HomeMy WebLinkAbout16050068 Building PlansMechanical Symbols and Abbreviations
Section number
M1
A
Denotes section
S 1
M1
General Plan Notes:
General Notes:
1
Note Designation
Plan Notes:
Motorized damper
Drawing Symbols
Temperature Control Symbols
Room thermostat or sensor
Room humidistat
Exhaust fan
H
T
Flexible connection
Exhaust grille
Return air grille
Duct not shown for clarity
Supply register
FD
Supply duct riser
Return duct riser
Volume damper
Supply diffuser
OR
Sheet Metal Symbols
Fire damper
Abbreviations
OR
M
Specific information as indicated on a
drawing
Leader line of plan note referenced
directed to item of plan note
reference
Circle with number indicates a plan
note reference, with the number
indicating the item number of the plan
note referenced
General information as it pertains
only to the drawing it is on
General information pertaining
to all the drawings of the
discipline it is on
Denotes
Construction
Start point
Letter
designating
Elevation
Sheet number
Where elevation
Is located
Arrow indicates Direction
in which Section is cut
Sheet number
Where section
Is located
Mechanical General Notes
#22.+%#$.'%1&'5#0&14&+0#0%'5
Provide all materials and equipment and perform all labor required to
install complete and operable mechanical systems as indicated on the
drawings, as specified and as required by code.
Entire installation shall be in strict accordance with applicable codes
and ordinances.
Secure and pay for all required permits.
Provide a minimum of 10'-0" between exhaust outlets, plumbing vents
and all outside air intakes.
Contractor shall not locate any duct or piping directly over any
electrical panel, switchgear, transformer, etc. Coordinate locations of
ducts and piping with the Electrical Contractor to avoid these conflicts.
#4%*+6'%6
Contractor shall be guided by the Architect's reflected ceiling plan for
exact location of diffusers, registers and grilles unless otherwise
noted.
Coordinate diffuser, register, and grille locations with architectural
reflected ceiling plans, lighting, and other ceiling items and make
minor duct modifications to suit.
Furnish all material and equipment as specified, except where specific
approval for substitution is given by the Architect/Engineer.
)'0'4#.
These drawings indicate required sizes and points of termination for
piping, ductwork, conduit, etc. The equipment shown illustrates
suggested routing, but all necessary offsets and fittings may not be
shown. Contractor shall install his work in a manner that will conform
with the structure. Contractor shall avoid obstructions, preserve head
room and maintain maximum clearance without additional cost to the
Owner.
All dimensions shown on these plans are in feet and/or inches unless
otherwise noted.
Mechanical work shall be complete in every detail and all
miscellaneous items of material and labor necessary to complete the
work described, shown or reasonably implied on drawings or
specifications, shall be included in the contract.
Proposal shall be based on specified material and equipment. In order
to promote competition, however, bidders may submit alternate
proposals on any alternate materials and/or equipment they wish to
propose, including any price changes affected by acceptance of
alternatives. These must be provided in addition to the base bid, not
in place of the base bid.
Contract document drawings for mechanical work are diagrammatic
and are intended to convey scope and general arrangement only.
Install all mechanical equipment and appurtenances in accordance
with Manufacturers' recommendations, contract documents, and
applicable codes and regulations.
Provide vibration isolation as specified for all mechanical equipment to
prevent transmission of vibration to building structure.
Provide vibration isolators for all piping supports connected to and
within 50 feet of isolated equipment (except at base elbow supports
and anchor points) throughout mechanical equipment rooms.
The location of existing underground utilities is shown in an
approximate way only. The Contractor shall determine the exact
location of all existing utilities before commencing work. The
Contractor shall pay for and repair all damages caused by failure to
exactly locate and preserve any and all underground utilities unless
otherwise indicated.
Coordinate construction of all mechanical work with Architectural,
Structural, Civil, Electrical work, etc., shown on other contract
document drawings.
Each respective contractor shall be responsible for coordinating the
installation of his work with the work of other contractors and trades
prior to the installation.
Maintain a minimum of 6'-8" clearance to underside of pipes, ducts,
conduits, suspended equipment, etc., throughout access routes in
mechanical rooms.
All tests shall be completed before any mechanical equipment or
piping insulation is applied.
Locate all temperature, pressure, and flow measuring devices in
accessible locations with straight section of pipe or duct up and
downstream as recommended by the Manufacturer for appropriate
accuracy.
Work shall include startup of all systems, furnishing of operating and
maintenance instructions and one (1) year guarantee, commencing on
date of acceptance by the Owner or as otherwise specified.
Testing, adjusting, and balancing agency shall be by a member of the
Associated Air Balance Council (AABC) or the National Environmental
Balancing Bureau (NEBB). Testing, adjusting, and balancing shall be
performed in accordance with the AABC standards.
Where two or more items of the same type of equipment are required,
the product of one Manufacturer shall be used unless otherwise noted.
Coordinate all equipment connections with Manufacturers' certified
drawings. Coordinate and provide all duct and piping transitions
required for final equipment connections to furnished equipment. Field
verify and coordinate all duct and piping dimensions before
fabrication.
The locations of all items shown on the drawings or called for in the
specifications that are not definitely fixed by dimensions are
approximate only.
The exact locations necessary to secure the best conditions and
results must be determined by the project site conditions and shall
have the approval of the Engineer before being installed. Do not
scale drawings.
All miscellaneous steel required to ensure proper installation and/or as
shown in details for piping, ductwork, and equipment shall be
furnished and installed by the Mechanical Contractor.
Provide access panels for installation in walls and ceilings, where
required, to service dampers, valves, smoke detectors, and other
concealed mechanical equipment. Access panels shall be turned
over to General Contractor for installation.
All equipment, piping, ductwork, etc., shall be supported as detailed,
specified, and/or required to provide a vibration free installation.
All roof mounted equipment curbs for equipment provided by the
Mechanical Contractor shall be furnished by the Mechanical
Contractor and installed by the General Contractor.
Locations and sizes of all floor, wall, and roof openings shall be
coordinated with all other trades.
All openings in fire walls due to ductwork, piping, conduit, etc., shall be
fire stopped with a product similar to 3M or equal. Product shall be
listed by UL or FM and meet the requirements of local and state
codes.
All Air Terminal Outlets shall be provided with radiation dampers,
where installed in fire rated assemblies.
All air conditioning condensate drain lines from each air handling unit
or rooftop unit shall be piped full size of the unit drain outlet, with "P"
trap, and piped to the nearest drain or roof deck. See details shown on
the drawings or the contract specifications for depth of air conditioning
condensate traps.
Refer to typical details for ductwork, piping, and equipment installation.
All valves, coils, dampers, etc. Shall be installed allowing easy access
to them. Areas adjacent to the access panels shall be clear of
obstruction.
Furnish and install all equipment and material required to complete
the installation as shown on the drawings.
Equipment sizes and service space requirements may vary between
different Manufacturers. Consult approved Manufacturer drawings as
submitted and coordinate with these drawings.
All air handling units shall operate without moisture carryover.
Locate all mechanical equipment (Furnaces, ACCU's electric heaters,
ERV's, etc.) for unobstructed access to unit access panels, controls,
and valving.
Refer to mechanical details for additional equipment requirements.
*8#%5*''6/'6#.
Certain items such as rises and drops in ductwork, access doors,
volume dampers, etc., are indicated on the contract document
drawings for clarity for a specific location requirement and shall not be
interpreted as the extent of the requirements for these items.
All ductwork dimensions, as shown on the drawings, are internal clear
dimensions.
Keep all ductwork, duct system and equipment openings covered with
adhesive duct protective wrap like VentureTape 1512, until system
start-up. This is to prevent intrusion of construction dirt and debris into
the duct system, and HVAC equipment.
Provide flexible connections in all ductwork systems (supply, return,
and exhaust) connected to air handling units, fans, and other
equipment which require vibration isolation. Flexible connections shall
be provided at the point of connection to the equipment unless
otherwise noted.
Unless otherwise noted, all ductwork is overhead, tight to the
underside of the structure, with space for insulation and below any
required piping.
Flexible duct shall not be used as an elbow. Provide sheet metal
elbow at diffuser neck where tap is not out of the bottom of the supply
main. Refer to details.
All ductwork shall be coordinated with all trades involved. Offsets in
ducts, including divided ducts and transitions around obstructions,
shall be provided at no additional cost to the Owner.
Provide access doors in ductwork to provide access for all smoke
detectors, fire dampers, volume dampers, and other items located in
the ductwork which require service and/or inspection.
See specifications for ductwork gauges, bracing, hangers, and other
requirements.
Contractor shall not locate any duct or piping directly over any
electrical panels, switchgear, transformer, etc. Coordinate locations of
ducts and piping with the Electrical Contractor to avoid these conflicts.
Provide volume dampers upstream of all air inlets/outlets unless
otherwise noted.
Furnish and install rain hoods on flues and intake ducts above roof.
Provide companion opposed blade volume dampers with all diffusers
mounted in drywall ceilings. Do not provide companion volume
dampers with diffusers mounted in lay-in tile ceilings. Provide manual
volume dampers in the branch ducts serving diffusers located above
lay-in tile ceilings.
Diffusers, registers, and grilles mounted in drywall ceilings shall have
plaster frames.
Unless otherwise noted all ductwork shall be insulated with 2"
ductwrap. Ductwrap shall be 0.75 lb / cf. density. R6 Min.
Install volume damper at each branch takeoff from main supply ducts.
Refer to Mechanical Detail Sheets for additional equipment
requirements.
Phenolic duct by Pal-Duct or Kool-Duct is an acceptable alternative to
sheetmetal duct and insulation in concealed spaces. Submit detailed
duct drawings for Engineer's review.
4'(4+)'4#06'37+2/'06#0&2+2+0)
Conceal all refrigerant piping unless otherwise noted. Contact
Engineer for alternatives if concealment is not possible.
Slope refrigerant piping one percent in the direction of oil return.
Liquid lines may be installed level.
Install horizontal refrigerant hot gas discharge piping with 14" per 10
feet downward slope away from the compressor.
Install horizontal refrigerant suction lines with 14" per 10 feet downward
slope to the compressor, with no long traps or dead ends which may
cause oil to separate from the suction gas and return to the
compressor in damaging slugs.
Provide line size liquid indicators in main liquid line leaving condenser
or receiver. Install moisture-liquid indicators in liquid lines between
filter dryers and thermostatic expansion valves and in liquid line to
receiver.
Provide line size strainer upstream of each automatic valve. Provide
shutoff valve on each side of strainer.
Provide permanent filter dryers in low temperature systems and
systems using hermetic compressors.
Provide replaceable cartridge filter dryers with three valve bypass
assembly for solenoid valves, adjacent to receivers.
Provide refrigerant charging valve connections in liquid line between
receiver shutoff valve and expansion valve.
Insulate all interior linesets with 12" thick, flexible elastomeric insulation.
Insulate exterior linesets with 1" thick flexible elastomeric insulation
with external .020" aluminum protective jacket.
4'.#6'&'.'%64+%#.#0&2.7/$+0)
Unless otherwise noted all low voltage wiring (24 volts) shall be
provided and installed by the Mechanical Contractor. This includes
fans, radiant heaters, rooftop units, etc.
Unless otherwise noted line voltage wiring (120 volts or greater) shall
be provided and installed by the Electrical Contractor. Wiring should
be concealed at all times unless otherwise noted on the plans.
Contact the Engineer if concealment is not possible.
All control wire and conduit shall comply with the National Electric
Code (NEC) and Division 16/26 of the specifications.
Condensate drain pipe run out shall be full size to the nearest drain.
Refer to "P" sheets for routing.
Coordinate installation of gas piping for HVAC units with Plumbing
Contractor.
Furnish and install a gas cock at each unit connection.
Refer to electrical and plumbing drawings for additional coordination
with these drawings.
Any unit supplied with natural gas shall be furnished with pressure
regulators by Unit Manufacturer.
#22'#4#0%'
All equipment should be installed with great regard to a neat finished
product.
Whenever possible, wiring should be routed in such a way as to
minimize visibility.
Piping should be tight to structure whenever possible, and orthogonal.
Eliminate the need for condensate pumps if possible.
Contact the Engineer prior to installing any equipment that will not be
able to be installed in a neat, first class manner, consistent with the
Manufacturer's installation instructions.
4'.#6'&)'0'4#.%105647%6+10
Unless otherwise noted flashing of roof openings will be done by the
General Contractor. Intake and exhaust curbs to General Contractor
for installation. Contact General Contractor to coordinate this portion
of the work.
Concrete housekeeping pads to suit mechanical equipment shall be
sized and located by the Mechanical Contractor. Minimum concrete
pad thickness shall be 312" unless otherwise noted. Pad shall extend
beyond the equipment a minimum of 6" on each side. Concrete
housekeeping pads shall be provided by the Mechanical Contractor. It
shall be the responsibility of the Mechanical Contractor to coordinate
size and location of concrete housekeeping pads with the General
Contractor.
57$56+676+105
Cost of any changes required by this, or other trades, due to
substitution of equipment other than the basis of design, shall be
included in the Mechanical Contractor's proposal.
76+.+6+'5
Unless otherwise noted the local gas company shall provide gas to
the building and furnish and install the meter. Connection to the meter
and extension of the piping shall be made in accordance with the
utility company requirements.
Contact local utility company to arrange for gas meter installation.
Furnish and install piping and specialties as required to receive meter.
Verify local conditions at the site.
4'.#6'&%10641.5
Unless otherwise noted, locate all room thermostats and humidistats
4'-0" (centerline) above finish floor. Notify the Engineer prior to
installation of any rooms where the above location cannot be
maintained or where there is a question on location.
All control wiring and related control components should be concealed
unless otherwise noted on the plans. Contact the Engineer if
concealment is not possible.
ACHP air cooled condensing unit
AFF above finish floor
AHU air handling unit
BDD backdraft damper
BOD bottom of duct
CD ceiling diffuser (supply air)
CFM cubic feet per minute
CW cold water
DB dry bulb
DSAC ductless split air conditioner
Ø diameter
EDB entering air dry bulb
EWB entering air wet bulb
EBR electric baseboard radiation
EC Electrical Contractor
ECR eggcrate grille
EDC electric duct coil
EF exhaust fan
EG exhaust grille
ER exhaust register
ERV energy recovery ventilator
ESP external static pressure
EWH electric wall heater
F furnace
FD fire damper
FLA full load amps
FPM feet per minute
FT foot
FTR fin tube radiation
G gas
GC General Contractor
HP heat pump
IN inch
LAT leaving air temperature
LS linear slot diffuser
MAN manual
MFR Manufacturer
MBH 1000 BTUh
MC Mechanical Contractor
O/A outside air
OAL outside air louver
PD plaque diffuser
PSI pounds per square inch
RA return air
RD round diffuser
RG return air grille
RPM revolutions per minute
RTU roof top unit
SA supply air
SDG spiral duct grille
SP static pressure
SR supply register
TSP total static pressure
UH unit heater
VD volume damper
WB wet bulb
WT weight
A A
M001
HVAC SYMBOLS,
ABBREVIATIONS &
GENERAL NOTES
WAB
JTL
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
T
Remove existing
vents (low to
floor)
Existing Rooftop Unit to be removed
completely
Remove existing
Exhaust Fan and
ductwork completely.
Existing analog, dial style thermostat
to be removed completely.
Remove all existing ductwork and HVAC
accessories completely (Typical)
Remove all existing HVAC ceiling devices
completely (Typical)
Coordinate with G.C.
the patching of the
exterior wall.
M101
HVAC
DEMOLITION
PLAN
SCALE: 1/4" = 1'-0"
WAB
JTL
1 HVAC DEMOLITION PLAN P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
CD-1
125
CD-2
375
CD-2
375
CD-2
375
CD-3
600
CD-2
290
CD-2
290
CD-2
285
CD-2
285
20x14
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
14x1412"Ø
T RTU-1
16x14
16x14 14"Ø 12"Ø
8"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
28
x
1
6
24x16
RTU-1
(On roof)
EF-1
(On roof)EG-1
170
EG-1
150
FRG-2
1025
FRG-2
725
FRG-2
725
20x14
20
x
1
4
14"Ø14"Ø 10"Ø
EG-1
150 8"Ø
11
2
3
FRG-1
125
24x16
8"Ø
14
"
Ø
16
"
Ø
Supply air trunk duct routed above low bulkhead. Provide
vertical duct taps as required.
Route exhaust ductwork in joist space.
Route return duct in joist space over supply ductwork.
2NCP0QVGU
)GPGTCN0QVGU
1.These plans are diagramatic in nature, and do not
represent every necessary offset and fitting. Contractor
shall install his work in a manner that will conform with
the structure. Contractor shall avoid obstructions,
preserve head room and maintain maximum clearance
without additional cost to the owner.
2.Conceal all linesets, piping, power wiring, control wiring
and control components unless otherwise noted. If
concealment is not possible, contact Engineer for
alternatives prior to fabrication.
3.Insulate all interior linesets with 12" thick, flexible
elastomeric insulation. Insulate exterior linesets with 1"
thick flexible elastomeric insulation with external .020"
aluminum protective jacket.
4.Sheet metal supply ductwork in concealed spaces shall
be insulated with 112" thick, 1.5 lb density, fiberglass
ductwrap. All ductwork in unconditioned spaces shall be
insulated with 2" thick, .75 lb / cu ft density, fiberglass
ductwrap. (Min R6)
5.Phenolic duct by Pal-Duct or Kool-Duct is an acceptable
alternative to sheetmetal duct and insulation in
concealed spaces. Use flanged joints. Submit detailed
duct drawings for engineer review.
6.Keep all ductwork, duct system and equipment
openings covered with adhesive duct protective wrap
like VentureTape 1512, until system start-up. This is to
prevent intrusion of construction dirt and debris into the
duct system, and HVAC equipment.
7.If any questions arise concerning the HVAC
requirements of these documents, please contact The
Engineering Collaborative at (317) 636-3941, prior to
bidding, fabrication or installation of equipment.
8.Sheet metal transitions by Sheet Metal Contractor.
9.Refer to detail sheet M701 and spec sheet M901 for
additional requirements and information that applies to
this project.
