACITY DEG. DEG. GPH (GALLONS) F F KW VOLT PH STAGES REMARKS WH-1 A.O.SMITH 50 40 140 74 18 208 3 1 (1) 18 KW PROVIDE DVE �2 INTEGRAL HEAT TRAPS - SEE 5/P-2 6' PVC CAP O 90• ANGLE 18 SUBFLD�R 6' PVC CHASE FINISHED FLOOR FIGURE 1.0 FILL IN H�LE WITH — — — — — — — — — — — — F�AM AND CAULKING AR�UND SYRUP LINES SEE FIGURE 1,0 S�DA CHASE TERMINATION DETAIL � Q N.T.S. C�� NOTE: 1. SPACE BLOCKING STANDS AT 6'-0" INTERVALS ON ROOF. 2. FOLD UP END OF SLIP SHEET AND NAIL TO BLOCK CONDENSATE PIPE METAL STRAP WITH 1/4"0 x 2" LAG EACH SIDE, ALLOW FOR MOVEMENT 4x6 "WOLMANIZED" BLOCKING - MASTIC TO ADDITIONAL ROOFING SHEET CONDENSATE SUPPORT SIMILAR N.T.S. 16 PLUMBING LEGEND — —SAN— — SAN— — SANITARY — —GW— —GVIN— — GREASE WASTE ------------- PLUMBINGVENT CW — CW COLD WATER HW — — HW HOT WATER GAS GAS GAS PIPING �I FLOOR DRAIN �O FLOOR CLEANOUT I� WALL CLEANOUT � FLOOR SINK Q HUB DRAIN �p� BALL VALVE � TEMPERING VALVE � BACKFLOW PREVENTER NOTES 1. ALL PLUMBING FIXTURES TO BE FULLY ACCESSIBLE TO INDIVIDUALS WITH DISABILITIES ACT OF 1990. FIXTURES AND THEIR INSTALLATION SHALL ALSO COMPLY WITH AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) PUBLICATION A117.1 - PROVIDING ACCESSIBILITY AND USABILITY FOR PHYSICALLY HANDICAPPED PEOPLE AND/OR GOVERNING CODES. - ALL PLUMBING FIXTURES EQUIPMENT, TRIM, & FITTINGS SHALL COMPLY WITH CITY REQUIREMENTS, AND FEDERAL REGULATIONS AND CODES, INCLUDING, BUT NOT LIMITED TO, WATER AND ENERGY CONSERVATION CODES. THE SCHEDULED AND/OR SPECIFIED PLUMBING FIXTURES AND EQUIPMENT REPRESENT THE MINIMUM CRITERIA AND SHALL BE THE BASIS FOR THE CONTRACTOR'S BASE BID. IF THE SCHEDULED OR SPECIFIED FIXTURES OR EQUIPMENT DO NOT COMPLY WITH GOVERNING CODES OR REGULATIONS IN ALL RESPECTS, THE CONTRACTOR SHALL PROVIDE AN ALTERNATE BID FOR COMPLYING FIXTURES, EQUIPMENT, TRIM, OR FITTINGS. THE ABSENCE OF AN ALTERNATE BID SHALL BE CONSTRUED TO MEAN THAT THE CONTRACTOR'S BID INCLUDES ALL COSTS NECESSARY TO MEET ALL REGULATIONS 8� CODES. 2. PROVIDE THERMOSTATIC MIXING VALVE (� AT ALL LAVATORIES AND HAND SINKS. PROVIDE ZURN TMV-1, 1 TO 15 GPM, NOT TO EXCEED 3 PSI, W/ UNION STOP CHECK INLETS, AND REMOVABLE STAINLESS STEEL STRAINERS, DIAL THERMOMETER AND DISCHARGE VALVE. SUPPLIES 110^F. 3. ALL ROOF PENETRATIONS SHALL BE APPROVED BY LANDLORD AND DONE IN ACCORDANCE WITH ROOF MANUFACTURERS RECOMMENDATIONS SO AS NOT TO VOID THE WARRANTY. PLUMBING FIXTURE SUPPLIER KEC DESIGN CONTACT: DAN PROCTOR 301 MERCURY DRIVE SUITE 1 CHAMPAIGN, IL 61822 PHONE: 217.356.1640 FAX: 217.356.1661 EMAIL: danproctor@kecdesign.net v � 13-892-491 � I' 1V��Y j��`�'�A1i � �1 S ; I Sinre l433 � Q� AM T�SANDN CB�a � �. �� I �. �. �� I � �. t� . � � � 1 �. :,: :t: ' ." , ��'"`'. �- ;;: � � �`„ S�;` `,• . ,�..'w • . . . ' � ; . �', �^:l:V ; .z•�,. ��� l ,.~;%;�, ,4,.,\��, �� . -:�_,;��/y�;�:� .. �� zs �. ,�..... ��� =� .� �,, , , ,�" >. ,.:k . ... f, :� . r% . ii �.<; " ...,....:...•• `l'�' , ,i. ,J' '� ^ S � i`a� `�� '� � ��`�:�`;�� � ,,...;4; % ; 1 � � �' � N � N � C ' � � • � �m � � � m� >� N� - � � _. J j( N � �� ' a �°' � � m� , .� o � N � N � � � '� t O �� � . ; L� a ��� � N N � W N � � � , . . � O � 0 �� � -- ��. � a ' W � r � � a � � � �� ��� � � . � ~� pa, A � � � O A � � � I � � Wm� �:� a° � � ��� . ��. � z� � �aw , � ��� f. ., E„ ��� � . w W�UV] L. � � W � �� � ti � � E � �.. � � � O ��.. f� V � ' �� r 1 DATE: 8��13 f i. DATE REVISED � L� . 1 SHEET TITLE F �� PLUMBING LEGENDS, 4 SCHEDULES AND DETAILS � . ,L.t, 1 SHEET NUMBER P-2 �� ,.�. � �