HomeMy WebLinkAbout17030162 Building Plans1.CONTRACTORS SHALL BE RESPONSIBLE FOR VISITING THE SITE TO BECOME
FAMILIAR WITH AND VERIFY THE EXISTING CONDITIONS. THESE DEMOLITION
DRAWINGS SHALL SERVE TO AID THE CONTRACTOR IN HIS EVALUATION OF THE
EXTENT OF DEMOLITION; BUT SHALL NOT BE HELD TO BE ALL INCLUSIVE.
2.CONTRACTORS SHALL BE RESPONSIBLE FOR ALL DEMOLITION REQUIRED FOR THE
INSTALLATION OF NEW CONSTRUCTION AND AS NECESSARY TO FULFILL THE
PURPOSE AND INTENT OF THE FINISHED WORK, WHETHER OR NOT IT IS
SPECIFICALLY SHOWN OR NOTED IN THESE DOCUMENTS. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR ALL ITEMS CALLED TO BE REMOVED THROUGH OUT
THE ENTIRE SET OF DOCUMENTS.
3.CONTRACTORS SHALL FIELD INSPECT ALL DEMOLITION WORK PRIOR TO REMOVAL,
TO INSURE SUCH REMOVAL DOES NOT IMPAIR STRUCTURAL INTEGRITY OF THE
EXISTING BUILDING. IF THE INSPECTION INDICATES THAT THE STRUCTURAL
INTEGRITY MAY BE IMPAIRED, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY.
4.REMOVE ALL DAMAGED OR EXISTING FINISH MATERIALS FROM REMAINING WALLS,
PARTITIONS AND COLUMNS (GYPSUM BOARD,WALL FABRIC, PANELING, TILE,
MASONRY, CONCRETE, ETC...). PATCH WALLS AND COLUMNS AS REQUIRED TO
RECEIVE NEW FINISH MATERIALS.
5.CONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING, INSTALLING AND
MAINTAINING DUST TIGHT TEMPORARY CONSTRUCTION BARRIERS TO ALL AREAS
WITHIN THE CONSTRUCTION LIMIT LINES, DURING THE CONSTRUCTION PROCESS.
LOCATIONS SHALL BE COORDINATED WITH THE OWNER AND ARCHITECT.
6.ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED
WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTORS DAILY.
7.PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO
REMAIN" FIXTURES AND EQUIPMENT REQUIRED TO REMAIN IN PLACE DURING
CONSTRUCTION.
8.REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION. ALL CONTRACTORS
SHALL COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK, TO BE
ASSURED THAT THEIR WORK IS COMPLIMENTARY TO THE WORK OF ALL OTHER
CONTRACTORS AND COMPLETE IN ALL RESPECTS.
9.UNLESS NOTED OTHERWISE ALL DEMOLITION MATERIAL BECOMES THE PROPERTY
OF THE CONTRACTORS AND IS TO BE REMOVED FROM THE PROPERTY, IN A LEGAL
MANNER. THE OWNER RESERVES THE RIGHT AND SHALL BE GIVEN THE
OPPORTUNITY TO CLAIM ITEMS WHETHER OR NOT THOSE ITEMS WERE
SPECIFICALLY NOTED FOR REMOVAL, RELOCATION, OR AS RETURNED TO
OWNER AND SAME SHALL BE RETURNED TO OWNER.
10.THE CONTRACTOR RESPONSIBLE FOR GENERAL DEMOLITION WORK SHALL
COORDINATE ANY AND ALL ASBESTOS REMOVAL WITH THE OWNER. ALL ASBESTOS
REMOVAL WILL BE PREFORMED BY A LICENSED ASBESTOS REMOVAL
CONTRACTOR. THIS TYPICALLY INCLUDES FLOOR TILE, TILE MASTIC AND PIPE
INSULATION.
11.ITEMS SHOWN IN LIGHTER PEN WEIGHTS ARE EXISTING TO REMAIN.
12.GENERAL CONTRACTOR RESPONSIBLE FOR PATCHING ALL REMOVED ELECTRICAL
OUTLETS. ELECTRICAL CONTRACTOR TO PROVIDE GENERAL CONTRACTOR WITH
QUANTITIES.
13.REMOVE EXISTING FINISHES AS REQUIRED TO INSTALL NEW FINISHES. PREPARE
SURFACES TO RECEIVE NEW FINISH AS PER FINISH MANUFACTURER'S PRINTED
INSTRUCTIONS, SEE FINISH SCHEDULE FOR NEW FINISHES.
14.REMOVE EXISTING CEILINGS AND CEILING SUPPORT SYSTEM WHERE NEW
CEILINGS ARE INDICATED, UNLESS OTHERWISE NOTED.
THESE NOTES SHALL APPLY TO ALL DEMOLITION
DRAWINGS AND TO ALL CONTRACTORS AND/OR
SUBCONTRACTORS THAT WORK ON THIS PROJECT.
INDICATES EXISTING WALL TO BE REMOVED IN ITS
ENTIRETY.
INDICATES EXISTING DOOR, FRAME AND ASSOCIATED
HARDWARE TO BE REMOVED IN ITS ENTIRETY. SEE DOOR
SCHEDULE FOR ITEMS TO BE SALVAGED AND REUSED IN
OTHER AREAS.
THESE NOTES APPLY TO ALL FLOOR PLANS, AND TO
ALL CONTRACTORS AND/OR SUBCONTRACTORS
THAT WORK ON THIS PROJECT.
1.OWNER WILL REMOVE ALL FURNISHINGS, LOOSE EQUIPMENT, SUPPLIES, ETC.... PRIOR
TO CONSTRUCTION COMMENCING.
2.ALL EQUIPMENT AND MATERIALS LABELED AS "SALVAGE" OR "RELOCATE AS DIRECTED
BY OWNER" SHALL BE REMOVED, PROPERLY PROTECTED AND TRANSPORTED TO A
LOCATION ON THE PREMISES AS DIRECTED BY THE OWNER.
3.ALL GENERAL CONTRACTORS AND THEIR SUBCONTRACTORS SHALL BE RESPONSIBLE
FOR VISITING THE CONSTRUCTION SITE TO BECOME FAMILIAR WITH ALL EXISTING
CONDITIONS WHICH AFFECT THAT SPECIFIC PORTION OF THEIR WORK. ANY CONFLICTS
OR APPARENT DEFICIENCIES MUST BE SUBMITTED TO THE ARCHITECT IN WRITING
PRIOR TO BIDDING.
4.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMING IN WRITING THE
OWNER ON A WEEKLY BASIS OF THE CONSTRUCTION SCHEDULE FOR THE
APPROACHING TWO WEEKS CONSTRUCTION ACTIVITY. ANY STORAGE OF MATERIALS,
ACCESS OR EGRESS PROBLEMS, TRAFFIC FLOW OR NORMAL OWNER OPERATIONS
WHICH ARE TO BE AFFECTED MUST BE PROTECTED AND/OR AGREED UPON BY THE
OWNER. ALL COSTS SHALL BE INCURRED BY THE GENERAL CONTRACTOR.
5.THE GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY WOOD BLOCKING FOR
ALL TRADES. THIS BLOCKING SHALL BE FIRE RETARDANT.
6.ANY PLASTER WORK REQUIRING NEW FINISH SHALL BE SMOOTH, SOUND AND IN A
FLUSH PLANE BEFORE FINISH APPLICATION. CONTRACTOR SHALL REPAIR THE
SURFACE FOR THE NEW FINISH AS SCHEDULED.
7.ALL FIRE RATED WALLS AND FLOOR PENETRATIONS MUST COMPLY WITH ASTME-814.
8.ITEMS SHOWN IN LIGHTER PEN WEIGHT ARE EXISTING TO REMAIN.
9.REMOVE ALL DAMAGED GYPSUM BOARD, MASONRY, CONCRETE, PLASTER, ETC...
FROM EXISTING SURFACES AND REPAIR TO MATCH ADJACENT CONSTRUCTION PRIOR
TO REFINISHING. ALL SURFACES SHALL BE SMOOTH AND IN A FLUSH PLANE.
10.ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED
WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTORS DAILY.
11.PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO
REMAIN" FIXTURES AND EQUIPMENT REQUIRED TO REMAIN IN PLACE DURING
CONSTRUCTION.
12.REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION. ALL CONTRACTORS SHALL
COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK, TO BE ASSURED THAT
WORK IN EITHER OF THESE AREAS IS COMPLEMENTARY TO THE OTHER AND
COMPLETE IN ALL RESPECTS. ANY CONFLICTS OR APPARENT DEFICIENCIES MUST BE
SUBMITTED TO THE ARCHITECT IN WRITING PRIOR TO BIDDING.
13.ALL WALL HUNG CASEWORK REQUIRES CONTINUOUS HORIZONTAL WOOD BLOCKING
BETWEEN STUDS AT TOP AND BOTTOM OF CASEWORK. BRACE WALL TO DECK AS
REQUIRED.
14.ALL DIMENSIONS ARE FROM FACE OF BASE MATERIAL (STUD/CMU) TO FACE OF BASE
MATERIAL (STUD/CMU) UNLESS NOTED OTHERWISE.
15.PORTIONS OF THE BUILDING SHALL BE OCCUPIED DURING CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL FOLLOW THE FOLLOWING LIFE SAFETY ISSUES.
FAILURE TO LIST ALL LIFE SAFETY ISSUES DOES NOT RELIEVE THE CONTRACTORS
FROM COMPLYING WITH FEDERAL, STATE AND LOCAL CODES, THE CONTRACTUAL
AGREEMENT BETWEEN THE CONTRACTOR AND OWNER, AND OTHER GOVERNING
BODIES WHICH HAVE JURISDICTION ON THIS PROJECT. THE FOLLOWING ARE INTERIM
LIFE SAFETY CODE ISSUES WHICH ARE SPECIFIC TO THIS PROJECT AND MUST BE
ADDRESSED:
a.INSURE ALL EXITS PROVIDE FREE AND UNOBSTRUCTED EGRESS. STAFF
AND PERSONNEL SHALL RECEIVE TRAINING AND WRITTEN NOTIFICATION IF
ALTERNATIVE EXITS MUST BE DESIGNATED.
b.INSURE FREE AND UNOBSTRUCTED ACCESS TO EMERGENCY
DEPARTMENTS OR SERVICES FOR EMERGENCY FORCES. COORDINATE
WITH OWNER AND ARCHITECT.
c.INSURE FIRE ALARM, DETECTION AND SUPPRESSION SYSTEMS ARE NOT
IMPAIRED. A TEMPORARY, BUT EQUIVALENT, SYSTEM SHALL BE PROVIDED,
INSTALLED AND TESTED PRIOR TO ANY EXISTING FIRE SYSTEM BEING
IMPAIRED.
d.INSURE TEMPORARY CONSTRUCTION PARTITIONS ARE SMOKE TIGHT AND
BUILT OF NON COMBUSTIBLE MATERIALS. THESE PARTITIONS SHALL BE
COORDINATED WITH THE OWNER AND ARCHITECT.
e.SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS OF THE
BUILDING.
f.DEVELOP AND ENFORCE STORAGE, HOUSEKEEPING AND DEBRIS REMOVAL
PROCEDURES THAT REDUCE THE FLAMMABLE AND COMBUSTIBLE FIRE
LOAD TO THE LOWEST LEVEL NECESSARY FOR DAILY OPERATIONS.
g.IOSHA REQUIRES MATERIAL SAFETY DATA SHEETS (MSDS) FOR ALL
MATERIALS BEING USED OR STORED ON THIS PROJECT BE MADE
AVAILABLE TO ALL WORKERS ON THIS JOBSITE. COPIES MUST BE
PROVIDED TO THE OWNER'S DIRECTOR OF SECURITY, IMMEDIATELY, AS
WORK BEGINS.
h.SECURE ALL TOOLS AND CONSTRUCTION MATERIALS DURING BREAKS AND
NON-CONSTRUCTION HOURS.
1.ALIGN ALL CEILING AND BULKHEAD REVEALS, CONTROL OR SEISMIC JOINTS WITH
THE ADJACENT REVEAL, CONTROL OR SEISMIC JOINTS IN WALLS INDICATED ON
ELEVATIONS.
2.ALL CEILING AND BULKHEAD HEIGHTS INDICATED ARE TO FINISHED FACE OF
GYPSUM BOARD OR TO THE BOTTOM FACE OF ACOUSTICAL CEILING TILE PAD,
UNLESS NOTED OTHERWISE.
3.CEILING CONTRACTOR TO PROVIDE ALL CEILING GRID TO SUPPORT HVAC SUPPLY
DIFFUSERS AND RETURN GRILLS.
4.DEVICES OTHER THAN LIGHTING AND DIFFUSERS ARE SHOW IN APPROXIMATE
LOCATIONS, FINAL LOCATION TO BE COORDINATED WITH ALL TRADES AND
ARCHITECT.
5.AT LOCATIONS WHERE GYPSUM BOARD CEILINGS ARE INDICATED, THE
CONTRACTOR HAS THE OPTION TO USE LIGHT GAGE METAL FRAMING OR
SUSPENDED GYPSUM BOARD GRID UNLESS OTHERWISE DETAILED. THE
CONTRACTOR WILL COORDINATE ANY MODIFICATIONS WITH THE OTHER TRADES
ON THE PROJECT. THE CEILING CONTRACTOR'S FINAL MEANS AND METHODS WILL
NOT CONFLICT WITH THE WORK OF OTHERS OR THE INTENT OF THESE
DOCUMENTS.
6.WHERE EXISTING SUSPENDED ACOUSTICAL CEILINGS ARE SCHEDULED TO
REMAIN, CUT AND PREP THE CEILING GRID IN PREPARATION FOR REPAIRING.
SALVAGE ENOUGH CEILING PADS FOR RECONSTRUCTION. STORE AND PROTECT
ALL MATERIALS. USE NEW MATCHING MATERIALS FOR RECONSTRUCTION AS
REQUIRED.
7.SEE THE ROOM FINISH SCHEDULE FOR ADDITIONAL COMMENTS REGARDING
MATERIALS AND FINISHES.
8.THE DESIGNATION 'CJ' INDICATES GYPSUM BOARD CONTROL JOINTS. WHERE
INDICATED PROVIDE USG #093 ZINC CONTROL TYPICAL. INSTALL JOINT THROUGH
THE FULL EXTENTS OF ANY GYPSUM CEILING OR BULKHEAD. WHERE THE GYPSUM
CEILING COMPONENT MEETS A GYPSUM WALL, EXTEND THE CONTROL JOINT
DOWN TO THE FLOOR TYPICAL.
9.THE GENERAL CONTRACTOR WILL PROVIDE AND INSTALL ALL SUPPLEMENTAL
AND/ OR MISCELLANEOUS STEEL FRAMING AS REQUIRED BY THEMSELVES OR BY
THEIR SUBCONTRACTORS FOR THE INSTALLATION OF THE EQUIPMENT
SCHEDULED AND SPECIFIED. NOT ALL OF THE REQUIRED SUPPORT STEEL MAY BE
DETAILED OR CALLED OUT FOR IN THESE DOCUMENTS. COORDINATE ALL
REQUIREMENTS WITH THE SPECIFICATIONS, EQUIPMENT SUPPLIERS AND
SUBCONTRACTORS. THERE WILL BE NO CHANGE ORDERS TO THE PROJECT FOR
SUPPLEMENTAL STEEL WHERE OMISSIONS MAY OCCUR IN THE BIDDING
DOCUMENTS.
THESE NOTES APPLY TO ALL CONSTRUCTION DRAWINGS AND TO ALL
CONTRACTORS AND/OR SUBCONTRACTORS THAT WORK WITHIN THIS
BUILDING.
ROOM NAME
101
1t
A
101A
A2-1
1 SIM
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
X
X
NEW DOOR
AND
FRAME
ROOM
NAME
AND
NUMBER
ELEVATION
SYMBOL
PLAN DETAIL
NEW
COLUMN
LINE
EXISTING
COLUMN LINE
SECTION
PARTITION TYPE
WINDOW
ELEVATION
SYMBOL
TOILET ACCESSORY
1i3.5A
1
A5-1
SIM DETAIL NUMBER
NORTH
ARROW
PROJECT NORTH
TRUE NORTH
SHEET NUMBER
DETAIL NUMBER
x /Xx-x
XX
X
EQUIPMENT TAGTAG ID
x 1XX-YYY FURNITURE TAGTAG ID
x QUANTITY
1 SPECIFIC
CONSTRUCTION
NOTES
1 SPECIFIC
DEMOLITION
NOTES
Architectural:
Kyle Hardie
MSKTD & Associates
kfh@msktd.com
317.917.1190
Electrical:
Josh Walke
Genesis Engineering
khutton@genesis-
engineering.com
317.927.8307 x5
Mechanical & Plumbing:
Kevin Hutton
Genesis Engineering
khutton@genesis-
engineering.com
317.501.9737
Interiors:
Sarah Savage
MSKTD & Associates
sjs@msktd.com
317.917.1190
EXTEND TO BOTTOM
OF DECK ABOVE
1.5A
5/8" GYPSUM BOARD
(BOTH SIDES)
3 5/8" METAL
STUD AT 16" O.C.
EXTEND TO BOTTOM
OF DECK ABOVE
1.7A
SOUND
ATTENUATION
BLANKET
INSULATION
5/8" GYPSUM BOARD
(BOTH SIDES)
6" METAL STUD
AT 16" O.C.
SOUND
ATTENUATION
BLANKET
INSULATION
4 7/8"7 1/4"
EXTEND TO BOTTOM
OF DECK ABOVE
1.5C
5/8" GYPSUM BOARD
(ONE SIDE)
3 5/8" METAL
STUD AT 16" O.C.
SOUND
ATTENUATION
BLANKET
INSULATION
4 1/4"DAVIDARCHI T E C TREG I S TERE
DAR10500075
STATE OF
I IND A AN
No.
SL
TA
ERN IC H LOAS
Architecture | Engineering | Interior Design
1715 Magnavox Way
Fort Wayne, IN 46804
260.432.9337
930 North Meridian
Indianapolis, IN 46204
317.917.1190
www.msktd.com
SHEET TITLE
SHEET NUMBER
SET DESCRIPTION
PROJECT NO.DATE
6993 2-21-17
MSKTD& Associates
PharmacyRenovationDate Signed 2-21-17
2/22/20173:50:04PMTitlesheet, Drawing
Index and General Info
G1-1 11700N.MeridianStreet|Carmel,Indiana46032NorthHospitalARenovationForPharmacy Renovation
Drawing Index
North Hospital
ElectricalArchitecturalMechanicalPlumbing
G1-1 Titlesheet, Drawing Index and General Info
G1-2 Life Safety Plans and Code Summary
A2-0 Lower Level Plans
A9-0 Lower Level Reflected Ceiling & Finish
Plans
A10-1 Casework Elevations & Details
General Demolition Notes General Reconstruction Notes General Ceiling Notes Graphic Symbols Contacts
Partition Types
P0-1 Plumbing Symbols and Abbreviations
P1-0 Foundation Plumbing Demolition Plan
P1-1 Lower Level Plumbing Demolition Plan
P2-0 Foundation Plumbing Plan
P2-1 Lower Level Plumbing Plan
M0-1 Mechanical Symbols and Abbreviations
M0-2 Temperature Control Schematics
M1-0 Lower Level Mechanical Ductwork Demolition
Plan
M1-1 Lower Level Mechanical Piping Demolition Plan
M2-0 Lower Level Mechanical Ductwork Plan
M2-7 Seventh Floor and Penthouse Mechanical Plans
M3-0 Lower Level Mechanical Piping Plan
M6-1 Mechanical Schedules
M7-1 Mechanical Details
M7-2 Mechanical Details
E0-1 Electrical Symbols and Abbreviations
E1-0 Lower Level Electrical Demolition Plan
E2-0 Lower Level Lighting Plan
E3-0 Lower Level Power and Systems Plan
E3-7 Seventh Floor and Penthouse Power and
Systems Plan
E5-1 Electrical One-Line Riser Diagram and
Schedules
E6-1 Electrical Panel Schedules
E7-1 Electrical Details
REV.DATE
UP
UP
UP
LIFE SAFETY CODE REVIEW (Per NFPA 101, 2012 Edition)
Chapter 18: New Healthcare
Chapter 19: Existing Healthcare
CONSTRUCTION LEGEND
2-HOUR FIRE BARRIER (Occupancy Separation)
19.1.3.4 - Occupancy separation.
18.1.3.4.1 - Occupancy separation.
19.2.2.4 Smokeproof Enclosures - "Smokeproof enclosures complying with 7.2.3 shall be
permitted."
7.2.3.3 - "A smokeproof enclosure shall be continuously enclosed by barriers having a 2-
hour fire resistance rating from the highest level of exit discharge. Where a vestibule is
used, it shall be within the 2-hour rated enclosure and shall be considered part of the
smokeproof enclosure."
18.2.2.4 Smokeproof Enclosures - "Smokeproof enclosures complying with 7.2.3 shall be
permitted."
8.3.4.2 (table)- 1½-hour opening rating (doors).
2-HOUR FIRE BARRIER (Vertical Openings):
18.3.1.1 - "Any vertical opening shall be enclosed or protected in accordance with 8.2.5."
8.6.5 – Enclosures connecting four stories or more in new construction – 2 hour fire
barriers
Other enclosures in new construction: 1-hour fire barriers.
8.6.7- Atriums are separated from the adjacent spaces by fire barriers with not less than 1-
hour fire resistance rating with opening protective for corridor walls. See exceptions in
section.
8.3.4.2 (table)- 1½-hour opening rating (doors).
2-HOUR FIRE BARRIER ( Exit Passageways):
19.2.2.7 Exit Passageways - "Exit passageways complying with 7.2.6 shall be permitted."
7.2.6.2 Enclosure - "An exit passageway shall be separated from other parts of the building
as specified in 7.1.3.2."
7.1.3.2.1 (b)- 2-hour fire resistive rating for four or more stories.
18.2.2.7 Exit Passageways - "Exit passageways complying with 7.2.6 shall be permitted."
8.3.4.2 (table)- 1½-hour opening rating (doors).
1-HOUR FIRE BARRIER (Hazardous Areas)
18.3.2.1 Hazardous Areas - "Any hazardous area shall be protected in accordance with
Section 8.4. The areas described in Table 18.3.2.1 shall be protected as indicated."
1. Boiler and fuel-fired heater rooms
2. Central/bulk laundries larger than 100 square feet. (9.3 square meters)
3. Paint shops
4. Repair Shops
5. Soiled linen rooms
6. Trash Collection rooms
7. Rooms or spaces larger than 50 square feet (4.6 square meters) including repair shops,
used for storage of combustible supplies and equipments in quantities deemed hazardous
by the authority having jurisdiction.
8. Laboratories employing flammable or combustible materials in quantities less than those
that would be considered a severe hazard.
18.3.6.3.11 - "Door-closing devices shall not be required on doors in corridor wall openings
other than those serving required exits, smoke barriers or enclosures of vertical openings
and hazardous areas."
SMOKE BARRIER WALL (1-hour Rated Existing):
19.3.7.3 - "Any required smoke barrier shall be constructed in accordance with
Section 8.3 and shall have a minimum 1/2 hour fire resistance rating....."
19.3.7.6 - 19.3.7.8 - Doors shall have a 20 minute fire rating and shall be self-closing or
automatic closing. Doors are not required to swing with egress travel and positive latching
hardware is not required.
18.3.7.3 - "Any required smoke barrier shall be constructed in accordance with Section
8.3 and shall a minumum 1-hour fire resistance rating....dampers shall not be required in
fully ducted system....."
18.3.7.6 - 18.3.7.8- Doors shall have a 20 minute fire rating and shall be self-closing or
automatic closing, and permitted to be held open only by an automatic releasing device.
Doors
shall be dual egress but positive latching hardware is not required.
SMOKE ZONES (Not to Exceed 22,500 s.f.):
19.3.7.1 - "To divide every story used by inpatients for sleeping by more than 30 patients
into not less than two smoke compartments;(1) To limit the size of each smoke
compartment to an area not exceeding 22,500 sq. ft. (2) Where neither the length nor
width of the smoke compartment exceeds 150 ft, the travel distance to each the smoke
barrier door shall not be limited.
18.3.7.1 - "(1) To divide every story used by inpatients for sleeping or treatment into not
less than two smoke compartments; (2) To divide every story having an occupant load of
50 or more persons, regardless of use, into not less than two smoke compartments; (3) To
limit the size of each smoke compartment to an area not exceeding 22,500 sq. ft. (4) To
limit the travel distance from any point to reach a door in the required smoke barrier to a
distance not exceeding 200 ft.
SMOKE PARTITION (Hazardous Areas):
19.3.2.1 Hazardous Areas - Any hazardous area shall be safe-guarded by a fire barrier
having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing
system in accordance with 8.7.1. The automatic extinguishing shall be permitted to be in
accordance with
19.3.5.9.Where the sprinkler option of 19.3.2.1 is used, the areas shall be separated from
other spaces by smoke-resisting partitions and doors.
19.3.2.1.5 Hazardous areas shall include, but shall not be restricted to, the following:
1. Boiler and fuel-fired heater rooms
2. Central/bulk laundries larger than 100 square feet. (9.3 square meters)
3. Paint shops
4. Repair Shops
5. Soiled linen rooms
6. Trash Collection rooms
7. Rooms or spaces larger than 50 square feet (4.6 square meters) including repair shops,
used for storage of combustible supplies and equipments in quantities deemed hazardous
by the authority having jurisdiction.
8. Laboratories employing flammable or combustible materials in quantities less than those
that would be considered a severe hazard.
Exception: Doors in rated enclosures shall be permitted to have non-rated, factory- or field
applied protective plates extending not more than 48in.(122cm) above the bottom of the
door.
SUITES (Non-Rated (Smoke Resistant) Corridors):
18.2.5.7.1.1 - Suites shall be separated from the remainder of the building, and from other
suites, by walls and doors meeting corridor wall construction requirements.
19.2.5.7.1.1 - Suites shall be separated from the remainder of the building, and from other
suites, by walls and doors meeting corridor wall construction requirements.
18.2.5.7.1.3 (A)- Intervening rooms shall not be hazardous areas as defined by 18.3.2.
19.2.5.7.1.3 (A)- Intervening rooms shall not be hazardous areas as defined by 18.3.2.
18.2.5.7.2.1 - (A) Sleeping Suites shall have access directly to exit corridor. (B) Where two
or more exit access doors are required from a suite, one of the exit doors shall be permitted
to be directly to an exit stair, exit passageway or exit door to the exterior. (C) Sleeping
suites shall be provided with constant staff supervision within the suite. (D) Sleeping suites
shall be arranged to provide one of the following (a) The patient sleeping rooms shall be
arranged to allow for direct supervision form a normally attended location within the suite or
(b) any patient rooms without direct supervision shall be provided by automatic smoke
detection.
19.2.5.7.2.1 - (A) Sleeping Suites shall have access directly to exit corridor. (B) Where two
or more exit access doors are required from a suite, one of the exit doors shall be permitted
to be directly to an exit stair, exit passageway or exit door to the exterior. (C) Sleeping
suites shall be provided with constant staff supervision within the suite. (D) Sleeping suites
shall be arranged to provide one of the following (a) The patient sleeping rooms shall be
arranged to allow for direct supervision form a normally attended location within the suite or
(b) any patient rooms without direct supervision shall be provided by automatic smoke
detection.
18.2.5.7.2.2 - Sleeping suites of more than 1000 sq. ft. shall have not less than two exit
access doors remotely located from one another. One means of egress shall be directly to
a corridor. One means of egress shall be permitted to be through another suite, provided
that the suite separation complies with corridor construction requirements.
19.2.5.7.2.2 - Sleeping suites of more than 1000 sq. ft. shall have not less than two exit
access doors remotely located from one another. One means of egress shall be directly to
a corridor. One means of egress shall be permitted to be through another suite, provided
that the suite separation complies with corridor construction requirements.
18.2.5.7.2.3 (B)- Sleeping suites shall not exceed 7500 sq. ft. Sleeping Suites larger than
7500 sq. ft. and not exceeding 10,000 sq. ft. shall be permitted where both direct visual
supervisiion is provided and automatic smoke detection is provided.
19.2.5.7.2.3 - (B) Sleeping suites shall not exceed 7500 sq. ft. without having an
electrically supervised sprinkler system and automatic smoke detection. Sleeping Suites
larger than 7500 sq. ft. and not exceeding 10,000 sq. ft. shall be permitted where both
direct visual supervisiion is provided and automatic smoke detection is provided.
18.2.5.7.2.4 - Suite Travel Distance between any point in a sleeping suite and the exit
access door from that suite shall not exceed 100 ft. Travel distance between any point in
a sleeping suite and the exit shall not exceed 200 ft.
19.2.5.7.2.4 - Suite Travel Distance between any point in a sleeping suite and the exit
access door from that suite shall not exceed 100 ft. Travel distance between any point in
a sleeping suite and the exit shall not exceed 200 ft if the building is protected by a
sprinkler system. Without a sprinkler system, distance is limited to 150 ft.
18.2.5.7.3 -Patient Care Non-Sleeping Suites shall have direct access to an exit access
corridor.
19.2.5.7.3.1 -Patient Care Non-Sleeping Suites shall have direct access to an exit access
corridor.
18.2.5.7.3.2 - Non-sleeping suites of more than 2500 sq ft shall have not less than two exit
access doors remotely located from one another. For suites requiring two means of
egress, one means of egress from the suite shall be permitted to be through another suite
provide dthat the suite separation complies with corridor wall construction.
19.2.5.7.3.2 - Non-sleeping suites of more than 2500 sq ft shall have not less than two exit
access doors remotely located from one another. For suites requiring two means of
egress, one means of egress from the suite shall be permitted to be through another suite
provide dthat the suite separation complies with corridor wall construction.
18.2.5.7.3.3 - Patient Care Non-Sleeping Suites shall not exceed 10,000 sq. ft.
19.2.5.7.3.3 - Patient Care Non-Sleeping Suites shall not exceed 10,000 sq. ft.
18.2.6.1 - Travel distance between any point in a room and an exit shall not exceed 200 ft.
19.2.6.1 - Travel distance between any point in a room and an exit shall not exceed 150 ft.
SMOKE RESISTANT CORRIDORS (Non-Rated Corridors):
19.3.6.2.4 - "In smoke compartments protected throughout by an approved, supervised
automatic sprinkler system in accordance with 19.3.5.7, a corridor shall be permitted to be
separated from all other areas by non-fire-rated partitions and shall be permitted to
terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke."
18.3.6.2 - "Corridor walls shall form a barrier to limit the transfer of smoke. Such walls shall
be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer
of smoke. No fire resistance rating is required for corridor walls."
19.3.6.3.4 - Door closing devices not required.
18.3.6.3.4 - Door closing devices not required.
