HomeMy WebLinkAboutFusion_PermitSet_111816.pdfMECHANICAL & ELECTRICAL NOTES GENERAL PROJECT NOTES 1. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE EXISTING BUILDING CONSTRUCTION TYPE AS DEFINED BY SECTION 601 OF THE INDIANA BUILDING CODE . 1. THE MECHANICAL, ELECTRICAL AND PLUMBING SCOPES OF WORK ARE LIMITED TO BASIC DESIGN-BUILD ALTERATIONS WHICH ARE OUTLINED IN THESE PLANS. THE 2. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF ALL APPLICABLE STATE AND DESIGN-BUILD CONTRACTORS FOR EACH TRADE MUST NOTIFY THE ARCHITECT IF THEY LOCAL BUILDING CODES. CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THE FIND THAT THE SCOPE OF WORK EXCEEDS THE LEVEL OF MECHANICAL, ELECTRICAL OR CURRENT APPLICABLE BUILDING CODE(S) FOR THEIR RESPECTIVE SCOPE OF WORK. PLUMBING WORK INDICATED ON THESE DRAWINGS SO THAT ANY NECESSARY ENGINEERING CAN OCCUR AND ADDITIONAL PLANS CAN BE FILED, OR IF ADDITIONAL 3. CONTRACTOR(S) SHALL VISIT THE WORK SITE PRIOR TO COMMENCEMENT. THE INFORMATION IS NEEDED IN ORDER TO DO THE WORK IN THE FIELD. THE MECHANICAL DRAWINGS CONTAINED HEREIN MAY NOT BE ALL INCLUSIVE OF EXISTING CONDITIONS ELECTRICAL AND PLUMBING DESIGN-BUILD CONTRACTORS SHALL COMPLY WITH ALL OR NEW WORK REQUIREMENTS. CONTRACTOR(S) SHALL MAKE THEMSELVES FAMILIAR APPLICABLE STATE AND LOCAL BUILDING CODES. FIRE SUPPRESSION AND FIRE ALARM WITH THE WORK SITE IN THE FIELD IN ORDER TO BE FULLY AWARE OF THE REQUIREMENTS SYSTEMS SHALL BE INSTALLED BY THE APPROPRIATE DESIGN-BUILD CONTRACTOR AND OF THE SCOPE OF WORK. MUST COMPLY WITH ALL APPLICABLE STATE AND LOCAL BUILDING CODES. FIRE SUPPRESSION AND FIRE ALARM DESIGN-BUILD CONTRACTORS ARE RESPONSIBLE FOR 4. FIELD VERIFY ALL DIMENSIONS AND MEASUREMENTS. INFORM THE GENERAL COMPLETING AND FILING THEIR PLANS AND OBTAINING THEIR PERMITS. CONTRACTOR BEFORE BEGINNING ANY CONSTRUCTION IF EXISTING CONDITIONS PREVENT OBTAINING RESULTS AS SHOWN OR SPECIFIED. DO NOT SCALE DRAWINGS. 2. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE NOTED DIMENSIONS TAKE PRECEDENCE. DRAWINGS. NO NEW MAIN MECHANICAL APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED. ALL MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND 5. VERIFY EXISTING CONDITIONS INDICATED ON THE DRAWINGS AND REPORT ANY FLEX DUCT PER NEW WALL LAYOUT. NO NEW HARD DUCTWORK OR EQUIPMENT IS DISCREPANCY THROUGH THE GENERAL CONTRACTOR TO SCHOTT DESIGN, INC. BEING ADDED; MECHANICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST 6. THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE OWNER REGARDING ALL COMPLY WITH THE INDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES. ON-SITE ACTIVITIES; SUCH AS, BUT NOT LIMITED TO, WORK SCHEDULE, MATERIALS STORAGE AND HANDLING, DELIVERIES, ACCESS TO THE WORK SITE, TRAFFIC CONTROL, 3. VERIFY HEAT LOADS OF ANY SPECIAL EQUIPMENT IN THE TENANT SPACE, AND PROVIDE AND BUILDING/PUBLIC SAFETY PROCEDURES DURING CONSTRUCTION. THE ADDITIONAL AIR FLOW IF REQUIRED. CONFIRM WITH OWNER PRIOR TO ANY PURCHASE CONTRACTOR SHALL ALSO COORDINATE WORK "BY OTHERS" WITH HIS/HER OWN OF NEW EQUIPMENT. REVISE ZONING IF REQUIRED. DO NOT DESIGN ANY SINGLE ACTIVITIES AS NECESSARY TO EXECUTE THE OVERALL PROJECT SCOPE. OFFICE SPACE TO BE ON A SPLIT ZONE UNLESS APPROVED BY BUILDING OWNER/LANDLORD. 7. THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE LANDLORD, DAILY WORKING HOURS, WEEKEND HOURS AND HOURS THAT MAY BE WORKED PRIOR TO AND DURING 4. RELOCATE AIR-SUPPLY DIFFUSERS AND RETURN-AIR GRILLES AS REQUIRED. PROVIDE HOLIDAYS. LANDLORD RESERVES THE RIGHT TO RESTRICT CONSTRUCTION TO NIGHTS AND PROPER AIR SUPPLY FOR DIFFUSERS AND RETURN AIR FROM RETURN AIR GRILLES. WEEKENDS WHEN THAT CONSTRUCTION IS DEEMED TO INTERFERE WITH THE OPERATIONS CONTRACTOR IS TO PLACE LOCATION OF DIFFUSERS AND RETURN AIR GRILLES AS OF ADJACENT TENANTS. REQUIRED BY CODE. 8. FOR THOSE ITEMS TO BE ORDERED REQUIRING LEAD TIME, THE CONTRACTOR SHALL 5. POSITION LOCATION OF ALL THERMOSTATS WHERE APPROPRIATE PER MECHANICAL COORDINATE THE PROJECT SCHEDULE ACCORDINGLY AND COMMUNICATE TO THE DESIGN. COORDINATE WITH TENANT AND BUILDING OWNER FOR FURNITURE PANEL OR OWNER, TENANT, AND SCHOTT DESIGN WHEN DECISIONS MUST BE RENDERED IN ORDER OTHER CONFLICTS. FOR THE CONTRACTOR TO MEET THE PROJECT SCHEDULE. THE OWNER, TENANT, OR DESIGNER/ARCHITECT IS NOT RESPONSIBLE FOR DELAYS RESULTING FROM THE b. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE CONTRACTOR'S FAILURE TO COMMUNICATE MATERIAL LEAD TIMES. DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF 9. SUBSTITUTIONS FOR SPECIFICALLY NAMED PRODUCTS WILL NOT BE ALLOWED WITHOUT THE EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS TO PRIOR APPROVAL FROM THE DESIGNER. SUBMIT REQUESTS FOR SUBSTITUTIONS WITH NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL APPROPRIATE SUPPORT INFORMATION TO THE DESIGNER. ALLOW REASONABLY PLANS CAN BE FILED AND MUST COMPLY WITH ALL APPLICABLE CODES. SUFFICIENT TIME FOR THE DESIGNER TO REVIEW THE REQUEST AND RENDER A DECISION. 7. COMPLY WITH THE INDIANA ELECTRICAL AND MECHANICAL CODE AND ALL OTHER 10. SCHOTT DESIGN, INC., SHALL NOT HAVE CONTROL OVER, OR BE IN CHARGE OF, AND APPLICABLE CODES. SHALL NOT BE RESPONSIBLE FOR A CONTRACTOR'S CONSTRUCTION MEANS, METHODS, SCHEDULES, SEQUENCES, OR SAFETY. THE CONTRACTORS SHALL BE RESPONSIBLE FOR 8. SIZE AND CIRCUIT ELECTRICAL POWER ITEMS. PROVIDE OR REUSE ELECTRICAL POWER MAINTAINING A SAFE ENVIRONMENT FOR WORKERS AND THE PUBLIC AT ALL TIMES. AND DATA OUTLETS AS REQUIRED. 1 1. THE GENERAL CONTRACTOR SHALL ESTABLISH WITH THE LANDLORD CLEANUP 9. ALL ELECTRICAL OUTLETS WITHIN 6'-0" OF WATER ARE TO BE G.F.C.I. PROCEDURES AND GUIDELINES TO BE FOLLOWED ON A DAILY BASIS IN ORDER TO CONDUCT BUSINESS IN A SAFE AND CLEAN ENVIRONMENT. 10. AT EACH PHONE AND DATA JACK, PROVIDE PULL STRING FROM ABOVE CEILING TO BOX. TENANT'S DATA CONTRACTOR IS RESPONSIBLE FOR PULLING CONDUCTORS AND � 2. THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE LANDLORD, AN AREA FOR PROVIDING APPROPRIATE TERMINALS AT FACE PLATE. STAGING OF CONSTRUCTION MATERIALS, EQUIPMENT, DUMPSTER AND PARKING CONSTRUCTION AND DELIVERY VEHICLES. THE USE OF EXISTING REST ROOM FACILITIES 1 1. PROVIDE COLORED FACEPLATES FOR ELECTRICAL OUTLETS & SWITCHPLATES TO MATCH SHALL BE APPROVED BY THE LANDLORD. ONLY THOSE DESIGNATED AREAS SHALL BE USED EXISTING, UNLESS OTHERWISE NOTED. ELECTRICIAN TO FIELD VERIFY PRIOR TO BY CONSTRUCTION CREWS. PURCHASE. 13. THE GENERAL CONTRACTOR SHALL USE DUST PARTITIONS TO MINIMIZE DISTURBANCES OF 12. PROVIDE JUNCTION BOXES OR POWER POLES AT WORKSTATIONS WHERE SHOWN. DAILY TENANT OPERATIONS DURING DEMOLITION AND CONSTRUCTION WORK. DUST REFER TO THE PLAN FOR THE APPROPRIATE DESIGNATIONS. DATA WILL BE RUN BY THE PARTITIONS SHALL BE CONSTRUCTED OF 2X4 WOOD STUDS @ 24"O.C., INSULATION AND 6 TENANT'S DATA VENDOR. ELECTRICIAN TO MAKE FINAL CONNECTION FROM MIL VAPOR BARRIER ON EACH SIDE. WORKSTATION WHIP TO JUNCTION BOX. THE FURNITURE VENDOR IS TO BE RESPONSIBLE FOR WIRING THE BASE PANELS OF THE WORKSTATIONS. 14. CONTACT THE DESIGNER IMMEDIATELY IF, IN THE FIELD, CONFLICTS ARE DISCOVERED BETWEEN COMPONENTS OF DIFFERENT SYSTEMS THAT PREVENT THE INSTALLATION OF 13. CONTRACTOR TO COORDINATE WITH TENANT ON WORKSTATION FURNITURE THOSE COMPONENTS AS INDICATED ON THE DRAWINGS. (I.E. WHERE EXISTING SPECIFICATIONS TO OBTAIN CIRCUITRY REQUIREMENTS PRIOR TO RUNNING ELECTRICAL MECHANICAL DUCTWORK MAY PREVENT THE INSTALLATION OF LIGHTING FIXTURES AS CONDUITS TO JUNCTION BOXES. INDICATED ON THE CEILING PLAN). 14. IF REQUIRED, AND AS NECESSARY, PROVIDE NEW BALLASTS AND LAMPS IN ALL LIGHTS IN � 5. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR THE IDENTIFICATION, DISCOVERY, EXISTING SPACES. CONSULT WITH LANDLORD. PRESENCE, HANDLING, REMOVAL, DISPOSAL OF, OR EXPOSURE TO ANY PERSONS, THAT OF HAZARDOUS MATERIALS IN ANY FORM ON THE PROJECT SITE. 15. VERIFY EXISTING LIGHTING CIRCUITING. SIZE NEW CIRCUITS AS REQUIRED. PROVIDE NEW OR REVISE EXISTING CIRCUITING FOR NEW LAYOUT OF LIGHT FIXTURES. 