HomeMy WebLinkAboutM501 00 MECHANICAL KITCHEN HOOD.pdfGREASE DRAIN
WITH REMOVABLE CUP
4"
EXHAUST RISER
HANGING ANGLE
SCREW IN COMPACT FLUORESCENT BULB, INCANDESCENT
LIGHT FIXTURE-HIGH TEMP ASSEMBLY, INCLUDES
CLEAR THERMAL AND SHOCK RESISTANT GLOBE
FIELD WRAPPER 20.00" HIGH
(SEE HOOD OPTIONS TABLE)
EQUIPMENT
BY OTHERS
48.0" MAX
24" NOM.
48"
SECTION VIEW - MODEL 4824ND-2
16" SS BAFFLE WITH
HANDLES AND HOOK
TEMP SENSOR
3" BACK STANDOFF
- WEATHERPROOF DISCONNECT
- GREASE CLASSIFICATION TESTING
- HIGH HEAT OPERATION 300°F (149°C)
- AMCA SOUND AND AIR CERTIFIED
- WIRING FROM MOTOR TO DISCONNECT SWITCH
21
17 1/2
13 1/4
30 1/4
27 1/4
2
21 1/2
GREASE DRAIN
FEATURES:
- RESTAURANT MODEL
- ROOF MOUNTED FANS
- UL705 AND UL762
DUCTWORK BETWEEN
EXHAUST RISER ON HOOD
AND FAN (BY OTHERS)
3" FLANGE
17 1/2
17 1/2
ROOF OPENING
DIMENSIONS
20 GAUGE
CONSTRUCTION
STEEL
24"
19 1/2"
19 1/2"
VENTED
CURB
FAN #1 NCA10FA - EXHAUST FAN (EF/1)
OPTIONS
GREASE BOX
NORMAL TEMPERATURE TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT
300°F (149°C) UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM,
AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD
CAUSE UNSAFE OPERATION.
ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING BURNING
GREASE VAPORS AT 600°F (316°C) FOR A PERIOD OF 15 MINUTES WITHOUT THE
FAN BECOMING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE
CONDITION.
NOTES
- FIELD PIPE DROPS AS SHOWN
SLEEVING, ELBOWS, TEES, AND NOZZLES SUPPLIED BY CAS
- RELOCATE NOZZLES IF FLOW PATTERN IS BLOCKED BY SHELVING,
SALAMANDERS, ETC.
- MAXIMUM 9 ELBOWS IN SUPPLY LINE.
- MINIMUM 72 INCHES OF AGENT LINE FROM TANK TO FIRST NOZZLE.
- IF APPLICABLE, PRE-PIPED CHARBROILER DROPS ARE SHIPPED LOOSE.
- FACTORY PIPING EXTENDS A MAXIMUM OF 6" ABOVE THE TOP OF THE HOOD.
- APPLIANCE DIMENSIONS LISTED REPRESENT THE COOKING SURFACE
SIZE, NOT THE OVERALL APPLIANCE SIZE.
- THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS
4' 0.00"Nom./4' 0.00"OD
48"
12"
Utility
Cabinet
3"
24"24"
8 1/2"
9"
8"
PLAN VIEW - Hood #1 (EH-1)
4' 0.00" LONG 4824ND-2
U.L. Listed Screw In Compact Fluorescent
Bulb
Fr
y
e
r
-
M
w
/
D
r
i
p
B
o
a
r
d
Hi
g
h
P
r
o
x
i
m
i
t
y
16
.
0
0
"
L
x
2
1
.
0
0
"
D
Fr
y
e
r
-
M
w
/
D
r
i
p
B
o
a
r
d
Hi
g
h
P
r
o
x
i
m
i
t
y
16
.
0
0
"
L
x
2
1
.
0
0
"
D
28
30
1W
1N
3N
37 1/2"
3N
16"16"16"
EXHAUST RISER
TEMP
SENSOR
ANSUL FIRE SUPPRESSION SYSTEM
ELECTRICAL PREWIRE PACKAGE
(w/ Equipment Contactors)
DETAIL - ANSUL FIRE SUPPRESSION SYSTEM
FAN & LIGHT
CONTROL PANEL
FANSLIGHTS
34
10
5
11
7
1B 3
ROOM TEMP SENSOR
5'-1.00" Overall Length
1" LAYER OF INSULATION
FACTORY INSTALLED IN
1.00" END STANDOFF MEETS
0" REQUIREMENTS CLEARANCE
TO COMBUSTIBLE SURFACES.
1"Fire System Information
1 Ansul R102 3.0 8 Fire Cabinet Left Right
FIRE
SYSTEM
NO.
TYPE SIZE FLOW
POINTS
INSTALLATION
SYSTEM LOCATION ON HOOD
HOOD INFORMATION
1 EH-1
4824
ND-2
4' 0.00"
450 Deg.800
9"8"800 -0.307"304 SS
Where Exposed
ALONE ALONE
HOOD
NO.TAG MODEL LENGTH
MAX.