TRAVEL DISTANCES TO EXIT
18.2.6.2.1 - "The travel distance between any point in a room and an exit shall not exceed
200 feet."
19.2.6.2.2 - The travel distance between any point in a room and an exit shall not exceed
150.(Exception: The maximum travel distance shall be permitted to be increased by 50 ft.
in buildings protected throughout by an approved, supervised automatic sprinkler system.)
TRAVEL DISTANCES TO SMOKE
19.3.7.1 - "The size of any such smoke compartment shall not exceed 22,500 s.f., and the
travel distance from any point to reach a door in the required smoke barrier shall not
exceed 200 feet. (Exception No. 1: Where neither the length nor width of the smoke
compartment exceeds 150 feet, the travel distance to reach the smoke barrier door shall
not be limited."
18.3.7.1 (4)- "To limit the travel distance from any point to reach a door in the required
smoke barrier to a distance not exceeding 200 feet."
1 HOUR FIRE BARRIER (Hazardous Rooms)
2 HOUR FIRE BARRIER (Occupancy Separation)
SMOKE BARRIER WALL (1 Hour Rated Walls, 20 Min. Rated Doors)
TRAVEL DISTANCE (Distance to Smoke Barrier)
SMOKE TIGHT EXIT ACCESS CORRIDOR
(Non-Rated Corridors; Hazardous Areas)
SUITE (Bounding walls to be Smoke Resistant)
2 HOUR FIRE BARRIER (Vertical Openings)
2 HOUR FIRE BARRIER (Exit Passageways / Horizontal Exit)
SMOKE PARTITION (Hazardous Rooms)
EXIT
TRAVEL DISTANCE (Distance to Exit)
NFPA 101 LIFE SAFETY CODE (2000) CHAPTER 18
(New Healthcare Occupancy)
NFPA 101 LIFE SAFETY CODE (2000) CHAPTER 38
(New Business Occupancy)
P MANUAL FIRE ALARM PULL STATION
STANDPIPE OUTLET
CHUTE (TRASH & LINEN)
FIRE EXTINGUISHERFE
c
FIRE RESISTIVE CEILING (Bounding walls to be 1 Hour Rated Fire Barrier)
FIRE RESISTIVE CEILING (Bounding walls to be 2 Hour Rated Fire Barrier)
APPLICABLE CODES:
NFPA 101 Life Safety Code 2012 Edition. Chapter 18 New Healthcare Occupancies.
BUILDING/DWELLING CODE 2014 Indiana Building Code (675 IAC 13-2.6)
STRUCTURAL CODE 2014 Indiana Building Code (2012 IBC, ANSI A-117.1-2009, ASCE-7-2005)
MECHANICAL CODE 2014 Indiana Mechanical Code (2012 IMC with state amendments)
ELECTRICAL CODE 2009 Indiana Electrical Code (2008 NEC with state amendments)
FIRE/LIFE SAFETY CODE 2014 Fire Code (675 1AC 22-2.5) consisting of 2012 IFC with state amendments
ACCESSIBILITY CODE 2014 Indiana Building Code, Chapter 11, and ICC standard A117.1 2009 edition
ENERGY CODE 2010 Indiana Energy Conservation Code (ASHRAE 90.1 - 2007 with state amendments)
BUILDING:Hospital
OCCUPANCY:Group I-2, Institutional IBC sec. 308.4
CONSTRUCTION TYPE Type I-A IBC Table 601
AUTOMATIC SPRINKLERS:Yes – Fully-Sprinkled
AREA
ALLOWABLE BUILDING AREA:Unlimited IBC Table 503
FLOOR AREAS (GROSS):
EXISTING:RENOVATION:
Lower Level:83,364 SF 2,350
First Floor:88,200 SF N/A
Second Floor:87,990 SF N/A
Third Floor:73,802 SF N/A
Fourth Floor:71,365 SF N/A
Fifth Floor:70,255 SF N/A
Sixth Floor:30,038 SF N/A
Seventh Floor: 3,656 SF N/A
(Penthouse)
TOTAL GROSS AREA:508,670 SF 2,350 SF
HEIGHT:
ALLOWABLE STORIES:Unlimited IBC Table 503
STORIES:Seven (7) including a Lower Level (Basement), plus Penthouse
FIRE RESISTANT REQUIREMENTS : (NON-COMBUSTIBLE)
Structural Framing 3-Hour IBC Table 601
Floor – Ceiling 2-Hour IBC Table 601
Roof 1 1/2-Hour IBC Table 601
SHAFT ENCLOSURES:
3 Stories or Less 2-Hour NFPA 101; 8.3.4.2/IBC 713.4
4 Stories or More 2-Hour
VERTICAL CIRCULATION:
2-Hour NFPA 101; 8.3.4.2
OCCUPANCY SEPARATION:B Occ. and I-2 Occupancy 2-Hour
SMOKE BARRIERS:(I-2 Occupancy and in B Occupancy located within 1-floor of I-2)
Max Area:22,500 SF
Max Travel Distance:200 Ft.
TRAVEL DISTANCE TO AN EXIT:
B Occupancy 300 Ft.
I-2 Occupancy 200 Ft.
110 SF
LINEN
C027
115 SF
TRASH
C028
1328 SF
BED STORAGE
C030
182 SF
REPAIR AREA
C030A
1448 SF
ELECTRICAL
ROOM
C032
SMOKE ZONE 0.6
4,869 SF
SMOKE ZONE 0.1
10,976 SF
c
FE
P
c
P
P
P
P
FE
FE
FEFE
FE
FE
FE
1880 SF
MECHANICAL
ROOM
C031
86 SF
STORAGE
C023
4919 SF
SHOP AREA
C024
CONSTRUCTION LIMIT
RATING PRIORITY
3 HOUR WALL
2 HOUR WALL
1 HOUR WALL
SMOKE PARTITION
NON RATED PARTITION
1
2
3
4
5
HIGHER PRIORITY
PARTITION
GYPSUM BOARD CONTINUES
THROUGH STUD CAVITY OF
LOWER PRIORITY WALL
LOWER PRIORITY
PARTITION
NOTE: CONTRACTOR IS RESPONSIBLE FOR MAINTAINING NEW AND EXISTING
FIRE RESISTIVE WALLS THAT ARE CONTINUOUS AND NOT INTERRUPTED BY NON-
RATED WALLS.
HIGHER PRIORITY
LOWER PRIORITY DAVIDARCHI T E C TREG IS TERE
DAR10500075
STATE OF
I IND A AN
No.
SL
TA
ERN IC H LOAS
True NorthPlanNorthMOB
HOSPITAL
CENTRAL
PLANT
Architecture | Engineering | Interior Design
1715 Magnavox Way
Fort Wayne, IN 46804
260.432.9337
930 North Meridian
Indianapolis, IN 46204
317.917.1190
www.msktd.com
SHEET TITLE
SHEET NUMBER
SET DESCRIPTION
PROJECT NO.DATE
6993 2-21-17
MSKTD& Associates
KEY PLAN PharmacyRenovationAREA OF
CONSTRUCTION
Date Signed 2-21-17
2/22/20173:50:06PMLife Safety Plans and
Code Summary
G1-2 11700N.MeridianStreet|Carmel,Indiana46032NorthHospitalARenovationForLife Safety Legend Code Citations
Life Safety Legend
Code Summary
3/32" = 1'-0"
Lower Level Life Safety Plan
Rated Wall Priority REV.DATE
UP
REF.UPREF.REF.4 4.3 5 6 7
H
J
OFFICE
C025E
PICK
STATION
C025D
PHARMACIST
C025
UNPACKING
C026
HAZARD
BUFFER
C025B STAFF TOILET
C026B
LOUNGE
C026AANTE
C025A
MASTER STATION
CORRIDOR
C0C01
CORRIDOR
C0C09
CORRIDOR
C0C10
CORRIDOR
C0C02
LINEN
C027
TRASH
C028
OFFICE
C029
ELEVATOR
ELEV 8
ELEVATOR
ELEV 9
BED STORAGE
C030
REPAIR AREA
C030A
ELECTRICAL
ROOM
C032
CORRIDOR
C0C04
CORRIDOR
C0C03
ELEVATOR
LOBBY
C0C06
CORRIDOR
C0C05
STAIR
C3-LL
C025E 2/ A10-1
A
CONSTRUCTION LIMIT 3/A10-1A2-0
1
4/ A10-1
NON-HAZARD
BUFFER
C025C20'-71/8"8'-47/8"11' - 6 5/8"7' - 9 3/4"
3' - 3"
1
9
10
6
8
8
IC
12
12
12
12
12 12
12
12
12
12
12
5'-0"2'-41/4"4 4.3 4.6 4.7 4.9 5 6 7
H
J
BSC
HOOD
REFRIGERATORPASS-THRU(EXISTINGSLIDER)LAFW
HOOD
LAFW
HOOD
PYXIS
LAFW
HOOD
2
5
1
5
12
CONSTRUCTION LIMIT
4
4
7
9
44
4
8
8
8
8
8
8
8
8
6
5
8 11 10
3
13
1
3
13 3
13
14
15 16
C025B
OFFICE C025C
FORMULA MIX
C025A
WORK ROOM
C026A
LOUNGE
C026B
STAFF TOILET
C026
STORAGE
C025
PHARMACY
C025D
LAB
C025E
WORK AREA
C025F
ANTE
C0C09
CORRIDOR
C0C01
CORRIDOR
C0C03
CORRIDOR
C0C04
CORRIDOR
C029
OFFICE
C027
LINEN C028
TRASH
ELEV 8
ELEVATOR
ELEV 9
ELEVATOR
C030
STORAGE
C030A
WORK
C032
ELEC
C0C10
CORRIDOR
C3-LL
STAIR
1.(INFECTION CONTROL.) CONSTRUCTION AND DUST SEPARATION WALL. 6" METAL
STUD WALL WITH 5/8" VINYL FACED GYPSUM BOARD AND SOUND ATTENUATION
BATT. EXTEND TO CEILING. TAPE SEAMS. MAINTAIN A MINIMUM OF 5'-0" AT
EXISTING CORRIDORS AND OWNER OCCUPIED SPACES FOR EGRESS.
CONTRACTOR IS RESPONSIBLE FOR SUPPLYING AND DETERMINING WALL
LOCATIONS AND NUMBER AND SIZE OF CONSTRUCTION DOORS WITHIN
SEPARATION WALL. REFINISH FLOOR, WALLS, AND CEILING AS NEEDED AFTER
REMOVAL OF WALLS.
2.ADDITIONAL ARCHITECTURAL DEMOLITION MAY BE REQUIRED FOR REMOVAL
AND INSTALLATION OF NEW MECHANICAL, ELECTRICAL AND PLUMBING
ELEMENTS. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR
EXTENT OF DEMOLITION.
3.WHERE ADDITIONAL DEMOLITION IS REQUIRED, LIKE MATERIALS ARE TO BE
REINSTALLED IN THEIR PLACE.
4.PROTECT ALL EXISTING SURFACES AND ELEMENTS TO REMAIN FROM DAMAGE
DURING DEMOLITION AND CONSTRUCTION.
PP = PUSH PLATE
IC = INTERCOM
IL = INDICATOR LIGHT
*NOT ALL LOCATIONS MAY BE NOTED. REFER TO ELECTRICAL DRAWINGS.
1.ALL WALLS TO BE TYPE 1.5A UNLESS OTHERWISE NOTED. REFER TO WALL TYPES ON SHEET G1 -1.
2.WHERE DIMENSION IS PRECEDED BY +/-, THE VALUE GIVEN IS FOR REFERENCE. ACTUAL DIMENSION
SHALL BE DETERMINED BY OTHER CONSTRAINTS, SUCH AS FINISH ALIGNMENT, OR EXISTING
CONSTRUCTION. SEE PLAN FOR DETAILS AS NOTED.
3.REFER TO DOOR HARDWARE SCHEDULE FOR OPERATOR TYPE, HOLD OPEN, CARD READERS AND
OTHER DOOR SPECIALTY HARDWARE.
4.REFER TO ENLARGED PLANS FOR ADDITIONAL DIMENSIONS AND NOTATION.
1.EXISTING DOOR LEAF AND HARDWARE RELOCATED. FURNISH NEW HOLLOW
METAL FRAME.
2.DOOR TO RECEIVE AUTO OPERATOR. CONNECT AUTO OPERATOR TO FIRE
ALARM. IN LOSS OF POWER AND/OR SMOKE DETECTION, AUTO OPERATOR
TO CEASE FUNCTIONING.
3.DOOR TO RECEIVE ELECTRIC STRIKE.
4.DOOR TO RECEIVE COORDINATOR DEVICES SO THAT PHARMACY DOORS
SHALL NOT OPEN UNTIL ALL OTHER PHARMACY DOORS ARE FULLY SHUT.
NOTED ON ELEVATIONS, INDICATES TEMPERED GLASS LOCATIONS IN
CONJUNCTION WITH GLAZING LABEL.
T
4.3 5
J
1/ A10-1
48"
REFRIGERATOR
PASS-THRU
HAZARD
BUFFER
C025B
ANTE
C025A
C025A
C025C
A
1.5C1.5C
1.7A
1.5C
TYP.
1.5C
TYP.
1.5C
TYP.
5/ A10-1 TYP.
1.7A
8' - 3 1/8"18' - 8"10' - 0 1/4"
1' - 4 1/4"1'-41/4"6' - 7 1/4"4' - 6 5/8"
ALIGN 8'-45/8"3'-6"3'-77/8"7'-7"2'-41/4"18'-11"1'-6"2' - 4 3/4"2'-101/2"6"5'-31/8"11' - 2 3/4"2' - 8"7' - 2"5' - 8"10' - 2 5/8"1'-6"C025B
NON-HAZARD
BUFFER
C025C2'-3"212
12
12
6
6
6
3
3
4
4
4
IC
IC
IC
PP
PP5
PP PP
5
PPPP
5
IL
IL
7
7
11
13
12
12
14
15
16
12
FE
ALIGN
3
4"4"3"4' - 0"2' - 9"15'-61/2"TO FINISH FACE OF
EXISTING WALL
F HV
T
FW-HM 3'-6"3'-8"4' - 0"
T
ASEESCHEDULE2"2"SEE SCHEDULE 2"
2/A2-0 SIM.
FW HOLLOW METAL
5/8" GYPSUM BOARD (BOTH SIDES)
DOUBLE 3 5/8" METAL STUD FRAMING
DOOR FRAME
(SEE SCHEDULE FOR TYPE)
DOOR LEAF
(SEE SCHEDULE FOR TYPE)
SEALANT BOTH SIDES
5/8" GYPSUM BOARD
(BOTH SIDES)
DOOR FRAME
(SEE SCHEDULE FOR TYPE)
DOOR LEAF
(SEE SCHEDULE FOR TYPE)
SEALANT BOTH SIDES DAVIDARCHI T E C TREG I S TERE
DAR10500075
STATE OF
I IND A AN
No.
SL
TA
ERN IC H LOAS
True NorthPlanNorthMOB
HOSPITAL
CENTRAL
PLANT
Architecture | Engineering | Interior Design
1715 Magnavox Way
Fort Wayne, IN 46804
260.432.9337
930 North Meridian
Indianapolis, IN 46204
317.917.1190
www.msktd.com
SHEET TITLE
SHEET NUMBER
SET DESCRIPTION
PROJECT NO.DATE
6993 2-21-17
MSKTD& Associates
KEY PLAN PharmacyRenovationAREA OF
CONSTRUCTION
Date Signed 2-21-17
2/22/20173:49:54PMLower Level Plans
A2-0 11700N.MeridianStreet|Carmel,Indiana46032NorthHospitalARenovationFor 1/8" = 1'-0"
Lower Level Floor Plan
1/8" = 1'-0"
Lower Level Demo Plan
6993 - Specific Demo Notes
1 (HATCH AREA) REMOVE ALL INTERIOR METAL STUD FRAMED WALL ASSEMBLIES TO DECK ABOVE, VCT FLOORING WITH
RUBBER BASE, AND LAY-IN CEILING SYSTEM. PREP AREA FOR NEW WALLS AND FINISHES.
2 (HATCH AREA) REMOVE ALL INTERIOR METAL STUD FRAMED WALL ASSEMBLIES TO DECK ABOVE, SHEET VINYL
FLOORING WITH INTEGRAL COVE, AND GYPSUM BOARD CEILING. PREP AREA FOR NEW WALLS AND FINISHES.
3 REMOVE LAY-IN CEILING IN ITS ENTIRETY FOR NEW OVERHEAD MECHANICAL, ELECTRICAL, AND PLUMBING. REFER TO
MEP DWGS.
4 REMOVE, SALVAGE, AND REINSTALL PORTIONS OF CEILINGS AS NECESSARY FOR MECHANICAL, ELECTRICAL, AND
PLUMBING. REFER TO MEP DWGS.
5 REMOVE AND SALVAGE DOOR, FRAME, AND ALL ASSOCIATED HARDWARE. PROVIDE TO OWNER.
6 REMOVE AND SALVAGE DOOR, FRAME, AND ALL ASSOCIATED HARDWARE. PROVIDE TO OWNER. REUSE/REINSTALL IN
NEW OFFICE LOCATION. REMOVE DOOR FRAME.
7 REMOVE PORTION OF WALL ASSEMBLY FOR WIDER OPENING. REFER TO ARCHITECTURAL PLAN.
8 REMOVE UPPER AND LOWER CASEWORK AND ALL ASSOCIATED BULKHEADS, ETC.
9 REMOVE 2'-9" WIDE LOWER BASE CABINET PASS-THRU CABINET AND CORRIDOR ACCESS DOOR UNDER COUNTERTOP.
PREP OPENING TO RECEIVE NEW BASE CABINET.
10 REMOVE COUNTERTOP, SPLASHES, AND ALL ASSOCIATED UNDERCOUNTER BRACING. PREP WALLS TO RECEIVE NEW
FINISHES.
11 REMOVE PLUMBING FIXTURE. REFER TO PLUMBING DWGS.
12 REMOVE, SALVAGE, AND REINSTALL PNEUMATIC TUBE STATION. COORDINATE WITH OWNER AND SWISSLOG.
13 EXISTING FLOORING AND RUBBER BASE TO REMAIN. PROTECT
14 REMOVE PORTION OF SLAB-ON-GRADE CONCRETE FLOOR FOR NEW SANITARY LINE DISTRIBUTION. REFER TO
PLUMBING DWGS.
15 REMOVE COUNTERTOP IN ITS ENTIRETY. PREP FOR NEW COUNTERTOP.
16 REMOVE, SALVAGE, AND REINSTALL SINK AND FAUCET. REFER TO PLUMBING DWGS.
1 General Notes
General Note6993 - Specific Plan Notes
1 PATCH/REPAIR WALL ASSEMBLY (JAMB AND HEAD) AT WIDER OPENING.
2 OFCI WALL-MOUNTED SINGLE BASIN SCRUB SINK. REFER TO PLUMBING DWGS.
3 OFCI FULL-HEIGHT PASS-THROUGH CABINETS. COORDINATE WALL OPENING WIDTH AND HEIGHT WITH MANUFACTURER.
CONTRACTOR TO PROVIDE AND INSTALL 1" STAINLESS STEEL PERIMETER TRIM AROUND OPENINGS FOLLOWING
INSTALLATION OF EQUIPMENT.
4 CFCI PASS-THROUGH CABINET. CONTRACTOR PROVIDED 'CLEAR AIR PRODUCTS, SERIES CAP18WBD-SST-24WX24HX24D.
PROVIDE INTERLOCKED DOOR LATCH AND 8 PIECE, "OUTSIDE FLUSH", STAINLESS STEEL MOUNTING FRAME.
CONTRACTOR TO PROVIDE AND INSTALL 1" STAINLESS STEEL PERIMETER TRIM AROUND OPENINGS FOLLOWING
INSTALLATION OF EQUIPMENT.
5 'PP' - HAND SENSOR MOTION DOOR ACTUATOR. REFER TO ELECTRICAL DWGS.
6 'IC' - INTERCOM. REFER TO ELECTRICAL SYSTEMS DWGS.
7 'IL' - WALL-MOUNTED INDICATION LIGHT. REFER TO ELECTRICAL DWGS.
8 VERTICAL POWER/DATA RACEWAY/CONDUIT. REFER TO ELECTRICAL DWGS.
9 CFCI FULL-HEIGHT 'WALLTALKER' WHITEBOARD SYSTEM. PROVIDE LEVEL-5 DRYWALL FINISH. REFER TO ELEVATION
3/A10-1.
10 PROVIDE STAINLESS STEEL SHEET COVER AT REMOVED PASS-THRU TRANSACTION CABINET ON CORRIDOR SIDE.
11 REINSTALLED/RELOCATED PNEUMATIC TUBE STATION. CONTRACTOR SHALL COORDINATE WITH OWNER AND SWISSLOG.
CONTRACTOR SHALL PROVIDE ALL NECESSARY TRANSFER DUCT EXTENSION, POWER, AND DATA.
12 OFOI SYSTEMS FURNITURE AND/OR EQUIPMENT. REFER TO EQUIPMENT PLAN.
13 'FE' - FULL-RECESSED FIRE EXT. CABINET. "FIRE EXTINGUISHER CABINET EQUAL TO POTTER-ROEMER, FRC 1700 SERIES,
#FRC1704-AL-A WITH WHITE POYLESTER-COATED, FULL GLASS."
14 PROVIDE 1" X 8" X 36" STAINED WOOD BOARD WITH STAGGERED COAT HOOKS AT 6" O.C. LOWER HOOKS TO BE AT 48"
HEIGHT. UPPER HOOKS TO BE AT 52" HIGH.
15 PROVIDE 36"W X 12"D STAINLESS STEEL SHELF ABOVE SCRUB SINK.
16 EYE WASH STATION. REFER TO PLUMBING DWGS.
6993 - Door and Opening Schedule
Opening
No.
Door Frame Details
Label
Door
Glass
Power
Req'd
Hdw.
Set RemarksSizeMat.Ele.Mat.Ele.Head Jamb
6993 - Pharmacy Renovation
C025A 3'-6" x 7'-0" X 1 3/4"HM HV FW-HM 1 3/A2-0 2/A2-0 ---T Yes 1 2, 3, 4
C025B 3'-6" x 7'-0" X 1 3/4"HM HV FW-HM 1 3/A2-0 2/A2-0 ---T Yes 1 2, 3, 4
C025C 3'-6" x 7'-0" X 1 3/4"HM HV FW-HM 1 3/A2-0 2/A2-0 ---T Yes 1 2, 3, 4
C025E 3'-0" x 7'-0" x 1-3/4"EX. SCWD F1 FW-HM 1 3/A2-0 2/A2-0 ------No EX.1
Door Schedule Remarks General Remarks
1
1/4" = 1'-0"
Enlarged Buffer Rooms1
Door Elevations Frame Elevations
1 1/2" = 1'-0"
Door Head Detail3
1 1/2" = 1'-0"
Door Jamb Detail2
REV.DATE
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC OC OC OC
UP
4 4.3 4.6 4.7 4.9 5 6 7
H
J
CONSTRUCTION LIMIT
OFFICE
C025E
PICK
STATION
C025D
PHARMACIST
C025
UNPACKING
C026
HAZARD
BUFFER
C025B
STAFF TOILET
C026B
LOUNGE
C026AANTE
C025A
CORRIDOR
C0C01
CORRIDOR
C0C09
CORRIDOR
C0C10
CORRIDOR
C0C02
LINEN
C027
TRASH
C028
OFFICE
C029
ELEVATOR
ELEV 8
ELEVATOR
ELEV 9
BED STORAGE
C030
REPAIR AREA
C030A
ELECTRICAL
ROOM
C032
CORRIDOR
C0C04
CORRIDOR
C0C03
ELEVATOR
LOBBY
C0C06
CORRIDOR
C0C05
STAIR
C3-LL
A.F.F.
7' - 0"
1
2
3 4
4
2
2 2 2
2
2 2
2 2
2
6
6
6
6
1
1
3
5
NON-HAZARD
BUFFER
C025C
+/-
7
8
8
3
C026
UNPACKING
2
ACT-1
P-1
ETR
ETR
1,3
C025B
HAZARD
BUFFER
GYB-1
P-1
SVB-1
SV-1,SV-2
1,2
C025D PICK
STATION
ACT-1
P-1
RB-1
VCT-1,VCT-2
C025E
OFFICE
2
ACT-1
P-1
RB-1
CPT-1
1,2,5,6
C025
PHARMACIST
ACT-1
P-1
RB-1
VCT-1,VCT-2
C026B
STAFF
TOILET
-
ACT-X
ETR
ETR
ETR
C026A
LOUNGE
2
ACT-X
P-1
ETR
ETR
1,3,4,6
C025A ANTE
GYB-1
P-1,WP-1
SVB-1
SV-1,SV-2
C0C01
CORRIDOR
C0C09
CORRIDOR
C0C10
CORRIDOR
C032
ELECTRICAL
ROOM
C030A
REPAIR
AREA
C030 BED
STORAGE
C0C03
CORRIDOR
C027 LINEN
C028
TRASH
C029
OFFICE
C0C04
CORRIDOR
ELEV 8
ELEVATOR
ELEV 9
ELEVATOR
C0C06
ELEVATOR
LOBBY
C0C02
CORRIDOR
C3-LL
STAIR
CONSTRUCTION LIMIT
CG
CG
CGCG
CG CG
CGCG
CG
CG CG
CG
CG
CG CG CG15'-0"2' - 0"
VCT-2 EXISTING
VCT
VCT-2 VCT-1
VCT-1 VCT-2
SV-1 SV-2
SV-1
C025C
NON-HAZARD
BUFFER
3
GYB-1
P-1
SVB-1
SV-1
WP-1
LINE UP VCT
TRANSITION
WITH WALL
6' - 6"3'-9"LINE UP SV
TRANSITION
WITH DOOR
FRAME
BRING NEW VCT INTO
ROOM AS REQUIRED
FOR CLEAN
TRANSITION TO
EXISTING
EXISTING VCT
TRANSITIONS
CG
SV-2 WT-1CG
1.ALL CEILINGS TO BE 9'-0" A.F.F. UNLESS NOTED OTHERWISE.
2.ALL BULKHEADS TO BE 7'-2" A.F.F. UNLESS NOTED OTHERWISE.
FLOOR
CARPET TILE
CPT-1 J+J FLOORING GROUP, KINETEX, PATTERN: UMBRA STRIPE, COLOR: DIFFUSE,
ASHLAR INSTALLATION
SHEET VINYL
SV-1 GERFLOR, MIPOLAM SYMBIOZ, COLOR: 6041 CLAY
SV-2 GERFLOR, MIPOLAM SYMBIOZ, COLOR: 6043 WOOD
VINYL COMPOSITION TILE
VCT-1 MANNINGTON, ESSENTIALS, WARM BEIGE 127
VCT-2 MANNINGTON, ESSENTIALS, PUTTY 129
BASE
RUBBER BASE
RB-1 JOHNSONITE, 4" HIGH COVED, MOON ROCK 29
SHEET VINYL BASE
SVB-1 GERFLOR, MIPOLAM SYMBIOZ, COLOR: MATCH ADJACENT FLOOR SHEET VINYL
WALL
PAINT
P-1 SHERWIN WILLIAMS; CRISP LINEN SW6378
P-2 SHERWIN WILLIAMS; INTERACTIVE CREAM SW6113
WALL PROTECTION
WP-1 KOROGUARD; K-3; PORCELAIN; INSTALL FROM TOP OF BASE TO CEILING
WALLTALKERS
WT-1 KOROSEAL; WALLTALKERS JUST-RITE; 60" WIDTH; PROVIDE ALUMINUM
ACCESSORY TRIM AROUND PERIMETER. CONTRACTOR SHALL PROVIDE A LEVEL-5
GYPSUM BOARD FINISH BEHIND COVERING. INSTALL PER MANUFACTURER'S
WRITTEN INSTRUCTIONS.
CEILING
ACOUSTICAL TILES
ACT-1 ARMSTRONG; CLEAN ROOM, VL 24" x 24"; #868
ACT-X EXISTING CEILING TO BE REINSTALLED
GYPSUM BOARD
GYB-1 LEVEL 5 DRYWALL FINISH PAINTED CEILING BRIGHT WHITE, SEMIGLOSS PRE-
CATALYZED WATERBASED EPOXY
CASEWORK
PLASTIC LAMINATE
PL-1 PIONITE, MILLWORK CHERRY, SUEDE FINISH, WC431
PL-2 PIONITE, IL PALIO PAPEL, SUEDE FINISH, AV981
EXISTING FINISHES
EXISTING TO REMAIN
ETR EXISTING FINISH TO REMAIN
(APPLICABLE THROUGHOUT ALL AREAS OF CONSTRUCTION)
A.FOR ALL FLOORING MATERIALS INSTALLED ON GRADE OR BELOW GRADE: THE FLOORING
CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE IN THEIR BID PRICES ALL REQUIRED
MATERIALS AND LABOR FOR A COMPLETE INSTALLATION THAT MEETS THE
MANUFACTURER'S TOTAL SYSTEM PERFORMANCE. THIS INCLUDES ALL PREP MATERIALS
AND LABOR REQUIRED TO MEET MANUFACTURER'S WRITTEN SPECIFICATIONS FOR
MOISTURE, PH, SMOOTHNESS OR LEVELNESS OR CLEANLINESS OF NEW OR EXISTING
SUBSTRATES, ETC. THIS INSTALLATION SHALL INCLUDE THE MANUFACTURER'S SPECIFIED
ADHESIVES, SEALERS, ETC.
B.PAINT ALL HOLLOW METAL DOORS, WINDOW FRAMES, AND DOOR FRAMES P -2, SEMI-
GLOSS.
C.PATCH AND MATCH ALL FINISHES DUE TO CONSTRUCTION.
D.PATTERN NAME, COLOR, AND NUMBER FOR EACH MATERIAL ARE GIVEN WHEREVER
POSSIBLE ON THE FINISH PLANS. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO
BRING ANY DISCREPANCIES TO THE ATTENTION OF THE INTERIOR DESIGNER SO THAT THE
CORRECT MATERIAL IS INSTALLED.
E.SEE REFLECTED CEILING PLAN AND DETAILS FOR LOCATION AND HEIGHT OF CEILINGS.
F.EVERY TRANSITIONS BETWEEN FLOORING MATERIALS TO BE FLUSH. IT IS FLOORING
CONTRACTOR'S RESPONSIBILITY TO LEVEL SUBSTRATE AS NECESSARY FOR MATERIALS TO
TRANSITION AT LEVEL HEIGHT, INCLUDING GRINDING OR BUILDING UP OF CONCRETE. ALL
TRANSITION STRIPS TO BE STAINLESS STEEL EQUAL TO SCHLUTER SYSTEMS AND MUST
MEET ADA; ALL PROFILES TO BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
TRANSITION STRIPS ARE UNNECESSARY BETWEEN LIKE MATERIALS (CARPET TO CARPET,
LINOLEUM TO VINYL, ETC).