1
2
3
M201
HVAC PLAN
SCALE: 1/4" = 1'-0"
WAB
JTL
1 HVAC PLAN P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
Exhaust Fan Schedule
/CTM /QFGN #KTHNQY
%(/
5VCVKE
2TGUUWTG
KPYI
'NGEVTKECN
%QPPGEVKQP 9GKIJV
NDU4GOCTMU
8QNVCIG
8
2JCUG
2QYGT
9CVVU*2
'(Ä)TGGPJGEM
)Ä*2
0QVGU
4QQHEWTD
)TCXKV[DCEMFTCHVFCORGTD[(CP/(4
&KTGEVFTKXGYKVJUQNKFUVCVGURGGFEQPVTQNNGT
&KUEQPPGEVD[(CP/(4
(CPVQQRGTCVGHTQOVKOGTOCVEJGFVQ467QEEEWRKGFUEJGFWNG
Terminal Outlets
/CTM (WPEVKQP 2TKEG
/QFGN
#KTHNQY
4CPIG
%(/
(CEG5K\G
KP
0GEM
5K\G
KP
%QNQT 4GOCTMU
%&Ä5WRRN[&KHHWUGT 5%&#ÄZ9JKVG
%&Ä5WRRN[&KHHWUGT 5%&#ÄZ9JKVG
%&Ä5WRRN[&KHHWUGT 5/:ÄZZ9JKVG
')Ä'ZJCWUV)TKNNG ÄZZ9JKVG
(4)Ä'IIETCVG(KNVGT4GVWTP ((ÄZZ9JKVG
(4)Ä'IIETCVG(KNVGT4GVWTP ((ÄZZ9JKVG
0QVGU
2TQXKFGHCEVQT[GZVGPFGFRCPGNHQTCP[FKHHWUGTYJKEJKUUOCNNGTVJCPVJG
ITKFKPYJKEJKVKUKPUVCNNGF
5QWPFDCHHNGD[5JGGV/GVCN%QPVTCEVQT
2TQXKFGRNCUVGTHTCOGHQTFKHHWUGTUTGIKUVGTUCPFITKNNGUKPUVCNNGFKP
I[RUWODQCTF
ÄYC[CKTFKUVTKDWVKQP.C[ÄKPEGKNKPIRCPGNTGSWKTGF
#EEGRVCDNG/CPWHCEVWTGTU
2TKEG
0CKNQT
6KVWU
/GVCNCKTG
#EEGRVCDNG/CPWHCEVWTGTU
)TGGPJGEM
.QTGP%QQM
2GPP$GTT[
Rooftop Unit Schedule
/CTM %CTTKGT
/QFGN
0QOKPCN
6QPU
#KT
8QNWOG
%(/
1WVUKFG
#KT/CZ
%(/
'ZVGTPCN
5VCVKE
2TGUUWTG
YI
%QQNKPI2GTHQTOCPEG *GCVKPI
2GTHQTOCPEG 'NGEVTKECN%QPPGEVKQP
9GKIJV
NDU4GOCTMU
'&$
(
'9$
(
.&$
(
.9$
(
0GV
5GPUKDNG
%QQNKPI
/$*
0GV
6QVCN
%QQNKPI
/$*
)CU
+PRWV
/$*
)CU
1WVRWV
/$*
8QNVCIG
8
2JCUG
/%#/1%2 5VCTVGT
$[
&KUEQPPGEV
$[
467Ä6%''##/(4 /(4
0QVGU
)CURTGUUWTGTGIWNCVQTUWKVCDNGHQTUKVGICURTGUUWTGÄ5VCIGICUJGCV5VCKPNGUUUVGGNJGCVGZEJCPIGT
KPUWNCVGFTQQHEWTD
&WCN'PVJCNR[GEQPQOK\GT$CTQOGVTKETGNKGH
Ä5VCIG%QQNKPI1RGTCVKQP*QVÄICUTGJGCVFGÄJWOKFKHKECVKQP6JGTOKFKUVCV
.KMG*QPG[YGNN6$7
SEQUENCE OF OPERATIONS:
4QQHVQR7PKV
467Ä
467UJCNNDGUEJGFWNGFQEEWRKGFWPQEEWRKGFOQFGYKVJOCPWCNQXGTTKFG
467UJCNNDGOCPWCNJGCVEQQNOQFGEJCPIGQXGT
1EEWRKGF/QFG
(CPUJCNNTWPEQPVKPWQWUN[
%QQNKPI/QFG
+HURCEGUGVRQKPVKUPQVOGVQRGTCVG467KPEQQNKPIOQFGWPVKNURCEG
UGVRQKPVKUTGCEJGF7PKVVQWVKNK\GUVUVCIGQHEQQNKPIVQEQQNURCEG+H
VGORGTCVWTGHCKNUVQHCNNQTFKUEJCTIGCKTVGORGTCVWTGKUITGCVGTVJCP(
CFLVJGPFUVCIGQHEQQNKPIVQGPGTIK\G+HURCEGTGNCVKXG*WOKFKV[
TJ
UGVRQKPVKUUCVKUHKGFUVQRQRGTCVKQPQH467
+HURCEGUGVRQKPVKUOGV URCEGTGNCVKXGJWOKFKV[
TJUGVRQKPVKUPQVUCVKUHKGF
QRGTCVG467UVUVCIGICUJGCVVQOCKPVCKP(
CFL+HVGORGTCVWTGHCKNUVQ
TKUGPFUVCIGQHJGCVVQGPICIG+HURCEGTGNCVKXG*WOKFKV[
TJUGVRQKPVKU
UCVKUHKGFUVQRQRGTCVKQPQH467
5RCEGVGORGTCVWTGUGVRQKPVJCURTKQTKV[QXGTURCEGJWOKFKV[
*GCVKPI/QFG
+HURCEGUGVRQKPVKUPQVOGVQRGTCVGICUHWTPCEGUGEVKQPCPFHCPQP467WPVKN
URCEGUGVRQKPVKUTGCEJGF+HURCEGTGNCVKXG*WOKFKV[
TJUGVRQKPVKUUCVKUHKGF
UVQRQRGTCVKQPQH467
7PQEEWRKGF/QFG
(CPUJCNNE[ENG
%QQNKPI/QFG
+HURCEGUGVRQKPVKUPQVOGVQRGTCVG467WPVKNURCEGUGVRQKPVKUTGCEJGF
*GCVKPI/QFG
+HURCEGUGVRQKPVKUPQVOGVQRGTCVG467WPVKNURCEGUGVRQKPVKUTGCEJGF
'ZJCWUV(CP
'(Ä
'(UJCNNDGUEJGFWNGFQEEWRKGFWPQEEWRKGFOQFGYKVJOCPWCNQXGTTKFG
1EEWRKGF/QFG
(CPUJCNNTWPEQPVKPWQWUN[
7PQEEWRKGF/QFG
(CPUJCNNDGFGGPGTIK\GF
#EEGRVCDNG/CPWHCEVWTGTU
%CTTKGT
6TCPG
$T[CPV
;QTM
M601
HVAC SCHEDULES
WAB
JTL
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
'ZGEWVKXG&TKXG·5WKVG·+PFKCPCRQNKU+PFKCPC··YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
1-1/2"
Round Flexible Connection
1" x 1/8" Band iron
Washer
1/2"
1" x 1/8" Draw band
1/2"
5/16" Flange
Bolt 4" on centers
Rectangular Flexible Connection
1" Flange and hem
Bolt 4" on centers
1" x 1/8" Band iron
Washer
Rivet 4" on centers
Ductwork
1-1/2" Pocket slip
Ductwork
Flexible material
as specified
1-1/2" Minimum to 3" maximum
installed. 6" nominal with material taut
Sheet metal as specified for ductworkFlanged connection
on fan side
Sheet metal as specified for ductwork
Alternate position of bolt
1-1/2" Minimum to 3" maximum
installed. 6" nominal with material taut
Flanged connection
on fan side
Flexible material as specified
1" x 1/8" Draw band
D (NGZKDNG%QPPGEVKQP
Scale: NoneM701
6
Note: Roof opening shall conform to manufacturer's curb size.
Curb insulation
Backdraft damper Roof
D &QYPDNCUV4QQH'ZJCWUV(CPYKVJ%WTD
Scale: NoneM701
1
Ductwork. See plans
for continuation.
Secure and seal ductwork
to angle frame all around
Exhaust fan housing
Prefabricated curb with
built-in cant. Offset for
roof insulation thickness
12" min.
More than 30°30° or less
V.D.
45° Boottap fitting
Duct offset
Use radius for more than 30°Use mitered for 30° or less
Duct offset
Branch off main90° Square Elbow
Turning vanes
90° Radiused Elbow
H H
2H
D .QY8GNQEKV[5JGGV/GVCN(KVVKPIU
Scale: NoneM701
3D4GVWTP)TKNNGCPF5QWPF$CHHNG
Scale: NoneM701
8
Ceiling
Reinforcing angles as required to receive
screws for support and anchorage of return
air grille.
Typical eggcrate return
Refer to plans for duct size
Line duct internally with flat
black, non-fibrous, acoustic duct
liner
Full size
Cleanout plug
Draw Through Coil
Blow Through Coil
Full size
Cleanout plug
Cleanout plug
Route full size condensate drain pipe to
nearest floor drain. Refer to plumbing
drawings for floor drain locations.
Unit manufacturers threaded
drain pipe connection (typ)
Cooling coil
drain pan
Drain line (bottom
connection only)
1" greater than
fan static pressure
1" greater than half of
fan static pressure
1" greater than
half of fan
static pressure
1" greater than fan
static pressure
D %QPFGPUCVG&TCKP
$NQY&TCYÄ6JTW%QKN
Scale: NoneM701
5
Drain line (bottom
connection only)
Cooling coil
drain pan
Full size
Full size
Unit manufacturers threaded
drain pipe connection (typ)
Cleanout plug
Route full size condensate drain pipe to
nearest floor drain. Refer to plumbing
drawings for floor drain locations.
Minimum 1" wide clamp.
Detail 2
Maximum flexible
duct length shall be
5'-0".
Wire support.
Detail 1
Detail 3
Notes:
1.Metallic flexible ductwork shall be attached using a minimum of three (3)
#8 sheet metal screws equally spaced around the ductwork
circumference. Ductwork larger than 12" shall have a minimum of five (5)
#8 sheet metal crews. Screws shall be located at least 1/2" from the
ductwork end.
2.Non-metallic flexible ductwork shall be secured to the sleeve or collar
using a draw band. If the ductwork collar exceeds 12", the draw band
must be positioned behind a bead on the metal collar.
3.Insulation and vapor barriers present on factory-fabricated ductwork shall
be fitted over the core connection and shall be supplementally secured
with a draw band.
4.Flexible ductwork sealing shall be a class "B" seal for low pressure
ductwork.
5.Support system shall not damage or cause out-of-round shape.
6.Flexible ductwork shall be a maximum of 5'-0" in length and shall NOT be
used as an elbow.
Maximum sag shall be
1/2" per foot of support
spacing.
Strap bracing shall be
provided at a maximum
of 3'-0" on centers.
1" Band clamp with
wire. (Optional)
D +PUWNCVGF(NGZKDNG&WEVYQTM
Scale: NoneM701
4
Sheet metal box
1-1/2" duct wrap
1-1/2" duct wrap
Sheet metal elbow
Supply diffuser
Application NOT Acceptable
CeilingCD-1 CD-2 thru CD-XX
Low pressure
supply branch duct
Collar with manual
volume damper & lock Insulated flexible
duct to supply
diffuser
Notes:
Provide a 45 degree entry square-to-round fitting from low pressure
supply branch duct when the supply diffuser branch size equals or
exceeds the depth of the supply branch duct. Width shall equal round
diffuser branch size, depth shall equal supply branch duct depth.
Refer to supply diffuser plenum connection detail if guidelines of this
detail can not be met due to physical limitations.
A maximum length of 5'-0" of flexible duct is allowed in a single run.
Secure flexible duct to
supply diffuser elbow
fitting with drawband
Lay-in panel
where required
Secure flexible duct to
supply diffuser elbow
fitting with drawband
Insulated flexible duct
to supply diffuser
8" Min.Provide shoe
tap fitting
Ceiling
D 5WRRN[&KHHWUGTCPF(NGZKDNG&WEV%QPPGEVKQP
Scale: NoneM701
6
Supply register
Application NOT Acceptable
Low pressure
supply branch
duct
Collar with manual
volume damper & lock
Insulated flexible
duct to supply
diffuser
Notes:
Provide a 45 degree entry square-to-round
fitting from low pressure supply branch duct
when the supply register branch size equals
or exceeds the depth of the supply branch
duct. Width shall equal round register
branch size, depth shall equal supply
branch duct depth.
A maximum length of 5'-0" of flexible duct is
allowed in a single run.
Insulated flexible duct
to supply register8" Min.Provide shoe
tap fitting
D 5WRRN[4GIKUVGTCPF(NGZKDNG&WEV%QPPGEVKQP
Scale: NoneM701
7
Sheet metal boot
Ceiling
Secure flexible duct to
supply register boot
fitting with drawband
Supply register
2" duct wrap.
R6 minimum.
Wood nailer
Neoprene weatherseal Rooftop Unit
Field applied cant strip
Wood nailer
Treated 2x4 shimming
to level top of curb
Counterflashing
Curb by RTU MFR unless
specified otherwise
4" flexible duct connection
between roof insulation and
bottom of rooftop unit
Roof construction.
Refer to architectural
drawings for type
Roof structure. Refer to
structural drawings for type
Supply and
return ducts
Notes:
1.Roof curbs shall be provided with properly designed fabricated leveling devices
so equipment is level and the roof curb is installed to match the roof slope.
2.Provide perimeter angle support at all sides between structural steel. Size of
angle based on load of equipment. Minimum size shall be 3" x 3" x 1/4".
3.Roof curbs shall not be supported by the roof insulation.
4.Coordinate location of roof curb and roof opening with structure.
5.Roofing insulation shall be continuous under the rooftop equipment.
D 4QQH'SWKROGPV5WRRQTV%WTD5GEVKQP
Scale: NoneM701
2
Provide radius 90° elbow
with turning vanes to
transition to horizontal. Do
not provide a duct plenum
and horizontal tap.
M701
HVAC DETAILS
WAB
JTL
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
REQUIREMENTS OF REGULATORY AGENCIES
All materials and workmanship shall comply with all applicable codes, specifications, local
ordinances, industry standards, and utility company regulations.
In case of a difference between building codes, specifications, state laws, local ordinances,
industry standards, utility company regulations and Contract Documents, the most stringent shall
govern. The Contractor shall promptly notify the Owner in writing of any such difference.
Non-Compliance: Should the Contractor perform any work that does not comply with requirements
of applicable building codes, state laws, local ordinances, industry standards and utility company
regulations, he shall bear all costs arising in correcting the deficiencies.
Applicable codes and standards shall include all state laws, local ordinances, utility company
regulations and applicable requirements of state plumbing and mechanical codes.
Permits: Contractor shall pay for all building permits required by work and permits. For opening
streets and for connection to various utilities, including fees for water meter installation and any
other requirements necessary to carry out his work. Where streets or sidewalks are cut, same must
be repaired to at least as good a condition as they were before, all at the expense of this
Contractor. Permits shall be posted in a prominent place at the building site properly protected
from the weather and physical damage.
GUARANTEE
Contractor shall, by accepting these Drawings and Specifications, guarantee:
Contractor shall furnish all material and equipment as specified except where specified approval is
given by Engineer for substitution.
All material and equipment shall be installed substantially as shown on drawings and as required
within the intent of these Specifications.
All equipment, etc., shall be driptight, airtight, free of vibration, pounding, and other objectionable
noises.
Contractor shall guarantee all equipment, accessories, and material furnished by him, including
installation for a period of one year from date of final acceptance against all defects in material and
workmanship.
If any equipment, material, and/or pipe joints, connections, etc., fail or do not operate satisfactorily
or show undue wear, he will, upon being notified, immediately remedy defect at his own expense.
WORK AND WORKMANSHIP
Provide all required labor, materials, equipment and Contractor's services necessary for complete
installation of systems required in full conformity with requirements of authorities having
jurisdiction, all as indicated on Drawings and herein specified.
Finished job shall be functional and complete in every detail, including any and all such items
required for a complete system whether or not these items be specified or shown on the Drawings.
All such accessories and appurtenances shall be provided and installed at no additional cost to the
owner.
Special attention shall be given to accessibility of working parts and controlling parts. Adjustable
parts shall be within easy reach. Removable parts shall have space for removal.
Each Contractor shall acquaint himself with details of all work to be performed by other trades and
take necessary steps to integrate and coordinate his work with other trades.
It is assumed that the Contractor is familiar with standard First Class installation procedures.
Therefore, these Specifications do not attempt to include every detail or operation necessary for
the complete installation.
It should be particularly noted that the terms "furnish" and "provide" are interchangeable and that
each of these means to provide, install and connect, unless otherwise stated.
Whenever tables or schedules show quantity of materials, they shall not be used as a guide to the
Contractor. Each Contractor shall be responsible for furnishing all material noted on the Drawings
and as specified.
Contractor shall be responsible for the protection, safekeeping, and cleanliness of all existing
equipment, material, etc., located in spaces to be remodeled in which he is working. As part of his
responsibility, he shall provide the necessary covers, structures, etc., as required to keep all dirt,
water, moisture and dust from equipment. The method the Contractor proposes to use in protecting
equipment shall be coordinated with the Engineer and Owner's representative for approval before
any work is started. Any damage sustained during construction shall be corrected or replaced by
the Contractor.
ASSIGNMENT OF MISCELLANEOUS WORK
Painting: Mechanical Contractor will provide prime painting on all ferrous metals such as support
steel or hangers for mechanical equipment. Any finish painting of mechanical work required,
including painting steel exposed to outside environment shall be painted by the Mechanical
Contractor.
Platforms and supporting stands for mechanical equipment shall be furnished by the Mechanical
Contractor unless noted otherwise. Owner shall give approval prior to any cutting. All larger holes
shall be provided by others, as detailed in the structural drawings.
Ceiling and Wall Access Panels: Mechanical Contractor shall cut and patch finished areas for
panels as required by the Mechanical Contractor. Provide access panels as specified, where
shown, or required for access to coils, valves, etc.
A.Acoustical tile Wall or Ceiling: 24" x 12" unless otherwise noted. Constructed to receive
tile to match ceiling. Milcor Style A.
B.Plastered Wall or Ceiling: 24" x 12" unless otherwise noted. Constructed to receive
plaster to match adjacent finish. Milcor Style B.
Cutting and Patching: Mechanical Contractor shall cut and patch finished areas as required by the
Mechanical Contractor. Cut structural materials only where required after approval from the
Architect and Engineer.
Disposition of existing equipment which is to be removed and salvaged shall remain the property of
the Owner and be stored by the Contractor as directed by the Owner.
Temporary partitions or barriers required to protect existing building or facilities shall be provided
by the Mechanical Contractor. Mechanical Contractor shall coordinate necessity and location of
such protection with Owner.
Roof openings and flashing required by Mechanical Contractor shall be by Mechanical Contractor.
Mechanical Contractor is responsible for the correct size and location of same. Counterflashing by
the Mechanical Contractor.
Pads and foundations for mechanical equipment shall be formed and poured by the Mechanical
Contractor. Mechanical Contractor shall verify pads and all anchoring devices.
Excavating and backfilling for mechanical work shall be by the Mechanical Contractor.
All outside downspouts shall be by the General Contractor. Downspout shoe shall be by the
Mechanical Contractor.
Kitchen equipment shall be set in place by the Mechanical Contractor. Rough-in shall be by the
Mechanical Contractor. Final connections shall be by the Mechanical Contractor.
Sanitary vent pans and flashing by the Mechanical Contractor.
Louvers shall be furnished by the Mechanical Contractor. Size and location shall be verified by the
Mechanical Contractor.
Roof curbs and bases for ventilators, roof intakes and relief and fans shall be furnished by the
Mechanical Contractor.
DRAWINGS
Mechanical Drawings show general arrangement of all equipment and appurtenances. They shall
be followed as closely as actual building construction and work of other trades will permit.
Mechanical work shall conform to requirements shown on all Drawings. General and Structural
Drawings shall take precedence over Mechanical Drawings. Because of the small scale of
Mechanical Drawings, it is not possible to indicate all offsets, fittings and accessories which may
be required. Contractor shall investigate structural and finish conditions affecting work and shall
arrange his work accordingly, providing such fittings, valves and accessories as may be required to
meet such conditions without additional cost
to the Owner.
COORDINATION BETWEEN CONTRACTORS
Each Contractor and Subcontractor shall study all drawings applicable to this work so complete
coordination between trades will be affected. Special attention shall be given to points where ducts
cross other ducts or piping, where lights fit into ceilings and where ducts, and conduit pass thru
walls and columns.
It is the responsibility of each Contractor and Subcontractor to leave necessary room for other
trades. No extra compensation will be allowed to cover the cost of removing conduit, ducts, or
equipment found encroaching on space required by others.
MINOR DEVIATIONS
For the purpose of clarity and legibility, Drawings are essentially diagrammatic although size and
location of equipment are drawn near to scale wherever possible. Verify Contract Document
information at site.
Drawings indicate required sizes and points of termination of ducts and suggested routes. It is not
the intention of Drawings to indicate all necessary offsets. Install work in a manner to conform to
structure, avoid obstructions, preserve headroom and keep openings and passageways clear. Do
not scale from Drawings.
ATTACHING TO BUILDING CONSTRUCTION
Equipment and piping supports shall be attached to structural members (beams, joists, etc.) Rather
than to floor or roof slabs. Do not attach hangars to bottom chord of structural members.
DEMOLITION AND REMOVAL OF EQUIPMENT
Contractor shall remove all equipment, pipes, ductwork, hangers and support for portion of
mechanical system in present building as shown on Drawings and/or implied by nature of the work
indicated to be removed.
Contractor shall properly support remaining portions of work. Contractor shall provide valves,
plugs, vents, etc. as required for complete operating system. All pipes, ductwork, etc., removed
shall become the property of the Contractor and shall be removed form the premises unless
specified otherwise.
Contractor shall cap all abandoned piping which cannot be removed. This would pertain to piping
which runs into concrete floors, thru outside walls below grade, etc.
BALANCING
Work shall be provided by the Mechanical Contractor.
General: Balance and adjust air and hydronic systems to achieve comfort and proper operation of
systems and to capacities indicated on the drawings.
A.Use procedures as outlined in the National Standards for Field Measurements and
Instrumentation, current volume, as published by the Associated Air Balance Council.
Certify balance of system to be complete and accurate as shown and submit report to
Engineer for review and approval.
B.If a piece of equipment is not operating in a satisfactory manner, coordinate with
manufacturer to repair or adjust as necessary.
C.Report to Engineer if system or piece of equipment cannot be adjusted to operate
satisfactorily.
D.Test and Balance shall be provided by a NEBB, AABC or TABB certified Balance
Contractor.
INSULATION
Ductwork Insulation
A.Service: Air conditioning and heating supply, fresh (outside) air in conditioned spaces -
insulate entirely. Material: 0.75 lb/cu ft. Flexible fiberglass 112" thick with flame resistant
aluminum kraft foil jacket.
B.Service: Air conditioning and heating supply and return, fresh (outside) air in
unconditioned spaces - insulate entirely. Material: 0.75 lb/cu ft. Flexible fiberglass 2"
thick with flame resistant aluminum kraft foil jacket. (R6 Minimum)
NOTE:All insulation: rating not to exceed 25 flame, 50 smoke and rated for use in return
air plenum.
REFRIGERATION PIPING SYSTEM
Service: Refrigerant required by selected equipment.
Maximum design: Pressure 525 psig; temperature 300°F.
Piping (above ground): Soft, seamless copper linesets as recommended by air conditioner
Manufacturer, cleaned, dehydrated and sealed according to manufacturer's recommendations.
Conceal all refrigerant piping unless otherwise noted. Contact Engineer for alternatives if
concealment is not possible.
Perform an initial test of the refrigeration system as follows:
A.Hold pressure for 12 hours and check for loss of pressure. Certify readings. Notify
equipment manufacturer of test and allow observance.
