HomeMy WebLinkAbout07_2017-03-30 - Sun King Distillery - CDs - DIV-26 DWGSFIRE ALARM SYMBOLS
FIRE ALARM BELL & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT
SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS
WHERE REQUIRED.
ELECTRICAL CONNECTION.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS
NOTED OTHERWISE).
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERWISE).
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH
TAYMAC #10310 STANDARD COVER, VERTICAL MOUNT.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH
UNLESS NOTED OTHERWISE), WITH TAYMAC #20310 STANDARD COVER, VERTICAL MOUNT.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, ON EMERGENCY POWER (18" MH UNLESS NOTED OTHERWISE).
20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).
20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLOOR BOX WITH SA-2525
COVERPLATE AND SC-3091 HOUSING. PROVIDE CARPET FLANGE WHERE REQUIRED.
20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).
20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).
30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).
50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).
20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).
30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).
50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).
JUNCTION BOX.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERWISE).
CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).
SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).
TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).
SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).
KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.
SWITCH WITH RECEPTACLE (46" MH UNLESS NOTED OTHERWISE) STANDARD TWO-GANG ASSEMBLY OF SWITCH AND
RECEPTACLE.
FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS
NOTED OTHERWISE).
HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
DISCONNECT SWITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.
LINE VOLTAGE THERMOSTAT.
UNIT HEATER.
FAN COIL.
ELECTRIC BASEBOARD HEATER.
AIR CONDITIONER.
CONDENSING UNIT.
UNIT VENTILATOR.
CORD REEL.
POWER POLE.
PHOTOELECTRIC SENSOR.
LIGHTING CONTACTOR.
CEILING MOUNTED OCCUPANCY SENSOR.
WALL MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
OCCUPANCY SENSOR POWER PACK.
FIRE ALARM SPEAKER & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS
NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM CHIME & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT
SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM HORN & SIGNAL LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT
SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM SIGNALING LIGHT (80" AFF), (# WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT
SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
CEILING MOUNTED HEAT DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRIC RELEASE DOOR CLOSER.
ELECTRO-MAGNETIC DOOR HOLDER.
WATER FLOW SWITCH.
VALVE SUPERVISORY SWITCH.
DUCT MOUNTED DETECTOR REMOTE TEST STATION AND ALARM INDICATOR LIGHT. SUBSCRIPT "W" INDICATES WALL
MOUNTED.
SMOKE DAMPER.
FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).
PUSHBUTTON (46" MH UNLESS NOTED OTHERWISE) EDWARDS 852 (120 VOLT).
BUZZER (90" MH UNLESS NOTED OTHERWISE) EDWARDS 340-A (120 VOLT).
4" DIAMETER (90" MH UNLESS NOTED OTHERWISE) EDWARDS "ADAPTABEL" (120 VOLT).
GF
WP
WP/GF
EM
T
IG
20A
30A
50A
20A
50A
30A
J
2
#
P
K
DM
R
H
UH
FC
AC
CU
UV
PP
OS
OS
DS
OP
PC
T
F
15
F
15
F
15
F
15
15
S F CEILING MOUNTED FIRE ALARM SPEAKER.
KF
S
H
C
D
FS
V
R
W
SD
FT
B
PRESSURE SWITCH.
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
POST INDICATOR VALVE.
KNOX BOX.
PS
AM C/I
PIV
K
FIRE ALARM CONTROL PANEL.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).
C
M
CR
LC
P/B
H
S S/R
S/R
ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERWISE) WITH RESET SWITCH (46" MH UNLESS NOTED
OTHERWISE).
INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH
UNLESS NOTED OTHERWISE).
INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).
INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).
INTERCOM SPEAKER FLUSH MOUNT IN CEILING.
I
M
H
S
FACP
DUCT HEATER.H DH
H EB
LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L
TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS
P WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLE
CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
XR WALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE
DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.
XV WALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE
DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE) PER DIV 26.
J TELECOM BOX AND CONDUIT PER DIV 26, REFER TO PLANS.
WALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE CORRIDOR
CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
XI
WALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUITS TO ABOVE ACCESSIBLE
CEILING PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X"
INDICATES ALTERNATE CONFIGURATION.
AP WALL MOUNTED WIRELESS ACCESS POINT (96” MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. WAP AND CABLE PER DIV 27.
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC CONTRACTOR (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING CONTRACTOR (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY CONTRACTOR
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTOR
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/0 - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
1
E2
B
E2 DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)
DENOTES CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CONDUIT FOR DATA CIRCUITRY.DAT
WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA
WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL
CONDUIT FOR PHONE CIRCUITRY.PHO
WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC
WIRE RUN IN SURFACE WIREWAY.W
CABLE MANAGEMENT SYSTEM PATHWAY.CM
X - 1,2
WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM
WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S
WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I
WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV
3
3
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES
SWITCHING ARRANGEMENT.
LIGHTING FIXTURE ON NIGHT LIGHT OR BATTERY CIRCUIT.
EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.
A
a
WIREMOLD RACEWAY, AS NOTED ON PLANS.
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
4"
4"
4"
3
3
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLUSH FLOOR BOX WITH ROUND SA-3925
COVERPLATE. PROVIDE CARPET FLANGE WHERE REQUIRED.
TECHNOLOGY FLOOR BOX PER DIV 26. PROVIDE APPROPRIATE CONNECTOR PLATE AND HINGED COVER. "#"
INDICATES OUTLET TYPE. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION. REFER TO FACEPLATE DETAILS.#X
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:09 AME001
SYMBOLS,
ABBREVIATIONS &
INDEX
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
No. Description Date
ELECTRICAL SHEET INDEX
Sheet Description
E001 SYMBOLS, ABBREVIATIONS & INDEX
E002 SINGLE LINE DIAGRAM & PANEL SCHEDULES
E003 ELECTRICAL SCHEDULES
E004 ELECTRICAL DETAILS
E201 FIRST FLOOR LIGHTING PLAN
E202 SECOND FLOOR LIGHTING PLAN
E301 FIRST FLOOR POWER & SYSTEMS PLAN
E302 SECOND FLOOR POWER & SYSTEMS PLAN
E303 ROOF POWER PLAN
M
5432
1
2 3 4 5
6 7 8
1 6
1 2
POWER CO. X'FMR
12,470V TO 208Y/120V
POWER CO. SOURCE
12470Y/7400V
CT'S BY POWER CO.
