HomeMy WebLinkAbout05_2017-03-30 - Sun King Distillery - CDs - DIV-22 DWGSA1
P1 P1OR
A1
OH
1
2
1
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD
CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER
DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN
UNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10"10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR
BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE
OF PIPE, UNLESS NOTED OTHERWISE
FIRE SUPPRESSION SYMBOLS
DOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
CARBON DIOXIDE OUTLET - HOSPITAL TYPE
MEDICAL AIR OUTLET - HOSPITAL TYPE
MEDICAL VACUUM INLET - HOSPITAL TYPE
NITROGEN OUTLET - HOSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN OUTLET - HOSPITAL TYPE
WAGD INLET - HOSPITAL TYPE
NATURAL GAS OUTLET - LAB TYPE
VACUUM OUTLET - LAB TYPE
VACUUM CLEANING STATION - WALL
VACUUM CLEANING STATION - FLOOR
PLUMBING AND FIRE SUPPRESSION
PIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER PIPE (180 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC
WATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYGEN PIPE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE WATER PIPE
SPRINKLER PIPE (WET)
SANITARY DRAINAGE PIPE
SOFT COLD WATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WASTE ANESTHESIA GAS DISPOSAL PIPE
WATER SERVICE
140
LV
180
140R
180R
AR
CA
CO2
CWS
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
WAGD
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
3
3
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND HOSE
CONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG
IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERWISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE WITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
TP
CO
COMBINATION SHUTOFF AND BALANCING
VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGS
DOUBLE LINE SINGLE LINE
SOLENOID VALVES
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF
VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR
DRAIN UNLESS NOTED OTHERWISE.
FIRE DEPARTMENT VALVE
WATER METERM
ACID VENT PIPEAV
ACID WASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACC - ACCESS
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID WASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTWN - BETWEEN
CA - COMPRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - MEDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT WATER
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLY
CWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DET - DETAIL
DF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DS - DOWN SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DWG - DRAWING
EA - EACH
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EEW - EMERGENCY EYE WASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERGENCY SHOWER
EQS - EQUIPMENT SUPPLIER
EWC - ELECTRICAL WATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GD - GARAGE DRAINAGE
GPM - GALLONS PER MINUTE
GS - GAS SERVICE
GW - GREASE WASTE
H2 - HYDROGEN
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER OR HIGH POINT
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY WATER
