HomeMy WebLinkAbout04_2017-03-30 - Sun King Distillery - CDs - DIV-21 DWGSA1
P1 P1OR
A1
OH
1
2
1
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD
CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER
DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN
UNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10"10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR
BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE
OF PIPE, UNLESS NOTED OTHERWISE
FIRE SUPPRESSION SYMBOLS
DOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
CARBON DIOXIDE OUTLET - HOSPITAL TYPE
MEDICAL AIR OUTLET - HOSPITAL TYPE
MEDICAL VACUUM INLET - HOSPITAL TYPE
NITROGEN OUTLET - HOSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN OUTLET - HOSPITAL TYPE
WAGD INLET - HOSPITAL TYPE
NATURAL GAS OUTLET - LAB TYPE
VACUUM OUTLET - LAB TYPE
VACUUM CLEANING STATION - WALL
VACUUM CLEANING STATION - FLOOR
PLUMBING AND FIRE SUPPRESSION
PIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER PIPE (180 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC
WATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYGEN PIPE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE WATER PIPE
SPRINKLER PIPE (WET)
SANITARY DRAINAGE PIPE
SOFT COLD WATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WASTE ANESTHESIA GAS DISPOSAL PIPE
WATER SERVICE
140
LV
180
140R
180R
AR
CA
CO2
CWS
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
WAGD
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
3
3
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND HOSE
CONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG
IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERWISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE WITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
TP
CO
COMBINATION SHUTOFF AND BALANCING
VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGS
DOUBLE LINE SINGLE LINE
SOLENOID VALVES
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF
VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR
DRAIN UNLESS NOTED OTHERWISE.
FIRE DEPARTMENT VALVE
WATER METERM
ACID VENT PIPEAV
ACID WASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACC - ACCESS
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID WASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTWN - BETWEEN
CA - COMPRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - MEDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT WATER
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLY
CWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DET - DETAIL
DF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DS - DOWN SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DWG - DRAWING
EA - EACH
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EEW - EMERGENCY EYE WASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERGENCY SHOWER
EQS - EQUIPMENT SUPPLIER
EWC - ELECTRICAL WATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GD - GARAGE DRAINAGE
GPM - GALLONS PER MINUTE
GS - GAS SERVICE
GW - GREASE WASTE
H2 - HYDROGEN
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER OR HIGH POINT
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY WATER
HPWR - HIGH PURITY WATER RETURN
HR - HOSE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
HW - HOT WATER
HWR - HEATING HOT WATER RETURN
HWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT CONTRACTOR
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD WATER
LEC - LABORATORY EQUIPMENT CONTRACTOR
LHW - LABORATORY HOT WATER
LHWR - LABORATORY HOT WATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATORY VENT
LW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIR
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL CONTRACTOR (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
MV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGEN
NG - GASOLINE (NON-LEAD)
NIC - NOT IN CONTRACT
NO - MEDICAL NITROUS OXIDE
NOM - NOMINAL
NPW - NON-POTABLE WATER
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
02 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR OVERFLOW DRAIN
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
PW - PURE WATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (WET)
SA - SHOCK ARRESTOR OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOWER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER DISCHARGE
TW - TEMPERED WATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/0 - WITHOUT
W - WASTE
WAGD - WASTE ANESTHESIA GAS DISPOSAL
WC - WATER CLOSET
WCO - WALL CLEANOUT
WH - WALL HYDRANT OR WATER HEATER
WIV - WALL INDICATOR VALVE
WS - WATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:07:44 AMFS000
SYMBOLS,
ABBREVIATIONS,
INDEX
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTSBP2 PROJECT STATUSBP3 PROJECT STATUSBP4 PROJECT STATUSBP5 PROJECT STATUSBP6 PROJECT STATUS
30 MARCH 201730 MARCH 201730 MARCH 2017
FIRE SUPPRESSION SHEET LIST
Sheet Number Sheet Name
FS000 SYMBOLS, ABBREVIATIONS, INDEX
FS100 FIRE SUPPRESSION PLANS
HYDRANT FLOW TEST DATA:
STATIC - 55 PSI
RESIDUAL - 35 PSI
FLOW - 1000 GPM
No. Description Date
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
Mill Room
121
Water
110
Food 1
120
JNTR CLST
119
Distillery
104
Freezer
109
Cooler
108
Cooler
107
Food 3
114
Hall
118
RR
116
RR
117
Hall
106
STAIR
112
STORAGE
105
Bar
102
Retail
122
Bar
103
Elec.