COOKING
TEMP.
EXHAUST PLENUM
TOTAL
EXH.
CFM
RISER(S)
WIDTH LENG.DIA.CFM S.P.
HOOD
CONSTRUCTION
HOOD CONFIG.
END TO
END ROW
HOOD INFORMATION
1 EH-1 SS Baffle with Handles
2 16"16"
2 Screw In Compact NO Left Ansul R102 3.0 SC-110110MA
1 Light
1 Fan
YES 358
LBS
HOOD
NO.TAG
FILTER(S)
TYPE QTY.HEIGHT LENGTH
LIGHT(S)
QTY.TYPE WIRE
GUARD
UTILITY CABINET(S)
LOCATION
FIRE SYSTEM
TYPE SIZE
ELECTRICAL
MODEL #
SWITCHES
QUANTITY
FIRE
SYSTEM
PIPING
HOOD
HANGING
WGHT
ELECTRICAL PACKAGES
1 ES-1 SC-110110MA Utility Cabinet Left
Utility Cabinet Left
Hood # 1
1 Light
1 Fan
Smart Controls Thermostatic Control w/ Relay
On/Off with Supply Exhaust 1 0.333 115 7.0
NO.TAG PACKAGE #LOCATION
SWITCHES
LOCATION QUANTITY
OPTION
FANS CONTROLLED
TYPE Ø H.P.VOLT FLA
EXHAUST FAN INFORMATION
1 EF/1 NCA10FA 800 0.700 1130 0.333 1 115 7.0 108 5.9
FAN
UNIT
NO.
TAG FAN UNIT MODEL #CFM ESP.RPM H.P.Ø VOLT FLA WEIGHT (LBS.)SONES
FAN OPTIONS
1 EF/1 1 - Grease Box
FAN
UNIT
NO.
TAG OPTION (Qty. - Descr.)
CURB ASSEMBLIES
1 # 1 34 LBS Curb 19.500"W x 19.500"L x 24.000"H Vented Hinged
NO.ON
FAN WEIGHT ITEM SIZE
HOOD OPTIONS
1 EH-1 FIELD WRAPPER 20.00" High Front, Left, Right
RIGHT END STANDOFF (FINISHED) 1" Wide 48" Long Insulated
HOOD
NO.TAG OPTION
DESCRIPTION OF OPERATION:
Get Go - #3557
SC-110110MA INSTALL
ECP #1-1
120V 1 Phase w/ 1 Exhaust Fan, Exhaust on in Fire, Lights out in Fire, Relay On/Off with Supply Fan, Fan(s) On/Off
Thermostatically Controlled. Room temperature sensor shipped loose for field installation.
BREAKER PANEL TO CONTROL PANEL
Responsibility: Electrician
BREAKER PANEL CONTROL PANEL
BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED
BREAKER 1PH
CONTROL POWER. DO NOT WIRE
TO SHUNT TRIP BREAKER.
Hot
Neutral
H1
N1120 V
15 A
Ground GND
1ST HOOD LIGHT BREAKER SHARED W/ CONTROL POWER. SWITCH
#1
BREAKER 1PH Hot
Neutral
L1
FN1
GNDGround
EF/1
115 V
15 AMP
BREAKER 3PH
WIRE directly to Equipment Contactor
PN:
VOLT:MAX
MAX AMP:
LINE
LINE
208 V LINE
L1
L2
L3
Ground GND
FRYER#1 AC_1
100-C60D10
208 V70 AMP
60 AMP
BREAKER 3PH
WIRE directly to Equipment Contactor
PN:
VOLT:MAX
MAX AMP:
LINE
LINE
208 V LINE
L1
L2
L3
Ground GND
FRYER#2 AC_2
100-C60D10
208 V70 AMP
60 AMP
BREAKER 1PH
BREAKER 1PH
WIRE directly to Equipment Contactor
PN:
VOLT1:
VOLT2:
MAX
MAX
MAX AMP1:
MAX AMP2:
Hot
Neutral
L1
L2115 V
115 V Neutral
Hot
L4
L3
DUMP AC_3
FREEZER
Ground GND
Ground GND
100-C23D400
115 V
115 V
25 AMP
25 AMP
23 AMP
23 AMP
CONTROL PANEL TO FANS
Responsibility: Electrician
CONTROL PANEL FANS
Load Wiring
WIRE DIRECT
TO STARTER WIRE TO
DISCONNECT
T1
T2
EF/1
LEG 1 / HOT
LEG 2 / NEUTRAL
GND GROUND
C-1
01FAN:
7.0
0.333
115 V
CONTROL PANEL TO ACCESSORY ITEMS
Responsibility: Electrician
CONTROL PANEL COMPONENT
WIRE C TO COMMON.
WIRE AR1 TO NORMALLY CLOSED.
C1 TO AR1 SHOULD HAVE
HOOD PANEL
FIRE SYSTEM
TO
MICROSWITCH
CONTINUITY WHEN ARMED.
