HomeMy WebLinkAboutE001 00 ELEVTRICAL LEGEN AND ABB.pdfFEEDER TAG - SEE FEEDER SCHEDULE
CONDUIT TURNED UP
CONDUIT TURNED DOWN
ABBREVIATION DESCRIPTION:
A/AMP AMPERE
AFCI ARC FAULT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AL ALUMINUM
ANSI AMER. NATIONAL STANDARDS INSTITUTE
ASA AMERICAN STANDARDS ASSOCIATION
ASTM AMER. SOCIETY OF TESTING MATERIALS
AWG AMERICAN WIRE GAUGE
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
BL BLANK
BKR BREAKER
C CONDUIT
CB, C/B CIRCUIT BREAKER
CKT BKR -
CKT CIRCUIT
CCTV CLOSED CIRCUIT T.V.
CLG CEILING
CO CONVENIENCE OUTLET
CONN CONNECTION
CU COPPER
DB DIRECT BURIAL
DISC DISCONNECT
DN DOWN
DWG DRAWING
EA EACH
E.C.ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EH ELECTRIC HEAT
EIA ELECTRONIC INDUSTRIES ASSOC.
EMT ELECTRIC METALLIC TUBING
XP EXPLOSION PROOF
E, EM EMERGENCY
ELEC ELECTRIC
EMT ELECTRIC METALLIC TUBING
EQ/EQPM EQUIPMENT
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
EX EXISTING
F FIXTURE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FDR FEEDER
FIXT FIXTURE
FL FLOOR
FLUOR FLUORESCENT
FSS FUSED SAFETY SWITCH
FT FEET
G, GND,GRD GROUND
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HP HORSE POWER
HPF HIGH POWER FACTOR
HR HOMERUN
HTR HEATER
HVAC HEATING, VENTILATION, AIR
CONDITIONING CONTRACTOR
HV HIGH VOLTAGE
HZ HERTZ
ICEA INTERNATIONAL CABLE ENGINEERS ASSO.
IEEE INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS
IES ILLUMINATING ENGINEERING SOCIETY
IN INCH
INCAN INCANDESCENT
IR INFRA-RED
JB/JBOX JUNCTION BOX
K THOUSAND
KVA KILOVOLT-AMPERE
KW KILOWATT
KWH KILOWATT HOUR
LA LIGHTING ARRESTER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LTS LIGHTS
LTG LIGHTING
LV LOW VOLTAGE
MC METAL CLAD
M.C.MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH MANHOLE
MLO MAIN LUGS ONLY
MISC.MISCELLANEOUS
MTD MOUNTED
MTG HGT MOUNTING HEIGHT
MTR MOTOR
1.ALL ELECTRICAL WORK SHALL BE IN ACCORD WITH ALL APPLICABLE ORDINANCES, CODES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION. ALL ELECTRICAL WORK SHALL BE INSPECTED AND
APPROVED BY THE LOCAL ELECTRICAL INSPECTION AGENCY. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY FEES AND PERMITS, INCLUDING THE CERTIFICATE OF ELECTRICAL
INSPECTION.
2.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION SAFETY. ARCHITECT AND/OR ENGINEER SHALL ASSUME NO RESPONSIBILITY FOR WORKMAN'S, OR PEDESTRIAN'S SAFETY.
NOTHING IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO INSTRUCT PROCEDURES OR COMPONENTS FOR PROJECT SAFETY.
3.WHERE A CONFLICT ARISES BETWEEN PLANS, SPECIFICATIONS, DETAILS, SCHEDULES, APPLICABLE CODES OR REGULATIONS, THE MOST STRINGENT SHALL APPLY.
4.NOTHING CONTAINED IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO CONFLICT WITH ANY NATIONAL, STATE, MUNICIPAL, OR LOCAL LAWS OR REGULATIONS GOVERNING THE WORK INDICATED
OR SPECIFIED. THE ELECTRICAL CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER SHALL SATISFY ALL SUCH REQUIREMENTS.
5.THE CONTRACT DOCUMENTS ARE COMPRISED OF DRAWINGS AND SPECIFICATIONS. EACH ELECTRICAL BIDDER SHALL VISIT SITE TO DETERMINE EXISTING CONDITIONS PRIOR TO SUBMITTING BID
PROPOSAL. BIDS SHALL BE BASED ON THE COMPLETE EXAMINATION OF THE DRAWINGS, SPECIFICATIONS AND EXISTING CONDITIONS. NO CONSIDERATION WILL BE GIVEN ANY CONTRACTOR WHO FAILS TO
DO SO.
