HomeMy WebLinkAboutSTRUCTURAL500 200 100 50 20 10 500 200 100 50 20 10 500 200 100 40 20 10 GENERAL NOTES V. WOOD FRAMING A. WALL SHEATHING 1. WALL SHEATHING SHALL BE MANUFACTURED BY A MEMBER OF AMERICAN PLYWOOD ASSOCIATION, SHALL BE LABELED WITH THE APA GRADE STAMP AND CONFORM TO THE FOLLOWING REQUIREMENTS: a. PANEL GRADE RATED SHEATHING b. SPAN RATING 16/32 c. EXPOSURE DURABILITY CLASSIFICATION EXPOSURE 1 d. PRODUCT STANDARD PS1 e. THICKNESS 5/8" 2. ALL SHEATHING SHALL BE INSTALLED WITH THE STRENGTH (TYPICALLY FACE GRAIN) DIRECTION PERPENDICULAR TO THE SUPPORTING FRAMING W ITH STAGGERED JOINTS. 3. WALL SHEATHING SHALL BE FASTENED TO SUPPORTING FRAMING WITH #10 TEK SCREWS AT THE SPACING INDICATED BELOW UNLESS NOTED OTHERWISE IN THE SHEAR WALL SCHEDULE: a. WALL EDGE 6" O.C. b. SUPPORTED PANEL EDGES AWAY FROM EDGE OF W ALL 6" O.C. c. CENTER OF PANELS 12" O.C. IV. CONCRETE A. CONCRETE SHALL CONFORM TO THE FOLLOWING REQUIREMENTS: CONCRETE 28 DAY COMPRESSIVE STRENGTH AND DENSITY REQUIREMENTS: STRENGTH CONC. USAGE (PSI) TYPE COMMENTS a. ALL CONCRETE NOT OTHERWISE SPECIFIED 4000 NWT b. FOOTINGS 3000 NWT c. FOUNDATIONS WALLS, GRADE BEAMS 4500 NWT d. SLAB-ON-GRADE INTERIOR 3000 NWT e. SLAB-ON-GRADE EXTERIOR 4500 1. NWT = NORMAL WEIGHT CONCRETE 2. ALL CONCRETE SHALL HAVE ALLOWABLE UNIT SHRINKAGE OF 0.045% AT 28 DAYS. (SEE ASTM C157) 3. ALL SLABS TO RECEIVE MOISTURE SENSITIVE FLOOR COVERINGS SHALL HAVE MAXIMUM WATER/ CEMENT RATIO OF 0.45. B. CONCRETE SHALL CONFORM TO THE FOLLOWING DURABILITY REQUIREMENTS PER ACI-318 SECTION 4.2 & 4.3: EXPOSURE/LOCATION a. FOOTINGS F0, S0, P0, C1 b. FOUNDATION WALLS, GRADE BEAMS F1, S0, P0, C1 c. RETAINING WALLS F2, S0, P0, C1 d. EXTERIOR SLAB ON GRADE F1, S1, P0, C2 e. INTERIOR SLABS F0, S0, P0, C0 C. ALL CONCRETE CONSTRUCTION SHALL CONFORM TO THE CURRENT "ACI MANUAL OF CONCRETE PRACTICE". D. PORTLAND CEMENT SHALL CONFORM TO ASTM C-150, TYPE I OR II. E. ALL AGGREGATE FOR NORMAL WEIGHT CONCRETE SHALL MEET ASTM C 33. F. ALL REINFORCEMENT SHALL CONFORM TO THE FOLLOWING SPECIFICATIONS: 1. ALL REINFORCING, UNO: ASTM A615 GRADE 60 2. WELDED WIRE REINFORCEMENT (WWR): a. SMOOTH WIRE: ASTM A 185 (65 KSI) b. DEFORMED WIRE: ASTM A 497 (70 KSI) c. POLYPROPYLENE FIBRILLATED FIBER MAY BE USED TO SUBSTITUTE WWR IN SLABS ON GRADE, WHEN ADDED TO CONCRETE MIX ACCORDING TO MANUFACTURER'S INSTRUCTIONS AND RECOMMENDED DOSAGES. G. REINFORCEMENT DETAILING: 1. REINFORCEMENT SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH ACI 315. 2. DEVELOPMENT AND SPLICE LENGTHS ARE IN TENSION UNLESS OTHERWISE INDICATED. 3. LAP WWR ONE CROSSWIRE SPACING PLUS 2". 4. PROVIDE CORNER BARS AT ALL FOOTINGS AND WALL INTERSECTIONS TO MATCH HORIZONTAL REINFORCING SIZE AND SPACING. AT INTERSECTIONS OF CONTINUOUS SPREAD FOOTINGS EXTEND ALL BARS TO FAR SIDE OF INTERSECTING FOOTING 5. REINFORCEMENT SHALL BE SECURELY PLACED TO PREVENT DISPLACEMENT DURING CONCRETE PLACEMENT. PROVIDE THE FOLLOWING CONCRETE COVER FOR REINFORCING, UNLESS SPECIFICALLY DETAILED OTHERWISE: a. CAST AGAINST EARTH 3" b. EXPOSED TO EARTH/WEATHER #6 THRU #18 2" #5 & SMALLER 1 1/2" 7. PROVIDE DOWELS TO MATCH REINFORCEMENT SIZE AND SPACING INDICATED FOR ALL STRUCTURAL ELEMENTS, UNLESS OTHERWISE INDICATED. H. FOUNDATION WALLS, GRADE BEAMS AND FOOTINGS SHALL BE CAST IN ALTERNATE PANELS NOT TO EXCEED 60'-0" IN LENGTH. SHEAR KEYS SHALL BE PROVIDED AT EACH CONSTRUCTION JOINT AND SHALL BE LOCATED AT 1/3 POINTS OF SPANS. I. HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS SHALL NOT BE USED UNLESS SHOWN ON THE DRAWINGS. THE ARCHITECT/ENGINEER SHALL APPROVE ALL DEVIATIONS OR ADDITIONAL JOINTS IN WRITING. J. CHAMFER ALL PERMANENTLY EXPOSED CONCRETE EDGES 3/4 INCH, UNO. K. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR LOCATIONS OF OPENINGS AND SLEEVES IN CONCRETE WALLS AND SUPPORTED FLOORS. SPREAD REINFORCEMENT AT OPENINGS AND SLEEVES UNLESS OTHERWISE SHOWN. DO NOT CUT REINFORCEMENT. SEE TYPICAL REINFORCEMENT DETAILS FOR OPENINGS IN SLABS AND WALLS FOR ADDITIONAL REQUIREMENTS. L. NO HOLES OR OPENINGS THROUGH FOUNDATION WALLS AND/OR FOOTINGS WITHOUT ENGINEER'S APPROVAL. M. ALUMINUM SHALL NOT BE EMBEDDED IN ANY CONCRETE. XI. SPECIAL INSPECTION AND TESTING (CHAPTER 17) A. ALL TESTS AND INSPECTIONS SHALL BE PERFORMED BY AN INDEPENDENT TESTING AND INSPECTION AGENCY. THE SPECIAL INSPECTOR FROM THIS TESTING AGENCY SHALL OBSERVE THE WORK FOR CONFORMANCE TO THE DESIGN DRAWINGS AND SPECIFICATIONS. B. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, THE ENGINEER OR ARCHITECT OF RECORD, AND ALL OTHER DESIGNATED INDIVIDUALS. ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN, IF NOT CORRECTED, TO THE PROPER DESIGN AUTHORITY AND TO THE BUILDING OFFICIAL. C. THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE INSPECTOR'S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED DESIGN DRAWINGS, SPECIFICATIONS, SOILS REPORT AND APPLICABLE WORKMANSHIP PROVISIONS OF THE INTERNATIONAL BUILDING CODE. X. SUBMITTALS A. THE GENERAL CONTRACTORS SHALL REVIEW AND STAMP ALL SHOP DRAWINGS BEFORE SUBMITTING FOR REVIEW. SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT AND/OR ENGINEER AND HAVE THE ENGINEER'S SHOP DRAWING STAMP AFFIXED PRIOR TO FABRICATION. FABRICATION AND ERECTION SHALL BE FROM REVIEWED SHOP DRAWINGS. B. A RECORD SET OF APPROVED SHOP DRAWINGS SHALL BE KEPT IN THE FIELD BY THE GENERAL CONTRACTOR. C. ANY DEVIATION FROM, ADDITION TO, SUBSTITUTION FOR, OR MODIFICATION TO THE STRUCTURE OR ANY PART OF THE STRUCTURE DETAILED ON THE CONTRACT DOCUMENTS SHALL BE SUBMITTED IN WRITING TO THE ENGINEER FOR REVIEW. SHOP DRAWINGS SUBMITTED FOR REVIEW DO NOT CONSTITUTE “IN-WRITING” UNLESS IT IS CLEARLY NOTED THAT SPECIFIC CHANGES ARE BEING SUGGESTED. D. THE CONTRACTOR SHALL PREPARE A LIST AND SCHEDULE OF ALL STRUCTURAL SUBMITTALS PRIOR TO CONSTRUCTION. E. THE FOLLOWING SHOP DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR FOR THE ENGINEER'S REVIEW: 1. BAR JOISTS (1, 3) 2. STRUCTURAL STEEL, SHOP AND ERECTION DRAWINGS (1, 3) 3. ROOF METAL DECK 4. CONCRETE MIX DESIGNS 5. REINFORCING STEEL F. ITEMS MARKED (1) SHALL HAVE SHOP DRAWINGS SEALED BY A REGISTERED ENGINEER IN THE STATE WHERE THE PROJECT IS LOCATED. ITEMS MARKED (2) SHALL BE SUBMITTED TO ENGINEER FOR OWNER'S RECORD ONLY AND WILL NOT HAVE THE ENGINEER'S SHOP DRAWING STAMP AFFIXED. ITEMS MARKED (3) SHALL HAVE DESIGN CALCULATIONS SEALED BY A REGISTERED ENGINEER IN THE STATE WHERE THE PROJECT IS LOCATED. 