B.Draw and hold 500 micron vacuum. Hold for 12 hours and check for loss of vacuum.
Notify equipment manufacturer of test and allow observance.
C.If leak(s) is detected, entire refrigerant system shall be checked with leak detector.
Caution: Any freon that might be present in area can interfere with detectors. Area
must be thoroughly ventilated.
D.Repair any leaks and repeat above procedure. Repairing leaks under pressure shall
not be done. Brazed joints shall be repaired by using new material.
E.Insulate all interior refrigerant suction piping with 12" flexible elastomeric insulation.
F.Insulate all exterior refrigerant piping with 1" flexible elastomeric insulation and provide
a .020" aluminum jacket sealed weather tight.
"LOW PRESSURE" DUCTWORK AND ACCESSORIES
Construct rectangular duct of first quality materials in accordance with SMACNA-HVAC Duct
Construction Standards, Metal and Flexible. Crossbreak except where rigid insulation is specified.
Construct round duct according to recommendations of ASHRAE Guide. Round duct should be
galvanized spiral unless noted otherwise. Longitudinal lock-seam duct is not acceptable.
Keep all ductwork, duct system and equipment openings covered with adhesive duct protective
wrap like VentureTape 1512, until system start-up. This is to prevent intrusion of construction dirt
and debris into the duct system, and HVAC equipment.
Phenolic duct by Pal-Duct or Kool-Duct is an acceptable alternative to sheetmetal duct and
insulation in concealed spaces. Use flanged joints. Submit detailed duct drawings for engineer
review.
Support horizontal duct in wall with bank iron strap hanger if width is under 18" and with shelf type
bracket if over 18".
Support ducts suspended from roof structure with band-type hangers if maximum is inside 48" and
with trapeze-type hangers if over 48".
Fittings:
B.Elbows (less than 24" wide): Use standard radius elbow. Radius shall be 1.5 times
width of fittings.
C.Elbows (24" wide and over): Shall be square elbows with turning vanes. Elbows less
than 36" wide shall have single-bladed vanes. Elbows 36" wide and over shall have
double-bladed vanes in airfoil pattern.
D.Main tee connections shall be radius or square depending on the size duct reduced to.
Adjustable splitter damper shall be provided ahead of tee.
E.Branch tee connections shall be 45° branch take-offs. Provide balancing dampers in
branches unless otherwise directed to delete them.
F.Transitions, raises and drops shall be built so that change in direction of side of duct
does not exceed 30° angle to projected same side.
Provide flexible connections (FC) at each inlet and outlet duct connection to every piece of fan
equipment. Fabric fastened to metal with double lock seam. Fabric for ordinary HVAC uses to be
waterproof, fire retardant and suitable for temperatures of 200°F. Manufacturers: Duro-Dyne,
Ventfabrics or equal.
Runs of flexible duct shall not exceed 5'-0". Flexible duct shall not be used as an elbow. Provide
sheet metal elbow at diffuser neck where tap is not out of the bottom of the supply main.
Furnish and install balancing dampers (BD) for each supply air runout and at additional locations,
as shown on the drawings. Construction to be galvanized steel, two gauges heavier than duct.
Shaft shall be steel with brass bearings. Blades shall not exceed 12" wide and 48" long. Frames of
same gauge metal are required where two blades or more are used.
Balancing dampers to have lock-type damper operator and linkage as best suits construction and
access conditions. Dampers with accessible operators to be provided with locking damper
quadrants complete with locking nuts and graduated scale. Dampers with non-accessible
operators provided with Young Series 300 concealed regulator and cover plate complete with work
gear or linkage as required for smooth damper operation. Dampers in underslab ducts provided
with Young Series 335 adjustable cover regulators.
DUCTS CONNECTED TO COMMERCIAL KITCHEN HOODS: COMPLY WITH NFPA 96.
A.Exposed to View: Type 304, stainless-steel sheet, No.4 finish.
B.Concealed: Carbon-steel sheet.
C.Welded seams and joints.
D.Pressure Class: Positive or negative 2-inch wg (500 Pa)
E.Minimum SMACNA Seal Class: Welded seams, joints, and penetrations.
F.SMACNA Leakage Class: 3.
Engineered, factory fabricated duct systems are an acceptable alternative. Obtain the Engineers
written approval of such duct systems prior to bidding.
Duct Sealing: Comply with SMACNA standard duct sealing requirements for class "A" ducts for all
O/A, supply, return and exhaust ductwork.
A.Water-Based Joint and Seam Sealant:
1.Application Method: Brush on.
2.Solids Content: Minimum 65 percent.
3.Shore A Hardness: Minimum 20.
4.Water resistant.
5.Mold and mildew resistant.
6.VOC: Maximum 75 g/L (less water).
7.Maximum Static-Pressure Class: 10-inch wg (2500 Pa), positive and negative.
8.Service: Indoor or outdoor.
9.Substrate: Compatible with galvanized sheet steel (both PVC coated and bare),
stainless steel, or aluminum sheets.
10.Tape shall not be acceptable.
Fire Dampers (FD): At each penetration through fire-rated partitions, provide fire dampers where
indicated on drawings to meet or exceed barrier rating.
Fire dampers shall be type "B", UL classified and meet all NFPA criteria for primary fire dampers.
Frame shall be 20 gauge minimum. Blades shall be 24 gauge minimum. Blades shall not infringe
on duct free area for airflow. Fusible link shall be rated at 165°F. Closure springs shall be 301
stainless steel. Finish shall be mill.
SMOKE DAMPER
A.Fabricate in accordance with NFPA 90A and UL 555S, and as indicated.
B.Normally Close Smoke Vent Dampers: Curtain type, opening by gravity upon actuation
of electro thermal link, flexible stainless steel blade edge seals to provide constant
sealing pressure.
C.Normally Open Smoke Vent Damper: Curtain type, closing upon actuation of electro
thermal link, flexible stainless steel blade edge seals to provide constant sealing
pressure, stainless steel springs with locking devices ensure positive closure for units
mounted horizontally.
HVAC EQUIPMENT
Refer to Plans and Schedule sheets. If equipment other than basis of design (scheduled
Manufacturer) is being considered, obtain prior written approval from the Engineer.
M901
HVAC
SPECIFICATIONS
WAB
JTL
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
CO-A
FS-A
FD-A
MV-A
L-1H
4"W12
GI-A1
3"W1
FS-A MV-A
FD-A
FD-A
FD-A FD-A
WC-1H
CO-A
3"W 1
L-1H
FS-A
FS-A
3"W 1
3"W 1 3"W 1
114"CW
12"CW-S 5
4
2"W 1
3"W 1
2"W 1
3"W 1
34"CW-S
12"HW-S
34"CW-S
12"HW-S
12"FCW
12"CW-S
12"HW-S
12"FCW
34"CW-S
34"HW-S
12"FCW
34"CW-S
34"HW-S 12"FCW
1"CW-S
34"HW-S
1"CW-S
34"HW-S
1"CW-S
12"HW-S
114"CW, extend to
existing meter pit.
Local utility co. to
provide new meter.FD-A
2"W 1 2
23
1
5
RPZBP
WC-1H
114"G down to
existing gas
meter serving
this tenant.
114"G on roof
1"G on roof
1"G
Existing water heater to be removed in its entirety.
Existing 34" water service to be removed back to existing
meter pit. Repair wall and floor in kind, ready for finish.
Existing water lines serving existing lavatory and water
closet to be removed above ceiling for connection to new
water lines.
Disconnect gas from existing RTU. Remove line back to
existing meter.
&GOQNKVKQP0QVGU
1
Neatly saw-cut existing slab along entire path of new
waste line. Repair slab in kind, ready for finish.
Connect new waste line to nearest active waste line
of equal or larger size. Field verify exact size,
location, elevation, material and condition of existing
waste line, prior to start of work.
Connect new water line to nearest active water
service above ceiling. Field verify exact size,
location, material and condition of existing water line,
prior to start of work.
Connect water filter system to water line serving sink
below.
Connect new water line(s) to existing line(s) serving
existing fixture.
2NCP0QVGU
1
2
3
4
2
5
3
4
A.Contractor shall be required to visit the premises prior to
bidding to determine all existing conditions and systems
related to his work. Contractor shall include in his bid
proposal all labor and material as required for the
plumbing installation to be complete and operative.
B.Coordinate the plumbing work with the architectural,
electrical, mechanical and other plans and details related
to this project for work of all other trades.
C.The drawings represent a general scheme of existing
conditions. All details of existing conditions may not
appear on the drawings. The contractor shall visit the
premise prior to bidding to determine all existing
conditions and systems related to his work and shall
include in his bid proposal all labor and material as
required:
1. To disconnect and remove all plumbing equipment
that is to be removed from service or that is not to be
reused.
2. To reconnect water, gas, waste and vent lines to all
existing equipment that is to be reused.
3. To provide a complete and operative system in
accordance with the intent of these drawings and
specifications.
D.The contractor shall include in his bid proposal all costs
related to the disposal of existing equipment removed
under his contract.
E.Existing waste, vent, water and gas lines no longer used
for any purpose shall be removed unless imbedded in
masonry, in which case it shall be cut off flush with
surface and patched, ready for finish.
F.Where plumbing fixtures are removed, all the existing
waste, vent and water lines shall be removed back to the
next active branch.
G.Existing PVC in new return air plenums shall be wrapped
within materials listed and labeled for such application, to
meet the 25/50 flame smoke rating.
H.All fittings, piping, fixtures, materials, etc. to meet the
current Safe Drinking Water Act with all of its
amendments and the Reduction of Lead in Drinking
water Act.
I.All work shall comply with all national, state, local codes
and ordinances pertaining to the work in this project.
J.All plumbing fixtures shall be supplied with individual
water supply stops and code approved traps. Exposed
piping shall be chrome plated.
K.All plumbing fixtures shall be installed with approved
backflow prevention devices.
L.No piping shall pass directly over electrical power
distribution cabinets, panelboards, etc. Contractor to
coordinate panel locations prior to piping installation.
M.Single runouts to plumbing fixtures shall be the same
size as on the plumbing fixture schedule unless
otherwise noted.
N.Concealed gas piping shall be constructed in accordance
with code without unions, tubing fittings or running
threads.
O.Gas lines run on roof to be supported by Roof Top Blox
or similar and equal. DO NOT USE LUMBER FOR GAS
PIPING SUPPORT.
P.Dry-pipe fire protection system shall be used in all areas
subject to freezing.
)GPGTCN0QVGU
P201
PLUMBING
PLAN
SCALE: 1/4" = 1'-0"
GJR
SLH
1 PLUMBING PLAN P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
Plumbing Fixture Schedule
/CTM
0Q
&GUETKRVKQP
*9 %9 9 8
2KRG%QPPGEVKQPU
KP/QFGN0WODGTU #EEGRVCDNG/CPWHCEVWTGTU
9#6'4%.15'6Ä)2(8KVTGQWUEJKPCHNQQTOVFUKRJQP
LGVHNWUJVCPMGNQPICVGFDQYN1RGPHTQPVUGCVNGUUEQXGT
%JTQOGRNCVGFDTCUUUWRRN[.QQUGMG[UVQR
#((VQVQR
QHUGCVVQUWKV#&#(NWUJJCPFNGVQDGQPYKFGUKFGQHUVCNN
/C2UEQTGITCOUQTDGVVGT
9%Ä*Ä -1*.'45.1#06161<740
$'/+5%'061%1%*74%*%
#/'4+%#056#0&##
#/'4+%#056#0&.#8#614;Ä)2/8KVTGQWUEJKPCYCNNJWPIHNCVRNCVGUVTCKPGT
ECUVDTCUUVTCRYKVJEQNQQUGMG[UVQRUEJTQOGRNCVGFUWRRNKGU
HNQQTOQWPVGFECTTKGTYKVJEQPEGCNGFCTOUWRRQTVQHHUGVVCKNRKGEG
RTQVGEVKXGRKRGCPFXCNXGEQXGTKPIU(CWEGVQPEGPVGTUNGXGT
JCPFNGU/QWPV"VQTKOVQUWKV#&#
.Ä*%*+%#)1)41*'6 5
-1*.'45.1#06161<740
<740<4Ä:.
,45/+6*9#&'<740<Ä'<
/%)7+4'2.7/$'4':<740647'$41'Ä<
<740<ÄÄÄ.)4'#5'+06'4%'2614Ä%CUVKTQPHNWUJOQWPVGFEQXGTHNQY
EQPVTQNFGXKEG)2/HNQYTCVGNDUITGCUGECRCEKV[)+Ä#Ä Ä ,15#/,45/+6*41%-(14&
<740<0ÄÄÄ<Ä(5Ä#(.1145+0-Ä%CUVKTQPPKEMGNDTQP\GUSWCTGHNCVUVTCKPGT
UGFKOGPVDWEMGV2TQXKFGFGGRUGCNRÄVTCR
Ä Ä Ä ,45/+6*,15#/9#665/+(#$
(.114%.'#0176Ä4QWPFUEQTKCVGFPKEMGNDTQP\GVQRDTQP\G
RNWICPFICUMGV%CTRGVOCTMGT
HQTECTRGVGFHNQQTU%1Ä#<740<0ÄÄ$2.+0'
5+<'Ä Ä Ä ,45/+6*,15#/9#665
(.114&4#+0Ä%CUVKTQPPKEMGNDTQP\GTQWPFHNCVUVTCKPGT&GGR
UGCNRÄVTCRYKVJVTCRUGCN(&Ä#Ä Ä Ä5+17:%*+'(,45/+6*,15#//+(#$9#665<740
574'5'#.558
/125+0-Ä(NQQTOQWPVGF:ECUVRQN[OGT2TQXKFGJQUG
YKVJJCPIGTOQRJQQMRÄVTCRUUUVTCKPGTUUYCNNIWCTFU5GTXKEG
HCWEGVYKVJXCEWWODTGCMGT5GCNCVYCNN
/5Ä
(+#659#0/756''56'409+..+#/5
%*+%#)16 5<740
(.14'5610'/54Ä
52'#-/#05%Ä
(.14'5610'/4Ä/4Ä/4Ä/4Ä(+#659#0/756''56'409+..+#/5
9#6'4*'#6'4Ä)CUJKIJGHHKEKGPE[ICNUVQTCIGVCPM
)2*TGEQXGT["(TKUG$672TQXKFGXGPVNGUU
ICURTGUUWTGTGIWNCVQTUWKVCDNGHQTUKVGICURTGUUWTGUGVVQ
OHITUTGEQOOGPFCVKQPU6JGTOCNGZRCPUKQPVCPM5GVQWVNGV
VGORGTCVWTGVQ(
9*Ä#
Ä #15/+6*$1%-.1%*+08#44*''/56#6'$4#&(14&9*+6''(Ä6Ä'Ä0
#/641.56Ä#15/+6*6#%1
/8Ä#
/+:+0)8#.8'Ä#55'6JGTOQUVCVKECNN[EQPVTQNNGF
VGORGTCVWTGCPFRTGUUWTGEQORGPUCVGF2TQXKFGYKVJWPKQPU
EJGEMUVQRUUJWVQHHXCNXG VJGTOQOGVGT5GVQWVNGVVGORGTCVWTG
VQ(
Ä Ä $4#&.';.'10#4&5;//105.#9.'4ÄÄ
9#6'451(6'0'4Ä)2/HNQYTCVG95Ä#%7..+)#0*'Ä Ä #37#5;56'/5/#4.1
9+.-+05:.4'&7%'&24'5574'<10'$#%-(.1924'8'06'4Ä/CMG
CPFOQFGNCUCRRTQXGFD[VJG+PF&GRVQH*GCNVJ42<$2 Ä Ä Ä %10$4#%1('$%19#665
Ä
8GTVKECNRKRGFTQRQWVQHDQVVQOQH
JQTK\QPVCNRKRG
8GTVKECNRKRGTKUGQWVQHVQRQHJQTK\QPVCN
RKRG
(NQQTFTCKP
(&
5JWVQHHXCNXGKPRKRG
'NDQYFQYP
FTQRKPRKRG
'NDQYWR
TKUGKPRKRG
%NGCPQWVKPHNQQT%1
5CPKVCT[DGNQYITCFGQTUNCD
9
8GPVRKRKPI
8
Plumbing Symbols and Abbreviations
%QNFYCVGTRKRKPI
%9
(KNVGTGFYCVGTRKRKPI
(9
(NQQTUKPM
(5
5QHVGPGFJQVYCVGTRKRKPI
*9Ä5
5QHVGPGFEQNFYCVGTRKRKPI
%9Ä5
)CU2KRKPI
)
%1Ä#
(5Ä#
(&Ä#
.Ä*
)+Ä#
(5Ä#
(&Ä#
(&Ä#
(&Ä#
9%Ä*
%1Ä#
(5Ä#
.Ä*
9%Ä*
2
2
/5Ä
9
9
9 9
9
9
9
9
9
9
9
9
9
9
9
9 8
(5Ä#
8
8
8
8
8
8 8
8
8
8EQPPGEVVQ
GZKUVKPI864
%CR
6GG
)CU
XCNXG
)CU
UWRRN[
7PKQP
%QPPGEVVQ
GSWKROGPV
O
K
P
%CR
6GG
)CU
XCNXG
)CU
UWRRN[
7PKQP
%QPPGEVVQ
GSWKROGPV
O
K
P
016'
&GVCKNUUJQYPJGTGCTGV[RKECNQPN[CPFOC[PQVDGEQORNGVG%QPVTCEVQTUJCNNRTQXKFGCNN
OCVGTKCNCPFNCDQTPGEGUUCT[HQTVJGEQPHKIWTCVKQPRKRKPICPFCEEGUUQTKGUTGSWKTGFVQ
QRGTCVGVJKUU[UVGOKPVJGOCPPGTKPVGPFGFYKVJEQORNGVGUCHGV[
)CUEQEM
&KTVNGI
6QOQRUKPM
9CVGTJGCVGT
HNWG
)
#5/'6 2TGNKGH
XCNXG
V[R
&KGNGEVTKE
WPKQP
V[R
KPVCMG
6JGTOQOGVGT
/KZKPIXCNXG
/8Ä#NQECVG
DGNQYYCVGTNKPG
6CPMFTCKP
6JGTOQOGVGT
V[R
6JGTOCNGZRCDUQTDGT
5WRRQTVCUPGEGUUCT[
%9
*9
0%
9CNNDTCEMGVKHPQVRTQXKFGF
D[OHITUJCNNDGEQPUVTWEVGF
QHCPINGKTQPUWKVCDNGHQT
UWRRQTVQHWPKV
%9
$TKPGEJCTIKPINKPG
$[RCUUXCNXG
0%
5JWVÄQHHXCNXG
V[R
4GUKPVCPM
6KOGTEQPVTQNNGT
DCEMYCUJXCNXG
7PKQP
V[R
#KTICR
1XGTHNQY
$TKPGVCPM
YHNQCVXCNXG
(NQQTFTCKP
%QPETGVG
JQWUGMGGRKPIRCF
%9Ä5
P601
PLUMBING
SCHEDULES
& DETAILS
SCALE: NTS
GJR
SLH
1 WASTE & VENT SCHEMATIC
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
'ZGEWVKXG&TKXG·5WKVG·+PFKCPCRQNKU+PFKCPC··YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
SCALE: NTS
2 WATER HEATER DETAIL
SCALE: NTS
3 GAS DIRT LEG DETAILS
SCALE: NTS
4 WATER SOFTENER DETAIL
Plumbing
1.General:
A.All work to be in compliance with the Indiana Plumbing Code, Indiana Accessibility Code and all state and local
ordinances.
B.All applicable provisions of the General Conditions and the General Requirements for Mechancial Work are a part
of this section.
2.Scope of Work:
A.Furnish all labor, materials , equipment, supervision and services required for complete installation of plumbing
service as required for complete installation of plumbing systems as indicated, specified or reasonably implied.
B.Systems shall be complete, operable installations. All work to be done in
accordance with local and national plumbing codes.
3.General Requirements:
A.Piping shall not be installed at locations having ductwork until after air ducts are in place and this contractor shall
be responsible for routing his work to clear air ducts as well as light fixtures and equipment of other trades.
B.Runs of piping are in part, diagrammatic, and contractor shall run piping to best fit field conditions. Field variation
of scale dimensions of drawings is required. Since actual locations, dimensions and levels will be governed by
architectural drawings and actual field conditions.
C.Fixtures shall be installed so that connecting and disconnecting of piping and accessories can be made readily and
parts are easily accessible for inspection, operations, maintenance and repair. Provide access panels where
required.
4.Shop Drawings:
A.Review of shop drawings does not relieve Contractor of responsibility for correct ordering of material or equipment.
B.Include all significant data on shop drawing submittals shown in Specifications and Equipment Schedules.
C.Contractor review should insure that equipment will fit into available space.
D.Submit shop drawings in brochure form and include all related equipment in one brochure.
E.Submit two (2) copies more than Contractor needs for his use. Or, provide electronic copies.
F.After award of contract, submit within 30 days.
G.Submit shop drawings of all major plumbing components, such as plumbing fixtures, etc. Coordinate with
Engineer.
H.Contractor shall review and approve and affix his company name (in the form of a stamp) and project name to all
shop drawings and submittals before submitting.