6.THE WORK UNDER THIS CONTRACT SHALL INCLUDE THE FURNISHING OF ALL NECESSARY MATERIALS, TOOLS, AND LABOR FOR A COMPLETE, AND WORKING INSTALLATION AS DEFINED BY THE PLANS AND
SPECIFICATIONS. THE ELECTRICAL CONTRACTOR SHALL WARRANT THE WORK INDICATED AND SPECIFIED FOR A PERIOD OF ONE YEAR. THE WORK SHALL FUNCTION AS INTENDED, BE COMPLETE IN ALL
DETAILS, AND SHALL INCLUDE ALL INDICATED, SPECIFIED, OR REQUIRED ACCESSORIES FOR A FUNCTIONING SYSTEM.
7.THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHT AND POWER AS REQUIRED BY THE GENERAL CONDITIONS OF THE SPECIFICATION.
8.THE ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES. ALL DEVICES PROVIDED BY OTHERS THAT REQUIRE LINE VOLTAGE ELECTRICAL POWER SHALL BE CONNECTED BY
THE ELECTRICAL CONTRACTOR. POWER, PHONE, DATA, TV, AND SIMILAR DEVICE OUTLET LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECTURAL INTERIOR LAYOUTS, THE GENERAL CONTRACTOR,
AND THE OWNER.
9.THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OWNER'S PROJECT MANAGER PRIOR TO AND FOR SCHEDULING ANY INTERRUPTION OF ANY BUILDING UTILITY.
10.THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE LOCAL UTILITIES AND ARRANGE FOR THE FOLLOWING SERVICES: ELECTRICAL POWER, CABLE TV, AND TELEPHONE SERVICE. THE ELECTRICAL
CONTRACTOR SHALL MEET WITH THE REPRESENTATIVES OF THE ELECTRICAL UTILITY & COMCAST TO CONFIRM DETAILS ON THE SERVICE AND METERING. THE ELECTRICAL CONTRACTOR SHALL PAY ALL
NECESSARY COSTS, FEES, AND PERMITS INVOLVED IN BRINGING SERVICE TO THE BUILDING.
11.THE ELECTRICAL CONTRACTOR AT THE SITE SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PERTAINING TO THE INSTALLATION OF THE ELECTRICAL SYSTEMS. WHERE A CONTRACTOR
UNCOVERS CONDITIONS NOT INDICATED ON THE PLANS OR IN THE SPECIFICATIONS, HE SHALL NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH ANY WORK. FAILURE TO NOTIFY THE ARCHITECT WILL
MAKE THE CONTRACTOR RESPONSIBLE FOR ALL COSTS AND CONSEQUENCES OF SUCH FAILURE.
12.THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE DESIGN/LAYOUT INTENT ONLY. THE ELECTRICAL CONTRACTOR SHALL DETERMINE CIRCUITING, ROUTING, WIRING ETC.., AS REQUIRED
BY THE SITE CONDITIONS, AND ALL APPLICABLE CODES.
13.ALL WIRING SHALL BE CONCEALED IN FINISHED AREAS AS SPECIFIED. WHERE PERMITTED IN THE SPECIFICATIONS, USE OF MC CABLE IN CONCEALED AREAS SHALL BE PER N.E.C., LOCAL CODES, AND
INSPECTION AGENCY APPROVAL. OTHERWISE, USE EMT CONDUIT, MINIMUM 3/4" UNLESS NOTED OR SPECIFIED OTHERWISE.
14.THE FOLLOWING CONDUCTORS SHALL BE RUN IN HEAVY WALL CONDUIT:
14.1.ALL FEEDERS RUN IN SLAB - MAY BY SCHEDULE 40 PVC.
14.2.WHERE REQUIRED BY THE N.E.C.
14.3.EXPOSED WIRING ON A ROOF - SEAL PROPERLY.
14.4.EXTERIOR, ABOVE GRADE WIRING.
15.FOLLOWING FEEDERS SHALL BE IN EMT:
15.1.BRANCH FEEDERS TO PANELS.
15.2.BRANCH RACEWAY RUN EXPOSED.
16.TRENCHING AND BACKFILL FOR UNDERGROUND CONDUITS SHALL BE BY THE ELECTRICAL CONTRACTOR.
