HomeMy WebLinkAboutE705 00 LIGHTING CONTROLS SCHEMA.pdfNORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING
FOOD PREP / RESTROOMS / COOLERS / STORAGE
3
NORMAL LIGHTING LOADS
EMERGENCY LIGHTING LOADS3
3
OCCUPANCY SENSOR(S)9
7
8
8
CUSTOMER SERVICE
4
DM1
TO ADDITIONAL FIXTURES
ON SAME DIMMING
MODULE CONTROL
GROUP
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING3
SALES AREA
4
DM2
TO ADDITIONAL NORMAL
LIGHTING FIXTURES ON
SAME DIMMING MODULE
CONTROL GROUP
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING3
CAFE
4
DM3
TO ADDITIONAL FIXTURES
ON SAME DIMMING
MODULE CONTROL
GROUP
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING
EMERGENCY LIGHTING LOAD
W/ 0-10V, 2-WIRE DIMMING3
4
DM4
TO ADDITIONAL
EMERGENCY LIGHTING
FIXTURES ON SAME
DIMMING MODULE
CONTROL GROUP
EMERGENCY LIGHTING LOAD
W/ 0-10V, 2-WIRE DIMMING
6
3
OFFICE / BREAKROOM
10
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING
11
6
3
ELECTRICAL AREA
NORMAL LIGHTING LOADS
NORMAL LIGHTING LOAD W/
0-10V, 2-WIRE DIMMING
TO ADDITIONAL FIXTURES
(IF APPLICABLE)
3
BUILDING EXTERIOR
NORMAL LIGHTING LOADS
3 EMERGENCY LIGHTING LOADS
DAYLIGHT SENSOR (PHOTOCELL)5
ELECTRICAL ROOM
NORMAL
LIGHTING CPC
DIMMING MODULE
ENCLOSURE
('DM1', 'DM2' &
'DM3')
EMERGENCY
LIGHTING CPC
DIMMING
MODULE
ENCLOSURE
('DM4')
BMS CPC I/O
ENCLOSURE
'BM1'
2
120VAC
INVERTER POWER.
SEE ELECTRICAL
DWGS
1
4 TYP
4 TYP
1
5 CAFE PHOTOCELL
PHOTOCELL
ON ROOF
5
1
KEY NOTESX
POWER FOR CPC LIGHTING CONTROL SYSTEM EQUIPMENT TO BE DERIVED
FROM INVERTER OUTPUT. REFER TO ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
DIMMING MODULE CONTROL CABLING. EACH DIMMING MODULE TO HAVE
DEDICATED CONTROL CABLING FROM BMS CPC I/O ENCLOSURE 'BM1'
ANALOG OUTPUT BY E.C. PER MANUFACTURER'S REQUIREMENTS. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
POWER FEEDS TO FIXTURES. WIRE AND CONDUIT BY E.C. (DEDICATED
NEUTRALS REQUIRED). POWER TO BE ROUTED THROUGH CONTROL
CONTACTORS. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
0-10V DIMMING SIGNAL TO FIXTURES (#18-2 SHIELDED CABLE) FROM
INDICATED CPC DIMMING MODULE. WIRE AND CONDUIT BY E.C. WIRING
CANNOT SHARE RACEWAY WITH LINE VOLTAGE WIRING.
CABLING TO PHOTOCELL BY E.C. REFER TO ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
LINE-VOLTAGE, WALL MOUNTED OCCUPANCY SENSOR. REFER TO
ELECTRICAL DRAWINGS FOR EXACT LOCATIONS AND SPECIFICATION.
LOW-VOLTAGE, CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY
SENSOR. REFER TO ELECTRICAL DRAWINGS FOR EXACT LOCATIONS AND
SPECIFICATION.
POWERPACK LIGHTING CONTROL VIA LOCAL CEILING MOUNTED OCCUPANCY
SENSOR. REFER TO ELECTRICAL DRAWINGS FOR EXACT LOCATIONS AND
SPECIFICATION.
LOW VOLTAGE WIRING BETWEEN CEILING MOUNTED OCCUPANCY SENSOR
AND POWERPACK PER MANUFACTURER'S REQUIREMENTS.
LOW-VOLTAGE, WALL DIMMER SWITCH. REFER TO ELECTRICAL DRAWINGS
FOR EXACT LOCATIONS AND SPECIFICATION.