16. PROVIDE FIRE-TREATED WOOD BLOCKING IN WALLS FOR ALL WALL HUNG ITEMS INCLUDING MILLWORK, WALL STOPS, CABINETRY, ETC. 16. ENSURE THAT ALL MOUNTING HEIGHTS OF ELECTRICAL DEVICES MEET A.D.A. REQUIREMENTS. 17. SHOP DRAWINGS OR CATALOG CUTS MUST BE SUBMITTED TO SCHOTT DESIGN, INC. FOR APPROVAL ON ALL MATERIALS OR ITEMS WHERE THE CONTRACTOR CHOOSES TO 17. WHERE MULTIPLE SWITCHES ARE SHOWN, PROVIDE (1) GANG BOX WITH A SINGLE DEVIATE FROM WHAT IS SHOWN ON THE DRAWINGS, OR IF THE DRAWINGS DO NOT COVER PLATE. INDICATE A SPECIFIC MANUFACTURER OR MODEL NUMBER. 18. CENTER CEILING ELEMENTS IN CEILING TILES, INCLUDING RECESSED DOWN LIGHTS, � g. EXPEDITE PREPARATION AND SUBMITTAL OF ALL SHOP DRAWINGS TO ALLOW SUFFICIENT SMOKE DETECTORS, SPRINKLER HEADS, AND EXIT SIGNS UNLESS OTHERWISE NOTED. TIME FOR CHECKING, APPROVAL, ORDERING, FABRICATION, AND DELIVERY OF MATERIALS AND EQUIPMENT. 19. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES F I N IS H N OTES SHOWN ON PLAN ARE FOR REFERENCE ONLY. 20. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES), EMERGENCY �. ALL FINISHES SHALL COMPLY WITH CHAPTER 8(INTERIOR FINISHES) OF THE INDIANA SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY OTHER REQUIRED ALARM & BUILDING CODE FOR CLASS A FIRE RATINGS. DETECTION SYSTEMS AS NECESSARY TO MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS, 2. FOR ALL NEW DRYWALL INSTALLATIONS, INSTALL AS RECOMMENDED BY THE GYPSUM CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE, ALL LOCATIONS ASSOCIATION. (SUCH AS, CONTROL JOINTS, FINISH LEVELS, FASTENERS, TAPING DETAILS, OF SUCH DEVICES MUST BE APPROVED BY SDI OR TENANT PRIOR TO INSTALLATION. CORNER BEADS, ETC.) FAILURE TO DO SO MAY RESULT IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE. 3. ALL NEW PLATES AND SWITCHES ARE TO MATCH EXISTING COLOR, UNLESS OTHERWISE NOTED. REMOVE ALL PLATES BEFORE PAINTING AND REATTACH AFTERWARDS. 21. COORDINATE WITH THE OWNER/TENANT PRIOR TO INSTALLATION OF FIRE DETECTION CONTRACTOR TO CONFIRM EXISTING COLOR PRIOR TO PURCHASING NEW. DEVICES REGARDING ALL DEVICE LOCATIONS TO AVOID CONFLICT WITH FEATURE WALLS (CONFERENCE ROOMS AND RECEPTION AREAS) AND TENANT-INSTALLED ITEMS 4. ALL AREAS RECEIVING PAINT ARE TO RECEIVE PRIMER COAT AND TWO (2) FINISH (I.E. PRESENTATION BOARDS, A/V EQUIPMENT AND PROJECTION SCREENS). COATS. 5. FOR CHANGE IN FLOOR FINISH MATERIAL, PROVIDE TRANSITION STRIP AT DOOR OPENINGS AS NOTED ON FINISH PLAN (I.E. WHERE VCT MEETS CARPET). b. WHERE LIMITS OF WORK ARE SHOWN, OTHER INCIDENTAL WORK LIKE PAINTING WHERE NEW OUTLETS HAVE BEEN INSTALLED, IS CONSIDERED PART OF THE SCOPE OF WORK. PROVIDE A COMPLETE AND FINISHED PRODUCT READY FOR TENANT AND BUILDING OWNER. 7. REFINISH SURFACES TO MATCH EXISTING WHERE DEMOLITION HAS OCCURRED. 8. WHERE PHONE BOARD IS PROVIDED, PAINT BOARD WITH FIRE RETARDANT PAINT TO MATCH ADJACENT WALL FINISH. 9. SUBMIT FINISH SAMPLE OF MILLWORK (STAINED OR PAINTED AS SPECIFIED) TO SCHOTT DESIGN FOR REVIEW AND APPROVAL PRIOR TO THE FINISHING PROCESS OF ALL MILLWORK. 10. REFERENCE INTERIOR ELEVATION & SECTIONS WHERE PROVIDED FOR ADDITIONAL FINISH INFORMATION. 1 1. ALL PAINTS AND ADHESIVES/SEALANTS SHALL HAVE LOW VOC CONTENT. 12. ALL ADHESIVES/SEALANTS TO BE USED AS RECOMMENDED BY PRODUCT MANUFACTURER. 19. ENSURE THAT ALL MATERIALS AND LABOR ARE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF EACH RESPECTIVE TRADE WHETHER SPECIFIED OR NOT. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL WORK IS IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL BUILDING CODES, AND STANDARDS FOR GENERAL, MECHANICAL, AND ELECTRICAL CONSTRUCTION. 20. ALL DETAILS, MATERIALS, AND INSTALLATIONS ARE SUBJECT TO FIRST APPROVAL BY SCHOTT DESIGN, INC., AND FINAL APPROVAL BY THE OWNER. 21. REVIEW AND COORDINATE ALL NEW WORK AND EXISTING CONDITIONS WITH ALL OTHER TRADES. FIELD WORK ORDERS & CHANGE ORDERS WILL NOT BE APPROVED FOR ANY CONDITIONS OR CONFLICTS THAT COULD HAVE BEEN ACCOUNTED FOR BY THE BIDDER DURING PRE-BID FIELD INSPECTION AND AFTER AWARD OF CONTRACT. 22. FURNITURE, OFFICE EQUIPMENT, OFFICE PARTITION SYSTEMS, REFRIGERATORS, VENDING MACHINES, AND OTHER SIMILAR ITEMS SHOWN DASHED ON THIS DRAWING AND NOT ATTACHED TO THE BUILDING ARE FOR REFERENCE ONLY AND ARE NOT TO BE PROVIDED AS PART OF THE WORK UNLESS SPECIFICALLY STATED TO BE PROVIDED. 23. REPAIR GYPSUM WALLBOARD WHERE DEMOLITION HAS OCCURRED AT REMAINING WALLS. REPAIR ANY GYPSUM BOARD DAMAGED BY DEMOLITION. PROVIDE EXPANSION JOINTS IN DRYWALL WHERE NEW WALLS MEET OR ADJOIN TO EXISTING CORE WALLS. 24. PATCH ALL GYPSUM WALLBOARD AT AREAS OF ELECTRICAL, DATA AND SWITCH DEVICES BEING REMOVED. PATCH HOLE WITH DRYWALL, TAPE, SPACKLE AND PREPARE FOR FINISH. 25. ALL EQUIPMENT AND/OR FIXTURES SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS OR INSTRUCTIONS. 26. EXECUTE A THOROUGH FINAL CLEAN AND INSPECTION OF THE SPACE UPON COMPLETION OF THE PROJECT. ALL SURFACES, FIXTURES, AND EQUIPMENT SHALL BE CLEAN, AND THE SPACE SHALL BE TURNED OVER TO THE OWNER IN A CONDITION THAT REPRESENTS THE HIGHEST LEVEL OF CARE AND PROFESSIONALISM. ENSURE ALL GENERAL CONTRACTOR INSTALLED APPLIANCE S WORK & DO NOT LEAK. 27. PROVIDE TO THE OWNER ALL OPERATION AND/OR MAINTENANCE MANUALS, OR INSTRUCTIONS FOR ALL EQUIPMENT AND SYSTEMS AT THE COMPLETION OF THE PROJECT. 28. ALL PLAN DIMENSIONS ARE FROM FACE OF EXISTING FINISH TO FACE OF NEW GYPSUM BOARD WALL, OR FACE TO FACE OF NEW GYPSUM BOARD WALL. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. 29. CONTRACTOR TO PROVIDE AN ALLOWANCE FOR CLEANING EXISTING WINDOW BLINDS. REPLACE ANY DAMAGED OR MISSING WINDOW BLINDS WITH NEW TO MATCH BUILDING STANDARD. 30. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE REQUIREMENTS REGARDING LOCAL PLAN REVIEW, PERMITS, INSPECTIONS, AND FEES. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING ALL REQUIRED DRAWINGS AND SUPPORTING DOCUMENTS TO THE LOCAL BUILDING OFFICIAL AND/OR PERMIT DEPARTMENT. ALL REQUIRED LOCAL PERMIT FEES SHALL BE PAID BY THE GENERAL CONTRACTOR UNLESS STIPULATED OTHERWISE IN THE OWNER/CONTRACTOR AGREEMENT. 31. FIRE SEAL ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND CEILINGS WITH APPROVED FIRE-RATED CAULK AS DIRECTED BY LOCAL JURISDICTIONS. 32. WHERE STRUCTURAL BEAMS, DUCTWORK, ETC. PENETRATE SOUND OR FIRE RATED PARTITIONS, GYPSUM WALLBOARD WALL TO BE SCRIBED TO FIT TIGHT, CAULKED AND FIRE DAMPERED IF REQUIRED. 33. CONTRACTOR TO ALLOW FOR UNLEVEL FLOOR CONDITIONS. ALL EXISTING FLOOR AND WALL SUBSTRATES SHALL BE LEVELED AND PATCHED AS REQUIRED TO RECEIVE NEW CONSTRUCTION AND FINISHES. ADJUST DOORS AND FRAMES AS REQUIRED. MILL/CASEWORK NOTES 1. CASEWORK AND MILLWORK GENERALLY INDICATED ON THESE DRAWINGS ARE TO BE PROVIDED UNDER THE GENERAL CONTRACT. 2. UNLESS INDICATED OTHERWISE, COMPLY WITH ARCHITECTURAL WOODWORK INSTITUTE (A.W.I.) CURRENT STANDARDS FOR CUSTOM GRADE WOODWORK. 3. FURNISH SHOP DRAWINGS ON ALL MILLWORK AND CASEWORK FOR APPROVAL BY THE TENANT AND SCHOTT DESIGN PRIOR TO FABRICATION. 4. WHERE CASEWORK AND MILLWORK ARE TO BE INSTALLED, VERIFY ALL DIMENSIONS ON PLANS AGAINST DIMENSIONS OF AS-BUILT CONDITIONS IN FIELD. REPORT ANY DISCREPANCIES TO SCHOTT DESIGN THROUGH THE GENERAL CONTRACTOR. MAKE ADJUSTMENTS TO CASEWORK AND MILLWORK TO FIT FIELD CONDITIONS UNLESS DOING SO WILL SIGNIFICANTLY ALTER THE INTENT OF THE DESIGN SHOWN ON THE DRAWINGS. 5. VERIFY FINISHES (LAMINATE, VENEER, STAINS, ETC.) ON THE SECTIONS AND ELEVATION DRAWINGS WITH FINISHES INDICATED ON THE FINISH PLAN/SCHEDULES. IMMEDIATELY REPORT ANY DISCREPANCIES TO SCHOTT DESIGN THROUGH THE GENERAL CONTRACTOR. b. REFER TO MILLWORK SECTIONS & ELEVATIONS . UNLESS OTHERWISE SHOWN, PLASTIC LAMINATE CLAD, COUNTERTOPS WITH 4" BACKSPLASHES WHERE INDICATED. BACKSPLASHES TO BE FIELD APPLIED. 7. REFER TO MILLWORK SECTIONS & ELEVATIONS FOR CABINETRY SPECIFICATIONS (CUSTOM PLASTIC LAMINATE OR PRE-MANUFACTURED STOCK CABINETRY). 