G.ALL FLOORING MATERIAL TRANSITIONS SHALL BE CENTERED UNDER THE DOOR JAMBS.
H.PAINT VENTS, DIFFUSERS, ELECTRICAL PANELS, FIRE CABINETS (UNLESS THEY ARE
NATURAL ALUMINUM OR STAINLESS STEEL), ETC. TO MATCH WALL COLOR.
I.2" CORNER GUARD (CG): 12 GA STAINLESS STEEL W/ RADIUSED CORNER AND EDGES.
INSTALL FULL HEIGHT FROM ABOVE BASE TO CEILING. SILICONE APPLIED.
J.ALL GYPSUM BOARD RECEIVING SEMI-GLOSS PAINT IS TO RECEIVE A LEVEL 5 DRYWALL
FINISH.
(SEE FINISH SCHEDULE FOR LOCATION)
1.SEE FINISH FLOOR PLAN FOR FLOOR PATTERN. ACCENT COLOR INDICATED WITH
HATCHED PATTERN. DIMENSIONS OR INSTRUCTIONS FOR TRANSITION LOCATION CALLED
OUT ON FINISH FLOOR PLAN.
2.PAINT TO BE EQUAL TO SHERWIN WILLIAMS PRE-CATALYZED WATERBASED EPOXY,
EGGSHELL FINISH.
3.PAINT TO BE EQUAL TO SHERWIN WILLIAMS PRE-CATALYZED WATERBASED EPOXY,
SEMIGLOSS FINISH.
4.WALL PROTECTION LOCATION INDICATED WITH HEAVY DOTTED LINES.
5.INSTALL 60" WIDE x 60" HIGH WT-1 AT AREA INDICATED WITH DASHED LINES. SEE
ELEVATION FOR HEIGHT AND LOCATION DETAILS. CONTRACTOR SHALL PROVIDE A
LEVEL-5 GYPSUM BOARD FINISH BEHIND COVERING. PROVIDE ALUMINUM ACCESSORY
TRIM AROUND PERIMETER.
6.SEE ELEVATIONS FOR CASEWORK DETAILS.
7 8
H
J
J.4
1 23
ROOF CURB
PROVIDE
CONTINUOUS
TREATED WOOD
BLOCKING TO BE
FLUSH OR ABOVE
INSULATION
HEIGHT
EXISTING (2)
LAYERS OF 2"
RIGID INSULATION
EXISTING 1 1/2"
ROOF DECK
EXISTING
MEMBRANE
SPLICE TAPE
(3") IN BONDING
ADHESIVE BED
FASTENER @ 12"
O.C. MAX WITH
SEALANT OVER
HEAD AND CURB
FLANGE
1 1/4" HOT
DIPPED GALV.
ROOF NAILS @
12" O.C. MAX EPDM MEMBRANE
ADHERED W/
BONDING ADHESIVE
MECH UNIT, SEE
MECH DWGS.
ROOF OPENING, SEE MECH.1'-0"CONTINUOUS
GASKET
INSULATION
WOOD NAILER
BASE FINISH
FLOOR FINISH
WALL FINISH
CEILING FINISH
REMARKS
ROOM # AND NAME DAVIDARCHI T E C TREG I S TERE
DAR10500075
STATE OF
I IND A AN
No.
SL
TA
ERN IC H LOAS
True NorthPlanNorthMOB
HOSPITAL
CENTRAL
PLANT
Architecture | Engineering | Interior Design
1715 Magnavox Way
Fort Wayne, IN 46804
260.432.9337
930 North Meridian
Indianapolis, IN 46204
317.917.1190
www.msktd.com
SHEET TITLE
SHEET NUMBER
SET DESCRIPTION
PROJECT NO.DATE
6993 2-21-17
MSKTD& Associates
KEY PLAN PharmacyRenovationAREA OF
CONSTRUCTION
Date Signed 2-21-17
2/22/20173:49:58PMLower Level Reflected
Ceiling & Finish Plans
A9-0 11700N.MeridianStreet|Carmel,Indiana46032NorthHospitalARenovationFor 1/8" = 1'-0"
Lower Level Reflected Ceiling Plan
1/8" = 1'-0"
Lower Level Finish Plan
General Reflected Ceiling Notes6993 - Specific Reflected Ceiling Plan Notes
1 NEW 24X24 ACOUSTICAL LAY-IN CEILING TILE WITH GASKETED GRID.
2 REMOVE PORTION OF LAY-IN CEILING AS REQUIRED FOR INSTALLATION OF NEW MECHANICAL, PLUMBING,
AND ELECTRICAL EQUIPMENT. SALVAGE TILE AND GRID AND REINSTALL.
3 NEW METAL FRAMING WITH GYPSUM BOARD BULKHEAD ABOVE CASEWORK TO BE AT 7'-2" UNLESS NOTED
OTHERWISE. BULKHEAD TO MATCH CASEWORK DIMENSION PLUS 1-INCH OVERHANG ON ALL "OPEN" SIDES
UNLESS NOTED OTHERWISE. COORDINATE WITH CASEWORK ELEVATIONS.
4 EXISTING BULKHEAD TO REMAIN.
5 NEW METAL FRAMING WITH GYPSUM BOARD BULKHEAD ABOVE REFRIGERATOR PASS-THRU. COORDINATE
HEIGHT WITH EQUIPMENT REQUIREMENTS.
6 NEW GYPSUM BOARD CEILING ON METAL FRAMING.
7 CEILING MOUNTED CAMERA. REFER TO ELECTRICAL SYSTEMS DWGS.
8 VERTICAL POWER/DATA RACEWAY. REFER TO ELECTRICAL DWGS.
1
Color LegendGeneral Remarks
Specific Remarks
REV.DATE
1/8" = 1'-0"
Penthouse Roof Plan
3" = 1'-0"
Typical Roof Curb Detail1
6993 - Specific Roof Plan Notes
1 MODIFY EXISTING MECHANICAL PENETRATION CURB FOR REVISED ROOFTOP DUCTWORK. PROVIDE NEW
ALUMINUM CURB TOP ENCLOSURE. REFER TO TYPICAL ROOF CURB DETAIL 1/A9-0.
2 PROVIDE NEW MECHANICAL CURB FOR EXHAUST FAN LOCATION. MODIFY EXISTING ROOF ASSEMBLY (BASE
AND TAPERED INSULATION AND ADHERED EPDM ROOF MEMBRANE) PER ROOF MANUFACTURER'S STANDARD
DETAILS AND RECOMMENDATION. REFER TO TYPICAL ROOF CURB DETAIL 1/A9-0.
3 PROVIDE HORIZONTAL DUCTWORK SUPPORTS AS REQUIRED.
1
Room Finish Tag Legend
UP
REF.2"7'-0"GYPSUM BOARD
BULKHEAD
EQ 1' - 10"1' - 10"3' - 6"EQ
7' - 5 1/2"
FILLER
14"D OPEN SHELF
UPPER CABINETS
EXISTING 5-DRAWER FILE
CABINET (42"W x 65 1/2"H)
RELOCATED1'-3"5'-9"VALANCE
14"D OPEN WARDROBE
CABINET WITH
ADJUSTABLE SHELVES
4"H BASE (REFER TO
FINISH PLAN)
FINISHED END
PANEL
6
A10-1
7
A10-1
SIM.7'-0"2"A
2'-6"2'-9"1'-9"3"4' - 0"2' - 9"
2' - 6"2' - 6"2' - 6"2' - 6"
10' - 1"+/- 2"1'-0"3'-8"1"
2"2' - 6"1"EQEQGYPSUM
BOARD
BULKHEAD
48"
REFRIGERATOR
PASS-THRU
(OFCI)
24x24x24
PASS-THRU
(CFCI)
PRINTER
FILLER
14"D OPEN UPPER
CABINET WITH
ADJUSTABLE SHELF
VALANCE
PLASTIC LAMINATE
COUNTERTOP (POSTFORM)
w/ 4"H SIDE & BACKSPLASH
24"D OPEN LOWER
CABINETS WITH
ADJUSTABLE SHELVES
4"H BASE (REFER TO
FINISH PLAN)
4 7/8"
FINISH FACE OF WALL
(OPPOSITE SIDE)
(VERIFY WITH MANUFACTURER SPECS.)
+/- 5' - 3" (CLEAR OPENING)
FINISHED
END PANEL
FINISHED
END PANEL
4" MIN. CLEARANCE (VERIFYWITHMANUFACTURERSPECS.)7'-0"(CLEAROPENING)4"MIN.CLEARANCEFINISH FACE OF
BULKHEAD
FILLER
WALL MOUNTED INDICATOR LIGHT -
REFER TO ELECTRICAL DRAWINGS.
7
A10-1
1" STAINLESS
STEEL TRIM
5' - 0"4"
(CLEAR OPENING)
5' - 0"+/- 2' - 3 1/2"
NARCOTICS
CABINET
(MAIN)
NARCOTICS
CABINET
(AUXILIARY)
PRINTER
ON
SHELF
4" BASE (REFER TO
FINISH PLAN)
"WALLTALKERS"
w/ ALUMINUM TRIM 5'-0"1"
1" FILLER 1' - 0"
4" BASE (REFER TO
FINISH PLAN)
NEW PLASTIC LAMINATE
COUNTERTOP (POSTFORM)
W/ 4"H SIDE & BACKSPLASH
NEW 24"D OPEN LOWER
CABINET WITH
ADJUSTABLE SHELVES 7'-0"2'-10"NARCOTICS
REF.
7
A10-1
SIM.
ALIGN EDGE OF TRIM
WITH WALL OPENING
1.CONTRACTOR SHALL PROVIDE WOOD BLOCKING AS REQUIRED FOR
INSTALLATION OF ALL UPPER AND LOWER UNITS
2.EDGE OF COUNTERTOP TO BE 1 1/2" THICK.
3.CABINET MFG. SHALL COORDINATE WITH OWNER ALL LOCATIONS FOR
"GROMMETS" QUANTITY WILL BE IDENTIFIED PER ELEVATION. ALL GROMMETS TO
BE 3 1/2" DIA.WITH BLACK PLASTIC TRIM RING - LOCATE AT REAR OF COUNTER. OR
AS DIRECTED BY OWNER.
4.ALL EXPOSED ENDS AND BACKS OF CASEWORK TO BE FINISHED SAME AS
BALANCE OF EXPOSED SURFACE, SEE FINISH SCHEDULE.
5.APPLY 1" RAD. ON ALL OUTER CORNERS OF COUNTER TOPS, U.N.O.
6.ALL END PANEL SUPPORT SHALL BE CONSTRUCTED W/ 1 1/2" LAMINATED
PARTICLE BD.
7.ALL COUNTER TOPS SHALL EXTEND 1" BEYOND FRONT OF CABINET DRAWER
FACE.
8.ALL DRAWERS AND DOOR HANDLES SHALL BE TYPE " STANLEY, MODEL No. 4484 -
CHROME VS26D
9.ALL BASE CABINET DEPTH SHALL BE 24" UNLESS NOTED OTHERWISE
10.ALL UPPER CABINET DEPTH SHALL BE 14" UNLESS NOTED OTHERWISE
11.APPLY A 4" BACKSPLASH AT PERIMETER OF ALL COUNTER TOPS
12.APPLY (1) ADJUSTABLE SHELF IN ALL BASE UNITS, AND (2) ADJUSTABLE SHELVES
IN ALL. UPPER UNITS W/ EXCEPTION OF SINK BASE UNITS. (UNLESS NOTED
OTHERWISE). ALL SHELVES IN CASEWORK TO BE ADJUSTABLE ON 1" CENTERS
VERTICALLY.
13.ALL BASE UNITS SHALL HAVE A 4" H. x 3" D. TOE SPACE WITH RUBBER BASE BY
FLOORING CONTRACTOR. BASE TO EXTEND TO ALL EXPOSED SIDES OF
CASEWORK.
14.REFER TO FLOOR PLAN FOR ALL WALL PARTITION TYPES
15.PAPER TOWEL DISPENSER LOCATED AT EVERY SINK. SUPPLIED BY OWNER,
INSTALLED BY G.C.
16.FOR ALL FILES DESIGNATED "BY OWNER"- CONTRACTOR TO VERIFY ACTUAL
HEIGHT OF FILES TO BE PURCHASED FOR COORDINATION, IF USED AS SUPPORT
FOR COUNTER TOP
17.INSTALL CLEAR SEALANT CONTINUOUS BETWEEN TOP OF BACKSPLASH AND
WALL.
18.ALL HARDWARE FOR ANCHORING/SUPPORTING CASEWORK SHALL BE
CONCEALED.
19.PROVIDE 2X2 WOOD BLOCKING CONTINUOUS AT PERIMETER FOR
COUNTERTOP/SHELF SUPPORT - PAINT TO MATCH WALL.
20.ALL COUNTERTOPS WITHOUT BACKSPLASH SHALL BE SCRIBED TO ADJACENT
WALLS/CASEWORK.
21.4 DIGIT NUMBER ABOVE OR BELOW CASEWORK REFERS TO HEIGHT AND WIDTH
OF UNIT.
22.FILLER PANELS BY CABINET MANUFACTURER TO MATCH CABINETS. PROVIDE AND
INSTALL.
" L " = DOOR/DRAWER TO BE LOCKED WITH KEY CYLINDER. COORDINATE WITH
OWNER ON KEYING REQUIREMENTS
" F " = FILE DRAWER, INTERIOR DIMENSIONS SHALL MEET STANDARD FILE DRAWER
DIMENSIONS. INSTALL HANGING FILE HARDWARE.
" UL " = UNDER UPPER CABINET LIGHT, REFER TO ELECTRICAL DRAWINGS, APPLY 2"
LAMINATED APRON.
" S " = STRUCTURAL SUPPORT FOR COUNTER AND OR RECEPTION DESK. REFER TO
" AP " = REMOVABLE ACCESS PANEL. PROVIDE COUNTERSUNK ANCHORS.
" K " = KEYBOARD TRAYS PROVIDED BY OWNER - 30" WIDE
" G " = GROMMETS, VERIFY LOCATION WITH OWNER
CABINET MFG. SHALL FIELD VERIFY ALL WALL DIMENSIONS PRIOR
TO FABRICATION. ALL GENERAL CASEWORK NOTES APPLY TO ALL
CASEWORK THROUGH OUT SET
C025
FINISHED END PANEL
4"H BASE (REFER TO
FINISH PLAN)2' - 9"2' - 9"2' - 9"2' - 0"+/- 1 1/2"
+/- 10' - 4 1/2"
NEW 24"D OPEN
LOWER CABINET WITH
ADJUSTABLE SHELVES
EXISTING 24"D OPEN LOWER
CABINETS & SINK APRON
TO REMAIN
EXISTING 14"D OPEN
UPPER CABINETS
TO REMAIN
EXISTING GYPSUM
BOARD BULKHEAD
TO REMAIN
FILL IN PORTION THAT
WAS DEMOLISHED
NEW PLASTIC LAMINATE
COUNTERTOP (POSTFORM)
W/ 4"H SIDE & BACKSPLASH
EXISTING STAINLESS STEEL
SHELF
TO REMAIN
SINK
4"H BASE (REFER TO
FINISH PLAN)
ADD FILLER PANEL TO
SURFACE OF EXISTING
CORNER CABINET THAT
IS TO REMAIN
REINSTALL EXISTING SINK
& FAUCET
7
A10-1
SIM.
48"
REFRIGERATOR
PASS-THRU
OFFICE
C025E
PICK
STATION
C025D
PHARMACIST
C025
UNPACKING
C026
HAZARD
BUFFER
C025B STAFF TOILET
C026B
LOUNGE
C026AANTE
C025A
INTERCOM
CORRIDOR
C0C01
CORRIDOR
C0C09
CORRIDOR
C0C10
CORRIDOR
C0C02
LINEN
C027
TRASH
C028
OFFICE
C029
ELEVATOR
ELEV 8
ELEVATOR
ELEV 9
BED STORAGE
C030
REPAIR AREA
C030A
ELECTRICAL
ROOM
C032
CORRIDOR
C0C04
CORRIDOR
C0C03
ELEVATOR
LOBBY
C0C06
CORRIDOR
C0C05
STAIR
C3-LL
13
23
6 12
9 15
4
4
2
1
4
2
2
2
2
3
3
16
2
4
9
11
23
4
12
8
8
7244
124
14
14
14
14
14
13
CONSTRUCTION LIMIT
5
5
18
19 26
26
20
21 21 21
21 21 21
21 21 21
21 21 21
21 21 21
21 21 21
21 21 21
21 21 21
21 21 21
21 21 21
22
22
22
22
22
22
22
7
27
3' - 0"
1"2'-10"2'-5"1'-9"7'-0"1"
12"D OPEN UPPER
CABINETS W/
ADJUSTABLE SHELF
VALANCE
PLASTIC LAMINATE
COUNTERTOP (POSTFORM)
W/ 4" BACKSPLASH
24"D OPEN LOWER
CABINET W/
ADJUSTABLE SHELVES
FINISHED END PANELS
4"H BASE (REFER TO
FINISH PLAN)
FINISHED END PANELS
7
A10-1
SIM.
FILLER
GYPSUM
BOARD
BULKHEAD
GYPSUM BULKHEAD
6COMPARTMENTS6'-71/4"43/4"2"7'-0"3/4" PLASTIC LAMINATE
ADJUSTABLE SHELF
BASE. REFER TO
INTERIOR FINISH PLANS
2 1/4"
BLOCKING - TYPICAL
SEE PLAN 1' - 2"
TRIM
3/4" PLASTIC LAMINATE
BACK PANEL
1 1/8"
END PANEL / CABINET
BEYOND
3"4"REFER TO
PLAN FOR
WALL TYPE
GYPSUM BULKHEAD
2"7'-0"3/4" PLASTIC LAMINATE
ADJUSTABLE SHELF
(VARIES - REFER TO
ELEVATION FOR
QUANTITIES)
BASE. REFER TO
INTERIOR FINISH PLANS
2 1/4"
BLOCKING - TYPICAL
SEE PLAN 2' - 0"
TRIM
3/4" PLASTIC LAMINATE
BACK PANEL
1 1/8"
(CLEAR DEPTH)
1' - 9 3/4"EQEQ23/8"1/8"
VALANCE
END PANEL / CABINET
BEYOND
3/4" PLASTIC LAMINATE
ADJUSTABLE SHELF
SEEELEVATIONSEEELEVATIONEQEQEQ1 1/2" PLASTIC LAMINATE
COUNTERTOP (POSTFORM)
WITH 4" BACKSPLASH
2' - 1"4"END PANEL / CABINET
BEYOND
(CLEAR DEPTH)
11 3/4"
1' - 2"
3/4" PLASTIC LAMINATE
BACK PANEL
43/4"4"3"
REFER TO
PLAN FOR
WALL TYPE DAVIDARCHI T E C TREG IS TERE
DAR10500075
STATE OF
I IND A AN
No.
SL
TA
ERN IC H LOAS
Architecture | Engineering | Interior Design
1715 Magnavox Way
Fort Wayne, IN 46804
260.432.9337
930 North Meridian
Indianapolis, IN 46204
317.917.1190
www.msktd.com
SHEET TITLE
SHEET NUMBER
SET DESCRIPTION
PROJECT NO.DATE
6993 2-21-17
MSKTD& Associates
PharmacyRenovationDate Signed 2-21-17
2/22/20173:50:02PMCasework Elevations &
Details
A10-1 11700N.MeridianStreet|Carmel,Indiana46032NorthHospitalARenovationFor 1/2" = 1'-0"
Casework Elevation2
1/2" = 1'-0"
Casework Elevation1
1/2" = 1'-0"
Casework Elevation3
C025 - PHARMACIST C025 - PHARMACIST
C025 - PHARMACIST
General Casework Notes
1/2" = 1'-0"
Casework Elevation4
C025 - PHARMACIST
6993 - Equipment Schedule
Type Mark Description Quantity
1 Computer, Single Display, w/ Keyboard & Mouse 2
2 Computer, Dual Display, w/ Keyboard & Mouse 6
3 Printer, 3 in 1, Laser, Network 3
4 Cart, Mobile 7
5 Laminar Flow Hood 2
6 Bio Safety Cabinet 1
7 High Density Shelving Unit - Wire Frame, 24" x 48" x 77", 4 Posts, 4 Shelves (Open Grid), 1 Shelf (Solid) w/ Casters 2
8 Storage, Pass-Thru, 24" x 48" x 74"2
9 Cleanroom Air-Lock Pass-Through, 24" x 24" x 24"2
11 Refrigerator, Pass-Thru, 2-door, 6' Wide 1
12 Cart, Mobile Sharps 3
13 Refrigerator, Chemo, Full-Height 1
14 Waste Container, 32-36 gal. w/ Lid and Dolly 5
15 6" Phuematic Tube Station 1
16 Shred Box 1
18 Meds Dispenser, Narcotics, Pyxis CII Safe - Main 1
19 Meds Dispenser, Narcotics, Pyxis CII Safe - Auxiliary w/ Shelf 1
20 Upright Refrigerator and Freezer Combination, 20.9 Cu. Ft. , Stainless (Domestic)1
21 High Density Shelving Unit - Wire Frame, 24" x 36" x 79", 4 Posts, 4 Shelves (Open Grid), 1 Shelf (Solid) w/ Casters 30
22 High Density Shelving Unit - Wire Frame, 18" x 36" x 80", 4 Posts, 4 Shelves (Open Grid), 1 Shelf (Solid) w/ Casters 7
23 High Density Shelving Unit - Wire Frame, 24" x 48" x 77", 4 Posts, 5 Intermediate Shelves (Open Grid), 1 Shelf (Solid) w/
Casters
2
24 High Density Shelving Unit - Wire Frame, Fluids, 24" x 48" x 77", 4 Posts, 4 Shelves (Open Grid), 1 Shelf (Solid) w/ Casters 1
26 Upright Refrigerator, Pharmacy, 2-Door 2
27 Refrigerator, Narcotics, Above Counter 1
1/8" = 1'-0"
Lower Level Equipment Plan
1/2" = 1'-0"
Casework Elevation5
C025A - ANTE
REV.DATE
1" = 1'-0"
Casework Section6
1" = 1'-0"
Casework Section7
DOMESTIC COLD WATERDOMESTIC HOT WATER RETURNDOMESTIC HOT WATERFIRE PROTECTIONNATURAL GASSANITARY6" DCW6" DHW6" DHWR6" FP6" NGVENT6" S6" V6" SCWDOMESTIC SOFT COLD WATERALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECTNTCONNECTION OF NEW WORK TO EXISTINGDETAIL WITH TOP LETTER INDICATING DETAIL DESIGNATIONAND BOTTOM NUMBER INDICATING DRAWING THAT DETAILIS REFERENCED ON OR DRAWING THAT DETAIL IS DRAWN ONSECTION WITH TOP NUMBER INDICATINGSECTION DESIGNATION AND BOTTOM NUMBERINDICATING DRAWING THAT SECTION IS CUT ONOR DRAWING THAT SECTION IS DRAWN ONA.GENERAL NOTE1FLOOR PLAN SYMBOLSPLAN NOTETHERMOSTAT -"N" INDICATING NIGHT SETBACK THERMOSTATHHUMIDISTAT1.PLAN NOTE LISTABBREV.A/EAC OR ACUACCUADADJAFCVAFFAFMSAHUAPDAPPROXARARCHASATMAVAVMSAWBBCUBDDBHPBIBLDGBOTBPBSTBTUBTUHCACAPCAVCCCCPCDSCENTRIFCFMCFOICHCICOCO2COLCOMCOMPCONCCONNCONSTCONTCPCPDCUHCWCWMCWPCWRCWSDDBDCDCVDCWBPDDDDCDEDEFLDEGDEPTDHWBPDIDIADISCDISCHDSDSWBPDUCDWGDWDWBPDWHEAEATEBHECECCECGEDEDCEEREFEFTEGELECELEVEMEREMGENCLENTREOMEQAEQACEQAIEQUIPEQVEQVPEQV VERPESESPETEUHEWEWCEWTEXHEXISTEXTFF&BF&TF/AF/SDFCFCUFDFHABBREV.FHCFINFLAFLRFODTFOPFORFOSFOSTFOVFPFPBFPCFPMFPSFPSTFSFTFTGFTRGGAGALGALVGCGHGPHGPMGVHHCHCPHDHEHGTHOHOAHORZHOSPHPHPRHPSHRHRCHTRHVACHWHWCHWCPHWPHWRHWSHXHZIAIACIADIDIFBIHOMININCLINSULINTINVI.P.S.ISOLJTKAICKECKWLLACLADLANLATLAVLBDLBSLDLFLFDLFTLOCLPRLPSLVGLVPLWTMAMACMADMAIMATMAXMBMBHMCMCAMCCMDMECHMFRMHMINMISCMOCPMPSRMPSMTDMVMVPNNANCNICNMNONOMNTSOOAOATABBREV.OCODOFCIOFOIOMOPEROPNGOSDPPCPDPEPFPGPHCPIVPLTPOCPPHPPMPRDPREFABPRESPRVPSIPSIGPVCRARADRATR/HRDRECRECIRREFRFRGRHRHCRLARMROMROPROSTRPRPGRPMRPZREQ'DRVSSASBSCSCCSCCHSCFMSCHSCWSDSECSENSSEPSFSGSHTSHWSKSMBHSMCSPSPECSQSQFTSRVSTSTDSTMSTRSTRUCTSVSWSYSSZTTBTCCTDHTDVTEMPTHWTLLTMVTMBHTSPTWUHUNOURUVLVVACVAVVBVDVELVSCVTRV VWWAGDWBW/W/OWCWCOWFMDWGWGTWHWMWPWPDWS#DESCRIPTIONARCHITECT AND ENGINEERAIR CONDITIONING UNIT OR AIR COMPRESSORAIR COOLED CONDENSING UNITACCESS DOORADJUSTABLE OR ADJACENTAIRFLOW CONTROL VALVEABOVE FINISHED FLOORAIR FLOW MEASURING STATIONAIR HANDLING UNITAIR PRESSURE DROPAPPROXIMATEAIR RECEIVERARCHITECTAIR SEPARATORATMOSPHEREACID VENTAIR VOLUME MEASURING STATIONACID WASTEBOILERBLOWER COIL UNITBACKDRAFT DAMPERBRAKE HORSEPOWERBACKWARD INCLINEDBUILDINGBOTTOMBRINE PUMPBULK SALT STORAGEBRITISH THERMAL UNITBTU PER HOURCOMPRESSED AIRCAPACITYCONSTANT AIR VOLUMECOOLING COILCOOLING COIL PUMPCONDENSATE PUMP DISCHARGECENTRIFUGALCUBIC FEET PER MINUTECONTRACTOR FURNISHED/OWNER INSTALLEDCHILLERCAST IRONCLEAN OUTCARBON DIOXIDECOLUMNCARBON DIOXIDE MANIFOLDCOMPRESSORCONCRETECONNECTIONCONSTRUCTIONCONTINUOUSCONDENSATE PUMPCONDENSATE PUMP DISCHARGECABINET UNIT HEATERCOLD WATERCOLD WATER MAKE-UPCHILLED WATER PUMPCHILLED WATER RETURNCHILLED WATER SUPPLYDIFFUSER OR DAMPERDECIBELS OR DRY BULBDUCT COILDOUBLE CHECK VALVEDOMESTIC COLD WATER BOOSTER PUMPDUAL DUCTDIRECT DIGITAL CONTROLDEAERATORDEFLECTIONDEGREEDEPARTMENTDOMESTIC HOT WATER BOOSTER PUMPDEIONIZED WATERDIAMETERDISCONNECTDISCHARGEDOWNSPOUTDOMESTIC SOFT WATER BOOSTER PUMPDOOR UNDER CUTDRAWINGDISTILLED WATERDOMESTIC WATER BOOSTER PUMPDOMESTIC WATER HEATEREXHAUST AIRENTERING AIR TEMPERATUREELECTRIC BASEBOARD HEATERELECTRICAL CONTRACTORENVIRONMENTAL CONTROL CONTRACTOREGG CRATE GRILLEEXHAUST DIFFUSERELECTRIC DUCT COILENERGY EFFICIENCY RATIOEXHAUST AIR FANENTERING FLUID TEMPERATUREEXHAUST GRILLE OR ETHYLENE GLYCOLELECTRICELEVATIONEMERGENCYEXTRUDED METAL GRILLEENCLOSUREENTERINGEND OF MAIN DRIPEQUIPMENT AIREQUIPMENT AIR COMPRESSOREQUIPMENT AIR INTAKEEQUIPMENTEQUIPMENT VACUUMEQUIPMENT VACUUM PUMPEQUIPMENT VACUUM VENTELECTRIC RADIANT PANELEMERGENCY SHOWEREXTERNAL STATIC PRESSURE OR ELEVATOR SUMP PUMPEXPANSION TANKELECTRIC UNIT HEATEREMERGENCY EYEWASHELECTRIC WATER COOLERENTERING WATER TEMPERATUREEXHAUSTEXISTINGEXTERIORDEGREES FAHRENHEITFACE & BYPASSFLOAT AND THERMOSTATIC TRAPFIRE ALARMFIRE AND SMOKE DAMPERFLEXIBLE CONNECTIONFAN COIL UNITFLOOR DRAIN OR FIRE DAMPERFIRE HOSE OR FUME HOODDESCRIPTIONFIRE HOSE CABINETFINISHFULL LOAD AMPSFLOORFUEL OIL DAY TANKFUEL OIL PUMPFUEL OIL RETURNFUEL OIL SUPPLYFUEL OIL STORAGE TANKFUEL OIL VENTFIRE PROTECTIONFAN POWERED BOXFIRE PROTECTION CONTRACTORFEET PER MINUTEFEET PER SECONDFIRE PROTECTION STORAGE TANKFLOW SWITCHFEET OR FLASH TANKFOOTING OR FITTINGFIN TUBE RADIATIONGAS, NATURALGAUGEGALLONGALVANIZEDGENERAL CONTRACTORGRAVITY HOODGALLONS PER HOURGALLONS PER MINUTEGAS NATURAL VENTHUMIDIFIER, HUMIDITY OR HEIGHTHEATING COILHEATING COIL PUMP (HOT WATER)HEADHEAT EXCHANGERHEIGHTHUB OUTLETHAND-OFF-AUTOMATICHORIZONTALHOSPITALHORSEPOWER OR HEATPUMPHIGH PRESSURE CONDENSATE RETURNHIGH PRESSURE STEAMHOURHEAT RECOVERY COILHEATERHEATING, VENTILATION AND AIR CONDITIONINGDOMESTIC HOT WATERDOMESTIC HOT WATER RECIRCHOT WATER CIRCULATING PUMPHEATING HOT WATER PUMPHEATING HOT WATER RETURNHEATING HOT WATER SUPPLYHEAT EXCHANGERHERTZINSTRUMENT AIRINSTRUMENT AIR COMPRESSORINSTRUMENT AIR DRYER, EQADINSIDE DIAMETER OR DIMENSIONINTEGRAL FACE AND BYPASSIN-HOUSE OXYGEN MANIFOLDINCHESINCLUDEINSULATEDINTERIORINVERTINTERNATIONAL PIPE SIZINGISOLATIONJOINTSHORT CIRCUIT RATINGKITCHEN EQUIPMENT CONTRACTORKILOWATTSLENGTHLAB AIR COMPRESSORLAB AIR DRYERLOCAL AREA NETWORKLEAVING AIR TEMPERATURELAVATORYLINEAR BAR DIFFUSERPOUNDSLINEAR DIFFUSERLINEAR FOOTLAMINAR FLOW DIFFUSERLEAVING FLUID TEMPERATURELOCATIONLOW PRESSURE CONDENSATE RETURNLOW PRESSURE STEAMLEAVINGLAB VACUUM PUMPLEAVING WATER TEMPERATUREMEDICAL AIRMEDICAL AIR COMPRESSORMEDICAL AIR DRYERMEDICAL AIR INTAKEMIXED AIR TEMPERATUREMAXIMUMMOP BASINBTU/HR X 1000MECHANICAL CONTRACTORMINIMUM CIRCUIT AMPACITYMOTOR CONTROL CENTERMOTORIZED DAMPERMECHANICALMANUFACTURERMANHOLEMINIMUMMISCELLANEOUSMAXIMUM OVERCURRENT PROTECTIONMEDIUM PRESSURE CONDENSATE RETURNMEDIUM PRESSURE STEAMMOUNTEDMEDICAL VACUUMMEDICAL VACUUM PUMPNORTH OR NITROGENNOT APPLICABLENORMALLY CLOSED OR NOISE CRITERIANOT IN CONTRACTNITROGEN MANIFOLDNORMALLY OPEN, NITROUS OXIDE, OR NUMBERNOMINAL OR NITROUS OXIDE MANIFOLDNOT TO SCALEOXYGENOUTSIDE