1. CONTRACTOR SHALL SUBMIT ONE SET OF REPRODUCIBLES AND TWO SETS OF PRINTS FOR ALL SHOP DRAWINGS SPECIFIED TO BE RETURNED BY THE ENGINEER. 2. THE OMISSION FROM THE SHOP DRAWINGS OF ANY MATERIALS REQUIRED BY THE CONTRACT DOCUMENTS TO BE FURNISHED SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF FURNISHING AND INSTALLING SUCH MATERIALS, REGARDLESS OF WHETHER THE SHOP DRAWINGS HAVE BEEN REVIEWED AND APPROVED. G. THE USE OF ELECTRONIC FILES OR REPRODUCTIONS OF THESE CONTRACT DOCUMENTS BY ANY CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR, OR MATERIAL SUPPLIER IN LIEU OF PREPARATION OF SHOP DRAWINGS SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT, AND OBLIGATES THEMSELVES TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON. IX. METAL STUD FRAMING A. DESIGN, FABRICATION, AND ERECTION SHALL CONFORM TO AISI "SPECIFICATIONS FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS", LATEST EDITION. ALL METAL STUDS SHALL BE GALVANIZED. B. ALL 33 MIL AND 43 MIL STUDS, JOISTS, TRACK, BRIDGING, END CLOSURES, AND ACCESSORIES SHALL BE FORMED FROM STEEL THAT CORRESPONDS TO THE REQUIREMENTS OF AISI "SPECIFICATIONS FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS" WITH A MINIMUM YIELD OF 33 KSI U.N.O. ALL 54 MIL AND THICKER MEMBERS SHALL HAVE A MINIMUM YIELD OF 50 KSI. C. ALL MATERIAL AND ACCESSORIES SHALL BE FORMED FROM STEEL HAVING A G-60 GALVANIZED COATING MEETING ASTM A 635. D. UNLESS NOTED OTHERWISE, ALL SCREWS OR PINS SHALL BE NON-CORROSIVE NO. 8-18 (D=.125") OR LARGER. DO NOT USE STAINLESS STEEL OR COPPER-COATED FASTENERS. E. UNLESS NOTED OTHERWISE, TRACKS SHALL BE THE SAME DEPTH AS STUDS OR JOISTS AND OF EQUAL OR THICKER GAUGE THAN STUDS OR JOISTS. TRACKS SHALL BE CONNECTED TO SUPPORT AT 16" O.C. MAX. STUDS OR JOISTS SHALL BE CONNECTED TO TRACKS AT EACH SIDE. F. THE QUANTITY OF STUDS AND JOISTS DISPLACED OR CUT FOR OPENING SHALL BE PLACED HALF ON EACH SIDE OF OPENING PER METAL STUD HEADER SCHEDULE ON THIS SHEET. G. INSTALLATION OF CURTAIN WALL FRAMING SHALL ACCOMMODATE VERTICAL DISPLACEMENT OF THE PRIMARY STRUCTURE. H. THE DESIGN OF SLIP TRACKS SHALL CONFORM TO GUIDELINES ESTABLISHED IN SSMA TECHNICAL NOTE NO. 1 PUBLISHED JAN. 2001. I. PROVIDE THE MANUFACTURER'S STANDARD TRACK, CLIP ANGLES, BRACING, REINFORCEMENTS, FASTENERS, AND ACCESSORIES AS RECOMMENDED BY THE MANUFACTURER FOR THE APPLICATION INDICATED AND AS NEEDED TO PROVIDE A COMPLETE FRAMING SYSTEM. UNLESS OTHERWISE NOTED, INSTALL THE FRAMING SYSTEM IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. J. ALL EXTERIOR METAL WALL STUDS FOR ELEVATED FLOORS SHALL BE 6" - 18 GAUGE STUDS SPACED AT 16" OC. MINIMUM SECTION PROPERTIES FOR STUDS SHALL BE: 1. I = 1.30 IN. 2. S = 0.66 IN. 3. FY = 33 KSI (MIN.) L. WALL SHEATHING SHALL BE FASTENED TO SUPPORTING FRAMING WITH NO. 10, FLAT-HEAD SELF-DRILLING TAPPING SCREWS WITH A MINIMUM HEAD DIAMETER OF 0.333 INCHES AT THE SPACING INDICATED BELOW UNLESS NOTED OTHERWISE IN THE SHEAR WALL SCHEDULE: 1. WALL EDGE 6"OC 2. SUPPORTED PANEL EDGES AWAY FROM EDGE OF WALL 6"OC 3. CENTER OF PANELS 12"OC M. PREPUNCHED HOLES SHALL NOT BE LOCATED WITHIN 10 INCHES OF THE STUD SUPPORT LOCATIONS. N. USE FLUX COVERED, MILD STEEL ELECTRODES AWS E-6012, E-6013, OR E-7014 FOR WELDING STEEL STUDS. ALL WELDING SHALL BE PERFORMED IN ACCORDANCE AWS PROCEDURES. CONSULT MANUFACTURER FOR EQUIPMENT RECOMMENDATIONS AND PROPER ELECTRODE SELECTION. TOUCH UP WELDED AREAS WITH A ZINC RICH PAINT. VIII. OPEN WEB STEEL JOISTS A. STEEL JOISTS AND BRIDGING SHALL BE DESIGNED, FABRICATED, AND ERECTED PER SJI RECOMMENDATIONS. B. THE SJI LOAD TABLES SHALL BE TAKEN AS THE MINIMUM DESIGN LOADINGS FOR JOISTS. JOISTS SHALL ADDITIONALLY BE DESIGNED TO CARRY ALL OTHER LOADINGS INDICATED ON THE DRAWINGS. C. BRIDGING INDICATED ON PLANS IS FOR PURPOSES OF ILLUSTRATING MISCELLANEOUS ATTACHMENTS AND DETAILS ONLY. GREATER OR FEWER LINES OF BRIDGING MAY BE REQUIRED BY SJI AND THESE REQUIREMENTS WILL SUPERSEDE THE CONTRACT DOCUMENTS. SEE PLANS AND DETAILS FOR SPECIAL BRIDGING AND BRACING REQUIREMENTS. D. ALL JOISTS SHALL BE CAMBERED IN ACCORDANCE WITH SJI CRITERIA. E. STEEL JOIST SPACING SHALL NOT EXCEED SPACING INDICATED ON DRAWINGS AND PLACEMENT OF JOISTS SHALL BE CAREFULLY COORDINATED WITH PARTITIONS AND WORK OF OTHER TRADES TO AVOID INTERFERENCES. F. ALL STEEL JOISTS, BRIDGING, AND THEIR CONNECTIONS SHALL BE DESIGNED FOR ALL LOADS INDICATED ON THE DRAWINGS. WHERE UPLIFT LOADS ARE INDICATED, AN OPPOSING DEAD LOAD OF 10PSF MAY BE UTILIZED. G. JOISTS AT OR NEAREST TO CENTERLINES OF COLUMNS ARE TO HAVE BOLTED CONNECTIONS. H. WHERE DOUBLE JOISTS ARE LOCATED PROVIDE BEARING PLATES OF TWICE THE NORMAL WIDTH SPECIFIED FOR MASONRY WALL SUPPORT. I. JOIST BEARING DETAILS INDICATING SUPPORT AT THE CENTER LINE OF THE MASONRY WALLS SHALL NOT BE CHANGED UNLESS APPROVED BY THE ENGINEER. J. SEAT DEPTHS SHALL BE AS FOLLOWS, ANY DEVIATIONS MUST BE APPROVED PRIOR TO SUBMITTAL OF SHOP DRAWINGS: 1. K & KCS JOIST: a. <1/4:12 SLOPE: 2.5" b. >1/4:12 SLOPE: PER SJI RECOMMENDATIONS VII. DECKING A. STEEL DECK SHALL BE DESIGNED AND FABRICATED IN COMPLIANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS, AND ROOF DECKS PUBLICATION. B. PROVIDE DECK IN LENGTHS ADEQUATE FOR A THREE-SPAN CONDITION WHERE POSSIBLE. C. THE CONTRACTOR SHALL VERIFY THE SIZE AND LOCATION OF ALL OPENINGS, SLEEVES, INSERTS, ETC., WITH SHOP DRAWINGS OF THE EQUIPMENT TO BE INSTALLED. D. STEEL DECK SHALL BE ATTACHED TO ALL MEMBERS ON WHOM IT BEARS. E. STEEL DECK SHALL HAVE SUFFICIENT BEARING AT END AND INTERMEDIATE SUPPORTS TO PREVENT WEB CRIPPLING (1 1/2" AND 3", RESPECTIVELY). MINIMUM SHORING BEAM WIDTHS SHALL BE PER THE DECK MANUFACTURER'S RECOMMENDATIONS. F. DECK MANUFACTURER SHALL PROVIDE CELL CLOSURES, COLUMN CLOSURES, FINISH STRIPS, GIRDER FILLERS, AND THE ATTACHMENTS AS REQUIRED TO ACHIEVE A COMPLETE SYSTEM. G. UNLESS INDICATED OTHERWISE, PROVIDE POUR STOPS OF LENGTH, DEPTH AND GAGE APPROPRIATE FOR OVERHANG AND SLAB DEPTH. H. GENERAL CONTRACTOR SHALL SUBMIT ALL ALTERNATE PRODUCTS TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO FABRICATION OF ANY MATERIAL I. CONDUIT SHALL NOT BE CAST WITHIN ANY ELEVATED SLABS WITHOUT ENGINEER APROVAL. IN NO CASE SHALL CONDUIT OUTER DIAMETER EXCEED 1/3 OF THE SLAB THICKNESS ABOVE THE DECK. VI. STRUCTURAL STEEL A. ALL HOT ROLLED STEEL PLATES, SHAPES, SHEET PILING, AND BARS SHALL BE NEW STEEL CONFORMING TO ASTM SPECIFICATION A6-98A. B. STRUCTURAL STEEL SHALL BE AS FOLLOWS, U.N.O.: 1. WIDE FLANGE SHAPES ASTM A992 FY = 50 KSI 2. STRUCTURAL RECTANGULAR TUBING ASTM A500 GRADE B FY = 46 KSI 3. ALL OTHER STRUCTURAL STEEL ASTM A36 FY = 36 KSI 4. CONNECTION MATERIALS: a. ALL OTHER CONNECTION MATERIAL, U.N.O.: ASTM A36 UNLESS A HIGHER GRADE OF STEEL IS REQUIRED BY STRENGTH AND PROVIDED THE RESULTING SIZES ARE COMPATIBLE WITH THE CONNECTED MEMBERS. 