HPWR - HIGH PURITY WATER RETURN
HR - HOSE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
HW - HOT WATER
HWR - HEATING HOT WATER RETURN
HWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT CONTRACTOR
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD WATER
LEC - LABORATORY EQUIPMENT CONTRACTOR
LHW - LABORATORY HOT WATER
LHWR - LABORATORY HOT WATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATORY VENT
LW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIR
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL CONTRACTOR (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
MV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGEN
NG - GASOLINE (NON-LEAD)
NIC - NOT IN CONTRACT
NO - MEDICAL NITROUS OXIDE
NOM - NOMINAL
NPW - NON-POTABLE WATER
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
02 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR OVERFLOW DRAIN
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
PW - PURE WATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (WET)
SA - SHOCK ARRESTOR OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOWER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER DISCHARGE
TW - TEMPERED WATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/0 - WITHOUT
W - WASTE
WAGD - WASTE ANESTHESIA GAS DISPOSAL
WC - WATER CLOSET
WCO - WALL CLEANOUT
WH - WALL HYDRANT OR WATER HEATER
WIV - WALL INDICATOR VALVE
WS - WATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 12:36:12 PMP001
SYMBOLS,
ABBREVIATIONS &
INDEX
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
PLUMBING SHEET LIST
Sheet Number Sheet Name
P001 SYMBOLS, ABBREVIATIONS & INDEX
P101 FOUNDATION PLUMBING PLAN
P102 FIRST & SECOND FLOOR PLUMBING PLAN
P103 PLUMBING ROOF PLAN
P400 SOIL, WASTE & VENT DIAGRAM
P500 PLUMBING SCHEDULES AND DETAILS
GAS LOAD DATA
HVAC EQUIPMENT - 950 CFH
BOILER - 630 CFH
KITCHEN - 1500 CFH
FIRE PLACE - 80 CFH
WATER HEATER - 76 CFH
TOTAL = 3236 CFH @ 2 PSI
No. Description Date
1.2 4
4" - K6" - K
4" - SAN SAN4" - SAN
6" - K
VR
4" - DCW6" - FS
4" - SAN
4"SS
3"SS SANSAN
8" - STM 8" - STM8" - STM 8" - STM6" SAN
INV. ELEV. = 824.64'
G
FS
4" SAN
INV. ELEV. = 825.10'
CO+TEST-Y
4" SAN
INV. ELEV. = 824.09'
CO
8" STORM
INV. ELEV. = 824.71'
CO
CO
CO
CO
CO
CO
COCOCO
G
FFE = 828.10
CO
FS
ROUTE 6" FS TO FDC FD6 FD6 FD6 FD6
FD6
FD6
FD4 FD4
FD4
FD1
FD1
FD4
FD4FD4
FD5
FD2
FD2FD1
FD2
TD1
8" DS (7440 SF)
6" DS
(2440 SF)
D1
FD2
FD2
CO
4" STORM
INV. ELEV. = 825.10'
FD7
FD7
STM
4"
4"
FD3
B2B2
2" SS
3" KW
2" SS
VR
VR
VR
VR
A1
A2
A2
A1
C1
C1
C2
B3(2)
VR
B2
2.5" G
4" DCW
6" FS UP
CO+TEST-Y
CO+TEST-Y
SAN
SAN
SANSANSAN
SAN
SANSAN
STM
1
1
1
1
1
1
10" PVC
CONDUIT
10" PVC
CONDUIT
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 12:36:16 PMP101
FOUNDATION
PLUMBING PLAN
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
0 - Plumbing1
PLAN NOTES
1. REFER TO CIVIL DRAWINGS FOR CONTINUATION.
No. Description Date
CRCRCRCRCRCRBFPM
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
Mill Room
121
Water
110
Food 1
120
JNTR CLST
119
Distillery
104
Freezer
109
Cooler
108
Cooler
107
Food 3
114
RR
116
RR
117
Hall
106 STAIR
112
STORAGE
105
Bar
102