0-10V DIMMING SIGNAL TO FIXTURES (#18-2 SHIELDED CABLE) FROM LOW
VOLTAGE WALL DIMMER SWITCH. WIRE AND CONDUIT BY E.C. WIRING
CANNOT SHARE RACEWAY WITH LINE VOLTAGE WIRING.
1
2
3
4
5
6
7
8
9
10
11
GENERAL NOTES
A.SINGLE LINE DIAGRAM IS FOR SCHEMATIC DESIGN INTENT PURPOSES
ONLY. ALL LAYOUTS, SIZING, CODE REQUIREMENTS PER E.E. ALL
WIRE/INTEGRATION PER E.C. IN CONJUNCTION WITH MANUFACTURER.
THIS IS IN NO WAY A SHOP DRAWING AND SHOULD NOT BE USED AS AN
INSTALLATION GUIDE.
B.E.C. TO ALLOW FOR PROGRAMMING AND COMMISSIONING, AS WELL AS
TRAINING SESSIONS FOR THE OWNER.
C.CONTROL LAYOUT IS SCHEMATIC ONLY. E.C. IS RESPONSIBLE FOR
COORDINATING THE LAYOUT OF THE ACTUAL LIGHTING CONTROL
EQUIPMENT WITH THE OTHER EQUIPMENT LOCATED WITHIN THE SPACE
ACCORDING TO CODE. THE E.C. SHALL SUBMIT A COORDINATED
ELEVATION DURING THE SHOP DRAWING PHASE FOR REVIEW.
D.CONTROLS SHOWN ARE FOR BUILDING-MOUNTED EXTERIOR LIGHTING
AND INTERIOR LIGHTING ONLY, AND DO NOT INCLUDE SITE AND
PUMP-CANOPY LIGHTS.
XX
LIGHTING CONTROLS SCHEMATICS
E705
AS NOTED
SAS
JER
SCALE:
2
NTS4
UNDER SIDE OF ROOF DECK
UNISTRUT MOUNTED TO TOP
CHORD OF ROOF TRUSS
JUNCTION BOX MOUNTED TO
BOTTOM UNISTRUT
CONDUIT
STEM
BOTTOM CHORD OF TRUSS
TYPE DL1/DL2 STEM MOUNTED
FROM UNISTRUT
NOTE:
1.E.C. IS RESPONSIBLE FOR PROVIDING ALL
MOUNTING HARDWARE. CONDUIT FEEDS,
CABLE CONNECTORS, AND OTHER
ACCESSORIES AS NEEDED. COORDINATE
INSTALLATION WITH THE G.C. REFERENCE
ARCHITECTURAL DETAILS FOR ADDITIONAL
INFORMATION.
2.FIXTURES SHALL BE CENTERED BETWEEN
TRUSSES.
UNISTRUT MOUNTED TO TOP OF BOTTOM CHORD OF
TRUSS
LS FIXTURE PENDANT MOUNTED 6" BELOW BOTTOM
CHORD OF TRUSS
NOTE:
1.E.C. IS RESPONSIBLE FOR PROVIDING ALL MOUNTING
HARDWARE, CONDUIT FEEDS CABLE CONNECTORS,
AND OTHER ACCESSORIES AS NEEDED. COORDINATE
INSTALLATION WITH THE G.C. REFERENCE
ARCHITECTURAL DETAILS FOR ADDITIONAL
INFORMATION.
SCALE:
TYPE LS SECTION DETAIL
NTS1
REV.
NO.
SPCR
NO.
PROJECT
LOCATION
FILE NAME LAYERS
DATE
SCALE
SHEET NO.
DWG. TITLE
OWNER
USERNAME
PROJECT NO.
PLANNER
KICK OFF MEETING
ISSUED FOR 90%
ISSUED FOR PERMIT
FINAL APPROVED PLAN
RECORD DRAWINGS
DRAWN BY
CHECKED BY
GETGO #3557
4927 EAST 146TH STREET
261 KAPPA DRIVE,
DATE REVISIONS BY
ISSUED FOR REDLINE REVIEW
GIANT EAGLE, INC.
750 HOLIDAY DRIVE, SUITE 200
PITTSBURGH, PA 15220
PHONE: 412-921-4300
FAX: 412-921-4313
PITTSBURGH, PA 15238
2016003.00
01-20-15
CARMEL, IN 46062
02-26-16
02-26-16