5. ASTM A572 GRADE 50 IS ACCEPTABLE AS A SUBSTITUTE FOR A992 C. STRUCTURAL STEEL SHALL MEET THE LATEST AISC "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS". D. THE CENTERLINES OF ALL COLUMNS AND BEAMS SHALL BE LOCATED ON COLUMN LINES UNLESS OTHERWISE SHOWN. E. CONNECTIONS: 1. BOLTS SHALL BE A325N TYPE 1, UNLESS OTHERWISE INDICATED. 2. ALL BOLTS SHALL BE SNUG TIGHT U.N.O. BOLTS SHALL BE TIGHTENED UNTIL ALL PLIES OF THE JOINT ARE IN FIRM CONTACT. 3. ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE. 4. THREADED RODS SHALL CONFORM TO ASTM A36 5. WELDING SHALL CONFORM TO THE STANDARDS SET FORTH IN AWS PUBLICATION, "WELDING IN BUILDING CONSTRUCTION". 6. UNLESS NOTED OTHERWISE, ELECTRODES FOR WELDING SHALL CONFORM TO E70XX (SMAW), F7XX-EXXX (SAW), ER70S-X (GMAW), OR E7XT-X (FCAW). 7. ALL ERECTION DRAWINGS SHALL SHOW ALL FIELD WELDS REQUIRED. 8. CONNECTION DETAILS NOT COMPLETELY DETAILED ON THE DRAWINGS SHALL BE DESIGNED BY THE CONTRACTOR'S ENGINEER TO RESIST FORCES INDICATED ON THE DRAWINGS. INDICATED FORCES ARE BASED ON FACTORED LOADS AND ARE INTENDED FOR USE WITH THE LOAD AND RESISTANCE FACTOR DESIGN METHOD. WHERE NONE ARE INDICATED, BEAMS SHALL BE DESIGNED FOR AN END REACTION EQUAL TO 1/2 OF THE TOTAL UNIFORM LOAD CAPACITY TABULATED IN THE UNIFORM LOAD TABLES OF THE AISC MANUAL. THE CONTRACTOR SHALL EMPLOY THE ASSISTANCE OF A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT. DESIGN CALCULATIONS FOR THE CONNECTIONS DESIGNED BY THE SPECIALTY ENGINEER SHALL BE SUBMITTED FOR THE FILES OF THE ARCHITECT AND ENGINEER. CALCULATIONS SHALL BEAR THE SEAL OF THE PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT. SHOP DRAWINGS CONTAINING CONNECTIONS FOR WHICH CALCULATIONS HAVE NOT BEEN RECEIVED WILL BE RETURNED UNCHECKED AS AN INCOMPLETE SUBMITTAL. CONNECTIONS ECCENTRICITY SHALL BE TAKEN INTO ACCOUNT WHEN DESIGNED AND DETAILING THE CONNECTION. F. WHERE THE WORK OF OTHER TRADES REQUIRES CUTS, HOLES, ETC., IN STRUCTURAL STEEL MEMBERS, CUTS, HOLES, ETC., SHALL BE MADE IN THE SHOP AND SHALL BE SHOWN ON THE SHOP DRAWINGS. MAKING HOLES OR CUTS IN STRUCTURAL STEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED WITHOUT SPECIFIC APPROVAL OF THE ENGINEER. G. GROUT BELOW BASE PLATES SHALL BE NON-METALLIC, NON-SHRINK GROUT WITH A MINIMUM STRENGTH OF 6000 PSI WHEN BEARING ON 3000 PSI CONCRETE OR LESS, STRENGTH OF 8000 PSI WHEN BEARING ON CONCRETE BETWEEN 3000 AND 4000 PSI. H. ALL STRUCTURAL STEEL SHALL BE SHIPPED WITH ONE COAT OF SHOP PRIMER EXCEPT THOSE MEMBERS THAT ARE GALVANIZED OR IN AREAS SCHEDULED TO RECEIVE FIRE PROOFING. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AREAS TO BE FIRE PROOFED. III. FOUNDATIONS A. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL INVESTIGATION REPORT BY PSI, INC DATED MAY 26, 2015. B. CONTRACTOR SHALL OBTAIN A COPY OF THE SOILS REPORT AND ADHERE TO ALL RECOMMENDATION WITHIN, INCLUDING PREPARATION OF SOILS AT BUILDING PAD. C. ALL SOILS WORK, INCLUDING BACKFILL OF UTILITY TRENCHES AND THE VERIFICATION OF BEARING CAPACITY OF SAME SHALL BE UNDER THE DIRECTION OF A QUALIFIED SOILS ENGINEER. PROXIMITY OF UTILITY TRENCHES TO BUILDING FOUNDATION SYSTEM SHALL BE AS APPROVED BY THE SOILS ENGINEER TO INSURE INTEGRITY OF THE BEARING SOILS. D. ALL FOOTINGS SHALL BEAR ON UNDISTURBED EARTH OR ENGINEERED FILL AT ELEVATIONS SHOWN ON PLANS AND DETAILS. FLOOR SLABS SHALL BEAR ON 4 INCHES OF COMPACTED STONE. THE MOISTURE RETARDER SHALL BE PLACED BETWEEN THE STONE AND THE SLAB. E. NO FOUNDATION CONCRETE SHALL BE INSTALLED UNTIL ALL FOUNDATION WORK HAS BEEN COORDINATED WITH UNDERGROUND UTILITIES. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ALL CONFLICTS THAT EXIST BETWEEN FOOTINGS AND UTILITIES. F. ALL FOUNDATIONS OR PORTIONS THEREOF, BELOW GRADE MAY BE EARTH FORMED BY NEAT EXCAVATIONS. G. UNLESS OTHERWISE SHOWN, ALL FOOTINGS SHALL BE CENTERED ON WALLS AND/OR COLUMNS. H. THE CONTRACTOR SHALL DETERMINE THE EXTENT OF CONSTRUCTION DEWATERING REQUIRED FOR THE EXCAVATION. THE CONTRACTOR SHALL SUBMIT TO THE GEOTECHNICAL ENGINEER FOR REVIEW THE PROPOSED PLAN FOR CONSTRUCTION DEWATERING, PRIOR TO EXCAVATION. I. FOOTINGS SHALL NOT BE PLACED ON FROZEN SUBGRADE OR IN STANDING WATER. J. FOUNDATION TYPE 1. SPREAD FOOTING: a. TOTAL LOAD: 2,000 PSF NET PRESSURE II. DESIGN CRITERIA A. THE CONTRACT DOCUMENTS ARE BASED ON THE REQUIREMENTS OF THE 2013 INDIANA BUILDING CODE (2012 INTERNATIONAL BUILDING CODE) B. DEAD LOADS 1. TYPICAL ROOF SYSTEMS: (20 PSF TOTAL) a. MEP*: 10 PSF b. INSULATION & ROOFING: 10 PSF * MISCELLANEOUS CEILING AND HANGING MECHANICAL LOADS SUCH AS DUCT WORK AND SPRINKLER PIPES. C. LIVE LOADS 1. LIVE LOADS ARE BASED ON THE MORE RESTRICTIVE OF THE UNIFORM LOAD LISTED BELOW OR THE CONCENTRATED LOAD LISTED ACTING OVER A 6.25 SQUARE FOOT AREA EXCEPT FOR PARKING GARAGES WHICH ACT OVER AN AREA OF 20 SQUARE INCHES. LIVE LOADS HAVE BEEN REDUCED AS PRESCRIBED IN THE AFOREMENTIONED BUILDING CODE. CATEGORY UNIFORM LOAD (PSF) CONCENTRATED LOAD (LBS) a. DINING ROOMS/RESTAURANTS 100 b. ROOFS ALL ROOF SURFACES SUBJECT TO WORKERS 300* ORDINARY ROOF 20 *OR EQUIPMENT WEIGHT IF GREATER D. DESIGN SNOW LOAD: GROUND SNOW LOAD, PG 20 PSF FLAT ROOF SNOW LOAD, PF 20 PSF EXPOSURE FACTOR, CE 1.0 SNOW THERMAL FACTOR, CT 1.0 SNOW IMPORTANCE FACTOR, I 1.0 RAIN ON SNOW SURCHARGE 5 PSF E. DESIGN WIND LOADS: BASIC WIND SPEED, Vu 115 MPH (3 SECOND GUST) WIND IMPORTANCE FACTOR, I 1.0 EXPOSURE B INTERNAL PRESSURE COEFF GCPI ±0.18 COMPONENT AND CLADDING LOADS (ULTIMATE): F. SEISMIC LOADS: SHORT PERIOD SPECTRAL RESPONSE ACCELERATION, SS 0.146 1-SEC PERIOD SPECTRAL RESPONSE ACCELERATION, S1 0.081 SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION, SDS 0.156 1-SEC PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION, SD1 0.130 RISK CATEGORY II SEISMIC DESIGN CATEGORY B SITE CLASS D BASIC SEISMIC-FORCE RESISTING SYSTEM BUILDING FRAME - LIGHT FRAME SHEAR WALL RESPONSE MODIFICATION FACTOR, R 7.0 DEFLECTION AMPLIFICATION FACTOR, CD 4.5 SEISMIC IMPORTANCE FACTOR IE 1.0 SEISMIC RESPONSE COEFFICIENT CS 0.022 ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE DESIGN BASE SHEAR V 4 KIPS G. THE CONTRACTOR SHALL VERIFY ALL MECHANICAL EQUIPMENT WEIGHTS, LOCATIONS AND ASSOCIATED OPENINGS WITH THE MECHANICAL CONTRACTOR AND SUBMIT SUCH INFORMATION PRIOR TO FABRICATION OF THE SUPPORTING STRUCTURE. PROMPTLY NOTIFY THE ENGINEER IF THE ACTUAL WEIGHT EXCEEDS THE WEIGHT SHOWN ON THE STRUCTURAL DRAWINGS. I. GENERAL A. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, SHOP DRAWINGS AND SPECIFICATIONS. B. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO OBTAIN ALL CONTRACT DOCUMENTS AND LATEST ADDENDA AND TO SUBMIT TO ALL SUBCONTRACTORS AND SUPPLIERS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS. C. THE GENERAL CONTRACTOR SHALL COMPARE ALL CONTRACT DRAWINGS AND REPORT ANY DISCREPANCY BETWEEN DISCIPLINES AND WITHIN A GIVEN DISCIPLINE TO THE ARCHITECT AND ENGINEER PRIOR TO FABRICATION AND ERECTION. D. IF A CONFLICT EXISTS AMONG THE STRUCTURAL DRAWINGS, GENERAL NOTES, OR THE SPECIFICATIONS, THE STRICTEST REQUIREMENTS, AS INDICATED BY THE ENGINEER, SHALL GOVERN. E. THE CONTRACTOR SHALL COORDINATE ALL ELEVATIONS AND DIMENSIONS, INCLUDING BUT NOT LIMITED TO THOSE FOR OPENINGS IN WALLS AND IN ROOF AND FLOOR SYSTEMS, WITH THE ARCHITECTURAL, PLUMBING, ELECTRICAL, AND MECHANICAL PLANS. F. ALL DIMENSIONS, ELEVATIONS, AND ANY OTHER CONDITIONS OF ANY EXISTING STRUCTURES OR OTHER FEATURES SHALL BE VERIFIED BY THE GENERAL CONTRACTOR AND ANY DISCREPANCIES WITH THE CONTRACT DRAWINGS REPORTED TO THE ARCHITECT AND ENGINEER BEFORE PROCEEDING WITH THE AFFECTED PART OF THE WORK. DURING THE CONSTRUCTION PROCESS, IT SHALL BE SOLELY THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF THE EXISTING STRUCTURE AND TO PROTECT FROM DAMAGE ANY PORTIONS THAT ARE TO REMAIN. G. THE COMPLETED LATERAL-FORCE RESISTING SYSTEMS AND DIAPHRAGMS ARE REQUIRED FOR THE STRUCTURE TO RESIST LATERAL LOADS AND PROVIDE STABILITY UNDER GRAVITY LOADS. DURING THE CONSTRUCTION PROCESS, THE CONTRACTOR SHALL PROVIDE ALL REQUIRED BRACING DURING CONSTRUCTION TO MAINTAIN THE STABILITY AND SAFETY OF ALL STRUCTURAL ELEMENTS UNTIL THE LATERAL-LOAD RESISTING OR STABILITY-PROVIDING SYSTEM IS COMPLETELY INSTALLED AND THE STRUCTURE IS COMPLETELY TIED TOGETHER. H. UNLESS OTHERWISE NOTED, DETAILS SHOWN ON ANY DRAWING ARE TO BE CONSIDERED TYPICAL FOR ALL SIMILAR CONDITIONS. I. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS AND FOR SAFETY PRECAUTIONS AND PROGRAMS. J. BRITT, PETERS & ASSOCIATES, INC. SHALL NOT BE RESPONSIBLE FOR THE ACTS OR OMISSION OF THE CONTRACTOR OR FOR THEIR FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ft 7.7 Width of pressure coeff. zone, a: -29.1 -33.2 -36.3 -39.4 -43.5 -46.6 - 37.3 38.7 39.7 45.3 52.7 58.2 +Area 3 Corner -29.1 -31.8 -33.9 -36.0 -38.7 -40.8 - 37.3 38.7 39.7 45.3 52.7 58.2 +Area 2 Edge Parapet: Effective Wind Area (sqft) Parapet Design Pressure (psf): -16.0 -16.0 -16.0 -25.2 -39.5 -50.3 - 16.0 16.0 16.0 16.0 16.0 16.0 +Area 3 Corner -19.9 -25.0 -28.7 -29.3 -30.0 -30.5 - 16.0 16.0 16.0 16.0 16.0 16.0 +Area 2 Edge -19.9 -25.0 -28.7 -29.3 -30.0 -30.5 - 16.0 16.0 16.0 16.0 16.0 16.0 +Area 1 Interior 500 200 100 50 20 10 Overhang: -23.0 -23.0 -23.0 -26.8 -31.8 -35.6 - 16.0 16.0 16.5 17.7 18.5 19.4 +Area 3 Corner -23.0 -23.0 -23.0 -26.8 -31.8 -35.6 - 16.0 16.0 16.5 17.7 18.5 19.4 +Area 2 Edge -19.4 -19.4 -19.4 -19.9 -20.6 -21.2 - 16.0 16.0 16.0 16.0 16.0 16.0 +Area 1 Interior Roof: -16.2 -18.4 -20.1 -22.4 -24.1 -25.9 - 16.0 16.0 16.5 17.7 18.5 19.4 +Area 5 Edge -16.2 -17.3 -18.2 -19.3 -20.1 -21.0 - 16.0 16.0 16.5 17.7 18.5 19.4 +Area 4 Interior Walls: Effective Wind Area (sqft) Design Wind Pressure (psf): 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ GENERAL NOTES S0.0 NO. DATE REMARKS X-5. PRIOR TO PLACEMENT OF CONTROLLED FILL, OBSERVE SUBGRADE AND VERIFY THAT SITE HAS BEEN PREPARED PROPERLY -X4. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING PLACEMENT AND COMPACTION OF CONTROLLED FILL X-3. PERFORM CLASSIFICATION AND TESTING OF CONTROLLED FILL MATERIALS. X-2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL. X-1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY. 1705.6 SOILS PERIODIC CONTINUOUS IBC REFERENCE REFERENCED STANDARD FREQUENCY OF INSPECTION VERIFICATION AND INSPECTION X-1. VERIFY COMPLIANCE WITH APPROVED SUBMITTALS TABLE 1.19.1 LEVEL A QUALITY ASSURANCE 1705.4 TMS 402/ACI 530/ASCE 5 AND TMS 602/ACI 530.1/ASCE 6 MASONRY CONSTRUCTION PERIODIC CONTINUOUS IBC REFERENCE REFERENCED STANDARD FREQUENCY OF INSPECTION VERIFICATION AND INSPECTION ACI 318: 6.1.1 X-12. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED ACI 318: 6.2 X- 11. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS. ACI 318: CH. 16 X-10. ERECTION OF PRECAST CONCRETE MEMBERS. ACI 318: 18.18.4 -XB. GROUTING OF BONDED PRESTRESSING TENDONS IN THE SEISMIC FORCE-RESISTING SYSTEM ACI 318: 18.20 -XA. APPLICATION OF PRESTRESSING FORCES 9. INSPECTION OF PRESTRESSED CONCRETE 1910.9 ACI 318: 5.11-5.13 X-8. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES 1910.6, 1910.7, 1910.8 ACI 318: 5.9, 5.10 -X7. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES 1910.10 ASTM C 172, ASTM C 31, ACI 318: 5.6, 5.8 -X 6. AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TEST, AND DETERMINE THE TEMPERATURE OF THE CONCRETE 1904.2, 1910.2, 1910.3 ACI 318: CH. 4, 5.2-5.4 X-5. VERIFYING USE OF REQUIRED DESIGN MIX. 1909.1 ACI 318: 3.8.6, 8.1.3, 21.2.8 X-4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS 1908.5, 1909.1 ACI 318: 8.1.3, 21.2.8 X-3. INSPECTION OF ANCHORS CAST IN CONCRETE WHERE ALLOWABLE LOADS HAVE BEEN INCREASED OR WHERE STRENGTH DESIGN IS USED. AWS D1.4, ACI 318: 3.5.2 --2. INSPECTION OF REINFORCING STEEL WELDING IN ACCORDANCE WITH TABLE 1705.2.2, ITEM 2B. 1910.4 ACI 318: 3.5, 7.1-7.7 X-1. INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, AND PLACEMENT. 