Retail
122
Bar
103
Elec.
111
Food 2
115
Dining
101
Kitchen
113
VESTIBULE
100
Info
54
TD-1
FD4FD4
FD6FD6FD6FD6FD6FD6
FD4 FD4
FD4
FD4
FD1
HB-1
GAS
METER
K K
VR
P102
3
G
G GGG
GG
FD5
FD1
FD1G GGFD2
B2
C2
C1
C1
A1
A2
A2
A1
B2
D1
(1220 SF)
8" DS DN (7440 SF)
CO
CO
6" DS DN (2440 SF)
STM
6"
3"
3"
0.75"
3"1"
0.75"
0.75"
1"
0.5"
0.75"
0.75"
1"
1"
0.5"
2"
2"
1.25"
0.75"
3"
1"
3"
2"
2.5"
0.75"
2"1"0.5"
1.25"1"
3"
3"
B4
HB-1
SAN SAN
SANSANSANSAN
CO
CO
PW PWB2PW0.5"
0.5"
CO
RD1OD1
(3720 SF)
CORD1OD1(3720 SF)
STM
6"
6"
OD1
RD1
(1220 SF)RD1
OD1
4"4"
6"STMSTMSTM
SAN
SANFD2
FD2
PW
0.5"
1.5"
1.5"
1.5"
1.5"
2.5"
2.5"
0.75"
2.5"
1.5"
2"
1.5"
F1
B3
B3
GREASE INTERCEPTOR
500 GALLON
FD7 FD7
12
FD2
B2
FD4
4
3
41 4
4
5 30
FD5
B2
FD2
D1
A1
FD2
B1
B3
FD1
A2
A1
FD1A1
C1
C2
VR
VR
VR
VR
3"
4" SS
FD4
3" SS
8
17
12
26
25
27 28
31
34
27
VR
33
33
35
12
2727
34
12
12
30
31
35
36 29
35
2712
22
22
12
29
CA
CA
23
CA
0.75"
24
32
17
12
12
25
0.75"
0.75"
0.75"
G
100 CFH
125 CFH
G
0.75"
17
17
10" PVC CONDUIT
10" PVC CONDUIT
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
RR
212
PIZZA OVEN
216
HALL
206
BOILER ROOM
207
RR
204
RR
205
STAFF BREAK
211
CATERING PREP
214
SUPPORT
215
JAN
208
OFFICE
210
BAR
201
DECK
202
PRIVATE FUNCTION
203
DINING
200
STAIR
213
Hall
209
NG
NG
NGPW
4"VTRFD1
FD1
FD2
FD4
FD5
FD4
C2
C2
C1
A1
A1
A2
A1
B1
D1
A2 B2
FD2
FD2
VVVVVVV
V1.25"GGGG 0.75"
0.75"
1"
F1
B3
B4
1
2
4" AIR INTAKE
4" EXHAUST
1"G DN
22
10
10
12
12
11
12
18
11
21
13
11
15
14
16
19
11
1219
20
HB-1
9
B2 B2
10" PVC CONDUIT STUB
A
6
SALT STORAGE
DWH1
ROP1,2
ROST1
ROM1
CF1
WS1
TMV1
RCP1
ET1
FD2
FD2
FD3
HB-1
4" AIR INTAKE
4" EXHAUST
NC
TMV2
G GPWPWPW PW
1"
1"
1.25"
1.25"
0.75"
1"
1.25"
3"
0.75"
1"
1"
5
P500
7
38
3839
40
1"
37
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 12:36:23 PMP102
FIRST & SECOND
FLOOR PLUMBING
PLAN
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
1 - Plumbing1
SCALE: 1/8" = 1'-0"
2 - Plumbing2 SCALE: 1/2" = 1'-0"
ENLARGED WATER ROOM3
PLAN NOTES
1. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (200CFH).
2. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (350CFH).
3. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (40 CFH).
4. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (500CFH).
5. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (400CFH).
6. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (630CFH).
7. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (76 CFH).
8. 4" DCW DROP TO REDUCED PRESSURE BACKFLOW PREVENTER. ROUTE
DRAIN LINE TO NEAREST FLOOR DRAIN.
9. CONNECT 0.75" G TO FIRE PLACE PER MANUFACTURER'S INSTRUCTIONS.
10. 2" CW DN. PROVIDE FULL SIZE MANIFOLD WITH VALVE AND SERVE EACH
FIXTURE INDIVIDUALLY FROM MANIFOLD. INSTALL HAMMER ARRESTOR.
11. 0.75" DCW, DHW DN.
12. INSTALL TRAP PRIMER ON FLOOR DRAIN.
13. 0.75" G, PW DN. CONNECT 0.75" G, PW TO BOILER PER MANUFACTURERS
INSTRUCTIONS.
14. 1.25" DCW DN.
15. 0.5" DHW DN.
16. 0.75" G, PW DN. CONNECT PW TO ICE MACHINE. STUB & CAP IN #216 FOR
FUTURE.
17. STUB 10" PVC CONDUIT UP 12"AFF.
18. CONNECT 1.25" G TO AHU PER MANUFACTURERS INSTRUCTIONS.
19. 0.5" DCW, DHW DN.
20. 0.5" PW DN.
21. 1.25" G DN. LOCATE SHUT OFF VALVE BELOW LAY-IN CEILING.
