Loading...
HomeMy WebLinkAboutWSM_ComCheck.pdfCOMcheck Software Version 4.0.2.6 Envelope Compliance Certificate Project Information Energy Code: Project Title: Location: Climate Zone: Project Type: Vertical Glazing / Wall Area� Construction Site: 3016 Warren Way Carmel, IN 46032 Building Area 90.1 (2007) Standard Woodland Springs Manor Indianapolis, Indiana 5a Alteration 17% Owner/Agent: Nicole James Hunt Pacific Indianapolis, IN 317-848-4022 Floor Area 1-Apartments (Multifamily) : Residential 2352 Envelope Assemblies Post-Alteration Assembly Designer/Contractor: James McCann KEELER-WEBB ASSOCIATES 486 Gradle Drive Carmel, IN 46032 317-574-0140 R-Value Proposed Max. Allowed Cavity Cont. U-Factor SHGC U-Factor SHGC Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1- Apartments] 38.0 0.0 0.027 — 0.027 — NORTH Wall - Brick Veneer: Wood-Framed, 16" o.c., [Bldg. Use 1- — — — — — — Apartments], Exemption: Cavity filled with minimum R-3/inch insulation Windows: Vinyl/Fiberglass Frame, Other, [Bldg. Use 1- — — 0.350 — 0.350 0.548 Apartments] Sliding Patio Doors: Other poor, Non-Swinging, [Bldg. Use 1- — — 0.350 --- 0.500 --- Apartmentsj (a) 'Other' components require supporting documentation for proposed U-factors. (b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. Project Notes ComCheck for damaged portions of the existing building only. Envelope Compliance Statement Compliance Statement: The proposed envelope alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have been designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.0.2.6 and to comply with the mandatory requirements listed in the Inspection Checklist. Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx ARDIZZONE - Woodland Springs ManohWSM - ComCheck.c Page 1 of 9 ���-}iY1t�S Pl ��.�viv, �.t. � '``ti 2�3 --lln Name - Title Sig ure Date _..uitti�l,s._ ''��I •���,....� � f e ¢ �,1ST��� ,� PE&�t1332 m �...�..�.''°�. o '8 Si�A�� fa� . � �•c� �o'13fA1�1�.a'' �a�G'�: �`�n �-.�....»^' �,�, �w� �. `��A�.'��' ..��•. Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs Manor�WSM - ComCheck.c Page 2 of 9 COMcheck Software Version 4.0.2.6 Inspection Checklist Energy Code: 90.1 (2007) Standard Requirements: 100.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. 5ection # & Req.ID 4.�.2 [PRl]1 Plan Review � Complies? Comments/Assumptions Plans and/or specifications provide all ❑Complies � Requirement will be met. information with which compliance ❑Does Not can be determined for the building envelope and document where ❑Not Observable exceptions to the standard are ❑Not Applicable claimed. Additional Comments/Assumptions: � _. .. _ - --- — -- , 1; High Impact (Tier 1) 2. Medium Impact (Tier 2) , 3 Low Impact (Tier 3) �__� — � ,_—__�-- � - -- -- - — -- -- - Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs ManohWSM - ComCheck.c Page 3 of 9 Se � on i Footing / Foundation i Plans Verified � Inspection Value & Reg.iD-�-- -- _ - -- — — - - —l- - - — — 5.5.3.3 Below-grade wall insulation R- R- [FO1]1 value. 