HomeMy WebLinkAbout06_2017-03-30 - Sun King Distillery - CDs - DIV-23 DWGSNOTE: ALL SYMBOLS AND ABBREVIATIONS
ARE SUBJECT TO MODIFICATIONS
ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS
MIGHT NOT NECESSARILY BE USED ON
THIS PROJECT.
ABBREVIATIONS
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AFMS - AIR FLOW MEASURING STATION
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATC - AUTOMATIC TEMPERATURE CONTROL
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CHGR - CHILLED WATER GLYCOL SOLUTION RETURN
CHGS - CHILLED WATER GLYCOL SOLUTION SUPPLY
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWR - CONDENSER WATER RETURN
CWS - CONDENSER WATER SUPPLY
D - DRAIN LINE
DB - DRY BULB
DDC - DIRECT DIGITAL CONTROLS
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DWG - DRAWING
EA - EACH OR EXHAUST AIR
EAT - ENTERING AIR TEMPERATURE
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
EQS - EQUIPMENT SUPPLIER
EWT - ENTERING WATER TEMPERATURE
EXH - EXHAUST
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
FD - FLOOR DRAIN
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GPM - GALLONS PER MINUTE
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HR - HOUR
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
HW - HOT WATER
HWR - HEATING HOT WATER RETURN
HWS - HEATING HOT WATER SUPPLY
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LAT - LEAVING AIR TEMPERATURE
LAV - LAVATORY
LBS - POUNDS
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LWT - LEAVING WATER TEMPERATURE
MAX - MAXIMUM
MDD - MOTORIZED DAMPER
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE
RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
NIC - NOT IN CONTRACT
NOM - NOMINAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOOR AIR
OBD - OPPOSED BLADE DAMPER
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PLBG - PLUMBING
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSIG - POUNDS PER SQUARE INCH GAUGE
RA - RETURN AIR
RAD - RADIUS
RCP - REFLECTED CEILING PLAN
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
S - SPRINKLER (WET)
SA - SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SHT - SHEET
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SRV - SAFETY RELIEF VALVE
SS - STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
V - VENT
VAC - VACUUM
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/0 - WITHOUT
WB - WET BULB
WCO - WALL CLEANOUT
GENERAL FLOOR PLAN NOTES
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS
NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
3
3
A1 EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS
REFER TO SCHEDULES.
H1 H1OR EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
2
1
H2
B
H2
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
H2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
H2 = SHEET WHERE DETAIL IS LOCATED
A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF
EQUIPMENT, UNLESS NOTED OTHERWISE
10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOD: 8' - 10"
BOD: 7' - 2"
20x20
20x20
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF
DUCTWORK, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE,
UNLESS NOTED OTHERWISE
DL-1
UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH
UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE WITH GC.
DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.
CONNECT TO EXISTING
HVAC PIPING DESIGNATIONS
CHILLED WATER SUPPLY PIPECHS
CONDENSER WATER SUPPLY PIPECWS
CONDENSER WATER RETURN PIPECWR
DRAIN LINE. PITCH IN DIRECTION INDICATEDD
HEATING HOT WATER SUPPLY PIPEHWS
HEATING HOT WATER RETURN PIPEHWR
WATER MAKE-UP PIPEMU
VENT PIPEV
REFRIGERANT LIQUID LINERL
REFRIGERANT SUCTION LINERS
EXPANSION TANK PIPEET
REFRIGERANT HOT GAS LINEHG
LOW PRESSURE CONDENSATE RETURN PIPELPC
LOW PRESSURE STEAM SUPPLY PIPELPS
MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC
MEDIUM PRESSURE STEAM SUPPLY PIPEMPS
PUMPED CONDENSATE RETURN PIPEPC
HIGH PRESSURE CONDENSATE RETURN PIPEHPC
HIGH PRESSURE STEAM SUPPLY PIPEHPS
STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10
MISC SYMBOLS
DUCTWORK SYMBOLS
ROUND BRANCH DUCTWORKCONICAL
FITTING
ACOUSTIC
FITTING
ACOUSTIC
FITTING
ADAD
D
R R
D
RECTANGULAR BRANCH DUCTWORK
SQUARE TEE WITH TURNING VANES
NOTE: ALL SQUARE ELBOWS IN
RECTANGULAR AND ROUND / OVAL
DUCTWORK SHALL BE PROVIDED WITH
TURNING VANES.
EXISTING DUCTWORK TO REMOVED
RETURN AIR, RELIEF AIR, OR TRANSFER AIR
DUCTWORK. (UP AND DOWN) RADIUSED OR
SQUARE WITH TURNING VANES.
SUPPLY AIR OR OUTDOOR AIR DUCTWORK.
(UP AND DOWN) RADIUSED OR SQUARE
WITH TURNING VANES.
EXHAUST AIR DUCTWORK. (UP AND DOWN)
RADIUSED OR SQUARE WITH TURNING
VANES.
RECTANGULAR AND ROUND / OVAL
DUCTWORK RISE / DROP WITH 90° RADIUSED
OR SQUARE ELBOWS AND TURNING VANES.
RADIUS ELBOW
90° SQUARE ELBOW (WITH TURNING VANES)
NOTE: ALL SQUARE ELBOWS IN
RECTANGULAR AND ROUND DUCTWORK
SHALL BE PROVIDED WITH TURNING VANES.
ACCESS DOOR OR PANEL
DUCTWORK RISE IN DIRECTION OF AIR
FLOW
DUCTWORK DROP IN DIRECTION OF AIR
FLOW
DUCTWORK WITH ACOUSTICAL LINER.
LISTED DUCT SIZES ARE INSIDE CLEAR
DIMENSIONS.
RECTANGULAR ROUND / OVAL
FLEXIBLE DUCTWORK
FLEXIBLE CONNECTION
DUCTWORK CONSTRUCTED OF SPECIAL
MATERIAL AS NOTED
DIRECTION OF PITCH
RECTANGULAR DUCTWORK DIMENSIONS
(W x H)26x20
ROUND DUCTWORK DIMENSIONS (DIA)26ø
OVAL DUCTWORK DIMENSIONS (W x H)26x20 OV
DUCTWORK DEVICE SYMBOLS
WALL OR DUCTWORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER
TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).
300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM
OF GRILLE.