22. 2" CW DROP. PROVIDE FULL SIZE MANIFOLD WITH VALVE AND SERVE EACH
FIXTURE INDIVIDUALLY FROM MANIFOLD. INSTALL HAMMER ARRESTOR.
23. 0.75" CA DROP TO OWNER PROVIDED CONTRACTOR INSTALLED
AIR COMPRESSOR.
24. COORDINATE FINAL 0.75" CA TERMINATION POINT WITH OWNER.
25. 0.75" G UP.
26. 1" G UP.
27. 0.75" DCW, DHW UP.
28. 1.25" G UP.
29. 0.5" DCW, DHW UP.
30. 0.75" G, PW UP.
31. 0.5" PW DROP.
32. 0.75" DCW UP.
33. 2" DCW UP.
34. 0.75" DCW, DHW UP.
35. 1.5" G DROP, STUB PIPING IN WALL FOR FUTURE.
36. 0.5" DCW, DHW DROP.
37. 1" G DROP TO DWH1.
38. 1" DCW DROP TO WS1.
39. 1" DCW, DHW DROP - 1" 77F DHW UP FROM TMV-2.
40. 1" SCW DROP TO REDUCED PRESSURE BACKFLOW PREVENTER. ROUTE
DRAIN LINE TO NEAREST FLOOR DRAIN.
41. PRESSURE REGULATING VALVE SET @ 14" W.C. FROM 2 PSI (265 CFH).
GENERAL NOTES
1. COORDINATE ALL NATURAL GAS VALVE LOCATIONS WITH RETURN
AIR PLENUMS. NO VALVES ARE PERMITTED TO BE LOCATED IN
PLENUM SPACES.
2. PROVIDE LONG SWEEP 90 DEGREE ELBOWS ON PVC CONDUIT.
COORDINATE EXACT LOCATIONS AND REQUIREMENTS WITH OWNER
PRIOR TO INSTALLATION.
3. PVC PIPING LOCATED WITH IN RETURN AIR PLENUM SPACE IS REQUIRED
TO BE FIRE WRAPPED. WRAPPING SHALL BE 3M FIRE BARRIER PLENUM
WRAP 5A+ OR EQUAL.
4. ROUTE ALL NATURAL GAS REGULATOR VENTS TO THE OUTSIDE INDIVIDUALLY
PER THE MANUFACTURER'S WRITTEN INSTRUCTIONS.
5. ALL DRAINAGE PIPING LOCATED ABOVE FOOD PREP AND DINING AREAS SHALL
HAVE A GALVANIZED DRAIN PAN INSTALLED UNDER DRAINAGE PIPING.
No. Description Date
ROOF SYSTEM 01
ROOF SYSTEM 01
ROOF SYSTEM 02
TYP.
OPEN TO BELOW
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
4"VTR
OD1 RD1OD1 RD1 (3720 SF)(3720 SF)
(1220 SF)(1220 SF)RD1
OD1
RD1
OD1
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 12:36:25 PMP103
PLUMBING ROOF
PLAN
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
Roof1
No. Description Date
2"2"
1.5"
2"
2.5"
2"
2"1.5"
3"
3"4"
4"
3"
4"
2"
2"
3"
3"
3"
3"
FD6
FD6
FD6
FD6
FD6
FD6
FD4
FD4
3"
3"
4"
4"
3"3"
3"
3"
2"
4"
4"
6"
6"
3"3"
3"
CO
CO
CO
CO
CO
CO
3"
3"
3"
3"
3"
3"
4"
4"
FD1
C1
C2
C2
A1
A1
A2
FD1
A2
3"
2"
6"
4"
2"
2"
2"
2"
2"
1.5"
1.5"2"
2"
2"
2"
2"
4"
4"
3"4"
3"
A2
A2
A1
B2
A1
FD4
FD4
FD2
FD4
FD1
4"
4"
FD2
1.5"
1.5"
1.5"
2"
2.5"
6"
4"
3"