5.5.3.5 Slab edge insulation R-value. [F03]1 5.53.5 Slab edge insulation [F05]1 depth/length. R- ❑ Unheated ❑ Heated ft 5.8.1.7.3 Insulation in contact with the � [F07]1 ground has <=0.3% water absorption rate per ASTM C272. Additional Comments/Assumptions: Field Verifed Complies? Comments/Assumptions ----Value-- --- -- -- - - R- ❑Complies See the Envelope Assemblies ❑DoeS Not table for values. ❑Not Observable ❑Not Applicable R- ❑Complies See the Envelope Assemblies ❑ Unheated �Does Not table for values. ❑ Heated ❑Not Observable ❑Not Applicable ft ❑COmplles See the Envelope Assemblies ❑Does Not table for values. ❑Not Observable ❑Not Applicable ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable 1 High Impact (Tier 1), � 2 Medium Impact (Tier 2) L3 � Low Impact (Tier 3) � Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs ManorlWSM - ComCheck.c Page 4 of 9 Section 4 # Framing / Rough-In Inspection & Req.ID � ` __ __ 5.43.2 Factory-built fenestration and [FR1]3 doors are labeled as meeting air leakage requirements. 5.5.4.3a Vertical fenestration U-Factor [FR8]1 5.5.4.3b Skylight fenestration U-Factor. [FR9]1 5.5.4.4.1 Vertical fenestration SHGC value. [FR10]1 5.5.4.4.2 Skylight SHGC value. [FR11]1 5.8.2.1, Fenestration products rated in 5.8.2.4 accordance with NFRC. [FR12]z 5.8.2.2 Fenestration products are [FR13)1 certified as to performance labels or certificates provided. 5.8.23, U-factor of opaque doors 5.5.3,6 associated with the building [FR14]z thermal envelope meets requirements. Additional Comments/Assumptions: Plans Verified I Field Verified �omplies? Value f value i Fenestration cfm/ftz Doors cfm/ftz Fenestration_ ❑Complies _ cfm/ft2 ❑Does Not Doors ❑Not Observable cfm/ftz ❑Not Applicable Comments/Assumptions Requirement will be met. U- U- ❑COmplies See the Envelope Assemblies ❑Does Not table for values. ❑Not Observable ❑Not Applicable U- U- ❑Complies See the Enve/ope Assemblies ❑Does NOt table for values. ❑Not Observable ❑Not Applicable SHGC: SHGC: ❑Complies See the Envelope Assemblies ❑Does Not table for values. ❑Not Observable ❑Not Applicable SHGC: SHGC: ❑Complies See the Envelope Assemblies ❑Does Not table for values. ❑Not Observable ❑Not Applicable ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable U- U- ❑COmplie5 See the Envelope Assemblies ❑ Swinging ❑ Swinging ❑Does Not table for values. ❑ Nonswinging ❑ Nonswinging ❑Not Observable ❑Not Applicable _ _ _.. .r _ ..._ . 1 High Impact (Tier 1) � 2, Medium Impact (Tier 2) �, 3� Low Impact (Tier 3) � Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs Manor�WSM - ComCheck.c Page 5 of 9 5ection Plans Verified Field Verified # Insulation Inspection Value Value E Complies? Comments/Assumptions & Reg.ID --- ---- ---� ---- - - -- — -- --- - -- - - ---- ---- 5.4.3.1 All sources of air leakage in the �❑Complies Requirement will be met. [IN1]1 building thermal envelope are ❑Does Not sealed,caulked,gasketed, weather stripped or wrapped with ❑Not Observable moisture vapor-permeable ❑Not Applicable wrapping material to minimize air leakage. 5.53.1 Roof R-value. For some ceiling R- � {R- � M ❑Complies See the EnvelopeAssemblies [IN2]1 systems, verification may need to � qbove deck ❑ Above deck �Does Not table Por values. occur during Framing Inspection. � Metal ❑ Metal ❑Not Observable ❑ Attic ❑ Attic ❑Not Applicable _ . .. ---•• -.�_._...__ .._...••-•__.-.