HomeMy WebLinkAboutE501 00 ELECTRICAL POWER RISER D.pdfXX
ELECTRICAL POWER RISER DIAGRAM
E501
AS NOTED
CSD
SAS
.
.
.
.
.
UTILITY COMPANY
TRANSFORMER
MC.T.
CABINET
GIG N
PANEL
S
208/120V
3Ø, 4W
225A
M.L.O.
STORE EXTERIOR
INTERSYSTEM
BONDING
BAR
SCALE:
POWER RISER DIAGRAM
NO SCALE1
PANEL
208/120V
3Ø, 4W
800A
M.C.B.
DP
PANEL
C
208/120V
3Ø, 4W
100A
M.L.O.
PANEL
H
208/120V
3Ø, 4W
400A
M.L.O.
PANEL
FUEL
208/120V
3Ø, 4W
225A
M.L.O.
PANEL
A
208/120V
3Ø, 4W
225A
M.L.O.
TRANSFORMER, CT'S, AND METER BY UTILITY COMPANY.
ELECTRICAL CONTRACTOR SHALL PREPARE SITE PER UTILITY
COMPANY REQUIREMENTS. E.C. SHALL PROVIDE METER SOCKET,
TRANSFORMER PAD, AND ALL TRENCHING PER UTILITY COMPANY
REQUIREMENTS.
SECONDARY CONDUCTOR LUGS FOR TRANSFORMER SHALL BE
FURNISHED BY ELECTRICAL CONTRACTOR. INSTALLATION AND
WIRE TERMINATIONS ARE BY UTILITY COMPANY.
PROVIDE (2) SETS OF (4) #600 KCMIL IN 4" CONDUIT AND (1) SPARE
4" CONDUIT.
EQUIPMENT IS TO BE SERVICE ENTRANCE RATED.
ELECTRICAL POWERWALL FURNISHED BY GIANT EAGLE AND
INSTALLED BY ELECTRICAL CONTRACTOR.
BRANCH CIRCUIT CONTACTORS ARE TO BE PROVIDED IN
POWERWALL CONTACTOR ENCLOSURE. REFER TO CONTACTOR
SCHEDULE FOR AMP RATING AND POLE INFORMATION.
CONTACTORS SHALL BE PRE-WIRED BY POWERWALL
MANUFACTURER.
MAIN GROUNDING ELECTRODE CONDUCTOR AND BONDING
CONDUCTOR TO BE #3/0 AWG. REFER TO DETAIL 8 ON DRAWING
E-702.
PROVIDE (4) #1 AND (2) #8 GND IN 1-1/2" CONDUIT
EC HAS THE OPTION TO UTILIZE ALUMINUM CONDUCTORS FOR THE
SERVICE ENTRANCE WIRING AS OPPOSED TO COPPER. ALUMINUM
CONDUCTORS SHALL BE COMPACTED STRANDED STABILOY BY
ALCAN OR APPROVED EQUAL. IF ALUMINUM IS USED, EC IS
RESPONSIBLE FOR PROVIDING FEEDER OF EQUAL OR GREATER
AMPACITY THAN THE COPPER FEEDER SIZE INDICATED. EC SHALL
RESIZE CONDUIT APPROPRIATELY AND VERIFY TERMINATION
COMPATIBILITY AT ALL ASSOCIATED EQUIPMENT. TERMINATIONS
SHALL BE LISTED FOR USE WITH ALUMINUM CONDUCTORS.
KEY NOTES
1
2
3
4
5
6
7
21
1
1
7
4 5 6
7
3 3 930" MIN. (TYP)
PANEL
R
ISO. GND.
208/120V
3Ø, 4W
100A
M.L.O.
8
8
9
GETGO NEC LOAD CALCULATION
NON-CONTINUOUS LOADS LOAD (KVA)D.F.NEC LOAD NOTES
HVAC 63360 1 63360
KITCHEN EQUIPMENT 132612 0.65 86197.8
REFRIGERATION 25000 1 25000
MISC. EQUIPMENT 50430 1 50430
FUEL EQUIPMENT 32890 1 32890
RECEPTACLE LOAD 19000 NEC 19000
CONTINUOUS LOADS LOAD (KVA)D.F.NEC LOAD NOTES
LIGHTING & SIGNAGE 22830 1.25 28537.5 CONNECTED LOAD
305415.3 TOTAL LOAD (KW)
0.75 229061.5 HISTORICAL GETGO DEMAND (0.75)
636.3 LOAD (A) @ 208V 3PH.
REV.
NO.
SPCR
NO.
PROJECT
LOCATION
FILE NAME LAYERS
DATE
SCALE
SHEET NO.
DWG. TITLE
OWNER
USERNAME
PROJECT NO.
PLANNER
KICK OFF MEETING
ISSUED FOR 90%
ISSUED FOR PERMIT
FINAL APPROVED PLAN
RECORD DRAWINGS
DRAWN BY
CHECKED BY
GETGO #3557
4927 EAST 146TH STREET
261 KAPPA DRIVE,
DATE REVISIONS BY
ISSUED FOR REDLINE REVIEW
GIANT EAGLE, INC.
750 HOLIDAY DRIVE, SUITE 200
PITTSBURGH, PA 15220
PHONE: 412-921-4300
FAX: 412-921-4313
PITTSBURGH, PA 15238
2016003.00
01-20-15
CARMEL, IN 46062
02-26-16
02-26-16