3"3"
4"
3"
3"
4"
4"
2.5"
2.5"
2"
2"
4"
4"
4"
4"
2"1.5"
2.5"
2"
2"
2"
2"
2"
2"
2"
2"2"2"
2"
1.5"
2.5"
2.5"
2"
TD-1
FD4
FD4
D1
FD4FD2
A1
D1
C1
C1
FD5
FD5
FD1
FD2
FD2
B1
C2
B2
FD2
FD2
FD3
B3
B3
FD2
2"
2"
4"VTR2"
B3
B4
2"
FD1
CO
CO
GREASE INTERCEPTOR
500 GALLONS
2"
2"
2"
2"
4"
3"
3"
2"
2"
2"
2"
2"
2"
4"3"
4"
4"
3"
3"
4"
4"
CO
CO
CO
CO
CO
6"
3"
CO
COORDINATE INSTALLATION WITH
STRUCTURAL DWGS/DETAILS
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 12:36:32 PMP400
SOIL, WASTE &
VENT DIAGRAM
Sun King Spirits
RGF
RGF
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE:
Soil, Waste & Vent Diagram1
DINING
101
RR
116
RR
117
DISTILLERY
104
BAR
102
RR
204
RR
205
WATER
110
BOILER ROOM
207
ROOM
105
DINING
101
JNTR
119
SUPPORT
215
FOOD 3
114
FOOD 3
115
RR
204
RR
205
No. Description Date
1 2
4 2
3
1
1
2
1
2
90 ELL PLUG
45 ELL45 ELL
UNDISTURBED EARTH SURFACE
CONCRETE PAD - SEE SCHEDULE
PLUG
TWO - 1.5" THICK OAK BLOCKS
PIPE
SIZE
90 ELL
45 ELL
TEE &
PLUG
3" 4" 6" 8" 10"
1.5" 2" 3" 4" 8"
1" 1"1.5"2"5"
1"1.5"2"8"7"
(APPROX. ONE CU.FT. CONCRETE/SQ.FT. BEARING AREA)
EARTH BEARING AREA - SQ. FT.
1
2
3
4
BUILDING
WALL
SHEETMETAL DOWNSPOUT
CAST IRON DOWNSPOUT
BOOT
GRADE
CONNECT TO DS BOOT
PVC ELBOW, SEE PLAN FOR SIZE
PVC PIPING, SEE PLANS FOR SIZE
STORM SEWER
PROVIDE ADAPTOR AND
MAKE FINAL CONNECTION
TO SEWER PIPE.
5'-0''
TRAP PRIMER, WITH DISTRIBUTION
UNIT WHEN SERVING MULTIPLE
DRAINS. LOCATE ABOVE CEILING
IN FINISHED AREAS.
0.5''SUPPLY SHALL BE
OFF TOP OF MAIN
COLD WATER MAIN
TPTPWALL
FINISHED CEILING
WHERE APPLICABLE
FLOOR DRAINS
FLOOR
TP
PIPING TO FLOOR DRAINS
SHALL BE RUN BELOW FLOOR,
UNLESS NOTED OTHERWISE.
INSTALL PIPING CONCEALED
IN WALL IN FINISHED AREAS.
INSTALL PIPING TIGHT TO WALL
SURFACE IN UNFINISHED AREAS.
1 AIR GAP OVER FLOOR DRAIN.
2 COMBINATION TEMPERATURE-PRESSURE RELIEF VALVE.
3 MINIMUM 27" HEAT TRAP.
4 AIR GAP OVER FLOOR.
3
14
2
ET1
DWH1 140TMV1
RCP1
.PTP/T
NOTES
1.25"
1.25"
1.25"
1.25"1.25"
0.75"
0.75"
PIPE SIZE AS
INDICATED
ON PLANS
SHUT-OFF VALVE
EQUIPMENT CONNECTION
PIPE SIZE
EQUIPMENT
CONNECTIONUNION
PIPE CAP3'' MIN.USER NOTES:
1 USE AS A TYPICAL DETAIL FOR ALL GAS FIRED EQUIPMENT (WATER HEATERS, UNIT HEATER,
ROOFTOP UNITS, ECT.) ON PROJECT.