1705.3 ACI 318 CONCRETE CONSTUCTION PERIODIC CONTINUOUS IBC REFERENCE REFERENCED STANDARD FREQUENCY OF INSPECTION VERIFICATION AND INSPECTION 1705.2.2.2 X-A. VERIFY TEMPORARY AND PERMANENT RESTRAINT/BRACING ARE INSTALLED IN ACCORDANCE WITH THE APPROVED TRUSS SUBMITTAL PACKAGE 4. COLD-FORMED STEEL TRUSSES SPANNING 60 FEET OR GREATER X-D. OTHER REINFORCING STEEL -XC. SHEAR REINFORCEMENT -X B. REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, BOUNDARY ELEMENTS OF SPECIAL CONCRETE STRUCTURAL WALLS AND SHEAR REINFORCEMENT AWS D.1, ACI 318: SECTION 3.5.2 X-A. VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN ASTM A706 1705.2.2.1.2 3. REINFORCING STEEL AISC 360, N6 X-B. OTHER FASTENERS AWS D1.3 X-A. WELDING 1705.2.2.1.1 2. CONNECTION OF COLD-FORMED STEEL DECK TO SUPPORTING STRUCTURE X-B. MANUFACTURER'S CERTIFIED TEST REPORTS APPLICABLE ASTM MATERIAL STANDARDS X-A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS 1. MATERIAL VERIFICATION OF COLD-FORMED STEEL DECK 1705.2.2 STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL PERIODIC CONTINUOUS IBC REFERENCE REFERENCED STANDARD FREQUENCY OF INSPECTION VERIFICATION AND INSPECTION AISC 360, N6 7. COMPOSITE CONSTRUCTION AISC 360, N5.6 C. INSPECTION TASKS AFTER TO BOLTING AISC 360, N5.6 B. INSPECTION TASKS DURING TO BOLTING AISC 360, N5.6 A. INSPECTION TASKS PRIOR TO BOLTING 6. STRUCTURAL STEEL BOLTING AISC 360, N5.4 C. INSPECTION TASKS AFTER TO WELDING AISC 360, N5.4 B. INSPECTION TASKS DURING TO WELDING AISC 360, N5.4 A. INSPECTION TASKS PRIOR TO WELDING 5. STRUCTURAL STEEL WELDING X-4. VERIFY MEMBER LOCATIONS, BRACES, STIFFENERS, AND APPLICATION OF JOINT DETAILS AT EACH CONNECTION COMPLY WITH CONSTRUCTION DOCUMENTS 1705.3 X-3. EMBEDMENTS AISC 360, A3 X-B. MANUFACTURER'S CERTIFIED MILL TEST REPORTS AISC 360, A3 X-A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS 2. MATERIAL VERIFICATION OF STRUCTURAL STEEL AISC 360, N3 --1. FABRICATOR AND ERECTOR DOCUMENTS 1705.2 AISC 360 STEEL CONSTRUCTION PERIODIC CONTINUOUS IBC REFERENCE REFERENCED STANDARD FREQUENCY OF INSPECTION VERIFICATION AND INSPECTION 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ SPECIAL INSPECTIONS S0.1 NO. DATE REMARKS 1 1 2 27'-11 1/2" 32'-4" 21'-7 1/2" 3'-8" 3 3.8 4 4 AA A.4 A.4 A.9 B C C.4 DD 1.9 2.2 2.8 3.3 3.7 2' - 1 1 3 / 4 " 18 ' - 6 1 / 4 " 19 ' - 6 " S W 1 2 0 '-1 " 1 5 '-6 " A.2 C.1 C.2 1 5 '-2 " 8 '-5 " 1 5 '-4 " 2 9 '-8 " 8 '-0 " 25'-7 1/2" 9'-9" 19'-3 1/2" 9'-11 1/2" 14'-0" 6'-11 1/2" 1 '-1 0 1 /4 " 3 '-3 3 /4 " 1 1 '-5 1 /2 " 3 '-3 3 /4 " 3'-3 3/4" 11'-5 1/2" 3'-3 3/4" 8'-6 1/2" 1 '-5 " 1'-5" 5" 1'-0" 8 " 3'-10" 7'-2 1/4" 14'-4 5/8" 3'-10" 5" 18'-6 1/8" 3'-4" 10'-8 1/2" 3'-4" 2" 2 " 3 '-4 " 9 '-0 " 3 '-4 " 7 '-1 0 " 3 '-4 " 7 '-1 0 " 3 '-4 " 7 '-0 " 3 '-4 " 2 " 8 '-9 7 /8 " 4 8 '-8 " 7 '-0 7 /8 " 1 5 '-6 " HSS5X5X1/4 HSS5X5X1/4 HSS5X5X5/16 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X5/16 HSS5X5X5/16 HSS5X5X1/4 HSS5X5X5/16 HSS5X5X5/16 HSS5X5X5/16 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 HSS5X5X1/4 F5.0 F5.0 F5.0 F5.0 F5.0 F5.0 3 3/4" 3 '-2 3 /4 " 1 '-8 1 /2 " 1 '-8 1 /2 " 3 '-4 3 /4 " 5" 1 '-0 " 1 '-0 " 1'-0" 6" 6 " 5" 5" 1 5 '-1 1 /8 " 3 '-5 3 /4 " 5 '-4 1 /8 " 4'-4 1/2" F O S 2 " 1 1 " 5 " 1 '-8 " 1 1 " 8" FOS 8 " F O S 8 " F O S 2" 2" FOS 2'-0" SW2 12'-2 1/2" 2'-0" 2 '-0 " S W 3 1 2 '-3 3 /8 " 2 '-0 " S W 3 7 '-6 1 /2 " SW2 25'-2 1/2" BP2 BP3 BP2 BP2 BP2 BP2 BP2 BP2 BP3 5" BP2 BP2 6 S3.0 2 S3.0 1 S3.0 5 S3.0 8 S3.0 7 S3.0 4 S3.0 NOTE 2 NOTE 3 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 F3.0 W F 1 .8 W F 4 .0 W F 1 .5 W F 1 .5 WF4.0 WF1.5 WF1.5 WF4.0 WF1.5 WF4.0 W F 4 .0 WF4.0 WF1.8 7 6 '-7 " 85'-7" 1'-4" 12'-1 1/2" 1'-4" 4'-8 1/2" 11'-10" 1'-4" 5 '-8 " 1 '-4 " 1 0 '-8 " 1 '-4 " NOTE 12 NOTE 12 NOTE 12 NOTE 12 NOTE 12 9 S3.0 3 S3.0 WF1.5 10" DIA PONDEROSA PINE TYP AT PATIO S W 1 1 8 '-1 1 /4 " 2 '-0 " NOTE 11 NOTE 11 NOTE 11 NOTE 11 NOTE 11 NOTE 11 NORTH SLOPE DN REF ARCH 6 S3.0 SIM 4 S1.3 6 S3.0 SIM CJ C J REF NOTE 3 NOTE: REF ARCH FOR FLOOR SLOPES TO TRRENCH DRAINS 5 S1.3 1'-10 5/8" TYP NOTE 13 HSS3x3x1/4 HSS3x3x1/4 HSS3x3x1/4 11 S3.0 BP4 BP4 BP4 4 S1.3 SIM. W F 1 .5 3'-9 3/4" 2'-10 1/2" 6" 11" 5 " 3 '-4 3 /4 " 362S 162-33 MIL STUDS @ 16" OC REF ARCH FOR WALL LAYOUT AT EQUIPMENT PLATFORM ABOVE 2'-0" SW2 13'-5 1/2" 2'-0" WF4.0 3'-9 3/4" 12'-0 1/16" 55'-11 1/4" 15'-3 11/16" 3'-8" 11" 2'-10 1/2" 2 S3.0 1 S3.0 3 S3.0 1 S3.0 7 S3.0 1 S3.0 1 S3.0 5'-4 1/2" 3'-4" 1'-8 1/2" 10'-11 1/4" 3'-4" 12'-8" 3'-4" 6 '-4 " WF1.5 WF1.5 WF1.5 WF1.8 W F 1 .8 W F 1 .5 W F 1 .8 W F 1 .5 W F 4 .0 1. FINISHED FLOOR ELEVATION = 0'-0". 2. 4" CONC. SLAB REINF. W/6x6-W2.1xW2.1 WWR ON 10 MIL VAPOR RETARDER ON 4" STONE BASE ON GRADE. 3. 4" CONC. SLAB ON 4" STONE BASE ON GRADE. 3. CONTROL JOINT SHALL BE PLACED AT 15 FEET OC MAX. SLAB UNITS CREATED BY JOINT LAYOUTS SHALL BE AS SQUARE AS POSSIBLE & WITH A MINIMUM ASPECT RATIO OF 1.25 TO 1. IN ADDITION, CONTROL JOINTS SHALL BE LOCATED AT THE CORNERS OF ALL ISOLATION POCKETS. REFER TO 3/S4.00 FOR DETAILS. 4. DIMENSIONS TO EDGE OF SLAB, UNO. 5. T/FTG = [X'-X"] DENOTES TOP OF FOOTING ELEVATION: [-0'-8"] INTERIOR, TYP UNO. [-2'-6"] EXTERIOR, TYP UNO. 6. F# DENOTES FOOTING TYPE, REFER TO SCHEDULE ON S2.0. 7. WF# DENOTES WALL FOOTING TYPE, REFER TO SCHEDULE ON S2.0. 8. REFER TO SECTIONS ON S3.0 FOR WALL FOOTINGS. 9. EXTERIOR WALLS SHALL BE FRAMED W/ 600S 200-43 MIL STUDS @ 16" OC TYP UNO, SEE SECTIONS FOR LOCATIONS. 10. SW# DENOTES SHEAR WALL, REFER TO SCHEDULE ON S2.0. 11. DOUBLE WYTHE 8" CMU WALL REINFORCED WITH #5 @ 16" OC. 12. SHEAR WALL ANCHORS MUST BE CAST IN PLACE. 13. DENOTES INSULATED SLAB ON GRADE, REF 17/S2.0 & ARCH. DWGS FOR EXTENTS. FOUNDATION/SLAB NOTES 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ FOUNDATION PLAN S1.1 1/4" = 1'-0" 1 FOUNDATION PLAN NO. DATE REMARKS 1 1 2 3 3 3.8 4 AA A.4 A.4 A.9 B C C.4 DD 1.9 2.2 2.8 3.3 3.7 A.2 C.1 C.2 27'-11 1/2" 32'-4" 25'-3 1/2" 1 5 '-2 " 8 '-5 " 1 5 '-4 " 2 2 '-2 " 7 '-6 " 8 '-0 " 2 '-1 1 3 /4 " 1 8 '-6 1 /4 " 1 9 '-6 " 2 0 '-1 " 1 5 '-6 " 25'-7 1/2" 9'-9" 19'-3 1/2" 9'-11 1/2" 14'-0" W 1 4 X 2 2 W14X22 W14X22 W 1 4 X 2 2 W 1 2 X 1 9 W 1 4 X 2 2 W 1 4 X 2 2 W12X19 W 1 2 X 1 9 W 1 2 X 1 9 W 1 2 X 1 9 W 1 4 X 2 2 W 1 4 X 2 2 W 1 4 X 2 2 W 1 4 X 2 2 W 1 2 X 1 9 W 1 2 X 1 9 W 1 2 X 1 9 W 1 2 X 1 9 W 1 2 X 1 9 W14X22 W12X19 W14X22 W14X22 W14X22 W14X22 W12X19 21'-7 1/2" 3'-8" 18'-4" 6'-11 1/2" 78'-7 1/2" 7 6 '-7 " B /D E C K = 2 1 ' - 1 0 1 /2 " B /D E C K = 2 0 ' - 1 " 2 S4.0 4 S4.0 1 S4.0 3 S4.0 11 S4.0 11 S4.0 SIM NOTE 4 NOTE 5 TYP NOTE 4 NOTE 4 NOTE 4 NOTE 5 TYP NOTE 5 TYP NOTE 3 NOTE 3 N O T E 2 SLOPE DN MUA-3 2250# MUA-3 857# KEF-3 373# KEF-2 182# KEF-4 180# MUA-2 619# KEF-1 182# RTU-2 1022# RTU-1 1624# KEF-5 243# RTU-3 1624# RTU-4 1624# EF-1 70# RTU-5 2522# NORTH 5 '-6 " 4 '-6 " 5 '-0 " 4 '-0 " 4 '-0 " 4 '-8 " 4 '-0 " 3 '-1 " 3 '-0 " 4 '-6 " 5 '-0 " NOTE 8 4 '-0 " 4 '-6 " 20K3 20K3 20KCS2 20KCS2 20K3 20K3 20KCS2 20KCS2 20K3 20KCS2 20KCS2 20KCS2 20K3 20K5 20K5 20K5 18KCS3 18KCS3 20K5 20K5 20K5 20K5 20K5 20KCS3 20KCS3 20K5 18K3 18K3 18K3 18K3 18K3 18KCS2 18KCS2 18KCS2 18K3 18K3 18K3 18K3 18K3 NOTE 8 NOTE 8 NOTE 8 NOTE 8 J O I S T S @ 6 '-0 " O .C . M A X J O I S T S @ 6 '-0 " O .C . M A X J O I S T S @ 6 '-0 " O .C . M A X R 1 5 R 1 5 R 1 5 R 1 5 R 1 5 R 1 5 R 1 5 R 2 5 R 2 5 R 2 5 R 2 5 R 2 5 R 2 5 R 2 5 R 2 5 R15 R15 R15 R15 R15 R15 R15 R15 R15 R 1 5 R 1 5 NOTE 7 TYP NOTE 7 TYP NOTE 7 TYP 10'-0" L5x5x5/16 @ 5'-0" OC L5x5x5/16 TYP 13 S4.0 4 S4.0 9 S4.0 1 S4.0 SIM SIM L5x5x5/16 TYP L5x5x5/16 TYP 14 S4.0 9 S4.0 8 S4.0 17 S4.0 NOTE 8 NOTE 8 SIGN REF ARCH. ROOF FRAMING PLAN NOTES 1. B/ DECK ELEVATION = REF PLAN. 2. 