17.UPON THE COMPLETION OF WORK THE E.C. SHALL PROVIDE ALL PANELBOARDS WITH TYPED PANEL SCHEDULES TO CLEARLY DEFINE THE EQUIPMENT SERVED.
18.UPON THE COMPLETION OF WORK THE E.C. SHALL PROVIDE ALL DISTRIBUTION EQUIPMENT WITH TYPED NAMEPLATES TO CLEARLY DEFINE THE EQUIPMENT SERVED.
19.CHANNELING OF THE FLOORS SHALL BE MINIMIZED.
20.SURFACE PANCAKE RACEWAY IS PROHIBITED.
21.REFER TO REFLECTED CEILING PLANS FOR THE COORDINATED PLACEMENT OF LIGHTS, DIFFUSERS, SPRINKLERS, AND RETURN AIR GRIDS.
22.E.C. SHALL COORDINATE ALL RECEPTACLE AND LIGHT FIXTURES LOCATIONS WITH CASEWORK AND THE OWNERS FIXTURES LAYOUT PLAN WHICH WILL BE DIMENSIONED.
23.ALL HOMERUNS WITH MORE THAN SIX (6) TOTAL CONDUCTORS SHALL BE A MINIMUM OF NO. 10 THWN WIRE UNLESS SPECIFICALLY SIZED OTHERWISE.
24.ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE BY THE ELECTRICAL CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
25.CONTRACTOR SHALL REMOVE DEMOLITION DEBRIS COMPLETELY. CONTRACTOR SHALL SCHEDULE WITH THE OWNER THE TIME, LOCATION, ELEVATOR AND HAULING ROUTE.
26.CONTRACTOR SHALL CLEAN UP ALL DEBRIS AT THE END OF EACH WORK DAY.
27.EXACT COUNTS/QUANTITIES FOR CONTRACT PURPOSES SHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR AND INCLUDED AS PART OF THE BASE BID.
28.REFER TO ARCHITECTURAL DRAWING FOR ALL WALL HEIGHTS.
29.VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH THE MECHANICAL CONTRACTOR, PRIOR TO ROUGH-IN. E.C. SHALL ALSO INCLUDE COORDINATION WITH DEVICES BY M.C., WIRING
REQUIREMENTS, INTERCONNECTIONS, AND TERMINATIONS AND PROVIDE AS REQUIRED.
30.ALL CONDUITS RUN IN EXPOSED AREAS SHALL BE MOUNTED TIGHT TO THE UNDERSIDE OF THE STRUCTURAL STEEL. THIS APPLIES FOR ALL BRANCH CIRCUIT AND FEEDER CONDUITS.
31.ALL HOLES AND OPENINGS CREATED TO EXTEND THE ELECTRICAL SYSTEMS THROUGH FLOORS AND FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED.
32.DURING THE BIDDING PROCESS, ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (GENERAL, HVAC, AND PLUMBING). ALL ITEMS REQUIRING POWER
INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL CONTRACTORS WORK. THIS WORK SHALL BE INSTALLED AS PER
NEC AT NO ADDITIONAL COST TO THE OWNER
33.WHERE CONDUIT SIZES HAVE BEEN OMITTED, THE CONTRACTOR SHALL INSTALL THE CORRECT SIZES REQUIRED BY THE N.E.C. AS DETERMINED BY THE NUMBER OF WIRES TO BE INSTALLED. WHERE THE
NUMBER AND OR SIZES OF HAVE BEEN OMITTED, THE CONTRACTOR SHALL INSTALL THE REQUIRED NUMBER AND OR SIZES AS DETERMINED BY THE EQUIPMENT REQUIREMENTS OR FROM ADJACENT
SECTIONS AND CIRCUIT NUMBERS.
34.WIRE SIZE FOR BRANCH CIRCUITS SHALL BE ADJUSTED TO COMPENSATE FOR VOLTAGE DROP CALCULATIONS AS REQUIRED BY NEC. IF CIRCUIT RUN EXCEEDS 100FT. IN WIRE LENGTH, NEXT WIRE SIZE (#10)
SHALL BE USED.
35.STARTERS, COMBINATION STARTERS, CONTRACTORS, ETC.. FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. ALL POWER WIRING AND CONDUIT TO EQUIPMENT
TERMINALS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. POWER TO MECHANICAL EQUIPMENT SHALL BE TURNED ON ONLY BY THE MECHANICAL CONTRACTOR. MECHANICAL NAME PLATE DATA
SHALL NOT BE COVERED BY ELECTRICAL DEVICES.
