HomeMy WebLinkAboutE701 00 ELECTRICAL DETAILS.pdfCONTRACTOR MUST RECONNECT BONDING JUMBER (REMOVED FOR SHIPMENT) TO THE LUGS PROVIDED CONTRACTOR MUST CONNECT EQUIPMENT GROUNDS TO THE EQUIPMENT GROUND BAR 1.THE SQUARE D IPaCS ELECTRICAL DISTRIBUTION AND CONTROL PANEL IS INSTALLED BY THE ELECTRICAL CONTRACTOR AND FURNISHED BY THE OWNER OR AS SPECIFIED. ·THIS CONTROL PANEL INCLUDES ALL SQUARE D PANELBOARDS, BREAKERS, LIGHTING CONTROLS, PILOT LIGHTS, SWITCHES, TERMINAL STRIPS, AND POWER CONDITIONING DEVICES WHICH ARE PREINSTALLED AND INTERNALLY PREWIRED. ·THE ENCLOSURE MATERIAL IS 1/8" ALUMINUM. ·THE ENTIRE BOTTOM OF CABINET IS OPEN EXCEPT FOR A 1" FLANGE ON EACH SECTION. ·THE ENTIRE TOP OF CABINET IS SOLID. HOLES CAN BE KNOCKED OUT FOR CONDUIT ENTRY EVERYWHERE EXCEPT WHERE CABINETS JOIN TOGETHER. 2.THE MAIN DISTRIBUTION PANEL, METER CABINET, AND PULL SECTION EQUIPMENT LOCATED OUTSIDE THE BUILDING IS NOT A PART OF THE SQUARE D IPaCS SYSTEM IF APPLICABLE. 3.THE SQUARE D IPaCS SYSTEM IS UL LISTED AS A COMPLETE ASSEMBLY. THE STAND ALONE FAULT CURRENT RATING OF THE SYSTEM IS 10,000 AIC. SERIES RATINGS UP TO 65,000 AIC ARE AVAILABLE WITH REMOTE SQUARE D MAIN. 4.QUESTIONS REGARDING THE OPERATIONS OR INSTALLATION OF THE SQUARE D IPaCS SYSTEM SHOULD BE DIRECTED TO THE SQUARE D IPaCS ELECTRICAL CONTROLS DIVISION - TECHNICAL SERVICE DEPARTMENT AT 1-800-868-9662. NOTES: SECTION #1 42" TYPICAL UNDERGROUND CONDUIT ENTRY LOCATIONS SECTION #2 SECTION #3 42"44" 128" 7-1/2" 9-1/2" 10-7/32" 1" FLANGE AROUND THE PERIMETER OF EACH SECTION. (CONDUITS SHOWN ARE TYPICAL. ACTUAL REQUIREMENTS MAY VARY) NEAREST WALL SEAL BOTH PENETRATIONS PLASTIC BUSHING TO PROTECT EMS WIRING 1/2" EMT RUN UP TO 1'-0" BELOW ROOF DECK PROPERLY SECURE TO WALL 4" X 4" JUNCTION BOX COOLER / FREEZER PANEL EVAPORATOR AIR FLOW 1/2" SCHED 40 PVC INTO KNOCK-OUT ON COIL SEAL BOTH PENETRATIONS ROOF DECK COOLER / FREEZER PANEL 4" X 4" JUNCTION BOX 1/2" EMT RUN UP TO 1'-0" BELOW ROOF DECK PROPERLY SECURE TO WALL AIR FLOW EVAPORATOR TEMP SENSOR (FURNISHED BY R.C AND INSTALLED BY E.C.) ROUTED OUTSIDE OF EVAPORATOR AND DOUBLE TIE-WRAPPED TO THE INSIDE OF THE FAN GUARD TO INSURE UNOBSTRUCTED FAN OPERATION. MAKE NO PENETRATIONS OF THE DRAIN PAN BELOW EVAPORATOR NOTE: ALL WORK BY ELECTRICAL CONTRACTOR, EXCEPT AS NOTED COOLER / FREEZER PANEL NEAREST WALL AIR FLOW COOLER / FREEZER PANEL TEMP SENSOR (FURNISHED BY R.C AND INSTALLED BY E.C. CON) PROTRUDING 75% GLUE TO CONDUIT AND COMPLETELY SEAL WITH SILICONE SEALANT. 