POWER CO. METER
2" C.MAIN PANEL MDP
DISTRIBUTION PANEL 1DP
1000A, 208Y/120V-3Ø-4W
800A, 208Y/120V-3Ø-4W
"1L1""1L2""1L3""1L4""2L1"
SERVICE
SPD
N
G REMOVABLE
LINK
MAIN BUILDING
GROUND BAR
CONCRETE ENCASED ELECTRODE
GROUND RODS
BUILDING STEEL
#3/0
METALLIC
WATER PIPE
SEE PANEL SCHEDULE FOR MECHANICAL LOADS
1
3 4 24
3 4 5 6 7
8
4 3
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:13 AME002
SINGLE LINE
DIAGRAM & PANEL
SCHEDULES
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SINGLE-LINE DIAGRAM1
312.10 kVA
TOTAL CONNECTED ESTIMATED DEMAND
NOTES:SEE SINGLE-LINE DIAGRAM FOR FEEDER SIZING
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6 1L4 1.16 kVA 250 A 2 60 A
5 1L3 0.98 kVA 250 A 2 60 A
4 1L2 1.01 kVA 250 A 2 60 A
3 2L1 27.81 kVA 250 A 3 225 A
2 1L1 40.74 kVA 250 A 3 225 A
1 1DP 240.37 kVA 800 A 3 800 A
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size:Spec. Ref. #:
Voltage:120/208 Wye-3PH-4W Mains Rating:1000 A
Supply From:Enclosure:NEMA 1 Mains Type:MCB
Location:Elec. 111 Mounting:SURFACE A.I.C. Rating:42K
DISTRIBUTION PANEL: MDP
40.76 kVA 32.79 kVA (91 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load:11.89 kVA 13.90 kVA 14.96 kVA
83 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 84
81 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 82
79 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 80
77 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 78
75 RECEPTACLES 20 A 1 180 VA 0 VA 1 20 A SPARE 76
73 RECEPTACLES 20 A 1 480 VA 830 VA 1 20 A RECEPTACLES 74
71 RECEPTACLES 20 A 1 720 VA 1000... 1 20 A TVS 72
69 RECEPTACLES 20 A 1 1100... 1000... 1 20 A TVS 70
67 RECEPTACLES 20 A 1 720 VA 1000...1 20 A BAR TVS 68
65 BAR RECEPTACLES 20 A 1 1440... 1500... 1 20 A SINK 66
63 RH-1,2 20 A 1 240 VA 1500... 1 20 A SINK 64
61 RCP-1 20 A 1 0 VA 1500...1 20 A SINK 62
59 ROM-1,2 20 A 1 2300... 1500... 1 20 A SINK 60
57 ROP-1,2 20 A 1 1590... 1500... 1 20 A SINK 58
55 RECEPTACLES 20 A 1 720 VA 1500...1 20 A SINK 56
53 RECEPTACLES 20 A 1 720 VA 360 VA 1 20 A RECEPTACLES 54
51 -- -- -- 0 VA 1260... 1 20 A RECEPTACLES 52
49 -- -- -- 0 VA 900 VA 1 20 A RECEPTACLES 50
47 DISTILLERY 20 A 3 0 VA 360 VA 1 20 A RECEPTACLES 48
45 -- -- -- 817 VA 180 VA 1 20 A FREEZER 46
43 -- -- -- 817 VA 180 VA 1 20 A COOLER 44
41 GRAIN MTR 20 A 3 817 VA 180 VA 1 20 A COOLER 42
39 -- -- -- 0 VA 360 VA 1 20 A RECEPTACLES 40
37 -- -- -- 0 VA 360 VA 1 20 A RECEPTACLES 38
35 MILL MACHINE 20 A 3 0 VA 540 VA 1 20 A RECEPTACLES 36
33 FERMENTERS 20 A 1 0 VA 1080... 1 20 A RECEPTACLES 34
31 RO SYSTEM 20 A 1 0 VA 540 VA 1 20 A RECEPTACLES 32
29 IDF 20 A 1 360 VA 360 VA 1 20 A RECEPTACLES 30
27 IDF 20 A 1 360 VA 720 VA 1 20 A RECEPTACLES 28
25 IDF 20 A 1 360 VA 0 VA 1 20 A SPARE 26
23 IDF 20 A 1 360 VA 0 VA 1 20 A SPARE 24
21 RECEPTACLES 20 A 1 360 VA 500 VA 1 20 A FACP 22
19 LIGHTING 20 A 1 280 VA 0 VA 1 20 A BAR LTG 20
17 LIGHTING 20 A 1 1272... 126 VA 1 20 A BAR LTG 18
15 LIGHTING 20 A 1 149 VA 418 VA 1 20 A BAR LTG 16
13 LIGHTING 20 A 1 315 VA 180 VA 1 20 A EXTERIOR LTG 14
11 LIGHTING 20 A 1 0 VA 174 VA 1 20 A LIGHTING 12
9 LIGHTING 20 A 1 0 VA 4 VA 1 20 A LIGHTING 10
7 LIGHTING 20 A 1 962 VA 0 VA 1 20 A LIGHTING 8
5 LIGHTING 20 A 1 499 VA 371 VA 1 20 A LIGHTING 6
3 EXTERIOR LTG 20 A 1 468 VA 112 VA 1 20 A ELEV LTG 4
1 EM / EXIT LTG 20 A 1 65 VA 180 VA 1 20 A ELEV PIT 2
CKT Circuit Description Trip Poles
A B C Poles Trip Circuit Description CKT
Voltage:120/208 Wye-3PH-4W Mains Rating:225 A
Supply From:MDP Enclosure:Type 1 Mains Type:MLO
Location:Elec. 111 Mounting:Surface A.I.C. Rating:42K
Panel: 1L1
27.81 kVA 23.23 kVA (64 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load:9.56 kVA 9.31 kVA 8.94 kVA
59 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 60
57 RH-1 20 A 1 120 VA 0 VA 1 20 A SPARE 58
55 EF-6 20 A 1 696 VA 0 VA 1 20 A SPARE 56
53 EF-5 20 A 1 1056... 0 VA 1 20 A SPARE 54
51 EF-4 20 A 1 696 VA 0 VA 1 20 A SPARE 52
49 EF-3 20 A 1 528 VA 0 VA 1 20 A SPARE 50
47 EF-2 20 A 1 1056... 0 VA 1 20 A SPARE 48
45 EF-1 20 A 1 648 VA 180 VA 1 20 A RECEPTACLES 46
43 SINK 20 A 1 1500... 720 VA 1 20 A BAR RECEPTACLES 44
41 SINK 20 A 1 1500... 1500... 1 20 A SINK 42
39 PIZZA OVEN 20 A 1 180 VA 1500... 1 20 A SINK 40
37 RECEPTACLES 20 A 1 360 VA 1500...1 20 A SINK 38
35 RECEPTACLES 20 A 1 540 VA 0 VA 1 20 A BOILER 36
33 RECEPTACLES 20 A 1 720 VA 2080... 1 20 A RECEPTACLES 34
31 RECEPTACLES 20 A 1 680 VA 1400...1 20 A RECEPTACLES 32
29 RECEPTACLES 20 A 1 1212... 360 VA 1 20 A RECEPTACLES 30
27 RECEPTACLES 20 A 1 360 VA 1080... 1 20 A RECEPTACLES 28
25 RECEPTACLES 20 A 1 360 VA 360 VA 1 20 A IDF 26
23 RECEPTACLES 20 A 1 540 VA 360 VA 1 20 A IDF 24
21 RECEPTACLES 20 A 1 900 VA 180 VA 1 20 A ELEV RECEPTACLE 22
19 RECEPTACLES 20 A 1 720 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 LIGHTING 20 A 1 210 VA 0 VA 1 20 A LIGHTING 14
11 LIGHTING 20 A 1 140 VA 502 VA 1 20 A PERGOLA LTG 12
9 LIGHTING 20 A 1 184 VA 0 VA 1 20 A BAR LTG 10
7 LIGHTING 20 A 1 0 VA 173 VA 1 20 A BAR LTG 8
5 LIGHTING 20 A 1 172 VA 0 VA 1 20 A LIGHTING 6
3 LIGHTING 20 A 1 483 VA 0 VA 1 20 A LIGHTING 4
1 EM / EXIT LTG 20 A 1 35 VA 316 VA 1 20 A LIGHTING 2
CKT Circuit Description Trip Poles
A B C Poles Trip Circuit Description CKT
Voltage:120/208 Wye-3PH-4W Mains Rating:225 A
Supply From:MDP Enclosure:Type 1 Mains Type:MLO
Location:STAFF BREAK 211 Mounting:Flush A.I.C. Rating:22K
Panel: 2L1
1.01 kVA 1.04 kVA (3 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:THIS PANEL SERVES KITCHEN EQUIPMENT IN FOOD 1. PROVIDE BRANCH CIRCUITS AS COORDINATED WITH K.E.C.
SUPPLIER.
ALL 120V, 15A & 20A BRANCH CIRCUITS TO BE GF PROTECTED.
PROVIDE SHUNT TRIP MAIN BREAKER AND INTERLOCK WITH FIRE SUPPRESSION SYSTEM.
Total Load:0.47 kVA 0.54 kVA 0.00 kVA
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 RECEPTACLES 20 A 1 360 VA 180 VA 1 20 A EXH HOOD 4
1 LIGHTING 20 A 1 112 VA 360 VA 1 20 A RECEPTACLES 2
CKT Circuit Description Trip Poles
A B C Poles Trip Circuit Description CKT
Voltage:120/208 Wye-3PH-4W Mains Rating:60 A
Supply From:MDP Enclosure:Type 1 Mains Type:MCB
Location:Food 1 120 Mounting:Surface A.I.C. Rating:10K
Panel: 1L2
0.98 kVA 1.01 kVA (3 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:THIS PANEL SERVES KITCHEN EQUIPMENT IN FOOD 2. PROVIDE BRANCH CIRCUITS AS COORDINATED WITH K.E.C.