1.5" 22 GA TYPE B G60 GALVANIZED METAL ROOF DECK, REF 16/S2.0 FOR ATTACHMENT. 3. ALIGN JOIST WITH WALL ABOVE AS SHOWN. DESIGN JOISTS FOR THE FOLLOWING SERVICE LOADS FROM THE TOWER WALL: DL = 405 PLF LL = 240 PLF WL = 113 PLF ± 4. UPLIFT BRIDGING AT FIRST PANEL POINT PER SJI. 5. STANDARD BRIDGING PER SJI. 6. TOWER WALLS SHALL BE FRAMED WITH 600S162-43 MIL STUDS @ 16" OC. 7. REF 11/S2.0 FOR CURB/OPENING FRAMING. 8. DESIGN TRUSSES FOR ±385 PLF SERVICE WIND LOAD. W12x19 ( ) R50 A20 M50/0 NUMBER OF SHEAR CONNECTIONS MOMENT CONNECTION EACH END REACTION (KIPS) DENOTES END MOMENTS OF 50 K-FT AT LEFT END AND 0 K-FT AT RIGHT END DENOTES AXIAL FORCE FOR CONNECTION DESIGN (KIPS) 1.5C CAMBER BEAM LEGEND 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ MAIN ROOF FRAMING PLAN S1.2 1/4" = 1'-0" 1 ROOF FRAMING PLAN NO. DATE REMARKS 1 DD 3.7 11 S4.0 11 S4.0 SIM 4 '-2 " 1 5 '-1 1 /2 " 4 '-2 " 4'-2" 15'-9 5/8" 4'-2" 4'-2" 12'-9 1/2" 6'-2 1/4" 23'-1 3/4" 2 5 '-6 3 /8 " 4 '-2 " 1 7 '-2 1 /4 " 4 '-2 1 /8 " 1 '-8 1 /2 " 2 '-3 1 /4 " 1 '-9 1 /4 " 2 '-3 1 /4 " 6" 3'-9" 2'-5 1/2" 1'-8 1/2" 1'-9 1/2" 2 3/4" 3'-6" 1 '-2 7 /8 " 11 3/8" 1 '-1 1 3 /4 " 1'-11 3/4" SLOPE DN 2 3 '-5 1 /2 " 24'-1 5/8" SLOPE DN S L O P E D N S L O P E D N NOTE 3 (2) 600S162-43 MIL STUDS TYP AT VALLEYS NOTE 3 N O T E 3 N O T E 3 NOTE 3 N O T E 3 NOTE 3 N O T E 3 SLOPE DN SLOPE DN S L O P E D N S L O P E D N B/ DECK = 31'-9 1/4" TYP AT PERIMETER B/ DECK = 35'-1 1/4" TYP AT PERIMETER 4'-5" 1 '-5 1 /4 " 6'-5 1/4" 5 '-1 1 1 /4 " 5 S4.0 4 B C C.4 4 x 8 R O U G H S A W N C E D A R @ 2 4 " O C 6x10 ROUGH SAWN CEDAR TYP 6x10 ROUGH SAWN CEDAR TYP 6x10 ROUGH SAWN CEDAR 6x10 ROUGH SAWN CEDAR 3 S1.3 HIGH ROOF FRAMING PLAN NOTES 1. B/ DECK ELEVATION = REF PLAN. 2. 1.5" 22 GA TYPE B G60 GALVANIZED METAL ROOF DECK, REF 16/S2.0 FOR ATTACHMENT. 3. 600S162-43 MIL STUDS @ 16" OC. 2 " 2 " 4 " 2 " 2 " 2 " 4 " 2 " 1 1 /2 " RAFTER REF PLAN BEAM REF PLAN PL 1/4"x3"x0'-8" W/ (2) 1/2" DIA THRU BOLTS 10 1/2" ID STD PIPE W/ (1) 1/2" DIA THRU BOLT REF ARCH. COL REF PLAN 3/16 TYP PL 1/4"x2"x1'-0" EA SIDE 10 1/2" INSIDE DIAMETER STD PIPE W/ 3/8" END PL & (1) 1/2" DIA THRU BOLT L3x3x1/4 W/ 1/2" DIA x 4" LAG BOLT EA SIDE & (1) 1/2" THRU BOLT AT EA RAFTER 3/16 EA SIDE NOTE: ALL STEEL AT PATIO SHALL BE HOT DIP GALV W/ POWDER COAT FINISH, REF ARCH #5@12" O.C. EA. WAY 8" CMU W/#5@16" O.C. 4#5xCONT. PL1/2"x13"x1'-1" W/(4) 1/2" DIA. ANCHOR RODS 1 '-0 " 10 1/2" INSIDE DIA STD. PIPE 3 '-8 " 1'-1" EQ EQ 1 '-1 " E Q E Q . TYP 1 1/2" BASE PLATE 4 CONC SLAB REF PLAN METAL STUD WALL REF PLAN NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 2'-1 5/8" (3) #3 @ 2" OC REM @ 6" OC ROUND WOOD COL REF PLAN (3) #5 VERT CL COL REF 5/S3.0 1'-10 5/8" 8" 8" 8 " 1 '-4 " 8 " 4CL COL (3) #5 EA WAY AT PILASTER 1 2 A A.4 7 '-5 " 8 '-8 3 /4 " W10x12 W10x12 8'-3 3/4" 6'-9 1/2" 7'-5" 7 3 /4 " 7'-6 1/8" 15'-0" 5'-5 3/8" 2'-4" 800S200-43 MTL STUDS @ 24" OC 18 S4.0 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ HIGH ROOF & TRELLIS FRAMING PLAN S1.3 1/4" = 1'-0" 1 HIGH ROOF FRAMING PLAN 1/4" = 1'-0" 2 TRELLIS FRAMING PLAN 1 1/2" = 1'-0" 3 SECTION 3/4" = 1'-0" 4 SECTION 3/4" = 1'-0" 5 SECTION 1/4" = 1'-0" 6 EQUIPMENT PLATFORM PLAN NO. DATE REMARKS SAW JOINT AS SOON AS POSSIBLE AFTER CONCRETE IS PLACED SO AS NOT TO DAMAGE SLAB "D " "D "/4 GREASED 1/2" DIA x 24" LONG DOWEL @ 24" OC AFTER REMOVING FORMS PULL DOWEL 1 1/2" CONSTRUCTION JOINT AT CONTRACTORS OPTION WHEN FORMED EDGE IS STRIPPED, LIGHTLY GRIND. DEBUR EDGE AT TOP DO NOT TOOL COLUMN, REF PLAN 2'-0" SQUARE ISOLATION POCKET CJ CJ C J C J NOTE: IT IS IMPERATIVE THAT THE ORIENTATION OF ISOLATION POCKET BE AS THAT SHOWN (WITH CORNERS AT CONTROL JOINTS) TO PREVENT EXCESSIVE CRACKING IN SLAB. JOIST LC O F S U P P O R T WID T H C O V E R 1 1/2" DEEP,WIDE RIB METAL ROOF DECK DECK-TO-SUPPORT FASTENING (REFER TO GENERAL NOTES) DECK BOUNDARY EDGE SUPPORT FASTENING (REFER TO GENERAL NOTES) DECK BOUNDARY EDGE SUPPORT FASTENING (REFER TO GENERAL NOTES) SIDELAPS FASTENING BETWEEN SUPPORTS (REFER TO GENERAL NOTES) NOTES: 1. DECK AT PERIMETER OF BULDING TO BE WELDED TO JOISTS OR ANGLES UNO. 2. END LAPS TO OCCUR AT SUPPORTS ONLY, MINIMUM LAP = 2". 3. METAL DECK SHALL BE CONTINUOUS OVER A MINIMUM OF 2 SPANS. 4. BUTT WELD ALL SPLICES AT PERIMETER ANGLE. SHEAR WALL SCHEDULE SEE DESIGN NOTE 1 SEE DESIGN NOTE 1 SEE DESIGN NOTE 1 "SW1" "SW2" "SW3" 5/8" DIA CIP 7/8" DIA CIP 18" 18" - - - SHEATHING TYPE SHEAR WALL MARK REMARKS HOLDOWN ANCHORS END POST HOLDOWN MODEL NO ANCHOR EMBED INTERMEDIATE SILL ANCHORS AND SPACING SCREW PATTERN EDGES INTERMEDIATE PANELS 5/8" DIA AB @ 32" OC 5/8" DIA AB @ 32" OC 5/8" DIA AB @ 32" OC 6" OC 4" OC 4" OC 12" OC 12" OC 12" OC S/HDU4 S/HDU9 (REF 14/S2.0) HSS COL NOTES: 1. END POST REQUIREMENTS AT SHEAR WALLS: (2) 600S200-54 MIL STUDS. 2. HOLDOWN ANCHORS ARE SPECIFIED IN THE SCHEDULE FOR EACH SHEAR WALL. 3. FOR BOTTOM SILL PLATE TO FOUNDATION CONNECTORS SEE SCHEDULE FOR TYPE AND SPACING. 4. FASTEN STUD TO COLUMN PER 14/S2.0 WHERE COLUMN IS SW END POST. SHEAR WALL DESIGN NOTES: 1. SHEAR WALL SHEATHING: 5/8" BLOCKED APA RATED STRUCTURAL SHEATHING, EXPOSURE I, PLYWOOD. 2. SCREW TYPE: #8 TEK SCREWS. 3. SCREW SPACING: SEE SCHEDULE. 4. SEE ELEVATION NOTES AND SCHEDULE FOR END POST, HOLDOWN AND SILL PLATE TO FOUNDATION ANCHOR REQUIREMENTS. 5. SEE FOUNDATION PLAN FOR SHEAR WALL (SW#) LOCATION. 