A3
10ø
300
MANUAL BALANCING VALVE DAMPER WITH LOCKING DEVICE
BDD = BACK DRAFT DAMPER
CBD = COUNTER-BALANCED BACK DRAFT DAMPER
SD = SMOKE DAMPER
FS = COMBINATION FIRE - SMOKE DAMPER
MDD = MOTORIZED DAMPER
AFMS = AIR FLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.
HUMIDITY SENSOR - DUCT MOUNTED
SG1
20x12
300
BOG: 9'-0"
XXX
A-D
XX
H
SD
SP
AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE
SCHEDULE FOR VARIOUS DESIGNATIONS).
10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE
DISCHARGE 4-WAY UNLESS NOTED WITH FLOW ARROWS. AIR DEVICE
SHOWN IS 2-WAY SIDE THROW. METHOD OF IDENTIFICATION ALSO APPLIES
TO OTHER CEILING MOUNTED AIR DEVICES.
FIRE DAMPER
A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)
D OR S = DYNAMIC OR STATIC
STATIC PRESSURE SENSOR - DUCT MOUNTED
C
CARBON DIOXIDE SENSOR - DUCT MOUNTED
S
TEMPERATURE SENSOR - DUCT MOUNTED
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND HOSE
CONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG
IN AND OUT
EXPANSION JOINT
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
2 PORT AUTOMATIC CONTROL VALVE
3 PORT AUTOMATIC CONTROL VALVE
QUICK OPENING MANUAL VALVE
VACUUM BREAKER
NEEDLE VALVE
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE WITH STOP
END CAP
GLOBE VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
A
M
M
N
V
COMBINATION SHUTOFF AND BALANCING
VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGS
DOUBLE LINE SINGLE LINE
SOLENOID VALVES
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS
PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN
UNLESS NOTED OTHERWISE. FOR STEAM SYSTEMS
PIPE DISCHARGE TO OUTDOORS.
WATER METERM
PRESSURE GAUGE WITH COCK AND SIPHON LOOP
BI-METALIC STEAM TRAP AND DRIP ASSEMBLY
THERMODYNAMIC STEAM TRAP AND DRIP
ASSEMBLY
INVERTED BUCKET STEAM TRAP AND DRIP
ASSEMBLY
FLOAT AND THERMOSTATIC STEAM TRAP AND
DRIP ASSEMBLY
THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
BM
TD
IB
FT
TS
10"
TOE: 3' - 0"
BOE: 0' - 6"
CHILLED WATER GLYCOL SOLUTION RETURN PIPE (PROCESS)CHGR
CHILLED WATER GLYCOL SOLUTION SUPPLY PIPE (PROCESS)CHGS
CHILLED WATER RETURN PIPECHR
SQUARE THROAT / RADIUS HEEL
FITTINGS NOT ACCEPTABLE
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PIPE RISER
RADIUS'D BRANCH
RADIUS'D TEE
EXISTING DUCTWORK TO REMAIN
15° MAX FOR DIVERGING, 30° MAX FOR
CONVERGING TRANSITION
EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERWISE.
SPACE TEMPERATURE SENSOR / THERMOSTAT. WHEN WALL MOUNTED, MOUNTING
HEIGHT 46" TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH
COORDINATE WITH ARCHITECT.
T
DP
DIFFERENTIAL PRESSURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO
MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH
ARCHITECT.
H HUMIDITY SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
CARBON DIOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.C
CO
CARBON MONOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET
ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH
ARCHITECT.
TEMPERATURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH
ARCHITECT.
S
S P TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.
STATIC PRESSURE SENSOR.SP
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:15:04 AMM001
SYMBOLS,
ABBREVIATIONS &
INDEX
Sun King Spirits
EEL
JSN
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
MECHANICAL SHEET LIST
Sheet Number Sheet Name
M001 SYMBOLS, ABBREVIATIONS & INDEX
M101 FIRST FLOOR MECHANICAL PLAN
M102 SECOND FLOOR MECHANICAL PLAN
M103 ROOF MECHANICAL PLAN
M501 MECHANICAL DETAILS
M701 MECHANICAL SCHEDULES
No. Description Date
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
Mill Room
121
Water
110
Food 1
120
JNTR CLST
119
Distillery
104
Freezer
109
Cooler
108
Cooler
107
Food 3
114
Hall
118
RR
116
RR
117
Hall
106
STAIR
112
STORAGE
105
Bar
102
Retail
122
Bar
103
Elec.
111
Food 2
115
Dining
101
Kitchen
113
VESTIBULE
100
Info
54
14x14 12x12
225 CFM
J2
12x12
225 CFM
J2
12x6
75 CFM
E1
10x10
8ø
50x20
8ø
A1
250 CFM
24x24
175 CFM
J348x20
6ø
A1
50 CFM
6ø
A1
100 CFM
6ø
A1
100 CFM24ø20x12
14x12
12x5
255 CFM
G2
12x6
310 CFM
G2
12x6
310 CFM
G212x6
310 CFM
G2
12x6
310 CFM
G2
12x6
310 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2 12x5
255 CFM
G2
12x5
255 CFM
G2
10x4
125 CFM
G2
10x4
125 CFM
G2
12x6
200 CFM
G2
14ø
18ø
12x6
310 CFM
G2
12x6
310 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2
20ø 16ø
14ø12x5
255 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2
12x5
255 CFM
G2
8ø
A1
300 CFM
10ø
A1
350 CFM
8ø
A1
300 CFM
10ø
6ø
10x10
10ø
10x10
7x4
50 CFM
H1
4 4
78
6
4
10x10
8ø
T
T
EUH-1
EUH-2
2
3
1
5 5
6ø
48x20
R2
48x20
R2
9
9
EWH-1
11
10
10x10
T
EUH-3
T
RTU-2
12
RH-1
RH-2
12x12
12x12
J1
2
M102
T
T
T
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:15:09 AMM101
FIRST FLOOR
MECHANICAL
PLAN
Sun King Spirits
EEL
JSN
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
FIRST FLOOR MECHANICAL PLAN1
PLAN NOTES
1. FLARE TO 62" X 20". COVER END OF DUCT WITH 1/2" MESH HARDWARE CLOTH.
2. 67" X 27" SUPPLY UP TO RTU-2. TRANSITION AS REQUIRED FOR CONNECTION TO RTU-2. SEE
SHEET M102 FOR CONTINUATION.