SUPPLIER.
ALL 120V, 15A & 20A BRANCH CIRCUITS TO BE GF PROTECTED.
PROVIDE SHUNT TRIP MAIN BREAKER AND INTERLOCK WITH FIRE SUPPRESSION SYSTEM.
Total Load:0.44 kVA 0.54 kVA 0.00 kVA
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 RECEPTACLES 20 A 1 360 VA 180 VA 1 20 A EXH HOOD 4
1 LIGHTING 20 A 1 84 VA 360 VA 1 20 A RECEPTACLES 2
CKT Circuit Description Trip Poles
A B C Poles Trip Circuit Description CKT
Voltage:120/208 Wye-3PH-4W Mains Rating:60 A
Supply From:MDP Enclosure:Type 1 Mains Type:MCB
Location:Food 2 115 Mounting:Surface A.I.C. Rating:10K
Panel: 1L3
1.16 kVA 1.19 kVA (3 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:THIS PANEL SERVES KITCHEN EQUIPMENT IN FOOD 3. PROVIDE BRANCH CIRCUITS AS COORDINATED WITH K.E.C.
SUPPLIER.
ALL 120V, 15A & 20A BRANCH CIRCUITS TO BE GF PROTECTED.
PROVIDE SHUNT TRIP MAIN BREAKER AND INTERLOCK WITH FIRE SUPPRESSION SYSTEM.
Total Load:0.44 kVA 0.72 kVA 0.00 kVA
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 RECEPTACLES 20 A 1 540 VA 180 VA 1 20 A EXH HOOD 4
1 LIGHTING 20 A 1 84 VA 360 VA 1 20 A RECEPTACLES 2
CKT Circuit Description Trip Poles
A B C Poles Trip Circuit Description CKT
Voltage:120/208 Wye-3PH-4W Mains Rating:60 A
Supply From:MDP Enclosure:Type 1 Mains Type:MCB
Location:Kitchen 113 Mounting:Surface A.I.C. Rating:10K
Panel: 1L4
FEEDER SCHEDULE
# SIZE SETS CONDUCTORS
1 1000A 3 3-#600 (AL), #3/0 G (CU), 4" C
2 800A 2 4-#600, # 1/0 G, 4" C
3 225A 1 4-#4/0, # 4 G, 2.5" C
4 60A 1 4-# 6, # 10 G, 1.25" C
FAULT CURRENT SCHEDULE
REF.
POINT DESCRIPTION EQUIP. RATING
AVAILABLE SHORT
CIRCUIT AMPS
1 UTILITY X'FMR
SECONDARY
- 36,206
2 MDP 42KAIC 32,706
3 1L1 42KAIC 25,742
4 1L2 10KAIC 3,049
5 1L3 10KAIC 3,469
6 1L4 10KAIC 3,725
7 2L1 22KAIC 18,999
8 1DP 42KAIC 30,877
240.37 kVA
TOTAL CONNECTED ESTIMATED DEMAND
NOTES:SEE MOTORS, STARTERS, DISCONNECTS & CONTROLS SCHEDULE FOR CIRCUIT SIZING
20
19 COOLER 7.21 kVA 150 A 3 30 A
18 COOLER 7.21 kVA 150 A 3 30 A
17 COOLER 7.21 kVA 150 A 3 30 A
16 BRIDGE CRANE 2.80 kVA 150 A 3 20 A
15 FORK TRUCK 2.80 kVA 150 A 3 20 A
14 AIR COMP 5.50 kVA 150 A 3 20 A
13 EWH-1 5.04 kVA 150 A 3 20 A
12 EUH-3 5.04 kVA 400 A 3 20 A
11 EUH-2 5.04 kVA 150 A 3 20 A
10 EUH-1 10.09 kVA 150 A 3 40 A
9 ACCU-C3 1.87 kVA 150 A 3 20 A
8 ACCU-C2 3.46 kVA 150 A 3 20 A
7 ACCU-C1 10.09 kVA 150 A 3 40 A
6 ACCU-1 35.31 kVA 150 A 3 125 A
5 CH-1 34.23 kVA 150 A 3 125 A
4 AHU-1 2.74 kVA 150 A 3 20 A
3 RTU-2 64.13 kVA 250 A 3 225 A
2 RTU-1 19.45 kVA 150 A 3 60 A
1 ELEVATOR 11.17 kVA 400 A 3 40 A
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size:Spec. Ref. #:
Voltage:120/208 Wye-3PH-4W Mains Rating:800 A
Supply From:MDP Enclosure:NEMA 1 Mains Type:MLO
Location:Elec. 111 Mounting:SURFACE A.I.C. Rating:42K
DISTRIBUTION PANEL: 1DP
No. Description Date
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:18 AME003
ELECTRICAL
SCHEDULES
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
NOTES:
1.
2.
3.
4.
LUMINAIRE SCHEDULE
MARK
LAMPS
LOAD (VA) FIXTURE VOLTAGEMANUFACTURER CATALOG NO. DESCRIPTION DIFFUSING MEDIA
TRIM COLOR MOUNTING SIZE
SEE NOTEQUANTITY
VA / LINEAR FOOT DELIVERED LUMENS COLOR WHITE BLACK ALUMINUM BRONZE STANDARD SEE NOTES-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE
DIAMETER WIDTH LENGTH DEPTH FLUORESCENT INCANDESCENT H.I.D. L.E.D.16 0 0 12" 48" 5.5"
A1 X 3200 3000K 35 120 METALUX SERIES "22GR LED" HEAVY GAUGE STEEL HOUSING WITH FLUSH
ALUMINUM TOOLESS DROP DOOR, RECESSED GRID
MOUNTED LENSED TROFFER, INSTANT START
ELECTRONIC MULTI-VOLTAGE BALLAST
PRISMATIC ACRYLIC
LENS
●R 24" 24" 3.75"
A2 X 5100 3000K 58 120 METALUX SERIES "SNLED LENSED" 4" LED LINEAR LENSED STRIP FIXTURE. DIE-FORMED
COLD ROLLED STEEL, BAKED WHITE ENAMEL FINISH.
PRISMATIC ACRYLIC
LENS
●P 4" 48" 5.5"
B1 X 900 3000K 12 120 HALO SERIES "ML4" 4" LED DOWNLIGHT W/ ULTRA-SHALLOW HOUSING SEMI SPECULAR
CLEAR
●R 4" 8.75"
B2 X 1000 3000K 11 120 HALO SERIES "PD615" 6" LED DOWN LIGHT SEMI SPECULAR
CLEAR
●R 6" 8.75"
B3 X 1500 3000K 17 120 HALO SERIES "PD615" 6" LED DOWN LIGHT SEMI SPECULAR
CLEAR
●R 6" 8.75"
C1 X 5 3000K 0 120 CONTECH LIGHTING SERIES "TLT" LED TAPE LIGHT WITH RIGID CHANNEL, WET RATED SURFACE 1" 1"
C2 X 743 3000K 80 120 LUMINAIRE LED THE STAIRLIGHTER "TSL93" DIE FORMED COLD ROLLED COATED STEEL. VANDAL
RESISTANT, INTEGRAL OCCUPACY SENSOR FOR
HI/LOW OPERATION W/ 2600 LUMEN
SELF-CONTAINED 90-MIN EMERGENCY BATTERY
PACK.
ACRYLIC LENS WM 4" 36" 10"
C3 3 8000 3000K 63 120 PHOENIX SERIES "LFXR" EXPLOSION PROOF INDUSTRIAL FLUORESCENT
FIXTURE
CLEAR ●C 12" 53"
D1 X 390/390 3000K 6 120 ARCLUCE SERIES "TULA" LED SCONCE WITH UP/DOWNLIGHT TEMPERED GLASS ●WM 2" 4.801"
D2 X 1250 3000K 13 120 LURALINE SERIES "RLM" SPUN ALUMINUM SHADE W/ EXTRUDED ARM AND
CAST CANOPY
WM 12" 17.125" 6"
G1 X 2600 3000K 13 120 ARCLUCE SERIES "DUEDIECI" ACCENT FLOOD FOR LOGO WM
H1 X 5882 3000K 56 120 METALUX SERIES "4VT2" INDUSTRIAL LED LINEAR FIXTURE. VAPORTITE
FIBERGLASS HOUSING W/ GASKETING FOR
SEAMLESS SEAL.