5.Electrical Wiring:
A.Will be furnished by Electrical Contractor. This Contractor shall furnish necessary controls, wiring diagrams and
instructions.
6.Piping Drawings:
A.Drawings are partially diagrammatic and are not intended to show in detail all features of work.
B.Location of piping shall be checked to determine that it clears openings and important structural members. That
piping indicated as concealed can be properly concealed in walls or partitions of finished rooms. And that it does
not interfere with cabinets, lights or other equipment having fixed locations.
C.Piping shall be concealed except where specifically noted otherwise.
D.All plumbing openings through walls and floors shall be fire stopped, by caulking annular spaces air tight, if the
pipes extend into adjacent areas.
7.Testing:
A.Water Lines:
1.Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or
repaired.
2.Test to a hydrostatic pressure of 100 psi., for a period of twenty-four (24) hours.
3.Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are
obtained.
4.Prepare report for tests and required corrective action.
B.Sanitary and Vent Lines:
1.Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or
repaired.
2.Test according to procedures of authorities having jurisdiction.
3.Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are
obtained.
4.Prepare report for tests and required corrective action.
C.Natural Gas Lines:
1.Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or
repaired.
2.Test, inspect and purge lines according to the International Fuel Gas Code and Authorities having jurisdiction.
3.Repair leaks and defects with new materials and retest piping, or portion there of, until satisfactory results are
obtained.
4.Prepare report for tests and required corrective action.
8.Materials:
A. In the event a material for a specific use is not mentioned, contractor shall supply best material suitable for use
intended.
B.Sanitary Waste and Vent:
1.All drain lines to be Solid wall PVC (ASTM D 2665), Type K Copper (ASTM B306) or Hubless Cast Iron
(ASTM A 888). DO NOT USE CELLULAR CORE PVC.
2.Vertical and horizontal lines shall be concealed, unless specifically indicated as exposed.
5.Installation of sanitary piping shall be carefully planned to meet invert elevations as required.
6.Turns in horizontal lines shall be accomplished via long turn wye branches or through combination wye and
eighth bends.
7.Slope 21/2" and smaller lines at 1/4"/ft. Slope 3" and larger lines at a minimum of 1/8”/ft.
8.All piping in a plenum shall be Copper, Hubless Cast Iron or PVC wrapped within materials listed and labeled
for such application and have a 25/50 flame smoke rating.
9.Every fixture trap shall be protected against siphonage and back pressure. Air circulation shall be assured.
10.Vent lines shall be free from drops or sags and shall be so graded and connected as to slope back to the soil
or waste pipe by gravity.
C.Domestic Water:
1.All water lines below slab to be type K copper (ASTM B 88M, Type A). All water lines above slab to be type L
copper (ASTM B 88M, Type B).
2.All piping in return air plenums to be copper and have a 25/50 flame smoke rating.
3.Copper service line to be stubbed out to existing meter pit.
4.All fittings to be wrought copper (ASTM B 16.22) with soldered joints.
5.Solder and fluxes shall be lead-free, equal to or less than 0.2 percent lead.
6.Install dielectric fittings where material changes make it necessary.
7.Hot and Cold water lines below slab shall be separated by a minimum of six (6) inches.
8.Water supply to fixtures shall be sized as shown on drawings. In no case shall they be less than as indicated
in state and local codes.
9.Fixture supplies to be chrome plated.
10.Provide individual stops for each fixture.
11.This contractor to provide for testing and certification of backflow preventers per state requirements.
12.Contractor shall verify with water co. before installation of meter for clearances required for maintenance by
water co.
D.Gas
1.Gas Pipe Materials:
a.Steel Pipe: ASTM A 53/A 53M, black steel, Schedule 40, Type E or S, Grade B.
(1)Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern.
(2)Wrought-Steel Welding Fittings: ASTM A 234/A 234M for butt welding and socket welding.
(3)Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground joint, and threaded
ends.
b.Corrugated, Stainless-Steel Tubing: Comply with ANSI/IAS LC 1.
(1)Manufacturers: Subject to compliance with requirements, provide products by one of the following:
(2)Tubing: ASTM A 240/A 240M, corrugated, Series 300 stainless steel.
(3)Coating: PE with flame retardant.
c.Fittings: Copper-alloy mechanical fittings with ends made to fit and listed for use with corrugated
stainless-steel tubing and capable of metal-to-metal seal without gaskets. Include brazing socket or
threaded ends complying with ASME B1.20.1.
d.Striker Plates: Steel, designed to protect tubing from penetrations.
e.Manifolds: Malleable iron or steel with factory-applied protective coating. Threaded connections shall
comply with ASME B1.20.1 for pipe inlet and corrugated tubing outlets.
f.Operating-Pressure Rating: 5 psig.
2.Comply with the International Fuel Gas Code for installation and purging of natural-gas piping.
3.Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems.
Indicated locations and arrangements are used to size pipe and calculate friction loss, expansion, and other
design considerations. Install piping as indicated unless deviations to layout are approved on Coordination
Drawings.
4.Arrange for pipe spaces, chases, slots, sleeves, and openings in building structure during progress of
construction, to allow for mechanical installations.
5.Install piping in concealed locations unless otherwise indicated and except in equipment rooms and service
areas.
6.Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or
parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.
7.Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
8.Locate valves for easy access.
9.Install natural-gas piping at uniform grade of 2 percent down toward drip and sediment traps.
10.Install piping free of sags and bends.
11.Install fittings for changes in direction and branch connections.
12.Verify final equipment locations for roughing-in.
13.Comply with requirements in Sections specifying gas-fired appliances and equipment for roughing-in
requirements.
14.Drips and Sediment Traps: Install drips at points where condensate may collect, including service-meter
outlets. Locate where accessible to permit cleaning and emptying. Do not install where condensate is subject
to freezing.
a.Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped. Use nipple a
minimum length of 3 pipe diameters, but not less than 3 inches long and same size as connected pipe.
Install with space below bottom of drip to remove plug or cap.
15.Extend relief vent connections for service regulators, line regulators, and overpressure protection devices to
outdoors and terminate with weatherproof vent cap.
16.Conceal pipe installations in walls, pipe spaces, utility spaces, above ceilings, below grade or floors, and in
floor channels unless indicated to be exposed to view.
17.Use eccentric reducer fittings to make reductions in pipe sizes. Install fittings with level side down.
18.Connect branch piping from top or side of horizontal piping.
19.Install unions in pipes NPS 2 and smaller, adjacent to each valve, at final connection to each piece of
equipment.
20.Do not use natural-gas piping as grounding electrode.
21.Install strainer on inlet of each line-pressure regulator and automatic or electrically operated valve.
22.Install sleeves for piping penetrations of walls, ceilings, and floors.
23.Install sleeve seals for piping penetrations of concrete walls and slabs.
24.Install escutcheons for piping penetrations of walls, ceilings, and floors.
25.Outdoor Piping Schedule
a.Aboveground natural-gas piping shall be one of the following:
(1)Steel pipe with malleable-iron fittings and threaded joints.
(2)Steel pipe with wrought-steel fittings and welded joints.
26.Indoor Piping Schedule
a.Aboveground, piping shall be one of the following:
(1)Corrugated stainless-steel tubing with mechanical fittings having socket or threaded ends to match
adjacent piping.
(2)Steel pipe with malleable-iron fittings and threaded joints.
9.Insulation:
A.Insulation Materials
1.Products shall not contain asbestos, lead, mercury, or mercury compounds.
2.Products that come in contact with stainless steel shall have a leachable chloride content of less than 50 ppm
when tested according to ASTM C 871.
3.Insulation materials for use on austenitic stainless steel shall be qualified as acceptable according to
ASTM C 795.
4.Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing process.
5.Cellular Glass: Inorganic, incombustible, foamed or cellulated glass with annealed, rigid, hermetically sealed
cells.
6.Flexible Elastomeric Insulation: Closed-cell, sponge- or expanded-rubber materials. Comply with
ASTM C 534, Type I for tubular materials.
B.Adhesives
1.Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to
itself and to surfaces to be insulated, unless otherwise indicated.
2.Cellular-Glass Adhesive: Two-component, thermosetting urethane adhesive containing no flammable
solvents, with a service temperature range of minus 100 to plus 200 deg F.
3.Flexible Elastomeric and Polyolefin Adhesive: Comply with MIL-A-24179A, Type II, Class I.
C.Protective Shielding Guards
1.Protective Shielding Pipe Covers:
a.Description: Manufactured plastic wraps for covering plumbing fixture hot- and cold-water supplies and
trap and drain piping. Comply with Americans with Disabilities Act (ADA) requirements.
D.Preparation
1.Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will adversely
affect insulation application.
2.Coordinate insulation installation with the trade installing heat tracing. Comply with requirements for heat
tracing that apply to insulation.
3.Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless-steel
surfaces, use demineralized water.
E.General Installation Requirements
1.Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids
throughout the length of piping including fittings, valves, and specialties.
2.Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses required for each item
of pipe system as specified in insulation system schedules.
3.Install accessories compatible with insulation materials and suitable for the service. Install accessories that
do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state.
4.Install insulation with longitudinal seams at top and bottom of horizontal runs.
5.Install multiple layers of insulation with longitudinal and end seams staggered.
6.Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties.
7.Keep insulation materials dry during application and finishing.
8.Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive
recommended by insulation material manufacturer.
9.Install insulation with least number of joints practical.
10.Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film
thicknesses.
11.Install insulation with factory-applied jackets as follows:
a.Draw jacket tight and smooth.
b.Cover circumferential joints with 3-inch- wide strips, of same material as insulation jacket. Secure strips
with adhesive and outward clinching staples along both edges of strip, spaced 4 inches o.c.
c.Overlap jacket longitudinal seams at least 1-1/2 inches. Install insulation with longitudinal seams at
bottom of pipe. Clean and dry surface to receive self-sealing lap. Staple laps with outward clinching
staples along edge at 2 inches o.c.
(1)For below-ambient services, apply vapor-barrier mastic over staples.
d.Cover joints and seams with tape, according to insulation material manufacturer's written instructions, to
maintain vapor seal.
e.Where vapor barriers are indicated, apply vapor-barrier mastic on seams and joints and at ends adjacent
to pipe flanges and fittings.
12.Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness.
13.Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal
movement.
14.Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at
least 4 inches beyond damaged areas. Adhere, staple, and seal patches similar to butt joints.
15.For above-ambient services, do not install insulation to the following:
a.Vibration-control devices.
b.Testing agency labels and stamps.
c.Nameplates and data plates.
d.Cleanouts.
F.Piping Insulation Schedule
1.Domestic Cold, Hot and Recirculated Hot Water: Insulation shall be one of the following:
a.Flexible Elastomeric: 3/4 inch thick.
b.Cellular Glass: 1 inch thick.
2.Exposed Sanitary Drains, Domestic Water, Domestic Hot Water, and Stops for Plumbing Fixtures for People
with Disabilities: Insulation shall be the following:
a.Protective Shielding Pipe Covers.
10.Hangers and Supports:
A.Carbon-Steel Pipe Hangers and Supports:
1.Description: MSS SP-58, Types 1 through 58, factory-fabricated components.
2.Galvanized Metallic Coatings: Pregalvanized or hot dipped.
3.Nonmetallic Coatings: Plastic coating, jacket, or liner.
4.Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of
piping.
5.Hanger Rods: Continuous-thread rod, nuts, and washer made of carbon steel or stainless steel.
B.Stainless-Steel Pipe Hangers and Supports:
1.Description: MSS SP-58, Types 1 through 58, factory-fabricated components.
2.Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of
piping.
3.Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.
C.Copper Pipe Hangers:
1.Description: MSS SP-58, Types 1 through 58, copper-coated-steel, factory-fabricated components.
2.Hanger Rods: Continuous-thread rod, nuts, and washer made of copper-coated steel or stainless steel.
D.Metal Pipe-Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install hangers, supports, clamps, and
attachments as required to properly support piping from the building structure.
E.Metal Trapeze Pipe-Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Arrange for grouping of
parallel runs of horizontal piping, and support together on field-fabricated trapeze pipe hangers.
1.Pipes of Various Sizes: Support together and space trapezes for smallest pipe size or install intermediate
supports for smaller diameter pipes as specified for individual pipe hangers.
2.Field fabricate from ASTM A 36/A 36M, carbon-steel shapes selected for loads being supported. Weld steel
according to AWS D1.1/D1.1M.
F.Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.
G.Fastener System Installation:
1.Install powder-actuated fasteners for use in lightweight concrete or concrete slabs less than 4 inches thick in
concrete after concrete is placed and completely cured. Use operators that are licensed by powder-actuated
tool manufacturer. Install fasteners according to powder-actuated tool manufacturer's operating manual.
2.Install mechanical-expansion anchors in concrete after concrete is placed and completely cured. Install
fasteners according to manufacturer's written instructions.
H.Pipe Positioning-System Installation: Install support devices to make rigid supply and waste piping connections to
each plumbing fixture.
I.Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other
accessories.
J.Vertical Piping: MSS Type 8 or 42, clamps.
K.Individual, Straight, Horizontal Piping Runs:
1.100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers.
2.Longer Than 100 Feet: MSS Type 43, adjustable roller hangers.
3.Longer Than 100 Feet if Indicated: MSS Type 49, spring cushion rolls.
L.Multiple, Straight, Horizontal Piping Runs 100 Feet or Longer: MSS Type 44, pipe rolls. Support pipe rolls on
trapeze.
M.Base of Vertical Piping: MSS Type 52, spring hangers.
N.Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters:
1.NPS 3/4 and Smaller: 60 inches with 3/8-inch rod.
2.NPS 1 and NPS 1-1/4: 72 inches with 3/8-inch rod.
3.NPS 1-1/2 and NPS 2: 96 inches with 3/8-inch rod.
4.NPS 2-1/2: 108 inches with 1/2-inch rod.
5.NPS 3 to NPS 5: 10 feet with 1/2-inch rod.
6.NPS 6: 10 feet with 5/8-inch rod.
7.NPS 8: 10 feet with 3/4-inch rod.
O.Install supports for vertical copper tubing every 10 feet.
P.Install hangers for steel piping with the following maximum horizontal spacing and minimum rod diameters:
1.NPS 1-1/4 and Smaller: 84 inches with 3/8-inch rod.
2.NPS 1-1/2: 108 inches with 3/8-inch rod.
3.NPS 2: 10 feet with 3/8-inch rod.
4.NPS 2-1/2: 11 feet with 1/2-inch rod.
5.NPS 3 and NPS 3-1/2: 12 feet with 1/2-inch rod.
6.NPS 4 and NPS 5: 12 feet with 5/8-inch rod.
7.NPS 6: 12 feet with 3/4-inch rod.
8.NPS 8 to NPS 12: 12 feet with 7/8-inch rod.
Q.Install supports for vertical steel piping every 15 feet.
R.Install vinyl-coated hangers for PVC piping with the following maximum horizontal spacing and minimum rod
diameters:
1.NPS 2 and Smaller: 48 inches with 3/8-inch rod.
2.NPS 2-1/2 to NPS 3-1/2: 48 inches with 1/2-inch rod.
3.NPS 4 and NPS 5: 48 inches with 5/8-inch rod.
4.NPS 6: 48 inches with 3/4-inch rod.
5.NPS 8: 48 inches with 7/8-inch rod.
S.Install supports for vertical PVC piping every 48 inches.
11.Escutcheon Plates:
A.Lines passing through floors, walls, sink backs, vanity backs or other finished areas shall be fitted with chrome
plated escutcheon plates. Split ring type may be used where necessary.
12.Traps:
A.Provide traps for fixtures and other equipment requiring connection to the drainage system, except where trap is
an integral part of the unit design.
B.Set traps level with respect to their water seal.
C.Traps for floor drains shall be p-traps of materials, weight and joint type conforming to the fittings of the pipe in
which installed.
13.Cleanouts:
A.Provide cleanouts on the ends of each sanitary line and at any other locations as required or as indicated on the
drawings.
B.In no case shall cleanouts be located more than one hundred (100) feet apart.
14.Valves:
A.Water:
1.Valves shall be provide for water lines.
2.Valves shall manufactured by Nibco, Hammond or equal.
3.All service valves shall be full-flow type gate valves or ball valves.
4.Valves shall be mounted in accessible locations and in workable positions. Care shall be taken for mounting
in correct locations.
B.Gas:
1.General Requirements for Metallic Valves, NPS 2 and Smaller: Comply with ASME B16.33.
2.CWP Rating: 125 psig.
3.Threaded Ends: Comply with ASME B1.20.1.
4.Dryseal Threads on Flare Ends: Comply with ASME B1.20.3.
5.Listing: Listed and labeled by an NRTL acceptable to authorities having jurisdiction for valves 1 inch and
smaller.
6.Service Mark: Valves 1-1/4 inches to NPS 2 shall have initials "WOG" permanently marked on valve body.
7.Two-Piece, Full-Port, Bronze Ball Valves with Bronze Trim: MSS SP-110.
8.Bronze Plug Valves: MSS SP-78.
9.Valve Installation
a.Install manual gas shutoff valve for each gas appliance ahead of corrugated stainless-steel tubing or
copper connector.
b.Install regulators and overpressure protection devices with maintenance access space adequate for
servicing and testing.
10.Aboveground Manual Gas Shutoff Valve Schedule
a.Valves for pipe sizes NPS 2 and smaller at service meter shall be one of the following:
(1)Two-piece, full-port, bronze ball valves with bronze trim.
(2)Bronze plug valve.
b.Distribution piping valves for pipe sizes NPS 2 and smaller shall be one of the following:
(1)Two-piece, full-port, bronze ball valves with bronze trim.
(2)Bronze plug valve.
c.Valves in branch piping for single appliance shall be one of the following:
(1)Two-piece, full-port, bronze ball valves with bronze trim.
(2)Bronze plug valve.
15.Finishing:
A.Plumbing fixtures shall be supported securely with concealed brackets, anchors or cleats or required.
B.Carefully seal cracks between fixture and wall or floor with mold resistant silicone caulking compound.
C.Cutting and patching shall be done using methods specifically approved by Architect/Engineer.
D.Carefully locate fittings using architectural drawings. Do not scale plumbing drawings.
E.Rough-in shall be in accordance with equipment and fixture supplier's roughing-in dimensions.
16.Fire Protection:
A.Contractor shall provide new equipment and adjust existing equipment as required to install a complete fire
protection sprinkler system to cover all areas of tenant renovation.
B.Fire Protection system shall meet all 2010 NFPA 13, national and local codes.
C.Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.
D.Delegated Design: Design sprinkler system(s), including comprehensive engineering analysis by a qualified
professional engineer, using performance requirements and design criteria indicated.
F.Dry-pipe fire protection system shall be used in all areas subject to freezing.
G.Sprinkler system design shall be approved by authorities having jurisdiction.
1.Margin of Safety for Available Water Flow and Pressure: 10 percent, including losses through water-service
piping, valves, and backflow preventers.
2.Sprinkler Occupancy Hazard Classifications:
a.Automobile Parking Areas: Ordinary Hazard, Group 1.
b.Building Service Areas: Ordinary Hazard, Group 1.
c.Churches: Light Hazard.
d.Electrical Equipment Rooms: Ordinary Hazard, Group 1.
e.General Storage Areas: Ordinary Hazard, Group 1.
f.Laundries: Ordinary Hazard, Group 1.
g.Mechanical Equipment Rooms: Ordinary Hazard, Group 1.
h.Office and Public Areas: Light Hazard.
i.Repair Garages: Ordinary Hazard, Group 2.
j.Residential Living Areas: Light Hazard.
k.Restaurant Service Areas: Ordinary Hazard, Group 1.
3.Minimum Density for Automatic-Sprinkler Piping Design:
a.Residential (Dwelling) Occupancy: 0.05 gpm over 400-sq. ft. area.
b.Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. area.
c.Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. area.
d.Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm over 1500-sq. ft. area.
4.Maximum Protection Area per Sprinkler: Per UL listing.
H.Piping Materials
1.Steel Pipe and Fittings
a.Standard Weight, Black-Steel Pipe: ASTM A 53/A 53M, Type E, Grade B. Pipe ends may be factory or
field formed to match joining method.
b.Schedule 30, Black-Steel Pipe: ASTM A 135; ASTM A 795/A 795M, Type E; or ASME B36.10M, wrought
steel; with wall thickness not less than Schedule 30 and not more than Schedule 40. Pipe ends may be
factory or field formed to match joining method.
2.CPVC Pipe and Fittings
a.Standard CPVC Fireguard (where concealed only).
I.Sprinklers
1.General Requirements:
a.Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global,
listing.
b.Pressure Rating for Residential Sprinklers: 175 psig maximum.
c.Pressure Rating for Automatic Sprinklers: 175 psig minimum.
d.Pressure Rating for High-Pressure Automatic Sprinklers: 250 psig minimum.
2.Automatic Sprinklers with Heat-Responsive Element:
a.Early-Suppression, Fast-Response Applications: UL 1767.
b.Nonresidential Applications: UL 199.
c.Residential Applications: UL 1626.
d.Characteristics: Nominal 1/2-inch orifice with Discharge Coefficient K of 5.6, and for "Ordinary"
temperature classification rating unless otherwise indicated or required by application.