1 / 2" SCHED 40 PVC LOCATED HALFWAY BETWEEN COOLER WALL AND REAR OF EVAPORATED AND CENTERED ALONG THE WIDTH OF THE EVAPORATOR CEILING 1'-0" FINISHED FLOOR QUAD RECEPTACLE MOUNTED IN CENTER OF DATA CABINET, COORDINATE WITH FLOOR PLAN D A T A C A B I N E T WIREMOLD SHOULD EXTEND 4" BELOW THE TOP OF THE DATA CABINET BACK OF DATA CABINET WILL REST AGAINST THE FRONT FACE OF THE WIREMOLD 3-CHANNEL, 5500 SERIES RACEWAY FROM WIREMOLD CEILING SHALL BE MODIFIED TO ALLOW FOR WIREMOLD CHASE 4" 4" MANAGER'S OFFICE FUSE SIZED PER TRANSFORMER 2-POLE, NORMALLY OPEN, MOMENTARY CONTACT PUSHBOTTON FOR CLEANING REQUEST ACTIVATION (TYP) WOMEN'S RESTROOM 1-POLE, NORMALLY CLOSED, MOMENTARY CONTACT PUSHBOTTON FOR CLEANING REQUEST RESET (TYP) MEN'S RESTROOM NORMALLY OPEN CONTACT CONTROLLED BY CORRESPONDING RELAY (TYP) RM RM RW RW 24V 120V L1 L2 SIZE CONTROL TRANSFORMER TO FEED LOADS INDICATED. VENTED, SURFACE MOUNTED ENCLOSURE WITH INDICATOR LIGHT, HORN, TRANSFORMER, AND FUSES 24V ALARM HORN 24V RED INDICATOR LIGHT (TYP) CUSTOMER SERVICE COUNTER FLUSH MOUNTED ENCLOSURE WITH INDICATOR LIGHT. FLUSH MOUNTED CONTROL STATION IN RESTROOM WITH CLEANING REQUEST AND RESET PUSHBUTTONS, INDICATOR LIGHT, CONTACTOR, AND RELAY 24V CONTROL RELAY (TYP) STUB CONDUIT ABOVE ACOUSTICAL TILE CEILING FINISHED CEILING TYPICAL 1" EMPTY CONDUIT W/ FISHWIRE TYPICAL COMP/TELEPHONE OUTLET - 4" SQUARE BOX WITH 1 GANG PLASTER RING & COVER FINISHED FLOOR 1'-6" CL RIGID CONDUIT CONCEALED IN WALL, WIRING PER EQUIPMENT SCHEDULE SURFACE MOUNTED DISCONNECT SWITCH PER EQUIPMENT SCHEDULE RIGID CONDUIT CONCEALED IN WALL, WIRING PER EQUIPMENT SCHEDULE 54 " A F F FLUSH JUNCTION BOX WITH WHIP CONNECTION COVER PLATE SECURE CONDUIT WITHIN 12" OF BOX IF WHIP EXCEEDS 3" IN LENGTH LIQUIDTIGHT FLEXIBLE NON-METALLIC CONDUIT CONNECTION. LENGTH SHALL NOT EXCEED 6'-0". MINIMIZE LENGTH WHILE STILL ALLOWING FOR VIBRATION OF EQUIPMENT L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 S1 S2 S3 S4 S5 S6 SCEEN 1 22" X 30" 2 X 4 P A N D U I T X 3 0 " 2" X 4 " X 2 4 " 2" X 4 " X 3 7 " NQ 0 D 4 4 2 L 2 2 5 C U NQ 0 D 4 4 2 L 2 2 5 C U PANEL C PANEL S SD M S 4 0 3 