S 4" 6" 48"
H2 X 3000K 2 120 COOPER SURE-LITES SERIES "AEL2" ARCHITECTURAL EMERGENCY EGRESS LIGHT WM 17.5" 8.25"
H3 X 2751 3000K 26 120 LUMARK SERIES XTOR CROSSTOUR LED" ARCHITECTURAL AREA LIGHT WM 12" 17.125" 6"
H4 X 12000 3000K 106 120 METALUX SERIES "SS LED" LED ROUND HIGH-BAY FIXTURE P 17" 16"
P1 X 4095 3000K 87 120 EUREKA SERIES "CYCLE 72" DECORATIVE PENDANT, AIRCRAFT CABLE
MOUNTING
P 72" 18"
P2 X 1392 3000K 18 120 TECH LIGHTING SERIES "HUTCH" LED PENDANT, 90 CRI P 13" 17"
P3 X 737 3000K 9 120 LBL LIGHTING SERIES "ZEVO PENDANT" DECORATIVE PENDANT P 18" 8"
P4 X 376 3000K 4 120 EUREKA SERIES "ANATOMY" DECORATIVE PENDANT P 13" 17"
P5 3000K 0 120 CUSTOM SUN KING SUPPLIED CUSTOM PALETTE FIXTURE P 17" 16"
P6 1 3000K 35 120 TECH LIGHTING SERIES "SOCO" SOCKET & CORD SET 6" 5"
P7 X 1860 3000K 40 120 EUREKA SERIES "CYCLE 36" DECORATIVE PENDANT, AIRCRAFT CABLE
MOUNTING
P 36" 17"
P8 X 1100 3000K 35 120 CONTECH LIGHTING SERIES "CY3" DECORATE LED CYLINDER FIXTURE 6" 5"
S1 X 357 3000K 4 120 TECH LIGHTING SERIES "FETT WALL" DECORATIVE WALL SCONCE P 4" 12"
TL 3000K 0 120 CONTECH LIGHTING SERIES "LT" TRACK LIGHTING CHANNEL, SINGLE CIRCUIT W/
CURRENT LIMITING POWER FEEDS
WM 1.5" 1"
TLF X 2700K 15 120 CONTECH LIGHTING SERIES "CTL8071" LED CYLINDER TRACK FIXTURE, MEDIUM, DIMMING,
BLACK FINISH
●TRACK 3" 5"
X X 5 5 120 COOPER SURE-LITES SERIES "LPXW"" FLAME RETARTDANT, POLYCARBONATE HOUSING,
WHITE WITH RED LETTERS. 90-MINUTE BATTERY
WITH SELF-DIAGNOSTIC MONITORING
●C 9" 13" 2.375"
X1 X 125 5 120 TELESIS SERIES "TCL LED" THERMOPLASTIC HOUSING, BLACK FINISH, 2W LED
HEADS, REMOTE HEAD CAPABILITY, 90-MINUTE
BATTERY WITH SELF-DIAGNOSTIC MONITORING
●WM 5.375" 13" 5.75"
NOTES:
1. SWITCH/STARTER LOCATED BY FORK TRUCK
2.
3.
4.
MOTORS, STARTERS, DISCONNECTS & CONTROLS
MARK
MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER
SEE NOTENAMEPLATE
CHARACTERISTICS
NEMA SIZETYPE LOCATION
FURNISHED BYTYPE LOCATION
FURNISHED BY INTERLOCK WITH MOTOR NO. BY E.C. MANUAL AT STARTER INTEGRAL WITH EQUIPMENT FURNISHED BY SEE NOTE NUMBER OF CONDUCTORS WIRE SIZE GROUND SIZE CONDUIT SIZE HORSEPOWER (HP) LOAD (kVA) 120V-1PH 208V-1PH 208V-3PH 240V-1PH 240V-3PH 277V-1PH 480V-1PH 480V-3PH MANUAL MAGNETIC BUILT-IN MOTOR O/L 2-SPEED VFD SEE NOTE NEAR MOTOR MOTOR CONT CENTER EQUIP CONT PANEL ROOM NUMBER SEE NOTE DISC SWITCH MANUAL STARTER RECEPTACLE FEEDER SW OR BREAKER NEMA TYPE DISC SIZE FUSE SIZE NEAR MOTOR MOTOR CONT CENTER EQUIP CONT PANEL PANELBOARD SEE NOTEACCU-1 35.3 ● ● ● ● ● ●MC ●MC 3 1 6 2"
ACCU-C1 2x 4 10.1 ● ● ● ● ● ●EC ●MC 3 8 10 1"
ACCU-C2 3 3.5 ● ● ● ● ● ●EC ●MC 3 12 12 0.75"
ACCU-F1 1.5 1.9 ● ● ● ● ● ●EC ●MC 3 12 12 0.75"
ACCU-R 7.2 ● ● ● ● ● ●EC ●MC 3 10 10 0.75"
AHU-1 5 2.7 ●● ● ● ●MC ●MC 3 8 10 1"
CH-1 5 34.2 ● ● ● ● ●MC ●MC 3 1 6 1.25"
EF-1 0.5 0.6 ●● ● ● ● ●MC ●EC 2 12 12 0.75"
EF-2 1 1.1 ●● ● ● ● ●MC ●EC 2 12 12 0.75"
EF-3 .16 0.5 ●● ● ● ● ●MC ●EC 2 12 12 0.75"
EF-4 .25 0.7 ●● ● ●MC ● ●MC ●MC 2 12 12 0.75"
EF-5 1 1.1 ●● ●MC ● ●MC ●EC 2 12 12 0.75"
EF-6 .25 0.7 ●● ●1 MC ● ●MC ●EC 2 12 12 0.75"
ELEV 10 11.2 ●●GC EC EC 3 8 10 1"
EUH-1 10.1 ● ● ● ● ● ●MC ●MC 3 8 10 0.75"
EUH-2 5 ● ● ● ● ● ●MC ●MC 3 12 12 0.75"
EUH-3 5 ● ● ● ● ● ●MC ●MC 3 12 12 0.75"
EWH-1 5 ● ● ● ● ● ●MC ●MC 3 12 12 0.75"
GRAIN 2 2.4 ●EC EC 3 12 12 0.75"
RCP-1 .20 0 ●● ●EC ● ●EC ●EC 2 12 12 0.75"
RH-1,2 0.1 ●EC EC 2 12 12 0.75"
RTU-1 19.5 ●● ● ● ●MC ●MC 3 6 10 0.75"
RTU-2 64.1 ●● ● ● ●MC ●MC 3 4/0 3 2"
No. Description Date
1 CONCRETE PAD BY E.C. 10" THICKNESS AND OPENINGS AS RECOMMENDED BY SUPPLIER OF
TRANSFORMER. 1/2" DIA. REINFORCED 12"CC BOTH WAYS.
2 PEA GRAVEL UNDER CONCRETE PAD 12" MINIMUM TO EXTEND 2FT.BEYOND EDGE OF PAD (12" DEEP).
3 SEE PLAN AND SCHEDULES FOR NUMBER AND SIZE OF CONDUIT.
4 GROUND GRID, #1/0 BARE COPPER UNLESS OTHERWISE SHOWN.
5 5/8" X 10FT. GROUND RODS UNLESS OTHERWISE SHOWN.
6 5FT. #1/0 BARE COPPER GROUNDING PIGTAIL.
7 CONCRETE DUCT ENCASEMENT.
8 EXPOSED CONCRETE SURFACES TO HAVE RUBBED FINISH AND 3/4" CHAMFERED CORNERS.
9 PROTECTIVE BOLLARD WHERE SPECIFIED: CONSISTING OF 4" DIA. RIGID GALVANIZED STEEL PIPES
FILLED WITH CONCRETE. SET IN 18" DIA. HOLE FILLED WITH TAMPED CONCRETE.