3. 76" X 20" RETURN UP TO RTU-2. TRANSITION AS REQUIRED FOR CONNECTION TO RTU-2. SEE
SHEET M102 FOR CONTINUATION.
4. 10" X 10" GREASE DUCT. COORDINATE LOCATION WITH OWNER SPPLIED HOOD. TRANSITION AS
REQUIRED FOR CONNECTION.
5. 48" X 20" INTERNALLY LINED TRANSFER DUCT.
6. 6" DIAMETER EXHAUST UP. SEE SHEET M102 FOR CONTINUATION.
7. 14" X 14" GREASE DUCT UP. SEE SHEET M102 FOR CONTINUATION.
8. 10" X 10" EXHAUST DUCT UP. SEE SHEET M102 FOR CONTINUATION.
9. 18" X 10" EXHAUST. TERMINATE AT 10' 0" A.F.F. COVER OPENING WITH STAINLESS STEEL 1/2"
MESH HARDWARE CLOTH. SEE SHEE M102 FOR CONTINUATION.
10. 10" X 10" EXHAUST UP TO EF-6. SEE SEET M102 FOR CONTINUATION.
11. 30" X 6" EXHAUST GRILLE IN BOTTOM OF DUCT. COORDINATE LOCATION WITH BATTERY
CHARGING STATION.
12. COORDINATE LOCATION OF THERMOSTAT WITH ARCHITECT AND ENGINEER.
No. Description Date
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
RR
212
PIZZA OVEN
216
HALL
206
BOILER ROOM
207
RR
204
RR
205
STAFF BREAK
211
214
CATERING
PREP
SUPPORT
215
JAN
208
OFFICE
210
63
CATERING
ALCOVE
BAR
201
DECK
202
PRIVATE FUNCTION
203
DINING
200
STAIR
213
Hall
209
RTU-1
RTU-2
AHU-1
12x6
300 CFM
G2
12x6
300 CFM
G2
12x6
300 CFM
G2
12x6
320 CFM
G2
12x6
320 CFM
G2
12x6
320 CFM
G2
12x6
320 CFM
G2
12x6
320 CFM
G2 12x6
320 CFM
G2
12x12
75 CFM
J2
12x8
75 CFM
E1
24x12
225 CFM
J2
24x12
225 CFM
J2
12x12
J1
6ø
A1
50 CFM
6ø
A1
75 CFM
6ø
A1
100 CFM
8ø
A1
175 CFM
6ø
A1
50 CFM
12x6
200 CFM
H1
14x12
12x10
40x20
R2
12x6
320 CFM
G2
T
T
T
10x12
18ø
16x8
670 CFM
G1
16x8
665 CFM
G1
16x8
665 CFM
G1
10x10
12x6
300 CFM
G2
24x12
R2 40x206ø
8ø
8ø 14x1214ø
20ø
12ø 16ø
12ø
14ø
6ø
A1
25 CFM
12x6
320 CFM
G2
12x6
320 CFM
G212x6
320 CFM
G2
16x6
400 CFM
G2
16x6
400 CFM
G2
PROCESS
CHILLER ACCU-1
1
ZD-1
ZD-3
26ø16ø
ZD-2
3
5 4
6
SP8 ZD-4
9
2
2
10
11
18x10
18x16
16ø 16ø
T
MD
EF-6
ACCU ACCU ACCU
12 13
6ø
A1
100 CFM
8ø
A1
175 CFM
ZD-2
ZD-3
14
ZD-1
18
17
ZD-4
16
7
22
2123
20
19
24
15
2
M102
24x12
36x36
MD
MD
T
AHU-1
26ø
RL
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:15:16 AMM102
SECOND FLOOR
MECHANICAL
PLAN
Sun King Spirits
EEL
JSN
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
SECOND FLOOR MECHANICAL PLAN1
PLAN NOTES
1. STAINLESS STEEL DRAINPAN UNDER RAH-1. PAN SHALL BE 6" LARGER THAN THROAT OF RAH-1 IN ALL
DIRECTIONS. PAN SHALL HAVE 2" TALL SIDES AND BE WELDED WATERTIGHT. PAINT TO MATCH
EXPOSED STRUCTURE.
2. 18" X 10" EXHAUST DUCT DOWN WALL. SEE SHEET M101 FOR CONTINUATION.
3. 6" DIAMETER EXHAUST UP AND DOWN. SEE SHEETS M103 AND M101 FOR CONTINUATION.
4. 14" X 14" GREASE DUCT UP AND DOWN. SEE SHEETS M103 AND M101 FOR CONTINUATION.
5. 14" X 12" EXHAUST UP, 10" X 10" EXHAUST DUCT DOWN. SEE SHEETS M101 AND M103 FOR
CONTINUATION.
6. 8" DIAMETER EXHAUST UP. COORDINATE WITH PIZZA OVEN MANUFACTURER. SEE SHEET M103 FOR
CONTINUATION.
7. REFRIGERANT PIPING SIZED BY EQUIPMENT MANUFACTURER.
8. SUPPLY DUCT STATIC PRESSURE SENSOR.
9. PROCESS CHILLER PROVIDED BY OWNER. FOR REFERENCE ONLY.
10. 18" X 16" EXHAUST DUCT UP. SEE SHEET M103 FOR CONTINUATION.
11. 72" X 36" LOUVER WITH FULL SIZE INSULATED CONTROL DAMPER.
12. CONDENSING UNIT FOR COOLER PROVIDED BY OWNER. FOR REFERENCE ONLY.
13. CONDENSING UNIT FOR FREEZER PROVIDED BY OWNER. FOR REFERENCE ONLY.
14. DUCT MOUNTED TEMPERATURE SENSOR.
15. 1" CONDENSATE DRAIN. TERMINATE OVER MOP BASIN.
16. 8" DIAMETER BOILER FLUE UP. SEE SHEET M103 FOR CONTINUATION. COORDINATE LOCATION WITH
BOILER (BY OTHERS) LOCATION.
17. 6" FLUE FROM AHU-1. SEE SHEET M103 FOR CONTINUATION.
18. 6" COMBUSTION AIR TO AHU-1. SEE SHEET M103 FOR CONTINUATION.