AIROUTSIDE AIR TEMPERATUREDESCRIPTIONON CENTEROUTSIDE DIAMETEROWNER FURNISHED/CONTRACTOR INSTALLEDOWNER FURNISHED/OWNER INSTALLEDOXYGEN MANIFOLDOPERATOROPENINGOPEN SITE DRAINPUMP, PNEUMATIC OR PRESSUREPLUMBING CONTRACTORPRESSURE DROP OR PERFORATED DIFFUSERPNEUMATIC ELECTRICPREFILTERSPROPYLENE GLYCOLPREHEAT COILPOST INDICATOR VALVEPLASTER TRAPPOINT OF CONNECTIONPOUNDS PER HOURPARTS PER MILLIONPRESSURE RELIEF DOORPREFABRICATEDPRESSUREPRESSURE REDUCING VALVEPOUNDS PER SQUARE INCHPOUNDS PER SQUARE INCH GAUGEPOLYVINYL CHLORIDERETURN AIR OR RELIEF AIRRADIATEDRETURN AIR TEMPERATUREREHEATROOF DRAINRECEIVERRECIRCULATINGREFRIGERATORRETURN AIR FANRETURN GRILLERELIEF HOOD OR RELATIVE HUMIDITYREHEAT COILRUNNING LOAD AMPSROOMREVERSE OSMOSIS VENTREVERSE OSMOSIS PUMPREVERSE OSMOSIS STORAGE TANKRADIANT PANELSRETURN PERFORATED GRILLEREVOLUTIONS PER MINUTEREDUCED PRESSURE BACKFLOWREQUIREDROOF VENTILATORSANITARY OR SEWERSUPPLY AIR OR SOUND ATTENUATORSTEAM BOILERSTEAM COILSTEAM CONDENSATE COOLERSUBCOOLED CHILLERSTANDARD CUBIC FEET PER MINUTESCHEDULESOFT COLD WATER (DOMESTIC)SUPPLY DIFFUSER OR SMOKE DAMPERSECTIONSENSIBLESEWAGE EJECTOR PUMPSUPPLY AIR FANSUPPLY GRILLESHEETSOFT HOT WATERSINKSENSIBLE MBHSHEET METAL CONTRACTORSTATIC PRESSURE OR STORM PUMPSPECIFICATIONSSQUARESQUARE FEETSAFETY RELIEF VALVESTEAM TRAPSTANDARDSTORMSTARTERSTRUCTURALSTEAM VENTSWITCHSYSTEMSPRINKLER ZONETHERMOSTATTERMINAL BOXTEMPERATURE CONTROL CONTRACTORTOTAL DISCHARGE HEADTRIPLE DUTY VALVETEMPERATURETEMPERED HOT WATERTEMPERATURE LOW LIMITTHERMOSTAT MIXING VALVETOTAL MBHTOTAL STATIC PRESSURETEMPERED WATERUNIT HEATERUNLESS NOTED OTHERWISEURINALULTRA VIOLET LIGHTVENTVACUUMVARIABLE AIR VOLUMEVACUUM BREAKERVOLUME DAMPER (MANUAL)VELOCITYVARIABLE SPEED CONTROLLERVENT THROUGH ROOFVACUUM VENTWASTE, WATTS OR WIDTHWASTE ANESTHESIA GAS DISPOSAL PUMPWET BULBWITHWITHOUTWATER CLOSET OR WATER COLUMNWALL CLEAN OUTWATER FLOW MEASURING DEVICEWATER GAUGEWEIGHTWALL HYDRANTWATER METERWEATHERPROOFWATER PRESSURE DROPWATER SOFTENERPOUNDACDAIR CONDITIONING CONDENSATE DRAINMECHANICAL AND PLUMBING ABBREVIATIONSPLUMBING PIPING SYMBOLSVALVE AND FITTING SYMBOLSCALIBRATED BALANCE VALVEPIPING FLEXIBLE CONNECTIONPIPE TURNED UP (UNLESS NOTED OTHERWISE)PIPE TURNED DOWNPIPE OUT TOPPIPE OUT BOTTOMTHREADED NIPPLE W/CAPPIPE WITH BLIND FLANGECONCENTRIC REDUCERECCENTRIC REDUCERCHECK VALVEUNIONGATE VALVEBALL VALVEGLOBE VALVEBUTTERFLY VALVETEMPERATURE CONTROL -2 WAY MODULATING VALVETEMPERATURE CONTROL -2 WAY 2 POSITION MODULATING VALVETEMPERATURE CONTROL -3 WAY MODULATING VALVETEMPERATURE CONTROL -3 WAY 2 POSITION MODULATING VALVESAFETY RELIEF VALVESTRAINERFLOW METERFLOOR DRAINZONE CONTROL VALVE (OS&Y)AUTOMATIC FLOW CONTROL VALVEFLOW MEASURING DEVICEMANUAL AIR RELIEF VENTAUTOMATIC AIR RELIEF VENTLUBRICATED PLUG VALVESTEAM PRESSURE REDUCING VALVEANGLE VALVEGAS PRESSURE RELIEF VALVEREFRIGERANT HOT GAS BY-PASS VALVESHUT-OFF COCK (HYDRONICS)SOLENOID VALVEREFRIGERANT EXPANSION VALVEWATER PRESSURE REDUCING/REGULATING VALVECOMBINATION WATER PRESSURE RELIEF AND REDUCING VALVESTEAM TRAPDIELECTRIC UNION BETWEEN STEEL AND COPPERSTRAINER (STEAM)PRESSURE AND TEMPERATURE PLUGREFRIGERANT SIGHT GLASSTHERMOMETER(P=PRESS V=VAC T=TEMP) GAUGESENSOR (T-TEMP H-HUMIDITY)FLOW SWITCHCLEAN OUTWATER HAMMER ARRESTOR OR ALARM PRESSURE/VACUUM SWITCHINDICATED EXPANSION LOOP (COLD SPRUNG)ANCHORGUIDEREDUCED PRESSURE BACKFLOW PREVENTERATMOSPHERIC VACUUM BREAKERPRESSURE VACUUM BREAKERREFRIGERANT SHUT-OFF VALVEDOMESTIC WATER TEMPERATURE REGULATING VALVEEXPANSION JOINTDIFFERENTIAL SWITCHΔTPATTANONCNONCDETAIL VIEWPLAN VIEWSA1011TYP1A101TYPTAGSV1V2V3V4V5V6V7V8V9V10V11V12V13V14V15V16V17V18V19V20V21V22V23V24V25V26V27V28V29V30V31V32V33V34V35V36V37V38V39V40V41V42V43V44V45V46V47V48V49V50V51V52V53V54V55V56V57V58V59V60TYPTYPICALCVCENTRAL VACUUMCENTRAL VACUUM OUTLETV61GENERAL NOTES REQUIRED TO COMPLETE THE SCOPE OF THIS PROJECT1.ALL CONTRACT DOCUMENTS (SPECIFICATIONS AND DRAWINGS) ARE COMPLIMENTARY ANDMUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.2.ALL CONFLICTS SHALL BE BROUGHT TO THE ARCHITECTS OR ENGINEERS ATTENTION INORDER TO ALLOW A CLARIFICATION TO BE ISSUED. ANY WORK COMPLETED WITHOUT THECLARIFYING INFORMATION IS AT THE CONTRACTORS FINANCIAL RISK.3.THE CONTRACTOR SHALL PROVIDE AND FURNISH ALL MATERIALS AND ACCESSORIES TOCREATE A FULLY OPERATIONAL, CODE COMPLIANT AND TESTED SYSTEM. ALL MATERIALSAND ACCESSORIES REQUIRED TO CREATE THE FULLY OPERATIONAL SYSTEM SHALL BEINCLUDED IN THE COST OF THIS PROJECT.4.THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR MAY AT THEIR OPTIONMODIFY THE PIPE ROUTING IN ORDER TO CREATE A SYSTEM THAT MEETS THE INTENT OF THISSET OF CONSTRUCTION DOCUMENTS.5.THE CONTRACTOR SHALL INCLUDE ALL ITEMS THAT ARE REQUIRED TO ENSURE THAT THEENTIRE SYSTEM IS FUNCTIONING IN COMPLIANCE WITH THE APPLICABLE CODES, ANDMANUFACTURES INSTALLATION RECOMMENDATIONS AND OR REQUIREMENTS.6.ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS AND/OR STRUCTURAL MEMBERS FOR THE INSTALLATION OF THE PLUMBING AND FIRE PROTECTION SYSTEMS SHALL BEPROVIDED AS PART OF THE SCOPE OF THIS PROJECT.7.STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY WAY WITHOUTTHE STRUCTURAL ENGINEERS REVIEW AND PRIOR WRITTEN APPROVAL.8.PROVIDE FIRE STOPPING WHERE PIPES PENETRATE FIRE RATED FLOORS AND WALLS. FIRESTOPPING MATERIALS AND METHODS SHALL BE PER LOCAL AND STATE CODES ANDREQUIREMENTS.9.ALL PLUMBING SYSTEMS SHALL BE INSTALLED PER THE CURRENT PLUMBING CODE FOR THELOCATION OF THE WORK BEING INSTALLED.10.ALL PLUMBING EQUIPMENT, PIPING, FIXTURES, AND PIPE ACCESSORIES SHALL BE NSF 61,ANNEX G COMPLIANT.11.ALL PIPING LOCATED WITHIN A RETURN AIR PLENUM SHALL COMPLY WITH A 25/50 FLAMESMOKE RATING. ANY EXISTING PIPING DISCOVERED WITHIN A RETURN AIR PLENUM THATDOES NOT COMPLY WITH THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT FOR FURTHER CLARIFICATION.12.ALL EXTERIOR WALL PENETRATIONS SHALL BE SEALED WATER AND WEATHER TIGHT BY THEAPPROPRIATE TRADE COMPETENT IN COMPLETING THIS WORK. THE COST OF THIS WORKSHALL BE INCLUDED IN THE SCOPE OF THIS PROJECT.13.ALL VENT THROUGH ROOF (VTR) LOCATIONS SHALL BE FIELD VERIFIED IN REGARDS TO ANYOUTDOOR INTAKE. LOCATION OF VTR SHALL BE NO LESS THAN AS REQUIRED BY THE LOCALOR STATE CODES.14.DO NOT ATTACH ANY CONSTRUCTION TO THE ROOF DECK JOIST BRIDGING, JOIST CROSSBRACING, PIPING, CONDUIT, DUCTWORK OR ANY OTHER NON-STRUCTURAL ITEM.15. DO NOT WELD OR DRILL INTO STRUCTURAL STEEL OR JOIST; INSTEAD USE CLAMPS, TIE WIRE, THRU-BOLTS WITH WASHERS16.DO NOT USE ANY PVC, PLASTIC, ETC. IN PLENUM OR DEMISING WALLS UNLESS FIRE WRAPPED.ALL WOOD BLOCKING AND NAILERS, CONCEALED OR NOT SHALL BE FIRE RETARDANTTREATED.17.DO NOT PENETRATE BUILDING WALLS FOR ANY DUCTING OR VENTING; ROUTE THROUGH ROOFUSING LANDLORDS ROOFING CONTRACTOR.18.VENT THROUGH ROOF INSTALLATION; ALL ROOFING WORK SHALL BE COMPLETED BY THELANDLORDS ROOFING CONTRACTOR. THE COST SHALL BE INCLUDED IN THE SCOPE OF THISPROJECT.19.PIPING BELOW GROUND SHALL BE SERVICE-WEIGHT CAST IRON OR SCHEDULE 40 PVC. NO-HUBPIPING OR FERNCO CONNECTIONS ARE NOT PERMITTED BELOW GRADE.20DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE "L" WATER TUBE.21.ALL PIPING SHALL BE PROPERLY SUSPENDED BY THE STRUCTURE PER THE LOCAL CODES.22.NO SANITARY WASTE OR VENT, HOT OR COLD WATER SHALL BE ALLOWED TO BE INSTALLED INTHE DEMISING WALLS.23.ALL PIPING INSULATED SHALL BE WITH PLENUM RATED MATERIALS.24.FLOOR DRAINS SHALL BE PROVIDED WITH TRAP PRIMERS.25.GAS PIPING SUPPORTED ON THE ROOF SHALL BE PROVIDED FREE FLOATING PREFABRICATEDSUPPORTS OR EQUIPMENT SUPPORTS WITH ROLLER ASSEMBLIES. WOOD SUPPORTS WILLNOT BE PERMITTED.26.ALL GAS PIPING SHALL BE PROVIDED PIPE LABELS IDENTIFYING THE GAS PRESSURE.27.ALL GAS PIPING SHALL BE INSTALLED PER THE LOCAL CODES FOR MATERIALS ANDINSTALLATIONS REQUIREMENTS.28.ALL SHUT-DOWN OF UTILITIES AND FIRE PROTECTION SYSTEMS SHALL BE ARRANGED WITH NOLESS THAN SEVEN (7) DAYS NOTICE TO THE LANDLORD. WORK MAY NOT COMMENCE UNLESSWRITTEN APPROVAL IS PROVIDED BY THE LANDLORD.29.ALL DOMESTIC WATER BRANCH PIPES SERVING FIXTURES OR EQUIPMENT WITH FAST ACTINGOR ELECTRONIC VALVES SHALL BE PROVIDED WATER HAMMER ARRESTORS.30.ALL BRANCH PIPES FROM DOMESTIC WATER MAINS SHALL BE PROVIDED QUARTER TURN FULLPORT BALL VALVES ON THE BRANCH PIPE JUST ADJACENT TO THE MAIN.Architecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:11:14 PMPlumbing Symbols andAbbreviationsP0-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForREV. DATE
REF.44.34.64.74.95678HJKLK.51323" S43" S2" S2" S2" S2" S112" S3" S453" S3" S31.ALL CONTRACT DOCUMENTS (SPECIFICATIONS AND DRAWINGS) ARE COMPLIMENTARY ANDMUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.2.ALL CONFLICTS SHALL BE BROUGHT TO THE ARCHITECTS OR ENGINEERS ATTENTION INORDER TO ALLOW A CLARIFICATION TO BE ISSUED. ANY WORK COMPLETED WITHOUT THECLARIFYING INFORMATION IS AT THE CONTRACTORS FINANCIAL RISK.3.THE CONTRACTOR SHALL PROVIDE AND FURNISH ALL MATERIALS AND ACCESSORIES TOCREATE A FULLY OPERATIONAL, CODE COMPLIANT AND TESTED SYSTEM. ALL MATERIALSAND ACCESSORIES REQUIRED TO CREATE THE FULLY OPERATIONAL SYSTEM SHALL BEINCLUDED IN THE COST OF THIS PROJECT.4.THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR MAY AT THEIR OPTIONMODIFY THE PIPE ROUTING IN ORDER TO CREATE A SYSTEM THAT MEETS THE INTENT OF THISSET OF CONSTRUCTION DOCUMENTS.5.THE CONTRACTOR SHALL INCLUDE ALL ITEMS THAT ARE REQUIRED TO ENSURE THAT THEENTIRE SYSTEM IS FUNCTIONING IN COMPLIANCE WITH THE APPLICABLE CODES, ANDMANUFACTURES INSTALLATION RECOMMENDATIONS AND OR REQUIREMENTS.6.ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS AND/OR STRUCTURAL MEMBERS FOR THE INSTALLATION OF THE PLUMBING AND FIRE PROTECTION SYSTEMS SHALL BEPROVIDED AS PART OF THE SCOPE OF THIS PROJECT.7.STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY WAY WITHOUTTHE STRUCTURAL ENGINEERS REVIEW AND PRIOR WRITTEN APPROVAL.8.PROVIDE FIRE STOPPING WHERE PIPES PENETRATE FIRE RATED FLOORS AND WALLS. FIRESTOPPING MATERIALS AND METHODS SHALL BE PER LOCAL AND STATE CODES ANDREQUIREMENTS.9.ALL PLUMBING SYSTEMS SHALL BE INSTALLED PER THE CURRENT PLUMBING CODE FOR THELOCATION OF THE WORK BEING INSTALLED.10.ALL PLUMBING EQUIPMENT, PIPING, FIXTURES, AND PIPE ACCESSORIES SHALL BE NSF 61,ANNEX G COMPLIANT.11.ALL PIPING LOCATED WITHIN A RETURN AIR PLENUM SHALL COMPLY WITH A 25/50 FLAMESMOKE RATING. ANY EXISTING PIPING DISCOVERED WITHIN A RETURN AIR PLENUM THATDOES NOT COMPLY WITH THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT FOR FURTHER CLARIFICATION.12.DO NOT ATTACH ANY CONSTRUCTION TO THE ROOF DECK JOIST BRIDGING, JOIST CROSSBRACING, PIPING, CONDUIT, DUCTWORK OR ANY OTHER NON-STRUCTURAL ITEM.13. DO NOT WELD OR DRILL INTO STRUCTURAL STEEL OR JOIST; INSTEAD USE CLAMPS, TIE WIRE, THRU-BOLTS WITH WASHERS14.DO NOT USE ANY PVC, PLASTIC, ETC. IN PLENUM OR DEMISING WALLS UNLESS FIRE WRAPPED.ALL WOOD BLOCKING AND NAILERS, CONCEALED OR NOT SHALL BE FIRE RETARDATTREATED.15.PIPING BELOW GROUND SHALL BE SERVICE-WEIGHT CAST IRON. NO-HUB PIPING OR FERNCO CONNECTIONS ARE NOT PERMITTED BELOW GRADE.16.DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE "L" WATER TUBE.17.ALL PIPING SHALL BE PROPERLY SUSPENDED BY THE STRUCTURE PER THE LOCAL CODES.18.ALL PIPING INSULATED SHALL BE WITH PLENUM RATED MATERIALS.19.FLOOR DRAINS SHALL BE PROVIDED WITH TRAP PRIMERS.20.ALL SHUT-DOWN OF UTILITIES AND FIRE PROTECTION SYSTEMS SHALL BE ARRANGED WITH NOLESS THAN SEVEN (7) DAYS NOTICE TO THE BUILDING OWNER. WORK MAY NOT COMMENCE UNLESS WRITTEN APPROVAL IS PROVIDED BY THE LANDLORD.21.ALL DOMESTIC WATER BRANCH PIPES SERVING FIXTURES OR EQUIPMENT WITH FAST ACTINGOR ELECTRONIC VALVES SHALL BE PROVIDED WATER HAMMER ARRESTORS.22.ALL BRANCH PIPES FROM DOMESTIC WATER MAINS SHALL BE PROVIDED QUARTER TURN FULLPORT BALL VALVES ON THE BRANCH PIPE JUST ADJACENT TO THE MAIN.PLUMBING GENERAL NOTESTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:11:16 PMFoundation PlumbingDemolition PlanP1-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Foundation Plumbing Demolition PlanPLAN NOTES1.REMOVE EXISTING 2"W UP2.ABANDONE PIPE UNDER SLAB3.REMOVE SECTION OF WASTE PIPE AND PLUG WASTE PIPE AT FITTING4.REMOVE EXISTING 3"S CLEANOUT FOR RELOCATION5.REMOVE 2"W FOR RECONNECTIONREV. DATE
REF.44.34.64.74.95678HJKLK.511234452" DCW3/4" DHW3/4" DHWR2" V1/2" DHW61 1/2" V1/2" DHW1/2" DCW1 1/2" V77FP CONTRACTOR SHALL REMOVE ALL FIRE SPRINKLER MAINS,BRANCH MAINS, BRANCH PIPES, SUB-BRANCH PIPES AND ALLFIRE SPRINKLER ARM-OVER PIPES AND ALL FIRE SPRINKLERHEADS FROM THE PROJECT SPACE. THE CONTRACTOR SHALLINSTALL A COMPLETE NEW FIRE SPRINKLER SYSTEM THATCOMPLIES WITH NFPA 13, AND NEW CEILING AND WALL LAYOUT.THIS CONTRACTOR SHALL COORDIANTE THE INSTALLATION OFTHE ENTIRE FIRE SPRINKLER SYSTEM INSTALLATION WITH ALLOTHER TRADES TO ENSURER THAT ALL TRADES EQUIPMENTAND MATERIALS WILL FIT WITHIN THE DESIGNATED SPACES.1.ALL CONTRACT DOCUMENTS (SPECIFICATIONS AND DRAWINGS) ARE COMPLIMENTARY ANDMUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.2.ALL CONFLICTS SHALL BE BROUGHT TO THE ARCHITECTS OR ENGINEERS ATTENTION INORDER TO ALLOW A CLARIFICATION TO BE ISSUED. ANY WORK COMPLETED WITHOUT THECLARIFYING INFORMATION IS AT THE CONTRACTORS FINANCIAL RISK.3.THE CONTRACTOR SHALL PROVIDE AND FURNISH ALL MATERIALS AND ACCESSORIES TOCREATE A FULLY OPERATIONAL, CODE COMPLIANT AND TESTED SYSTEM. ALL MATERIALSAND ACCESSORIES REQUIRED TO CREATE THE FULLY OPERATIONAL SYSTEM SHALL BEINCLUDED IN THE COST OF THIS PROJECT.4.THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR MAY AT THEIR OPTIONMODIFY THE PIPE ROUTING IN ORDER TO CREATE A SYSTEM THAT MEETS THE INTENT OF THISSET OF CONSTRUCTION DOCUMENTS.5.THE CONTRACTOR SHALL INCLUDE ALL ITEMS THAT ARE REQUIRED TO ENSURE THAT THEENTIRE SYSTEM IS FUNCTIONING IN COMPLIANCE WITH THE APPLICABLE CODES, ANDMANUFACTURES INSTALLATION RECOMMENDATIONS AND OR REQUIREMENTS.6.ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS AND/OR STRUCTURAL MEMBERS FOR THE INSTALLATION OF THE PLUMBING AND FIRE PROTECTION SYSTEMS SHALL BEPROVIDED AS PART OF THE SCOPE OF THIS PROJECT.7.STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY WAY WITHOUTTHE STRUCTURAL ENGINEERS REVIEW AND PRIOR WRITTEN APPROVAL.8.PROVIDE FIRE STOPPING WHERE PIPES PENETRATE FIRE RATED FLOORS AND WALLS. FIRESTOPPING MATERIALS AND METHODS SHALL BE PER LOCAL AND STATE CODES ANDREQUIREMENTS.9.ALL PLUMBING SYSTEMS SHALL BE INSTALLED PER THE CURRENT PLUMBING CODE FOR THELOCATION OF THE WORK BEING INSTALLED.10.ALL PLUMBING EQUIPMENT, PIPING, FIXTURES, AND PIPE ACCESSORIES SHALL BE NSF 61,ANNEX G COMPLIANT.11.ALL PIPING LOCATED WITHIN A RETURN AIR PLENUM SHALL COMPLY WITH A 25/50 FLAMESMOKE RATING. ANY EXISTING PIPING DISCOVERED WITHIN A RETURN AIR PLENUM THATDOES NOT COMPLY WITH THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT FOR FURTHER CLARIFICATION.12.DO NOT ATTACH ANY CONSTRUCTION TO THE ROOF DECK JOIST BRIDGING, JOIST CROSSBRACING, PIPING, CONDUIT, DUCTWORK OR ANY OTHER NON-STRUCTURAL ITEM.13. DO NOT WELD OR DRILL INTO STRUCTURAL STEEL OR JOIST; INSTEAD USE CLAMPS, TIE WIRE, THRU-BOLTS WITH WASHERS14.DO NOT USE ANY PVC, PLASTIC, ETC. IN PLENUM OR DEMISING WALLS UNLESS FIRE WRAPPED.ALL WOOD BLOCKING AND NAILERS, CONCEALED OR NOT SHALL BE FIRE RETARDATTREATED.15.PIPING BELOW GROUND SHALL BE SERVICE-WEIGHT CAST IRON. NO-HUB PIPING OR FERNCO CONNECTIONS ARE NOT PERMITTED BELOW GRADE.16.DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE "L" WATER TUBE.17.ALL PIPING SHALL BE PROPERLY SUSPENDED BY THE STRUCTURE PER THE LOCAL CODES.18.ALL PIPING INSULATED SHALL BE WITH PLENUM RATED MATERIALS.19.FLOOR DRAINS SHALL BE PROVIDED WITH TRAP PRIMERS.20.ALL SHUT-DOWN OF UTILITIES AND FIRE PROTECTION SYSTEMS SHALL BE ARRANGED WITH NOLESS THAN SEVEN (7) DAYS NOTICE TO THE BUILDING OWNER. WORK MAY NOT COMMENCE UNLESS WRITTEN APPROVAL IS PROVIDED BY THE LANDLORD.21.ALL DOMESTIC WATER BRANCH PIPES SERVING FIXTURES OR EQUIPMENT WITH FAST ACTINGOR ELECTRONIC VALVES SHALL BE PROVIDED WATER HAMMER ARRESTORS.22.ALL BRANCH PIPES FROM DOMESTIC WATER MAINS SHALL BE PROVIDED QUARTER TURN FULLPORT BALL VALVES ON THE BRANCH PIPE JUST ADJACENT TO THE MAIN.PLUMBING GENERAL NOTESTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:11:18 PMLower Level PlumbingDemolition PlanP1-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Lower Level Plumbing Demolition PlanPLAN NOTES1.REMOVE EXISTING CO2.REMOVE EXISTING HW, CW, HWC FOR RECONNECTION3.REMOVE EXISTING V AND CAP4.REMOVE EXISTING WASTE, VENT AND WATER PIPE BACK TO MAIN AND CAP5.REMOVE EXISTING DRAIN PAN DRAIN. DRAIN SHALL BE RELOCATED.6.REMOVE EXISTING FIXTURE COMPLETE, REMOVE W &V, H&CW BACK TO MAINS AND CAP7.REMOVE EXISTING FP MAIN FOR RE-INSTALLATION IN ORDER TO COORDIANTE WITH THE NEW AHUREV. DATE
REF.44.34.64.74.95678HJKLK.513" S343" S3" SCO2CO3" S3" S55462" S2" S2" S2" S3" S1.ALL CONTRACT DOCUMENTS (SPECIFICATIONS AND DRAWINGS) ARE COMPLIMENTARY ANDMUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.2.ALL CONFLICTS SHALL BE BROUGHT TO THE ARCHITECTS OR ENGINEERS ATTENTION INORDER TO ALLOW A CLARIFICATION TO BE ISSUED. ANY WORK COMPLETED WITHOUT THECLARIFYING INFORMATION IS AT THE CONTRACTORS FINANCIAL RISK.3.THE CONTRACTOR SHALL PROVIDE AND FURNISH ALL MATERIALS AND ACCESSORIES TOCREATE A FULLY OPERATIONAL, CODE COMPLIANT AND TESTED SYSTEM. ALL MATERIALSAND ACCESSORIES REQUIRED TO CREATE THE FULLY OPERATIONAL SYSTEM SHALL BEINCLUDED IN THE COST OF THIS PROJECT.4.THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR MAY AT THEIR OPTIONMODIFY THE PIPE ROUTING IN ORDER TO CREATE A SYSTEM THAT MEETS THE INTENT OF THISSET OF CONSTRUCTION DOCUMENTS.5.THE CONTRACTOR SHALL INCLUDE ALL ITEMS THAT ARE REQUIRED TO ENSURE THAT THEENTIRE SYSTEM IS FUNCTIONING IN COMPLIANCE WITH THE APPLICABLE CODES, ANDMANUFACTURES INSTALLATION RECOMMENDATIONS AND OR REQUIREMENTS.6.ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS AND/OR STRUCTURAL MEMBERS FOR THE INSTALLATION OF THE PLUMBING AND FIRE PROTECTION SYSTEMS SHALL BEPROVIDED AS PART OF THE SCOPE OF THIS PROJECT.7.STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY WAY WITHOUTTHE STRUCTURAL ENGINEERS REVIEW AND PRIOR WRITTEN APPROVAL.8.PROVIDE FIRE STOPPING WHERE PIPES PENETRATE FIRE RATED FLOORS AND WALLS. FIRESTOPPING MATERIALS AND METHODS SHALL BE PER LOCAL AND STATE CODES ANDREQUIREMENTS.9.ALL PLUMBING SYSTEMS SHALL BE INSTALLED PER THE CURRENT PLUMBING CODE FOR THELOCATION OF THE WORK BEING INSTALLED.10.ALL PLUMBING EQUIPMENT, PIPING, FIXTURES, AND PIPE ACCESSORIES SHALL BE NSF 61,ANNEX G COMPLIANT.11.ALL PIPING LOCATED WITHIN A RETURN AIR PLENUM SHALL COMPLY WITH A 25/50 FLAMESMOKE RATING. ANY EXISTING PIPING DISCOVERED WITHIN A RETURN AIR PLENUM THATDOES NOT COMPLY WITH THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT FOR FURTHER CLARIFICATION.12.DO NOT ATTACH ANY CONSTRUCTION TO THE ROOF DECK JOIST BRIDGING, JOIST CROSSBRACING, PIPING, CONDUIT, DUCTWORK OR ANY OTHER NON-STRUCTURAL ITEM.13. DO NOT WELD OR DRILL INTO STRUCTURAL STEEL OR JOIST; INSTEAD USE CLAMPS, TIE WIRE, THRU-BOLTS WITH WASHERS14.DO NOT USE ANY PVC, PLASTIC, ETC. IN PLENUM OR DEMISING WALLS UNLESS FIRE WRAPPED.ALL WOOD BLOCKING AND NAILERS, CONCEALED OR NOT SHALL BE FIRE RETARDATTREATED.15.PIPING BELOW GROUND SHALL BE SERVICE-WEIGHT CAST IRON. NO-HUB PIPING OR FERNCO CONNECTIONS ARE NOT PERMITTED BELOW GRADE.16.DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE "L" WATER TUBE.17.ALL PIPING SHALL BE PROPERLY SUSPENDED BY THE STRUCTURE PER THE LOCAL CODES.18.ALL PIPING INSULATED SHALL BE WITH PLENUM RATED MATERIALS.19.FLOOR DRAINS SHALL BE PROVIDED WITH TRAP PRIMERS.20.ALL SHUT-DOWN OF UTILITIES AND FIRE PROTECTION SYSTEMS SHALL BE ARRANGED WITH NOLESS THAN SEVEN (7) DAYS NOTICE TO THE BUILDING OWNER. WORK MAY NOT COMMENCE UNLESS WRITTEN APPROVAL IS PROVIDED BY THE LANDLORD.21.ALL DOMESTIC WATER BRANCH PIPES SERVING FIXTURES OR EQUIPMENT WITH FAST ACTINGOR ELECTRONIC VALVES SHALL BE PROVIDED WATER HAMMER ARRESTORS.22.ALL BRANCH PIPES FROM DOMESTIC WATER MAINS SHALL BE PROVIDED QUARTER TURN FULLPORT BALL VALVES ON THE BRANCH PIPE JUST ADJACENT TO THE MAIN.PLUMBING GENERAL NOTESTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:11:20 PMFoundation PlumbingPlanP2-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Foundation Plumbing PlanPLAN NOTES1.PLUG EXISTING S PIPE2.2"W UP TO SCRUB SINK3.CONNECT 2"W TO EXISTING 2"W4.CONNECT 4"S TO EXISTING 4"S5.SANITARY TO FLOOR CLEAN OUT6.2"W UP TO EEWREV. DATE