36.THE ELECTRICAL CONTRACTOR SHALL FURNISH SUBMITTALS IN ACCORD WITH THE SPECIFICATIONS. ALL SUBMITTALS SHALL BE REVIEWED AND STAMPED BY THE ENGINEER PRIOR TO INSTALLATION.
37.THE ELECTRICAL CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS FOR THE ENTIRE PROJECT AS DEFINED IN THE SPECIFICATIONS
38.THIS CONTRACTOR SHALL VISIT THE SITE AND FULLY INFORM HIMSELF OF ALL THE EXISTING CONDITIONS, WHICH IN ANY WAY WILL AFFECT THE EXECUTION OF HIS WORK AND THE REQUIREMENTS OF THIS
CONTRACT AS SHOWN OR REASONABLY INFERRED ON THE DRAWINGS AND PRODUCT SPECIFICATIONS.
POWER SYMBOLS ELECTRICAL ABBREVIATIONS ELECTRICAL NOTES
TOP OF PANELBOARDS,
LIGHT FIXTURES
PENDANT MOUNTED
FIRE ALARM HORNS/STROBES
TOP OF DISCONNECT
SWITCHES, STARTERS,
AND CONTACTORS
CABINETS
6'-6"
6'-0"
4'-0"
FINISHED FLOOR
2'-0"
3'-6"
1'-6"
0'-0"
TOP OF ACTUATING DEVICE ON
LIGHT SWITCHES, FIRE ALARM
PULL STATIONS, MANUAL MOTOR
STARTERS OR PUSH BUTTON
CTR COUNTER TOP RECEPTACLE
MOUNT CENTER OF RECEPTACLE
6" ABOVE COUNTER TOP OR
BACKSPLASH
MOUNTING HEIGHT SCHEDULE
GENERAL SYMBOLS
WALL MOUNTED
HANDICAPPED TELEPHONE
OUTLETS
ELECTRICAL RECEPTACLES IN
MECHANICAL/ELECTRICAL
ROOMS & ELEVATOR MACHINE
ROOMS
ELECTRICAL RECEPTACLES
(U.N.O.) COMMUNICATIONS/DATA
OUTLETS (U.N.O.)
EMERGENCY DUPLEX RECEPTACLE
SINGLE EXIT SIGN CEILING/WALL MOUNT FACE
DIRECTION AS SHOWN BY ARROWS. PROVIDE
DIE-CAST ALUMINUM WITH RED LETTERING LED EXIT
SIGN, LITHONIA LQC SERIES OR APPROVED EQUAL.
COMBINATION MOTOR STARTER
FURNISHED BY MC INSTALLED BY EC
MOTOR STARTER
FURNISHED BY MC INSTALLED BY EC
EQUIPMENT CONTROL PANEL
FINAL CONNECTION BY EC
2x2 RECESSED FLUORESCENT FIXTURE
2x4 RECESSED FLUORESCENT FIXTURE
4' RECESSED FLUORESCENT FIXTURE
STRIP FIXTURE.
DOWNLIGHT FIXTURE
WALL WASHER FIXTURE
WALL MOUNTED FIXTURE
TRACK LIGHT FIXTURE.
DUPLEX RECEPTACLE
SINGLE POLE SWITCH
JUNCTION BOX
SIMPLEX RECEPTACLE
QUAD RECEPTACLE
SPECIAL RECEPTACLE NEMA TYPE AS SHOWN
WALL FLR CLG
NOMENCLATURE:
+6" ABOVE COUNTER
+48 MOUNTED 48" A.F.F.