6. ALL HOLDOWN TYPES (EXCEPT INTERMED. A.B'S) REFER TO "SIMPSONS STRONG-TIE" MODEL NO'S. (OR APPROVED EQUAL). BP2 3 SIDES PL 1/2"x12"x1'-0" W/ (4) 3/4" DIA F1554 GR 36 ANCHOR RODS 0 ' - 6 " 0 ' - 6 " 0 ' - 1 1 /2 " 0 ' - 1 1 /2 " 0' - 2 1/2" 0' - 9 1/2" 0' - 3" 0' - 1 1/2" BP1 TYP PL 1/2"x12"x1'-0" W/ (4) 3/4" DIA F1554 GR 36 ANCHOR RODS 0 ' - 6 " 0 ' - 6 " 0 ' - 1 1 /2 " 0 ' - 1 1 /2 " 0' - 6" 0' - 6" 0' - 1 1/2" 0' - 1 1/2" B Y S T E E L S U P P L I E R P R O J E C T A S R E Q D 1 2 " E M B E D M E N T DBL NUTS W/ WASHERS TYP 3/4" DIA F1554 A36 ANCHOR ROD 2" SQ X 3/8" PL WASHER TYP ANCHOR ROD BP3 2 SIDES PL 1/2"x12"x1'-0" W/ (3) 3/4" DIA F1554 GR 36 ANCHOR RODS 0 ' - 9 1 /2 " 0 ' - 2 1 /2 " 0 ' - 1 1 /2 " 0' - 2 1/2" 0' - 9 1/2" 0' - 3" 0' - 1 1/2" 0 ' - 3 " BP4 TYP PL 1/2"x10"x0'-10" W/ (4) 3/4" DIA F1554 GR 36 ANCHOR RODS 0 ' - 5 " 0 ' - 5 " 0 ' - 1 1 /2 " 0 ' - 1 1 /2 " 0' - 5" 0' - 5" 0' - 1 1/2" 0' - 1 1/2" OPENING LC JOIST LC JOIST L5x5x5/16 TYP VARIES SEE PLANS 1/4" TYP 2 '-0 " M A X 1 /4 " T Y P 3/16 TYP 3/16 0 ALIGN STL ANGLE W/ EQUIP CURB LOCATIONS, REF ARCH CHORD PANEL POINT LOAD POINT TO TOP CHORD PANEL POINT NOT AT BOTTOM HANGING LOAD IF EQUIPMENT IF NOT AT TOP CHORD PANEL POINT MIN. AS REQ'D. BY JST. MANUF. L2 X 2 X 1/4 FROM LOAD POINT TO BOTTOM CHORD PANEL POINT L2 X 2 X 1/4 FROM LOAD FROM ROOF TOP TOP CHORD SPLICE REF DETAIL, STAGGER LOCATIONS OF SPLICES FIELD FASTENING REF SCHEDULE PROVIDE EDGE FASTENING PER SCHEDULE AT ALL BLOCKING LOCATED AT ROOF DIAPHRAGM ELEVATION SILL ANCHORS PER SHEAR WALL SCHEDULE CONT TRACK CONT. BLOCKING TO MATCH STUD DEPTH AND THICKNESS AT ALL JOINTS IN SHEATHING, STAGGER JOINTS AS SHOWN WALL STUDS , REF PLAN BLOCKING AT ELEVATION OF ROOF DIAPHRAGM (PARAPET LOCATIONS AS REQ'D) CONT. TOP PLATE EDGE FASTENER PER SCHEDULE HEADER, REF SCHEDULE (1) SCREW AT EACH CORNER OF SHEATHING EDGE FASTENING: REF SHEARWALL SCHEDULE CENTER JOINT ON WALL STUD MEMBER MIN OF (1) JAMB STUD BEARING UNDER SILL REF SCHED MIN OF (2) KING STUDS FULL-HEIGHT AT EACH HOLDOWN, REF SCHEDULE CONT TRACK HOLDOWN REF TO PLAN REF PLAN HEADER SCHEDULE NOTES: STUDS ARE 600S162-54 TRACKS ARE 600T125-54 1 HORIZONTAL STUD 3 HORIZONTAL TRACKS 2 VERTICAL STUDS W/ STIFFCLIP HE CONNECTION 2 VERTICAL STUDS 2 HORIZONTAL STUDS W/ VERTICLIP SLB EA. SIDE AT TOP & STIFFCLIP AL EA. SIDE AT BOTTOM 1 HORIZONTAL STUD 1 HORIZONTAL TRACK 3 VERTICAL STUDS 3 VERTICAL TRACKS 4 HORIZONTAL TRACKS 2 HORIZONTAL STUDS W/ STIFFCLIP HE CONNECTION 3 VERTICAL STUDS 3 VERTICAL TRACKS W/ VERTICLIP SLB EA. SIDE AT TOP & STIFFCLIP AL EA SIDE AT BOTTOM 2 HORIZONTAL STUDS 2 HORIZONTAL TRACKS HEADER SPAN UP TO 10'-0" JAMB SILL UP TO 15'-4" 2 HORIZONTAL TRACKS 2 VERTICAL STUDS W/ STIFFCLIP HE CONNECTION 2 VERTICAL STUDS 2 HORIZONTAL STUDS W/ VERTICLIP SLB EA. SIDE AT TOP & STIFFCLIP AL EA. SIDE AT BOTTOM 1 HORIZONTAL STUD 1 HORIZONTAL TRACK UP TO 6'-0" HSS COLUMN, REF PLAN ATTACH END STUD TO HSS COLUMN W/ (2) 0.156" DIA PAFS @ 4" OC SHEAR WALL 0 ' - 4 " R E F A R C H F R E E Z E R F L R & I N S U L , 0' - 8" 0' - 8" FREEZER/COOLER DOOR BY SUPPLIER 0' - 6 1/2" 0 ' - 4 " #4@18" OC FREEZER/COOLER FLOOR BY SUPPLIER 6x6 BLOCKING W/ SIMPSON A34 TOP & BOTTOM AS SHOWN 2x6 x 2'-0" @ CANOPY ATTACHMENT W/(2)#10 SCREWS TO EA. WALL STUD CANOPY TIE ROD BY SUPPLIER REF ARCH PROVIDE STEEL TUBE COMPRESSION SLEEVE THRU VENEER (GALV) NOTE : USE SIMILAR BLOCKING DETAIL AT BOTTOM CANOPY ATTACHMENT WHERE NO HEADER IS PRESENT 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ TYPICAL DETAILS S2.0 3/4" = 1'-0" 3 CONTROL/ CONSTRUCTION JOINT DETAIL 3/4" = 1'-0" 4 TYP ISOLATION POCKET 3/4" = 1'-0" 16 1 1/2" ROOF DECK FASTENING ISOMETRIC 1" = 1'-0" 5 BASE PLATES & ANCHOR ROD DETAIL 3/4" = 1'-0" 11 ROOF CURB/OPENING SUPPORT 3/4" = 1'-0" 12 JOIST REINF AT POINT LOAD 3/4" = 1'-0" 7 TYPICAL SHEAR WALL FRAMING DETAIL & SCHEDULE FOOTING (F) SCHEDULE MARK DIMENSION REINFORCING REMARKS "W" "L" "H" F3.0 3' - 0" 3' - 0" 1' - 0" (3) #5 EW BOTT ---- F5.0 3' - 0" 3' - 0" 1' - 0" (6) #5 EW BOTT ---- WALL FOOTING (WF) SCHEDULE MARK DIMENSION REINFORCING REMARKS "W" "L" "H" WF1.5 1' - 6" CONT. 1' - 0" (2) #5 CONT ---- WF1.8 1' - 10" CONT. 1' - 0" (2) #5 CONT ---- WF4.0 4' - 0" CONT. 1' - 0" (4) #5 CONT ---- N.T.S. 14 DETAIL 1 1/2" = 1'-0" 17 INSULATED SLAB NO. DATE REMARKS 1" = 1'-0" 18 CANOPY CONNECTION TOP TRACK, MATCH LT GA THICKNESS UNLESS NOTED OTHERWISE ATTACH LT GA TO RUNNER TRACK W/ #8-18 SCREWS IN EACH FLANGE STUD TO TOP TRACK CONNECTION CONT TRACK STUD PIECE, 6" LONG MIN, W/ (6) #10-16 SCREWS TO JAMB SILL REF SCHED FASTEN ELEMENTS TOGETHER W/ #8-18 SCREWS @ 12" OC MAX BUILT-UP SILL CLOSURE TRACK WITH #10- 16 SCREWS AT 12" OCEACH FLANGE BOXED HEADER TYP, REF SCHED ATTACH JAMB STUDS TOGETHER W/ (2) #10-16 CREWS @ 12" OC TYP HE-43 50 KSI W/ (20) #10-16 SCREWS EACH SIDE OF HEADER JAMB REF SCHEDULE 3"X3"X16 GA. x5 1/2" LG. CLIP ANGLE ATTACHED TO JAMB AND BOX HEADER T&B W/ (4) #10-16 SCREWS EACH LEG SCREW ATTACH JAMB STUDS TOGETHER W/ (2) #8-18 SCREWS @ 12" OC, TYP LT GA JAMB STUDS REF SCHED DOUBLE JAMB STUDS WITH CLOSURE TRACK - FULL HEIGHT CLOSURE TRACK W/ #8-18 SCREWS @ 12" OC, EACH FLANGE CONT SILL TRACK, REF SCHED STUD PIECE ATTACHED W/ (4) #10-16 SCREWS TYPICAL SILL TO JAMB CONNECTION D D WW D W S I Z E SIZE ZEES CEES TRACK ANGLE MEMBERS ARE DESIGNATED ON DETAILS AND PLANS AS FOLLOWS: •CEES - 600S162-033 D S=STUDS W THICKNESS IN MILS •TRACKS - 600T125-033 D T=TRACK W THICKNESS IN MILS •ZEES - 8ZS2.25-070 D ZS=Z-SEC LIP W THICKNESS IN INCHES •ANGLES - L3x3x16ga SIZE THICKNESS IN GAUGE 125 = 1.25" = 1 1/4" 362 = 3.62" = 3 5/8" 137 = 1.37" = 1 3/8" 400 = 4.00" = 4" 162 = 1.62" = 1 5/8" 600 = 6.00" = 6" 200 = 2.00" = 2" 800 = 8.00" = 8" 250 = 2.50" = 2 1/2" 1000 = 10.00" = 10" 300 = 3.00" = 3" 1200 = 12.00" = 12" D = SECTION DEPTH W = FLANGE WIDTH MIL - GAUGE DESIGNATIONS MIL THICK GAUGE 33 43 54 68 97 118 20 GA 18 GA 16 GA 14 GA 12 GA 10 GA L EN G T H 3/4" 1/2" 3/4" 3/4" 1 1/2" 16 GA U-CHANNEL @ 4'-0" SPACING 1 1/2 x 1 1/2 x 16 GA x 0'-5 1/2" CLIP ANGLE, FASTENED TO STUD & U-CHANNEL W/ (2) #10- 16 SCREWS PER CONNECTION TYP LATERAL BRIDGING 2 " M I N 6 " 3 " ATTACH LT GA TO TRACK W/ (2) #8-18 SCREWS THROUGH EACH FLANGE RUNNER TRACK W/ 1 1/4" LEGS TYP PROVIDE 0.145" DIA POWER DRIVEN FASTENER W/ 1 1/4" MIN EMBEDMENT. (6) AT EA JAMB TYP ANCHORAGE AT JAMBS LT GA JAMB STUDS ATTACH LT GA TO RUNNER TRACK W/ #8-18 SCREW THROUGH EACH FLANGE PROVIDE 0.145" DIA POWER DRIVEN FASTENER W/ 1 1/4" MIN EMBEDMENT @ 16" OC TYP LT GA FRAMING RUNNER TRACK W/ 1 1/4" LEGS TYP RUNNER TRACK ANCHORAGE (2) TRACKS BACK-TO-BACK. REF SCHED #10-16 SCREWS @ 12" OC, EACH FLANGE REF SCHED #10-16 SCREWS @ 12" OC, EACH FLANGE BOXED HEADER DETAIL TRACK REF SCHED 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ TYPICAL DETAILS S2.1 3/4" = 1'-0" 1 DETAIL 3/4" = 1'-0" 2 DETAIL 3/4" = 1'-0" 3 DETAIL 3/4" = 1'-0" 4 DETAIL 3/4" = 1'-0" 8 DETAIL 3/4" = 1'-0" 5 DETAIL 3/4" = 1'-0" 6 DETAIL 3/4" = 1'-0" 7 DETAIL 3/4" = 1'-0" 9 DETAIL NO. DATE REMARKS T/ FOOTING = REF PLAN T/ SLAB = REF PLAN (2) #5 CONT BOTT (1) #5 CONT CONC SLAB REF PLAN #5 @ 9" OC #5 @ 12" OC METAL STUD WALL REF PLAN REF ARCH FRT PLYWD SHEATHING CONT TRACK TO MATCH STUD GAUGE W/ 0.156" DIA PAFS @ 16" OC TYP EQ EQ EQ EQ 1 2 " & SCHED REF PLAN 8" . TYP 3" CLR