PLUMBING FIXTURE SCHEDULEFIXTUREREFERENCEMANUFACTUREREFERENCE MODEL WATER USAGECONNECTION SIZESNOTESWASTE VENTHOTWATERCOLDWATERTEPIDWATERSK-1 - - - 2" 1-1/2"1/2"1/2" -OWNER FURNISHED, CONTRACTOR INSTALLED. PROVIDE ASSE 1070MIXING VALVESK-2 (FAUCET) SPEAKMAN SEF1800-CA-TW 1.5 GPM - - 1/2" 1/2"- WITH ASSE 1070 MIXING VALVEEEW-1, TMV=1 SPEAKMANSE-580 WITH PT, SPV-SCALDPROTECTION VALVE- 2" 1-1/2"1/2"1/2" 3/4"INSTALL PER MANUFACTURES REQUIREMENTS, STATE AND LOCALCODE REQUIREMENTSPIPE INSULATION SCHEDULEPIPING SYSTEMTHICKNESS, TYPENOTESMOISTURE CONDENSATE DRAINS - ABOVE GRADE 3/4" CELLULAR FOAM 1INTERIOR HORIZONTAL WASTE LINES FROM AIRCONDITIONING EQUIPMENT3/4" CELLULAR FOAM 1DOMESTIC HOT WATER LINE 3/4" AND LESS 1" PRE-FORMED FIBERGLASS 1,2DOMESTIC COLD WATER LINES 1-1/4" AND LESS .5" PRE-FORMED FIBERGLASS 1,2NOTES:1. MINIMUM 1" WITH CONDUCTIVITY LESS THAN 0.28 BTU * INCH / (HR * FT * F)2. FIELD APPLIED JACKET : FOIL AND PAPER - APPLY WITH 2" OVERLAPPIPE CLEANOUT DETAILFLOWSCALE:NONEBRONZE PLUG6" PIPE AND SMALLER: PROVIDE 18" CLEAR SPACE AROUND ALL SIDES8" PIPE AND LARGER: PROVIDE 36" CLEAR SPACE AROUND ALL SIDESCLEANOUT BOX WITHRECESSED SOLID COVERFINISHED FLOORDEPTH TO SEWERVARIESCLEANOUT PIPE DIAMETERPER STATE AND LOCAL CODETERRAZZO OR CERAMICTILED FLOORSCONCRETEFINISHED FLOORSCARPETED FLOORSSAOCN RESILIENT TILED FLOORSFLOOR CLEANOUT DETAILNO SCALETHREADED CO PLUGRECESSED COVERFERRULE W/CUT-OFF SECTIONSTHREADED CO PLUGCARPETPAD1-1/4" DIA CO MARKERCARPETFERRULE W/CUT-OFF SECTTIONSTHREADED CO PLUGADJ HEADCISCORIATED BRONZETOP (WHEN SPECIFIED)BRONZE TOPBACK FILL BOTH SIDES AND OVERTOP OF PIPE WITH CONSTRUCTIONSITE SOIL (CLEAN WITH NO DEBRIS)COMPACT AS REQUIRED.CONCRETE FLOORSTORM/SANITARY PIPESLOPE PER CODEPIPE BEDDING MATERIAL: 6" THICKCLEAN #57, ENSURE PIPE SLOPE ASREQUIRED BY THE LOCAL PLUMBING CODE.STONE PER STRUCTURALDETAILSFLOWFLOWPIPE BEDDING DETAILEXTERIOR WALLSINTERIOR FIRE RATED WALLSTHROUGH INTERIOR NON-RATED WALLSAREAS ONLY.PROVIDE ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING IN EXPOSEDNOTES:SEE SPECIFICATION SECTIONS FOR FURTHER REQUIREMENTS INCLUDING FLOOR SLEEVES.INSULATED OR UNINSULATED PIPEINTERIOR FIRE RATED WALLSUNINSULATED PIPE THROUGHINSULATED PIPE THROUGHOR SMOKE-RESISTANT CORRIDOR WALLSLOCATE FIRESTOP LABEL ON EACH SIDE OF PENETRATION SO THAT IT IS VISIBLE FROM AN ACCESSIBLE LOCATIONINCLUDES FIRE WALLS, FIRE BARRIERS, SMOKE BARRIERS, AND FIRE PARTITIONS.ABOVE CEILING.1313WALL SLEEVESLEEVE WATER STOPFINISHED WALLSURFACENONCOMBUSTIBLESEALANTFILL ANNULAR GAPSAROUND PIPES ONEACH SIDE OF WALLASSEMBLYPIPEPIPE INSULATION TOBE CONT. THRU WALLPIPE SLEEVE TO BE SIZED TOPASS PIPE AND INSULATIONTHRU SLEEVE AND ALLOWSPACE FOR SEALANT TOMEET UL-LISTINGFINISHED WALL SURFACEOF RATED ASSEMBLYPIPEFIRESTOP EACH SIDEOF SLEEVE ASSPECIFED IN DIV 7TERMINATE SLEEVEFLUSH WITH FINISHED WALLPIPE SLEEVE TO BE SIZED TO PASSPIPE THRU SLEEVE AND ALLOW SPACEFOR SEALANT TO MEET UL-LISTINGPIPEHYDO-STATIC PIPECLOSURE; "LINK-SEAL"WALLFINISHED WALL SURFACEOF RATED ASSEMBLYFIRESTOP EACH SIDEOF SLEEVE ASSPECIFED IN DIV 7PIPETERMINATE SLEEVE FLUSHWITH FINISHED WALLPIPE PENETRATION DETAIL2341REF.44.34.64.74.95678HJKLK.5HIGH HAZARDBUFFERC025BANTEC025ANON-HAZARDBUFFERC025CPICKSTATIONC025DOFFICEC025EPHARMACISTC025UNPACKINGC026LOUNGEC026ASTAFF TOILETC026B123455566556655EEW-1SK-2AHU-PH55FP CONTRACTOR SHALL REMOVE ALL FIRE SPRINKLER MAINS,BRANCH MAINS, BRANCH PIPES, SUB-BRANCH PIPES AND ALLFIRE SPRINKLER ARM-OVER PIPES AND ALL FIRE SPRINKLERHEADS FROM THE PROJECT SPACE. THE CONTRACTOR SHALLINSTALL A COMPLETE NEW FIRE SPRINKLER SYSTEM THATCOMPLIES WITH NFPA 13, AND NEW CEILING AND WALL LAYOUT.THIS CONTRACTOR SHALL COORDIANTE THE INSTALLATION OFTHE ENTIRE FIRE SPRINKLER SYSTEM INSTALLATION WITH ALLOTHER TRADES TO ENSURER THAT ALL TRADES EQUIPMENTAND MATERIALS WILL FIT WITHIN THE DESIGNATED SPACES.1 1/2" V3/4" DCW3/4" DHWRSK-11 1/2" V1/2" DCW1/2" DHW1/2" DCW1/2" DHW3/4" DHWR3/4" DHW2" DCW1.ALL CONTRACT DOCUMENTS (SPECIFICATIONS AND DRAWINGS) ARE COMPLIMENTARY ANDMUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.2.ALL CONFLICTS SHALL BE BROUGHT TO THE ARCHITECTS OR ENGINEERS ATTENTION INORDER TO ALLOW A CLARIFICATION TO BE ISSUED. ANY WORK COMPLETED WITHOUT THECLARIFYING INFORMATION IS AT THE CONTRACTORS FINANCIAL RISK.3.THE CONTRACTOR SHALL PROVIDE AND FURNISH ALL MATERIALS AND ACCESSORIES TOCREATE A FULLY OPERATIONAL, CODE COMPLIANT AND TESTED SYSTEM. ALL MATERIALSAND ACCESSORIES REQUIRED TO CREATE THE FULLY OPERATIONAL SYSTEM SHALL BEINCLUDED IN THE COST OF THIS PROJECT.4.THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR MAY AT THEIR OPTIONMODIFY THE PIPE ROUTING IN ORDER TO CREATE A SYSTEM THAT MEETS THE INTENT OF THISSET OF CONSTRUCTION DOCUMENTS.5.THE CONTRACTOR SHALL INCLUDE ALL ITEMS THAT ARE REQUIRED TO ENSURE THAT THEENTIRE SYSTEM IS FUNCTIONING IN COMPLIANCE WITH THE APPLICABLE CODES, ANDMANUFACTURES INSTALLATION RECOMMENDATIONS AND OR REQUIREMENTS.6.ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS AND/OR STRUCTURAL MEMBERS FOR THE INSTALLATION OF THE PLUMBING AND FIRE PROTECTION SYSTEMS SHALL BEPROVIDED AS PART OF THE SCOPE OF THIS PROJECT.7.STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY WAY WITHOUTTHE STRUCTURAL ENGINEERS REVIEW AND PRIOR WRITTEN APPROVAL.8.PROVIDE FIRE STOPPING WHERE PIPES PENETRATE FIRE RATED FLOORS AND WALLS. FIRESTOPPING MATERIALS AND METHODS SHALL BE PER LOCAL AND STATE CODES ANDREQUIREMENTS.9.ALL PLUMBING SYSTEMS SHALL BE INSTALLED PER THE CURRENT PLUMBING CODE FOR THELOCATION OF THE WORK BEING INSTALLED.10.ALL PLUMBING EQUIPMENT, PIPING, FIXTURES, AND PIPE ACCESSORIES SHALL BE NSF 61,ANNEX G COMPLIANT.11.ALL PIPING LOCATED WITHIN A RETURN AIR PLENUM SHALL COMPLY WITH A 25/50 FLAMESMOKE RATING. ANY EXISTING PIPING DISCOVERED WITHIN A RETURN AIR PLENUM THATDOES NOT COMPLY WITH THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT FOR FURTHER CLARIFICATION.12.DO NOT ATTACH ANY CONSTRUCTION TO THE ROOF DECK JOIST BRIDGING, JOIST CROSSBRACING, PIPING, CONDUIT, DUCTWORK OR ANY OTHER NON-STRUCTURAL ITEM.13. DO NOT WELD OR DRILL INTO STRUCTURAL STEEL OR JOIST; INSTEAD USE CLAMPS, TIE WIRE, THRU-BOLTS WITH WASHERS14.DO NOT USE ANY PVC, PLASTIC, ETC. IN PLENUM OR DEMISING WALLS UNLESS FIRE WRAPPED.ALL WOOD BLOCKING AND NAILERS, CONCEALED OR NOT SHALL BE FIRE RETARDATTREATED.15.PIPING BELOW GROUND SHALL BE SERVICE-WEIGHT CAST IRON. NO-HUB PIPING OR FERNCO CONNECTIONS ARE NOT PERMITTED BELOW GRADE.16.DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE "L" WATER TUBE.17.ALL PIPING SHALL BE PROPERLY SUSPENDED BY THE STRUCTURE PER THE LOCAL CODES.18.ALL PIPING INSULATED SHALL BE WITH PLENUM RATED MATERIALS.19.FLOOR DRAINS SHALL BE PROVIDED WITH TRAP PRIMERS.20.ALL SHUT-DOWN OF UTILITIES AND FIRE PROTECTION SYSTEMS SHALL BE ARRANGED WITH NOLESS THAN SEVEN (7) DAYS NOTICE TO THE BUILDING OWNER. WORK MAY NOT COMMENCE UNLESS WRITTEN APPROVAL IS PROVIDED BY THE LANDLORD.21.ALL DOMESTIC WATER BRANCH PIPES SERVING FIXTURES OR EQUIPMENT WITH FAST ACTINGOR ELECTRONIC VALVES SHALL BE PROVIDED WATER HAMMER ARRESTORS.22.ALL BRANCH PIPES FROM DOMESTIC WATER MAINS SHALL BE PROVIDED QUARTER TURN FULLPORT BALL VALVES ON THE BRANCH PIPE JUST ADJACENT TO THE MAIN.PLUMBING GENERAL NOTES2" V1 1/2" V2" S3" S3" SSK-1EEW-12" S2" S3" S2" S3" S2" S1 1/2" V2" S1 1/2" V1 1/2" VSK-1EEW-1TMV-13/4" DHW1/2" DHW1/2" DCW1/2" DHW1/2" DCW1/2" DHW1/2" DCW3/4" DHWR3/4" DCW1/2" DHW1/2" DCW1" DCW3/4" DHWR1/2" DHW1/2" DCW1/2" DHW1/2" DCWTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:11:24 PMLower Level PlumbingPlanP2-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Lower Level Plumbing PlanPLAN NOTES1.REPLACE EXISTING FAUCET WITH NEW FAUCET SIMILAR TO SPEAKMAN SEF-1800-CA-TW. SET MIXING VALVE TEMPERATUREPER OWNERS REQUIREMENT. PROVIDE ALL MATERIALS AND ACCESSORIES IN ORDER TO CREATE A COMPLETE ANDOPERATIONAL INSTALLATION. ADJUST SUPPLY STOPS TO ENSURE THAT WHEN THE EYE WASH IS ACTIVATED, THE WATERDOES NOT EXTEND OUT OF FIXTURE BOWL.2.1/2"H&CW DROP TO SCRUB SINK (SK-1), 2"W DN, 1-1/2"V RISE3.3/4"H&CW DROP TO TMV-1, MOUNT TMV-1 JUST BELOW THE CEILING AND SET WATER TEMPERATURE AS REQUIRED BY OWNER.INSTALLATION OF TMV SHALL BE PER THE MANUFACTURES REQUIREMENTS. PROVIDE ALL MATERIALS AND ACCESSORIESIN ORDER TO CREATE A COMPLETE AND OPERATIONAL INSTALLATION.4.INSTALL EEW-1, INSTALLATION SHALL BE PER MANUFACTURES REQUIREMENTS. ROUTE DRAIN FROM EYE WASH THROUGHWALL AND CONNECT TO W PIPE SERVING SCRUB SINK5.INSTALL SHEET METEL DRAIN PAN UNDER WASTE PIPE. PROVIDE DRAIN OUT OF DRAIN PAN AND ROUTE DIRECTLY OUT OFSUITE.6.DRAIN PAN DRAIN, COORDIANTE WITH THE OWNER THE EXACT LOCATION OF THE DRAIN. TERMINATE JUST ABOVE CEILING2SANITARY RISER DIAGRAM3DOMESTIC WATER RISER DIAGRAMREV. DATE
ALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECTTSENSOR (T=TEMP H=HUMIDITY)(P=PRES V=VAC T=TEMP) GAUGETHERMOMETERPRESSURE AND TEMPERATURE PLUGWATER PRESSUREREDUCING/REGULATING VALVEAUTOMATIC AIR VENTMANUAL AIR VENTFLOOR DRAINFLOW METERCLEANOUTTEMPERATURE CONTROL 3-WAY2-POSITION VALVEMECHANICAL VALVEAND FITTING SYMBOLSDESCRIPTIONSYMBOLTEMPERATURE CONTROL 2-WAY MODULATING VALVETEMPERATURE CONTROL 2-WAY 2-POSITION VALVETEMPERATURE CONTROL3-WAY MODULATING VALVECALIBRATED BALANCING VALVEPIPING FLEXIBLE CONNECTIONPIPE TURNED UP (UNLESS NOTED OTHERWISE)PIPE TURNED DOWNPIPE OUT TOPPIPE OUT BOTTOMTHREADED/FLANGED CAPCONCENTRIC REDUCERECCENTRIC REDUCERCHECK VALVEUNIONSTRAINERSAFETY RELIEF VALVEBUTTERFLY VALVEBALL VALVEGATE VALVEPLAN VIEWDETAIL VIEWR OR DFDSDF/SDMDDESCRIPTIONSYMBOLDESCRIPTIONMECHANICAL DUCTWORK SYMBOLSSYMBOLWITH FLEX DUCTSECTIONPLAN VIEWSTANDARD RADIUS ELBOW WITH CENTER RADIUS EQUAL TO 1-1/2 TIMES WIDTH OF DUCT UNLESS OTHERWISE INDICATEDFLAT OVAL SPIRAL DUCT (FIRST DIMENSION, SIDE SHOWN)RECTANGULAR DUCT (FIRST DIMENSION, SIDE SHOWN)SPIN-IN FITTING WITH MANUAL VOLUME DAMPER ANDFLEXIBLE DUCT CONNECTIONTYPICAL TERMINAL UNIT WITH REHEAT COILGRILLE/REGISTER/DIFFUSER CONNECTIONSIDEWALL SUPPLY, RETURN OREXHAUST GRILLEDIFFUSER (NO AIRFLOW IN SHADED DIRECTION)INSULATED METAL PANEL45 DEGREE LATERAL (ROUND OR FLAT OVAL ONLY)90 DEGREE TEE (ROUND OR FLAT OVAL ONLY)SQUARE-TO-ROUND TRANSITIONCONICAL FITTINGROUND SPIRAL DUCT90 DEGREE ELBOW WITH TURNING VANESFLEXIBLE CONNECTIONBEVELED ENTRY FITTINGMANUAL VOLUME DAMPERFIRE DAMPER WITH ACCESS DOORSMOKE DAMPER WITH ACCESS DOORFIRE/SMOKE DAMPER WITH ACCESS DOORDUCT TURNED UP (SOLID LINES)DUCT TURNED DOWN (DASHED LINES)R(RISE), D(DROP) SUPPLY DIFFUSER OR SUPPLY GRILLERETURN GRILLEEXHAUST GRILLESUPPLY, RETURN, OR EXHAUSTSLOT DIFFUSERW" X H"DIA"øAUTOMATIC MOTOR OPERATED DAMPERW "X H"øDIA"øW" X H"CDCPDCHWRCRCSCHWSHWSHWRDIRECTION OF PIPE SLOPE (DOWN)CONDENSATE & EQUIPMENT DRAINCONDENSATE PUMP DISCHARGECONDENSER WATER RETURNCONDENSER WATER SUPPLYCHILLED WATER RETURNCHILLED WATER SUPPLYHEATING WATER RETURNHEATING WATER SUPPLYHVAC PIPING SYMBOLSLINE SYMBOLSSCREENED LINES INDICATE EXISTING TO REMAINHEAVY CONTINUOUS LINES INDICATE NEW WORKHEAVY DASHED LINES INDICATE EXISTING TO BE REMOVEDADACCESS DOORذFA/EACCACCUADADJAFCVAFFAFMSAGAAHUALANSIAOAPAPDARIASASHRAEASMEASPEASTMATMAUTOAWWABBCUBDBDDBHPBIBODBOPBTUHCACAPCAVCBCDCO2CFMCHCHWPCHWRCHWSCOCOMPCONDCONVCPCPDCRCSCTCUHCWPdBDDDDCDEGDIADISCDWHDWVDXEAEATECECGEDREEREFEFFEFTEGEMGEOMESPETEWTEXHFF&TFCOFCUFDFMFPBFPMFPSPHASEDEGREES FAHRENHEITARCHITECT/ENGINEERAIR COOLED CONDENSERAIR COOLED CONDENSING UNITAREA DRAIN, ACCESS DOORADJUSTABLE, ADJACENTAIRFLOW CONTROL VALVEABOVE FINISHED FLOORAIRFLOW MEASURING STATIONAMERICAN GAS ASSOCIATIONAIR HANDLING UNITALUMINUMAMERICAN NATIONAL STANDARDS INSTITUTEANALOG OUTPUTACID PROOF, ACCESS PANELAIR PRESSURE DROP (IN. WC)AIR CONDITIONING REFRIGERATION INSTITUTEAIR SEPARATORAMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING ENGINEERSAMERICAN SOCIETY OF MECHANICAL ENGINEERSAMERICAN SOCIETY OF PLUMBING ENGINEERSAMERICAN SOCIETY FOR TESTING AND MATERIALSATMOSPHEREAUTOMATICAMERICAN WATER WORKS ASSOCIATIONBOILERBLOWER COIL UNITBALANCE DAMPERBACK-DRAFT DAMPERBRAKE HORSEPOWER OR BOILER HORSEPOWERBINARY INPUT, BACKWARD INCLINEDBOTTOM OF DUCTBOTTOM OF PIPEBRITISH THERMAL UNITS PER HOURCOMPRESSED AIRCAPACITYCONSTANT AIR VOLUMECATCH BASIN OR CHILLED BEAMCONDENSATE DRAINCARBON DIOXIDECUBIC FEET PER MINUTECHILLERCHILLED WATER PUMPCHILLED WATER RETURNCHILLED WATER SUPPLYCLEANOUTCOMPRESSORCONDENSERCONVECTORCONDENSATE PUMPCONDENSATE PUMP DISCHARGECONDENSER WATER RETURNCONDENSER WATER SUPPLYCOOLING TOWERCABINET UNIT HEATERCONDENSER WATER PUMPDECIBELDUAL DUCTDIRECT DIGITAL CONTROLDEGREE (°F)DIAMETERDISCONNECT SWITCHDOMESTIC WATER HEATERDRAIN, WASTE, AND VENTDIRECT EXPANSIONEXHAUST AIRENTERING AIR TEMPERATURE (°F)ELECTRICAL CONTRACTOREGG-CRATE GRILLEEQUIVALENT DIRECT RADIATIONENERGY EFFICIENCY RATIOEXHAUST FANEFFICIENCYENTERING FLUID TEMPERATURE (°F)EXHAUST GRILLEEXTRUDED METAL GRILLE (WELDED WIRE MESH)END OF MAIN DRIPEXTERNAL STATIC PRESSURE (IN. WC.)EXPANSION TANKENTERING WATER TEMPERATURE (°F)EXHAUSTFURNACEFLOAT AND THERMOSTATIC STEAM TRAPFLOOR CLEANOUTFAN COIL UNITFLOOR DRAINFACTORY MUTUALFAN POWERED TERMINAL UNITFEET PER MINUTEFEET PER SECONDABBREVIATIONS AND TERMSFLOOR SINKFIRE/SMOKE DAMPERFINNED TUBE RADIATIONGAGE OR GUAGEGALLONGENERAL CONTRACTORGALLONS PER DAYGALLONS PER HOURGALLONS PER MINUTEHEAD (FT.)HORSEPOWERHIGH PRESSURE STEAM RETURNHIGH PRESSURE STEAM SUPPLYHOT WATER PUMPHEATING WATER RETURNHEATING WATER SUPPLYHEAT EXCHANGERINTEGRAL FACE/BYPASSLEAVING AIR TEMPERATURE (°F)LOW PRESSURE STEAM RETURNLOW PRESSURE STEAM SUPPLYLEAVING WATER TEMPERATURE (°F)MIXED AIRMIXED AIR TEMPERATURE (°F)THOUSAND BTU PER HOURMECHANICAL CONTRACTORMINIMUM CIRCUIT AMPACITYMOTOR CONTROL CENTERMOTORIZED DAMPERMEDIUM PRESSURE STEAM RETURNMEDIUM PRESSURE STEAM SUPPLYNOISE CRITERIA, NORMALLY CLOSEDNATIONAL ELECTRIC CODENATIONAL FIRE CODENATIONAL FIRE PROTECTION ASSOCIATIONNOT IN CONTRACTNORMALLY OPENNOT TO SCALEOUTSIDE AIROUTSIDE AIR TEMPERATURE (°F)OPPOSED BLADE DAMPEROUTSIDE DIAMETEROWNER FURNISHED/CONTRACTOR INSTALLEDPUMPPLUMBING CONTRACTORPRESSURE DROPPRE-FILTERPROPYLENE GLYCOL WATERPREHEAT COILPARTS PER MILLIONPRESSURE REDUCING VALVEPOUNDS PER SQUARE INCHPOUNDS PER SQUARE INCH (ABSOLUTE)POUNDS PER SQUARE INCH (GAUGE)PACKAGED TERMINAL AIR CONDITIONERRETURN AIRRETURN AIR TEMPERATURE (°F)RETURN FANRETURN GRILLERELATIVE HUMIDITYREHEAT COILRADIANT PANELROOFTOP UNITSUPPLY AIRSUPPLY AIR TEMPERATURE (°F)SUPPLY DIFFUSERSEASONAL ENERGY EFFICIENCY RATIOSUPPLY GRILLESHEETMETAL AND AIR CONDITIONING CONTRACTORS ASSOCIATIONSTATIC PRESSURESUPPLY REGISTERSAFETY RELIEF VALVESTEAM VENTTHERMOSTATTEMPERATURE CONTROL CONTRACTORTEMPERATURE DIFFERENCETOTAL STATIC PRESSURETHERMAL EXPANSION VALVETYPICALUNIT HEATERUNDERWRITER'S LABORATORIESVARIABLE AIR VOLUMEVOLUME DAMPERVARIABLE FREQUENCY CONTROLLER (SAME AS VFD, VSC)VARIABLE FREQUENCY DRIVE (SAME AS VFC, VSC)VARIABLE SPEED CONTROLLER (SAME AS VFC, VFD)WITHWITHOUTWET BULB TEMPERATURE (°F)WATER PRESSURE DROP (FT. HD)WATER SOURCE HEAT PUMPFSFSDFTRGAGALGCGPDGPHGPMHDHPHPRHPSHWPHWRHWSHXIFBLATLPRLPSLWTMAMATMBHMCMCAMCCMDMPRMPSNCNECNFCNFPANICNONTSOAOATOBDODOF/CIPPCPDPFPGWPHCPPMPRVPSIPSIAPSIGPTACRARATRFRGRHRHCRPRTUSASATSDSEERSGSMACNASPSRSRVSVTTCCTDTSPTXVTYPUHULVAVVDVFCVFDVSCW/W/OWBWPDWSHPGENERAL MECHANICAL DEMOLITION NOTESA. CONTRACTOR TO FIELD VERIFY EXISTING DUCTWORK LOCATION, SIZE, AND ELEVATION PRIOR TO REMOVAL. COORDINATE ANTICIPATED ROUTING WITH EXISTING AND NEW DUCTWORK, PIPING, AND CONDUITS. CONTACT ENGINEER IF FIELD CONDITIONS REQUIRE ALTERNATIVE ROUTING. VERIFY THAT ALL SERVICES TO BE REMOVED DO NOT SERVE AREAS OUTSIDE INDICATED SCOPE OF WORK.B. PIPE AND DUCT ROUTINGS AND CLEARANCES INDICATED ARE BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL VERIFY PIPING, DUCTWORK, ELECTRICAL, AND STRUCTURAL DETAILS OF EXISTING AND NEW INSTALLATIONS DURING AND AFTER DEMOLITION (PRIOR TO NEW INSTALLATIONS) TO DETERMINE WORK NECESSARY TO INSTALL WORK AS SHOWN AND INTENDED. CONTRACTOR SHALL CONTACT THE ENGINEER WITH ANY CONCERNS UPON COMPLETION OF THIS EFFORT.C. COORDINATE OUTAGES WITH OTHER CONTRACTORS, OWNER, AND MAINTENANCE STAFF. PROVIDE SUFFICIENT ADVANCE SCHEDULING TO MEET OCCUPANTS AND FACILITY PERSONNELS REQUIREMENTS FOR PLANNING AND COORDINATING FOR SYSTEMS WHICH MAY NOT BE EASILY INTERRUPTED.D. WHERE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION WORK IS DETERMINED TO PENETRATE EXISTING FLOORS, WALLS, CEILING, OR ROOF, THE OPENING THROUGH WHICH THE ABOVE DESCRIBED ITEM IS TO PASS MUST BE REPAIRED OR BUILT BACK BY THE CONSTRUCTION TRADE SKILLED IN THE WORK TO BE PERFORMED. SUBCONTRACTOR SHALL BE RESPONSIBLE FOR PROCURRING THE SERVICES OF SKILLED CONTRACTOR.E. PROVIDE TEMPORARY PATCHING AS REQUIRED FOR INFECTION CONTROL AS DETERMINED BY HOSPITAL INFECTION CONTROL DEPARTMENT AND MAINTAIN EXISTING FIRE AND SMOKE RATINGS.F. WHERE PRE-DEMOLITION AIRFLOW READINGS ARE NOTED, TAKE READINGS PRIOR TO BEGINNING ANY DEMOLITION WORK OR CONSTRUCTING NEGATIVE AIR PRESSURE BARRIERS. PRE-DEMOLITION TAB WORK WILL LIKELY OCCUR AFTER NORMAL HOURS, CONFIRM WITH OWNER.G. ALL DUCTWORK, PIPING, AND EQUIPMENT INDICATED BY DASHED LINETYPE SHALL BE REMOVED AS DESCRIBED BY PLAN NOTES. REMOVE OR REUSE ASSOCIATED HANGERS. DO NOT LEAVE UNUSED EQUIPMENT ABANDONED ABOVE CEILING. ALL TERMINAL UNITS TO BE REMOVED SHALL ALSO HAVE SUPPLY DUCTS REMOVED BACK TO MAIN DUCTS AS INDICATED AND CAP SUITABLE FOR +4" W.G. REMOVE PIPING RUNOUTS BACK TO MAIN AND CAP. FOR PIPING RUNOUTS THAT ARE TO BE REUSED, REMOVE ALL CONTROL VALVES, BALANCE VALVES, STRAINERS , AND PIPING ACCESSORIES TO BRANCH SHUT-OFF VALVES. ALL EXISTING TERMINAL UNITS, DDC CONTROLLERS, ROOM PRESSURE MONITORS, AND HARDWARE TO BE REMOVED SHALL BE DONE SO IN A MANNER TO MINIMIZE DAMAGE AND OFFERED TO THE OWNER. CONTRACTOR SHALL DISCARD ALL DEVICES NOT WISHED TO BE RETAINED BY THE OWNER.GENERAL MECHANICAL NOTESA. CONTRACTOR TO INSTALL ACCESS PANELS AT ALL FIRE DAMPERS. REFER TO DETAILS AND SPECIFICATIONS FOR MINIMUM ACCESS PANEL SIZES. COORDINATE LOCATIONS TO ENSURE ACCESS PANELS ARE NOT OBSTRUCTED.B. REFER TO SCHEDULES FOR DIFFUSER AND TERMINAL UNIT RUNOUT SIZES.C. UNLESS NOTED OTHERWISE, TERMINAL UNIT DISCHARGE DUCT SHALL BE THE SAME SIZE AS THE TERMINAL UNIT DISCHARGE CONNECTION.D. LOCATE ALL TERMINAL UNITS, DAMPERS, VALVES, AND EQUIPMENT REQUIRING ACCESS IN AN UNOBSTRUCTED LOCATION ABOVE LAY-IN CEILING. COORDINATE THE INSTALLATION OF A CEILING ACCESS PANEL WITH GENERAL CONTRACTOR.E. FIELD VERIFY LOCATION OF ALL FLOOR PENETRATIONS PRIOR TO CUTTING TO ASSURE THAT NO FLOOR PENETRATION CONFLICTS WITH EXISTING BEAMS OR JOISTS. FLOOR PENETRATIONS SHALL BE ONLY THROUGH THE SLAB. DO NOT CUT THROUG BEAMS OR JOISTS. NOTIFY ARCHITECT AND ENGINEER FOR ANY REQUIRED MODIFICATIONS PRIOR TO CUTTING. F. REFER TO TERMINAL UNIT SCHEDULE FOR PIPE RUNOUT SIZES. G. MINIMUM PIPE SIZE SHALL NOT BE LESS THAN 3/4".H. ALL NEW AIR-HANDLING SYSTEMS AND ASSOCIATED DISTRIBUTION SHALL COMPLY WITH NFPA-90A.I. ALL DUCTWORK AND PIPE INSULATION SHALL BE INSTALLED CONTINUOUSLY THROUGH WALLS. OPENINGS SHALL BE FRAMED LARGE ENOUGH TO ACCOMMODATE INSULATED PIPE/DUCT. ALLOW ENOUGH ANNULAR SPACE FOR PROPER SEALANT. NON-RATED WALLS SHALL HAVE NON-COMBUSTIBLE SEALANT. RATED BARRIERS SHALL HAVE A UL-LISTED FIRESTOPPING ASSEMBLY. INSTALL FIRESTOPPING ASSEMBLY IN COMPLIANCE WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND IN COMPLIANCE WITH UL-LISTED ASSEMBLY.Architecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:06 PMMechanical Symbols andAbbreviationsM0-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForREV. DATE