8. TO PROVIDE BLOCKING IN WALLS FOR ALL MILLWORK, WALL STOPS, HARDWARE, AND CABINETRY WHERE SPECIFIED. ALL WOOD BLOCKING TO BE FIRE RATED. DOCUMENT APPROVAL DEMOLITION NOTES 1. COORDINATE DEMOLITION WITH NEW WORK CONSTRUCTION DRAWINGS IN ORDER TO DETERMINE THE FULL EXTENT OF NECESSARY DEMOLITION. SALVAGE REUSABLE ITEMS. 2. NO STRUCTURAL OR LOAD-BEARING CONSTRUCTION SHALL BE REMOVED, DEMOLISHED, OR DAMAGED AS A RESULT OF THIS PROJECT UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. PROTECT ALL EXISTING STRUCTURAL MEMBERS DURING DEMOLITION/CONSTRUCTION. THE CONTRACTOR SHALL VERIFY IN THE FIELD, PRIOR TO DEMOLITION, THAT ALL ITEMS NOTED TO BE DEMOLISHED ARE NOT STRUCTURAL. CONTACT SCHOTT DESIGN IMMEDIATELY IF THE CONTRACTOR(S) IN THE FIELD SUSPECT THAT AN ITEM NOTED FOR DEMOLITION APPEARS TO BE STRUCTURAL OR OTHERWISE LOAD-BEARING. BEWARE OF STRUCTURAL COLUMNS AND/OR BEAMS THAT MAY BE CONCEALED BEHIND FINISHES THAT ARE NOTED FOR REMOVAL. EXERCISE CAUTION WHEN DEMOLISHING BUILDING FINISHES OR PARTITIONS ADJACENT TO OR AROUND STRUCTURAL MEMBERS. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR INADVERTENT DAMAGE TO THE BUILDING STRUCTURAL SYSTEM. 3. PRIOR TO DEMOLITION, COORDINATE WITH THE OWNER IN THE FIELD REGARDING THOSE ITEMS THAT MAY BE REMOVED AND REUSED. CONFIRM WITH THE OWNER THOSE ITEMS THE OWNER CHOOSES TO RETAIN FROM DEMOLITION, AND THOSE ITEMS OF WHICH THE OWNER CHOOSES TO DISPOSE. COMPLY WITH THE OWNER'S REQUESTS. 4. WHERE EQUIPMENT, FIXTURES, OR FINISHES ARE MOVED FROM ANY OTHER PART OF THE BUILDING TO BE REUSED IN THE PROJECT AREA, THE CONTRACTOR SHALL INCLUDE IN THEIR SCOPE OF WORK ANY NECESSARY PATCHING OR REPAIRING OF THE REMAINING AREAS FROM WHERE THE ITEMS WERE RELOCATED, UNLESS OTHERWISE DIRECTED BY OWNER. 5. REMOVE ALL EXISTING WALLS AND DOORS WHERE INDICATED BY NOTE, SYMBOL, OR DASHED LINES. NOTE THAT SOME ITEMS HAVE NOT BEEN SHOWN ON DEMOLITION PLAN. VISIT AREA OF WORK TO ASSURE EXTENT OF DEMOLITION. b. REMOVE ALL CARPET, VINYL BASE, VCT, WALL FABRIC, AND ANY OTHER FINISHES AS REQUIRED FOR NEW CONSTRUCTION. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS. REFER TO FINISH PLAN/SCHEDULE FOR CLARIFICATION OF EXISTING FINISHES TO REMAIN. 7. REMOVE ALL ELECTRICAL OUTLETS AND CONDUCTORS AS REQUIRED OR INDICATED. SALVAGE OUTLETS FOR REUSE IN NEW CONSTRUCTION. 8. REFER TO DEMOLITION PLAN AND REFLECTED CEILING PLAN LEGEND FOR CEILING GRID INSTRUCTIONS. 9. USE CARE TO PROTECT EXISTING BUILDING ELEMENTS INDICATED ON THE DRAWINGS TO REMAIN SUCH AS, BUT NOT LIMITED TO, EXISTING CEILING GRID, TILES, FIRE SUPPRESSION EQUIPMENT, DIFFUSERS, LIGHT FIXTURES, EQUIPMENT, CASEWORK, AND FINISHES. THE CONTRACTOR SHALL REPLACE AND/OR REPAIR, AT THE CONTRACTOR'S COST, ANY SUCH ELEMENTS DAMAGED DURING CONSTRUCTION THAT COULD HAVE OTHERWISE BEEN REASONABLY PROTECTED AND MAINTAINED IN GOOD CONDITION FOR THE OWNER'S USE IN THE PROJECT. 10. PER THE INDIANA ELECTRICAL CODE (SPREAD OF FIRE OR PRODUCTS OF COMBUSTION) REMOVE ALL ACCESSIBLE PORTIONS OF ABANDONED CABLES AND WIRING INCLUDING BUT NOT LIMITED TO: DATA WIRING, COMMUNICATIONS WIRING, FIRE ALARM CABLES, AUDIO CABLES, COAXIAL CABLES, FIBER OPTIC CABLES/RACEWAYS, AND PLTC CABLES. REFER TO SECTION 300.21. 1 1. WHERE FIXTURES OR EQUIPMENT ARE REMOVED FROM ANY ELECTRICAL, PLUMBING, MECHANICAL, OR VOICE/DATA SYSTEMS, ALL REMAINING TERMINATIONS SHALL BE CLOSED AND PROTECTED IN STRICT ACCORDANCE WITH INDUSTRY STANDARDS AND GOVERNING SAFETY REGULATIONS OR PROCEDURES. MARK, LABEL, OR FLAG ALL TERMINATED SYSTEMS FOR FUTURE REFERENCE. CONTRACTOR TO PROVIDE AN "AS-BUILT" SET INDICATING THE LOCATION OF ALL PERMANENTLY ABANDONED SYSTEMS. 12. GENERAL CONTRACTOR TO PROVIDE RECYCLING COSTS TO THE BUILDING OWNER/LANDLORD ON ALL ITEMS BEING DEMOLISHED, SUCH AS, METAL STUDS, DRYWALL, CARPET, CEILING TILES, DOORS,GLASS, AND CABINETRY. I•irli�r�.pr,li5 Rr��iun�l GFiCi] Qftic4° � �: , _. 36� Pennsylvania Parkway HUIiCi:yl�n � . . .. _ . .. I�idiars.pr.lis Cannr,l �" � c� p �' LdMekr,�.ItyCu'Pora}i.^.r . � [if�f' II�; rit_� . � . . .. . �[7;;[� �S Ffl,'Wf��}' Sfa���iu�MS � � . �_ � . VICI N ITY MAP TENANT/CLIENT, UPON SIGNATURE, APPROVES ALL ASPECTS OF THE SCOPE OF WORK CONTAINED IN THESE DOCUMENTS. c��i�i� c����c P,htcr E Fap�irtrr�=�it FIRE PROTECTION NOTES 1. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA 10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY POINT TO A VISIBLE EXTINGUISHER. THE FOLLOWING NOTES APPLY ONLY IN EXISTING SPRINKLERED FACILITIES. 2. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN BUILD SERVICES UNDER THE / GENERAL CONTRACT. PROVIDE A COMPLETE WORKING SYSTEM. SCHOTT DESIGN INC., IS NOT RESPONSIBLE FOR THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER SYSTEM. 3. THE DESIGN/BUILD CONTRACTOR SHALL COMPLY WITH THE INDIANA BUILDING CODE, THE INDIANA FIRE CODE, AND ALL OTHER APPLICABLE LAWS, CODES, RULES AND REGULATIONS THAT APPLY TO DESIGN AND INSTALLATION OF FIRE SPRINKLER/FIRE SUPPRESSION SYSTEMS. 4. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT. 5. PROVIDE NEW OR RELOCATE EXISTING SPRINKLER HEADS AS REQUIRED. PROVIDE MISSING COVER/ESCUTCHEON PLATES FOR SPRINKLER HEADS WHERE APPLICABLE. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF WORK. KEY PLAN - 2ND FLOOR NOT TO SCALE NOT TO SCALE TENANT/CLIENT COMANY NAME TENANT REPRESENTATIVE SIGNATURE TENANT REPRESENTATIVE PRINTED NAME DATE ALL COSTS INCURRED DUE TO ANY CHANGES REQUESTED AFTER SIGN-OFF OF THESE DOCUMENTS SHALL BE THE FULL RESPONSIBILITY OF THE TENANT/CLIENT. THESE DRAWINGS, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. INDEX OF DRAWINGS T1 1 1 COVER SHEET AND GENERAL PROJECT NOTES L100 LIFE SAFETY PLAN D111 DEMOLITION PLAN Al 1 1 ARCHITECTURAL FLOOR PLAN A121 REFLECTED CEILING PLAN: HVAC / LIGHTING A131 FINISH PLAN A21 1 DOOR SCHEDULE / INTERIOR DETAILS A212 INTERIOR DETAILS E1 1 1 ELECTRICAL PLAN O � } N O � � O � � � � � c� Z '�n - I� N � ,v_i � � a` � I� O Q� � w � <''� U O � N �� �3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W - � � � � = J � O W ' � � Q z Z Q � N Q Zaz J � � N - . � � �� � � � LL � O Q V z Z Q Q J _� � z � z W w �� � � C`7 ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS MARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR COVER SHEET AND GENERAL NOTES CODE SUMMARY 1 � SCOPE OF WORK 2 PREVIOUS USE OF SPACE 3 OCCUPANCY CLASSIFICATION 4 CHANGE OF OCCUPANCY CLASS? 5 TOTAL BUILDING AREA 6 TOTALPROJECTAREA 7 8 9 10 11 12 13 14 OCCUPANCY CALCULATIONS NUMBER OF EXITS SPRINKLER SYSTEM (YES/NO) TOTAL AREA OF ACCESSORY USES TOTAL AREA ON THE FLOOR ACCESSORY AREA EXCEEDS 10� FIRE WALLS, AND/OR OCCUPANCY SEPARATIONS (IF REQUIRED) ASHRAE 90.1 SUMMARY 15 BUILT BEFORE 1978? 1 6 BUILDING CONSTRUCTION TYPE LEGEN D OFFICE REMODEL OF PREVIOUSLY BUILT-OUT OFFICE SPACE B(USINESS) B(USINESS) NO 36,006 SF/FLOOR 20,296 SF SPACE TYPE I GEN. OFFICE X I 4 STORIES a 144, 024 S F AREA � SF PER OCCUPANT � OCCUP LOAD 20,296 SF 100 203 TOTAL OCCUPANTS IN PROJECT AREA REQUIRED:2 PROVIDED:4 YES - EXISTING TO REMAIN 0 SF 36,006 SF NO N/A REQUIREMENTS WILL BE MET (SEE A121) NO II-B Ep EXISTING ELECTRICAL PANEL LOCATION EX EXISTING EXIT- BUILDING STAIR LOCATION � FE FIRE EXTINGUISHER � EXIT SIGN � EMERGENCY LIGHT — — — TRAVEL DISTANCE GENERAL NOTES L1. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION D ETAI LS. L2. EXISTING COMMON CORRIDOR TO REMAIN. EXISTING EXIT SIGNS, FIRE PULLS, FIRE EXTINGUISHERS, ALARM NOTIFICATION APPLIANCES TO REMAIN. RELOCATE EXISTING EXIT SIGNS, FIRE PULLS, FIRE EXTINGUISHERS AND ALARM NOTIFICATIONS AS REQUIRED TO MEET ALL LOCAL AND STATE CODES. LIFE SAFETY NOTES 1. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY. 2. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES), EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS, CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE. 3. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A COMPLETE, WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER SYSTEM. 4. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT. 5. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA 10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY POINT TO A VISIBLE EXTINGUISHER. AREA NOT IN CONTRACT AREA OF WORK VEL DISTANCE = 108' � i�� � �� ♦ i�� � .-' � �� � ��� � �� � i�� � i�� � �� � i�� � �� � i � � �� � � � m � � ♦ � ♦ �� ♦ O �� ♦ e � � ♦ ♦ ♦ ♦ ♦ °N s EX � � I � ♦� I � I � -- ♦ � �` �� ' � i i � ESS � ♦ � � i � �it i � i '� i� � TRAVEL DISTANCE = 94' i �. � i ,- �. � � .�� � OFFI I � 255i, � � � 17'-6"xy5'-11" � � � O256C,E '' � � ^ff ^^ 14'-10"x10'_2" � ENLARGED LIFE SAFETY PLAN 0 4' 8' 16' o � O � � O � � � � � cn Z � '� � ,v_i � � � Q� � w � <,•� U O � N �� �3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z � . � � � � � O W ' � _ Q z Z Q � N Q Zaz �- � � N — . � � �� � �� ��OQ V z Z � Q J _ � � z � z W w �� � � C`7 ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS � � MARI� DATE I DB IDESCRIPTION PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR LIFE SAFETY LEGEN D EXISTING TO BE REMOVED ------ WALL EXISTING TO REMAIN WALL �--_-- PARTIAL HEIGHT WALL �— PARTIAL HEIGHT WALL c�� DOOR AND FRAME � DOOR AND FRAME . -�-{- WINDOW / SIDELIGHT x WINDOW / SIDELIGHT i i i CEILING GRID AND �__t__� TILES, 2'x2' i i DRYWALL CEILING L--__J �-� � <y SUPPLY AIR DIFFUSERS C�E�C] r-� ��J EXHAUST FAN �� =_�� LIGHT FIXTURE, �L _ _ J� FLUORESCENT, 2'x4' r-1 LIGHT FIXTURE, �L=J FLUORESCENT, 2'x2' ,r.� LIGHT FIXTURE, CAN �----i LIGHT FIXTURE, FLUORESCENT �� � �� LIGHT FIXTURE, TRACK L� ?"� LIGHT FIXTURE, SCONCE LIGHT FIXTURE, ,�� PENDANT y� LIGHT SWITCH �y^ EXIT LIGHT ��� EMERGENCY LIGHT �� � ELECTRIC OUTLET(S) �Bi��i��i DATA OR ��� COMMUNICATION OUTLET NOTE: EXISTING FIXTURES THAT ARE REMOVED CAN BE REUSED IF IN GOOD CONDITION. �y 0 v/�� �/� // // D 1 1 � 8,�a3�;� 4 � AREA NOT IN CONTRACT ❑ AREA OF WORK , oo� �, D07 D07 � ;o �— . ��� � D09 rE� k�� . 0� L-_ k�J L=_�J �i � � �� �� ii D05 ��� ������ � � � l'-� 's`� � �'s-�. -�i � � ,-�_-�:E�. � ..� � � � � -- �i ' � �' i �i ,— — — i , , , �i i-6 � I rr---- � I r r 43�� � � D05 D05 � •i �i %� ,.� i . � , i i ra �_� r� i � , . i ,� ,� � � i i i ii �rj,H----� II �xy II �a�-- —�� �°i i i_ �ii ii � i i�� i i i ii ii � ` i i r� r„�- i. i i� %E ��" i?'i ?'-i i D07 I i I ��" ---- —�� ' I 6� ?'f i i r. ��� D04r ��� i� 0 L-�-t' J Il ., � i i. �---� D03 ��� D08 ii.`i� �i �o D08 � ii ,iiir r�iii. r ii Ii ii � D05 � ��, ii ii---�---y . D07 ,,� � '``J' ii � � � C D07 � ? � h ,9A � PLAN NOTES D01 REMOVE EXISTING CABINETRY AND COUNTERTOP. D02 REMOVE EXISTING SINK. NO SERVICE SINKS ARE BEING REMOVED. D03 EXISTING MILLWORK DESK AND BASE CABINETS TO REMAIN. REPAIR TO LIKE NEW CONDITION OR RE-LAMINATE AS REQUIRED. REMOVE EXISTING LAMINATE WORK SURFACE. SEE A131 FOR MORE INFORMATION. REMOVE EXISTING TILE BASE AND REPLACE WITH STAINLESS STEEL TOE KICK TO MATCH HEIGHT. D07 REMOVE EXISTING RECEPTACLE AND/OR SWITCH AS SHOWN. PATCH WALL AND PREPARE FOR NEW FINISHES AS REQUIRED. REMOVE EXISTING PLUMBING IN THIS AREA. PATCH FLOOR AS D08 REQUIRED AND PREPARE TO RECEIVE NEW FINISH. OREMOVE EXISTING FLOOR CORE AND INFILL AS REQUIRED TO D09 MAINTAIN BUILDING CONSTRUCTION TYPE. PREPARE FLOOR FOR NEW FINISHES AS REQUIRED. D04 EXISTING DOORBELL AND COMMUNICATION SYSTEM IN D10 COORDINATE AREA SHOWN FOR REMOVAL OF CEILING W ITH COMMON CORRIDOR/RECEPTION TO REMAIN. CONFIRM THAT O TENANT'S FURNITURE VENDOR. AREA TO RECEIVE NEW SYSTEM IS IN WORKING CONDITION AND RUN DATA FEED TO DEMOUNTABLE WALL SYSTEM WITH NEW BULKHEAD AND CEILING TENANT'S SERVER ROOM. GRID AND TILE. ENSURE LOCATION IS PRECISE WITH LOCATION OF DEMOUNTABLE WALLS. D05 REMOVE EXISTING CEILING GRID, TILE, BULKHEAD, LIGHT FIXTURES AND OTHER CEILING ELEMENTS AS SHOWN AND PREPARE AREA TO BE OPEN TO DECK. SEE SHEET A121 FOR MORE INFORMATION D06 PROVIDE SEPARATE PRICE TO REMOVE ALL EXISTING CEILING GRID, TILE, LIGHT FIXTURES AND OTHER CEILING ELEMENTS AS SHOWN AND PREPARE AREA TO BE OPEN TO DECK. SEE SHEET A121 FOR MORE INFORMATION. BASE BID TO INCLUDE EXISTING GRID AND TILE REMAINING IN PLACE, REWORK EXISTING LIGHT FIXTURES AS NEEDED FOR NEW WALL LAYOUT. DEMOLITION SHOWN IN THIS AREA IS TO BE PART OF SEPARATE PRICE. D1 1 REMOVE AREA OF COMMON CORRIDOR CEILING GRID AND TILE AND PREPARE AREA FOR NEW. REFER TO REFLECTED CEILING PLAN FOR MORE INFORMATION. _ ;o, , � ���%-�� ���� .o,i �' i ��. \p� � �� � �� � . D10 ��%�� � . � ` // ��� / / � �: %�, D.06 � ��� >> D07 � � �'� << `�` ��/ / \\��� � „ c �� � �, � � � 11� i•�i1� \� t � � « � \� �\ \\ �..i � �`� ;�` % �I� ' '/ � �` ' � ' ♦ �\��`..�. \4 �� ` \��\ � � /i/�� \ �' � �� j� w << � � � � � ` � � `y':%�' tiis�� � �' �T ��'`�� �w >> ` �\ �i i- 4 � �\��.. `/ /��` �' � ,) ' .... `` �` � y . ��� �J�. ". ��V K T ��` \\\�. i � i � / / �D w � � �� lJ�. .. - � it � q `� �' M / .. .., �. � �� �� \� � iii1,\ . 1� ��i" r��'1`\ 1 t�.�` �� � i/��,yy�� � � �`� \\ � � �� �`� ..\\� �� j'�� �'�i�`` `�..\\ `V �' ...... ^�_ \` �yii �� ; �\ / `�� � �• << �� � ��y„ ♦ � � �� � � i 4 , ���* i���� �� �.. /� �4�.� �,` �'y �} ..... ��I\` `V �i D09 \�� `�y �i ;�� . � I� , �� �` �%%'� ���%�� ��%'��� � �\�� ����� D07 ��� Q �S'.�i� Vi'�, .. �"i���` ���^���i��. 4 ` � \�\ � ` y O `�'���� ii � `v���,' � \`'�y'�x�- .� n� D10 \O�\1 \\\ i � << �i � „ j� �i 1 � t� 1� ` \�� , D09` ���� D06 r`� -�� � ,.� �� �� �� D07 FL.�` �� � �� �.• •� �� � `,,-�� . ��,: �!' �, D05 � �t �� >> � ��� ��s%�, � �� � �` �,� � � ��` �\ �` ��\ H C,_ ��-�� `L �, ' ii � �� X y `� � \� `V �_. \�� ,� � .,i� . `�'`y �i" �'�� �,.ri�� \y% �\� << �� ,c - � ,. �� �, �� D07 ��s%' ����-�� �4%' 4 =� �_ . � ♦ �� ' `� �4 �,, � �% j� . 1 / �:%, ��Xy �X% �� ��%' �%� D02 ���� r�� �, � ,, � //'i ��p� � ����\�� �4� t`�� �� ��� f�� ^ �\ �� ���� �\_ `� �� �� r ��� j � r \ � \ % � / � � ...4 � �y\ � t� / �.. N. `� ` � � T % .r � � \ \ � \ r �� D07 \�� <<' j; 7 <' � ..� ,`��� ��'` : ���, ��� ��. � � �o� ��� �y %' ��� r �� �"`� D 01 � x ` � ~ ��� `� ,� � � �'� . \, � �� i`k \ \ \ �s"`� rc�t �y���� �� �L�F ��� �` . \�� �� �� �� ;�; : '' `�' `�`� „ �a �� y �- %'' �`� <<' �; ��� y \�� `��� ��%�� D06 �� �.—�� ��:%' ���i �. ,� � �� � t �, � � ; ' �, �� � �� <<-�� ' -o�l D07 ; '��` �������, �� �s- js' ��- �� �� T ��\ �` �� j';� , '�J' �B• t\ \� 1�\� \� ��/ ����\ � �V:� ���' c.'� >>\�� \��a . `� �' ,� , �\� '� ` �' �s� �� �%' �` " r � y� �. � � �' �� � � �� � r t� �1 ii � �\ � �y �/ /li�i1;...; iii1� . .... `�'��' t� �� n �\ � �.� . � � ii1�//l � � �!�X ,' ��:.. . �ii� �� �xy ., `�'��' t`� ,'�\\ ''/�yii � � . ��%�� ���� j� � ��` D06 �w�s� '� .� '`� ��%' � � � � , , � � � / t� �k . wi1 �Vi � , ii � �� � a ��/ ���� Y� � T „ ` �� �� T\ � ��� � � ..... `y's���C?i iii1� ��i� �,(�y • a / ��� 1 � ` >> � � �i � `� i �! � � .. � /i .� ; . M � � C� � �1 / ` � � �� � ' �� s%� r �s%'�� ��' �`� � �� . � x � \ _ � ;'%���` � �,\ �k � „ ' �`' ,' \� y ` � i ��\ `��� �a ��y '.i�` ����i ��� a,i .. Y�� �l n � .. i i�� � iii �\ . `w i � � � �i.'�� �` � . �\ %� � >> w � \ \ i� �i1 �� V� �,� X y. T � � � � 'f� �? .. '� y � � �� � 1 �(7\ i i �,/�� ��\ � \ � \ \\ ' /a. � i i1� \ y ii �.�i � r ii 1 , � � �_ � 5' � - �s%�, : ��� �� �y�� �, D07 �\�-'���� „ \ ,� D07 y �ii��\ ` ..i1 � I .. � ` ���\ % i \ \ � \\ \ '�a Viz,� �` � Vi",i ��\�`\�/ ��<<// ,� \�\ s��� `\ �i ,� �'� ' D09 '" ����` �\\ �M�%' �\ \� �� �� 1 D01 � �p. D07 �� � � �� � � � � �� � �a �., �\ �� ���,., / \ \� O�T Y�F� � ���I �� �� \� ^ �� M �O � �) � � �(�fi� �. M . � f �i� �� ii1 �� �� ii1 Qpi �i .... '/��` ' . . \��.:� . �\ t� �) \� ��__ \� i � \ t� \ � << � �,�� �` `4�� �, �;s�� D06 �\� ���� � ��.s%'`� �� � �� °�a r� � �: , �� i t` �� � i� ii� J' ... �y� .... i Gr � i � �� I �,:�/� /�/ /� \j� �� ii� , /�,� �, ' - ��s%�, D07 ��� ��' �' � � D07 � c�� � � �a � � �� � �� �� .s-'h � :, � �� s� �, , ���-�� ���� � `� � ���o` '' `� �� � �� � �' �� ii �� \ X y � i i \ 1 �� �� � i � i \ i \ ii � i �i \� � /�Y �3 �� // /�i�i�' � / ��j�` Q � / // \\ i i��/ \\_Q �.� . �// / � ��7 ��� `\\\ �1/ ��% — \� J�° i � �� 1� ..i 1 ' `� _ �� �� <<� � �, D05 �- . �\� ���. �o� v � �� >� � *` � J �\ ��` ��\� r �� � �` '_ � �D�7 �� .