CR OVERHEAD CORD REEL
GFI GROUND FAULT INTERRUPTER
IG ISOLATED GROUND
TR TAMPER RESISTANT
WP WEATHER PROOF
#NUMERICAL NUMBER INDICATES THE NUMBER
OF DEVICES
EMERGENCY QUAD RECEPTACLE
FURNITURE FEED
UNFUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
CIRCUIT BREAKER
RELAY
120/208V ELECTRIC PANEL
METER
GROUNDING ROD
HANDHOLE / MANHOLE
NOMENCLATURE:
'P'POWER
'T' TELECOM
DEVICE SYMBOL
POLE MOUNTED ROUND SITE LIGHTING FIXTURE
NUMBER OF HEADS AS SHOWN ON PLANS
POLE MOUNTED SQUARE SITE LIGHTING FIXTURE
NUMBER OF HEADS AS SHOWN ON PLANS
BOLLARD
INTERCOM SLAVE
INTERCOM MASTER
INTERCOM
POWER DEVICE KEY
INTERCOM SUBSTATION
MICROPHONE
PUSH BUTTON
PUSH BUTTON - 3 POSITION
SPECIAL RECEPTACLE NEMA TYPE AS SHOWN
PENDANT LIGHT
VOICE/DATA OUTLET. PROVIDE 4" SQUARE BOX WITH SINGLE
GANG DEVICE BRACKET AND 1" EMT CONDUIT TO ABOVE
NEAREST ACCESSIBLE CEILING - PROVIDE PULL STRING IN
ALL CONDUIT
VOICE OUTLET. PROVIDE 4" SQUARE BOX WITH SINGLE
GANG DEVICE BRACKET AND 1" EMT CONDUIT TO ABOVE
NEAREST ACCESSIBLE CEILING - PROVIDE PULL STRING IN
ALL CONDUIT
DATA OUTLET. PROVIDE 4" SQUARE BOX WITH SINGLE GANG
DEVICE BRACKET AND 1" EMT CONDUIT TO ABOVE NEAREST
ACCESSIBLE CEILING - PROVIDE PULL STRING IN ALL
CONDUIT
8' RECESSED FLUORESCENT FIXTURE
2x4 PENDANT MOUNTED FIXTURE
4' PENDANT MOUNTED FIXTURE
2x4 SURFACE MOUNTED FIXTURE
4' SURFACE MOUNTED FIXTURE
LIGHTING CONTROL STATION
DUAL TECHNOLOGY OCCUPANCY SENSOR
CEILING/WALL MOUNTED
SWITCH BYPASS DEVICE
PHOTO CELL
SPLIT WIRED RECEPTACLE
JJ
TMHPHH
R
AUXILIARY SOUND SYSTEM SPEAKER
PAGING SPEAKER
VOLUME CONTROL
XX
TTB TELEPHONE TERMINAL BOARD, 4' x 8' x 3/4"
MARINE GRADE PLYWOOD
LIGHTING SYMBOLS
NOMENCLATURE - X=:
a,b,c DESIGNATES LIGHT FIXTURE CONTROLLED
3 THREE WAY
4 FOUR WAY
D DIMMER
DT DUAL TECHNOLOGY OCCUPANCY SENSOR
E EMERGENCY
F FAN
K KEY OPERATED
LV-x LOW VOLTAGE (x DENOTES SWITCH
NUMBER, REFER TO SCHEDULE)
MC MOMENTARY CONTACT
M MANUAL MOTOR STARTER
P PASSIVE INFRARED OCCUPANCY SENSOR
T TIME
W WET LOCATION
OS OCCUPANCY SENSOR
OS2 OCCUPANCY SENSOR WITH 2 SWITCHES
LINE VOLTAGE OCCUPANCY SENSOR
CEILING/WALL MOUNTED
COMMUNICATION SYMBOLS
WIRING SYMBOLS
GND GROUND CABLE
UNDER FLOOR OR UNDER GROUND CONDUIT
AND WIRING
SURFACE CONDUIT AND WIRING
WIRING HOMERUN, INDICATES BRANCH CIRCUIT
CONDUIT AND WIRE TO PANELBOARD
SURFACE RACWAY WITH 20 AMP DUPLEX
OUTLETS 120 V SPACED AS INDICATED
CONCEALED CONDUIT AND WIRING
INDICATES PANEL NAME INDICATES CIRCUIT
NUMBER
INTERCOM / PAGING SYMBOLS
ACCESS CONTROL/SECURITY SYMBOLS
WALL
MOUNTED
CEILING
MOUNTED
SP
IM
IS
IC
I
M
SP SP
V
LC
SBD
PC
M
CP
CB
X
XXX
POWER PACKPP
B1-3
XX-XX
ABBREVIATION DESCRIPTION:
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NF NON-FUSED SAFETY SWITCH
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN THIS CONTRACT
NM NON-METTALIC
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OEM ORIGINAL EQUIPMENT MANUFACTURER
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
P POLE
PBOX PULL BOX
PC PHOTOCELL
P.C.PLUMBING CONTRACTOR
PH / Ø PHASE
PNL PANEL
POS POSITION
PR PRESENT LIGHTING FIXTURE,
SWITCH, DEVICE, ETC., TO REMAIN
PRI PRIMARY
PRN PRESENT LIGHTING FIXTURE,
SWITCH, DEVICE, ETC., TO BE
REMOVED AND REPLACED WITH
NEW
PRR PRESENT LIGHTING FIXTURE,
SWITCH, DEVICE, ETC., SHOWN AT
NEW LOCATION
PRX PRESENT LIGHTING FIXTURE,
SWITCH, DEVICE, ETC., TO BE
REMOVED AND OUTLET BOX
EXTENSION INSTALLED FOR
SURFACE CONDUIT OR SMR AND
WIRE EXTENSION TO NEW OUTLET
SHOWN. REINSTALL PRESENT
LIGHTING FIXTURE, SWITCH, DEVICE,
ETC.