10 ALL PRIMARY AND SECONDARY UNDERGROUND CONDUITS TO HAVE LONG SWEEPING BENDS,
PROPER ADAPTER FROM PVC TO RIGID METALLIC CONDUIT AND STUB 3" ABOVE CONCRETE PAD.
11 A MINIMUM OF 10FT. CLEAR AREA MUST BE MAINTAINED IN FRONT OF TRANSFORMER AND OTHER
ELECTRIC DISTRIBUTION EQUIPMENT.
12 REFER TO SPEC. SECTION 26 27 13 FOR METERING REQUIREMENTS. COORDINATE METERING AND
SERVICE ENTRANCE REQUIREMENTS WITH POWER COMPANY.
13 TRANSITION CABINET WITH METERING TRANSFORMERS.
14 TRENCH WITH DIAMOND PLATE COVER FOR SECONDARY CONDUCTOR IF PERMITED BY POWER
COMPANY MY BE PROVIDED.
DETAIL NOTES
A COORDINATE EXACT CONCRETE PAD SIZE, OPENINGS AND OTHER REQUIREMENTS TO EXTEND
EDGE OF CONCRETE 12" BEYOND EQUIPMENT. ALL SIDES OF EQUIPMENT PAD SHALL BE
MAINTAINED RECTANGULAR WITH RUBBED FINISH AND CHAMFERED EDGE. REFER TO SPEC
SECTION 26 27 13. COORDINATE EXACT ORIENTATION OF EQUIPMENT WITH POWER COMPANY
PRIOR TO EXCAVATION AND PROVIDE ACCORDINGLY.
B BOLLARDS NOT TO BE PROVIDED ON SIDES NEAR BUILDING.
GENERAL DETAIL NOTES
SECTION .30"...3"42"42"MIN.2
861
9
5 7 2 3 7
53
6
208Y/120V-3Ø-4W SECONDARY ELECTRICAL
FEEDER(S) PROVIDED BY EC; REFER TO
SINGLE-LINE DIAGRAM ON SHEET E002
2" EMPTY CONDUIT (WITH PULLWIRE)
TO ELECTRIC METER; LOCATIONS AS
INDICATED ON PLAN
UNDERGROUND PRIMARY
ELECTRIC SERVICE
DUCTBANK BY CONTRACTOR,
AND CONDUCTORS PROVIDED
BY POWER COMPANY REFER
TO SITE PLAN ON SHEET E301
FOR CONTINUATION.
PAD MOUNTED TRANSFORMER BY
POWER CO. 208Y/120V-3Ø-4W.
SECONDARY. REFER TO SITE
PLAN ON SHEET E301 FOR
LOCATION.
PLAN
8' 0" APPROX.36"TYP.APPROX 36"
5
14
11
6
10
12 13
4
10
5
9
1
11
1 3000 LB. CONCRETE.
2 4" I.D. DUCTS, SCHEDULE 40 PVC.
3 MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"
ENCASEMENT (TYPICAL). PROVIDE CONDUIT
SPACERS 6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
DETAIL NOTES
FINISH GRADE
.......
TAMPED
BACKFILL
1'-6"1'-6"2'-3" COVER1'-6"4
1
2
33
3A BUILDING STEEL CONNECTION SHALL BE EXOTHERMIC WELD. CLEAN SURFACE TO
BRIGHT METAL BEFORE CONNECTION AND RESTORE TO ORIGINAL FINISH AFTER
MAKING CONNECTION.
B BUILDING STEEL CONNECTION SHALL BE LOCATED ABOVE THE FINISH FLOOR. IN
SOME CASES CONNECTIONS ARE TO BE MADE BELOW SLAB ON EXPOSED TUBE
STEEL CASES.
GENERAL DETAIL NOTES
BUILDING STEEL CONNECTION
FINISHED FLOOR LINE
STEEL BUILDING COLUMN
FOUNDATION
#2/0 BARE CU GROUNDING CONDUCTOR
#4/0 BARE CU GROUNDING GRID
EXOTHERMIC WELD CONNECTION
UNI-STRUT OR EQUAL
CHANNEL BY DIV. 26
CONDUIT CLAMP
CONDUIT SIZE AS REQUIRED
SAFETY CABLE SHALL BE
ATTACHED TO CHANNEL OR
STRUCTURAL STEEL
WIRE GUARD AND
TEMPERED GLASS
SAFETY LENS
REFLECTOR
BALLAST HOUSING
POWER HOOK ASSEMBLY
CONDUIT LENGTH AS REQUIRED
JUNCTION BOX SHALL BE SUPPORTED
FROM CHANNEL OR DIRECTLY FROM
STRUCTURAL STEEL AS REQUIRED BY
THE LOCATION OF THE LIGHT FIXTURE.
CHANNEL SUPPORT AND
THREADED ROD BY DIV. 26.
SUPPORTED FROM
STRUCTURAL STEEL
A SEE DRAWINGS FOR MOUNTING HEIGHT
AND FIXTURE TYPE.
GENERAL DETAIL NOTES
SUPPRESSION SYSTEM
MICRO SWITCHES
120 V DEDICATED
CONTROL CIRCUIT
CONTROL RELAY,
8 POLE, 120 VAC
COIL MOUNTED IN
NEMA 1
ENCLOSURE.
SQUARE D
#8501X080V02 OR
APPROVED EQUAL
GAS VALVE
SHUNT TRIP CIRCUIT BREAKER
SUPPLY AIR FAN INTERLOCK
EXHAUST FAN INTERLOCK
FAP SIGNAL
SPARE
SPARE
120V
MECHANICALLY
HELD CONTACTOR
100A-3P
FUSED DISC SW
100A-3P
100AF
TO 208V/3Ø
SOURCE
TO 120V
SOURCE
AUXILARY
RELAY
TO FA
24VDC
OPT. AUX. CONTACT (SET)
L
NC
O
C
O R
NL
C
C
L2L1L2L1 L3
FUSED DISC SW
30A-2P
20AF
T2T1 T3
ELEVATOR
PUMP MOTOR
ELEVATOR
CONTROL
POWER
PACK
(PP)N
H
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
(AS REQ'D.)
H LED DRIVER(S)
LV
N
A
B
C
D
E
F
LV LOW VOLTAGE AS REQUIRED BY THE MANUFACTURER
H HOT WIRE LINE VOLTAGE
N NEUTRAL WIRE LINE VOLTAGE
120V
INTENT OF DETAIL IS FOR AUTO-ON/OFF OPERATION OF THE NORMAL-POWER LUMINAIRES IN THE CORRIDOR/ROOM. THE OCCUPANCY SIGNAL
WILL BE PROVIDED BY THE INSTALLED SENSOR(S).
DETAIL IS SCHEMATIC IN NATURE. REFER TO MANUFACTURES SPECIFIC WIRING DIAGRAMS FOR EXACT WIRING INFORMATION.
EQUIPMENT SUPPLIER/ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL COST FOR REVISIONS REQUIRED FROM
DETAIL DUE TO A DIFFERENT SYSTEM SELECTION.
MOUNT POWER PACK ABOVE ACCESSIBLE CEILING.
ALL EQUIPMENT SHALL BE MOUNTED IN AN ENCLOSURE PER THE MANUFACTURERS DIRECTIONS.
CONTRACTOR SHALL COORDINATE WITH MANUFACTURER FOR EXACT NUMBER OF POWER PACKS, OCCUPANCY SENSORS (FOR COMPLETE
COVERAGE OF THE CORRIDOR) AND ANY ADDITIONAL COMPONENTS FOR A COMPLETE AND OPERABLE SYSTEM. COORDINATE EXACT
COMPONENT MOUNTING LOCATIONS FOR PROPER CLEARANCE AND ACCESSIBILITY PRIOR TO ROUGH-IN.
GENERAL NOTES
1 20A 120V. CONTROL CCT.