3.Sprinkler Finishes:
a.Chrome plated.
b.Bronze.
c.Painted.
4.Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications.
Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.
a.Ceiling Mounting: Chrome-plated steel, one piece, flat.
b.Sidewall Mounting: Chrome-plated steel, one piece, flat.
J.Sprinkler Installation
1.Install sprinklers in suspended ceilings in center of narrow dimension of acoustical ceiling panels.
2.Install dry-type sprinklers with water supply from heated space. Do not install pendent or sidewall, wet-type
sprinklers in areas subject to freezing.
3.Install sprinklers into flexible, sprinkler hose fittings and install hose into bracket on ceiling grid.
K.Sprinkler Schedule
1.Use sprinkler types in subparagraphs below for the following applications:
a.Rooms without Ceilings: Upright sprinklers.
b.Rooms with Suspended Ceilings: Pendent sprinklers.
2.Wall Mounting: Sidewall sprinklers.
3.Spaces Subject to Freezing: Pendent, dry sprinklers or Sidewall, dry sprinklers.
P901
PLUMBING
SPECIFICATIONS
GJR
SLH
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
'C3'
'C3''C3''C3''C3''C3'
'C3''C4'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'C1'
'T1''T1''TR1''TR1'
'P1'
'P1'
'P1'
'C2''C2''C2'
'C2'
'C2'
'C2''C2'
'C2'
'C2'
'C2''C2'
'F1'
'F1''F1''F1''F1'
'F1''F1''F1'
'F1''F1'
'F1'
'F2''F2''F2'
'F2'
'F3'
'F3'
'F3'
'F3''F3'
'EM1'
1
P1-2
P1-2 P1-1
Existing
2
Panel 'P1'
':
+
6
'EM1'
':
+
6
P1-6
2NCP0QVGU
See Arch detail 5/A-4 for track lighting mounting height.
Existing light fixture to remain in place. E.C. shall clean
and execute a functional check light fixture and replace
bulbs with new. Existing lighting controls swtich to be
removed and relocated, patch and prepare for new
finish, see plan for new location.
1
2
Unless otherwise noted on plans, connect all exit signs
(fixture type[s] 'X_') to the room lighting circuit the sign
is serving (ahead of any local switching means).
A.All 120V., 20 Amp circuits over 60' in length shall be
#10 AWG.
B.Contractor shall coordinate with all other trades to
avoid conflicts of space.
C.Contractor shall coordinate the exact location of all
devices with all other trades prior to rough-in. Exact
location to be determined in the field.
D.Contractor shall coordinate with the mechanical and
plumbing contractors for exact locations of equipment
prior to rough-in.
E.Refer to sheet E701 for details and symbols.
F.Refer to sheet E901 for electrical specifications.
G.Shared neutrals shall not be permitted.
H.Upon completion of their work, the Electrical Contractor
shall update all panel schedules that were effected by
the work done in this space.
I.Contractor shall place circuit identification strips on the
inside of all electrical device cover plates upon
completion of their work.
J.E.C. shall clean and execute a functional check for the
demolished devices prior to reuse.
K.If any questions arise concerning the Electrical
requirements of these documents, please contact The
Engineering Collaborative (317) 636-3941, prior to
bidding, fabrication or installation of equipment.
)GPGTCN0QVGU
E201
ELECTRICAL
LIGHTING
PLAN
SCALE: 1/4" = 1'-0"
ABC
SLH
1 ELECTRICAL LIGHTING PLAN P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
Panel 'P1'
3
P1-9
3
Sub-Panel 'SP1'
Pre-wired. By others.
Stub-out 1"C. at 18"A.F.F.
for Data/Phone
Stub-out 1"C. at 18"A.F.F.
to feed power to sub-panel.
5
(2)5 5
5
4
Outlet mounted
within cabinet.
P1-7
E3
P1-4 P1-2
J
(5)11 14
1613
15
(1) Convienent
(4) Dedicated Circuit
receptacles to panel
'P1'. See Arch. detail
7/A-8 for mounting
heights.
P1-12P1-17
E9E8
EF-1
(On roof)
RTU-1
(On roof)
P1-(37,39,41)
#6 wire
WS-A
P1-38
E1
+12"+12"+7'-6"
P1-19
E10
P1-(40,42)
#1 wire
5
5
5
5
5
5
P1-56
P1-36
In ceiling for
optional WI-FI
Optional
Optional
+22"P1-11
E5
Mounted in
base of booth.
3 3
2
2
2
2
P1-8
P1-(21,23)
P1-5
P1-7
P1-8
1
2NCP0QVGU
E.C. to remove existing 125A - 120/208V,3Ø,4W. panel
and returned to own. Install NEW 200A -
120/208V,3Ø,4W.
Outlet mounted +6" above storefront glazing and tied
into light switches.
Outlet with USB charger.
Outlet mounted +6" above ceiling for lighted menu
boards.
Sub-panel box, electrical outlet boxes and whips in
cabinetry by others. E.C. to provide power to sub-panel
box, run whips thru cabinetry and make connections to
electrical power outlets.
Run wiring thru cabinetry.
A.All 120V., 20 Amp circuits over 60' in length shall be
#10 AWG.
B.Contractor shall coordinate with all other trades to
avoid conflicts of space.
C.Contractor shall coordinate the exact location of all
devices with all other trades prior to rough-in. Exact
location to be determined in the field.
D.Contractor shall coordinate with the mechanical and
plumbing contractors for exact locations of equipment
prior to rough-in.
E.Refer to sheet E701 for details and symbols.
F.Refer to sheet E901 for electrical specifications.
G.Shared neutrals shall not be permitted.
H.Upon completion of their work, the Electrical Contractor
shall update all panel schedules that were effected by
the work done in this space.
I.Contractor shall place circuit identification strips on the
inside of all electrical device cover plates upon
completion of their work.
J.E.C. shall clean and execute a functional check for the
demolished devices prior to reuse.
K.If any questions arise concerning the Electrical
requirements of these documents, please contact The
Engineering Collaborative (317) 636-3941, prior to
bidding, fabrication or installation of equipment.
)GPGTCN0QVGU
1
2
120V, 1Ø, 9.0 Amp, electrical outlet on a 20.0 Amp
electrical circuit in wall at 18"AFF, for service to prep.
table. (Item #1) (NEMA 5-15P)
120V, 1Ø, 5.7 Amp, electrical outlet on a 20.0 Amp
electrical circuit in wall at 18"AFF, for service to
dipping freezer. (Item #3) (NEMA 5-15P)
120V, 1Ø, 8.1 Amp, electrical outlet on a 20.0 Amp
electrical circuit in wall at 22"AFF, for service to
merchandise cooler. (Item #5) (NEMA 5-15P)
208/230V, 1Ø, 15.0 Amp, electrical service in wall at
7'-6"AFF, extend and connect to ice machine w/ bin
(Item #8) (3 wire with dedicated neutral for 115V)
120V, 1Ø, 9.1 Amp, electrical outlet in wall at
12"AFF, for service to reach-in refrigerator. (Item #9)
120V, 1Ø, 12.0 Amp, electrical outlet in wall at
12"AFF, for service to reach-in freezer. (Item #10)
(NEMA 5-20P)
'.'%64+%#.%100'%6+10
5%*'&7.'
E1
E3
E5
E9
E10
E8
3
4
5
6
E202
ELECTRICAL
POWER
PLAN
SCALE: 1/4" = 1'-0"
ABC
SLH
1 ELECTRICAL POWER PLAN P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
2410 Executive Drive · Suite 100 · Indianapolis, Indiana 46241 · 317.636.3941 · YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
Light Fixture Schedule
6[RG /CPWHCEVWTGT /QFGN0Q0Q
.CORU .COR6[RG 8QNVCIG /QWPVKPI &GUETKRVKQP +NNWUVTCVKQP
5GG0QVG
0QVGU
2KEVWTGUCTGUJQYPCUCXKUWCNCKFQPN[CPFOC[PQVFGRKEVURGEKHKECVVTKDWVGUNKUVGFKPVJKUUEJGFWNG
%QQTFKPCVGYKVJEGKNKPIUVTWEVWTGRTKQTVQTQWIJÄKPCPFCFLWUVCUPGEGUUCT[VQCXQKFKPUVCNNCVKQPEQPHNKEVU
(
%QQRGT )4Ä.&ÄÄ(Ä708Ä.Ä%&Ä7
.'&4GEGUUGF
.C[ÄKP
Z.'&ITKFVTQHHGTYKVJUVGGNJQWUKPICPFFQQTHTCOG
$CMGTYJKVGGPCOGNHKPKUJ#ET[KNKERTKUOCVKENGPU%TGG
,WPQ
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
(
.KVJQPKC 2/2)$2.5#&'<
96-4GEGUUGF
.C[ÄKP
Z(NWQTGUEGPVITKFVTQHHGTYKVJUVGGNJQWUKPI$CMGF
YJKVGGPCOGNHKPKUJEGNNFGGRNQYKTKFGUEGPVCPQFK\GF
URGEWNCTUKNXGTRCTCDQNKENQWXGTU
%TGG
,WPQ
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
(
%QQRGT )4Ä.&ÄÄ(Ä708Ä.Ä%&Ä7
.'&4GEGUUGF
.C[ÄKP
Z.'&ITKFVTQHHGTYKVJUVGGNJQWUKPICPFFQQTHTCOG
$CMGTYJKVGGPCOGNHKPKUJ#ET[KNKERTKUOCVKENGPU%TGG
,WPQ
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
%
*KÄ.KVG *ÄÄ(Ä.$.
9#5WTHCEG
EGKNKPIOQWPVGFE[NKPFGT
ITG[
%
%QP6GEJ.KIJVKPI 4.Ä%64Ä2
92#44GEGUUGF
%GKNKPI
TGEGUUGFKPECPFGUEGPVYCNNYCUJFQYPNKIJV
5GOKÄURGEWNCTTGHNGEVQTYKVJENGCTVTKO7.NKUVGFHQTFCO
NQECVKQPU
%TGG
,WPQ
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
%
%QP6GEJ.KIJVKPI 40%-&Ä%Ä%.4Ä%.4
.'&4GEGUUGF
%GKNKPI
TGEGUUGF.'&FQYPNKIJV5GOKÄ5RGEWNCTTGHNGEVQTYKVJ
ENGCTVTKO7.NKUVGFHQTFCORNQECVKQPU%TGG
,WPQ
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
2
,COKG;QWPI2GPFCPV %748Ä5/%'
9#
2GPFCPV
$QVVQOQHHKZVWTG
EQQTFKPCVGYKVJ
CTEJKVGEV
5OCNNEWTXGFRGPFCPV*Z%QQTFKPCVGYKVJ#TEJ
INCUUHKPKUJUKNXGTENQVJEQTFYKVJUKNXGTEGKNKPIECR
CPFDCEMRNCVG5JCVVGTRTQQHNCOR
6
,WPQ 66Ä$.
96*1 6TCEM
6TCEÄ/CUVGTYCNNYCUJHNQQFU'ZVTWFGFCNWOKPWOYKVJ
FKGÄECUVCNWOKPWOGPFECRUTKEJVGZVWTGFHKPKUJ$NCEM
HKPKUJ
%TGG
.KVJQPKC
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
'/
#UVTC.KVG ''7Ä7Ä4Ä9
Ä .'&
5WTHCEG
9CNN
℄QHHKZVWTG
Ä#((
.'&EQODKPCVKQPGZKVUKIPYKVJTGFNGVVGTUCPFYJKVG
VJGTOQRNCUVKEJQWUKPIYKVJVYQNKIJVKPIJGCFU5GCNGF
OCKPVGPCPEGÄHTGGNGCFECNEKWODCVVGT[9CNNQTEGKNKPI
OQWPVPWODGTQHHCEGUCPFFKTGEVKQPCNCTTQYUCUUJQYP
QPRNCPU&CORNQECVKQPU%QQTFKPCVGEQNQTYKVJ#TEJKVGEV
7.NKUVGF
%TGG
.KVJQPKC
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
64
,WPQ 4$.
Ä Ä 5WTHCEG
UKPINGEKTEWKVVTCEMYKVJQPG
NKXGGPFHGGFEQPPGEVQT
49
CFLEQPPGEVQT49$NCEMHKPKUJ%TGG
.KVJQPKC
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
64
,WPQ 4$.
Ä Ä UWTHCEG
UKPINGEKTEWKVVTCEM$NCEMHKPKUJ
%TGG
.KVJQPKC
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
1HHKEG
2CPGN2
8
9
#OR
/%$
467Ä
$WKNFKPI'ZVGTKQT
'/GVGTDCUG
4QQH
5%#.'010'
'.'%6+%#.4+5'4&+#)4#/01
'
Volts 120/208 Notes:
Panel 'P1'
Main:200 Amp Main Circuit Breaker
Amps:225 Bus:Copper
Phase:3 Mounting:Surface
Wire:4 Location:Office
Remarks Load (kw)Cir.
No.
20 AMP 1 Pole U.O.N.Cir.
No.
Load (kw)Remarks
Light Rec.Heat A/C Equip.Other A B C Other Equip.A/C Heat Rec.Light
Lighting Back Area 0.99 1 20/1 *20/1 2 1.40 Lighting Serving/Retail Area
Lighting Customer Area 0.97 3 20/1 *20/1 4 0.01 Exit/Emergency Light
Water Heater 0.50 5 20/1 *20/1 6 0.30 Sign
EF-1 0.08 7 20/1 *20/1 8 0.80 Receptacles Storefront Signs
Receptacles w/ USB 0.80 9 20/1 *20/1 10 0.20 Receptacle Convenience
Receptacle Office 0.20 11 20/1 *20/1 12 1.44 Reach-In Freezer
Receptacle Office 0.20 13 20/1 *20/1 14 0.20 Receptacle Office
Receptacle Office 0.20 15 20/1 *20/1 16 0.20 Receptacle Office
Reach-In Refrigerator 1.09 17 20/1 *20/1 18 0.50 WS-A
Ice Bin 0.20 19 20/1 *20/1 20 Spare
Ice Machine 3.12 21 20/2 *20/1 22 Spare
23 *20/1 24 Spare
Spare 25 20/1 *20/1 26 Spare
Spare 27 20/1 *20/1 28 Spare
Space 29 -*-30 Space
Space 31 -*-32 Space
Space 33 -*-34 Space
Space 35 -*-36 Space
RTU-1 17.29
37
60/3
*-38 Space
39 *125/2
40 9.00 Sub-Panel 'SP1'41 *42
1.96 1.60 0.00 17.29 4.79 0.00 Connected Load (kw)9.31 1.94 0.00 0.00 1.40 1.40
1.96 1.60 0.00 17.29 4.79 0.00 Demand Load (kw)9.31 1.94 0.00 0.00 1.40 1.40
Legend Total Demand (kw)Feeder Calculated +/-
Light Rec.Heat A/C Equip Other Total Fed From:Bottom
Total Demand Amps =110 +/-3.36 3.00 0.00 17.29 6.73 9.31 39.69 Wire Size:
Conduit:
'(Ä
6KOGTHQTUKIP
%
)TQWPFKPIRGT
0'%TGHGTVQ
ITQWPFKPIFGVCKN
%
%QP6GEJ.KIJVKPI 40%-&Ä%/Ä%.4Ä%.4
.'&4GEGUUGF
%GKNKPI
TGEGUUGF.'&FQYPNKIJV5GOKÄ5RGEWNCTTGHNGEVQTYKVJ
ENGCTVTKO7.NKUVGFHQTFCORNQECVKQPU%TGG
,WPQ
.KIJVQNKGT
2QTVHQNKQ
2TGUEQNKVG
5RGEVTWO
E601
ELECTRICAL
SCHEDULES
& RISER
DIAGRAM
ABC
SLH
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
'ZGEWVKXG&TKXG·5WKVG·+PFKCPCRQNKU+PFKCPC··YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
Electrical Symbols Legend
.KIJVKPI
5YKVEJGU
2QYGT
(KTGCPF%QOOWPKECVKQP
%KTEWKVKPI
0QVG
%QPFWKVU[UVGOEQPEGCNGFCDQXGEGKNKPI
%QPFWKVU[UVGOWPFGTHNQQT
*QOGTWP%QPFWKVU[UVGOVQRCPGNCUPQVGFQPFTCYKPIU
,WPEVKQPDQZ
%QPFWKVWR
%QPFWKVFQYP
5WTHCEGOQWPVGFEQPFWKVU[UVGO
5KPINGRQNGUYKVEJ
5KPINGRQNGMG[QRGTCVGFUYKVEJ
/QOGPVCT[EQPVCEVUYKVEJ
5KPINGRQNGUYKVEJYKVJRKNQVNKIJV
&KOOGTUYKVEJ
(WUCDNGUYKVEJ
5YKVEJYKVJVJGTOCNQXGTNQCFU
6JTGGÄYC[UYKVEJ
(QWTÄYC[UYKVEJ
-G[GFRWUJDWVVQPMKNNUYKVEJ
&KUEQPPGEVUYKVEJ
/QVQTUVCTVGT
%QODKPCVKQPOQVQTUVCTVGTFKUEQPPGEV
&WRNGZTGEGRVCENG
&WRNGZTGEGRVCENGJQTK\QPVCNN[OQWPVGF
3WCFTGEGRVCENG
)TQWPFHCWNVKPVGTTWRVTGEGRVCENG
9GCVJGTRTQQHITQWPFHCWNVKPVGTTWRVTGEGRVCENG
5KPINGRNGZTGEGRVCENG
(NQQTOQWPVGFFWRNGZTGEGRVCENG
(KTGCNCTORWNNUVCVKQP
%QODKPCVKQPHKTGCNCTORWNNUVCVKQPJQTPUVTQDG
%QODKPCVKQPHKTGCNCTOJQTPUVTQDG
(KTGCNCTOUVTQDGNKIJV
(KTGCNCTOUOQMGFGVGEVQT
(KTGCNCTOVJGTOCNFGVGEVQT
(KTGCNCTOFWEVFGVGEVQT
(KTG#NCTO%QPVTQN2CPGN
6GNGRJQPG6GTOKPCN$QCTF
6GNGRJQPGQWVNGVNQECVKQPEQPFWKVYKVJRWNNYKTGVQCDQXGCEEGUUKDNGEGKNKPI
6GNGRJQPGFCVCQWVNGVNQECVKQPEQPFWKVYKVJRWNNYKTGVQCDQXGCEEGUUKDNGEGKNKPI
&CVCQWVNGVNQECVKQPEQPFWKVYKVJRWNNYKTGVQCDQXGCEEGUUKDNGEGKNKPI
/KETQRJQPGLCEM
%CNNDCEM
%GKNKPIURGCMGT
9CNNOQWPVGFURGCMGT
/CIPGVKEJQNFQRGP
%NQEMNQECVKQP
%#68NQECVKQP
&WRNGZTGEGRVCENGOQWPVGFCDQXGEQWPVGTQTUKPM%QQTFKPCVGYKVJHWTPKVWTGRTKQTVQ
KPUVCNNCVKQP
2NWIUVTKR
&T[ÄV[RGVTCPUHQTOGT
-KVEJGPTQWIJÄKP
/QVQTEQPPGEVKQP
82CPGN$QCTF
82CPGN$QCTF
2QYGTRQNG
5RGEKCNRWTRQUGTGEGRVCENGCUPQVGFQPFTCYKPIU
9CNNOQWPVGFGZKVGOGTIGPE[NKIJVKPIEQODQWPKV
9CNNOQWPVGFGZKVUKIP
%GKNKPIOQWPVGFGZKVUKIP
9CNNOQWPVGF*+&.KIJVHKZVWTG
9CNNOQWPVGFKPECPFGUEGPVQTEQORCEVHNWQTGUEGPVNKIJVHKZVWTG
&QYPNKIJVYKVJGOGTIGPE[DCVVGT[DCEMWR
UYKVEJGF
&QYPNKIJV
NQPIHNWQTGUEGPVUVTKRNKIJVHKZVWTG
ZHNWQTGUEGPVNKIJVHKZVWTG
ZHNWQTGUEGPVNKIJVHKZVWTG
ZHNWQTGUEGPVNKIJVHKZVWTGYKVJGOGTIGPE[DCVVGT[DCEMWR
UYKVEJGF
ZHNWQTGUEGPVNKIJVHKZVWTG
'/
ZHNWQTGUEGPVNKIJVHKZVWTG
PQPÄUYKVEJGF
0.
'/0.