111
Food 2
115
Dining
101
Kitchen
113
VESTIBULE
100
Info
54
3
FS100
FS FS3
3
3 2
OH
2
OH
1
OH
1
OH
1
OH
1
OH
2
OH
1
1 SS
SFS
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
RR
212
PIZZA OVEN
216
HALL
206
BOILER ROOM
207
RR
204
RR
205
STAFF BREAK
211
CATERING PREP
214
SUPPORT
215
JAN
208 OFFICE
210
CATERING ALCOVE
63
BAR
201
DECK
202
PRIVATE FUNCTION
203
DINING
200
STAIR
213Hall
209
OH
1
OH
1
OH
1
4
S S5
1 2
4 2
3
1
1
2
1
2
90 ELL PLUG
45 ELL45 ELL
UNDISTURBED EARTH SURFACE
CONCRETE PAD - SEE SCHEDULE
PLUG
TWO - 1.5" THICK OAK BLOCKS
PIPE
SIZE
90 ELL
45 ELL
TEE &
PLUG
3" 4" 6" 8" 10"
1.5" 2" 3" 4" 8"
1" 1"1.5"2"5"
1"1.5"2"8"7"
(APPROX. ONE CU.FT. CONCRETE/SQ.FT. BEARING AREA)
EARTH BEARING AREA - SQ. FT.
1
2
3
4
FIRE MAIN
F
FS
SIGNAL WIRING IN CONDUIT
TO ALARM BELL ON WALL
OF BLDG.
WATER FLOW SWITCH
FURNISHED AND WIRED
SWING CHECK VALVE
MAIN DRAIN VALVE
MAIN DRAIN & TEST LINE
FLOOR
FLANGE-TYPICAL
SLEEVE THRU FOUNDATION WALL
FOOTING
FIRE SUPPRESSION
SERVICE
EXTERIOR WALL
SWING CHECK VALVE
PRESSURE GAUGE
SLEEVE THRU WALL,
CAULK WEATHER TIGHT
SPLASH BLOCK
GRADE
P
P
S
FSROUTE TO FDC. REFER TO CIVIL DWGS
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:07:49 AMFS100
FIRE
SUPPRESSION
PLANS
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN1
SCALE: 1/8" = 1'-0"
SECOND FLOOR FIRE SUPPRESSION2 SCALE: NONE
UNDER GROUND WATER PIPE THRUST BLOCKS4
A. ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE
IN EXPOSED STRUCTURAL AREAS) UNLESS OTHERWISE INDICATED.
B. REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING PLANS
AND GENERAL TRADES CONSTRUCTION INFORMATION. COORDINATE
SPRINKLER LOCATIONS WITH CEILING DEVICES (LIGHTING, GRILLES,
ETC.) OBTAIN ARCHITECTS APPROVAL OF SPRINKLER LAYOUT PRIOR TO
INSTALLATION. FINAL FINISHED APPEARANCE OF WORK MUST BE
APPROVED BY THE ARCHITECT.
C. TOTAL SQUARE FOOTAGE OF PROJECT IS 16,300 SQUARE FEET.
MAXIMUM PER FLOOR SQUARE FOOTAGE IS 20,000 SQUARE FEET.
TOTAL NUMBER OF FIRE RISERS REQUIRED 1.
D. CONTRACTOR SHALL MAKE REQUIRED FLOW TESTS, LAY OUT SYSTEMS,
OBTAIN APPROVALS FROM THE AUTHORITY HAVING JURISDICTION AND
THE OWNER’S INSURER PRIOR TO BEGINNING ANY FABRICATION OR
INSTALLATION WORK.