��� Y���`y �' D05 �� �� „�' � � � �;, �, _�'` � �, �� ,. - �` �\ � � �\� `�'' s �� G9 ' .� '� t \ \� �\ � �1 �� �\ �� �\ �y �a \ ` �y �j � D EMO �a D07 LITION PLAN 0 4' 8' 16' N 3/32" = 1'-0" O � O � � O � } � � cn Z � '� � ,v_i � � � Q� � w � <''� U O � N � � � 3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W — � � � � � � � O W ' � � � Z Z Q Q N Q Zaz J � � � — . � � �� � � � LL � O Q V z Z Q Q J � � � 7 L � z W � � � 0 ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS MARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR DEMOLITION PLAN ARCHITECTURAL LEGEND GENERAL NOTES PLAN NOTES NEW CONSTRUCTION WALL W? � PARTIAL HEIGHT WALL �a WINDOW / SIDELIGHT ## DOOR AND FRAME (SEE DOOR SCHEDULE) EXISTING TO REMAIN WALL � PARTIAL HEIGHT WALL T�- WINDOW / SIDELIGHT ## DOOR AND FRAME NOTE: IF IN GOOD CONDITION, EXISTING DOORS SALVAGED FROM DEMOLITION CAN BE SUBSTITUTED FOR NEW DOORS. WALL TYPES NOTE: ALL PLAN DIMENSIONS ARE FROM FACE TO FACE OF FINISHED WALL. ALL WALLS ARE TO BE W1 UNLESS OTHERWISE NOTED. NOT ALL WALL TYPES LISTED BELOW ARE NECESSARILY USED ON THIS PROJECT. REFER TO REFLECTED CEILING PLAN FOR CEILING HEIGHTS. W� WALL WITH INSULATION 35/g " METAL STUDS AT 16" O.C.; ONE LAYER OF 5/g" TYPE "X" GYPSUM BOARD EACH SIDE; EXTEND WALL TO UNDERSIDE OF CEILING; FIBERGLASS SOUND BATT INSULATION INSIDE WALL AND 2'-0" EACH SIDE OF WALL ABOVE CEILING W2 STANDARD WALL 35�g " METAL STUDS AT 16" O.C.; ONE LAYER OF 5/8' TYPE "X" GYPSUM BOARD EACH SIDE; EXTEND WALL TO UNDERSIDE OF CEILING DEMISING WALL TO DECK W3 WITH INSULATION 35/g" METAL STUDS AT 16" O.C.; ONE LAYER OF 5/g" TYPE "X" GYPSUM BOARD EACH SIDE; EXTEND WALL TO UNDERSIDE OF DECK; FIBERGLASS SOUND BATT INSULATION INSIDE WALL W4 PARTIAL HEIGHT WALL 35/g " METAL STUDS AT 16" O.C.; ONE LAYER OF 5/g" TYPE "X" GYPSUM BOARD EACH SIDE; EXTEND WALL TO 47" A.F.F.; PROVIDE 1" STEEL PIPE ANCHORS INTO CONCRETE FLOOR FOR SUPPORT AS REQUIRED; PROVIDE 6"xl"SOLID SURFACE (SS_)TOP CAP WITH SQUARE EDGE PROFILE. ■ ' ■ AREA NOT IN CONTRACT AREA OF WORK l. SEE ELECTRICAL PLAN FOR INTENDED FURNITURE LAYOUT. 2. REFER TO FINISH PLAN FOR ALL WALLS PAINTED PT_ THAT REQUIRE LEVEL 5 FINISH. ALIGN FINISHED WALL SURFACES. PROVIDE SAME THICKNESS A01 STUDS AS EXISTING WALL AT DOOR INFILLS OR WHERE NEW WALLS ARE IN LINE WITH EXISTING WALLS. PROVIDE PLYWOOD PHONE BOARD, 4'x8'x4', PAINTED WITH FIRE A02 RETARDANT PAINT TO MATCH ADJACENT WALL FINISH. VERIFY LOCATION WITH TENANT PRIOR TO INSTALLATION. A03 NEW FIRE EXTINGUISHER TO BE PROVIDED AND INSTALLED BY CONTRACTOR. ALL FIRE EXTINGUISHERS ARE TO BE INSTALLED ACCORDING TO NFPA 10. A04 PROVIDE NEW 24" DEEP SOLID SURFACE (SS1) COUNTER AT 36" A.F.F.; SCRIBE COUNTER TO WALL AND PROVIDE BEAD OF CLEAR SILICONE AT WALL TO COUNTER TRANSITION. CASEWORK CONTRACTOR TO INSTALL RAKKS EH-1818-FM BRACKET AS NEEDED PRIOR TO INSTALLATION OF DRYWALL. COORDINATE APPROVAL OF SHOP DRAWINGS WITH DRYWALL INSTALLATION AS NEEDED. CONFIRM THAT EXISTING WALL MATCHES WALL TYPE "Wl". IF NOT, A05 ALTER EXISTING WALL AS REQUIRED TO MATCH "W1". PROVIDE ADDITIONAL BLOCKING IN WALL AS REQUIRED FOR TENANT'S WALL MOUNTED TELEVISION; COORDINATE EXACT A06 LOCATION WITH TENANT. A07 PROVIDE LEVEL 5 FINISH PER MANUFACTURER'S RECOMMENDATIONS FOR WALL INDICATED TO ALLOW FOR SMOOTH APPLICATION OF INTENDED SPECIALTY PAINT AS NOTED ON SHEET A131. A08 CONFIRM THAT EXISTING WALL MATCHES WALL TYPE "W3". IF NOT, ALTER EXISTING WALL AS REQUIRED TO MATCH "W3". A09 PROVIDE SEPARATE PRICE FOR WALL TYPE TO BE "W3" WHERE CEILING IS OPEN TO DECK. IF WALL IS EXISTING, MAKE NECESSARY ADJUSTMENTS SO THAT CONSTRUCTION MATCHES "W3". SEE REFLECTED CEILING PLAN FOR MORE INFORMATION. A10 WHERE CEILING IS EXPOSED, EXTEND DRYWALL AT EXTERIOR WALL TO DECK. A1 1 PROVIDE SEPARATE PRICE FOR DRYWALL TO EXTEND TO DECK AT EXTERIOR WALL WHERE CEILING IS EXPOSED. Al2 PROVIDE 3'-0" X 8'-0" DRYWALL WRAPPED OPENING FOR SLIDING BARN DOOR; SEE DOOR SCHEDULE FOR MORE INFORMATION. A13 EXISTING MILLWORK DESK AND BASE CABINETS TO REMAIN. REPAIR TO LIKE NEW CONDITION OR RE-LAMINATE AS REQUIRED. REMOVE EXISTING LAMINATE WORK SURFACE. SEE A131 FOR NEW COUNTERTOP INFORMATION. REMOVE EXISTING TILE BASE AND REPLACE WITH STAINLESS STEEL TOE KICK TO MATCH HEIGHT. P01 PROVIDE POTABLE HOT AND COLD WATER AND SANITARY WASTE AND VENT PIPING FOR SINKS. REFER TO LANDLORD FOR SOURCE OF HOT WATER AND LOCATION ALLOWED IN THIS BUILDING. � P02 PROVIDE WATER LINES FOR COFFEE, WATER COOLER AND REFRIGERATOR. CONFIRM EXACT LOCATIONS WITH TENANT. P03 PROVIDE SEPARATE PRICE FOR WATER LINES FOR COFFEE, ICE MAKER AND FILTERED WATER DISPENSER. CONFIRM LOCATIONS WITH TENANT. ARCH ITECTU RAL PLAN 0 4' 8' 16' 3/32" = 1'-0" o � O � � o � } � � cn Z � '� � ,v_i � � � Q� � w � <''� U O � N �� �3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W - H � — (�i � � � O W ' � � Q z Z Q � N Q Zaz J � � � - . � � �� � �� LL � O Q V z Z Q Q J � � � z � z W w �� � O c� ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS MARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR ARCHITECTURAL FLOOR PLAN LEGEN D NEW OR RELOCATED EXISTING TO REMAIN �LIGHT FIXTURE, 2'x4', � LIGHT FIXTURE, 2'x4', FLUORESCENT, PARABOLIC FLUORESCENT, PARABOLIC �LIGHT FIXTURE, 2'x2', � LIGHT FIXTURE, 2'x2', FLUORESCENT. PARABOLIC FLUORESCENT. PARABOLIC COOPER LIGHTING, 1' X 8' �� CORELITE: DIVIDE LED SUSPENDED LIGHT FIXTURE, MOUNTING HEIGHT: TBD CONTACT: MELINDA DYKSTRA 317.407.0038 � RECESSED LIGHT FIXTURE: HALO LED MODULE 1200 SERIES ML561 2930 / 0-1 OV DC DIMMABLE MODULE, WHITE TRIM RING � LIGHT FIXTURE, PENDANT, MOUNTING HEIGHT: TBD. MATERIAL ALLOWANCE OF $800 EA. NL NIGHT LIGHT Q EXIT LIGHT FIXTURE � EMERGENCY LIGHT FIXTURE �N LIGHT SWITCH �N3 LIGHT SWITCH, 3-WAY �ND LIGHT SWITCH, DIMMER �NG SWITCH, GARBAGE DISPOSAL � — � LIGHT CIRCUIT CEILING GRID, SUSPENDED, 2'x2' .,�<.^_;.:.; .. ..� :.a•.:.r:;!. ^��' •::;' � GYPSUM BOARD r,..:�;.; .;�k;;�< CEILING :,.. EXPOSED TO DECK �RELOCATED DIFFUSER, LAY-IN, 2'x2' RELOCATED � DIFFUSER, LAY-IN, 4"x4' �� LIGHT FIXTURE, 1'x4', FLUORESCENT, INDIRECT � RECESSED LIGHT FIXTURE � LIGHT FIXTURE, PENDANT � EXIT LIGHT FIXTURE � EMERGENCY LIGHT FIXTURE � LIGHT SWITCH �3 �D �G LIGHT SWITCH, 3-WAY LIGHT SWITCH, DIMMER SWITCH, GARBAGE DISPOSAL ��--�� LIGHT CIRCUIT CEILING GRID, SUSPENDED, 2'x2' GYPSUM BOARD CEILING � EXISTING DIFFUSER, LAY-IN, 2'x2' � EXISTING DIFFUSER, LAY-IN, 4"x4' NOTE: IF IN GOOD CONDITION, EXISTING H.V.A.C. DEVICES AND CEILING TILES SALVAGED FROM DEMOLITION CAN BE SUBSTITUTED FOR NEW. NO NEW HVAC DUCTWORK IS TO BE INSTALLED PER THIS SHEET. +9'-�A. F. F. +g'-�A.F.F. :UCTURAL DECK OVE. NEW SUSPENDED PAINTED BRIGHT CEILING CEILING TILE & GRID WHITE SECTION - BULKHEAD RELOCATE DIFFUSERS & n rvr�i i�T ir nr�i iinrr� 0 6" 1' 2' GENERAL NOTES 1. REUSE EXISTING CEILING GRID AND TILE UNLESS OTHERWISE NOTED. EXISTING GRID IS 2x2 AT 9'-0" A.F.F. TILES ARE 2x2 ACOUSTICAL LAY IN TILES. REPAIR ANY DAMAGED GRID AND REPLACE ANY DAMAGED TILES WITH NEW TO MATCH EXISTING. 2. PROVIDE LIKE CEILING TILES IN INDIVIDUAL ROOMS WHERE POSSIBLE TO CREATE UNIFORM LOOK. 3. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS, CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE. 4. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1, CONTRACTOR MUST NOTIFY SDI. ASHRAE WATTAGE REQUIREMENTS WILL NEED TO BE MET. 5. IF PROJECT CRITERIA REQUIRES ALL NEW SWITCHES TO BE OCCUPANCY SENSORS, PROVIDE COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED, OR RELAY TIME CLOCK CONTROLS (COORDINATE WITH SDI). EXISTING SWITCHES TO BE CONVERTED IF REQUIRED BY CODE. b. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH ALL APPLICABLE CODES. MECHANICAL DIFFUSER RELOCATION *REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION � AREA NOT IN CONTRACT ❑ AREA OF WORK MECHANICAL NOTES 1. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE DRAWINGS. NO NEW MAIN MECHANICAL APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED. ALL MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND FLEX DUCT PER NEW WALL LAYOUT. NO NEW HARD DUCTWORK OR EQUIPMENT IS BEING ADDED; MECHANICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE INDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES. PLAN NOTES OCONTROL ENTRY, CORRIDOR AND HUDDLE LIGHTING WITH O PROVIDE SEPARATE PRICE FOR 4" WIDE DRYWALL BULKHEAD TO R01 3-WAY SWITCH AT THIS LOCATION. PROVIDE MULTIPLE SWITCHES R�g EXTEND FROM 8'-1 1" AFF TO DECK. HORIZONTAL FACE OF AS REQUIRED. BULKHEAD TO BE PAINTED BRIGHT CEILING WHITE. SEE FINISH PLAN FOR VERTICAL FACE PAINT COLOR(S). SEE DETAIL 3/A121 R02 CEILING TO BE EXPOSED TO DECK IN THIS AREA. REMOVE AS FOR MORE INFORMATION. (BASE BID: EXISTING 2X2 GRID TO MUCH OF THE EXPOSED CONDUIT, PIPING, JUNCTION BOXES REMAIN) AND MISCELLANEOUS UNUSED EQUIPMENT AS POSSIBLE. REMOVE LOW PRESSURE SUPPLY BRANCH LINE DUCT AND O AT DEMOUNTABLE WALL OFFICES, PROVIDE 4" WIDE PERIMETER REPLACE WITH NEW RIGID SPIRAL DUCT AND RECTANGULAR R10 DRYWALL BULKHEAD FROM TOP OF DEMOUNTABLE WALLS TO SUPPLY DIFFUSERS AS REQUIRED. CLEAN AND PREPARE FOR DECK; COORDINATE EXACT HEIGHT AND LOCATION WITH DRYFALL PAINT AS SCHEDULED. PAINT EXISTING EXPOSED TENANT'S FURNITURE VENDOR. PROVIDE NEW BUILDING CEILING DECK, EXPOSED DUCTWORK, SPRINKLER PIPING, STANDARD 2'X2' CEILING GRID AND TILE AT 8'-0" AFF AS SHOWN. JUNCTION BOXES, CONDUIT, STRUCTURAL BEAMS AND SEE DETAIL 2/A121 FOR MORE INFORMATION. HORIZONTAL FACE FIREPROOFING IN ACCORDANCE WITH NFPA 13 6.3.8. OF BULKHEAD TO BE PAINTED BRIGHT CEILING WHITE. SEE FINISH PLAN FOR VERTICAL FACE PAINT COLOR(S). R03 PROVIDE 4" WIDE DRYWALL BULKHEAD TO EXTEND FROM 8'-1 1" AFF TO DECK. HORIZONTAL FACE OF BULKHEAD TO BE PAINTED O PATCH EXISTING DRYWALL CEILING AS REQUIRED AND PAINT BRIGHT CEILING WHITE. SEE FINISH PLAN FOR VERTICAL FACE R1 1 gRIGHT CEILING WHITE. PAINT COLOR(S). SEE DETAIL 3/A121 FOR MORE INFORMATION. PROVIDE SEPARATE TEMPERATURE ZONE FOR THIS ROOM; R04 PATCH COMMON CORRIDOR CEILING GRID AND TILE AS R� 2 COORDINATE EXACT REQUIREMENTS WITH TENANT. REQUIRED PER NEW WALL LAYOUT. PROVIDE DRYWALL CEILING AT 9'-0" AFF; AT EXPOSED CEILING OR05 CONTROL OPEN OFFICE AREA LIGHTING WITH 4-WAY SWITCH AT R13 TRANSITION, EXTEND DRYWALL TO DECK. HORIZONTAL FACE OF THIS LOCATION. PROVIDE MULTIPLE SWITCHES AS REQUIRED. BULKHEAD TO BE PAINTED BRIGHT CEILING WHITE. SEE FINISH PLAN FOR VERTICAL FACE PAINT COLOR(S). FINISH DRYWALL R06 PROVIDE NEW 2'X2' CEILING GRID AND TILE TO MATCH AND TIE CLEANLY WHERE IT MEETS DECK TO ALLOW FOR CRISP PAINT INTO EXISTING AT THIS LOCATION. TRANSITION. R07 COORDINATE SWITCHING FOR LIGHT FIXTURE(S) IN DEMOUNTABLE WALL OFFICES WITH FURNITURE VENDOR. OR08 PROVIDE SEPARATE PRICE FOR EXPOSED CEILING IN THIS AREA. '� : REMOVE AS MUCH OF THE EXPOSED CONDUIT, PIPING, JUNCTION BOXES AND MISCELLANEOUS UNUSED EQUIPMENT AS � R12'` POSSIBLE.REMOVE LOW PRESSURE SUPPLY BRANCH LINE DUCT - � AND REPLACE WITH NEW RIGID SPIRAL DUCT AND � � ��� RECTANGULAR SUPPLY DIFFUSERS AS REQUIRED. CLEAN AND `c � ' � Y PREPARE FOR DRYFALL PAINT AS SCHEDULED. PAINT EXISTING � ''� � FXPC�SFn CFII ING f�FCK. FXPC)SFf� f�l1CTWC�RK. SPRINKI FR \\ \ _ FINISH DRYWALL CLEANLY WHERE IT MEETS DECK TO ALLOW FOR CRISP PAINT TRANSITION +8'-1 1 " A. F. F. � \ GYP. BD. ON MTL. STUD, EXTENDED TO DECK; ALL VISIBLE SIDES TO BE PAINTED BRIGHT CEILING WHITE STRUCTURAL DECK ABOVE. EXISTING SUSPENDED CEILING TILE & GRID SECTION - BULKHEAD 0 6" 1' 2' � - REFLECTED CEILING PLAN 0 4' 8' 16' 3/32" = 1'-0" O � O � � O � } � � cn Z � '� � ,v_i � � � Q� � w � <''� U O � N � � � 3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � 0 � O � N z W - H � - (�i � J � O W ' � _ Q Z Z Q Q N Q Zaz � � � � - � Y � �� � �� ��OQ V z Z � Q J � � � 7 L � Z W w �� � � C`7 ISSUE � DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS IMARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR REFLECTED CEILING PLAN LEGEN D FLOOR COVERINGS CARPET CPT1 MFG: J+J FLOORING TYPE: MODULAR CARPET TILE PATTERN: ELEVATED 7074 COLOR: 2064 VIEW INSTALL: MONOLITHIC (IN DIRECTION OF ARROWS ON PLAN) CPT2 MFG: SHAW TYPE: PATTERN: COLOR: DIRECT GLUE BROADLOOM SWITCH 5A205 03557 OUTLOOK CPT3 MFG: J+J FLOORING TYPE: 12X48 PLANK PATTERN: INDEX 7009 COLOR: 1831 TABLE INSTALL: ASHLAR (IN DIRECTION OF ARROWS ON PLAN) VINYL COMPOSITION TILE VCT1 MFG: ARMSTRONG SIZE: 12"xl2" PATTERN: STANDARD EXCELON COLOR: 51861 SOFT WARM GRAY LUXURY VINYL TILE NOTE: PROVIDE SKIMCOAT OF ARDEX LEVELING LATEX AS NEEDED FOR SMOOTH SUBFLOOR THAT WILL NOT ALLOW FOR TELEGRAPHING OF IMPERFECTIONS IN THE FLOOR LVT1 MFG: SHAW SIZE: PATTERN: COLOR: ��2 MFG: SHAW SIZE: PATTERN: COLOR: LVT3 MFG: SHAW SIZE: PATTERN: COLOR: LVT4 MFG: SHAW SIZE: PATTERN: COLOR: LVT5 MFG: SHAW SIZE: PATTERN: COLOR: WALL BASE HEXAGON 0551V LEVEL 51515 BLANK HEXAGON 0551V LEVEL 51535 WEIGHT HEXAGON 0551V LEVEL 51436 STEADY HEXAGON 0551V LEVEL 51429 BALANCE HEXAGON 0551V LEVEL 51668 SCALE MFG: JOHNSONITE VB1 TYPE: 4" VINYL COVE,%$' GAUGE COLOR: 08 ICICLE W PAINT / WALLCOVERING PT1 MFG: SHERWIN WILLIAMS TYPE: PROMAR 200 ZERO VOC INTERIOR LATEX COLOR: SNOWBOUND SW7004 FINISH: EGGSHELL PT2 MFG: SHERWIN WILLIAMS TYPE: PROMAR 200 ZERO VOC INTERIOR LATEX COLOR: ARGOS SW7065 FINISH: EGGSHELL PT3 MFG: SHERWIN WILLIAMS TYPE: PROMAR 200 ZERO VOC INTERIOR LATEX COLOR: LOCH BLUE SW6502 FINISH: EGGSHELL PT4 MFG: SHERWIN WILLIAMS TYPE: PROMAR 200 ZERO VOC INTERIOR LATEX COLOR: DIGNITY BLUE SW6804 FINISH: EGGSHELL PT5 MFG: SHERWIN WILLIAMS TYPE: PROMAR 200 ZERO VOC INTERIOR LATEX COLOR: INVIGORATE SW6886 FINISH: EGGSHELL PT6 MFG: MDC WALLS/ FUZE DRY ERASE PAINT TYPE/ COLOR: CLEAR NOTE: MUST BE INSTALLED BY CERTIFIED INSTALLER. DRYWALL MUST BE PREPARED TO LEVEL 5 FINISH AS RECOMMENDED BY MANUFACTURER PRIOR TO INSTALLATION OF PRODUCT CONTACT: BRENDA CAPUANO AT 317-383-6995 FOR INSTALLATION CERTIFICATION AND RECOMMENDATIONS, PRICING AND KIT SIZES MFG: SHERWIN WILLIAMS PT7 TYPE: PRIMER: PRO-CRYL / TOP COAT: PRO INDUSTRIAL RECATALYZED WATERBASED EPDXY K46W 151 COLOR: -- FINISH: SEMI-GLOSS INSTALL: PREP AND INSTALL PER MANUFACTURER'S RECOMMENDATIONS FOR MAXIMUM ADHESION. THIS INCLUDES CLEANING AND SCUFF SANDING THE DOORS PRIOR TO APPLYING NEW FINISH. APPLY USING SPRAY APPLICATION. PT8 MFG: KRYLON (EXPOSED CEILING) TYPE: ACRYLIC DRYFALL COLOR: DIGNITY BLUE SW6804 FINISH: EGGSHELL PT9 MFG: KRYLON (EXPOSED CEILING) TYPE: ACRYLIC DRYFALL COLOR: INVIGORATE SW6886 FINISH: EGGSHELL PLASTIC LAMINATE / SOLID SURFACE PL1 MFG: FORMICA COLOR: BRITE WHITE 459-90 (GLOSS) PL2 MFG: FORMICA COLOR: PLATINUM DROPS 8825-58 PL3 MFG: WILSONART COLOR: CRISP LINEN 4942-38 PL4 MFG: FORMICA COLOR: CITADEL WARP 5882-58 PL5 MFG: FORMICA COLOR: BLUEBERRY HALFTONE 6618-58 SS1 MFG: DUPONT - ZODIAQ COLOR: STRATUS WHITE PLAN NOTES F01 PROVIDE JOHNSONITE SLIMLINE SLT-XX-F PROFILE TRANSITION STRIP AT FLOORING TRANSITION; COLOR: TBD. CONTRACTOR MUST PROVIDE LEVELING LATEX SUCH THAT HEIGHTS OF MATERIALS ARE APPROPRIATE FOR USE WITH SPECIFIED PROFILE TRANSITION. BE AWARE TRANSITION STRIP MUST BE ORDERED IN A TIMELY MANNER AS IT IS NOT ALWAYS IMMEDIATELY AVAILABLE. OPAINT FULL WALL AS NOTED AND PROVIDE PTb FROM 3'-0" AFF TO F02 7'-0" AFF WITH CLEAR ANODIZED ALUMINUM TRIM PIECE AT TRANSITION POINTS. FULL WALL TO HAVE LEVEL 5 DRYWALL FINISH. PROVIDE SEPARATE PRICE TO REMOVE GLASS TRANSACTION TOP F03 AND REPLACE WITH SAME SIZE AND THICKNESS CAMBRIA QUARTZ TRANSACTION TOP. OPATCH COMMON CORRIDOR FINISHES TO MATCH EXISTING AS F04 REQUIRED. VERIFY POTENTIAL MATERIAL STOCK WITH BUILDING MANAGEMENT. OEXPOSED CEILING TO BE PAINTED (PT8). REFER TO REFLECTED F05 CEILING PLAN FOR MORE INFORMATION. OEXPOSED CEILING TO BE PAINTED (PT9). REFER TO REFLECTED F06 CEILING PLAN FOR MORE INFORMATION. � AREA NOT IN CONTRACT ❑ AREA OF WORK FINISH PLAN N 3/32" = 1'-0" o � O � � O � � � � � cn Z '�n — I� N � ,v_i � � � Q� � w � <''� U O � N � � � 3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W - � � - (�i � J � O W ' � � Q � z Z Q � N Q Zaz J � � N - . � � �� � � � LL � O Q V z Z Q Q J � � � z � Z W � � � � C`7 ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS MARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR FINISH PLAN �`� _ TO EXISTING Y STACK � ��%2�v. I c��. � � I J x� I � �J � � � �� � � � � � I c��. �/„� � I � � � � � I �EXIST SINK I 4"V. 2°w. � F.F. I NOTE: REFER TO FLOORPLAN I AND CASEWORK ELEVATIONS FOR SINK LOCATIONS. � ;_� � z�w. � ' � F.F. 2"w. EXIST TO 4��w• BUILDING DRAIN , RISER DIAGRAM A21 1 TYPICAL ALL SINGLE LOCATIONS, NOT TO SCALE ANGLED PORTION OF WALL; CONFIRM ANGLE IN FIELD AND SCRIBE COUNTERTOP TO WALL AND SEAL WITH CLEAR CAULK 8" DEEP SOLID SURFACE (SSl ) TOP CAP WITH SQUARE EDGE, CENTERED ON WALL BELOW; VERIFY ANGLE IN FIELD 24" DEEP SOLID SURFACE (SSl ) COUNTERTOP, SCRIBE TO WALL AND SEAL WITH CLEAR CAULK. SUPPORT SUPPORT TOP AS NEEDED WITH RAKKS EH-1818-FM ATTACHED TO METAL STUDS WITH WOOD BLOCKING AS NEEDED. DRYWALLTOBE INSTALLED OVER VERTICAL SUPPORT. ���,+ � i o'-o" � ELEVATION - ENTRY 201 ANGLED PORTION OF WALL; CONFIRM ANGLE IN FIELD, COUNTERTOP AND BACKSPLASH TO EXTEND TO ANGLE 8" DEEP SOLID SURFACE (SSl ) TOP CAP WITH SQUARE EDGE, CENTERED ON WALL BELOW; VERIFY ANGLE IN FIELD 15" X 19" STAINLESS STEEL SINGLE BOWL UNDERMOUNT SINK, WITH DELTA: TRINSIC FAUCET, ARCTIC STAWLESS FINISH # 1959LF-AR 25" DEEP SOLID SURFACE (SS1) COUNTERTOP WITH 4" H BACKSPLASH aSE CABINETS (PL1 � EE CASEWORK NOTE 2) � 1'-6" � 1'-3" � 2'-9" � 2'-0" � 1'-4„ I I �„+ � LI. � ELEVATION - ENTRY 201 DOOR/FRAME TYPES CV � 6'-4" 2�� 2,� F5 �� � �.�� D5 CV � 4'-6" 2" 3'-0" 2 1'-0" 2�� SLIDING DOOR HARDWARE AS SCHEDULED, TOP TRACK 3'-0"W x 8'-0"H DRYWALL WRAPPED p OPENING � F4 0 1' 2' 4' Ya" TEMPERED GLASS CV 00 2'-10" 2" 2'-6" 2 F3 25" DEEP SOLID SURFACE (SS1) COUNTERTOP, SCRIBE TO WALL AND SEAL WITH CLEAR CAULK CV � FILLER PANEL, TYP. BASE CABINETS (PLl ) (SEE CASEWORK NOTE 2) 0 1' 2' 4' CASEWORK NOTES 1. PROVIDE ADA COMPLIANT A.W.I. CUSTOM GRADE, FLUSH-OVERLAY CABINETS. FABRICATE WITH PLASTIC LAMINATE (PL1) COVERED M.D.O. BOARD WITH 4" WIRE PULLS. PROVIDE VINYL BASE AS SCHEDULED. COORDINATE WITH ELEVATIONS FOR QUANTITIES. 24" DEEP COUNTERTOPS 23" DEEP BASE CABINETS 12" DEEP UPPER CABINETS 2. PROVIDE A.W.I. CUSTOM GRADE, FLUSH-OVERLAY CABINETS. FABRICATE WITH PLASTIC LAMINATE COVERED M.D.O. BOARD WITH 4" WIRE PULLS. PROVIDE VINYL BASE AS SCHEDULED. COORDINATE WITH ELEVATIONS FOR QUANTITIES. 25" DEEP COUNTERTOPS 24" DEEP BASE CABINETS 12" DEEP UPPER CABINETS 5'-b" 2" 3'-0" 2 2'-0" 2�, F2 12'-0" 3'-0" 3'-0" 3'-0" 3'-0" 4" STAINLESS STEEL TOP RAIL / \ 1 /2" TEMPERED / \ GLASS 0 PROVIDE ONE PULL ON o EACH SIDE OF DOOR ao (TOTAL COUNT 4), AS � / NOTED IN REMARKS 4" STAINLESS STEEL BOTTOM RAIL I 2'-9" I 2'-9" I 2'-9" I 2'-9" I 2'-9" I ELEVATION - CONFERENCE 202 %4' TEMPERED GLASS � D3 0 o� CV � 3'-4" 2" 3'-p" 2 Fl � � � D2 BEAD IGHT, y4' =RED i 0 � 0 1' 2' 4' � Dl DOOR SCHEDULE NUM. � � 02 03 � � 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 26 27 28 29 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 60 DIMENSIONS EXISTING 3'-0"x8'-0"xl %4' 3'-0"x8'-0"x13/4' (PAIR) 2'-6"x8'-0"x 1 %4 ' 3'-0"x8'-0"xl %4' 2'-6"x8'-0"x 1 %4 ' 3'-0"x8'-0"xl %4' 3'-4"x8'-3"xl %4' 3'-4"x8'-3"xl %4' EXISTING EXISTING 3'-0"x8'-0"xl %4' 3'-0"x8'-0" (PAIR) 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' EXISTING 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' EXISTING 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' EXISTING 3'-0"x8'-0"xl %4' EXISTING 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' EXISTING EXISTING 3'-0"x8'-0"xl %4' EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' 3'-0"x8'-0"xl %4' EXISTING EXISTING EXISTING 3'-0"x8'-0"x13/4' (PAIR) EXISTING DOORS FRAME HARDWARE TYPE MATERIAL FINISH TYPE MATERIAL FINISH SET -- -- -- -- -- -- C R, E L R 7 D2 SOLID CORE STAIN TO F4 HOLLOW PT7 CR, ES, CL, SL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F5 HOLLOW PT7 PP, CL, KS R6 BIRCH VNR. MATCH EXIST. METAL D3 SOLID CORE STAIN TO F3 HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL p� SOLID CORE STAIN TO F� HOLLOW SEE REMARK CR, ES, CL, SL R3 BIRCH VNR. MATCH EXIST. METAL D3 SOLID CORE STAIN TO F3 HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F2 HOLLOW PT7 PS BIRCH VNR. MATCH EXIST. METAL D5 SOLID CORE STAIN TO 3'-0"x 8'-0" DRYWALL WRAPPED SEE REMARK R2 BIRCH VNR. MATCH EXIST. OPENING D5 SOLID CORE STAIN TO 3'-0"x 8'-0" DRYWALL WRAPPED SEE REMARK R2 BIRCH VNR. MATCH EXIST. OPENING SEE __ __ __ __ PT7 OL Rl REMARK SEE __ __ __ __ PT7 OL Rl REMARK D2 SOLID CORE STAIN TO F2 HOLLOW PT7 PS BIRCH VNR. MATCH EXIST. METAL D4 HERCULITE GLASS SYSTEM DRYWALL WRAPPED OPENING SEE REMARK R5 D2 SOLID CORE STAIN TO F2 HOLLOW PT7 PS BIRCH VNR. MATCH EXIST. METAL p� SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL SEE __ __ __ __ PT7 OL Rl REMARK D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL p� SOLID CORE STAIN TO F� HOLLOW PT7 CR, ES, CL, SL BIRCH VNR. MATCH EXIST. METAL SEE __ __ __ __ PT7 OL Rl REMARK D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL p� SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL SEE __ __ __ __ PT7 OL Rl REMARK D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL SEE __ __ __ __ PT7 OL Rl REMARK SOLID CORE STAIN TO HOLLOW �� BIRCH VNR. MATCH EXIST. F� METAL SEE REMARK CR, ES, CL, SL R3 D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL SEE REMARKS Rl. IF POSSIBLE, CUT NEW LIGHT KIT INTO EXISTING DOOR TO MATCH DOOR TYPE "D2". IF NOT POSSIBLE, PROVIDE NEW "D2" DOOR AT THIS LOCATION. R2. PROVIDE 3'-0" W X 8'-0"H DRYWALL OPENING WITH WALL MOUNTED HARDWARE REQUIRED FOR SLIDING "BARN" DOOR ASSEMBLY. PROVIDE BOTTOM CATCH AND STOP AS REQUIRED. HARDWARE TO BE REAL CARRIAGE DOORS STAINLESS STEEL BOX RAIL SLIDING HARDWARE #SB-400-S WITH STAINLESS STEEL 24" SWISS ROD / 15" FLUSH PULL SET. R3. TENANT SIDE OF FRAME TO BE PAINTED (PT_); CORRIDOR SIDE OF FRAME TO MATCH BUILDING STANDARD PUBLIC CORRIDORS. R4. PROVIDE SEPARATE PRICE FOR BLINDS ON LIGHT KIT IN DOOR AT THIS LOCATION. R5. PROVIDE CONCEALED CLOSERS AND PULL ON EACH SIDE OF EACH DOOR (4 TOTAL) TO MATCH EXISTING SUITE ENTRY PULLS. R6. PROVIDE PULL ON EACH SIDE OF EACH DOOR (4 TOTAL) TO MATCH EXISTING SUITE ENTRY PULLS. R7. EXISTING DOOR PULLS AND CLOSERS TO REMAIN. DOOR/FRAME NOTES 1. REUSE DOORS FROM DEMOLITION WHERE POSSIBLE. PROVIDE NEW BUILDING STANDARD DOORS MATCHING EXISTING VENEER AS REQUIRED. STAIN NEW DOORS TO MATCH EXISTING. PRE-MACHINE NEW DOORS FOR CYLINDRICAL LOCKSETS. 2. PROVIDE NEW HARDWARE TO MATCH EXISTING ON NEW DOORS. REUSE EXISTING HARDWARE ON EXISTING DOORS WHERE POSSIBLE. FOR NEW DOOR HARDWARE, PROVIDE GRADE 2 MINIMUM BUILDING STANDARD. PROVIDE A.D.A. ACCESSIBLE LEVER HANDLES ON NEW LOCK AND LATCHSETS. 3. PROVIDE NEW BUILDING STANDARD FRAMES AS REQUIRED. REUSE EXISTING FROM DEMOLITION WHERE POSSIBLE. 4. FRAME ALL DOOR ROUGH OPENINGS 4" FROM ADJACENT WALL CORNERS UNLESS OTHERWISE NOTED ON PLAN. 5. REFER TO TENANT AND LANDLORD FOR KEYING REQUIREMENTS AND LOCKSETS. 6. TENANT'S SECURITY VENDOR IS RESPONSIBLE FOR THE SPECIFICATION, PURCHASE, AND INSTALLATION OF ALL ACCESS CONTROLLED ELECTRONIC AND/OR MAGNETIC HARDWARE AND ASSOCIATED DEVICES. ALL SPECIFICATIONS AND INSTALLATIONS MUST COMPLY WITH THE INDIANA BUILDING CODE, CHAPTER 10, MEANS OF EGRESS. 7. PROVIDE BUTT HINGES ON ALL DOORS AS FOLLOWS: • 7'-0" HT. TO HAVE 3 HINGES • GREATER THAN 7'-0" IN HT. TO HAVE 4 HINGES • FINISH TO MATCH HARDWARE SET 8. PROVIDE (1) SET OF SILENCERS ON ALL DOOR FRAMES UNLESS OTHERWISE NOTED. 