19. 2" PROCESS CHGS AND CHGR DOWN WALL TO 8'-0" AFF. VALVE AND CAP.
20. 2 1/2" PROCESS STEAM DOWN WALL TO 8'-0" ADD. VALVE AND CAP.
21. 2 1/2" PROCESS STEAM. CONNECT TO BOILER (BY OTHERS). TRANSITION AT BOILER AS REQUIRED.
22. 2" PROCESS CHGS AND CHGR. CONNECT TO PROCESS CHILLER (BY OTHERS). TRANSITION AT
CHILLER AS REQUIRED.
23. RACK PIPING VERTICALLY ON WALL.
24. PROVIDE TWO (2) COMBUSTION AIR OPENINGS BETWEEN BOILER ROOM 20D AND HALL 20B. LOCATE ONE
(1) OPENING HIGH AND ONE (1) OPENING LOW AS REQUIRED BY NFPA31. EACH OPENING SHALL HAVE A
MINIMUM FREE AREA OF 4.1 SQUARE FEET.
SCALE: 1/8" = 1'-0"
SECTION 12
No. Description Date
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
EF-3
EF-2
EF-1
EF-4
EF-5
RAH-1
1
2
3
2
M102
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:15:18 AMM103
ROOF
MECHANICAL
PLAN
Sun King Spirits
EEL
JSN
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
MECHANICAL ROOF PLAN1
PLAN NOTES
1. 6" FLUE FROM AHU-1. TERMINATE PER AHU MANUFACTURER. SEE SHEET M102 FOR
CONTINUATION.
2. 6" COMBUSTION AIR INTAKE TO AHU-1. TERMINATE PER AHU MANUFACTURER. SEE SHEET
M102 FOR CONTINUATION.
3. 8" DIAMETER BOILER FLUE. TERMINATE PER BOILER MANUFACTURER.
No. Description Date
SUPPLY DUCT
6
4 3 4 5 4
6
12
8
7
CEILING CEILING DIFFUSER
1. SQUARE-TO-ROUND ADAPTER IF DIFFUSER NECK IS SQUARE.
CONNECT ADAPTOR TO DIFFUSER. SEAL TO AIR DEVICE,
SEAL CLASS A. INSULATE ADAPTOR AND EXPOSED
BACKSIDE SURFACES OF AIR DEVICE.
2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH
DUCT , 3 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE.
STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY
EXTENDED LENGTH.
3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE WITH MANUAL
DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL
INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO
MAIN DUCT WITH INTERNAL INSULATION, AND EXTENDED
DAMPER SHAFT AND HANDLE WITH STAND-OFF TO
ACCOMMODATE EXTERNAL INSULATION.
4. DUCT STRAP HANGER. ATTACH TO STRUCTURE.
5. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS
LONGER THAN 4 FT.
6. MINIMUM CENTERLINE RADIUS EQUAL TO DUCT
DIAMETER.
7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS
DIFFUSER INLET UNLESS NOTED OTHERWISE.
8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).
COORDINATE AND VERIFY T-BAR TYPE FOR
COMPATIBILITY WITH DIFFUSER.
9. RADIUS'D SHEET METAL ELBOW.
7
NOTES
9
ROUND SHEETMETAL BRANCH DUCT
BRANCH CFM RD. DUCT SIZE
0 TO 80 CFM 6"D
81 TO 120 CFM 7"D
121 TO 200 CFM 8"D
401 TO 700 CFM 12"D
701 TO 1000 CFM 14"D
201 TO 400 CFM 10"D
7
CEILING RETURN OR EXHAUST GRILLE
553 56
8
98
4
1
2RETURN OR EXHAUST DUCT
1. SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK,
MINIMUM 6" TALL WITH SAME INTERNAL OR EXTERNAL
INSULATION AS RETURN OR EXHAUST DUCT. CONNECT TO
GRILLE. SEAL PLENUM AND CONNECTION TO GRILLE, SEAL
CLASS A.
2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT ,
1 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH
FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED
LENGTH.
3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE WITH
MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.
INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP
FITTING TO MAIN DUCT WITH INTERNAL INSULATION.
EXTENDED DAMPER SHAFT AND HANDLE WITH STAND-OFF
REQUIRED FOR EXTERNALLY INSULATED DUCTWORK.
4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.
5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.
6. ROUND SHEET METAL BRANCH DUCT, SIZE AS INDICATED
IN ADJACENT SCHEDULE UNLESS NOTED OTHERWISE ON
PLANS.
7. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).
COORDINATE AND VERIFY T-BAR TYPE FOR
COMPATIBILITY WITH GRILLE.
8. MINIMUM CENTERLINE RADIUS EQUAL TO DUCT
DIAMETER.
9. RADIUS'D SHEET METAL ELBOW.
7
3
NOTES 6" MAX7CEILING RETURN OR EXHAUST GRILLE
3 1 3 2 3
6
4
5
RETURN OR EXHAUST DUCT
1. 45 DEGREE STATIC BOOT AND MANUAL DAMPER. INTEGRAL INSULATION
GUARD SLEEVE REQUIRED WHEN MAIN DUCT HAS INTERNAL INSULATION.
EXTENDED DAMPER SHAFT AND HANDLE WITH STAND-OFF REQUIRED FOR
EXTERNALLY INSULATED DUCTWORK.
2. SHEET METAL DUCT, SIZE AS NOTED ON PLANS.
3. DUCT STRAP HANGER.
4. STATIC BOOT SIMILAR TO EXCEPT NO DAMPER.
5. SHEET METAL DUCT, FULL SIZE OF GRILLE NECK SIZE. CONNECT AND
SEAL DUCT TO GRILLE, SEAL CLASS A.
6. FLEXIBLE DUCT CONNECTOR.
7. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND
VERIFY T-BAR TYPE FOR COMPATIBILITY WITH GRILLE.
1
NOTES
MOUNTING ANGLEBLADE DEFLECTION
G TYPE AIR
DEVICE
SPIRAL DUCTWORK
A. REFER TO AIR DISTRIBUTION DEVICES
SCHEDULE FOR DUCT "MOUNTING ANGLE."
B. AIR DEVICE "BLADE DEFLECTION" SHALL BE
ADJUSTED TO DIRECT AIR PATH SUCH THAT AIR
HITS CORNER WHERE THE WALL OR WINDOW
MEETS THE FLOOR.