2 PHOTOCELL INTERMATIC *K4136M (120/277V).
3 CONTACTOR C1A - MECHANICALLY HELD 10 POLE
LIGHTING CONTACTOR. SQUARE D, LXG-1000R6 WITH
ONE H.O.A. SWITCH AND 120V. COIL. WIRE IN
ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
4 CONTACTOR C1A, TIMECLOCK AND H.O.A. SWITCH TO BE
MOUNTED IN ONE NEMA 1 LOCKABLE ENCLOSURE WITH
HINGED COVER.
5 TIMECLOCK: TORK DZS400BP (120V). ASTRONOMIC 2 DAY
2 CIRCUIT WITH POWER BACKUP.
DETAIL NOTES
CCT.
NO.FIXTURES
CONTROLLED
CONTACTOR
C1A
PHOTOCELL ON
TIMER OFF
*INDICATES SPARE FOR
FUTURE USE
T A
O
H
C
PC
T
*
*
*
*
*
*
*
3
1
2
4
5
A STRUCTURAL DETAIL SHOWN IS REPRESENTATIVE ONLY. REFER TO
ARCHITECTURAL CONDITIONS ON THIS PROJECT.
GENERAL DETAIL NOTES
..3'-0"12"3/4" RGS CONDUIT
1-1/2" TO 3/4" REDUCING FITTING
EPDM RUBBER CAP WITH
STAINLESS STEEL CLAMP
SPUN ALUMINUM BASE FLANGE
ROOFING/FLASHING
3-1/2" X 3-1/2" X
1/4" L (TYP. 2)
1-1/2" U-BOLT
(TYP. 2)
1-1/2" TO 3/4" REDUCING FITTING
4" X 4" J-BOX WITH BLANK COVER
3/4" EMT BOX
COMPRESSION
CONNECTION
3/4" EMT CONDUIT
3/4" RGS NIPPLE, NUT
WASHER AND
COMPRESSION CONNECTOR
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:23 AME004
ELECTRICAL
DETAILS
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017ELECTRICAL DISTRIBUTION CENTER & TRANSFORMER PAD1
UNDERGROUND DUCTS2STRUCTURAL GROUNDING3
TYPE II HIGH BAY LUMINAIRE MOUNTING5
KITCHEN HOOD RELAY4
ELEVATOR WIRING SCHEMATIC7
OCCUPANCY SENSING - SINGLE CIRCUIT8
EXTERIOR LIGHTING CONTROLS9 PHOTOCELL MOUNTING6
(USED IN FOOD 1, FOOD 2 & FOOD 3)
No. Description Date
3
DM
L
DM
DM
DM
DMDM
OS
OS
OS
OS
OS OS
OS
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
Mill Room
121
Water
110
Food 1
120
JNTR CLST
119
Distillery
104
Freezer
109
Cooler
108
Cooler
107
Food 3
114
Hall
118
RR
116
RR
117
Hall
106
STAIR
112
STORAGE
105
Bar
102
Retail
122
Bar
103
Elec.
111
Food 2
115
Dining
101
Kitchen
113
VESTIBULE
100
C1
B1
B1
B1
D1 D1 D1 D1
B1
B1
P3 P3 P3 P3 P3 P3
B2 B2 B2 B2 B2 B2
B2 B2 B2 B2
H1
H1
H2
H2
A1
A1
A1
A1 A1 A1
B3 B3 B3B3
B3B3 B3
TL
TL
TL
TL
TL
TL
TL TL
TL TL
TL TL
TL
TL
C1
P2 P1
B2
H2
A2
A2
A2
D2 D2 D2 D2 D2 D2 D2 D2 D2
1
2
3
4
A2 A2 A2
A2A2A2
A2 A2 A2 A2 A2 A2 A2 A2
P1
B2
P4
P5 P5
B1
B1
B1
B1 B1 B1
B1B1B1
B2 B2 B2
B2
B2
B2
B2
B2
B2
B2B2
H3
5
5
5
A1
6
7
B1
D1
G1
B3
B3
B1
B1
S1S1
S1 S1
C2
C2
P2
P2
P2
X
C3 C3
B3
8
1L1 - 4
1L1 - 5
1L1 - 7
1L1 - 6
1L2 - 1
1L3 - 1
1L4 - 1
C1
1L1 - 14
1L1 - 11
1L1 - 12
1L1 - 9
1L1 - 3
1L1 - 9
1L1 - 9
1L1 - 15
1L1 - 16
1L2
1L4
1L3
MDP
1L1
P6
P6 P6 P6 P6 P6 P6 P6
X1
X1
X
X
X
X
X
XX
X
X1
X1
X1
P8 P8 P8 P8 P8 P8 P8 P8
P6
TL TLTL
TL1L1 - 20 TLF (TYP)
TLF (TYP) TLF (TYP)TLF (TYP)
TLF (TYP) TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP) TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)
1L1 - 18
1L1 - 8
1L1 - 9
1L1 - 10
1L1 - 13
1L1 - 19
X1
9
9
9
99
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:33 AME201
FIRST FLOOR
LIGHTING PLAN
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN1
1 THIS WINDOW IS TO BE OUTLINED WITH LED TAPE LIGHTING. REFER TO ARCHITECTURAL DRAWINGS
FOR DETAIL ON LED TAPE INSTALLATION.
2 FIXTURE IS MOUNTED ON TOP OF CANOPY. COORDINATE AIMING WITH ARCHITECT AND/OR LIGHTING
REPRESENTATIVE UPON COMPLETION OF INSTALLATION.
3 LED TAPE LIGHT ALONG PERIMETER. REFER TO ARCHITECTURAL DRAWINGS FOR DETAIL ON LED
TAPE INSTALLATION.
4 REFER TO 2ND FLOOR PLANS, SHEET E202, FOR LIGHTING IN THIS SPACE/ROOM.
5 LIGHTING INTEGRAL TO AND PROVIDED BY COOLER/FREEZER SUPPLIER. E.C. IS TO WIRE FIXTURES AND
SWITCHING UPON INSTALLATION OF THE COOLER/FREEZER.
6 THIS ROOM IS CLASSIFIED AS A N.E.C. CLASS II, DIVISION 1 INSTALLATION. ALL WIRING METHODS AND EQUIPMENT
IN THIS ROOM IS TO MEET APPLICABLE SECTIONS OF N.E.C. 502.
7 LIGHT SWITCH FOR MILL ROOM 121.
8 ELEVATOR CAB LIGHTING SWITCH/DISCONNECT. PROVIDE SWITCH LOCK-OUT MECHANISM.
9 EXTERIOR BUILDING LIGHTING TO BE CONTROLLED BY TIME CLOCK/PHOTO-CELL CONTROL. REFER TO
DETAIL 6\E004 & 9\E004 FOR DETAILS.
PLAN NOTES
A ALL EMERGENCY AND EXIT FIXTURES ARE TO BE CIRCUITED TO 1L1-1.
B EMERGENCY LIGHTING IS TO BE WIRED AHEAD OF ALL LOCAL CONTROLS (WALL
SWITCHES, OCCUPANCY SENSORS, ETC) SUCH THAT FIXTURES OPERATE
WITH THE NORMAL LIGHTING. CIRCUIT THE LOSS-OF-POWER SENSE WIRE
AHEAD OF ALL LOCAL CONTROLS,
C VERIFY EXACT LOCATION OF ALL LIGHTING FIXTURES WITH REFLECTED CEILING PLAN
AND/OR ARCHITECT PRIOR TO ROUGH-IN.
D COORDINATE LOCATIONS OF LIGHTING FIXTUES WITH MECHANICAL DUCTS AND
SPRINKLER PIPES AND HEADS BEFORE ROUGH-IN TO PREVENT CONFLICTS.
E COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT WITH MANUFACTURER
OR SUPPLIER PRIOR TO INSTALLATION.
F OCCUPANCY SENSOR MANUFACTURERS WITH DIFFERENT COVERAGE PATTERNS OR
RECOMMENDED AIMING PRACTICES FROM SPECIFIED MANUFACTURER SHALL
SUBMIT 1/8 INCH SCALE FLOOR PLANS SHOWING PROPOSED LAYOUT WITH DEVICES
CLEARLY IDENTIFIED DURING THE SHOP DRAWING REVIEW PHASE. SHOP DRAWINGS
MISSING THIS INFORMATION WILL BE REJECTED. REQUEST AUTOCAD FLOOR PLANS
WELL IN ADVANCE OF SHOP DRAWING SUBMITTAL TO ENSURE ON TIME DELIVERY.