IF MORE THAN
WIRE IN SERIES
ONE FIRE SYSTEM
AS SHOWN HERE
C1
AR1
MICROSWITCH 1
1:C
4:NO
2:NC
MS-1
1:C
4:NO
2:NC
1:C
4:NO
2:NC
MS-2
ALL SWITCHES FACTORY WIRED
CAT-5 CONNECTION
HOOD PANEL
SWITCHES
TO J4
HOOD PANEL
HOOD LIGHTS
TO
1400 W MAX WIRE TO J-BOX ON TOP OF HOOD
B1
W1
GND
BLACK
WHITE
GREEN
HOOD LIGHTS 1
WIRE TO CONTROL BOARD.
SENSOR MOUNTED IN ROOM AWAY
FROM HEAT SOURCES. SEE MANUAL
HOOD PANEL
KITCHEN TEMP
TO
SENSOR
T1A
T1B ROOM TEMP
FACTORY WIRED TEMPERATURE
SENSOR. MOUNTED IN EXHAUST DUCT
HOOD PANEL
DUCT SENSOR
TO
T2A
T2B HOOD 1
RISER 1
EXTERNAL
SPARE CONTACT ON/OFF WITH
FIRE
WIRE DIRECT TO CONTACTOR
HOOD PANEL
ON/OFF WITH
CIRCUIT
FIRE
T1
T2
line
line
FRYER#1
GroundGND
T3 line
EQT1
EXTERNAL
SPARE CONTACT ON/OFF WITH
FIRE
WIRE DIRECT TO CONTACTOR
HOOD PANEL
ON/OFF WITH
CIRCUIT
FIRE
T1
T2
line
line
FRYER#2
GroundGND
T3 line
EQT2
EXTERNAL
EXTERNAL
SPARE CONTACT ON/OFF WITH
FIRE.
WIRE DIRECT TO CONTACTOR
HOOD PANEL
ON/OFF WITH
CIRCUIT
FIRE
T1
T2
Hot
Neutral
FREEZERGroundGND
T3
T4
Hot
Neutral
DUMPGroundGNDEQT3
THE FOLLOWING CONNECTIONS
MAY OR MAY NOT BE
REQUIRED BASED ON JOBSITE
SPECIFICATIONS
HOOD PANEL
EXTERNAL
SIGNAL FOR
SHUNT TRIP
ST TERMINAL IS ENERGIZED
IN FIRE CONDITION.
ST
N1 NEUTRAL FROM SHUNT COIL
HOT TO SHUNT COIL SHUNT COIL
SPARE CONTACTS USED WHEN FIRE
HOOD PANEL
SYSTEM DRY
SPARE FIRE
CONTACT SYSTEM DISCHARGES TO DISABLE
EQUIPMENT OR PROVIDE SIGNALS.
(NOT FOR BUILDING FIRE ALARM)
C2
AR2
COMMON
NORMALLY OPEN
SPARE CONTACTS WILL MAKE
HOOD PANEL
ON/OFF WITH
DRY CONTACT
SUPPLY FAN
COMMON TO NORMALLY OPEN
WHEN SUPPLY FAN IS ON.
GROUP 1
SFC1
SFO1
COMMON
NORMALLY OPEN
SFC2
SFO2
COMMON
NORMALLY OPEN
MECHANICAL KITCHEN HOOD DETAILS
M501
AS NOTED
JPO
PIB
XXX
FI
L
T
R
A
T
I
O
N
E
F
F
I
C
I
E
N
C
Y
(
%
)
0
0.1
10
20
30
40
1
PARTICLE DIAMETER (um)
10
FILTER COLLECTION EFFICIENCY
90
50
60
80
70
100
2" Captrate Grease-Stop Solo FilterRR
Made From 430 Stainless Steel
ETL Listed Grease Extracting Filters
CaptiveAire Captrate Solo Filter
STANDARD 710
SLI DTE
R
R
ACCORDANCE
No. 96
BUILT
NFPA
WITH
IN
REV.
NO.
SPCR
NO.
PROJECT
LOCATION
FILE NAME LAYERS
DATE
SCALE
SHEET NO.
DWG. TITLE
OWNER
USERNAME
PROJECT NO.
PLANNER
KICK OFF MEETING
ISSUED FOR 90%
ISSUED FOR PERMIT
FINAL APPROVED PLAN
RECORD DRAWINGS
DRAWN BY
CHECKED BY
GETGO #3557
4927 EAST 146TH STREET
261 KAPPA DRIVE,
DATE REVISIONS BY
ISSUED FOR REDLINE REVIEW
GIANT EAGLE, INC.
750 HOLIDAY DRIVE, SUITE 200
PITTSBURGH, PA 15220
PHONE: 412-921-4300
FAX: 412-921-4313
PITTSBURGH, PA 15238
2016003.00
01-20-15
CARMEL, IN 46062
02-26-16
02-26-16