PWR POWER
REC / RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RMC RIGID GALVANIZED METAL CONDUIT
RPC REMOVE PRESENT FIXTURE,
SWITCH, DEVICE, ETC., AND CAP
OUTLET.
RPP REMOVE PRESENT FIXTURE,
SWITCH, DEVICE, ETC., PATCH THE
PLASTER IF IN PLASTER: CAP IF IN
METAL OR WOOD.
RPR REMOVE PRESENT FIXTURE,
SWITCH, DEVICE, ETC., TO BE
REMOVED AND RELOCATED.
RPX REMOVE PRESENT FIXTURE,
SWITCH, DEVICE, ETC., WIRE AND
ALL RELATED EXPOSED RACEWAY
INSOFAR AS IS POSSIBLE. ALL
DAMAGED SURFACES TO BE
REPAIRED.
RT RAIN TIGHT
SCHED SCHEDULE
SEC SECONDARY
SIG SIGNAL
SM SURFACE MOUNTED
SMR SURFACE MOUNTED RACEWAY
SP SPARE
SS SAFETY SWITCH
SW SWITCH
SWBD SWITCHBOARD
TEL / TELE TELEPHONE
TL TWIST LOCK
TP TAMPER PROOF
TX / XFMR TRANSFORMER
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITERS' LABORATORIES, INC
UNO UNLESS NOTED OTHERWISE
V VOLTAGE
VT VAPOR TIGHT
W WIRE; WATT
W/WITH
W/O WITHOUT
WP WEATHER PROOF
WT WATER TIGHT
REFERENCE LIGHTING
FIXTURE SCHEDULE FOR
MOUNTING REQUIREMENTS
6'-8" AFF OR 6" BELOW
FINISHED CEILING,
WHICHEVER IS LOWER
(BOTTOM OF LENS; MIN.)
30 3
NF 3R
DISCONNECT SWITCH KEY
SIZE NO. OF POLES
NEMA TYPE
FUSED # OR NF
LIGHTING FIXTURE KEY
Xa
XX-XX
INDICATES CIRCUIT NUMBER
INDICATES SWITCH CONTROL (a)
INDICATES FIXTURE TYPE SEE
SCHEDULE FOR DESCRIPTION
INDICATES PANEL NAME
SHADING
INDICATES
FIXTURE ON
EMER. CIRCUIT
INTERCOM SPEAKERS
OS OS
OS OS
X
LN
VOICE/DATA FLOOR BOX - PROVIDE PULL STRING AND
CONDUIT TO NEAREST FULL HEIGHT WALL AND ABOVE
ACCESSIBLE CEILING.
LN
DAYLIGHT SENSORD
SECURITY PANELSEC
DOOR CONTACTDC
PANIC/HOLD-UP BUTTON. MOUNT UNDER FACE OF COUNTERPB
VIDEO CAMERA
FW NOMENCLATURE:
FW FIXED WALL MOUNTED VIDEO CAMERA
FC FIXED CEILING MOUNTED
PTZ-C PAN, TILT, ZOOM CEILING MTD
PTZ-W PAN, TILT, ZOOM WALL MTD
KEY PADKP
MOTION SENSORMS
LOCAL ALARMLA
CCX
INDICATES CONTROL ZONE
(REFER TO LD DRAWINGS)
X X
NOMENCLATURE:
B INTERIOR BEAM SPEAKER
C INTERIOR CEILING SPEARK
O OUTDOOR WET RATED
A.ALL WIRING AND PIPING WILL BE SURFACE MOUNTED INSIDE WALK-IN
COOLERS AND FREEZERS PENETRATION MUST BE KEPT TO A MINIMUM.