OF STUD 2" FACE EQ EQ T/ FOOTING = REF PLAN T/ SLAB = REF PLAN METAL STUD WALL REF PLAN REF ARCH FRT PLYWD SHEATHING EQ EQ & SCHED REF PLAN OF STUD 5 5/8" FACE NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 362S162-33 MIL STUD TIES @ 48" OC T/ FOOTING = REF PLAN T/ SLAB = REF PLAN (2) ADDITIONAL #5 CONT BOTT CONC SLAB REF PLAN #5 @ 9" OC #5 @ 12" OC METAL STUD WALL REF PLAN REF ARCH FRT PLYWD SHEATHING EQ EQ & SCHED REF PLAN OF STUD 2" FACE CLR 3" 5" PLAN REF NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 T/ FOOTING = REF PLAN T/ SLAB = REF PLAN CONC SLAB REF PLAN (4) #5 VERT HSS COL REF PLAN REF ARCH T FTG SIZE & REINF REF PLAN & SCHED FOR EQ 16" EQ BASE PLATE REF S2.0 1 1/2" GROUT TYP 6 " O C R E M @ @ 2 " O C (3 ) #3 T I E S 2 " 16"x16" CONC PIER, TYP AT ALL EXT COLS PROVIDE 3" COVER MIN . ISOLATION POCKET, REF PLAN COLUMN, REF PLAN CONC SLAB REF PLAN FOOTING SIZE & REINFORCEMENT REF TO SCHEDULE FOR T 3" CLR TYP C L R 3 " T/ SLAB REF PLAN T/ FOOTING REF PLAN . BASE PLATE, REF S2.0 G R O U T 1 1 /2 " CONC SLAB REF PLAN METAL STUD WALL REF PLAN EQ EQ REF ARCH NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 #4 x 18" @ 24" OC DRILL & EPOXY 6" INTO STEM WALL 1'-0" 2" CONC SLAB REF PLAN NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 #4 x 18" @ 24" OC CENTERED ON JOINT 4" 8 " REF ARCH & CIVIL CONC SLAB REF PLAN METAL STUD WALL REF PLAN REF ARCH FRT PLYWD SHEATHING ARCH REF NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 #4 x 18" @ 24" OC DRILL & EPOXY 6" INTO STEM WALL 1'-0" T/ FOOTING = REF PLAN T/ SLAB = REF PLAN CONC SLAB REF PLAN (4) #5 VERT T FTG SIZE & REINF REF PLAN & SCHED FOR EQ 16" EQ 6 " O C R E M @ @ 2 " O C (3 ) #3 T I E S 16"x16" CONC PIER METAL STUD WALL REF PLAN EQ EQ REF ARCH NOTE: FOR ITEMS NOT CALLED OUT, REF DETAIL 1/S3.0 SHEAR WALL HOLD DOWN W/ CIP ANCHOR REF SCHED COLUMN, REF PLAN CONC SLAB REF PLAN T/ SLAB REF PLAN BASE PLATE, REF S2.0 FOR COL 12"x12"x6" LEAVE OUT G R O U T 1 1 /2 " 1 '-6 " 2'-0" SQ (3) #5 EW (3) #5 EW 3'-6" 1 '-0 " 1'-5" 8" CMU REINF. W/#5@32" O.C. 8" BOND BEAM W/2#5xCONT REF CIVIL 3#5xCONT GROUT CELL SOLID BELOW GRADE G R A D E 1 6 " B E L O W 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ FOUNDATION SECTIONS S3.0 3/4" = 1'-0" 1 SECTION 3/4" = 1'-0" 2 SECTION 3/4" = 1'-0" 7 SECTION 3/4" = 1'-0" 3 SECTION 3/4" = 1'-0" 4 SECTION 3/4" = 1'-0" 5 SECTION 3/4" = 1'-0" 6 SECTION 3/4" = 1'-0" 8 SECTION 3/4" = 1'-0" 9 SECTION 1" = 1'-0" 11 SECTION 3/4" = 1'-0" 10 DUMSTER WALL NO. DATE REMARKS 4#10 TEK SCREWS TYP 5/8" EXTERIOR GRADE PLYWD SHEATHING 600S162-43 MIL STUD KICKERS @ 16" O.C. STIFFCLIP AL362 W/0.156" DIA. PAFS TO CHANNEL C6x8.2 TYP DESIGN JOIST FOR ±2.3K SERVICE WIND LOAD SHEATHING REF ARCH. FRT PLYWOOD SHEATHING REF ARCH. CONT. TRACK W/0.156" DIA. PAFS TO PLATE 2 '-0 " T/ PARAPET = 28'-0" BENT PL 3/16"x2"x0'-6"xCONT LLH TYP HSS2 1/2x2 1/2x1/4xCONT AT SW LOCATIONS, WELD TO BEAM AND PLATE CONT. 6" TRACK TO MATCH STUD GAUGE W/#10 TEK SCREWS TO EA. FLANGE 4'-0" TYP T/PARAPET 28' - 0" ROOF DECK REF PLAN SIMPSON H2A TYP SIMPSON H2A TYP (2) 600S162-43 MIL STUD PACK AT VALLEY STUD BEAMS (TYP 4 LOCATIONS) (3) 600S162-43 MIL STUDS CENTERED ON STUD PACKS AND @16" 0C TYP 600S162-43 MIL STUDS, REF ARCH FOR ALIGNMENT (2) 600S162-43 MIL STUDS AT VALLEY CORNERS, REF PLAN 600S162-43 MIL STUD WALL STUD REF PLAN CONT TRACK TYP SIMPSON H2A TYP 600S162-43 MIL STUD JOIST TYP 600S162-43 MIL STUD JOIST TYP SIMPSON H2A TYP 600S162-43 MIL STUDS @ 32" O.C. 2 '-0 " 4#10 TEK SCREWS SHEATHING REF ARCH. 600S162-43 MIL STUDS @ 16" O.C. 600S162-43 MIL STUD KICKERS @ 16" O.C. STIFFCLIP AL362 ATTACHED AT LOW FLUTE TO JOIST W/0.156" DIA. PAFS #10 TEK SCREW TO EA. FLANGE 600T125-43 MIL TRACK W/3#10 TEK SCREWSTO EA. HIGH FLUTE W-SECTION FRT PLYWOOD SHEATHING METAL STUD WALL REF PLAN T/ PARAPET = 28'-0" REF PLAN FOR JOIST LOAD CL 4'-0" TYP METAL STUD WALL STIFCLIP AL362 W/0.145" DIA. PAFS TO CHANNEL C6x8.2 3/16 CONT. 600T125-43 MIL TRACK W/3#10 TEK SCREWS TO EA. HIGH FLUTE ATTACH TO EA. STUD FLANGE W/#10 TEK SCREWS TYP METAL DECK ALIGN JOIST W/WALL ABOVE 3/16 ROOF DECK REF PLAN BEAM REF PLAN STIFFCLIP AL362 W/ 0.156" DIA PAFS TO ANGLE METAL STUD WALL REF ARCH L3x3x1/4 @ 4'-0" OC L4x4x1/4 CONT 3/16 3/16 3/16 BEAM REF PLAN COL REF PLAN BEAM REF PLAN L5x5 L5x5 5/8 ROOF DECK REF PLAN 16 S4.0 PL 1/4" TYP 3/16 TYP 3/16 3/16 L5x5 ROOF DECK REF PLAN PL 1/4"x5"x0'=5" TYP BEAM REF PLAN JOIST REF PLAN 3/16 3/16 BEAM REF PLAN HSS COL W/ 1/4" CAP PL TYP, REF PLAN L5x5 AT BAYS SHOWN ON PLAN, TYP ROOF DECK REF PLAN 3/16 TYP PL 1/4"x5"x0'=5" TYP JOIST, TYP REF PLAN 3/16 TYP REF 11/S2.0 METAL STUD WALL REF PLAN CONT TRACK SIMPSON H2A TYP SHEATHING REF ARCH SHEATHING REF ARCH S600S162-43 MIL STUDS @ 16" OC 4#10 TEK SCREWS TYP (5) #12 TEK SCREWS TYP SIMPSON SJC8.25 TYP 3/4" STRUCTO-CRETE PANELS TYP 362S162-33MIL STUDS @ 16" OC T/ JOISTS REF ARCH W SECTION REF PLAN HSS COL REF PLAN STUD BLOCKING TYP MTL STUD JOISTS REF PLAN MTL STUD JOISTS REF PLAN HSS COL REF PLAN W I T H S I G N M F R G C T O C O O R D SIGN BY SUPPLIER HSS4x4x1/4 OUTRIGGER (GALV) 3/16 TYP T/ COL = 25'-6" 2 '-0 " 4#10 TEK SCREWS (TYP) SHEATHING REF ARCH. 600S162-43 MIL STUDS @ 16" O.C. 600S162-43 MIL STUD KICKERS @ 16" O.C. STIFFCLIP AL362 ATTACHED AT LOW FLUTE TO JOIST W/0.156" DIA. PAFS STIFFCLIP AL362 W/0.156" DIA. PAFS TO W-SECTION W-SECTION FRT PLYWOOD SHEATHING METAL STUD WALL REF PLAN T/ PARAPET = 28'-0" REF PLAN FOR JOIST LOAD CL 362S162-33 MIL STUDS @ 16" O.C. 96211 N. Meridian St Indianapolis, IN 46290 2014.0487 BR I T T , P E T E R S 20 1 5 604 COURTLAND STREET SUITE 100 ORLANDO, FLORIDA 32804 PH 407.645.5008 FX 407.629.9124 Firebirds at Drury Plaza CHECKED: PROJECT NO: DATE: REVISIONS DRAWN: SEAL: CONSULTANT: CO P Y R I G H T c R E S E R V E S C O P Y R I G H T & O T H E R R I G H T S R E S T R I C T I N G T H E S E D O C U M E N T S T O T H E O R I G I N A L S I T E O R P U R P O S E F O R W H I C H T H E Y W E R E P R E P A R E D . R E P R O D U C T I O N S , C H A N G E S O R A S S I G N M E NT S A R E P R O H I B I T E D . 999 WATERSIDE DRIVE SUITE 2202 NORFOLK, VA 23510 PH 757.965.5710 BPA# 150293 8-18-15 WBU JNJ FRAMING SECTIONS S4.0 3/4" = 1'-0" 1 SECTION 3/4" = 1'-0" 11 SECTION 3/4" = 1'-0" 2 SECTION 1" = 1'-0" 3 SECTION 1" = 1'-0" 4 SECTION 3/4" = 1'-0" 13 SECTION 3/4" = 1'-0" 14 SECTION 3/4" = 1'-0" 16 SECTION 3/4" = 1'-0" 9 SECTION 3/4" = 1'-0" 5 SECTION 3/4" = 1'-0" 18 SECTION N.T.S. 8 SECTION 3/4" = 1'-0" 17 SECTION NO. DATE REMARKS