COOLING COILTSUPPLY FANVFCTΔPAI-4SDTO FAN STARTERTO F/A SYSTEMCHWRCHWSHAI-6TAI-5SEQUENCE OF OPERATION(ALL SETPOINTS, TIMERS, AND SCHEDULES SHALL BE ADJUSTABLE)1.UNIT SHALL OPERATE CONTINUOUSLY TO PROVIDE POSITIVE PRESSURIZATION AND TEMPERATURE CONTROL TO PHARMACY COMPOUNDING AND ANTE ROOMS2. BLOWER COIL –COOLING COIL2.1COOLING COIL CONTROL VALVE SHALL MODULATE TO SATISFY THE CRITICAL SPACE TEMPERATURE SETPOINT. THE CRITICAL SPACE SHALL BE THE SPACE THAT HAS THE GREATEST CALL FOR COOLING. BAS SHALL POLL THE SENSORS AND RESPOND TO VARYING CONDITIONS TO DETERMINE THE CRITICAL SPACE.2.2IF A SPACE HUMIDITY SENSOR IS ABOVE SETPOINT (INITIALLY SET FOR 60% RH) THE COOLING COIL SHALL MODULATE TO LOWER THE HUMIDITY TO 5% BELOW SETPOINT.2.3WHEN ALL SPACE HUMIDITY SENSORS ARE BELOW SETPOINT, THE CRITICAL SPACE TEMPERATURE SENSOR SHALL AGAIN CONTROL THE COOLING COIL.2.4A HIGH LEVEL WATER SENSOR IN THE COOLING COIL CONDENSATE PAN SHALL GENERATE AN ALARM IF THE WATER LEVEL IS ABOVE THE NORMAL OPERATING LEVEL AND CLOSE THE CHILLED WATER VALVE. FAN SHALL CONTINUE TO OPERATE.3.BLOWER COIL –FAN OPERATION3.1FAN SHALL VARY SPEED TO MAINTAIN ONE TERMINAL UNIT AT 95% OPEN.3.2THE DISCHARGE AIR PRESSURE SHALL BE DETERMINED DURING TEST AND BALANCE. WHENEVER THE SUPPLY AIR PRESSURE IS 1.0” ABOVE THE TAB MEASURED PRESSURE, AN ALARM SHALL BE GENERATED AND THE FAN SPEED LIMITED TO NOT EXCEED THAT PRESSURE.3.3GENERATE AN ALARM ON LOSS OF STATUS.3.4A SMOKE DETECTOR IN THE SUPPLY AIR DUCT SHALL SEND AN ALARM TO THE FIRE ALARM SYSTEM AND SHUT FAN DOWN IF INITIATED.4.TERMINAL UNITS 4.1TERMINAL UNITS SHALL RESPOND TO FILTER LOADING AND MODULATE DAMPER TO MAINTAIN A CONSTANT DESIGN AIRFLOW.4.2REHEAT COIL SHALL MODULATE OPEN WHEN SPACE TEMPERATURE IS BELOW ROOM TEMPERATURE SETPOINT.4.3AIRFLOW CONTROL VALVES SHALL MODULATE MOTORIZED DAMPER TO TRACK THE SUPPLY AIR TERMINAL (SERVING THE SAME SPACE) TO MAINTAIN AN AIRFLOW EQUAL TO THE SUPPLY AIRFLOW MINUS AN OFFSET. OFFSET SHALL BE DETERMINED DURING TEST AND BALANCE AS REQUIRED TO MAINTAIN DIFFERENTIAL PRESSURE REQUIREMENTS OF EACH SPACE.5.SUPPLY AIRFLOW CONTROL VALVE5.1SUPPLY AIRFLOW CONTROL VALVE RESPOND TO CHANGES IN THE SUPPLY AIR PRESSURE AND MODULATE DAMPER TO MAINTAIN A CONSTANT DESIGN AIRFLOW.5.2AHU-PH RETURN DAMPER SHALL BE OPEN DURING NORMAL OPERATION AND AHU-PH BYPASS DAMPER SHALL BE NORMALLY CLOSED.5.3ON A LOSS OF FAN STATUS FOR AHU-PH, AHU-PH RETURN DAMPER SHALL CLOSE AND AHU-PH BYPASS DAMPER SHALL OPEN TO ALLOW FOR PARTIAL TEMPERATURE AND PRESSURE CONTROL DUE TO LOSS OF AHU-PH.6.EXHAUST FAN6.1EXHAUST FAN EF-15 SHALL MAINTAIN A CONSTANT SPEED AS DETERMINED DURING TEST AND BALANCE.6.2AIRFLOW MEASURING STATION IS SUPERVISORY. GENERATE AN ALARM IF THE AIRFLOW VARIES BY MORE THAN 20% OF THE DESIGN AIRFLOW.6.3A HIGH NEGATIVE STATIC PRESSURE SENSOR SHALL ALARM IF EXHAUST FAN INLET PRESSURE IS 1” HIGHER THAN INITIAL OPERATING PRESSURE.PRIMARY SUPPLY FROM PRIMARY AIR HANDLERAMSSUPPLY AIRFLOW CONTROL VALVEMDHWRHWSAI-1AO-1BI-1AO-3480V/3PHWSBI-2AI-2AI-3AO-2ΔP24V FROM BASLAN TO BAS1AMSTU-C025MDTAI-8AO-4AI-7AO-5AMSTU-C025FMDTAI-10AO-6AI-9AO-7AMSTU-CO25BMDTAI-12AO-8AI-11AO-9ΔP24V FROM BASLAN TO BAS1ΔPLAN TO BAS124V FROM BAS(-)(+)(-)(+)(+)(-)ANTEROOMC025CHAZARD BUFFERC025BNON-HAZARD BUFFERC025FHWRHWSHWRHWSEF-15VSCAO-10480V/3PHAI-19BO-1TAI-13HAI-14TAI-15HAI-16TAI-17HAI-18AMSAI-20ΔPFDMVD2SDTO FAN STARTERTO F/A SYSTEMBI-3PHARMACY BIO-SAFETY CABINETΔPBI-43ΔPBI-53ΔPBI-63MDBO-2MDBO-3HARDWIRE TO AHU-PH COOLING COIL VALVE.LAN TO BAS4BO-4LAN TO BAS4AFCV-C025FMDAO-11AMSAI-21AFCV-C025CMDAO-12AMSAI-22TC24V FROM BASLAN TO BAS5CSCSPRE-FILTERΔPAI-2366SEQUENCE OF OPERATION:(ALL SETPOINTS, TIMERS, AND SCHEDULES SHALL BE ADJUSTABLE)1.OCCUPIED MODE1.1TERMINAL UNIT CONTROLLER SHALL RESPOND TO CHANGES IN SPACE TEMPERATURE AND VARIATIONS IN SYSTEM STATIC PRESSURE TO MODULATE SUPPLY AIR VOLUME FROM SCHEDULED MINIMUM TO MAXIMUM WHILE MODULATING REHEAT COIL WHEN THE TERMINAL UNIT IS AT THE MINIMUM AIRFLOW SETPOINT. WHEN A DISCHARGE AIR TEMPERATURE OF 85°F IS REACHED, THE AIR VOLUME SHALL BE GRADUALLY INCREASED TO SATISFY HEATING SETPOINT WHILE MAINTAINING A DISCHARGE AIR TEMPERATURE OF 85°F. THERE SHALL BE SEPARATE ADJUSTABLE SETPOINTS FOR COOLING MINIMUM AIRFLOW, HEATING MINIMUM AIRFLOW, COOLING MAXIMUM AIRFLOW, HEATING MAXIMUM AIRFLOW, AND HEATING DISCHARGE TEMPERATURE.PRIMARY SUPPLY FROM RTUCONTROL PANELLAN TO NETWORK CONTROLLERAMSMDT24VTOCCC02DISCONNECT BY VAV MANUFACTURERSPACE TEMPERATURE SENSOR WITH +/-4°F FROM SETPOINT ADJUSTMENTOCCUPANCY SENSOR BY DIVISION 26 CONTRACTOR WITH AUXILIARY CONTACTS. CONTROLS CONTRACTOR TO TIE INTO BAS SYSTEM.WHERE INDICATED ON PLANSVAV AIR TERMINAL UNITHWRHWSArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:08 PMTemperature ControlSchematicsM0-211700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForNOT TO SCALE1PHARMACY TEMPERATURE CONTROL SCHEMATICPOINT LISTAI-1 SUPPLY AIRFLOW CONTROL VALVE AIRFLOW READING (CFM)AI-2 BLOWER COIL MIXED AIR TEMPERATUREAI-3 COOLING COIL LEAVING AIR TEMPERATUREAI-4 BLOWER COIL DISCHARGE STATIC PRESSUREAI-5 BLOWER COIL SUPPLY AIR TEMPERATUREAI-6 BLOWER COIL SUPPLY AIR HUMIDITYAI-7 TU-C025C AIRFLOW READING (CFM)AI-8 TU-C025C DISCHARGE AIR TEMPERATUREAI-9 TU-C025F AIRFLOW READING (CFM)AI-10 TU-C025F DISCHARGE AIR TEMPERATUREAI-11 TU-C025B AIRFLOW READING (CFM)AI-12 TU-C025B DISCHARGE AIR TEMPERATUREAI-13 ANTEROOM C025C SPACE TEMPERATUREAI-14 ANTEROOM C025C SPACE HUMIDITYAI-15 NON-HAZARD BUFFER C025F SPACE TEMPERATUREAI-16 NON-HAZARD BUFFER C025F SPACE HUMIDITYAI-17 HAZARD C025B SPACE TEMPERATUREAI-18 HAZARD BUFFER C025B SPACE HUMIDITYAI-19 EXHAUST FAN EF-15 INLET STATIC PRESSUREAI-20 EXHAUST FAN EF-15 AIRFLOW (CFM)AI-21 AFCV-C025F AIRFLOW READING (CFM)AI-22 AFCV-C025C AIRFLOW READING (CFM)AI-23 BLOWER COIL MIXED AIR TEMPERATUREAO-1 SUPPLY AIRFLOW CONTROL VALVE MOTORIZED DAMPERAO-2 BLOWER COIL COOLING COIL CONTROL VALVEAO-3 BLOWER COIL SUPPLY FAN SPEEDAO-4 TU-C025C MOTORIZED DAMPERAO-5 TU-C025C REHEAT COIL VALVEAO-6 TU-C025F MOTORIZED DAMPERAO-7 TU-C025F REHEAT COIL VALVEAO-8 TU-C025B MOTORIZED DAMPERAO-9 TU-C025B REHEAT COIL VALVEAO-10 EXHAUST FAN EF-15 SPEEDAO-11 AFCV-C025F MOTORIZED DAMPERAO-12 AFCV-C025C MOTORIZED DAMPERBI-1 BLOWER COIL FAN STATUSBI-2 BLOWER COIL HIGH WATER LEVELBI-3 EXHAUST FAN EF-15 STATUSBI-4 HEPA FILTER DIFFUSER PRESSURE DROP ALARM - ROOM C025CBI-5 HEPA FILTER DIFFUSER PRESSURE DROP ALARM - ROOM C025FBI-6 HEPA FILTER DIFFUSER PRESSURE DROP ALARM - ROOM C025BBO-1 EXHAUST FAN EF-15 VSC ENABLE/DISABLEBO-2 AHU-PH BYPASS DAMPERBO-3 AHU-PH RETURN DAMPERBO-4 SUPPLY VFC ENABLE/DISABLESCHEMATIC NOTES1 NEW DIFFERENTIAL PRESSURE SENSORS. GENERATE AN ALARM WHEN ROOMS C025F OR C025C ARELESS THAN +0.02" DIFFERENTIAL PRESSURE OR WHEN ROOM C025B IS GREATER (MORE POSITIVE)THAN -0.01" DIFFERENTIAL PRESSURE. PROGRAM A 1 MINUTE DELAY PRIOR TO GENERATING ALARM.UNIT SHALL HAVE BACNET COMMUNICATION. WIRE BACNET COMMUNICATION BACK TO BAS AND MAPIN POINTS AS DIRECTED BY THE OWNER.2 CONTROL PANEL MOUNTED ADJACENT TO SUPPLY TERMINAL UNIT WITH 24V POWER BYTEMPERATURE CONTROL CONTRACTOR3 HEPA DIFFUSERS SHALL BE FACTORY EQUIPPED WITH PORTS FOR MEASURING PRESSURE DROP.INSTALL A DIFFERENTIAL PRESSURE SWITCH ON ONE FILTER FOR EACH TERMINAL UNIT AND SET TOALARM AT 2 X CLEAN FILTER DROP.4 VARIABLE FREQUENCY CONTROLLER SHALL BE EQUIPPED WITH BACNET COMMUNICATION CARD TOTRANSMIT ALL INFORMATION REQUESTED BACK TO BAS. COORDINATE WHICH OF THE AVAILABLEPOINTS ARE TO BE MAPPED BACK TO THE OWS WITH THE OWNER PRIOR TO PROGRAMMING.5 NEW COLOR TOUCHSCREEN MULTI-ROOM DISPLAY. DISPLAY SHALL BE PROGRAMMED TO DISPLAYTHE ROOM NAME, TEMPERATURE, HUMIDITY, AND DIFFERENTIAL PRESSURE FOR THE ANTEROOM,HAZARD BUFFER, AND NON-HAZARD BUFFER ROOM. SIMILAR TO LOYTEC L-VIS-07.6 PROVIDE WEATHERPROOF ENCLOSURE ON ALL DEVICES INSTALLED OUTSIDE.NOT TO SCALE2VAV (AND CAV) TERMINAL UNIT TEMPERATURE CONTROL SCHEMATICREV. DATE
REF.AHU-HL344.34.64.74.95678HJKLK.512LOUNGEC026A4554667True NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:10 PMLower Level MechanicalDuctwork DemolitionPlanM1-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Lower Level Mechanical Ductwork Demolition PlanPLAN NOTES1 REMOVE EXISTING BIO-SAFETY CABINET EXHAUST DUCT BACK TO POINT INDICATED.2 REMOVE BIO-SAFETY EXHAUST DUCT AND ASSOCIATED FIRE DAMPER BACK TO SHAFTPENETRATION. CAP AND ABANDON EXHAUST DUCT RISER WITHIN SHAFT. REBUILD SHAFTPENETRATION BACK TO MAINTAIN FIRE RATING OF SHAFT.4 REMOVE EXISTING TERMINAL UNIT AND ASSOCIATED DUCTWORK AS INDICATED.5 REMOVE EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK BACK TO MAIN. CAP ANDSEAL MAIN DUCT CONNECTION.6 REMOVE AND RELOCATE EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK ASREQUIRED FOR NEW WORK.7 REMOVE AND RELOCATE EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK AS REQUIREDFOR NEW WORK.REV. DATE
REF.44.34.64.74.95678HJKLK.5AHU-HL3112TU-L2070TU-L2107TU-L2095TU-L2088TU-L2085TU-L2090TU-L20603TΔPTTTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:12 PMLower Level MechanicalPiping Demolition PlanM1-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Lower Level Mechanical Piping Demolition PlanPLAN NOTES1 REMOVE EXISTING TERMINAL UNIT, PIPING, AND ASSOCIATED CONTROLS AS INDICATED. CAP ALL PIPING NOTREUSED IN NEW WORK AT MAIN.2 REMOVE EXISTING LPR AND CPD AS REQUIRED FOR NEW MECHANICAL EQUIPMENT AND DUCTWORKINSTALLATION.3 REMOVE EXISTING MPR AS REQUIRED FOR NEW MECHANICAL EQUIPMENT AND DUCTWORK INSTALLATION.REV. DATE
REF.AHU-HL344.34.64.74.95678HJKLK.5OFFICEC025EPHARMACISTC025PICKSTATIONC025DLOUNGEC026AUNPACKINGC026AHU-PHTU-C025DTU-C025M2-02TU-C025ESD1- 150RG1- 150TU-L20857SD1- 200SD1- 200SD1- 200(TYP. 4)SD3- 410SD3- 410RG2- 210SD2- 210EG1- 130RG4- 600RG4- 600RG5- 79089400 CFM 400 CFM400 CFM400 CFM230 CFM9101010TU-PHVFD-AHUPH11AFCV-C025AM7-13TYPM7-1112ROOM DATAROOMANTEAIR CHANGESMAXIMUMTEMP./ HUMIDITYPRESSURIZATIONNOTES68°F / 60%+0.02" W.C.--30-40HAZARD BUFFERNON-HAZARD BUFFER30-4030-4068°F / 60%68°F / 60%-0.01" to -0.03" W.C.+0.02" W.C.----4.34.64.74.95J1PICKSTATIONC025DTU-C025FTU-C025ATU-C025BHIGH HAZARDBUFFERC025BANTEC025AANTEC025ANON-HAZARDBUFFERC025CHIGH HAZARDBUFFERC025BLFD1- 280(TYP. 4)LFD1- 255(TYP. 4)LFD1- 235(TYP. 2)WRG1- 410LFD1- 215(TYP. 3)23AFCV-C025F4WRG1- 410WRG2- 1,3006M7-21TYPM7-14TYP5M7-17TYPTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:16 PMLower Level MechanicalDuctwork PlanM2-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1LOWER LEVEL MECHANICAL PLANPLAN NOTES1 14"Ø EXHAUST DUCT DOWN TO BIO-SAFETY CABINET. BALANCE TO 850 CFM.2 24"X10" DOWN TO WALL RETURN GRILLE, 8" ABOVE FINISHED FLOOR.3 12"X10" RETURN GRILLE DOWN TO WALL RETURN GRILLE, 8" ABOVE FINISHED FLOOR.4 INSTALL BUBBLE TIGHT LEAK PROOF MANUAL VOLUME DAMPER AT BIO-SAFETY CABINET.5 12"X8" RETURN GRILLE DOWN TO WALL RETURN GRILLE, 8" ABOVE FINISHED FLOOR.6 COORDINATE LOCATION OF ALL TERMINAL UNITS AND AIRFLOW CONTROL VALVES WITHFURNITURE AND CASEWORK IN THIS AREA. LOCATED TERMINAL UNITS AND AIRFLOW CONTROLVALVES SO THEY ARE NOT DIRECTLY OVER FURNITURE AND CAN BE ACCESSED WITH AHOSPITAL CONTAINMENT CART.7 CONNECT NEW 14"Ø TO EXISTING 10"X10" EXHAUST DUCT.8 REBALANCE EXISTING TERMINAL UNIT TO 1,030 CFM MAXIMUM, 450 CFM MINIMUM, AND 1.5 GPM9 RELOCATED SUPPLY DIFFUSER. BALANCE TO AIRFLOW INDICATED.10 BALANCE EXISTING DIFFUSER TO AIRFLOW INDICATED.11 VFD PROVIDED BY DIVISION 23 CONTROLS CONTRACTOR. INSTALLED BY DIVISION 26CONTRACTOR.12 INSTALL NEW SUPERVISORY CONTROL PANEL. COORDINATE FINAL LOCATION WITH ELECTRICALCONTRACTOR. 1/4" = 1'-0"2ENLARGED LOWER LEVEL MECHANICAL PLANREV. DATE
78HJJ.41FD78HJJ.42EF-15EF-1878HJJ.43VFD-EF15778HJJ.45' - 0"EF-15EF-18456AIRFLOW MEASURING STATION89M7-2378GG.3HELECTRICALROOMC602X6LCRSBC16HCRSBC16LCRSBC16LLSDPC1X6LLSDPC16HLSDPC16HESBC1X6LEQDPC16LEQDPC16LLSC16LNRC26LEQC1ATSCRC1ATSLSC1ATSEQC1ATSEQMCCC1ATSEQMCCC26HEQDPC1MECHANICALROOMC60010True NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:17 PMSeventh Floor andPenthouse MechanicalPlansM2-711700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Seventh Floor Mechanical Demolition Plan 1/8" = 1'-0"2Penthouse Roof Mechanical Demolition PlanPLAN NOTES1 EXISTING DUCT UP TO EF-15 TO REMAIN. INSPECT FIRE DAMPER TO ENSURE PROPEROPERATION AND REPLACE FUSIBLE LINK. SEAL ALL DUCTWORK THAT IS ACCESSIBLE.2 REMOVE EXISTING EF-15 AND ASSOCIATED DUCTWORK, POWER, AND CONTROLS COMPLETE.EXISTING CURB MAY REMAIN IF NEW DUCTWORK CAN BE ROUTED THROUGH. REFER TO NEWWORK.3 EXISTING EXHAUST DUCT UP TO EXHAUST FAN ON ROOF.4 CONNECT NEW 14"Ø EXHAUST DUCT TO EXISTING EXHAUST DUCT.5 INSTALL A SPOOL PIECE OF DUCTWORK IN THIS SECTION TO ALLOW FOR FUTURE HEPA FILTER.6 INSTALL A PERMANENT WARNING LABEL ON EXHAUST FAN THAT SAYS "WARNING - BIOSAFETYCABINET EXHAUST" AND PAINT A RED RECTANGLE BENEATH WARNING SIGN. WARNING SIGNSHALL BE RED WITH WHITE LETTERS. LETTERS SHALL BE 1" TALL.7 VFD PROVIDED BY DIVISION 23 CONTROLS CONTRACTOR. INSTALLED BY DIVISION 26CONTRACTOR.8 INSTALL ALL EXTERIOR SENSORS IN A WEATHERTIGHT ENCLOSURE.9 WIRE ALL POINTS BACK TO NEW SUPERVISORY CONTROLLER IN 6TH FLOOR M ECHANICALROOM.10 LOCATION OF NEW SUPERVISORY CONTROL PANEL. COORDINATE LOCATION WITH ELECTRICALCONTRACTOR. 1/8" = 1'-0"3Seventh Floor Mechanical Plan 1/8" = 1'-0"4Penthouse Roof Mechanical PlanREV. DATE 1/8" = 1'-0"5Sixth Floor Mechanical Plan
REF.THTHΔPΔPTU-C025ATU-C025FTU-C025E2AHU-PH1" CD31 1/4" HWS1 1/4" HWR44.34.64.74.95678HJKLK.5OFFICEC025EPHARMACISTC025PICKSTATIONC025DANTEC025ANON-HAZARDBUFFERC025CHIGH HAZARDBUFFERC025BUNPACKINGC026LOUNGEC026ASTAFF TOILETC026BBED STORAGEC030CORRIDORC0C03CORRIDORC0C01LINENC027OFFICEC029CORRIDORC0C04TRASHC028ELEVATORELEV 8ELEVATORELEV 9CORRIDORC0C05ELEVATORLOBBYC0C06CORRIDORC0C02MECHANICALROOMC031ELECTRICALROOMC032CORRIDORC0C10CORRIDORC0C09THΔP11TU-C025TU-C025DTTTTTU-C025B3" HWS1" HWRTU-L20852" CHWS2" CHWRTU-L2107AFCV-C025AAFCV-C025F2TU-PH2222TC561" CD7VFD-AHUPH98M7-22M7-121" HWR1" HWSM7-15TYPTrue NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:00:20 PMLower Level MechanicalPiping PlanM3-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForPLAN NOTES1 TOUCHSCREEN PRESSURE MONITOR WITH 4" COLOR TOUCHSCREEN DISPLAY. DISPLAY SHALL BECOLOR CODED TO FOR VISUAL INDICATION OF ALARM. DISPLAY ROOM PRESSURE, TEMPERATURE, ANDHUMIIDITY. SIMILAR TO CRC-PM.2 MONITOR REFRIGERATOR THROUGH BUILDING AUTOMATION SYSTEM.3 CONNECT NEW 2" CHWS&R TO EXISING 10" CHWS&R. INSTALL NEW SHUT-OFF VALVES AND CAPS TOALLOW FOR FUTURE CONNECTION WITHOUT SHUTTING DOWN NEW AHU.5 PROGRAMMABLE DISPLAY OF ROOM NAME, TEMPERATURE, HUMIDITY AND DIFFERENTIAL PRESSURE.REFER TO TEMPERATURE CONTROL SCHEMATICS FOR MORE INFORMATION.6 REROUTE PIPING AT HIGHER ELEVATION, OUTSIDE OF AHU SERVICE AREA.7 ROUTE 1" CD DOWN TO NEAREST FLOOR DRAIN.8 INSTALL NEW SUPERVISORY CONTROL PANEL. COORDINATE FINAL LOCATION WITH ELECTRICALCONTRACTOR.9 VFD PROVIDED BY DIVISION 23 CONTROLS CONTRACTOR. INSTALLED BY DIVISION 26 CONTRACTOR.REV. DATE