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 12:36:39 PMP500
PLUMBING
SCHEDULES AND
DETAILS
Sun King Spirits
Checker
Author
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
NOTES:
1. BASIS OF DESIGN: AO SMITH BTX-80
2. BASIS OF DESIGN: PUROMAX LP-5000
3. BASIS OF DESIGN: GRUNDFOS MQ3-45
4. BASIS OF DESIGN: AQUA SYSTEMS WS1.0 CC 300
5. BASIS OF DESIGN: B&G NBF-10S/LW
6. BASIS OF DESIGN: WATTS DETA-12
7. BASIS OF DESIGN: LAWLER 801
8. BASIS OF DESIGN: DEN HARTOG CB0300-42, WITH CB042-45ST STAND
9. BASIS OF DESIGN: AQUA SYSTEMS SCIITW250VT
GENERAL NOTES:
A. PROVIDE ROUGH-IN.
B. INSTALL ALL "LOOSE" COMPONENTS.
C. CONNECTION SIZES SHALL BE AS LISTED. TERMINAL OUTLETS AND
INLETS ON EQUIPMENT MAY BE SMALLER AND INCREASER/REDUCER
FITTINGS REQUIRED.
PLUMBING EQUIPMENT
MARK DESCRIPTION CAPACITYPRESSURE VOLUME
EFFICIENCYINPUT
ELECTRICAL
(VOLTAGE - PHASE)
CONNECTIO
NS
APPROX.
DIMENSIONS
SEISMIC
RESTRAINTS
SEE NOTEHEAD DROP TOTAL ACCEPTANCECFH KW BTU HP
FLUID
F
U
EL WIDTH / DIA. LENGTH HEIGHT REQUIRED IMPORTANCE FACTOR IN OUT
CF1 CARBON FILTER 10 GPM/SF 5 PSI 120V-1PH 0.75
"
0.75
"
14" 65" 4
DWH1 DOMESTIC WATER HEATER 92 GPH @ 90 DEGREES F RISE 80 76 120V-1PH 1.5" 1.5" 27" 68-5
/8"
1
ET1 THERMAL EXPANSION TANK 5 GALLONS 3.1
GAL
1.25
"
6
RCP1 DOMESTIC HOT WATER RECIRC PUMP 1 GPM 15 FT .55 120V-1PH 0.75
"
0.75
"
5" 6" 5" 5
ROM1 REVERSE OSMOSIS MACHINE 5000 GPD @ 77 DEGREE F 115
PSI
0.5 120V-1PH 0.75
"
0.75
"
22" 23" 65" 2
ROP1,
2
REVERSE OSMOSIS DISTRIBUTION PUMPS 5 GPM 125 FT 1.150 120V-1PH 0.75
"
0.5" 8.5" 22" 12.5
"
3
ROST1 REVERSE OSMOSIS WATER STORAGE TANK 300 GALLON, CONICAL BOTTOM 8
TMV1 THERMOSTATIC MIXING VALVE 17 GPM 5 PSI 1.25
"
1.25
"
7
TMV2 THERMOSTATIC MIXING VALVE 5 GPM 5 PSI 1" 1"7
WS1 DUPLEX WATER SOFTENER 60,000 GRAINS; 19 GPM CONT, 26 GPM PEAK 15 PSI 120V-1PH 0.75
"
0.75
"
13" 54" 9
NOTES:
1. PROVIDE "TRUEBRO" HANDI-LAV GUARD MODEL 103E-Z OR
APPROVED EQUAL
2. INSTALL TRIP LEVER ON WIDE SIDE OF STALL
3. PROVIDE HOSE, HOSE BRACKET, VINYL BUMPER GUARD,
STAINLESS STEEL WALL GUARD, MOP HANGER, ACCESSORIES BY