E. FIRE SUPPRESSION SPRINKLER SYSTEMS. REFER TO DRAWING AND
SPECIFICATIONS FOR COMPLETE SCOPE OF WORK.
1 FIRE SUPPRESSION CONTRACTOR SHALL DESIGN AND INSTALL
AUTOMATIC SPRINKLER SYSTEMS AND SUPERVISORY ALARM
SYSTEM FOR THE ENTIRE BUILDING. BUILDING TO BE TOTALLY FIRE
SUPPRESSED.
F. BASIS FOR DESIGN OF FIRE SUPPRESSION SYSTEM(S) TO BE:
1. LIGHT HAZARD 1500 SQUARE FEET, 0.10 GPM/SQ. FT., 225 SQUARE
FEET MAXIMUM PER SPRINKLER. 100 GPM HOSE STREAM
ALLOWANCE.
2. ORDINARY HAZARD, (GROUP 1) 1500 SQUARE FEET, 0.15 GPM/SQ. FT.,
130 SQUARE FEET MAXIMUM PER SPRINKLER. 250 GPM HOSE
STREAM ALLOWANCE.
AREA OF OPERATION REDUCTIONS AND INCREASES SHALL BE
CALCULATED PER NFPA STANDARDS. VERIFY DENSITIES WITH
GOVERNING AUTHORITIES AND OWNER’S INSURER BEFORE
PROCEEDING WITH DESIGN OF SYSTEM(S). IF GOVERNING AUTHORITIES
OR OWNER’S INSURER REQUIREMENTS ARE MORE STRINGENT THOSE
REQUIREMENTS SHALL PREVAIL. ALL AREAS ARE TO BE LIGHT HAZARD
CLASSIFICATION, UNLESS OTHERWISE INDICATED ON THE PLANS OR
REQUIRED BY THE GOVERNING AUTHORITY.
G. PROVIDE THE FOLLOWING SPRINKLER TYPES, UNLESS OTHERWISE
NOTED ON THE DRAWINGS. PENDENT TYPE SPRINKLERS SHALL BE
LOCATED IN THE CENTER OF SQUARE PADS AND AT THE CENTER OR AT
QUARTERPOINTS OF THE LONG AXIS OF RECTANGULAR PADS.
1. SPRINKLERS IN PUBLIC AREAS WITH CEILINGS SHALL BE
CONCEALED TWO PIECE ADJUSTABLE PENDENT QUICK RESPONSE
TYPE WITH WHITE FINISH COVERPLATE.
2. SPRINKLERS IN EXPOSED AREAS SHALL BE QUICK RESPONSE
BRASS UPRIGHT TYPE.
H. ALL PIPING SHOWN (WITH SIZES) SHALL BE INSTALLED AS SIZED UNLESS
HYDRAULIC CALCULATIONS INDICATED A LARGER SIZE IS NECESSARY. FOR
PIPING NOT SHOWN OR SIZED ON THE DRAWINGS, PIPE SIZING SHALL BE
BASED ON FIRE SUPPRESSION CONTRACTORS HYDRAULIC CALCULATIONS.
I. EXERCISE SPECIAL CARE TO COORDINATE PIPING AND EQUIPMENT
LOCATIONS WITH ALL OTHER TRADES.
FIRE SUPPRESSION DESING NOTES
1 ROUTE 6" FS TO FDC. INSTALL BALL DRIP AND ROUTE TO
EXTERIOR. SEAL WALL PENETRATION WEATHER TIGHT. REFER TO
CIVIL DRAWINGS FOR CONTINUATION.
2 NO PIPING TO BE ROUTED OVER THIS AREA OTHER THEN WHAT
SERVES THIS AREA.
3 PROVIDE DRY TYPE SPRINKLER HEADS TO SERVCE
COOLER/FREEZER.
4 DRY PIPE SYSTE TO SERVE PERGOLA. ROUTE DRY PIPING WITHIN
CAN LIGHT TRACK. (WORK AS PART OF ALTERNATE BID).
5 FS DRY PIPE VALVE. ROUTE DRAIN TO ADJACENT MOP BASIN.
NOTES
SCALE: NONE
FIRE RISER - W/PUMPER CONNECTION3
No. Description Date