• ••_ -_ •- •••_ - 5.8.1.2, Roof insulation installed per ❑Complies Requirement will be met. 5.8.1.3 manufacturer's instructions. ❑Does Not [IN3]1 Blown or poured loose-fill insulation is installed only where ❑Not Observable the roof slope is <=3 in 12. ❑Not Applicable 5.5.3.1.1 High-albedo roofs meet solar SR: SR: ❑Complies Requirement will be met. [IN5]3 reflectance of 0.70 and thermal SRI: SRI: �Does Not emittance of 0.75 or SRI of 82. ❑Not Observable ❑Not Applicable 5.5.3.2 Above-g�ade wall Insulatlon R- R- R- ❑Complies See the Envelope Assemblies [IN6]1 value. table for values. ❑ Mass ❑ Mass �Does Not ❑ Metal ❑ Metal ❑Not Observable ❑ Steel ❑ Steel ❑Not Applicable ❑ Wood ❑ Wood 5.8.1.2 [IN7]1 5.5.3.4 [IN8]1 Above-grade wall insulation ❑Complies Requirement will be met. installed per manufacturer's ❑Does Not instructions. ❑Not Observable ❑Not Applicable Floor insulation R-value. R- f R- � ❑Complies See the Envelope Assemblies ❑ Mass ❑ Mass �Does Not table for values. ❑ Steel ❑ Steel ❑Not Observable ❑ Wood ❑ Wood ❑Not Applicable 5.8.1.1 Building envelope insulation is ^ [IN10]� labeled with R-value or insulation certificate providing R-value and other relevant data. 5.8.1.4 Eaves are baffled to deflect air to ~ � [IN11]z above the insulation. 5.8.1.5 Insulation is installed in [IN12]� substantial contact with the inside surtace separating conditioned space from unconditional space. 5.8.1.6 Recessed equipment installed in [IN13]� building envelope assemblies does not compress the adjacent insulation. ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable ❑Complies Requirement will be met. ❑Does Not ❑Not Observable ❑Not Applicable -T -- — � � �High Impact (Tier 1) 2� Medium Impact (Tier 2) � 3 i Low Impact (Tier 3) Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx ARDIZZONE - Woodland Springs ManorlWSM - ComCheck.c Page 6 of 9 5e �ion Insulation Ins ection P�ans Verified Field Veri�ed � P Value Value I Complies? Comments/Assumptions & Rec�.ID ° 5.8.1.7 Exterior insulation is protected —__ ._ ._.... _._.. ___� -- `OComplies Requirement will be met [IN14]z from damage with a protective ❑Does Not material. Verification for exposed foundation insulation may need ❑Not Observable to occur during Foundation ❑Not Applicable Inspection. 5.8.1.7.1 Attics and mechanical rooms ❑Complies Requirement will be met. [IN15]z have insulation protected where ❑Does Not adjacent to attic or equipment access. ❑Not Observable ❑Not Applicable 5.8.1.7.2 Foundation vents do not interfere T T ❑Complies Requirement will be met. [IN16]z with insulation. ❑Does Not ❑Not Observable ❑Not Applicable 5.8.1.8 Insulation intended to meet the ^� ^ ��� ❑Complies Requirement will be met. [IN17]3 roof insulation requirements ❑Does Not cannot be installed on top of a suspended ceiling. Mark this ❑Not Observable requirement compliant if ❑Not Applicable insulation is installed accordingly. Additional Comments/Assumptions: - � - -- - ,- - -- — -- . , 1 High Impact (Tier 1) '`2 ; Medium Impact (Tier 2) �, 3 Low Impact (Tier 3) ._ _ Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs ManohWSM - ComCheck.c Page 7 of 9 5.4.3.3 [FI1]1 Final Inspection Weatherseals installed on all loading dock cargo doors in Climate Zones 4- 8. Additional Comments/Assumptions: Complies? � — Comments/Assumptions ❑Complies Exception: Requirement does not apply. ❑Does Not ❑Not Observable ❑Not Applicable 1� High Impact (Tier 1) _ I 2, Medium Impact (Tier 2) � 3 Low Impact (Tier 3) Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs ManohWSM - ComCheck.c Page 8 of 9 Project Title: Woodland Springs Manor Report date: 02/03/16 Data filename: E:\PROJECTS\ARDIZZONE\1601-xxx_ARDIZZONE - Woodland Springs ManohWSM - ComCheck.c Page 9 of 9