DIFFUSER/REGISTER/GRILLE SCHEDULETAGNECKSIZEFACESIZE(IN.)MATERIALCFMRANGEMAX.NCMAX.TOTAL A.P.D.(IN. WG.)MANUFACTURERMODEL NOTESDESIGN REFERENCETHROW (FT. BASED ON VELOCITY OF 50 FPM)SD18"Ø24"X24""0 - 180200.040PRICE12SD210"Ø24"X24""185 - 300250.040PRICE13SD06"Ø12"X12""0 - 100150.040PRICEAPDSP10SD312"Ø24"X24""305 - 400250.040PRICE14ALUMINUMAPDSPAPDSPAPDSPAIR TERMINAL TYPEPERFORATED CEILING SUPPLYPERFORATED CEILING SUPPLYPERFORATED CEILING SUPPLYPERFORATED CEILING SUPPLY1, 2, 31, 2, 31, 2, 31, 2, 3ALUMINUMALUMINUMALUMINUMPRICELFD110"Ø24X24"205 -350200.40LFDC19PRICEEG01, 38"Ø12"X12"0 -150200.040PDRN/APRICEEG18"Ø24"X24"0 -200200.040N/APRICEEG210"Ø24"X24"205-350200.040N/APRICEEG312"Ø24"X24"355 -500200.040N/ALAMINAR FLOW HEPAPERFORATED CEILING EXH.PERFORATED CEILING EXH.PERFORATED CEILING EXH.PERFORATED CEILING EXH.PDRPDRPDR1, 2, 3, 41, 31, 31, 3PRICERG522"X22"24"X24""0 -1,000200.013PDRN/A1, 3, 5PERFORATED CEILING RET.PRICEEG414"Ø24"X24"505 -700200.040N/APERFORATED CEILING EXH.PDR1, 3ALUMINUMALUMINUMALUMINUMALUMINUMALUMINUMALUMINUMALUMINUMALUMINUMNOTES:1. BRANCH DUCT RUNOUT TO THE DIFFUSER SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED OTHERWISE ON THE DRAWINGS. 2. ALL SUPPLY DIFFUSER BACKPLATES SHALL BE INSULATED WITH A MINIMUM OF 1" INSULATION. INSULATION MAY BE FACTORY OR FIELD APPLIED.3. PROVIDE FRAME STYPLE APPROPRIATE FOR CEILING TYPE (I.E. LAY-IN, SURFACE MOUNT, SIDEWALL, ETC.). REFER TO DRAWINGS AND ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS.4. DIFFUSER SHALL HAVE INTEGRAL HEPA FILTER THAT CAN BE ACCESSED BY REMOVAL OF THE HINGED ALUMINUM FACEPLATE. PROVIDE PRESSURE SWITCH FOR ACTIVELY MONITORING DIFFUSER PRESSURE DROP. PROVIDE PORT FOR AEROSOL CONCENTRATION TESTING OF FILTER.5. PLENUM RETURN GRILLES SHALL HAVE A RETURN BOOT WITH RETURN DAMPER ATTACHED TO THE BACK.6. HORIZONTAL BLADES PARALLEL TO THE LONG DIMENSION.7. HORIZONTAL BLADES PARALLEL TO THE SHORT DIMENSION.PRICEWRG13, 710"X18"10"X18"STAINLESS STEEL0 -420200.040730N/ALOUVERED GRILLEPRICEWRG23, 624"X20"24"X20"STAINLESS STEEL0 -1,350250.040730N/ALOUVERED GRILLEPRICERG01, 38"Ø12"X12"0 -150200.040PDRN/APRICERG18"Ø24"X24"0 -200200.040N/APRICERG210"Ø24"X24"205-350200.040N/APRICERG312"Ø24"X24"355 -500200.040N/APERFORATED CEILING EXH.PERFORATED CEILING EXH.PERFORATED CEILING EXH.PERFORATED CEILING EXH.PDRPDRPDR1, 31, 31, 3PRICERG414"Ø24"X24"505 -700200.040N/APERFORATED CEILING EXH.PDR1, 3ALUMINUMALUMINUMALUMINUMALUMINUMALUMINUMArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:06:25 PMMechanical SchedulesM6-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForTERMINAL UNIT SCHEDULETAGUNIT INLETSIZE ("Ø)DUCTRUNOUTSIZE ("Ø)AIRFLOW DATAHOT WATER REHEAT COIL DATANOTESAIRFLOWMAXIMUM (CFM)AIRFLOWMINIMUM (CFM)AIRFLOWMAXIMUMHEATING (CFM)MAXIMUM AIRPRESSURE DROP(IN. W.C.)ENTERING AIRTEMPERATURE(°F)LEAVING AIRTEMPERATURE(°F)HEAT OUTPUT ATHEATINGAIRFLOW (MBH)WATER FLOWRATE (GPM)PIPERUNOUTSIZE (IN)TU-C025 10 12 800 800 800 0.4 50 85 30,380 3.0 3/4TU-C025A 14 14 1,560 1,560 1,560 0.4 50 85 60,380 6.0 1TU-C025B 10 12 645 645 645 0.3 50 85 24,500 2.4 3/4TU-C025D 8 10 400 400 400 0.2 50 85 15,200 1.5 3/4TU-C025E 6 8 150 70 70 0.2 50 85 4,600 0.5 3/4TU-C025F 12 12 1,020 1,020 1,020 0.4 50 85 38,740 3.9 1TU-PH 12 14 1,200 1,200 1,200 0.1 50 50 N/A N/A N/AAIR HANDLER SCHEDULETAG CONFIGURATION SERVICE AREAAIRFLOW DATAMOTOR DATACOOLING COIL DATAACOUSTICAL DATA (DISCHARGE, MAXIMUM SOUND POWER LEVEL, DBA)WEIGHT(LBS)NOTESMAXIMUM(CFM)RETURN AIR(CFM)VENTILATIONAIR (CFM)ESP (IN.W.C.)BRAKEHORSEPOWER(BHP)RATEDHORSEPOWER(HP)VOLTAGE(V)PHASEENTERING AIRTEMPERATURE(°F)LEAVING AIRTEMPERATURE(°F)TOTALCAPACITY(MBH)SENSIBLECAPACITY(MBH)ENTERING WATERTEMPERATURE(°F)LEAVING WATERTEMPERATURE(°F)WATER FLOWRATE (GPM)63 HZ 128 HZ 250 HZ 500 HZ 1000 HZ 2000 HZ 4000 HZ 8000 HZAHU-PH HORIZONTAL PHARMACY 3,500 2,300 1,200 3.5 4.7 5.0 4603 63.5 57.1 67.1 51.7 44 54 13.5 83 82 81 82 79 80 82 74 1,260 1,2,3,4EXHAUST FAN SCHEDULETAG SERVICE AREAAIRFLOW DATACONFIGURATIONMOTOR DATAACOUSTICAL DATA (MAXIMUM SOUND POWER LEVEL, DBA) DESIGN REFERENCENOTESDESIGNAIRFLOW (CFM)EXTERNALSTATICPRESSURE (IN.W.C.)FAN RPMOUTLETVELOCITY (FPM)FANTYPE/DISCHARGEFAN WHEELDIAMETER (IN.)MINIMUM FANCLASSBRAKEHORESPOWER(BHP)RATEDHORSEPOWER(HP)MOTOR RPMVOLTAGE(V)PHASEVFD SPEED(HZ)63 HZ 128 HZ 250 HZ 500 HZ 1000 HZ 2000 HZ 4000 HZ 8000 HZMANUFACTURER MODELEF-15 HAZARD BIO-SAFETY CABINET 950 3.0 2,000 740VERTICALDISCHARGE15 II 0.7 1-1/2 1,750 480 3 68 86 85 81 82 80 76 74 70 GREENHECK CSW-15-BI 1,2,3AIRFLOW CONTROL VALVE SCHEDULETAGUNIT INLETSIZEAIRFLOW DATANOTESAIRFLOWMAXIMUM (CFM)AIRFLOWMINIMUM (CFM)AIRFLOWMAXIMUMHEATING (CFM)MAXIMUM AIRPRESSURE DROP(IN. W.C.)AFCV-C025A 12 1,300 1,300 1,300 0.1AFCV-C025F 10 820 820 820 0.1NOTES:1. DIRECT DRIVE FAN. MOTOR SHALL BE CONTROLLED BY VARIABLE FREQUENCY DRIVE.2. PROVIDE SINGLE POINT POWER CONNECTION WITH DISCONNECT. DISCONNECT SHALL HAVE AUXILIARY CONTACT FOR INTERLOCKING TO VFD.3. UNIT SHALL HAVE DOUBLE WALL INSULATED CONSTRUCTION. NO INSULATION SHALL BE EXPOSED TO THE AIRSTREAM. 4. PROVIDE CONDENSATE HIGH LEVEL SWITCH. IF REQUIRED FOR FIELD ROUTING OF PIPING, PROVIDE A CONDENSATE PUMP. COORDINATE ELECTRICAL CONNECTION WITH ELECTRICAL CONTRACTOR.MOTOR CONTROLLER SCHEDULEDESIGNATION LOAD SERVED LOCATIONEQUIPMENT DATA STARTER DATANEMA ENCLOSURE COMMENTSHP FLA VOLTAGE PHASEDISCONNECT SWITCH STARTERSWITCH SIZE FUSE SIZE TYPE NEMA SIZEVFD-AHUPH AHU-PH MECHANICAL ROOM C031 5 7.6 480V 3 30 20 VFD- TYPE 1 PROVIDE WITH INTEGRAL BYPASS. VFD SUPPLIEDBY DIV. 23 AND INSTALLED BY DIV. 26.VFD-EF15 EF-15 MECHANICAL ROOM C700 1 2.1 480V 3 30 20 VFD - TYPE 1 PROVIDE WITH INTEGRAL BYPASS. VFD SUPPLIEDBY DIV. 23 AND INSTALLED BY DIV. 26.NOTES:1. HEATING PERFORMANCE BASED ON 150°F ENTERING WATER AND 130°F LEAVING WATER. VERIFY ALL TERMINAL UNITS CAN REHEAT TO 75°F LEAVING AIR TEMPERATURE WITH 120°F ENTERING WATER. INCREASE TERMINAL UNIT SIZE AS REQUIRED TO ACHIEVE BOTH CONDITIONS.2. PROVIDE MINIMUM 2-ROW COILS.3. ALL TERMINAL UNITS SHALL HAVE 1" INSULATION WITH SOLID INTERNAL SHEETMETAL LINER. 4. PROVIDE SINGLE POINT POWER CONNECTION WITH DISCONNECT.5. SIMILAR TO PRICE SDV.6. INSTALL TERMINAL UNITS WITH A MINIMUM OF 3 X DIA STRAIGHT INLET DUCT AT EACH TERMINAL UNIT. WHERE THE DUCT RUNOUT IS LESS THAN 8' AND HAS NOT OFFSETS OR ELBOWS, THE DUCT RUNOUT MAY BE THE SAME SIZE AS THE TERMINAL UNIT INLET.NOTES:1. DIRECT DRIVE FAN. MOTOR SHALL BE CONTROLLED BY VARIABLE FREQUENCY DRIVE. DESIGN CONDITIONS REQUIRE OVERSPEED TO SCHEDULED VALUE. PROVIDE MOTOR DESIGNED FOR OPERATION UP TO 120 HZ.2. PROVIDE SINGLE POINT POWER CONNECTION WITH DISCONNECT. DISCONNECT SHALL HAVE AUXILIARY CONTACT FOR INTERLOCKING TO VFD.3. PROVIDE ROOF CURB/RAILS WITH 2" RESTRAINED SPRING ISOLATORS. ANCHOR FAN ASSEMBLY TO CURB IN ACCORDANCE WITH LOCAL WIND REQUIREMENTS.REV. DATE
DETAIL NOTES:1FIELD MOUNT DDC CONTROLLER SO IT DOES NOT OBSTRUCT ACCESS TO FCU COMPONENTS OR ACCESSORIES.ALLOW A MINIMUM 36" CLEARANCE ADJACENT TO THE AIR HANDLER. INCREASE ACCESS AS REQUIRED FOR NEC MINIMUM CLEARANCE. ROUTE ALL PIPING OUTSIDE OF THIS SERVICE AREA. INSTALL SUCH THAT VALVES AND OTHER PIPING ACCESSORIES ARE ACCESSIBLE FROM THIS LOCATION. SERVICE AREA SHALL EXTEND DOWN TO AND INCLUDE THE CEILING BELOW. COORDINATE WITH ALL TRADES SUCH THAT SERVICE AREA IS UNOBSTRUCTED BY LIGHTS, DIFFUSERS, SPRINKLER HEADS, SPEAKERS, OR OTHER CEILING INSTALLED DEVICES. DO NOT ROUTE PIPING, CABLE TRAYS, OR OTHER SERVICES BENEATH AIR HANDLER THAT WILL HINDER REMOVAL AND REPLACEMENT.SUPPORT AIR HANDLER WITH HANGER RODS OR AT ALL FOUR CORNERS. INSTALL RODS WHERE THEY DO NOT INFRINGE UPON UNIT ACCESS. UNIT SUPPORTS SHALL EXTEND UP TO STRUCTURE. DO NOT SUPPORT FROM DUCTWORK, PIPES, OR OTHER SERVICES LOCATED ABOVE CEILING. INSTALL NEOPRENE ISOLATORS BETWEEN AIR HANDLER AND SUPPORT. SEISMICALLY RESTRAIN AS REQUIRED BY SPECIFICATION 230548 OR AS REQUIRED BY CODE.RESTRAINED SPRING ISOLATORS WITH 1" DEFLECTION. REMOVE SHIPPING BOLTS PRIOR TO OPERATING FAN.ROUTE CONDENSATE TO NEAREST OPEN FLOOR DRAIN. ROUTE OVERFLOW DRAIN SEPARATELY FROM CONDENSATE DRAIN PAN PRIMARY DRAIN TO OPEN FLOOR DRAIN AND ATTACH A SIGN TO PIPE THAT STATES "CONTACT FACILITIES IF WATER IS OBSERVED DRAINING FROM THIS PIPE." SIGN SHALL BE PERMANENT PLASTIC SIGN WITH ETCHED LETTERING. WHERE NO OPEN SITE DRAIN EXISTING, ROUTE OVERFLOW TO TERMINATE FLUSH WITH THE FINISHED CEILING. COORDINATE WITH OWNER AND ENGINEER PRIOR TO ROUTING AND TERMINATING.DOUBLE WALL CASING WITH 2" FOAM PANEL. INTERIOR SURFACE SHALL BE COVERED WITH GALVANIZED METAL LINER SUCH THAT NO AIR IS EXPOSED TO THE AIRSTREAM. ALL INTERIOR SURFACES SHALL MEET ASHRAE 62.1 STANDARD.2DUCT MOUNTED ACCESS DOOR. MINIMUM SIZE IS 18"X18". 123COOLING COILDIRECT DRIVE PLENUM FAN444FLEXIBLE CONNECTORS AT SUPPLY AND RETURN CONNECTIONS.FLEXIBLE CONNECTOR WITH NEOPRENE THRUST BLOCKS.355RETURN AIRSUPPLY AIRRETURN AIRSUPPLY AIRMERV 8 PRE-FILTERSTATIC PRESSURE0.50NEGATIVE PRESSURE (IN W.C.)2.252.751"FLOORDRAINAIR HANDLING UNIT DRAIN PANDRAIN SHALL BE AT LEAST THE SAME SIZE AS THE NIPPLE ON THE DRAIN PANCLEAN OUTPITCH DOWNTOWARD DRAINCLEAN OUTBAPP = NEGATIVE PRESSURE (IN OF WATER)A = 1/2P + 2 INB = 1 1/2P + 2 INDRAIN PAN TRAP SIZINGBA1.001.502.002.503.003.504.004.505.005.506.006.507.007.508.008.509.009.5010.02.502.753.003.503.754.004.254.504.755.005.255.505.756.006.256.506.757.003.254.255.006.507.258.008.759.5010.2511.0011.7512.5013.255.753.5014.0014.7515.5016.2517.00FLEXIBLE DUCTWORK BENDS SHALL NOT BE LESS THAN 1.5 TIMES THE DUCT DIAMETER. INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY-FABRICATED DUCTS SHALL BE FITTED OVER THE CORE CONNECTION AND SHALL BE SUPPLEMENTALLY SECURED WITH A DRAW BAND. TAPE AND SEAL ALL JOINTS AND SEAMS WITH FSK TAPE TO MAINTAIN VAPOR BARRIER.SUPPORT FLEXIBLE DUCTWORK FROM STRUCTURE. DO NOT SUPPORT FLEXIBLE DUCTWORK FROM ADJACENT ABOVE CEILING UTILITIES (DUCTWORK, PIPING, CONDUITS, ETC.)A.B.C.GENERAL DETAIL NOTESSPIN-IN FITTING AT BRANCH/MAIN CONNECTIONFLEX DUCT-MAXIMUM 8'-0"LENGTH AND NO MORE THANTWO (2) 90° BENDS.INSULATE BACK OF SUPPLY DIFFUSERS WITH 1" MINERAL FIBER WITH FSK JACKET.CEILINGDIFFUSER/GRILLEATTACHED FLEXIBLE DUCTWORK WITH DRAWBAND AND SEAL INSULATION AND VAPOR BARRIER WITH FSK TAPE.INSTALL MANUAL VOLUME DAMPER AT ALL BRANCH DUCTS. PROVIDE 2" EXTENDED OPERATOR HANDLE FOR INSULATED DUCTS.DETAIL NOTESUTILIZE HIGH VELOCITY TAKE-OFFS FOR MAIN/BRANCH CONNECTION:SQUARE TO SQUARE - BEVELED BOOT-TAPSQUARE TO ROUND - BELLMOUTHROUND TO ROUND - LATERALREFER TO PLANS FOR DUCT SIZE.ALLOW A MINIMUM OF 24"X36" CLEARANCE ADJACENT TO THE AIRFLOW CONTROL VALVE CONTROL PANEL. INCREASE ACCESS AS REQUIRED FOR NEC MINIMUM CLEARANCE. ROUTE ALL PIPING OUTSIDE OF THIS SERVICE AREA. INSTALL SUCH THAT VALVES AND OTHER PPING ACCESSORIES ARE ACCESSIBLE FROM THIS LOCATION. SERVICE AREA SHALL EXTEND DOWN TO AND INCLUDE THE CEILING BELOW. COORDINATE WITH ALL TRADES SUCH THAT SERVICE AREA IS UNOBSTRUCTED BY LIGHTS, DIFFUSERS, SPRINKLER HEADS, SPEAKERS, OR OTHER CEILING INSTALLED DEVICES.SUPPORT AIRFLOW CONTROL VALVE WITH HANGER RODS OR STRAPS AT ALL FOUR CORNERS. UNIT SUPPORTS SHALL EXTEND UP TO STRUCTURE. DO NOT SUPPORT FROM DUCTWORK, PIPES, OR OTHER SERVICES LOCATED ABOVE CEILING. DO NOT OBSTRUCT FACTORY INSTALLED ACCESS DOOR.INSTALL GRILLE RUNOUT IN THE SIDE OF THE DISCHARGE DUCT WITH SPIN-IN DUCT FITTINGS AND MANUAL VOLUME DAMPERS. 1122334REFER TO DIFFUSER DETAIL FOR REQUIREMENTS455RETURN/EXHAUST MAIN2HWRMODULATING CONTROL VAVE WITH UNIONAIR VENTUNIONCOILUNIONCALIBRATED BALANCE VALVESTRAINER WITH BLOWDOWN BALL VALVEHWSBALL VALVEDRAIN WITH THREADED CAPDUCT (TYP)FILL SPACE AROUND DUCT WITH NONCOMBUSTIBLE SEALANT.FINISHED WALLSURFACE OFRATED ASSEMBLYFINISHED WALL SURFACEUNINSULATED DUCT THROUGHINTERIOR FIRE RATED BARRIERSUNINSULATED DUCT THROUGH INTERIORNON-RATED WALLS OR SMOKE-RESISTANTCORRIDOR WALLSFRAMED WALL OPENING (TYP)INSULATION CONTINUOUS THROUGH WALL (TYP)FINISHED WALLSURFACE OFRATED ASSEMBLYFILL ANNULAR GAPSEACH SIDE OF DUCTON EACH SIDE OF WALL WITH NONCOMBUSTIBLESEALANT.FINISHED WALL SURFACEINSULATED DUCT THROUGH INTERIORNON-RATED OR SMOKE-RESISTANTCORRIDOR WALLSINSULATED DUCT THROUGH INTERIORFIRE RATED BARRIERSDETAIL NOTES:INSTALL FIRESTOP AND RETAINING ANGLES AS SPECIFIED IN DIVISION 7. ALL PENETRATIONS SHALL MEET UL LISTED RATING APPROPRIATE FOR WALL RATING.INSTALL FIRESTOP LABEL ABOVE CEILING ON BOTH SIDES OF PENETRATION122112REFER TO PLANS FOR SIZERETURN/ EXHAUST DUCTCEILINGFLOOR8" AFF12DETAIL NOTESGRILLE SHALL BE 8" FROM BOTTOM OF GRILLE TO FINISHED FLOOR LEVE.1LOCATE BALANCE DAMPER IN AN ACCESSIBLE LOCATION ABOVE LAY-IN CEILING. WHERE DAMPER CANNOT BE LOCATED ABOVE LAY-IN CEILING, INSTALL AN ACCESS PANEL.2INSTALL 8' OF FLEXIBLE DUCTWORKSPIN-IN DUCT CONNECTIONEXTERIOR WALLSPROVIDE ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENINGIN EXPOSED AREAS ONLY.NOTES:SEE SPECIFICATION SECTIONS FOR FURTHER REQUIREMENTS INCLUDING FLOOR SLEEVES.INSULATED OR UNINSULATED PIPE THROUGH INTERIOR NON-RATED WALLS OR SMOKE=RESISTANT CORRIDOR WALLSUNINSULATED PIPE THROUGH INTERIOR FIRE RATED WALLSINSULATED PIPE THROUGH INTERIOR FIRE RATED WALLSLOCATE FIRESTOP LABEL ON EACH SIDE OF PENETRATION SO THAT IT IS VISIBLE FROM AN ACCESSIBLE LOCATION ABOVE CEILING.INCLUDES FIRE WALLS, FIRE BARRIERS, SMOKE BARRIERS, AND FIRE PARTITIONS.TERMINATE SLEEVE FLUSHWITH FINISHED WALLPIPEFIRESTOP EACH SIDEOF SLEEVE ASSPECIFED IN DIV 7FINISHED WALL SURFACEOF RATED ASSEMBLYWALLHYDO-STATIC PIPECLOSURE; "LINK-SEAL"PIPEPIPE SLEEVE TO BE SIZED TO PASSPIPE THRU SLEEVE AND ALLOW SPACEFOR SEALANT TO MEET UL-LISTINGTERMINATE SLEEVEFLUSH WITH FINISHED WALLFIRESTOP EACH SIDEOF SLEEVE ASSPECIFED IN DIV 7PIPEFINISHED WALL SURFACEOF RATED ASSEMBLYPIPE SLEEVE TO BE SIZED TO PASS PIPE AND INSULATION THRU SLEEVE AND ALLOW SPACE FOR SEALANT TO MEET UL-LISTINGPIPE INSULATION TO BECONT THRU WALLPIPEFILL ANNULAR GAPSAROUND PIPES ONEACH SIDE OF WALLASSEMBLYNONCOMBUSTIBLE SEALANTFINISHED WALL SURFACESLEEVE WATER STOPWALL SLEEVE312341143Architecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:06:26 PMMechanical DetailsM7-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForNO SCALE1AHU-PH DETAILNO SCALE2NEGATIVE PRESSURE CONDENSATE DRAIN TRAP DETAILNO SCALE3CEILING DIFFUSER/GRILLE DETAIL 1/4" = 1'-0"4AIRFLOW CONTROL VALVE DETAILNO SCALE5COIL PIPING DETAILNO SCALE6DUCT PENETRATION DETAILNO SCALE7TYPICAL LOW EXHAUST/RETURN DETAILNO SCALE8PIPE PENETRATION DETAILSREV. DATE
DETAIL NOTESUTILIZE HIGH VELOCITY TAKE-OFFS FOR MAIN/BRANCH CONNECTION:SQUARE TO SQUARE - BEVELED BOOT-TAPSQUARE TO ROUND - BELLMOUTHROUND TO ROUND - LATERALWHERE DUCT RUNOUT IS LONGER THAN 10', INCREASE THE RUNOUT SIZE TO THE NEXT LARGER EVEN SIZE UNLESS NOTED OTHERWISE. PROVIDE A MINIMUM OF 3 X INLET DIAMETERS OF STRAIGHT DUCT RUN AT TERMINAL UNIT INLET. A MAXIMUM OF 1'-0" FLEXIBLE DUCT MAY BE USED AT TERMINAL UNIT CONNECTION BUT MUST BE PULLED TIGHT AND NOT USED FOR CHANGES IN DIRECTION.ALLOW A MINIMUM OF 24"X36" CLEARANCE ADJACENT TO THE TERMINAL UNIT CONTROL PANEL. INCREASE ACCESS AS REQUIRED FOR NEC MINIMUM CLEARANCE. ROUTE ALL PIPING OUTSIDE OF THIS SERVICE AREA. INSTALL SUCH THAT VALVES AND OTHER PPING ACCESSORIES ARE ACCESSIBLE FROM THIS LOCATION. SERVICE AREA SHALL EXTEND DOWN TO AND INCLUDE THE CEILING BELOW. COORDINATE WITH ALL TRADES SUCH THAT SERVICE AREA IS UNOBSTRUCTED BY LIGHTS, DIFFUSERS, SPRINKLER HEADS, SPEAKERS, OR OTHER CEILING INSTALLED DEVICES.DISCHARGE DUCT SHALL BE THE SAME SIZE AS THE TERMINAL UNIT DISCHARGE CONNECTION UNLESS NOTED OTHERWISE. TRANSITION TO A DEEPER DUCT AS REQUIRED FOR DIFFUSER RUNOUT SIZES.SUPPORT TERMINAL UNIT WITH HANGER RODS OR STRAPS AT ALL FOUR CORNERS. TERMINAL UNIT SUPPORTS SHALL EXTEND UP TO STRUCTURE. DO NOT SUPPORT FROM DUCTWORK, PIPES, OR OTHER SERVICES LOCATED ABOVE CEILING. INSULATE ALL EXPOSED METAL THAT IS NOT FACTORY INSULATED. EXTEND DUCT INSULATION 2" PAST BOUNDARY OF INSULATED/UNISULATED MATERIALS AND SEAL WITH FSK TAPE. DO NOT OBSTRUCT FACTORY INSTALLED ACCESS DOOR.INSTALL DIFFUSER RUNOUT IS THE SIDE OF THE DISCHARGE DUCT WITH SPIN-IN DUCT FITTINGS AND MANUAL VOLUME DAMPERS. VOLUME DAMPER OPERATORS SHALL EXTEND 2" BEYOND DUCT TO ALLOW FOR INSULATION TO BE INSTALLED. TERMINAL UNIT DISCHARGE DUCT SHALL HAVE A "DEAD-END" WHERE NOT DIFFUSERS ARE CONNECTED TO ALLOW FOR END REFLECTION SOUND CONTROL.11223344REFER TO DIFFUSER DETAIL FOR REQUIREMENTS5566COILP/T PLUG (TYP.)BALL VALVE (TYP.)STRAINER W/ BLOWDOWN VALVE AND CAPUNION (TYP.)CALIBRATED BALANCE VALVE2-WAY MODULATING CONTROL VALVEMANUAL AIR VENT.INSTALL AT HIGHEST POINT IN RETURN PIPINGDETAIL NOTES:INSTALL BUTTERFLY VALVES IN LIEU OF BALL VALVES WHEN PIPE SIZE IS 2-1/2" AND GREATER.113/4" DRAIN WITH BALL VALVE, HOSE CONNECTION AND CAP.INSTALL AT LOWEST POINT IN PIPINGCOVER OPENINGWITH 1/2" MESH BIRD SCREEN16 GA. GALV. DISCHARGE PLENUMRESTRAINED PSPRING ISOLATORS WITH 2" DANCHOR TO ROOF IN ACCORDANCE WITH LOCAL WIND ORDINANCE.VERIFY ACTUAL ROOF CONSTRUCTIONWITH ARCHITECTURAL DRAWINGSSEE PLAN FOR DUCT CONTINUATIONHOLE THRU ROOF TO BE1" LARGER(BOTH WAYS) THAN DUCTSSTORM COLLAR SECURED & CAULKED TO DUCTSEE PLAN FORDUCT SIZEWEATHERPROOF FLEX CONNECTIONVERIFY SIZE OR FAN INLET WITH FAN MANUFATURERSTANDARD EQUIPMENT CURBSCURBCURB CAP-SECURE TO DUCT & CAULK WATER TIGHTINSTALL A PERMANENT WARNING LABEL ON EXHAUST FAN THAT SAYS "WARNING -BIOSAFETY CABINET EXHAUST" AND PAINT A RED RECTANGLE BENEATH WARNING SIGN. WARNING SIGN SHALL BE RED WITH WHITE LETTERS. LETTERS SHALL BE 1" TALL. FIELD LOCATE SIGN SO IT CAN BE SEEN PRIOR TO APPROACHING EXHAUST FAN.Architecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 1:06:27 PMMechanical DetailsM7-211700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForNO SCALE1TERMINAL UNIT DETAILNO SCALE2AIR HANDLER COOLING COIL DETAILREV. DATENO SCALE3UTILITY SET EXHAUST FAN DETAIL
ABBREV.A or AMPACA/CACPACUADDADJAFAFCAFFAFGAHUAICALAMAMBAPPROX.ARCHATSAUTOAVGBCBKRBHPBLBLDGBRBTMCºCCABCB or C/BC/CCCTVCKTCLCLGCOLCOMMCOMPCONCCONSTCONTCONTRCRCTCUDBDCDEPTDFDISTDMDODRSDWGECEFELECELEVELVEMERENCLEPEQUIPEWCEXEXHEXPEXTºFFAFAAPFACPFCFCUFFCFFSFHCFINFIXTFLFLUORFLEX-CONNFPCFSSFTGFVRFVFVNRG or GNDGALVGCGENGFCIGFIGFPHGTHHHIDHOHOAHORZHPHPSHTRHVDESCRIPTIONAMPEREALTERNATING CURRENTAIR CONDITIONINGACCESS PANELAIR CONDITIONING UNITADDITIONADJUSTABLEAMPERE FRAMEABOVE FINISHED CEILINGABOVE FINISHED FLOORABOVE FINISHED GRADEAIR HANDLING UNITAMPERE INTERRUPTING CAPACITYALUMINUMAMMETERAMBIENTAPPROXIMATELYARCHITECTAUTOMATIC TRANSFER SWITCHAUTOMATICAVERGEBARE COPPERBREAKERBRAKE HORSEPOWERBUILDING LINEBUILDINGBRANCHBOTTOMCONDUITDEGREES CELSIUSCABINETCIRCUIT BREAKERCENTER TO CENTERCLOSED CIRCUIT TELEVISIONCIRCUITCENTER LINECEILINGCOLUMNCOMMUNICATIONCOMPRESSORCONCRETECONSTRUCTIONCONTINUOUSCONTRACTORCRITICALCURRENT TRANSFORMERCOPPERDIRECT BURIALDIRECT CURRENTDEPARTMENTDRINKING FOUNTAINDISTRIBUTIONDEMAND METERDRAWOUTDOCTORSDRAWINGELECTRICAL CONTRACTOREXHAUST FANELECTRICELEVATORELEVATIONEMERGENCYENCLOSUREELECTRIC PNEUMATICEQUIPMENTELECTRIC WATER COOLEREXPLOSIONPROOFEXHAUSTEXPANSIONEXTERIORDEGREES FAHRENHEITFIRE ALARMFIRE ALARM ANNUNCIATOR PANELFIRE ALARM CONTROL PANELFLAT CABLEFAN COIL UNITFOOD FACILITY CONTRACTORFOOD FACILITY SUPPLIERFIRE HOSE CABINETFINISHFIXTUREFLOORFLUORESCENTFLEXIBLE CONNECTIONFIRE PROTECTION CONTRACTORFUSED SAFETY SWITCHFOOTINGFILMVIEWERFULL VOLTAGEFULL VOLTAGE NON REVERSINGGROUNDGALVANIZEDGENERAL CONTRACTORGENERATORGROUND FAULT CKT. INTERRUPTERGROUND FAULT INTERRUPTERGROUND FAULT PROTECTIONHEIGHTHANDHOLEHIGH INTENSITY DISCHARGEHAND OPERATEDHAND-OFF-AUTOMATICHORIZONTALHORSEPOWERHIGH PRESSURE SODIUMHEATERHIGH VOLTAGEABBREV.ICIDINCANINCLISGJBJTKECKTKVAKVARKWLABLBLFLOCLSLTLTGLVMATVMAXMCMCBMCCMDPMECHMHMINMISCMLOMTDMTG HTMUODOFCIOFOIOPNGOPPORPPBPBOXPEPFPH or ØPVPNLPLPREFABPRESPTPTSPWPWRRACURADRECEPTREF or REFRREINFRGIPRMRPMSASCSGSHTSIGSNSPECSQSSSSSSSTDSTNSTRSUSPSWSWBDSWGRTCCTELETEMPTMHTVTYPUCU/CUHUVVVACVBVCVELVFDVMVOLVPVSD/VFCW/W/OWTRWPWTXFMRZDESCRIPTIONINTERCOMMUNICATIONINSIDE DIAMETERINCANDESCENTINCLUDEISOLATED GROUND SURGE GUARDJUNCTION BOXJOINTKITCHEN EQUIPMENT CONTRACTORKITCHENETTEKILOVOLT AMPEREKILOVOLT AMPERE REACTIVEKILOWATTLABORATORYPOUNDLINEAR FEETLOCATIONLIFE SAFETYLIGHTLIGHTINGLOW VOLTAGEMASTER ANTENNA TELEVISIONMAXIMUMMECHANICAL CONTRACTORMAIN CIRCUIT BREAKERMOTOR CONTROL CENTERMAIN DISTRIBUTION PANELMECHANICALMANHOLEMINIMUMMISCELLANEOUSMAIN LUGS ONLYMOUNTEDMOUNTING HEIGHTMEDICINE UNITOUTSIDE DIAMETEROWNER FURNISHED-CONTRACTOR INSTALLEDOWNER FURNISHED-OWNER INSTALLEDOPENINGOPPOSITEOPERATING ROOMPOLEPUSHBUTTONPULL BOXPNEUMATIC ELECTRIC CONVERTERPOWER FACTORPHASEPOST INDICATOR VALVEPANELBOARDPILOT LIGHTPREFABRICATEDPRESSUREPNEUMATIC TUBEPNEUMATIC TUBE STATIONPART WINDINGPOWERROOM AIR CONDITIONING