GENERAL NOTES
MOUNTING ANGLEB LA D E D E F L E C T IO N
G TYPE AIR
DEVICE
AIR FLOW
AIR FLOW
AIRFLOWTURNING VANES
SEE FLOOR PLAN FOR
SPLIT DIMENSION
MAIN SUPPLY
DUCT
MANUAL VOLUME
DAMPER
SUPPLY REGISTER ON
BRANCH DUCT
SQUARE ELBOW SHOWN
PROVIDE ROUND ELBOW
WHEN SHOWN ON PLANS
AIR FLOW
AIRFLOWW/4 OR 4"
MIN.
MAIN SUPPLY DUCT
MANUAL VOLUME DAMPER
BRANCH DUCT
W
BRANCH DUCT TAKE-OFF PLAN VIEWAIR SPLIT DUCT TAKE-OFF PLAN
VIEW
THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM, AND UP TO 40% WHEN
THE MAIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL OTHER
CASES
BRANCH DUCT
PLAN VIEW
W
W/4 OR 4" MIN.
PROVIDE MANUAL VOLUME DAMPER AT
EACH BRANCH DUCT
MAIN EXHAUST OR
RETURN AIR FLOW
45 DEG.AIR FLOWAIR FLOW
AIR FLOW
EQUIPMENTAIR FLOW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT PLAN OR
SIDE VIEW
TYPICAL DUCTWORK TRANSITION PLAN
OR SIDE VIEW
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
30 DEG.
MAX.
AIR FLOW
15 DEG. MAX
15 DEG. MAX15 DEG.
MAX.
30 DEG.
MAX.
15 DEG.
MAX.
CONCENTRIC TRANSITIONS UNLESS
SHOWN OTHERWISE ON PLANS
3
1
2
9
8
7
4
5
6
A. PAINT ALL EXTERIOR DUCTWORK AND DEVICES WITH
TWO COATS OF ENAMEL. ALL EXTERIOR SHEET
METAL SHALL BE "PAINT-GRIP" CONSTRUCTION.
1. 1/2" MESH BIRDSCREEN.
2. 2" WIDE x 1/8" THICK STEEL SUPPORTS.
3. 3'-0" CLEARANCE TYPICAL ALL VENTS.
4. STRUCTURAL FRAMING FOR OPENING. COORDINATE
REQUIRED OPENING DIMENSIONS.
5. SUPPORT RING. FASTEN TO DUCTWORK AND CHANNEL.
6. CHANNEL SUPPORT FROM ADJACENT JOISTS.
7. 16" HIGH CURB.
8. FLASHING COLLAR FASTEN TO DUCTS.
9. STORM COLLAR FASTEN TO DUCT..NOTES
GENERAL NOTES 1
12"3
4
2
COUNTER FLASHING
INSULATION
ROOFING
DUCT WALL
1. 12" HIGH INSULATED STEEL CURB.
2. PROVIDE PRESSURE TREATED RIGID WOOD
BLOCK FRAME SAME THICKNESS AS ROOF
INSULATION. BOLT TO CONCRETE ROOF
DECK.
3. SHEET METAL SCREW.
4. CONCRETE ROOF DECK OPENING.
COORDINATE REQUIRED OPENING SIZE..NOTES
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:15:24 AMM501
MECHANICAL
DETAILS
Sun King Spirits
EEL
JSN
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
CEILING DIFFUSER DUCT CONNECTION1 RETURN/EXHAUST GRILLE DUCT CONNECTION2 RETURN/EXHAUST GRILLE DUCT CONNECTION3
DUCT-MOUNTED GRILLE DETAIL4 SUPPLY DUCTWORK TAKE-OFFS5 EXHAUST OR RETURN BRANCH DUCTWORK6
DUCTWORK TRANSITIONS7 VENT DUCTS THRU ROOF8 FAN MOUNTING CURB9
No. Description Date
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:15:31 AMM701
MECHANICAL
SCHEDULES
Sun King Spirits
EEL
JSN
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
DUCT CONSTRUCTION, SEALING, AND INSULATION
GENERAL NOTES:
A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR
INSULATION; FIBERGLASS DUCTBOARD; ETC.
NOTES:
1. ROUND SHEET METAL RUN-OUTS TO AIR DEVICES DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.
2. RETURN DUCTWORK WITHIN 15' OF AIR HANDLING UNIT SHALL BE INTERNALLY LINED.
3. WATERTIGHT SEAL.
4. FIRE WRAPPED, PER CODE REQUIREMENTS.
5. STAINLESS STEEL DUCTWORK.
DUCT SYSTEM
SUPPLY DUCTWORK +3" A 12 -
S.P. CON-
STRUCT.
SEAL
CLASS
LEAKAGE
CLASS
S.M.A.C.N.A. CLASS.
INTERNALLY
LINED
●
EXTERNAL
INSULATION
- -
NOT
INSULATED
SEE
NOTE
DOUBLE
WALL
INSULATED
RETURN DUCTWORK -2" A ●2- -
TOILET OR GENERAL EXHAUST A -●--1"
EXHAUST DUCTWORK - KITCHEN HOOD WELDED -4- - -
1
-
--
-2"
TRANSFER/RETURN AIR SOUND BOOT A - --1"3
RECT RND
24
24
6
12
12
24 12
HVAC DESIGN DATA
GENERAL NOTES:
A. OUTDOOR DESIGN CONDITIONS:
92°F DB SUMMER
74°F WB SUMMER
1°F DB WINTER
NOTES:
1. "FLOATING" MEANS THERE IS NO ACTIVE CONTROL.
SPACE NAME / TYPE °F DB
INTERIOR DESIGN DATA
SEE NOTE
OFFICES 1
SUMMER WINTER
1
1
1
-
% RH
(NOTE 1) °F DB % RH
74 55 72 FLOATING
75 60 68 FLOATING
- FLOATING 65
74 55 72
- - - -
TOILET ROOMS
MECHANICAL ROOMS
ALL OTHER SPACES
-
FLOATING
FLOATING
B. DESIGN ALTITUDE: 850 FT.
NOTES:
1. GRILLES SHALL BE DOUBLE DEFLECTION TYPE WITH (2) SETS OF
FULLY ADJUSTABLE DEFLECTION BLADES.