G WIRE ALL OCCUPANCY SENSORS IN SAME AREA IN PARALLEL (NORMAL POWER
LIGHTING) FOR COMMON ZONE CONTROL.
GENERAL NOTES
No. Description Date
J
J
3DM
DM
DM DM DM
DM
DM
DM
DM
DM
OS
OS
OS
OS
OS
OS
OS
OS
A
B
C
C.4
D
E.7
11.2 1.4 2 2.4 3 4 5 6
RR
212
PIZZA OVEN
216
HALL
206
BOILER ROOM
207
RR
204
RR
205
STAFF BREAK
211
CATERING PREP
214
SUPPORT
215
JAN
208
OFFICE
210
BAR
201
DECK
202
PRIVATE FUNCTION
203
DINING
200
STAIR
213
Hall
209
C1
TLTLTLTL
TL
1
2
H4
H4 H4
H4 H4
H4 H4
H4 H4
H4 H4
H4
P2 PENDANTS ARE MOUNTED @ 23'-6" AFF
B2
B2
B2
B2
B2
B2
B2
A1 A1
A1
A1A1
A1 A1 A1
A1
A2 A2
A1 A1
A1 A1
A1A1
B2
B2 B2
B2B2
B2
B1 S1S1
B1
S1S1
TL
TL
TL
TLTL
B2
B2 B2 B2
B3
B3 B3
C2
C2
P2
P2
P2
P2
P2
P2
P2
P2
X
P7
TL
H3
H3
1L1 - 17
2L1
1L1 - 5
2L1 - 8
2L1 - 7
2L1 - 9
2L1 - 4
2L1 - 3
2L1 - 5
2L1 - 2
1L1 - 3
2L1 - 12
H2
H1
P6P6 P6P6 P6 P6
P8 P8 P8 P8
2L1 - 10 TL
TLF (TYP) TLF (TYP)
TLF (TYP)
TLF (TYP) TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)
TLF (TYP)TLF (TYP)
2L1 - 14
1L1 - 53
2L1 - 132L1 - 11
X
X1
X1
X1
X1
X
4
4
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:43 AME202
SECOND FLOOR
LIGHTING PLAN
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
SECOND FLOOR LIGHTING PLAN1
1 120V BRANCH CIRCUIT FOR SIGNAGE.
2 120V BRANCH CIRCUIT FOR FUTURE PERGOLA LIGHTING.
3 PROVIDE EM INVERTER FOR STAIR TRACK LIGHTING. LOCATE
ABOVE ACCESSIBLE CEILING NEAR STAIRS.
4 EXTERIOR BUILDING LIGHTING TO BE CONTROLLED BY TIME CLOCK/PHOTO-CELL CONTROL.
REFER TO DETAIL 6\E004 & 9\E004 FOR DETAILS.
PLAN NOTES
GENERAL NOTES
A ALL EMERGENCY AND EXIT FIXTURES ARE TO BE CIRCUITED TO 2L1-1.
B EMERGENCY LIGHTING IS TO BE WIRED AHEAD OF ALL LOCAL CONTROLS (WALL
SWITCHES, OCCUPANCY SENSORS, ETC) SUCH THAT FIXTURES OPERATE
WITH THE NORMAL LIGHTING. CIRCUIT THE LOSS-OF-POWER SENSE WIRE
AHEAD OF ALL LOCAL CONTROLS,
C VERIFY EXACT LOCATION OF ALL LIGHTING FIXTURES WITH REFLECTED CEILING PLAN
AND/OR ARCHITECT PRIOR TO ROUGH-IN.
D COORDINATE LOCATIONS OF LIGHTING FIXTUES WITH MECHANICAL DUCTS AND
SPRINKLER PIPES AND HEADS BEFORE ROUGH-IN TO PREVENT CONFLICTS.
E COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT WITH MANUFACTURER
OR SUPPLIER PRIOR TO INSTALLATION.
F OCCUPANCY SENSOR MANUFACTURERS WITH DIFFERENT COVERAGE PATTERNS OR
RECOMMENDED AIMING PRACTICES FROM SPECIFIED MANUFACTURER SHALL
SUBMIT 1/8 INCH SCALE FLOOR PLANS SHOWING PROPOSED LAYOUT WITH DEVICES
CLEARLY IDENTIFIED DURING THE SHOP DRAWING REVIEW PHASE. SHOP DRAWINGS
MISSING THIS INFORMATION WILL BE REJECTED. REQUEST AUTOCAD FLOOR PLANS
WELL IN ADVANCE OF SHOP DRAWING SUBMITTAL TO ENSURE ON TIME DELIVERY.
G WIRE ALL OCCUPANCY SENSORS IN SAME AREA IN PARALLEL (NORMAL POWER
LIGHTING) FOR COMMON ZONE CONTROL.
No. Description Date
WP/GFWP/GF
WP/GF
WP/GF
WP/GF
WP/GF
GF GF
GF
WP/GF
GF
GF
GF
GF
GF GF
J
J J
J
J
J
WP/GF
WP/GF
J J
GF
GF GFGF GF
GF
GF
GF GF
GFGF
H
V V FS
GFGFGFGFGFGFF
30
F F
30
F
15
F
30
F
15
F
30
F
30
15
15
F
F
F
K
FACP TV
102" MH
TV102" MH
TV102" MH TV102" MH
15
15
15
GF
F
30
HGFGFTV 90" MH TV 90" MHGF
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
Mill Room
121
Food 1
120
JNTR CLST
119
Distillery
104
Freezer
109
Cooler
108
Cooler
107
Food 3
114
Hall
118
RR
116
RR
117
Hall
106
STAIR
112
STORAGE
105
Bar
102
Retail
122
Bar
103
Food 2
115
Dining
101
Kitchen
113
VESTIBULE
100
Info
54
MDP
METER
SERVICE
X'FMR
8
9
9
9
4
5
6
7
3 3
3
1L1
10
11 11
1
1
1
14
1L2
1L4
1L3
15
1
EUH-1
EWH-1
1DP
1DP - 13
1DP - 10
1L1 - 30
1L1 - 36
1L4 - 3
1L4 - 4
1L4 - 2
1L3 - 31L3 - 4
1L2 - 4
1L2 - 2
1L2 - 3
1L1 - 47,49,51
1L1 - 33
1DP - 16
1L1 - 32
1DP - 15
1L1 - 34
1L1 - 35,37,39
1L1 - 41,43,45
GRAIN
1DP - 14
1L1 - 2
1L1 - 38
1L1 - 40
1L1 - 42
1L1 - 46
1L1 - 44
1L1 - 48
1L1 - 50
1L1 - 52
1L1 - 54
1L1 - 55
E301
2
1L1 - 561L1 - 581L1 - 661L1 - 601L1 - 621L1 - 642 2
RH-1
RH-2
1L1 - 63
1L1 - 63
1L1 - 72
1L1 - 70
+46"
+46"
+46"
WP
16
1L1 - 22
E301
3
1L1 - 75
21
WP
A
6
A
6
A
6A.12
Water
110
Elec.
111
1L1 1DP
MDP
EUH-3
EUH-2
1L1 - 21
1L1 - 28
1L1 - 251L1 - 29
1L1 - 23
1L1 - 27 1DP - 12
1L1 - 31
1DP - 11
13
1L1 - 61
RCP-1
ROM1
ROP-1,2
1L1 - 59
2 2.4
C.3
2 2.422.4
Bar
103
1L1 - 65
12 TYP.
1L1 - 68 1L1 - 53 1L1 - 531L1 - 68
17 18 17
192019
1L1 - 53
1L1 - 67 1L1 - 711L1 - 73
1L1 - 74 1L1 - 691L1 - 69
1 1 121
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:25:55 AME301
FIRST FLOOR
POWER &
SYSTEMS PLAN
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
1 POINT-OF-SALE STATION. PROVIDE 120V BRANCH CIRCUIT AND DATA OUTLET(S) FOR EACH POS STATION.
COORDINATE QUANTITY AND ACTUAL LOCATIONS WITH ARCHITECT PRIOR TO ROUGH-IN.