MOP SINK MANUFACTURER
ADA HANDICAP ACCESSIBLE
FS FLOOR SET
FT FLUSH TANK
FV FLUSH VALVE
GN GOOSENECK
HS HAND SHOWER
QD QUICK DISCONNECT
SB SINGLE BOWL
SST STAINLESS STEEL
VB VACUUM BREAKER
VR VANDAL RESISTANT
WB WRIST BLADE
WH WALL HUNG
SCHEDULE ABBREVIATIONS:GENERAL NOTE:
1. SUPPLY PIPE SIZES IN THIS SCHEDULE ARE FIXTURE OR SUPPLY STOP CONNECTION SIZES. DOMESTIC COLD AND HOT WATER SUPPLY PIPE SIZES SERVING FIXTURES SHALL BE, AT A MINIMUM,
THE SIZES LISTED UNLESS NOTED OTHERWISE OR LABELED ON THE FLOOR PLANS. DOMESTIC COLD WATER SUPPLY PIPE SIZES SERVING FLUSH VALVES SHALL BE AT MINIMUM ONE
PIPE SIZE LARGER THAN THE INDICATED CONNECTION SIZE, OR SIZED AS SHOWN ON THE FLOOR PLANS. PIPING AT THE FLUSH VALVE CONNECTION OF A SIZE EQUAL TO THE CONNECTION SIZE
SHALL BE LIMITED TO A MAXIMUM 2 FEET IN DEVELOPED LENGTH AND INCLUDE A MAXIMUM OF ONE 90 DEGREE ELBOW FITTING. FULL SIZE MANIFOLDS, WHERE INDICATED ON THE FLOOR PLANS,
SHALL BE PROVIDED FULL SIZE FOR THE LENGTH OF THE PIPING CHASE AND TERMINATED WITH A FULL SIZE CAP.
A. ZURN (KOHLER, CRANE, AMERICAN STANDARD)
B. SLOAN (DELANY, ZURN) _
C. OLSONITE (BENEKE, CHURCH, BEMIS) _
D. SMITH (WADE, ZURN, JOSAM, WATTS) _
E. CHICAGO (TOTO, T&S BRASS, ZURN) _
F. GUY GRAY (OATEY, PLASTIC ODDITIES) _
G. McGUIRE (EBC, DEARBORN BRASS) _
H. FIAT (STERN WILLIAMS, CREATIVE IND.) _
J. ELKAY (JUST WITH LUG AND SCREW) _
K. AMERICAN STANDARD (ZURN, ELKAY, KOHLER) _
L. LEONARD (POWERS, SYMMONS) _
M. AQUARIUS (AQUA-BATH, KOHLER, CRANE) _
N. BRADLEY (SLOAN, ZURN, AMERICAN STANDARD) _
_
_
_
CATALOG NUMBERS INDICATED ARE THOSE OF THE FIRST NAMED MANUFACTURER IN EACH CATEGORY LISTED BELOW - ADDITIONAL MANUFACTURERS ARE LISTED IN PARENTHESIS
PLUMBING FIXTURES
MARK DESCRIPTION MOUNTING HEIGHT FLOW CONTROL SUPPLY WASTE & VENT FIXTURE SUPPLY TRIM SUPPLY / STOP WASTE TRIM TRAP / FIX. DR. MISC. SEE NOTE GPM GPF MANUAL METERINGSENSOR
COLD WATER HOT WATER TEMPERED NAT. GAS FIX. OUTLET TRAP FIX. DRAIN WASTE-MIN. VENT-MIN. INDIRECT AIR GAP AIR BREAK MFR.CAT. NO. MFR.CAT. NO. MFR.CAT. NO. MFR.CAT. NO. MFR.CAT. NO. MFR.CAT. NO. ELECTRIC BATTERYA1 WATER CLOSET/FS/FV/ADA 17" 1.6 ●1" 3" 3" 3" 2" A Z5655-BWL1 B 111-1.6 C 95SS 2