2. 0° MOUNTING ANGLE, 0° BLADE DEFLECTION.
3. 20° MOUNTING ANGLE, 0° BLADE DEFLECTION.
4. PROVIDE RETURN AIR SOUND BOOT ON ALL RETURN GRILLES.
GENERAL NOTES:
A. ALL LAY-IN AIR DEVICES SHALL FIT IN 24"X24" LAY-IN CLG SYSTEM.
VERIFY GRID TYPE AND COORDINATE AIR DEVICE COMPATIBILITY.
B. FINISH KEY: "W.B.E." - WHITE BAKED ENAMEL;
"E.C.L." - ETCHED CLEAR LACQUER OR ANODIZED;
"C.C.B.A." - CUSTOM COLOR SELECTED BY ARCHITECT.
C. SUPPLY AIR DIFFUSERS SHALL BE 4-WAY BLOW, UNLESS
INDICATED OTHERWISE ON DRAWINGS.
D. PROVIDE AUX. FRAMES FOR AIR DEVICES IN PLASTER,
GYPSUM BOARD, TILE OR OTHER HARD SURFACES.
AIR DISTRIBUTION DEVICES
MARKDESCRIPTION
MOUNTING TYPE MATERIAL FINISH
OPPOSED BLADE DAMPER SQ-TO-RD NECK ADAPTOR BASIS OF DESIGN
SEE NOTE LAY-IN SURFACE DUCT SPLINE SNAP-IN STEEL ALUMINUM STAINLESS STEEL W.B.E. E.C.L. C.C.B.A.MANUFACTURER MODEL
A1 SQUARE PLAQUE DIFFUSER ● ● ●PRICE ASPD
E1 SIDEWALL FIXED BLADE EXHAUST GRILLE ● ● ●PRICE 635
G1 SPIRAL DUCT GRILLE ● ● ●PRICE SDGE 2
G2 SPIRAL DUCT GRILLE ● ● ●PRICE SDGE 3
H1 SIDEWALL ADJ. BLADE SUPPLY GRILLE ● ● ●PRICE 620 1
J1 EGGCRATE RETURN GRILLE ● ● ●PRICE 80 4
J2 EGGCRATE EXHAUST GRILLE ● ● ●PRICE 80
J3 EGGCRATE FILTERED EXHAUST GRILLE ● ● ●PRICE 80FF
R2 SIDEWALL FIXED BLADE RETURN GRILLE ● ● ●PRICE 635
NOTES:
1. SUSPENDED ABOVE CEILING.
GENERAL NOTES:
A. GAS HEATING.
B. DX COOLING.
C. MOTORS - 208V - 3PH, UNLESS NOTED OTHERWISE.
D. VFD'S SHALL BE CONSTRUCTED AND LABELED FOR REQUIRED SCCR
(SHORT CIRCUIT CURRENT RATING). COORDINATE WITH DIVISION 26.
E. UNIT CONFIGURATIONS (SUPPLY FAN POSITION RELATIVE TO COOLING
COIL) -
"HDT" - HORIZONTAL DRAW THRU; "VDT" - VERTICAL DRAW THRU;
"HBT" - HORIZONTAL BLOW THRU; "VBT" - VERTICAL BLOW THRU....
AIR HANDLING UNITS
UNIT NUMBERLOCATION
UNIT CONFIGURATIONAREA SERVED
SUPPLY FAN COOLING COIL REHEAT COIL FINAL FILTER
OUTSIDE
AIR MISC. BASIS OF DESIGN
SEE NOTE ROOM NAME ROOM NUMBER FAN SYSTEM NUMBER CFM (TOTAL) EXT / TOTAL STATIC PRESSURE (IN. W.C.) FAN QTY / WHEEL DIA. WHEEL TYPE MOTOR (HP EACH) VARIABLE FREQUENCY DRIVE (QTY) VIBRATION ISOLATOR TYPE MINIMUM FACE AREA (SQ. FT.) TOTAL CAPACITY (MBH) SENSIBLE CAPACITY (MBH) ENTERING AIR TEMPERATURE DB/WB (°F) LEAVING AIR TEMPERATURE DB/WB (°F) CAPACITY (MBH) ENTERING AIR TEMPERATURE DB (°F) LEAVING AIR TEMPERATURE DB (°F) THICKNESS / MERV MINIMUM FACE AREA (SQ. FT.) MAXIMUM CLEAN AIR PRESS. DROP (IN. W.C.) MINIMUM CFM ECONOMIZER MAXIMUM UNIT WEIGHT (LBS.)MANUFACTURER MODEL
AHU-1 RESTROOM 204 HDT SECOND FLOOR SF-1 6,150 1.2/3.0 1/18" AF 5 1 INTERNAL 12 250.3 169.0 80.0/67.0 55.0/53.8 320 45.0 92.3 2" / 8 16.6 .75 2,000 ●2750 - - 1
NOTES:
1. INTEGRAL DISCONNECT 2. ECM MOTOR WITH MANUFACTURER SPEED CONTROL
GENERAL NOTES:
A. ALL FANS SHALL BE A.M.C.A. 211 AND 311 PERFORMANCE
CERTIFIED AND SHALL BEAR THE A.M.C.A. LABEL.
B. MOTOR HORSEPOWERS LISTED SHALL BE CONSIDERED
MINIMUM.
C. COORDINATE STEEL FRAMING AROUND ROOF OPENING
WHERE REQUIRED FOR DECK SUPPORT, AND WALL LINTELS
FOR WALL OPENINGS.
D. ALL MOTORS SHALL BE EC TYPE UNLESS OTHERWISE NOTED.
E. VFD'S SHALL BE CONSTRUCTED AND LABELED FOR REQUIRED
SCCR (SHORT CIRCUIT CURRENT RATING). COORDINATE WITH
DIVISION 26.