2 120V BRANCH CIRCUITS FOR SINK CONTROLS AND INTEGRATED HAND DRYER. COORDINATE LOCATIONS WITH
ARCHITECT PRIOR TO ROUGH-IN.
3 120V BRANCH CIRCUIT FOR EXHAUST HOOD.
4 208V/3Ø/30A DISCONNECT FOR AIR COMPRESSOR.
5 FERMENTER CONTROL PANEL. PROVIDE 120V BRANCH CIRCUIT. COORDINATE ACTUAL LOCATION
WITH ARCHITECT PRIOR TO ROUGH-IN.
6 DISTILLER CONTROL PANEL. PROVIDE 30A, 208V, 3Ø CIRCUIT TO INTEGRAL FUSED DISCONNECT.
7 208V/3Ø/30A DISCONNECT FOR FORK TRUCK BATTERY CHARGER. BATTERY CHARGER TO BE LOCATED ABOVE
FORK TRUCK PARKING, SUSPENDED FROM STRUCTURE ABOVE.
8 208V/30A BRANCH CIRCUIT FOR STEP-IN COOLER.
9 120V BRANCH CIRCUIT FOR COOLER/FREEZER. E.C. IS RESPONSIBLE FOR ALL WIRING ASSOCIATED
W/ COOLERS & FREEZERS (I.E. LTG, EVAPORATORS, DISCONNECTS, HEAT TAPE, CONTROL WIRING, ETC)
10 DISCONNECT FOR BRIDGE CRANE. COORDINATE ACTUAL LOCATION WITH ARCHITECT PRIOR TO
ROUGH-IN.
11 120V/20A BRANCH CIRCUIT FOR BEER LINE CHILLER.
12 MOUNT 6" UNDER BAR SURFACE IN KNEE SPACE ON CUSTOMER SIDE.
13 120V/20A BRANCH CIRCUIT FOR RO SYSTEM CONTROL PANEL.
14 208V/3Ø/30A FUSIBLE SAFETY SWITCH FOR MILLING MACHINE.
15 THIS ROOM IS CLASSIFIED AS A N.E.C. CLASS II, DIVISION 1 INSTALLATION. ALL WIRING METHODS AND EQUIPMENT
IN THIS ROOM IS TO MEET APPLICABLE SECTIONS OF N.E.C. 502.
16 ALL DEVICES IN THIS ROOM ARE TO HAVE WEATHERPROOF (WP) COVERS AND/OR BE NEMA 3R RATED.
17 BACK BAR COOLER.
18 WINE COOLER DISPENSER.
19 BOTTLE COOLER.
20 UNDERCOUNTER SINK W/ GLASSWARE SCRUBBER.
21 SODA DISPENSER.
PLAN NOTES
A INSTALL A 4"X4" DEEP BACKBOX W/ A SINGLE GANG MUDRING NEXT TO EACH
TV RECEPTACLE FOR INSTALLATION OF TV FEED.
GENERAL NOTES
SCALE: 1/8" = 1'-0"
FIRST FLOOR POWER & SYSTEMS PLAN1 SCALE: 1/4" = 1'-0"
ENLARGED PLAN - 110 & 1112
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - BAR 1033
No. Description Date
WP/GF
WP/GF WP/GF
GF
GF
GF
GF
GF
GF
GF
GF
GF
GF
H
J
GF
WP/GF WP/GF
FS VGFGFGF
GFGFF
30
15
15
F
15
F
30
F
30
FF
30
F
30
F
TV102" MHTV102" MH
TV 102" MH
TV 90" MH
15
15S
HSAMCAMCAMCAMC
TV 102" MH
GF
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
RR
212
PIZZA OVEN
216
HALL
206
BOILER ROOM
207RR
204
RR
205
STAFF BREAK
211
CATERING PREP
214
SUPPORT
215
JAN
208
OFFICE
210
BAR
201
DECK
202
PRIVATE FUNCTION
203
DINING
200
STAIR
213
Hall
209
2L1
2
RTU-1 RTU-2 CH-1
AHU-1
1
3
ACCU-C1 ACCU-C2 ACCU-F1
ELEV 2L1 - 22
2L1 - 35
2L1 - 32 2L1 - 33
2L1 - 34
2L1 - 28
2L1 - 19
2L1 - 262L1 - 24
2L1 - 27 2L1 - 23
2L1 - 21
2L1 - 37
2L1
2L1 - 39
2L1 - 36
2L1 - 29
ACCU-1 EF-6
1DP - 2 1DP - 3 1DP - 5 1DP - 6
1DP - 7 1DP - 8 1DP - 9 2L1 - 55
2L1 - 25
1DP - 4
1L1 - 575
1DP - 1
2
22L1 - 382L1 - 422L1 - 402L1 - 412L1 - 432L1 - 31
WP
E302
2
2L1 - 30
3 3.7
C.3
33 3.7
C.3
A.11
BAR
201
2L1 - 44
2L1 - 30
2L1 - 31
716
4 TYP.
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:26:04 AME302
SECOND FLOOR
POWER &
SYSTEMS PLAN
Sun King Spirits
JB
KAS
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
1 POINT-OF-SALE STATION. PROVIDE 120V BRANCH CIRCUIT AND DATA OUTLET(S) FOR EACH POS STATION.
COORDINATE QUANTITY AND ACTUAL LOCATIONS WITH ARCHITECT PRIOR TO ROUGH-IN.
2 120V BRANCH CIRCUIT FOR SINK CONTROLS AND INTEGRATED HAND DRYER. COORDINATE LOCATIONS
WITH ARCHITECT PRIOR TO ROUGH-IN.
3 120V BRANCH CIRCUIT FOR PIZZA OVEN.
4 MOUNT 6" UNDER BAR SURFACE IN KNEE SPACE ON CUSTOMER SIDE.
5 120V BRANCH CIRCUIT FOR DRY-PIPE SYSTEM AIR COMPRESSOR.
6 SODA DISPENSER
7 BOTTLE COOLER.
PLAN NOTES
A INSTALL A 4"X4" DEEP BACKBOX W/ A SINGLE GANG MUDRING NEXT TO EACH
TV RECEPTACLE FOR INSTALLATION OF TV FEED.
GENERAL NOTES
SCALE: 1/8" = 1'-0"
SECOND FLOOR POWER & SYSTEMS PLAN1
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - BAR 2012
No. Description Date
WP/GF
A
B
C
C.4
D
E.7
11.2
1.4
2 2.4 3 4 5 6
RH-1
EF-5
EF-1
EF-4 EF-2
EF-3
2L1 - 53
2L1 - 57
2L1 - 47
2L1 - 49
2L1 - 45
2L1 - 51
2L1 - 46
www.DELVdesign.com
Scale
Date
Drawn By
Checked By
Project Number
DELV Design
212 W 10th St, STE F125
Indianapolis, IN 46202
(317) 296-7400
www.DELVdesign.com
ARCHITECT
JPS CONSULTING ENGINEERS
9365 COUNSELORS ROW, STE 116
INDIANAPOLIS, IN 46240
(317) 617-4270
STRUCTURAL
HEAPY ENGINEERING
3850 PRIORITY WAY
SUITE #204
INDIANAPOLIS, IN 46240
(317) 571-8795
MEP ENGINEERING
CIVIL & ENVIRONMENTAL CONSULTANTS
530 E. OHIO STREET, SUITE G
INDIANAPOLIS, IN 46204
(317) 655-7778
CIVIL ENGINEERING
F.A. WILHELM CONSTRUCTION.CO
3914 PROSPECT ST.
INDIANAPOLIS, IN 46203
(317) 359-5411
DESIGN BUILD CONTRACTOR
3/30/2017 11:26:10 AME303
ROOF POWER
PLAN
Sun King Spirits
JB
Author
16-048
CONSTRUCTION DOCUMENTS
30 MARCH 2017
SCALE: 1/8" = 1'-0"
ROOF POWER PLAN1
No. Description Date