ZHNWQTGUEGPVNKIJVHKZVWTGYKVJGOGTIGPE[DCVVGT[DCEMWR
PQPÄUYKVEJGF
ZHNWQTGUEGPVNKIJVHKZVWTGYKVJGOGTIGPE[DCVVGT[DCEMWR
UYKVEJGF
ZHNWQTGUEGPVNKIJVHKZVWTGYKVJGOGTIGPE[DCVVGT[DCEMWR
UYKVEJGF
'/
0QVCNNU[ODQNUNKUVGFCDQXGCTGUJQYPQPRNCPU
6JGU[ODQNNGIGPFKUWUGFHQTTGHGTGPEGQH
U[ODQNUUJQYPQPRNCPU5GGURGEKHKECVKQPUHQT
KPHQTOCVKQPTGNCVGFVQU[ODQNU
92
%GKNKPIOQWPVGFQOPKÄFKTGEVKQPCNV[RGFWCNVGEJPQNQI[QEEWRCPE[UGPUQT
UVCPFCTF
TCPIG4GHGTVQ/CPWHCEVWTGTUKPUVTWEVKQPUHQTGZCEVKPUVCNNCVKQPTGSWKTGOGPVURTKQT
VQTQWIJÄKP
%GKNKPIOQWPVGFQOPKÄFKTGEVKQPCNV[RGFWCNVGEJPQNQI[QEEWRCPE[UGPUQT
GZVGPFGF
TCPIG4GHGTVQ/CPWHCEVWTGTUKPUVTWEVKQPUHQTGZCEVKPUVCNNCVKQPTGSWKTGOGPVURTKQT
VQTQWIJÄKP
9CNNEQTPGTOQWPVGFFWCNVGEJPQNQI[QEEWRCPE[UGPUQT4GHGTVQ/CPWHCEVWTGTU
KPUVTWEVKQPUHQTGZCEVKPUVCNNCVKQPTGSWKTGOGPVURTKQTVQTQWIJÄKP
9CNNUYKVEJV[RGFWCNVGEJPQNQI[QEEWRCPE[UGPUQT4GHGTVQ/CPWHCEVWTGTU
KPUVTWEVKQPUHQTGZCEVKPUVCNNCVKQPTGSWKTGOGPVURTKQTVQTQWIJÄKP
%QODKPCVKQPVCORGTTGUKUVCPVFWRNGZTGEGRVCENGCPF75$
7PKXGTUCN5GTKCN$WU
EJCTIKPIRQTVUNKMG%QQRGT64
'/
'/
No Scale2Key to Electrical Circuit Wiring
5YKVEJNGIQT)QÄDGVYGGP
#NNEQPFWEVQTU#9)
%KTEWKV0QFGUKIPCVKQP
#NNEQPFWKVWPNGUU
OC[DGKPUK\GQVJGTUCUPQVGF
#9)KUOKPEQPFWEVQTUK\GGZEGRVCUPQVGF
EQPFWKVKUOKP5K\GGZEGRVCUECRCEKV[
RGTOKVVKPIXQNVEQPVTQNEQPFWEVQTUCPFUYKVEJNGIU
KUOKP(NGZUVGGN)TGGPHKGNFCPF5GCNKVGUK\G
0QVGU
#.ÄQVJGTYKUGPQVGF
QVJGTYKUGPQVGF
)TQWPFEQPFWEVQT
U
KHWUGF
2CPGNFGUKIPCVKQP
2JCUGEQPFWEVQT
U
0GWVTCNEQPFWEVQT
U
*QV
%QOOQP
'OGTIGPE[
$CNNCUV
#%
$CNNCUV
6GUV
5YKVEJ
2TKOCT[EKTEWKVQPN[.CORNGCFUPQVUJQYP
'/
Ä
'
O
G
T
I
G
P
E
[
5
Y
K
V
E
J
G
F
9CNN
5YKVEJ
No Scale3Light Fixture with Battery Backup Wiring Schematic
1 Grounding Detail
}
0QVG
'%UJCNNHQNNQYVJKUFGVCKNHQTRTQRGT
ITQWPFKPIEQPPGEVKQPU
%7UJWPVCTQWPFYCVGT
OGVGT
6[RHQTQTTQFITQWPFKPIHKGNF
%7
/KP
&KUE.KPM
'SWKROGPVITQWPFDWU
0GWVTCNDWU
#V/CKP&KUVTKDWVKQP2CPGN
/&2
6QEQPETGVGGPECUGFGNGEVTQFG
KPOKPQHEQPETGVG
YKVJKPQTPGCTDQVVQOQHHQWPFCVKQPHQQVKPIYKVJOKPQH
ÄQHDCTGEQRRGTEQPFWEVQTPQVUOCNNGTVJCP#9)
%QPPGEVKQPVQEQNF
YCVGTU[UVGO
%7%QPPGEVKQPVQUVTWEVWTCN
UVGGNQHDWKNFKPI
%7
%7
%
7
%7
EQRRGTYGNFNQPI
ITQWPFTQFU
%7VQYCVGTOGVGT
9CVGTOGVGT %QNFYCVGTRKRG
5WTIGCTTGUVQT
%
7
6QFT[VTCPUHQTOGT
U
%QPVTCEVQTUJCNNXGTKH[YKVJNQECN
ICUEQORCP[HQTICUOGVGT
ITQWPFKPIKHTGSWKTGF
%7VQICUOGVGT %7UJWPVCTQWPFICUOGVGT
)CUOGVGT
No Scale
':+6
E701
ELECTRICAL
DETAILS &
SYMBOLS
ABC
SLH
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
'ZGEWVKXG&TKXG·5WKVG·+PFKCPCRQNKU+PFKCPC··YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6
Electrical Specifications
9QTM 9QTMOCPUJKR
6JGGNGEVTKECNKPUVCNNCVKQPUKPENWFKPICNCTOCPFEQOOWPKECVKQPU[UVGOUUJCNNDGVGUVGFVQFGOQPUVTCVG
VJCVGSWKROGPVKPUVCNNCVKQPCPFQRGTCVKQPKUCRRTQRTKCVGCPFHWPEVKQPCN#YTKVVGPTGEQTFQHRGTHQTOCPEG
VGUVUQPURGEKCNGNGEVTKECNU[UVGOUCPFGSWKROGPVUJCNNUJQYEQORNKCPEGYKVJCRRNKECDNGEQFGUCPF
UVCPFCTFU
2TQXKFGCNNTGSWKTGFNCDQTOCVGTKCNUGSWKROGPV %QPVTCEVQTUUGTXKEGUPGEGUUCT[HQTEQORNGVG
KPUVCNNCVKQPQHU[UVGOUTGSWKTGFKPHWNNEQPHQTOKV[YTGSWKTGOGPVUQHCWVJQTKVKGUJCXKPILWTKUFKEVKQPCNNCU
KPFKECVGFQP&TCYKPIU JGTGKPURGEKHKGF
(KPKUJGFLQDUJCNNDGHWPEVKQPCN EQORNGVGKPGXGT[FGVCKNKPENWFKPICP[ CNNUWEJKVGOUTGSWKTGFHQTC
EQORNGVGU[UVGOYJGVJGTQTPQVVJGUGKVGOUDGURGEKHKGFQTUJQYPQP&TCYKPIU
5RGEKCNCVVGPVKQPUJCNNDGIKXGPVQCEEGUUKDKNKV[QHYQTMKPIRCTVU EQPVTQNNKPIRCTVU#FLWUVCDNGRCTVU
UJCNNDGYKPGCU[TGCEJ4GOQXCDNGRCTVUUJCNNJCXGURCEGHQTTGOQXCN
'CEJ%QPVTCEVQTUJCNNCESWCKPVJKOUGNHYFGVCKNUQHCNNYQTMVQDGRGTHQTOGFD[QVJGTVTCFGU VCMG
PGEGUUCT[UVGRUVQKPVGITCVG EQQTFJKUYQTMYQVJGTVTCFGU
+VKUCUUWOGFVJG%QPVTCEVQTKUHCOKNKCTYUVCPFCTFUV%NCUUKPUVCNNCVKQPRTQEGFWTGU6JGTGHQTGVJGUG
5RGEUFQPQVCVVGORVVQKPENWFGGXGT[FGVCKNQTQRGTCVKQPPGEGUUCT[HQTVJGEQORNGVGKPUVCNNCVKQP
+VUJQWNFDGRCTVKEWNCTN[PQVGFVJCVVJGVGTOUHWTPKUJ RTQXKFGCTGKPVGTEJCPIGCDNG VJCVGCQH
VJGUGOGCPUVQRTQXKFGKPUVCNN EQPPGEVWPNGUUQVJGTYKUGUVCVGF
9JGPGXGTVCDNGUQTUEJGFWNGUUJQYSWCPVQHOCVGTKCNUVJG[UJCNNPQVDGWUGFCUHKPCNEQWPV6JGUG
HKIWTGUUGTXGQPN[CUCIWKFGVQ%QPVTCEVQT'C%QPVTCEVQTUJCNNDGTGURQPUKDNGHQTHWTPKUJKPICNN
OCVGTKCNUKPFKECVGFQP&TCYKPIU KP5RGEU
%QPVTCEVQTUJCNNDGTGURQPUKDNGHQTRTQVGEVKQPUCHGMGGRKPI ENGCPNKPGUUQHCNNGZVIGSWKROCVGTKCN
GVENQECVGFKPURCEGUVQDGTGOQFGNGFKPYJKEJJGKUYQTMKPI#URCTVQHJKUTGURQPUKDKNKV[JGUJCNN
RTQXKFGPGEGUUCT[EQXGTUUVTWEVWTGUGVECUTGSFVQMGGRCNNFKTVYCVGTOQKUVWTG FWUVHTQOGSWKR
/GVJQFVJG%QPVTCEVQTRTQRQUGUVQWUGKPRTQVGEVKPIGSWKROGPVUJCNNDGEQQTFKPCVGFY'PIT 1YPGTU
TGRHQTCRRTQXCNDGHQTGCP[YQTMKUUVCTVGF#P[FCOCIGUWUVCKPGFFWTKPIEQPUVTWEVKQPUJCNNDG
EQTTGEVGFQTTGRNCEGFD[%QPVTCEVQT
#UUKIPOGPVQH/KUEGNNCPGQWU9QTM
'ZECXCVKPI DCEMHKNNKPIHQTGNGEVYQTMUJCNNDGD['%
#2TQRGTN[UWRRQTVDCPMUQHGZECXCVKQPYUCHGV[UJGGVHKNG+PUVCNNPGEGUUCT[IWCTFU2TQXKFG
CFGSWCVGRWORKPIGSWKR MGGRGZECXCVKQPHTGGQHYCVGT
$'ZECXCVGRKRGVTGPEJGUVQRTQRGTFGRVJ9JGTGTQEMKUGPEQWPVGTGFGZECXCVGVQDGNQYRKRG
TGHKNNVQCDQXGRKRGYEQORCEVGFITCPWNCTHKNN)TCPWNCTHKNNUJCNNEQPUKUVQHFWPGUCPFITCXGNQT
QVJGTUWKVCDNGOCVGTKCNEQPVCKPKPIPQVOQTGVJCPD[YGKIJVRCUUKPIUKGXG
RCUUKPIUKGXG
%'ZECXCVKQPHQTWVKNKVKGUUJCNNPQVDGDCEMHKNNGFWPVKNCNNTGSFVGUVUCTGRGTHQTOGF CRRTQXGFD['PIT
RQYGTEQ
&9JGPGXGTWPFGTITQWPFHGGFGTUCTGTWPDGNQYHQQVKPIU ITCFGDGCOU%QPVTCEVQTUJCNNDCEMHKNN
VJGXQKFYRQWTGFUVGGNÄTGKPHQTEGFEQPETVQGNGXQHDQVVQOQHHQQVKPIQTITCFGDGCO
'$CEMHKNNYKPDNFINKPGUUJCNNDGOCFGYITCPWNCTHKNNQTEQORCEVGFDCEMHKNNOCVGTKCNNCKFKPNC[GTU
VCORGFVQURGEFEQORCEVKQPCHVGTGCNC[GT
($CEMHKNNWPFGTRCXGFCTGCUJCNNDGOCFGYITCPWNCTHKNNEQORCEVGFDCEMHKNNOCVGTKCNNCKFKP
NC[GTU VCORGFVQEQORCEVKQPCHVGTGCNC[GT
)$CEMHKNNWPFGTQRGP[CTFUQTHKGNFUUJCNNDGOCFGYPQPÄEQORCEVGFDCEMHKNNNCKFKPNC[GTUPQVVQ
GZEGGFFGGR5CPFVTGPEJGUOC[DGCNNQYGFVQUGVVNGPCVWTCNN[ UJCNNDGTGHKNNGFDCEMVQ
ITCFGCUTGSFFWTKPIUV[TCHVGTHKPCNCEEGRVCPEG
*%QPVTCEVQTUJCNNTGHKNNTGITCFG TGHKPKUJCP[CTGCVJCVDGEQOGUWPUCVKUHCEVQT[FWGVQUGVVNGOGPV
YKPQPG[TCHVGTHKPCNCEEGRVCPEG
+%QPVTCEVQTUJCNNXGTKH[CNNGZVIITCFGUKPXGTVUWVKNKVKGUQDUVCENGU VQRQITCRJKECNEQPFKVKQPURTKQT
VQCP[VTGPEJKPIGZECXCVKQPQTWPFGTITQWPFKPUVCNNCVKQPKPGXGPVGZVIEQPFKVKQPUCTGUWEJCUVQ
RTGXGPVKPUVCNNCVKQPKPCEEQTFCPEGY&YIU%QPVTCEVQTUJCNNKOOGFKCVGN[PQVKH['PIT
4QQHQRGPKPIU HNCUJKPITGSFD['%UJCNNDGD['%'%KUTGURQPUKDNGHQTEQTTGEVUK\G NQECVKQP
QHUCOG%QWPVGTHNCUJKPID['%
%WVVKPI RCVEJKPIHQTGNGEVGSWKRUJCNNDGD['%
#%WVUVTWEVWTCNOCVGTKCNUYJGTGTGSFCHVGTCRRTQXCNHTQO#TEJ 'PIT
$'%UJCNNFQCNNJKUQYPEWVVKPI RCVEJKPIKPHKPKUJGFCTGC
5NGGXGU UOCNNQRGPKPIU
PQVHTCOGFHQTGNGEVGSWKRUJCNNDGHWTPKUJGF UGVD['%
#9JGTGGNGEVEQPFWKVURCUUVJTWYCNNUTQQHUEGKNKPIUQTHNTU%QPVTCEVQTUJCNNJCXGUNGGXGUUGVHQT
VJGOYJGPHNTUYCNNUEGKNKPIUQTTQQHUCTGEQPUVTWEVGF+HCP[JQNGUCTGEWVKPHKPKUJGFYQTM
YJGTGUNGGXGUJCXGDGGPQOKVVGFEWVVKPIUJCNNDGFQPGYCEQPETGVGEQTKPIOCEJKPGQTQVJGT
CRRTQXGFOGVJQF QPN[YEQPUGPVQH'PIT#NNUWEJJQNGUCTGVQDGECTGHWNN[EWV UJCNNPQVDG
NCTIGTVJCPPGEGUUCT[6JGUGJQNGUCTGVQDGGPVKTGN[EQXGTGFD[GUEWVEJGQPRNCVGUYJGPYQTMKU
EQORNGVGF5NGGXGUUJCNNDGOCFGQHUVGGNRKRGQTTQNNGFUJGGVUVGGNPQNKIJVGTVJCPIC
$9JGTGEQPFWKVURCUUVJTWUNGGXGUKPGZVYCNNUCPPWNCTURCEGUJCNNDGECWNMGFYQCMWO HKNNGF
KPUKFG QWVYPQPÄJCTFGPKPIYCVGTRTQQHUGCNCPVHKPKUJGFQHHHNWUJYDQVJHCEGUQHYCNN
5JQR&TCYKPIU
4GXKGYQHUJQRFYIUFQGUPQVTGNKGXG%QPVTCEVQTQHTGURQPUKDKNKV[HQTEQTTGEVQTFGTKPIQHOCVGTKCN
GSWKR
+PENWFGCNNUKIPKHKECPVFCVCQPUJQRFYIUWDOKVVCNUUJQYPKP5RGEU 'SWKR5EJGFWNG
%QPVTCEVQTTGXKGYUJQWNFKPUWTGVJCVGSWKRYKNNHKVKPVQCXCKNCDNGURCEG
5WDOKVUJQRFYIUKPDTQEJWTGHQTO KPENWFGCNNTGNCVGFGSWKRKPQPGDTQEJWTG
5WDOKVEQRKGUOQTGVJCP%QPVTCEVQTPGGFUHQTJKUWUG
#HVGTCYCTFQHEQPVTCEVUWDOKVYKPFC[U
5WDOKVUJQRFYIUQHCNNOCLQTGNGEVEQORQPGPVUUWEJCUNKIJVHKZVURCPGNUHKTGCNCTOU[UVGOUGVE
%QQTFY'PIT
%QPVTCEVQTVQCHHKZJKUEQPCOG
KPHQTOQHCUVCOR RTQLPCOGVQCNNUJQRFYIU UWDOKVVCNUDGHQTG
UWDOKVVKPI
%QQTFKPCVKQP$GVYGGP%QPVTCEVQTU
'CEJ%QPVTCEVQT 5WDEQPVTCEVQTUJCNNUVWF[CNN&TCYKPIUCRRNKECDNGVQVJKUYQTMUQEQORNGVGEQQTF
DGVYGGPVTCFGUYKNNDGGHHGEVGF5RGEKCNCVVGPVKQPUJCNNDGIKXGPVQRQKPVUYJGTGEQPFWKVUETQUURKRGU
QTFWEVUYJGTGEQPFWKVRCUUVJTWYCNNU EQNWOPUGVE
+VKUTGURQPUKDKNKV[QHGC%QPVTCEVQT 5WDEQPVTVQNGCXGPGEGUUCT[TQQOHQTQVJGTVTCFGU0QGZVTC
EQORGPUCVKQPYKNNDGCNNQYGFVQEQXGTEQUVQHTGOQXKPIRKRKPIEQPFWKVQTGSWKRHQWPFGPETQCEJKPIQP
URCEGTGSFD[QVJGTU
#VVCEJKPIVQ$WKNFKPI%QPUVTWEVKQP
'SWKROGPVTCEGYC[UWRRQTVUUJCNNDGCVVCEJGFVQUVTWEVWTCNOGODGTU
DGCOULQKUVUGVETCVJGTVJCP
VQHNQQTQTTQQHUNCDU&QPQVCVVCEJVQEGKNKPIUWRRQTVYKTGU
9JGTGGSWKR TCEGYC[KUUWURGPFGFHTQOGZVIEQPETGVGQTOCUQPT[EQPUVTWEVKQPWUGGZRCPUKQP
UJKGNFUVQCVVCEJUWRRQTVUVQEQPUVTWEVKQPGZRCPUKQPUJKGNFDQNVFKCUJCNNDGUCOGUK\GCUUWRRQTVTQF
FKC
9JGTGGZVIOCUQPT[KUPQVUWKVCDNGVQTGEGKXG JQNFGZRCPUKQPUJKGNFQTYJGTGQVJGTOGCPUQH
CVVCEJOGPVKUCFXCPVCIGQWU%QPVTCEVQTUJCNNUWDOKVCNVGTPCVGOGVJQFHQTCRRTQXCND['PIT
'SWKRVQDGKPUVCNNGFKPITQWRUUJCNNPQVDGOVFFKTGEVN[VQOCUQPT[QTEQPETYCNNU/QWPVZ
UVTWEVWTCNEJCPPGNUWEJCUWPKUVTWVVQYCNN UGEWTGGSWKRVQVJGUGEJCPPGNU
9JGTGTCEGYC[KUUWURGPFGFHTQOUVTWEVWTCNUVGGNDNFIHTCOKPIQTUWRRQTVKPIOGODGTUHWTPKUJ
KPUVCNNDGCOENCORUHQTCVVCEJKPIRKRKPIFGXKEGVQDNFIOGODGT
1DVCKPCRRTQXCNHTQO1YPGTQT'PITDGHQTGEWVVKPIQTYGNFKPIVQUVTWEVWTCNOGODGTUQTDGHQTG
JCPIKPIJGCX[GSWKR
'NGEVTKECN%QPPGEVKQPUVQ'SWKROGPV
+PGXGPVVJCVUWRRNKGTTGSWKTGUNCTIGTUVCTVGTQTFKUEQPPVJCPVJQUGKPFKECVGFQPFQEWOGPVUJGUJCNN
TGKODWTUG%QPVTCEVQTUWRRN[KPIVJGUGKVGOUHQTFKHHGTGPEG
.CDGNNKPI 6CIIKPI
'%UJCNNNCDGNCNNGNGEVGSWKRD[QPGQHVJGOGVJQFUFGUETKDGFDGNQY
2TKPVGFECTFNCDGNUOC[DGWUGFQPKVGOUQHGSWKRHWTPKUJGFYRNCUVKEYKPFQYU.CDGNNKPIQHECTFUJCNN