FANS
MARKDESCRIPTION SERVICE CFM STATIC PRESSURE (IN. W.C.) MAXIMUM SONESMOTOR
APPROX. WEIGHT (LBS.) VIBRATION ISOLATOR TYPE BASIS OF DESIGN
SEE NOTE HORSEPOWER VOLTAGE - PHASEMANUFACTURER MODEL
EF-1 DOWNBLAST CENTRIFUGAL EXHAUST RESTROOMS 1,200 1.25" 15 1/2 120-1 60 GREENHECK G-123-VG 1, 2
EF-2 UPBLAST CENTRIFUGAL EXHAUST KITCHEN HOODS 1,800 1.5" 15 1 120-1 90 GREENHECK CUE-141-VG 1, 2
EF-3 UPBLAST CENTRIFUGAL EXHAUST PIZZA OVEN HEAT 400 0.75" 10 1/4 120-1 50 GREENHECK CUE-095-VG 1, 2
EF-4 DOWNBLAST CENTRIFUGAL EXHAUST MILL ROOM 175 0.75" 10 1/4 120-1 50 GREENHECK G-097-VG 1, 2
EF-5 DOWNBLAST CENTRIFUGAL EXHAUST DISTILLERY 2,000 1.3" 20 1 120-1 80 GREENHECK G-143-VG 1, 2
EF-6 DOWNBLAST CENTRIFUGAL EXHAUST FORK TRUCK CHARGE 550 0.75" 10 1/4 120-1 50 GREENHECK G-098-VG 1, 2
NOTES:
1. NOT USED.
GENERAL NOTES:
A. COOLING CAPACITIES BASED ON 95°F AMBIENT AIR TEMPERATURE.
B. NATURAL GAS DELIVERY PRESSURE TO UNIT IS 14" W.C. PROVIDE
SECONDARY REGULATOR IF REQ'D FOR UNIT OPERATION.
C. ELECTRIC SERVICE - SINGLE POINT POWER SERVICE CONNECTION
TO UNIT. ADEQUACY OF LISTED CIRCUIT SIZE MUST BE VERIFIED BY
H.C. AND UNIT SUPPLIER. COST FOR INCREASE OR CHANGE OF
ELECTRIC SERVICE FOR EQUIPMENT SELECTED SHALL BE BORNE
BY H.C. THIS SHALL INCLUDE LUG SIZE AND QUANTITY REQUIREMENTS.
D. UNIT CONFIGURATIONS (SUPPLY FAN POSITION RELATIVE TO
COOLING COIL) - "HDT" - HORIZONTAL DRAW THRU; "VDT" - VERTICAL
DRAW THRU; "HBT" - HORIZONTAL BLOW THRU; "VBT" - VERTICAL BLOW
THRU. REFER TO DRAWINGS FOR LAYOUT.
E. HEATING L.A.T. IS BASED ON FULL UNIT CFM AT LISTED E.A.T. AND MBH OUTPUT.
ROOFTOP HEATING & COOLING UNITS - DX/GAS FIRED
UNIT NUMBER NOMINAL TONS UNIT CONFIGURATION AREA SERVED
SUPPLY FAN COOLING SECTION HEATING SECTION
FINAL
FILTERS OUTSIDE AIR MISCELLANEOUS ELECTRICAL SERVICE BASIS OF DESIGN
SEE NOTE CFM (TOTAL) EXTERNAL / TOTAL STATIC PRESSURE (IN. W.C.) FAN QTY / WHEEL TYPE MOTOR (HP EACH) VARIABLE FREQUENCY DRIVE (QTY) VIBRATION ISOLOATOR TYPEDX-COOLING COIL
CONDENSING
SECTION
HEATING CAPACITY (MBH OUTPUT) ENTERING AIR TEMPERATURE DB (°F) LEAVING AIR TEMPERATURE DB (°F) (NOTE F) GAS INPUT MIN./MAX. (CFH) THICKNESS / MERV MAX. CLEAN AIR PRESSURE DROP (IN. W.C.) MINIMUM CFM ECONOMIZER ENERGY RECOV. SECTION (REFER TO SEP. SCHED.) HOT GAS REHEAT AIR BLENDER (REFER TO SEP. SCHED.) INTERNAL LIGHTS SERVICE RECEPTACLE UVGI (NOTE G) MINIMUM CURB HEIGHT MAXIMUM UNIT WEIGHT INCLUDING CURB (LBS) VOLTAGE - PHASE MINIMUM CIRCUIT AMPS MAXIMUM OVER CURRENT PROTECTION (AMPS) FUSED DISCONNECTMANUFACTURER MODEL MINIMUM FACE AREA (SQ. FT.) TOTAL CAPACITY (MBH) SENSIBLE CAPACITY (MBH) ENTERING AIR TEMPERATURE DB/WB (°F) LEAVING AIR TEMPERATURE DB/WB (°F) MAXIMUM AIR PRESSURE DROP (IN. W.C.) REFRIGERANT TYPEAIR-COOLED
MINIMUM QUANTITY OF COMPRESSORS MINIMUM STAGES OF COOLING HOT GAS BYPASSRTU-1 10 HDT DISTILLERY 2,000 0.50/1.0 1/BC 4 1 INTERNAL 25 127.7 75.1 90.0/74.0 55.5/54.9 .5 R410A 2 5 ●160.0 0.0 74.1 200 2" / 13 1 2,000 ● ● ● ●14" 3,000 208-3 53.9 60 ●- -
RTU-2 20 HDT FIRST FLOOR 7,490 1.0 / 4.0 1/BC 5 1 INTERNAL 40 248.7 150.5 80.0/67.0 61.7/57.1 .5 R410A 5 5 ●295.7 40.0 76.6 370 2" / 8 1.5 2,000 ● ● ● ●14" 3,000 208-3 178.2 225 ●- -
NOTES:
1. MOUNTING HEIGHT TO BOTTOM OF UNIT, UNLESS
NOTED...
2. COORDINATE LOCATION WITH ARCHITECT.
GENERAL NOTES:
A. HEATING CAPACITY BASED ON 60°F ENT. AIR
B. ELECTRICAL SERVICE TO 3-PHASE UNITS SHALL BE
3-WIRE UNLESS NOTED OTHERWISE.
C. 3-PHASE COIL LOADS SHALL BE DIVIDED EVENLY
ACROSS EACH PHASE.
D. VERIFY/COORDINATE CABINET DIMENSIONS,
MOUNTING
& RECESS REQUIREMENTS PRIOR TO ORDERING.
E. RECESSED UNITS SHALL HAVE FOUR(4) SIDE
OVERLAP...
