Loading...
HomeMy WebLinkAboutE501 00 ELECTRICAL POWER RISER D.pdfXX ELECTRICAL POWER RISER DIAGRAM E501 AS NOTED CSD SAS . . . . . UTILITY COMPANY TRANSFORMER MC.T. CABINET GIG N PANEL S 208/120V 3Ø, 4W 225A M.L.O. STORE EXTERIOR INTERSYSTEM BONDING BAR SCALE: POWER RISER DIAGRAM NO SCALE1 PANEL 208/120V 3Ø, 4W 800A M.C.B. DP PANEL C 208/120V 3Ø, 4W 100A M.L.O. PANEL H 208/120V 3Ø, 4W 400A M.L.O. PANEL FUEL 208/120V 3Ø, 4W 225A M.L.O. PANEL A 208/120V 3Ø, 4W 225A M.L.O. TRANSFORMER, CT'S, AND METER BY UTILITY COMPANY. ELECTRICAL CONTRACTOR SHALL PREPARE SITE PER UTILITY COMPANY REQUIREMENTS. E.C. SHALL PROVIDE METER SOCKET, TRANSFORMER PAD, AND ALL TRENCHING PER UTILITY COMPANY REQUIREMENTS. SECONDARY CONDUCTOR LUGS FOR TRANSFORMER SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR. INSTALLATION AND WIRE TERMINATIONS ARE BY UTILITY COMPANY. PROVIDE (2) SETS OF (4) #600 KCMIL IN 4" CONDUIT AND (1) SPARE 4" CONDUIT. EQUIPMENT IS TO BE SERVICE ENTRANCE RATED. ELECTRICAL POWERWALL FURNISHED BY GIANT EAGLE AND INSTALLED BY ELECTRICAL CONTRACTOR. BRANCH CIRCUIT CONTACTORS ARE TO BE PROVIDED IN POWERWALL CONTACTOR ENCLOSURE. REFER TO CONTACTOR SCHEDULE FOR AMP RATING AND POLE INFORMATION. CONTACTORS SHALL BE PRE-WIRED BY POWERWALL MANUFACTURER. MAIN GROUNDING ELECTRODE CONDUCTOR AND BONDING CONDUCTOR TO BE #3/0 AWG. REFER TO DETAIL 8 ON DRAWING E-702. PROVIDE (4) #1 AND (2) #8 GND IN 1-1/2" CONDUIT EC HAS THE OPTION TO UTILIZE ALUMINUM CONDUCTORS FOR THE SERVICE ENTRANCE WIRING AS OPPOSED TO COPPER. ALUMINUM CONDUCTORS SHALL BE COMPACTED STRANDED STABILOY BY ALCAN OR APPROVED EQUAL. IF ALUMINUM IS USED, EC IS RESPONSIBLE FOR PROVIDING FEEDER OF EQUAL OR GREATER AMPACITY THAN THE COPPER FEEDER SIZE INDICATED. EC SHALL RESIZE CONDUIT APPROPRIATELY AND VERIFY TERMINATION COMPATIBILITY AT ALL ASSOCIATED EQUIPMENT. TERMINATIONS SHALL BE LISTED FOR USE WITH ALUMINUM CONDUCTORS. KEY NOTES 1 2 3 4 5 6 7 21 1 1 7 4 5 6 7 3 3 930" MIN. (TYP) PANEL R ISO. GND. 208/120V 3Ø, 4W 100A M.L.O. 8 8 9 GETGO NEC LOAD CALCULATION NON-CONTINUOUS LOADS LOAD (KVA)D.F.NEC LOAD NOTES HVAC 63360 1 63360 KITCHEN EQUIPMENT 132612 0.65 86197.8 REFRIGERATION 25000 1 25000 MISC. EQUIPMENT 50430 1 50430 FUEL EQUIPMENT 32890 1 32890 RECEPTACLE LOAD 19000 NEC 19000 CONTINUOUS LOADS LOAD (KVA)D.F.NEC LOAD NOTES LIGHTING & SIGNAGE 22830 1.25 28537.5 CONNECTED LOAD 305415.3 TOTAL LOAD (KW) 0.75 229061.5 HISTORICAL GETGO DEMAND (0.75) 636.3 LOAD (A) @ 208V 3PH. REV. NO. SPCR NO. PROJECT LOCATION FILE NAME LAYERS DATE SCALE SHEET NO. DWG. TITLE OWNER USERNAME PROJECT NO. PLANNER KICK OFF MEETING ISSUED FOR 90% ISSUED FOR PERMIT FINAL APPROVED PLAN RECORD DRAWINGS DRAWN BY CHECKED BY GETGO #3557 4927 EAST 146TH STREET 261 KAPPA DRIVE, DATE REVISIONS BY ISSUED FOR REDLINE REVIEW GIANT EAGLE, INC. 750 HOLIDAY DRIVE, SUITE 200 PITTSBURGH, PA 15220 PHONE: 412-921-4300 FAX: 412-921-4313 PITTSBURGH, PA 15238 2016003.00 01-20-15 CARMEL, IN 46062 02-26-16 02-26-16