A2 WATER CLOSET/FS/FV 15" 1.6 ●1" 3" 3" 3" 2" A Z5655-BWL1 B 111-1.6 C 95SS
B1 LAVATORY/WH/ADA 34" .5 ●0.5" 0.5" 1.25
"
1.25
"
1.5" 1.5" 1.5" A Z5364 K 605B.105 G 2165LK G 155A G 8902 1
B2 LAVATORY/WH 31" .5 ●0.5" 0.5" 1.25
"
1.25
"
1.5" 1.5" 1.5" A Z5364 K 605B.105 G 2165LK G 155A G 8902
B3 LAVATORY/WH/ADA/ 34" .5 ●1.25
"
1.5" 1.5" 1.5" N LVQD3-TMA-L
SD-HD1
G 2165LK G 155A G 8902
B4 LAVATORY/WH/ADA 34 .5 ●1.25
"
1.5" 1.5" 1.5" N LVQD2-TMA-L
SD-HD1
G 2165LK G 155A G 8902
C1 URINAL/FV 24" 1 ●1" 2" 2" 2" 1.5" A Z5755-U B 186-1
C2 URINAL/ADA/FV 17" 1 ●1" 2" 2" 2" 1.5" A Z5755-U B 186-1
D1 MOP BASIN/FS FLOOR 12 ●0.75
"
0.75
"
3" 3" 3" 3" 2" H MSB-2424 E 897-CP 3
F1 SCULLERY SINK/SS FLOOR 2.2 ●2" 2"●BY OWNER BY OWNER G 2165LK
HB-1 WALL HYDRANT 24"
AFG
0.75
"
REFER TO
SPEC
NOTES:
1. SECURED 1/2 GRATE
GENERAL NOTE:
1. ALL DRAINS ARE MANUFACTURED BY J.R. SMITH UNLESS NOTED OTHERWISE.
DRAINS
MARK CATALOG NOS.
TYPE BODY OUTLET STRAINER / GRATE TOP FINISH ADDITIONAL FEATURES
SEE NOTE FLOOR ROOF AREAWAY CAST IRON BRASS ACID RESIST. STAINLESS STEEL PLASTIC SIZE BOTTOM SIDESIZE
ADJUSTABLE FLAT DOME RECESSED FUNNEL HINGED STAINLESS STEEL NICKLE-BRONZE CAST IRON ACID RESIST. STAINLESS STEEL PLASTIC DUCTILE IRON ANCHOR FLANGE FLASHING CLAMP DBL DRAINAGE SED. BUCKET AUX. STRAINER BEARING PAN U'DECK CLAMP 2" STANDPIPE TRAP PRIMER CON. WATER DAM DIAMETER / WIDTH LENGTHFD1 2005Y-A ● ●3"●5" -12"● ● ●●●
FD2 2310Y ● ●3"●5" -12"● ● ● ●●
FD3 2633Y-12 ● ●3"●5" -12"● ●● ● ●1
FD4 3021Y ● ●3"●5" -12"● ● ● ● ●
FD5 3101Y-12 ● ●4"●12" 12"● ● ● ● ●1
FD6 2450 ● ●3"●5" -12"● ● ●●●1
FD7 2473 ● ●3"●5" -12"● ● ● ● ● ●
OD1 1074 ● ●4"●15"● ●● ● ● ● ● ● ●
RD1 1015 ● ●4"●15"● ●● ● ● ● ● ●
TD-1 9665 ● ●3"● ● ● ● ●●
SCALE: NONE
UNDER GROUND WATER PIPE THRUST BLOCKS1 SCALE: NONE
DOWNSPOUT BOOT2
SCALE: NONE
TRAP PRIMER4
SCALE: NONE
DOMESTIC WATER HEATER PIPING5
SCALE: NONE
TYPICAL GAS CONNECTION AT EQUIPMENT6SCALE: NONE
GREASE INTERCEPTOR DETAIL7
No. Description Date