ALL CONDUIT PENETRATING WALK-IN UNITS MUST BE SEALED INSIDE
THE RACEWAY AS WELL AS OUTSIDE.
B.ALL OUTLET COVERS MUST BE TAGGED SHOWING PANEL AND CIRCUIT
NUMBERS ALONG WITH THE EQUIPMENT NAME THE RECEPTACLE IS
FEEDING.
C.ALL OUTLETS CONNECTED TO ISOLATED GROUND PANELS MUST BE
ORANGE IG RECEPTACLES.
GENERAL NOTES
A.GENERALLY, RECEPTACLES SHALL BE MOUNTED AT HEIGHTS AS DESCRIBED BELOW UNLESS SPECIFIC MOUNTING
HEIGHTS ARE INDICATED FOR THE RECEPTACLE EITHER IN THE EQUIPMENT SCHEDULES OR ON PLANS.
A.A.RECEPTACLES SHOWN WITHOUT NO OTHER MARKINGS SHALL BE 18" AFF.
A.B.RECEPTACLES SHOWN WITH A + OR INDICATED TO BE ABOVE COUNTER SHALL BE 48" AFF.
B.ON TILE WALLS, IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE ALL RECEPTACLE
ROUGH-IN LOCATIONS WITH THE TILE INSTALLER SUCH THAT ALL RECEPTACLES LAND ON GROUT LINES. THE MOUNTING
HEIGHTS GIVEN ABOVE MAY NEED TO BE ADJUSTED BY +/- 6" BASED ON THE TILE SIZE. RECEPTACLES SHALL NOT BE
MOUNTED ON FINISH TRANSITIONS, I.E. WHERE TILE TERMINATES ON DRYWALL. IN NO INSTANCE SHALL A RECEPTACLE BE
MOUNTED BELOW 42" AFF WHEN SHOWN TO BE MOUNTED ABOVE A COUNTER AS 42" IS THE BACKPLASH HEIGHT OF A
STANDARD STAINLESS STEEL TABLE.
C.ON TILE WALLS, ALL RECEPTACLES SHALL BE MOUNTED HORIZONTALLY. OTHER DEVICES SHALL BE MOUNTED
VERTICALLY.
D.AT THE CUSTOMER SERVICE COUNTER, ALL RECEPATCLES SHALL BE MOUNTED AT 17" AFF BELOW THE COUNTER.
COORDINATE EXACT DIMENSIONS WITH THE MILLWORK SHOP DRAWINGS.
E.ALL RECEPTACLES SHOWN MOUNTED ON REFRIGERATED CASES SHALL BE MOUNTED HORIZONTALLY IN THE EQUIPMENT
KICKPLATE.
F.ALL RECEPTACLES WITH A WP NOTATION SHALL BE WEATHERPROOF, WHILE IN USE. DEVICES SHALL HAVE A MINIMUM
INGRESS PROTECTION RATING OF IP25. MOUNT RECEPTACLES IN LOW CAFE EXTERIOR WALL SUCH THAT THE IN-USE
COVER IS OPERABLE AND NOT OBSTRUCTED BY THE STONE CAP. COORDINATE MOUNTING HEIGHT WITH MASONRY
CONTRACTOR.
G.NO ADDITIONAL COST TO ADJUST MOUNTING HEIGHTS OR RELOCATE RECEPTACLES WILL BE PAID TO THE EC IF THE EC
DID NO COORDINATE WITH THE TILE INSTALLER OR THE EQUIPMENT CUT SHEETS MADE AVAILABLE BY THE OWNER.
RECEPTACLE MOUNTING NOTES
TV OUTLET. PROVIDE 4" SQUARE BOX WITH SINGLE GANG
DEVICE BRACKET AND 1" EMT CONDUIT TO ABOVE NEAREST
ACCESSIBLE CEILING - PROVIDE PULL STRING IN ALL
CONDUIT
TV
XX
ELECTRICAL LEGEND AND ABBREV.
E001
AS NOTED
SAS
SAS
.
.
.
.
.
REV.
NO.
SPCR
NO.
PROJECT
LOCATION
FILE NAME LAYERS
DATE
SCALE
SHEET NO.
DWG. TITLE
OWNER
USERNAME
PROJECT NO.
PLANNER
KICK OFF MEETING
ISSUED FOR 90%
ISSUED FOR PERMIT
FINAL APPROVED PLAN
RECORD DRAWINGS
DRAWN BY