P SD M S 4 0 3 P SD M S 4 0 3 P HCR548612U PANEL FUEL (BF) 2" X 4 " X 5 2 " 2" X 4 " X 3 5 " 2 X 4 P A N D U I T X 3 0 " TA250 USE COOPER CONDUCTORS ONLY PK 2 3 G T A ( G B C ) PK 2 3 G T A ( G B C ) PANEL A PANEL H1 PANEL H2PANEL DP PK T 3 2 D G T A USE COOPER CONDUCTORS ONLY SCALE: POWERWALL ELEVATION NO SCALE1 RW RM L L L L H 7'-0" 18" 2 X 4 P A N D U I T X 3 0 " PK23GTA TA250 USE COOPER CONDUCTORS ONLY NQ 0 D 4 4 2 L 2 2 5 C U NQ 0 D 4 4 2 L 2 2 5 C U NQ 0 D 4 4 2 L 2 2 5 C U NQ 0 D 4 4 2 L 2 2 5 C U PK 2 3 G T A ( * * G B C ) 1 (TF)(TF) SD M S 4 0 3 P SUBMERSIBLE TURBINE CIRCUITS EXTERIOR LIGHTING CIRCUITS PANELS A,S & R UNDERGROUND CIRCUITS UNDERGROUND SERVICE CONDUCTORS PANEL H1, H2 & FUEL UNDERGROUND CIRCUITS DISPENSER CIRCUITS AC AIR FLOW SCALE: TEMPERATURE SENSOR MOUNTING NO SCALE2 SCALE: DATA CABINET FRONT ELEVATION NO SCALE5 SCALE: CLEAN RESTROOM BUTTON WIRING DIAGRAM NO SCALE6 SCALE: COMPUTER/ TELEPHONE OUTLET DETAIL NO SCALE7 SCALE: DETAIL- FLEXIBLE POWER CONNECTIONS FOR EQUIPMENT NO SCALE17 DUPLEX RECEPTACLE MOUNTED ON HINGE SIDE, COORDINATE WITH FLOOR PLAN 90° MC CONNECTOR (CROUSE HINDS 38MCQ90 OR EQUAL) MOUNTED TO BOX 20A ISOLATED GROUND SURGE PROTECTIVE RECEPTACLE (TYP. OF 6) 4" SQ. X 1-1/2" DEEP BOX W/ 1-1/2" DEEP EXTENSION RING MOUNTED DIRECTLY TO PLYWOOD (8)CAT 6 DATA PORTS 90° MC CONNECTOR (CROUSE HINDS 38MCQ90 OR EQUAL) MOUNTED TO EXTENSION RING 90° MC CONNECTOR (CROUSE HINDS 38MCQ90 OR EQUAL) MOUNTED TO BOX 90° MC CONNECTOR (CROUSE HINDS 38MCQ90 OR EQUAL) MOUNTED TO EXTENSION RING 1" GROMMETED OPENING FOR (8)CAT 6 CABLES SCALE: ORDER KIOSK DEVICE DETAIL NO SCALE3 90° MC CONNECTOR (CROUSE HINDS 38MCQ90 OR EQUAL) MOUNTED TO BOX 90° MC CONNECTOR (CROUSE HINDS 38MCQ90 OR EQUAL) MOUNTED TO EXTENSION RING XX ELECTRICAL DETAILS E701 AS NOTED - SAS . . . . . REV. NO. SPCR NO. PROJECT LOCATION FILE NAME LAYERS DATE SCALE SHEET NO. DWG. TITLE OWNER USERNAME PROJECT NO. PLANNER KICK OFF MEETING ISSUED FOR 90% ISSUED FOR PERMIT FINAL APPROVED PLAN RECORD DRAWINGS DRAWN BY CHECKED BY GETGO #3557 4927 EAST 146TH STREET 261 KAPPA DRIVE, DATE REVISIONS BY ISSUED FOR REDLINE REVIEW GIANT EAGLE, INC. 750 HOLIDAY DRIVE, SUITE 200 PITTSBURGH, PA 15220 PHONE: 412-921-4300 FAX: 412-921-4313 PITTSBURGH, PA 15238 2016003.00 01-20-15 CARMEL, IN 46062 02-26-16 02-26-16