F. COORDINATE LINTELS IN MASONRY WALLS FOR FULL &
SEMI-RECESSED UNIT WALL OPENINGS.
G. WHEN APPLICABLE, REFER TO SPECIFICATIONS FOR
VIBRATION ISOLATOR TYPES.
ELECTRIC HEATING UNITS
MARKDESCRIPTION MOUNTING CFMHEATI
NG
ELECTRICAL
SERVICE
APPROX. CABINET
DIMENSIONS THERMOSTAT
SEE NOTE KW VOLTAGE - PHASE AMPS INTEGRAL DISCONNECT WIDTH DEPTH HEIGHT MOUNTING HEIGHT (AFF, NOTE 1) UNIT MOUNTED WALL MOUNTEDEUH-1 PROPELLER UNIT HEATER WALL MOUNTED 650 10.0 208-3 28.0 ●19" 8" 22" 8'-0"●- 1
EUH-2 PROPELLER UNIT HEATER WALL MOUNTED 350 5.0 208-3 14.0 ●14" 8" 16" 8'-0"●- 1
EUH-3 PROPELLER UNIT HEATER WALL MOUNTED 350 5.0 208-3 14.0 ●14" 8" 16" 8'-0"●- 1
EWH-1 WALL UNIT HEATER WALL RECESSED 650 4.8 208-3 13.3 ●14.375" 3.5" 18.25" 0'-0"●- 2
●-
NOTES:
1. NOT USED
GENERAL NOTES:
A. COOLING CAPACITY BASED ON 95°F AMBIENT AIR TEMPERATURE.
B. REFRIGERANT PIPING - SIZES LISTED ARE APPROX. CIRCUITING, SIZING,
NUMBER OF PIPES AND CIRCUITS, ARRANGEMENT, ETC. SHALL BE IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
C. ELECTRIC SERVICE - SINGLE POINT POWER SERVICE CONNECTION. ADEQUACY
OF LISTED CIRCUIT SIZES MUST BE VERIFIED BY CONTRACTOR AND UNIT
SUPPLIER. COST FOR INCREASE OR CHANGE OF ELECTRIC SERVICE FOR
EQUIPMENT SELECTED SHALL BE BORNE BY HVAC CONTRACTOR.
AIR-COOLED CONDENSING UNITS
MARK SERVICE NOMINAL CAPACITY (TONS) UNIT RATING (SEER) REFRIGERANT TYPECONDENSER FANS COMPRESSORS
ELECTRICAL
SERVICE DIMENSIONS MISC. BASIS OF DESIGN
SEE NOTETYPE MIN. QTY. MOTOR (HP / WATTS, EACH) TYPE MIN. QTY. UNIT MCA MAX FUSE / BREAKER (AMPS) UNIT VOLTAGE - PHASE LENGTH WIDTH HEIGHT APPROX. WEIGHT (LBS.) LOW AMBIENT CONTROL HOT GAS BYPASS CRANKCASE HEATER CONCRETE PADMANUFACTURER MODEL
ACCU-1 AHU-1 20 12.1 R410A DIRECT DRIVE 2 1.00 HP SCROLL 2 98 125 208-3 96" 48" 46" 1,000 - - - - - -
NOTES:
1. NOT USED
GENERAL NOTES:
A. ROOF OPENING SIZES ARE APPROXIMATE.
VERIFY SIZE AND COORDINATE.
B. COORDINATE STEEL FRAMING AROUND ROOF
OPENING, WHERE REQUIRED FOR DECK SUPPORT.
GRAVITY ROOF VENTILATORS
MARKDESCRIPTION CFM MAX. STATIC PRESSURE (IN. W.C.)NECK SIZE
APPROX. HOOD
SIZE
APPROX. ROOF OPENING SIZE APPROX. WEIGHT (LBS.)BACKDRAFT
DAMPER BASIS OF DESIGN
SEE NOTE LENGTH WIDTH LENGTH WIDTH / DIAMETER HEIGHT MOTORIZED GRAVITYMANUFACTURER MODEL
RAH-1 RELIEF HOOD 13640 .03 84" 60" 108" 93" 26" 90" X 66" 400 -●GREENHECK FGR
NOTES:
1. BASIS OF DEISGN: PRICE RDV
GENERAL NOTES:
A. TYPES - "V.V.", VARIABLE VOLUME;
"V.V.T.", VARIABLE VOL./TEMP.
B. .5" MAXIMUM STATIC PRESSURE
DROP THRU UNIT AT MAXIMUM CFM.
AIR TERMINAL UNITS
MARK TYPEMINIMUM
INLET SIZE CFM
SEE NOTE DIAMETER WIDTH HEIGHT MAXIMUM MINIMUMZD-1 V.V. 12" 1,200 400 1
ZD-2 V.V. 16" 2,080 650 1
ZD-3 V.V. 16" 1,920 650 1
ZD-4 V.V. 12" 825 400 1
DISTILLERY SUPPLY A - -+3"512 6 ●-
DISTILLERY EXHAUST A -●--1"-524 12
NOTES:
1. NOT USED
GENERAL NOTES:
A. GAS DELIVERY PRESSURE IS 14" W.C. B. WHEN APPLICABLE, REFER TO SPECIFICATIONS FOR VIBRATION
ISOLATOR TYPES.
GAS-FIRED RADIANT HEATING UNITS
MARKDESCRIPTION MOUNTING
LOCATION
GAS INPUT (CFH) HEATING OUTPUT (MBH)ELECT
RICAL
SERVI
CE DIMENSIONS
THERMOS
TAT BASIS OF DESIGN
SEE NOTEROOM NAME VOLTAGE - PHASE GAS CONNECTION SIZE VENT OUTLET SIZE COMB. AIR INLET SIZE APPROX. OPERATING WEIGHT (LBS) UNIT MOUNTED WALL MOUNTED LINE VOLTAGEMANUFACTURER MODEL
RH-1 GAS-FIRED UNIT HEATER OVERHEAD EXTERIOR DINING 100 1,000 120-1 0.75" 4" 4" 175 ●-●ROBERTS GORDON COMPLETE HED -
RH-2 GAS-FIRED UNIT HEATER OVERHEAD EXTERIOR DINING 125 1,250 120-1 0.75" 4" 4" 225 ●-●ROBERTS GORDON COMPLETE HED -
No. Description Date