9. PROVIDE WALL STOP (FLOOR STOP WHERE APPLICABLE) AT EACH DOOR UNLESS OTHERWISE NOTED. PROVIDE WOOD BLOCKING REMARK -- -- -- PT7 OL Rl BEHIND WALL STOP. SEE __ __ __ __ PT7 OL R1, R4 REMARK p2 SOLID CORE STAIN TO F� HOLLOW PT7 OL H A R D WA R E L E G E N D BIRCH VNR. MATCH EXIST. METAL SEE __ __ __ __ PT7 OL Rl REMARK SEE __ __ __ __ PT7 OL Rl REMARK -- -- -- -- -- PT7 CR, ES, CL, SL SEE __ __ __ __ PT7 OL Rl REMARK SEE __ __ __ __ PT7 OL Rl REMARK SEE __ __ __ __ PT7 OL R1, R4 REMARK D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL D2 SOLID CORE STAIN TO F� HOLLOW PT7 OL BIRCH VNR. MATCH EXIST. METAL SEE __ __ __ __ PT7 OL R1, R4 REMARK SEE __ __ __ __ PT7 OL Rl REMARK SEE __ __ __ __ PT7 OL Rl REMARK p� SOLID CORE STAIN TO F5 HOLLOW PT7 DL, RL BIRCH VNR. MATCH EXIST. METAL -- -- -- -- -- SEE REMARK CR, ES, CL, SL R3 CL CLOSER CH COATHOOK CR CARD READER BY TENANT (N.I.C.) DB DEADBOLT DL DUMMY LEVER EL ELECTROMAGNETIC LOCK (PER IBC 2012) ES ELECTRIC STRIKE BY TENANT (N.I.C.) H HOLD OPEN KP KICK PLATE KS KICK STOP OL OFFICE LOCKSET PH PANIC HARDWARE PL PRIVACY LOCKSET PP PUSH/PULL PS PASSAGE LATCHSET PV PIVOT HINGE RL ROLLER LATCHES SL STOREROOM LOCKSET TS TOP STRIKES o � O � � O � } � � cn Z � '� � ,v_i � � � Q� � w � <''� U O � N �� �3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W - � � � � = J � O W ' � � � z Z Q � N Q Zaz J � � N - . � � �� � � � LL � O Q V z z� Q J � � � z � z W � � � � ISSUE � DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS IMARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR DOOR SCHEDULE INTERIOR DETAILS WALL CABINETS (PL3) (SEE CASEWORK NOTE 2) 25" DEEP PLASTIC LAMINATE (PL4) COUNTERTOP WITH 4"H BACKSPLASH FILLER PANEL, TYP. BASE CABINETS(PL3) (SEE CASEWORK NOTE 2) WALL CABINETS (PL3) (SEE CASEWORK NOTE 2) 25" DEEP PLASTIC LAMINATE (PL4) COUNTERTOP WITH 4"H BACKSPLASH BASE CABINETS (PL3) (SEE CASEWORK NOTE 2) � 3'-3" � 3'-3" � 3'-3" � 3'-3" � ELEVATION - WORK ROOM 213 0 1' 2' 4' � 2'-9" � 2'-9" � 2'-9" � � 5'-10" I �� �� � (HOLD) CONFIRM DIMENSION OF COPIER WITH TENANT ELEVATION - OPEN OFFICE 259 0 1' 2' 4' 7'-6" X 3'-6" PLASTIC LAMINATE (PL5) COUNTERTOP OPEN CABINETS, PLASTIC LAMINATE (PL3) INTERIOR WITH ADJUSTABLE PLASTIC LAMINATE (PL3) SHELVES EQ. I EQ. 7'-6" EQ. 3 A212 EQ. ELEVATION - WORK ROOM 213 WALL CABINETS (PLl ) (SEE CASEWORK NOTE 2) STAINLESS STEEL DOUBLE BOWL SINK, GOOSENECK FAUCET, LEVER CONTROLS, GARBAGE DISPOSAL 24" DEEP PLASTIC LAMINATE (PL2) COUNTERTOP WITH 4"H BACKSPLASH BASE CABINETS (SEE CASEWORK NOTE 1) � N � 0 N 0 1' 2' 4' 2'-6�� 2,_6�� �n I MICROWAVE MICROWAVE BOX BOX �N 7'-6" X 3'-6" PLASTIC LAMINATE (PL5) COUNTERTOP 3'-6" 3'-0" 3'-0" �� �� � EQ. � EQ. � �STIC RIOR SECTION - WORK ROOM 213 I I I WATER I �OOLEf� I BY I �TENANT� � 2'-3" � 2'-3" � 3'-3" � 3'-3" � 5'-0" � (CLEAR) ELEVATION - BREAK 225 0 1' 2' 4' 0 6" 1' 2' CASEWORK NOTES 1. PROVIDE ADA COMPLIANT A.W.I. CUSTOM GRADE, FLUSH-OVERLAY CABINETS. FABRICATE WITH PLASTIC LAMINATE (PLl ) COVERED M.D.O. BOARD WITH 4" WIRE PULLS. PROVIDE VINYL BASE AS SCHEDULED. COORDINATE WITH ELEVATIONS FOR QUANTITIES. 24" DEEP COUNTERTOPS 23" DEEP BASE CABINETS 12" DEEP UPPER CABINETS 2. PROVIDE A.W.I. CUSTOM GRADE, FLUSH-OVERLAY CABINETS. FABRICATE WITH PLASTIC LAMINATE COVERED M.D.O. BOARD WITH 4" WIRE PULLS. PROVIDE VINYL BASE AS SCHEDULED. COORDINATE WITH ELEVATIONS FOR QUANTITIES. 25" DEEP COUNTERTOPS 24" DEEP BASE CABINETS 12" DEEP UPPER CABINETS o � O � � O � } � � cn Z '�n — I� N � ,vi � � � � Q � � w � � U O � �? �� �3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W - � � � � � � � O W ' � � � Z Z Q Q N Q Zaz � � � N - � Y � �� � � � LL � O Q V z z� aJ � � � z � z W w �� � O c� ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS MARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR INTERIOR DETAILS LEGEND GENERAL NOTES PLAN NOTES NEW CONSTRUCTION POWER OUTLET, DUPLEX POWER OUTLET, QUADRUPLEX JUNCTION BOX CEILING MOUNTED JUNCTION BOX BOX, BLANK COVER PLATE � BOX, OPEN QC CABLE BOX, OPEN p POWER POLE FOR � ELECTRICAL AND DATA. PROVIDE JUNCTION BOX ABOVE CEILING. FLOOR BOX WITH POWER �I� AND DATA, FLUSH MOUNTED FLOOR BOX WITH � IQ JUNCTION BOX AND DATA, FLUSH MOUNTED DATA/COMMUNICATION le OUTLET (PROVIDE BOX AND PULL STRING ONLY) DED DEDICATED CIRCUIT GFCI GROUND FAULT CIRCUIT INTERRUPT OUTLET +42" HEIGHT OF ELECTRICAL OR DATA DEVICE EXISTING TO REMAIN 0 :�: P ❑ POWER OUTLET, DUPLEX POWER OUTLET, QUADRUPLEX JUNCTION BOX CEILING MOUNTED JUNCTION BOX BOX, BLANK COVER PLATE BOX, OPEN POWER AND DATA POLE FLOOR BOX WITH POWER �IQ AND DATA, FLUSH MOUNTED FLOOR BOX WITH �J IQ JUNCTION BOX AND DATA, FLUSH MOUNTED a DATA/COMMUNICATION OUTLET ' ■ AREA NOT IN CONTRACT AREA OF WORK 1. TENANT'S FURNITURE VENDOR IS RESPONSIBLE FOR INSTALLATION OF FURNITURE AND FIELD VERIFICATION OF ALL CRITICAL DIMENSIONS. 2. ALL OUTLETS ARE TO INSTALLED 18" MIN. A.F.F. TO THE CENTER OF THE DEVICE PER ADA GUIDELINES UNLESS NOTED OTHERWISE. 3. REFER TO DOOR SCHEDULE AND COORDINATE WITH TENANT/OWNER REGARDING POWER LOCATIONS TO ACCOMMODATE ELECTRIC STRIKES, CARD READERS AND/OR MAG-LOCKS. CARD READERS ARE TYPICALLY INSTALLED BY THE TENANT'S SECURITY CONTRACTOR AND NOT SPECIFIED BY SDI. 4. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH ALL APPLICABLE CODES. 5. IF POSSIBLE, CONVERT EXISTING BLANK/OPEN BOXES TO NEW DATA RECEPTACLES AS SHOWN. IF NOT POSSIBLE, REMOVE BLANK/OPEN BOX AND PROVIDE NEW DATA RECEPTACLE AT THIS LOCATION. E01 PROVIDE POWER AS REQUIRED FOR ELECTRIC STRIKE AT DOOR FOR CARD READER (CARD READER BY TENANT). COORDINATE WITH TENANT'S SECURITY CONTRACTOR. SEE DOOR SCHEDULE FOR MORE DETAILS. E02 COORDINATE COPIER RECEPTACLE WITH TENANT. PROVIDE DEDICATED RECEPTACLE AS REQUIRED. E03 PROVIDE JUNCTION BOX AND DATA FOR TENANT'S FURNITURE SYSTEM. COORDINATE EXACT LOCATION WITH TENANT'S FURNITURE VENDOR. E04 PROVIDE JUNCTION BOX ABOVE CEILING FOR POWER POLE FOR TENANT'S FURNITURE SYSTEM. COORDINATE EXACT LOCATION WITH TENANT'S FURNITURE VENDOR. POWER POLE BY FURNITURE VENDOR. PROVIDE DEDICATED POWER OUTLET IN RECESSED BOX INSET INTO E05 CABINET/ WALL FOR TENANT'S MICROWAVE, CENTERED AT 24" AFF. E06 PROVIDE POWER AND DATA AT 60" A.F.F. FOR TENANT'S WALL MOUNTED TELEVISION. COORDINATE EXACT LOCATION WITH TENANT. E07 PROVIDE FLUSH MOUNT FLOOR CORE FOR (2) ELECTRICAL AND (2) DATA. COORDINATE WITH TENANTS FURNITURE VENDOR ON EXACT LOCATION. POKE THRU DEVICE MUST BE APPROVED BY TENANT PRIOR TO PURCHASE. PROVIDE 2" CONDUIT CONNECTION FROM FLOOR BOX TO WALL MOUNTED TV. E08 PROVIDE POWER ABOVE CEILING FOR TENANT PROVIDED CEILING MOUNTED PROJECTOR. COORDINATE WITH TENANT ON EXACT REQUIREMENTS AND LOCATION. E09 PROVIDE POWER AT THIS LOCATION FOR TENANT'S GARBAGE DISPOSAL. E10 ENSURE DOOR BELL AND COMMUNICATION SYSTEM IN COMMON CORRODR/RECEPTION IS IN PROPER WORKING CONDITION. CONTRACTOR TO RUN DATA FEED TO TENANT'S SERVER ROOM. E1 1 PROVIDE SEPARATE PRICE TO RELOCATE ELECTRICAL PANELS AND PHONE BOARD TO ADJACENT WALL. E12 IF POSSIBLE, REUSE EXISTING FLOOR CORE. IF NOT POSSIBLE, REMOVE FLOOR CORE, PATCH FLOOR AS NEEDED AND PREPARE TO RECEIVE NEW FINISHES; PROVIDE NEW FLOOR CORE WITH (2) DUPLEX OUTLETS AND (2) DATA PORTS. PROVIDE 2" CONDUIT CONNECTION FROM FLOOR BOX TO WALL MOUNTED TV. E13 SERVER ROOM TO HAVE THE FOLLOWING; CONFIRM EXACT LOCATIONS WITH TENANT: - 4 STANDARD ELEC. DUPLEXES - ALL PHONE BOARDS TO HAVE 1 DED DUPLEX - PROVIDE TESTED EARTH GROUND E14 CONFIRM WITH TENANT IF EXISTING POWER IN CEILING IS SUFFICIENT. IF NOT, REMOVE EXISTING POWER AND PROVIDE NEW AS REQUIRED. E15 E16 CONFIRM LOCATION OF EXISTING RAISED POWER AND DATA FOR TELEVISION WITH TENANT. RELOCATE AS REQUIRED. COORDINATE POWER AND DATA REQUIREMENTS FOR DEMOUNTABLE WALLS WITH FURNITURE VENDOR. ELECTRICAL PLAN 0 4' 8' 16' N 3/32" = 1'-0" o � O � � O � � � � v� Z �'� � ,v_i � � � Q� � w � <''� U O � N � � � 3 � 3 THIS DRAWING, AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN, ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF SCHOTT DESIGN, INC., AND ARE NOT TO BE USED OR REPRODUCED IN WHOLE, OR IN PART, WITHOUT THE WRITTEN CONSENT OF SCHOTT DESIGN. � � 0 � � � N z W — H � — c� � � t/� Q W ' � _ Q - z Z Q Q N Q ZQZ �- - �� v� _ . � � �� � �� ��OQ V z Z � Q J _ � � z � z W w �� � O c� ISSUE DATE DESCRIPTION 11.04.16 REVIEW SET 11.11.16 REVISED SET 11.18.16 PERMIT SET REVISONS IMARI� DATE I DB IDESCRIPTION � PROJECT NUMBER 2016.405 PROJ. MGR DRAWN BY VG SLF / AS 2ND FLOOR ELECTRICAL PLAN