DGPGCVN[RTKPVGFWUKPINGVVGTKPIFGXKEGUWEJCU.GTQ[+PUVTWOGPV
&KTGEVQTKGUQPKPUKFGQHRCPGNDQCTFUUJCNNDGV[RGYTKVVGP UJCNNUJQYNKUVQHEKTEWKVU RQKPVUGSWKRQT
CTGCUUWRRNKGF
/QVQTUVCTVGTUKPVGTNQEMGFYQVJGTUVCTVGTUQTEQPVTQNUVQDGRTQXKFGFYNCDGNUQPKPUKFGQHVJGEQXGT
UVCVKPIPCVWTGQHKPVGTNQEMU[UVGO
KGKPVGTNQEMGFY8EKTEWKVHTQO248
.CDGNUQTVCIUKPUKFGEQXGTQHUCHGV[UYKVEJGUQTOQVQTUVCTVGTUPQVKPIKPVGTNQEMUEQPFWEVQTUK\GUGVE
OC[DGQHGODQUUGFCFJGUKXGVCRGV[RG
.CDGNKPUKFGQHCNNYKTKPIFGXKEGEQXGTRNCVGUVQKPFKECVGEKTEWKV7UGYCVGTRTQQHHGNVVKROCTMGT
2TQXKFGGPITCXGFNCOKPCVGFNCDGNUQPHCEGQHCNNRCPGNUUYKVEJDQCTFUGVE.CDGNUUJCNNDGUETGYGFQT
TKXGVGFVQFGXKEG.GVVGTUUJCNNDGOKPJKIJWPNGUUQVJGTYKUGKPFKECVGF
&GOQNKVKQP 4GOQXCNQH'SWKROGPV
%QPVTCEVQTUJCNNTGOQXGCNNGSWKREQPFWKVUJCPIGTU UWRRQTVUGVEHQTGZVIGNGEVFGXKEGU GSWKR
TGPFGTGFQDUQNGVGD[VJKU%QPVTCEV
9JGTGGZVIGSWKRQTOCVGTKCNUCTGTGOQXGFQTEJCPIGFCNNDTCPEJEQPFWKVUYJKEJPQNQPIGTCTGKP
UGTXKEGUJCNNDGTGOQXGFCUFKTGEVGFD['PIT+HKPEQWTUGQHYQTMQWVNGVUCTGEQXGTGFWRQTQVJGTYKUG
TGPFGTGFKPCEEGUUKDNGCNNYKTKPIVQUCOGUJCNNDGTGOQXGFVQUQWTEG+HEMVVJCVOWUVTGOCKPKPUGTXKEG
KUKPVGTTWRVGFKVUJCNNDGTGEQPPFD[OQUVKPEQPURKEWQWUOGCPUUQCUVQTGOCKPQRGTCVKQPCNYUCOG
ECRCUDGHQTG#NNDNFIUWTHCEGUFCOCIGF QRGPKPIUNGHVD[TGOQXCNQHDQZGURKRKPI QVJGTGSWKR
UJCNNDGTGRCKTGFD[%QPVTCEVQT*QNGUNGHVKPLDQZGUUYKVEJGURCPGNUGVEUJCNNDGENQUGF
9JGTGPGYQRGPKPIUCTGEWV EQPEGCNGFEQPFWKVUGVECTGGPEQWPVGTGFVJG[UJCNNDGTGOQXGFQT
TGNQECVGFCUTGSF9JGTGEQPFWKVVQDGTGOQXGFUVWDUVJTWHNQQTUYCNNU EGKNKPIUUWEJEQPFWKVUJCNN
DGTGOQXGFVQRQKPVYJGTGHKPKUJUWTHCEGUECPDGRCVEJGFCFGSWCVGN[UQVJCVPQGXKFGPEGQHHQTOGT
KPUVCNNCVKQPTGOCKPU2CVEJKPI TGHKPKUJKPITGSFUJCNNDGTGURQPUKDKNKV[QH%QPVTCEVQT
#NNEQPFWKVUGSWKRGVEFGGOGFQDUQNGVGD[1YPGTUJCNNDGEQOGRTQRGTV[QH%QPVTCEVQTWPNGUU
QVJGTYKUGPQVGF UJCNNDGTGOQXGFHTQORTGOKUGUKOOGFKCVGN[
%QFGU 5VCPFCTFU
#NNOCVGTKCNU YQTMOCPUJKRUJCNNEQORN[YCNNCRRNKECDNGEQFGU
#RRNKECDNGEQFGU UVFUUJCNNKPENWFGCNNUVCVGNCYUNQECNQTFKPCPEGUWVKNKV[EQTGIWNCVKQPU CRRNKECDNG
TGSOGPVUQHPCVKQPCNN[CEEGRVGFEQFGU UVCPFCTFU
#NNGNGEVTKECNOCVGTKCNCPFGSWKROGPVKPENWFKPIEQPFWEVQTUEQPVTQNUCPFUKIPCNKPIFGXKEGUUJCNNDG
KPUVCNNGFKPEQORNKCPEGYKVJCRRNKECDNGUGEVKQPUQH0(2#CPF0(2#CPFUJCNNDGNKUVGFCU
EQORN[KPIYKVJCXCKNCDNGUVCPFCTFUQHNKUVKPICIGPEKGUQTQVJGTUKOKNCTGUVCDNKUJGFUVCPFCTFUYJGTG
UWEJUVCPFCTFUCTGTGSWKTGF
+PECUGQHFKHHDGVYGGPDNFIEQFGUURGEUUVCVGNCYUNQECNQTFKPCPEGUKPFWUVT[UVCPFCTFU WVKNKV[EQ
TGIWNCVKQPU %QPVTCEV&QEWOGPVUVJGOQUVUVTKPIGPVUJCNNIQXGTP%QPVTCEVQTUJCNNRTQORVN[PQVKH[
'PITKPYTKVKPIQHUWEJFKHHGTGPEG
0QPÄ%QORNKCPEGUJQWNF%QPVTRGTHQTOCP[YQTMVJCVFQGUPVEQORN[YTGSOGPVUQHCRRNKECDNGDNFI
EQFGUUVCVGNCYUNQECNQTFKPCPEGKPFWUVT[UVFU WVKNKV[EQTGSOGPVUJGUJCNNDGCTCNNEQUVUCTKUKPIKP
EQTTGEVKPIVJGFGHKEKGPEKGU
'NGEVTKECN4CEGYC[U
4CEGYC[U
#4KIKFUVGGNJGCX[YCNNV[RGHWNNYGKIJVOKNFUVGGNRKRGQHUVFRKRGFKOGPUKQPUWPKHQTOYCNN
VJKEMPGUUVJTGCFGFYEQWRNKPIQPQPGGPFJQVFKRICNXQTUJGTCTFK\GF7.CRRTQXGF#NNKGF
4GRWDNKE5VGGN6TKCPINGQTGSWCN
$+PVGTOGFOGVCNEQPFWKV
+/%*QVFKRICNXQTUJGTCTFK\GFUVGGNYDKQEJTQOCVGHKPKUJKPUKFG
QWVUVFRKRGFKOGPUKQPUVJTGCFGF7.CRRTQXGF#NNKGF4GRWDNKE5VGGN6TKCPINGQTGSWCN
%'NGEVOGVCNNKEVWDKPI
'/6Ä6JKPYCNN)CNXQTUJGTCTFK\GFUVGGNV[RG7.CRRTQXGF#NNKGF
4GRWDNKE5VGGN6TKCPINGQTGSWCN
/%ECDNGKUCPCEEGRVGSWCNVQ'/6
&(NGZ6[RG)CNXITQWPFKPI UKPINGUVTKRV[RGYUOQQVJYKTKPIEJCPPGN7.CRRTQXGFPGQRTGPG
LCEMGVGFKPOQKUVNQECVKQPU HQTEQPPGEVKQPUVQOQVQTU#OGT$TCUU5GCNVKVG6[RG'('NGEVTKÄ(NGZ
*-2QTVGTVTKCPINGQTCRRTQXGFGSWCN
'4KIKF0QPÄ/GVCNNKE6[RG
28%*GCX[YCNN5EJGF28%FWEV7.NKUVGFLQKPVUUQNXGPVYGNFGF
HKVVKPIU EGOGPVD[UCOGOHT%CTNQPQTGSWCN
(5WTHCEGOGVCNTCEGYC[
9KTGOQNFÄRKGEGTCEGYC[U[UVGOYCNNPGEGUUCT[HKVVKPIU9KTGOQNF
QT5GTKGU
CUTGSFQT9CNMGTOQNF
(KVVKPIU
#5VGGN%QPFWKV$QFKGU6JTGCFGFUGVUETGYQHEQORTGUUKQPV[RGUVGGNQTOCNNGCDNGKTQPHKVVKPIU
UJCNNDGUVFRKRGFKOGPUKQPU OCKPVCKPEQPVKPWKV[QHITQWPF#RRNGVQP4CEQ6JQOCU $GVVU
QTGSWCN
$'NGEV/GVCNNKE6WDKPI
'/6#NNHKVVKPIUUJCNNDGTCKPVKIJVEQPETVKIJVEQORTGUUKQPV[RGVJKPYCNN
UVGGNQTOCNNGCDNGKTQP(KVVKPIUUJCNNOCKPVCKPEQPVKPWKV[QHITQWPF#RRNGVQP4CEQ6JQOCU
$GVVUQTGSWCN
%(NGZ.KSWKFÄVKIJVEQPPGEVQTUUJCNNJCXGKPUWNCVGFVJTQCVUUVGGNQTOCNNGCDNGKTQPDQF[PGQRTGPG
ICUMGV OCKPVCKPEQPVKPWKV[QHITQWPF%QPPGEVQTUUJCNNDGEQORTGUUKQPV[RG#RRNGVQP4CEQ
6JQOCU $GVVUQTGSWCN
&$WUJKPIUOGVCNNKEQTKPUWNCVGFCUTGSFUVGGNQTOCNNGCDNGKTQPEQPUVTQHUVFRKRGFKOGPUKQPU
#RRNGVQP4CEQ6JQOCU $GVVUQTGSWCN
''.QEM0WVU%CUGJCTFGPGFUVGGNQTOCNNGCDNGKTQP.QEMPWVUJCNNKPUWTGEQPVKPWKV[QHITQWPF
#RRNGVQP4CEQ6JQOCU $GVVUQTGSWCN
+PUVCNNCVKQPÄ)GPGTCN4GSWKTGOGPVU
#EQPFWKVUOC[DGKPUVCNNGFKPEQPETUNCDUVJKEMQTVJKEMGT EQPFWKVUOC[DGKPUVCNNGF
KPUNCDU0QEQPFWKVUNCTIGTVJCPUJCNNDGKPUVCNNGFKPEQPETUNCDUWPNGUUUJQYPQPFYIUQT
CRRTQXGFD['PIT%QPFWKVUUJCNNPQVDGKPUVCNNGFKPEQPETUNCDUNGUUVJCPVJKEM+PPQECUG
YKNNKPUVCNNCVKQPQHEQPFWKVUDGRGTOKVVGFVQKPVGTHGTGYRTQRGTRNCEGOGPVQHRTKPEKRCNTGKPHQTEGOGPV
$%QPFWKVKPEQPETUNCDUJCNNPQVEQOGVQYKPQHHKPKUJGFVQRQHUNCDCVCP[RQKPVKPENWFKPI
ETQUUQXGTU#NNETQUUQXGTUUJCNNQEEWTCVOKFURCP0QVKH['PITYJGTGUWEJQEEWTTGPEGUCTG
WPCXQKFCDNG
'NGEVTKECN9KTKPI
%CDNG.WIU 6CRU
#.WIUHQTVGTOKPCVKQPQHEQPFWEVQTUKPFKUVTKDWVKQPRCPGNUOQVQTUGVEGKVJGTRTQXKFGFD[OHTQTD[
%QPVTCEVQTUJCNNDG6 $EQORTGUUKQPV[RGQTGSWCN5GTKGUHQTEQPFWEVQTU#9)VQ
5GTKGUHQTEQPFWEVQTU/%/ NCTIGT#NNNWIU EQPVCEVUWTHCEGUYJGTGNWIUCTG
KPUVCNNGFUJCNNDGUKNXGTRNCVGF
$6GTOKPCNHQTEQPVTQNYKTGUJCNNDGVKPPGFTKPIVQPIWGV[RG$WEJCPCP6GTOGPF6 $5VCMQPQT
CRRTQXGFGSWCN
%5RNKEGU EQPPGEVKQPUVQEQPFWEVQTUNCTIGTVJCP#9)UJCNNDGD[OGCPUQHEQORTGUUKQPV[RG
6 $5GTKGUHQTÄYC[ 5GTKGUHQTÄYC[EQPPGEVKQPUQTGSWKXCNGPV$WTPF[
EQPPGEVQTU5RNKEGU VCRUUJCNNJCXGCVNGCUVGSWKXCNGPVOGEJUVTGPIVJ KPUWNCUEQPFWEVQTU
&5RNKEKPIQHEQPFWEVQTU#9)QTUOCNNGTUJCNNDGD[QPGQHVJGHQNNQYKPIOGVJQFUEQPFWEVQTU
UJCNNDGVYKUVGFVQIGVJGT UQNFGTGF2TGKPUWNCVGFURTKPIRTGUUEQPPGEVQTUUWEJCU5EQVEJNQM
V[RGU;4 $+FGCN9KPIPWVQTGSWCN
9KTG %CDNG7R6Q8QNVU
#+PUWNCVKQP%QNQTEQFGFVJGTOQRNCUVKEV[RGTCVGF8GZEGRVYJGTGQVJGTYKUGPQVGF
$%QPFWEVQTUUQHVFTCYPEQRRGTGCUVTCPFKPFKXKFWCNN[VKPPGFQTEQCVGFYCRRTQXGFCNNQ[
%NCUU$
UVTCPFKPI
%%QPFWEVQTU 5OCNNGTHQTHKPCNEQPPGEVKQPUVQOQVQTU CNNNQECVKQPUYJGTGXKDTQTOQXGOGPV
KURTGUGPVÄ%NCUU$UVTCPFGFEQPFWEVQTU(QTCNNQVJGTNQECVKQPUÄUQNKFEQPFWEVQTU
&%QPFWEVQTU .CTIGT&QWDNGDTCKF%NCUU$UVTCPFGF
'/KP9KTG5K\G)GPGTCNÄQXGTÄQXGTÄEQPVTQNÄUKIPCNÄQTCU
FGVCKNGFKPCRRTQRTKCVGFUGEVKQPQHVJGUGURGEUQTUJQYPQP&YIU
(6[RGU 7UGU
7PNGUU1VJGTYKUG5RGEFQT+PFKECVGFQP&YIU7RVQ KPENWFKPICOREMVUÄ
6*96*90QT6**0TCVGFCVFGI%CORCEKVKGU)TGCVGTVJCPCOREMVUÄ6*96*90
QT6**0TCVGFCVFGI%CORCEKVKGU
)/HTU#PCEQPFC+66Ä4Q[CN6TKCPING)'QTGSWCN
*9KTG6CIU/CKP HGGFGTECDNGUUJCNNDGVCIIGFKPCNNRWNNDQZGUYKTGYC[U YKTKPIIWVVGTUQH
RCPGNU6CIUUJCNNKFGPVKH[YKTGQTECDNG QTGSWKRUGTXGFCUUJQYPQP&YIU6CIUUJCNNDG
OGVCNQTQHHNCOGÄTGUKUVKPICFJGUKXGOCVGTKCN6 $6[RG95.QTCRRTQXGFGSWCN
+/%%CDNGKUCEEGRVGSWCNVQ'/6HQTCOREMVU
1WVNGV$QZ+PUVCNNCVKQP
1YPGTQTJKUTGRTGUGTXGTKIJVVQEJCPIGNQECVKQPQHCP[QWVNGVWRVQFKUVCPEGQHÄCVPQGZVTC
EJCTIGRTQXKFKPIPGEGUUCT[KPUVTWEVKQPUCTGIKXGPRTKQTVQTQWIJKPIÄKPQWVNGV
.QECVKQPUQHCNNHNTQWVNGVUUJCNNDGXGTKHKGFDGHQTGTQWIJÄKP
'NGEVTKECN2CPGNU
2CPGNU
#6[RG)CNXUVGGNECDKPGVUYVTKO JKPIGFFQQTYNQEM#NNNQEMUVQDGMG[GFCNKMG
$(KPKUJ5VFHCEVQT[HKPKUJ
%)WVVGT5RCEGOKPHQTCORQTNGUURCPGNUOKPHQTCDQXGCORRCPGNDQCTF
&2CPGN&GCFHTQPVUCHGV[V[RG
'.WIU5GRCTCVGUQNFGTNGUUV[RGHQTGCEQPFWEVQT
($TCPEJGU$QNVÄQPEMVDTGCMGTUCUURGEF UK\GCUKPFKECVGFQPFYIU
))TQWPFKPI$WU2TQXKFGUGRCTCVGDWUHQTITGGPITQWPFEQPFWEVQTU+UQNCVGITQWPFDWUHTQO
PGWVTCNDWU
*/HTU)''NGEVTKE9GUVKPIJQWUG)QWNF+6'5SWCTG&
031&
+PUVCNNCVKQPRTQXKFGVYQURCTGEQPFWKVUVQCDCEEGUUKDNGEGKNKPIHQTHWVWTGWUG
'NGEVTKECN9KTKPI&GXKEGU
6QIING5YKVEJGU
#5YKVEJGUUJCNNDGUKPINGRQNGVYQRQNGÄYC[ÄYC[OQOGPVCT[QTRKNQVNVFCUTGSF UJCNNDG
JGCX[FWV[VQIINGQTMG[QRGTCVGFTCVGFCORU8
$2TQXKFGURCTGMG[UHQTMG[QRGTCVGFUYKVEJGU%/HTU*WDDGNN$T[CPV2CUU
5G[OQWT#%
4GEGRVCENGU
##NNTGEGRVUJCNNDGITQWPFKPIV[RG UJCNNDGFWRNGZ8XÄ8UKPINGRJCUGQT
Ä8VJTGGRJCUGCUTGSF
$&WRNGZTGEGRVUJCNNDGQTCOR8JGCX[FWV[URGEITCFGITQWPFKPIV[RGCOR/HTU
*WDDGNN$T[CPV2CUU 5G[OQWTCOR/TU*WDDGNN$T[CPV
2CUU 5G[OQWT
%)TQWPFHCWNVKPVGTTWRVGT
)(+TGEGRVUJCNNDGFWRNGZYDWKNVÄKP)(+UGVVQVTKRCVCOKNNKCORGTG
OCZITQWPFHCWNV4GEGRVUJCNNDGTCVGFQTCORU8UVFQTHGGFÄVJTWCUTGSF/HTU
*WDDGNN)(Ä$T[CPV)(4(62CUU 5G[OQWTÄ(
'NGEVTKECN/QVQT5VCTVGTU
/CPWCNOQVQTUVCTVGTUUJCNNDGVQIINGV[RGUPCRUYYVJGTOCNQXGTNQCFFGXKEG/CPWCNUVCTVGTUUJCNNDG
UKOKNCTVQ5SWCTG&%NCUU
/CIPGVKEOQVQTUVCTVGTUUJCNNDGRJCETQUUÄVJGÄNKPGV[RGTCVGFKPCEEQTFCPEGY0'/#5VFU%QKNUUJCNNDG
QHOQNFGFEQPUVTWEVKQP1XGTNQCFTGNC[UUJCNNDGTGRNCEGCDNGOGNVKPICNNQ[OCPWCNTGUGVV[RGRGTRJCUG
2TQXKFGQPGURCTGCWZKPVGTEJCPIGCDNGEQPVCEV%QPVTQNFGXKEGU
UVQRUVCTV*Ä1Ä#RKNQVNKIJVUJCNNDGOVF
KPEQXGTQHGPEN2KNQVNKIJVUUJCNNDGTGFWPNGUUQVJGTYKUGKPFKECVGF/CIPUVCTVGTUUJCNNDGUKOKNCTVQ
5SWCTG&%NCUU%QODOCIPOQVQTUVCTVGTUYHWUGF
QTPQPÄHWUGFFKUEQPPUYUJCNNDGRJ
CETQUUÄVJGÄNKPGV[RGTCVGFKPCEEQTFCPEGY0'/#5VFU&KUEQPPUYUJCNNEQPUKUVQHXKUKDNGDNCFGU
&KUEQPPJCPFNGUJCNNDGENGCTN[OCTMGFCUVQYJGVJGTFKUEQPPFGXKEGKU10QT1((/QVQTUVCTVGTUKP
EQODOCIPOQVQTUVCTVGTUUJCNNOGGVTGSWKTGOGPVUQHOCIPOQVQTUVCTVGTURTGXKQWUN[QWVNKPGF%QOD
OCIPOQVQTUVCTVGTUUJCNNDGUKOKNCTVQ5SWCTG&%NCUU
%QPVTQNUVCVKQPUUJCNNEQPVCKPJGCX[FWV[V[RGFGXKEGU2WUJDWVVQP UGNGEVQTUYKVEJGUKPEQPVTQNUVCVKQPU
UJCNNDGDCUGOVFYFQWDNGDTGCMUKNXGTEQPVCEVU2KNQVNKIJVUUJCNNDGVTCPUHQTOGTV[RGWUKPIÄ8OKPKCVWTG
DWND%QNQTGFRKNQVNKIJVNGPUGUJCNNDGKPVGTEJCPIGCDNG/HTU#NNGP$TCFNG[5SWCTG&9GUVKPIJQWUG)
'
'NGEVTKECN5CHGV[5YKVEJGU
&KUEQPPGEVU
5CHGV[UYUUJCNNDGJGCX[FWV[HWUGFQTPQPHWUGFYQHRQNGUGNGEVEJCTCEVGTKUVKEUTCVKPIU
OQFKHKECVKQPUCUTGSF
KGJRTCVKPIUJQTVEMVKPVGTTWRVKPITCVKPIGVE
5YKVEJKPIOGEJCPKUOUJCNNDGSWKEMÄOCMGSWKEMÄDTGCMYJCPFNGVJCVKURCFNQEMCDNGKP1((RQUKVKQP
'PENUJCNNDGUWKVCDNGHQTCTGCKPYJKEJKVKUVQDGKPUVCNNGF UJCNNJCXGFGHGCVCDNGFQQTKPVGTNQEMYJKEJ
RTGXGPVUFQQTHTQODGKPIQRGPGFYJGPUYKVEJKU10
(WUKDNGWPKVUYJKEJCTGVQDGGSWKRRGFYEWTTGPVNKOKVKPIHWUGUUJCNNJCXGHWUGJQNFGTUYTGLGEVKQPENKRU
VQRTGXGPVQVJGTV[RGHWUGUHTQODGKPIKPUVCNNGF
/HTU5SWCTG&)'9GUVKPIJQWUG)QWNF+6'
1XGTEWTTGPV2TQVGEVKQP
)GPGTCN4GSWKTGOGPVU
#5JQTVEMVKPVGTTWRVKPITCVKPIUUJCNNDGGSWCNVQQTITGCVGTVJCPOCZUJQTVEMVEWTTGPVURQUUKDNGKP
EMVNQECVKQPYJGTGFGXKEGUYKNNDGKPUVCNNGF NCTIGTYJGTGKPFKECVGF
$9JGTGWUGFHQTQVJGTVJCPOQVQTEMVUFGXKEGUUJCNNDGUK\GFUCOGCUQTPGZVUVFUK\GCD
EQPFWEVQTCORCEKV[
%9JGTGWUGFHQTOQVQTEMVUUK\GUJCNNDGKPCEEQTFCPEGY0'% VKOGFGNC[EJCTCEVGTKUVKEUUJCNN
DGUWKVCDNGHQTOQVQTUCEEGNGTCVKQPVKOG
&#NNFGXKEGUUJCNNDGQHVKOGFGNC[QPPQOKPCNQXGTNQCFU KPUVCPVCPGQWUQRGTCVKQPQPJKIJHCWNV
EWTTGPVV[RGWPNGUUQVJGTYKUGPQVGF
(WUGU
#6JGHQNNQYKPIHWUGTGSWKTGOGPVUCTGIGPGTCNKPPCVWTG#NNEQPFKVKQPUUJCNNDGXGTKHKGFUQVJCVHWUG
UGNGEVKQPYKNNRTQXKFGCFGSWCVGRTQVGEVKQP EQQTF(WUGUUJCNNDGCUHQNNQYUWPNGUUQVJGTYKUG
KPFKECVGFQTTGSFD[HKGNFEQPFKVKQPU
$#DQXGCORU7.%NCUU.EWTTGPVNKOKVKPIV[RGYCORKPVGTTWRVKPIECR
UGEQPF
VKOGFGNC[YEWTTGPV$WUUOCP*KÄ%CR-42Ä%QTGSWCN
%(WUGURTQVGEVKPIEMVDTGCMGTUQTEMVDTGCMGTRCPGNU7.%NCUU4-ÄFWCNGNGOGPVEWTTGPV
NKOKVKPI
UGEVKOGFGNC[YEWTTGPV$WUUOCP.QY2GCM.20Ä4- .25Ä4-QTGSWCN
&#NN1VJGT(WUGU7.%NCUU4-ÄUGEVKOGFGNC[CVTCVKPICORKPVGTTWRVKPI
ECREWTTGPVNKOKVKPIFWCNGNGOGPV$WUUOCP.QY2GCM.20Ä4- .25Ä4-QTGSWCN/QVQTEMVU
HWUGUHQTKPFKXOQVQTTWPPKPIRTQVGEVKQPUJCNNDGUK\GFCVQTOQVQTPCOGRNCVGTCVKPIWPNGUU
QVJGTYKUGKPFKECVGFQTTGEQOOGPFGF(WUGUHQTEQPVTQNEMVUUJCNNDG$WUUOCP(03HQTEQPVTQN
VHQTOGTRTKOCT[ $WUUOCP(WUGVTQP(40HQTUGEQPFCT[QTGSWCN
%MV$TGCMGTU
#%MV$TGCMGTUUJCNNDGICPIÄQRGTCVGFNQCFKPVGTTWRVGTV[RGYUWDUVCPVKCNECUGQHOQKUVWTGTGUKUV
PQPÄCIKPIOQNFGFKPUWNCVKPIOCVGTKCN$TGCMGTUUJCNNDGDQNVGFFGUKIPWPNGUUQVJGTYKUGKPFKECVGF
$%QPVCEVUUJCNNDGEQRRGTCNNQ[QTEQRRGT UKNXGTCNNQ[YCTESWGPEJGTU DCTTKGTHQTGCRQNG
%/GEJCPKUOUJCNNDGSWKEMÄOCMGSWKEMÄDTGCMYVTRGNGOGPVHQTGCRQNG GNGEVTKECNN[
OGEJCPKECNN[VTKRÄHTGG1XGTEWTTGPVQPCP[RQNGQHOWNVKÄRQNGEMVDTGCMGTUJCNNECWUGCNNRQNGUVQ
QRGP
&6TKRGNGOGPVUUJCNNDGCODVGOREQORGPUCVGFVJGTOCNOCIPV[RGYVKOGFGNC[QPPQOKPCN
QXGTNQCFU KPUVCPVCPGQWUVTKRQHUJQTVEMVU%MVDTGCMGTUNCTIGTVJCPCORUJCNNJCXGCFL
VTKRU
''ZVQRGTCVGFJCPFNGUJCNNDGRTQXKFGFYJKEJYKNNKPFKECVG1064+22'& 1((RQUKVKQPU
()(+DTGCMGTUWUGFKPDTCPEJEMVUUJCNNJCXGDWKNVÄKPITQWPFHCWNVUGPUQTYJKEJYKNNCWVQVTKR
DTGCMGTQPOCZOKNNKCORITQWPFHCWNV7PKVUJCNNJCXGDWKNVÄKPRWUJÄVQÄVGUVDWVVQP
)$TGCMGTUHQTEQPVTQNQHHNWQTNKIJVKPIUJCNNDGUYKVEJKPIFWV[V[RGUY$TGCMGTUHQTEQPVTQNQH*+&
NVIUJCNNDG59&Ä*+&TCVGF
*9JGPDTGCMGTUCTGVQDGKPUVCNNGFKPRCPGNDQCTFUDTGCMGTOHTUJCNNDGUCOGCURCPGNDQCTFOHT
)TQWPFKPI
'PVKTGKPUVCNNCVKQPVQDGITQWPFGFKPCEEQTFCPEGY0'%TGSWKTGOGPVU
'SWKRUJCNNDGITQWPFGFVJTWQPGQHVJGHQNNQYKPIRCVJUVQITQWPFEQPFWKVU[UVGOUGRCTCVG
ITQWPFKPIEQPFWEVQTEQPPGEVGFVQOCKPITQWPFKPIEQPFWEVQTQTRCPGNDQCTFITQWPFDWUUGRCTCVG
ITQWPFKPIEQPFWEVQTEQPPGEVGFVQITQWPFTQFKPUVCNNCVKQP
#VCNNGNGEVRCPGNUKPUVCNNITQWPFKPIDWUJKPIUQPCNNEQPFWKVU DQPFVQRCPGNITQWPFDWUWUKPIDCTG
#9)EQRRGTEQPFWEVQT#VLDQZGUDQZGUKPHGGFGTEQPFWKVTWPUKPUVCNNITQWPFKPIDWUJKPIUQPCNN
EQPFWKVUNWIQPLDQZ DQPFEQPFWKVU DQZVQIGVJGTWUKPIDCTG#9)EQRRGTEQPFWEVQT
7PNGUUQVJGTYKUGKPFKECVGFEQPFWKVU[UVGOUJCNNDGCFGSWCVGHQTITQWPFKPITGEGRVUNKIJVHKZVUDTCPEJ
EMVLDQZGUOQVQTUVCTVGTUFKUEQPPUYKVEJGU QVJGTDTCPEJEMVFGXKEGU%QPVTCEVQTUJCNNFTCYWR
EQPFWKVEQPPGEVKQPUVKIJVN[VQKPUWTGRTQRGTITQWPFEQPVKPWKV[+HITQWPFEQPVKPWKV[FQGUPQVGZKUVQTJCU
JKIJTGUKUVCPEGDQPFKPIUVTCRUQTUGRCTCVGITQWPFKPIEQPFWEVQTUUJCNNDGKPUVCNNGF
9KTKPITWPKPPQPÄOGVCNNKEFWEV HNGZEQPFWKVUJCNNECTT[UGRCTCVGITQWPFKPIEQPFWEVQT
#VOQVQTNQECVKQPUOQVQTHTCOGUUJCNNDGDQPFGFVQITQWPFU[UVGOD[OGCPUQHUGRCTCVGEQPFWEVQT
RWNNGFHTQORCPGNITQWPFDWUQTDQPFKPILWORGTHTQOEQPFWKVVQOQVQTHTCOGU
(QTVGNGRJQPGCNCTOEQOOU[UVGOUGVEC#9)EQRRGTEQPFWEVQTHTQOGNGEVITQWPFU[UVGOVQ
GCVGTOKPCNECDKPGVQTGSWKRNQECVKQPUJCNNDGEQPUKFGTGFUWHHKEKGPVWPNGUUQVJGTYKUGKPFKECVGF
4GUKUVCPEGVQITQWPFCVCP[RQKPVUJCNNPQVOGCUWTGOQTGVJCPQJOU
'NGEVTKECN.KIJV(KZVWTGU
(NWQTGUEGPV.KIJV(KZVWTGU
#%QPUVTWEVKQP5JGGVUVGGNFKGHQTOGFVQRTQXKFGUVTWEVWTCNUVTGPIVJ.QWXGTUVQDGEQPUVTWEVGFQH
URTKPIUVGGN
ICOKP
$2CKPVKPIHKZVUVQDGRTQRGTN[VTGCVGFHQTCEEGRVCPEGHQTHKPKUJEQCVU(KPKUJGUVQDGDCMGFYJKVG
JKIJTGHNGEVCPEGGPCOGNQTRQTEGNCKPGPCOGN
%.GPURCPGNHTCOGUNGPURCPGNUHQTUWTHDQZV[RGHKZVU HQTTGEGUUGFVTQHHGTUUJCNNDGHTCOGF
JKPIG NCVEJ(TCOGU NQWXGTUUJCNNDGGSWKRRGFYTGVCKPKPIOGCPUVQUWRRQTVHTCOGFWTKPI
TGNCORKPI
&.CORJQNFGTURQTEGNCKPVWTTGVÄV[RGHQTKPFWUVTKCNHKZVU6QODUVQPGÄ6[RGHQTEQOOGTEKCNHKZVU
'9KTGUJGCVTGUKUVKPIV[RGKPCEEQTFCPEGY0'%
($CNNCUV/QWPVKPIHKZVVQDGFGUKIPGFKPUWEJCOCPPGTVJCVECUGVGORQHDCNNCUVFQGUPQVGZEGGF
FGI%#NNDCNNCUVOQWPVKPIUVWFUVQDGYGNFGFVQHKZV
)(KZVOCPWHCEVWTGFYRTGRCKPVGFUVGGNVQDGRCKPVGF0QWPRCKPVGFGFIGUQHHKZVJQWUKPIYKNNDG
CEEGRVGF
.KIJV(KZV+PUVCNNCVKQP
#(KZVUVQDGGSWKRRGFYNCORUQHRTQRGTUK\G V[RGCUUEJGFWNGFQTTGEQOOGPFGFD[/HT
$6CPFGOHKZVUOC[DGWUGFKPEQPVKPWQWUTQYURTQXKFKPIHKPKUJGFCRRGCTCPEGEQPHQTOUVQ
CRRGCTCPEGQHKPFKXWPKVU
%#NNTQYUQHNKIJVHKZVUVQDGRTQRGTN[CNKIPGF RNWODGF
&5EJGFQH.VI(KZVUQP&YIUEQPVCKPUYTKVVGPFGUETKRVKQPQHHKZV OHTUECVCNQIUURTQXKFGF
CTGKPVGPFGFVQKPFKECVGFGUKIP SWCNKV[FGUKTGF(KZVUOWUVOGGVTGSWKTGOGPVUQHVJKUURGE QH
FGUETKRVKQPEQPVCKPGFKPUEJGFWNG
'+HQWVNGVFQGUPQVJCXGHKZVU[ODQNKPUVCNNHKZVQHUCOGV[RGWUGFKPUKOKNCTNQECVKQPUGNUGYJGTGQP
&YIU
(2TQXKFGCFFKVKQPCNVTKOCUTGSFHQTPGCVOQWPVKPIQHTGEGUUGFHNWQTNKIJVUOVFKPRCVVGTPU
).KIJVHKZVUOC[DGUWRRQTVGFHTQOUWURGPFGFEGKNKPIU[UVGORTQXKFGFEGKNKPIUWURGPUKQPYKTGUQT
TQFUCTGQHUWHHKEKGPVUVTGPIVJVQUWRRQTVCFFGFYGKIJVQHNKIJVHKZVU+VKUTGURQPUKDKNKV[QH'%VQ
EQQTFYEGKNKPIEQPVTCEVQT GPUWTGCFGSWCVGUWRRQTVUCTGHWTPKUJGF
)GPGTCN4GSWKTGOGPVU
#+PUVCNNRTQRGTV[RG UK\GNCORUKPNKIJVHKZVCUKPFKECVGFQP&YIU
$4GRNCEGCNNDWTPGFQWVNCORUCVVKOGQHCEEGRVCPEG
%%QPVTCEVQTUJCNNHWTPKUJVQ1YPGTCEJCTVNKUVKPIUK\G V[RGQHNCORUTGSFD[GCV[RGQHNKIJVHKZV
6JKUEJCTVUJCNNWVKNK\GVJGHWNNNCORQTFGTKPIEQFG
KG6[RG#Ä(%96[RG$Ä2#4(.
4CEGYC[7UCIG
'ZRQUGFTCEGYC[UNCTIGTVJCPTKIKFQTKPVGTOGFKCVG
'ZRQUGF4CEGYC[U 5OCNNGT'/6
4CEGYC[UEQPEGCNGFKPEQPETQTUQNKFRNCUVGTRCTVKVKQPUTKIKF
4CEGYC[UEQPEGCNGFKPHWTTGFURCEGU RCTVKVKQPUQVJGTVJCPEQPETQTUQNKFRNCUVGT'/6
7PFGTITQWPFGNGEV VGNGRJQPGUGTXKEGGPVTCPEGTKIKF28%QTCUDGUVQUEGOGPV
DQVJKPEQPET
GPXGNQRG
'NGEV VGNGRJUGTXKEGUQVJGTVJCPWPFGTITQWPFTKIKFQT+/%
4CEGYC[UKPEQPETUNCDTKIKF+/%QT'/6+H'/6KUWUGFHKVVKPIUUJCNNDGEQORTGUUKQPV[RG
CRRTQXGFHQTWUGKPRQWTGFEQPETGVG
4CEGYC[UDGNQYNQYGUVHNTUNCDTKIKF
28%QTCUDGUVQUEGOGPVKPEQPETGPXGNQRG
4CEGYC[UKPOQKUVNQECVKQPUQTGZRQUGFVQYGCVJGTTKIKFQT28%
7PFGTITQWPFTCEGYC[UVQTGOQVGNQECVKQPUUWEJCUHNQQFNKIJVURWORJQWUGUGVEYJGPEQPET
RTQVGEVKQPGPXGNQRGKUPQVKPFKECVGFQP&YIUTKIKFTCEGYC[NKDGTCNN[EQCVGFYCURJCNVWO
(KPCNEQPPGEVKQPUVQOQVQTUVHQTOGTUQTQVJGTGSWKRTGSWKTKPIOQXGOGPVQTUWDLGEVVQXKDTCVKQPHNGZ
TCEGYC[PGQ2TGPGLCEMGVGF
(TQOQWVNGVDQZVQTGEGUUGFNVIHKZVHNGZTCEGYC[
5JQTVEQPPU KPQVJGTNQECVKQPUYJGTGWUGQHTKIKFTCEGYC[KUKORTCEVKECNHNGZTCEGYC[
#NNQVJGTNQECVKQPUWPNGUUPQVGFQVJGTYKUGQPFYIU'/6
(KTG#NCTOCPF&GVGEVKQP5[UVGOU
0QVKHKECVKQP#RRNKCPEGU
#)GPGTCN4GSWKTGOGPVUHQT0QVKHKECVKQP#RRNKCPEGU%QPPGEVGFVQPQVKHKECVKQPCRRNKCPEGUKIPCN
EKTEWKVU\QPGFCUKPFKECVGFGSWKRRGFHQTOQWPVKPICUKPFKECVGFCPFYKVJUETGYVGTOKPCNUHQT
U[UVGOEQPPGEVKQPU
$%JKOGU.QYÄ.GXGN1WVRWV8KDTCVKPIV[RGÄF$#OKPKOWOTCVGFQWVRWV
%%JKOGU*KIJÄ.GXGN1WVRWV8KDTCVKPIV[RGÄF$#OKPKOWOTCVGFQWVRWV
&8KUKDNG0QVKHKECVKQP#RRNKCPEGU:GPQPUVTQDGNKIJVUEQORN[YKVJ7.YKVJENGCTQTPQOKPCN
YJKVGRQN[ECTDQPCVGNGPUOQWPVGFQPCPCNWOKPWOHCEGRNCVG6JGYQTF(+4'KUGPITCXGFKP
OKPKOWOÄKPEJÄ
ÄOOÄJKIJNGVVGTUQPVJGNGPU
4CVGF.KIJV1WVRWV
CEFUGNGEVCDNGKPVJGHKGNF
/QWPVKPI9CNNOQWPVGFWPNGUUQVJGTYKUGKPFKECVGF
(QTWPKVUYKVJIWCTFUVQRTGXGPVRJ[UKECNFCOCIGNKIJVQWVRWVTCVKPIUUJCNNDG
FGVGTOKPGFYKVJIWCTFUKPRNCEG
(NCUJKPIUJCNNDGKPCVGORQTCNRCVVGTPU[PEJTQPK\GFYKVJQVJGTWPKVU
5VTQDG.GCFU(CEVQT[EQPPGEVGFVQUETGYVGTOKPCNU
/QWPVKPI(CEGRNCVG(CEVQT[HKPKUJGFYJKVG
'#NNFGXKEGUUJCNNOCVEJGZKUVKPIHKTGCNCTOU[UVGO
/CPWHCEVWTGT
#5KORNGZ)TKPPGNN.2C6[EQ+PVGTPCVKQPCNEQORCP[
$(CTCFC[
%(KTGÄ.KVG
&)COGYGNN
'0QVKHKGT
E901
ELECTRICAL
SPECIFICATIONS
ABC
SLH
P
R
O
F
E
SS
IONA L E N G NI E E R
S A M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
mitsch
DESIGN
200 s rangeline road
suite 213
carmel, indiana 46032
ph 317.573.2222
fx 317.573.2230
www.mitschdesign.com
AL
L
I
D
E
A
S
,
D
E
S
I
G
N
S
A
N
D
P
L
A
N
S
I
N
D
I
C
A
T
E
D
O
R
RE
P
R
E
S
E
N
T
E
D
B
Y
T
H
E
S
E
D
R
A
W
I
N
G
S
A
R
E
O
W
N
E
D
B
Y
,
AN
D
T
H
E
P
R
O
P
E
R
T
Y
O
F
M
I
T
S
C
H
D
E
S
I
G
N
.
C
O
N
T
R
A
C
T
O
R
S
SH
A
L
L
V
E
R
I
F
Y
A
N
D
B
E
R
E
S
P
O
N
S
I
B
L
E
F
O
R
A
L
L
DI
M
E
N
S
I
O
N
S
O
N
T
H
E
J
O
B
S
I
T
E
.
A
L
L
R
I
G
H
T
S
R
E
S
E
R
V
E
D
,
EX
C
E
P
T
F
O
R
U
S
E
S
E
X
P
R
E
S
S
L
Y
P
E
R
M
I
T
T
E
D
I
N
W
R
I
T
I
N
G
.
CHECKED BY:
DWG SCALE:
DRAWN BY:
MD PROJECT #:16014
'ZGEWVKXG&TKXG·5WKVG·+PFKCPCRQNKU+PFKCPC··YYY6'%Ä/'2EQO
M E C H A N I C A L · E L E C T R I C A L · P L U M B I N G
THE
ENGINEERING
COLLABORATIVE
AS NOTED
SG
R
O
I
E
N
T
E
R
P
R
I
S
E
S
SM
O
O
T
H
I
E
K
I
N
G
-
C
A
R
M
E
L
13
6
6
S
.
R
A
N
G
E
L
I
N
E
R
D
.
CA
R
M
E
L
,
I
N
4
6
0
3
2
AR
C
H
I
T
E
C
T
U
A
L
D
R
A
W
I
N
G
S
CO
N
S
T
R
U
C
T
I
O
N
D
O
C
U
M
E
N
T
S
04
.
1
5
.
1
6