UNITRADIATIONRECEPTACLEREFRIGERATORREINFORCEDREMOTE GROUND INDICATING PANELROOMREVOLUTIONS PER MINUTESUPPLY AIRSHORT CIRCUITSURGE GUARD PROTECTIONSHEETSIGNALSOLID NEUTRALSPECIFICATIONSSQUARESAFETY SWITCHSOLID STATE SOFT STARTSTANDARDSTATIONSTRUCTURALSUSPENDEDSWITCHSWITCHBOARDSWITCHGEARTEMPERATURE CONTROL CONTRACTORTELECOMMUNICATIONTEMPERATURETOP OF MANHOLETELEVISIONTYPICALUNDER CARPETUNDER CABINET or UNDER COUNTERUNIT HEATERUNIT VENTILATORVOLTVACUUMVACUUM BREAKERVACUUM CLEANINGVELOCITYVARIABLE FREQUENCY DRIVEVOLTMETERVOLUMEVAPORPROOFVARIABLE SPEED DRIVE/CONTROLLERWITHWITHOUTWATERWEATHERPROOFWEIGHTTRANSFORMERIMPEDANCEELECTRICAL ABBREVIATIONSMFIRE ALARM SYSTEMSYMBOLDESCRIPTIONMANUAL SENDING STATIONPIVPOST INDICATOR VALVESDCEILING SMOKE DETECTORTSSPRINKLER SYSTEM TAMPER SWITCHFSSPRINKLER SYSTEM FLOW SWITCHSDWALL SMOKE DETECTORSDWALL SMOKE DETECTOR WITH SOUNDER BASESDCEILING SMOKE DETECTOR WITH SOUNDER BASEDDAUTOMATIC DUCT DETECTOR ("X" DENOTES AS FOLLOWS)RTREMOTE DETECTOR TEST STATIONRIREMOTE DETECTOR INDICATOR STATIONARFIRE ALARM ADDRESSABLE RELAYXNONE -PHOTOELECTRIC TYPE S -SUPPLYR -RETURNDRDOOR RELEASEDUDOOR UNLOCKJFIREMANS JACKHDHEAT DETECTORFDFLAME DETECTORBDBEAM DETECTORHWALL HORN ONLYHWALL HORN STROBESWALL SPEAKER ONLYSWALL SPEAKER STROBEVWALL VISUAL ONLYFACPFIRE ALARM CONTROL PANELFAAPFIRE ALARM ANNUNCIATOR PANELALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT3SST -20 AMP, 125VAC, SAFETY TYPES -20 AMP, 125VAC, SURGE GUARD PROTECTION TYPEWP -20 AMP, 125VAC, WEATHERPROOF TYPEHM -20 AMP, 125VAC, HORIZONTAL MOUNT TYPEIG -20 AMP, 125VAC, ISOLATED GROUND TYPENONE -20 AMP, 125VACELECTRICAL RECEPTACLESDUPLEX RECEPTACLE -NORMAL POWER CIRCUIT DESCRIPTIONSYMBOLDUPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT DUPLEX GFCI RECEPTACLE -NORMAL POWER CIRCUIT DUPLEX GFCI RECEPTACLE -EMERGENCY POWER CIRCUIT QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT QUADRAPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT QUADRAPLEX GFCI RECEPTACLE -NORMAL POWER CIRCUIT QUADRAPLEX GFCI RECEPTACLE -EMERGENCY POWER CIRCUIT SIMPLEX RECEPTACLE -NORMAL POWER CIRCUIT SIMPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT SPECIAL RECEPTACLE -NORMAL POWER CIRCUIT SPECIAL RECEPTACLE -EMERGENCY POWER CIRCUIT DUPLEX RECEPTACLE -TOP SWITCHEDXXXXXXXXXXXXX"X" DENOTES AS FOLLOWS:CEILING DUPLEX RECEPTACLE -NORMAL POWER CIRCUITCEILING DUPLEX RECEPTACLE -EMERGECNY POWER CIRCUITCEILING QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUITCEILING QUADRAEPLEX RECEPTACLE -EMERGECNY POWER CIRCUITFLOOR BOX DUPLEX RECEPTACLE -NORMAL POWER CIRCUITFLOOR BOX DUPLEX RECEPTACLE -EMERGECNY POWER CIRCUITFLOOR BOX QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUITFLOOR BOX QUADRAPLEX RECEPTACLE -EMERGECNY POWER CIRCUITFLOOR BOX POWER AND DATAFLOOR BOX BLANKPLUGSTRIP (POWER AND/OR DATA) WELECTRICAL SWITCHESDESCRIPTIONSYMBOLTOGGLE SWITCH -20 AMP, 120/277VACSTOGGLE SWITCH -3 WAY4STOGGLE SWITCH -4 WAYKSTOGGLE SWITCH -KEY OPERATEDTSTOGGLE SWITCH -HORSE POWER RATED MANUAL MOTOR STARTER WITH THERMAL OVERLOAD PROTECTIONPSTOGGLE SWITCH -PILOT LIGHTDDIMMER SWITCH -20 AMP, 120/277VACDDIMMER SWITCH -3 WAY34DDIMMER SWITCH -4 WAYOCWALL OCCUPANCEY SENSOR -1 BUTTON CONTROLOC2WALL OCCUPANCEY SENSOR -2 BUTTON CONTROLOC3WALL OCCUPANCEY SENSOR -DUAL RELAY FOR EXHAUST FAN CONTROLOCCEILING OCCUPANCEY SENSOR VSWALL VACANCY SENSOR -1 BUTTON CONTROLVS2WALL VACANCY SENSOR -2 BUTTON CONTROLLCLOW VOLTAGE LIGHTING CONTROLLERT0 -3 HOUR TIMER SWITCH -20 AMP, 120/277VACINFORMATION SYSTEMSDESCRIPTIONSYMBOLDATA ONLY OUTLETVOICE ONLY OUTLETVOICE ONLY OUTLET (WALL PHONE)VOICE AND DATA OUTLETDATA ONLY (WIRELESS ACCESS POINT)WAPFLOOR BOX -DATA ONLYFLOOR BOX -VOICE ONLYFLOOR BOX -VOICE AND DATACEILING -VOICE ONLYCEILING -VOICE AND DATATELECOMMUNCATIONS EQUIPMENT RACKXR -ROUGH-IN ONLY# = QUANTITY OF JACK(S) AND CABLE(S)"X" DENOTES AS FOLLOWS:LIGHTINGDESCRIPTION24" x 48" LIGHTING FIXTURESYMBOL24" x 24" LIGHTING FIXTURE12" x 48" LIGHTING FIXTUREHALF SHADED INDICATES LIFE SAFETY POWERFULL SHADED INDICATES EMERGENCY POWER12" x 96" LIGHTING FIXTURE6" x 96" LIGHTING FIXTURE6" x 48" LIGHTING FIXTURE6" x 36" LIGHTING FIXTURE6" x 24" LIGHTING FIXTURE8" DOWNLIGHT6" DOWNLIGHT4" DOWNLIGHTWALL MOUNTED LIGHTCEILING EXIT LIGHT (DUAL FACED)CEILING EXIT LIGHT (SINGLE FACE)WALL EXIT LIGHTEXIT LIGHT DIRECTIONAL ARROWSWALL EMERGENCY BATTERY LIGHTWALL EXIT WITH EMERGENCY LIGHTSCEILING EMERGENCY BATTERY LIGHTWALL EXIT WITH INTERIOR AND EXTERIOR EMERGENCY LIGHTSEXTERIOR POLE LIGHT (ONE HEAD)EXTERIOR POLE LIGHT (TWO HEADS)EXTERIOR POLE LIGHT (THREE HEADS)EXTERIOR POLE LIGHT (FOUR HEADS)EXTERIOR POLE LIGHT (TOP MOUNT)EXTERIOR BOLLARDNEUTRALGROUNDRACEWAY SYSTEMDESCRIPTIONPHASE CONDUCTORSSYMBOLLIGHT/SCREENED SOLID OR DASHED LINES INDICATE EXISTING TO REMAINHEAVY CONTINUOUS LINES INDICATE NEW WORKLINE SYMBOLSHEAVY DASHED LINES INDICATE EXISTING TO BE REMOVEDJJUNCTION OR PULL BOXPUSHBUTTON OR PUSH PLATEPAD MOUNTED TRANSFORMERBRANCH PANELBOARD -SURFACE MOUNTCOMBINATION MOTOR CONTROLLER / DISCONNECTDISCONNECT SWITCH -NON-FUSEDMOTOR CONTROLLERDISCONNECT SWITCH -FUSEDMOTOR ("X" DENOTES HORSEPOWER)GROUND CONNECTIONELECTRIC THERMOSTATTDESCRIPTIONMOLDED CASE CIRCUIT BREAKERELECTRICAL EQUIPMENTSYMBOLGROUND POINTGROUND RODXPCPHOTO CELLSUSPENDED TRANSFORMERDISTRIBUTION PANELBOARD BRANCH PANELBOARD -RECESSED MOUNTAUTOMATIC TRANSFER SWITCHN ELTELECOM TERMINAL BOARDGROUND BARGENERATORTVAVTV SYSTEM OUTLETAUDIO/VISUAL CONTROLLERCLOCK SYSTEM OUTLETCMMMICROPHONE INPUT RECEPTACLE -WALL MOUNTEDSPEAKER -WALL MOUNTEDSPEAKER -CEILING MOUNTEDVOLUME CONTROLMICROPHONE INPUT RECEPTACLE -CEILING MOUNTEDSSVMDSEPLNMTVCCTVDRESICMISCPMLCRMDDCPBKBSDSSMSSDEPCPCPCLNURSE ASSIST / CODE BLUEDOOR SECURITY SYSTEMSYMBOLDESCRIPTIONDOOR BUZZERSECURITY DOOR ALARM MAGNETIC LOCKCCTV MONITOR OUTLETELECTRIC DOOR OPENERELECTRIC DOOR STRIKEINTERCOM UNIT FLUSH MTD.MASTER INTERCOM AND DIRECTORY UNITMOTION DETECTORCCTV COAXIAL CABLE OUTLET AND POWER OUTLETSECURITY CARD READERSECURITY CONTROL PANELSECURITY DOOR CONTACTSSECURITY EXIT PUSH BUTTONSECURITY KEYPADBIOSCAN ACCESS PADCAMERADUTY STATIONDESCRIPTIONMASTER STATIONSTAFF STATIONSTAFF LOCATOR STATIONSYMBOLNURSE CALL SYSTEMPATIENT STATION -SINGLE OUTLETEMERGENCY/BATH STATIONCEILING MOUNTED DOME LIGHTSECURITY DUTY STATIONSECURITY STAFF STATIONSECURITY MONITORSECURITY DOOR EGRESSPULL CORDPULL CORD WITH AUDIOAPATIENT STATION -SINGLE OUTLET WITHECODE/STAFF ASSIST BUTTONCWALL CHIME(APPLY TO ALL ELECTRICAL SHEETS)1. PROVIDE SUPPORT WIRES FOR ALL LIGHT FIXTURES. 2. COORDINATE INSTALLATION OF LIGHT FIXTURES WITH ARCHITECTURAL REFLECTED CEILING PLAN, HVAC EQUIPMENT, DUCTWORK, PIPING AND SUPPORTS.3. ELECTRICAL CONTRACTOR SHALL VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL.4. ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS TO FAMILIARIZE HIMSELF WITH EXTENT OF REMODELING / ALTERATION WORK.5. ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THE CURRENT ANSI / NFPA 70 WITH STATE AMENDMENTS, ENERGY CODE, ANSI / IEEE C2 AND ALL FEDERAL, STATE, LOCAL AND MUNICIPAL CODES AND ORDINANCES. THE ELECTRICAL SUBCONTRACTOR SHALL COMPLY WITH THE DIRECTIONS OF ALL AUTHORITIES HAVING JURISDICTION.6. INSTALL WORK USING PROCEDURES DEFINES IN NECA STANDARDS OF INSTALLATION. ALL WORK SHALL PRESENT A NEAT MECHANICAL APPEARANCE WHEN COMPLETED.7. REFER TO THE ARCHITECTURAL DRAWINGS FOR CEILING WORK BY THE GENERAL CONTRACTOR. COORDINATE ALL ELECTRICAL WORK.8. THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL FLOOR, WALL, AND CEILING PENETRATIONS TO COMPLETE HIS / HER WORK. PROVIDE PROPER FIRE SAFEING FOR ALL PENETRATIONS MADE. PROVIDE APPROPRIATE SEALANT (I.E. FIRESAFEING) TO MAINTAIN CONSTRUCTION INTEGRITY FOR ANY PENETRATIONS THROUGH FLOORS, STRUCTURAL CEILING, AND FIRE WALLS.9. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES TO ENSURE EFFECTIVE AND EFFICIENT OVERALL INSTALLATION.10. COORDINATE ALL ELECTRICAL SYSTEM DOWNTIME WITH THE OWNER AND OTHER TRADES. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE REMODELING / ALTERING OF THE EXISTING BUILDING. THE SPECIFIC AREA(S) BEING REMODELED / ALTERED AT ANY TIME ARE OBVIOUSLY EXCLUSIVE OF THE STATEMENT. SERVICES TO EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION INCLUDING POWER, FIRE ALARM, LIGHTING, TELEPHONE, ETC., DOWNTIME OF THESE SYSTEMS SHALL BE MINIMIZED. WEEKEND AND AFTER HOURS WORK MAY BE REQUIRED TO PREVENT OR MINIMIZE INTERFERENCE WITH OWNERS OPERATION.11. CONTRACTOR SHALL WORK CLOSELY WITH THE OWNER TO IDENTIFY ALL SYSTEMS WIRING, DEVICES, ETC., THAT MUST REMAIN OPERATIONAL DURING CONSTRUCTION. COORDINATE ALL DEMOLITION WITH THE OWNER PRIOR TO ANY DEMOLITION WORK.12. THE LOCATION OF NEW RECEPTACLES, PHONE / DATA JACKS, AND ROOM EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE. FINAL LOCATIONS WILL BE DETERMINED WITH THE ARCHITECT DURING THE CONSTRUCTION PHASE.13. IN REMODELED / ALTERED AREA ANY FEEDERS, CONDUITS, BRANCH CIRCUITS, SIGNAL AND TELEPHONE CIRCUITS, ETC., PASSING THROUGHOUT THE REMODELED / ALTERED AREAS TO SERVE (OR BE SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONS AND SHALL BE REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE ACCOMPLISHED IN THE REMODELED / ALTERED AREA.14. WHERE DEVICES ARE OMITTED FROM PRESENT BRANCH CIRCUITS, THE REMAINING DEVICE SHALL BE REWIRED. IF NEEDED AND AS REQUIRED, TO REMAIN IN THEIR RESPECTIVE CIRCUITS AND IN OPERATING CONDITION. 15. ALL NEW EQUIPMENT SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING.16. PHYSICAL SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE. COORDINATE ELECTRICAL WORK FOR THIS EQUIPMENT WITH THE OTHER TRADES.17. ALL BRANCH CIRCUITS SHALL UTILIZE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS. DO NOT COMBINE NEUTRAL CONDUCTORS. 18. ALL FEEDER NEUTRAL / GROUNDED CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. DERATE MULTIPLE CONDUCTORS IN A RACEWAY ACCORDINGLY WITH NEC TABLES.19. INSTALL ALL CONDUITS, RACEWAYS, AND CABLE TRAY FOR MAXIMUM HEAD CLEARANCE IN MECHANICAL AREAS.20. ALL DEVICES SHOWN ON THESE DRAWINGS TO BE REMOVED SHALL BE REMOVED COMPLETE INCLUDING ALL ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE UNLESS OTHERWISE NOTED. ALL CIRCUIT BREAKERS OR EQUIPMENT MADE SPARE BY THE DEMOLITION SHALL BE TURNED OFF AND MARKED SPARE. IT IS THE INTENT THAT ALL EXISTING ELECTRICAL DEVICES, CONDUIT, WIRING, ETC. IN THIS SPACE THAT ARE NOT REUSED AND ARE ABANDONED SHALL BE REMOVED COMPLETE. CONTRACTOR SHALL FIELD VERIFY EXACT REQUIREMENTS. NOT ALL DEVICES ARE SHOWN ON THIS DRAWING.21. ALL DEVICES AND LIGHT FIXTURES SHOWN TO BE REMOVED FROM EXISTING BLOCK WALLS THAT ARE NOT REUSED SHALL HAVE BLANK COVERS INSTALLED.22. ALL DEVICES SHOWN TO BE REMOVED FROM EXISTING WALLS THAT REMAIN SHALL HAVE DEVICES AND ASSOCIATED CONDUIT REMOVED AND WALL SHALL BE PATCHED.23. REFER TO MECHANICAL DEMOLITION PLANS FOR ALL EQUIPMENT THAT IS TO BE REMOVED. REMOVE ALL ASSOCIATED CONDUIT AND WIRING TO THESE DEVICES.24. TELEVISION SYSTEM: REMOVE ALL TELEVISION SYSTEM DEVICES AND WIRING IN AREAS OF DEMOLITION THAT ARE INSTALLED IN WALLS OR CEILINGS. ALL OTHER TELEVISION WIRING, EQUIPMENT AND DEVICES SHALL REMAIN. COORDINATE REMOVAL OF THIS SYSTEM AND ITS COMPONENTS WITH THE OWNER PRIOR TO WORK.25. TELEPHONE / DATA SYSTEM: REMOVE ALL TELEPHONE / DATA SYSTEM DEVICES AND WIRING IN AREAS OF DEMOLITION THAT ARE INSTALLED IN WALLS OR CEILINGS. ALL OTHER TELEPHONE / DATA WIRING, EQUIPMENT AND DEVICES SHALL REMAIN. COORDINATE REMOVAL OF THIS SYSTEM AND ITS COMPONENTS WITH THE OWNER PRIOR TO WORK.26. CCTV SYSTEM: REMOVE ALL CCTV SYSTEM DEVICES AND WIRING IN AREAS OF DEMOLITION THAT ARE INSTALLED IN WALLS OR CEILINGS. ALL OTHER CCTV WIRING, EQUIPMENT AND DEVICES SHALL REMAIN. COORDINATE REMOVAL OF THIS SYSTEM AND ITS COMPONENTS WITH THE OWNER PRIOR TO WORK.27. NURSE CALL SYSTEM: REMOVE ALL NURSE CALL SYSTEM DEVICES AND WIRING IN AREAS OF DEMOLITION THAT ARE INSTALLED IN WALLS OR CEILINGS. ALL OTHER NURSE CALL WIRING, EQUIPMENT AND DEVICES SHALL REMAIN. COORDINATE REMOVAL OF THIS SYSTEM AND ITS COMPONENTS WITH THE OWNER PRIOR TO WORK.28. FIRE ALARM SYSTEM: REMOVE ALL FIRE ALARM SYSTEM DEVICES AND WIRING IN AREAS OF DEMOLITION THAT ARE INSTALLED IN WALLS OR CEILINGS. ALL OTHER FIRE ALARM WIRING, EQUIPMENT AND DEVICES SHALL REMAIN. COORDINATE REMOVAL OF THIS SYSTEM AND ITS COMPONENTS WITH THE OWNER PRIOR TO WORK.29. ALL LIGHT FIXTURES SHOWN WITH EMERGENCY BATTERY BALLASTS/DRIVERS SHALL HAVE UNSWITCHED "HOT" WIRE INSTALLED TO EMERGENCY BATTERY BALLASTS/DRIVERS.30. NEW DEVICES SHOWN TO BE INSTALLED ON EXISTING DRYWALL WALLS SHALL BE INSTALLED FLUSH IN WALL WITH CONDUIT AND WIRING CONCEALED. CUT AND PATCH EXISTING WALLS AS REQUIRED.31. NEW DEVICES SHOWN TO BE INSTALLED ON EXISTING BLOCK WALLS SHALL BE INSTALLED SURFACE MOUNTED AND IN SURFACE MOUNTED WIREMOLD PAINTED TO MATCH WALL.32. WIRING SHALL BE INSTALLED ABOVE ACCESSIBLE CEILINGS AND IN DRYWALL WALLS WHERE POSSIBLE. 33. WIRING THAT IS TO BE INSTALLED IN AREAS WHERE THERE ARE NO CEILINGS SHALL BE INSTALLED EXPOSED. CABLING SHALL BE INSTALLED NEATLY AND AT RIGHT ANGLES TO STRUCTURE. WIRING SHALL BE INDEPENDENTLY SUPPORTED AS REQUIRED. WIRING SHALL NOT LAY OVER OTHER TRADES.34. NEW DEVICES SHALL MATCH EXISTING DEVICES AND COVERPLATES UNLESS OTHERWISED INDICATED.35. WHERE OCCUPANCY SENSORS ARE INDICATED ON PLANS, THE ENTIRE ROOM SHALL BE COVERED. MANUFACTURER IS RESPONSIBLE FOR SENSOR LAYOUT. ADDITIONAL SENSORS REQUIRED DUE TO LACK OF COVERAGE SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. PROVIDE QUANTITY AS REQUIRED. CEILING AND WALL MOUNTED SENSORS SHALL BE DUAL TECHNOLOGY TYPE. SENSORS SHALL INCLUDE ALL POWER SUPPLIES AND RELAYS NECESSARY TO CONTROL LIGHT FIXTURES IN ROOM / AREA. SENSORS SHALL OPERATE IN "VACANCY" MODE -MANUAL ON / AUTO OFF. TYPE OC SQUARE -INDICATES A WALL MOUNTED SINGLE CIRCUIT SENSOR WITH 1 SWITCH, TYPE ROUND OC INDICATES A CEILING MOUNTED SENSOR. PROVIDE A SET OF AUXILIARY CONTACTS ON ALL WALL AND CEILING MOUNTED OCCUPANCY SENSORS FOR SENSOR STATUS FOR TEMPERATURE CONTROL. 36. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR HIS OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTION, RELOCATING AND RECONNECTION OF EXISTING ELECTRICAL EQUIPMENT AND MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND REFINISHING, SHALL MATCH THE EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE.37. ALL WIRING (POWER, LIGHTING) NOT REUSED FOR REMODELING AREAS SHALL BE COMPLETELY REMOVED BACK TO ASSOCIATED PANELS.38. THE OWNER SHALL HAVE THE FIRST CHOICE TO ACCEPT EXISTING DEVICES BEING REMOVED.39. REMOVE ALL ABANDONED CONDUITS, BOXES AND WIRING WITHIN PROJECT AREA.40. FIRE ALARM SYSTEM SHALL BE MAINTAINED DURING PROJECT.41. CEILING MOUNTED DEVICES TO REMAIN SHALL BE SUPPORTED FROM STRUCTURE DURING CONSTRUCTION AND REINSTALLED IN NEW CEILING.42. ARRANGEMENTS SHALL BE MADE WITH OWNER REPRESENTATIVE TO COORDINATE FIRE ALARM SYSTEM OUTAGE.43. CONTRACTOR SHALL PROTECT EXISTING CABLES DURING ALL PHASES OF CONSTRUCTION.44. ALL DEVICES (EXIT SIGNS, FIRE ALARM, LIGHTING, ETC) THAT ARE TAKEN OUT OF SERVICE AND NOT REUSED SHALL BE RETURNED TO THE OWNER.45. ALL RECEPTACLES SHALL BE HOSPITAL GRADE.GENERAL NOTESHZHERTZArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO.DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:02 PMElectrical Symbols andAbbreviationsE0-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForREV. DATE
REF.JJJJJVVSSJCRCRCRCRCRCRCRCRCRCRCRCRSSSSSSSSVVSSSSSSMSSSSSSSDSSDSSD SDSSDSSDSDSSDSCRMSSDSDSSDSDSSSSSSDSSDSDSSDSSDSSDSDSSDSDSDSSVVSSSSDSDSDSMS1244.34.64.74.95678HJKLK.5CORRIDORC0C09GHNLA5GHCRA1GLCRA3GLEQA2GHEQA1GLLSA1GHLSA1GLNRA7GLNRA1GHNLA1GHNSBA1GHNSBA1GHNSBA2XGLNSBA1GLNSBA13TYP.GLNRA3ELECTRICALROOMC03245TYP.5TYP.6666667WAPREPAIR AREAC030ALOUNGEC026ASTAFF TOILETC026BBED STORAGEC030UNPACKINGC026CORRIDORC0C03LINENC027TRASHC028OFFICEC029ELEVATORELEV 9CORRIDORC0C04ELEVATORELEV 8ELEVATORLOBBYC0C06CORRIDORC0C05STAIRC3-LLCORRIDORC0C02CORRIDORC0C01CORRIDORC0C01CORRIDORC0C10MECHANICALROOMC031STAIRC3-LLFIREALARMPANEL(S)True NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:04 PMLower Level ElectricalDemolition PlanE1-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForPLAN NOTES1 DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES SHOWN AS DASHED, INCLUDING BUT NOTLIMITED TO LIGHTING, RECEPTACLES, FIRE ALARM DEVICES, EXIT SIGNS, NURSE CALL ETC.INSIDE DASHED LINE. REMOVE BACK TO SOURCE OR NEAREST JUNCTION BOX TO REMAIN.REFER TO E2-0 AND E3-0 FOR ADDITIONAL INFORMATION.2 EXISTING TO REMAIN.3 ALL ELECTRICAL EQUIPMENT AND DEVICES IN THIS ROOM ARE EXISTING TO REMAIN.4 DISCONNECT, REMOVE, RETAIN AND REINSTALL CEILING DEVICES IN CORRIDOR AS REQUIREDFOR ABOVE CEILING MECHANICAL WORK. REFER TO MECHANICAL SHEETS FOR ADDITIONALINFORMATION.5 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE SHOWN AS DASHED. MAINTAIN WIRING /CONDUIT IN AREA FOR REUSE. REFER TO E2-0 FOR ADDITIONAL INFORMATION.6 DISCONNECT AND REMOVE EXISTING LIGHT SWITCH SHOWN AS DASHED. MAINTAIN WIRING /CONDUIT IN AREA FOR REUSE. REFER TO E2-0 FOR ADDITIONAL INFORMATION.7 DISCONNECT, REMOVE, RELOCATE AND REINSTALL CONDUIT IN BED STORAGE AS REQUIREDFOR NEW PHARMACY AIR HANDLER AND ABOVE CEILING MECHANICAL WORK. REFER TOMECHANICAL SHEETS FOR ADDITIONAL INFORMATION. 1/8" = 1'-0"1Lower Level Electrical Demolition PlanREV. DATE
REF.OCOCOCOCOCOCDOCOCOCOCOCOCOCOCOCOCOCOCOCOCOCOC2222143544.34.64.74.95678HJKLK.5CORRIDORC0C09CORRIDORC0C10HIGH HAZARDBUFFERC025BANTEC025ANON-HAZARDBUFFERC025CPICKSTATIONC025DPHARMACISTC025OFFICEC025ECORRIDORC0C01UNPACKINGC026CORRIDORC0C03CORRIDORC0C04OFFICEC029LINENC027TRASHC028ELEVATORELEV 9ELEVATORELEV 8ELEVATORLOBBYC0C06CORRIDORC0C02CORRIDORC0C05STAIRC3-LLLOUNGEC026ASTAFF TOILETC026BELECTRICALROOMC032REPAIR AREAC030ABED STORAGEC030MECHANICALROOMC031F1 F1F1 F1 F1 F1F1F1F1 F1 F1F1 F1F1F1F1 F1 F1F2F2F2F2 F2F2 F2F2333TYP.5FXNLNLF1F1F1F1 F1 F1F1 F1 F1F1F1F1NLNLa a aaaaaaa aaa a ab bbbbb babF1NLF1cF1cF1cF1cF1cF1cF1cF1cF1cF1cF1cF1dF1dF1ddc4544433355F2F2F2F3F3GHLSA1- 2GHLSA1- 2GHLSA1- 2GHLSA1- 2GHLSA1- 2333366111GHLSA1- 2a33b33True NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:06 PMLower Level LightingPlanE2-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForPLAN NOTES1 EXISTING TO REMAIN.2 LIGHTING IN THIS ROOM SHALL FUNCTION AS AUTOMATIC ON / AUTOMATIC OFF VIA LOCALOCCUPANCY SENSOR.3 CONNECT NEW LIGHT FIXTURES IN THIS ROOM TO 277V, 20A, 1P CRITICAL POWER CIRCUIT FROMPANEL 'GHCRA1' THAT WAS MAINTAINED DURING DEMOLITION.4 CONNECT NEW LIGHT FIXTURES IN THIS ROOM TO 277V, 20A, 1P NORMAL POWER CIRCUIT FROMPANEL 'GHNLA1' THAT WAS MAINTAINED DURING DEMOLITION.5 CONNECT NEW LIGHT FIXTURE TO NEW 277V, 20A, 1P LIFE SAFETY POWER CIRCUIT FROM PANEL'GHLSA1'.6 CONNECT NEW PASS-THRU RECESSED WALL INDICATOR LIGHT FIXTURES TO NEAREST 120V,20A, 1P CRITICAL POWER RECEPTACLE CIRCUIT FROM PANEL 'GLCRA3'. REFER TO DETAIL ONSHEET E7-1 FOR ADDITIONAL INFORMATION. 1/8" = 1'-0"1Lower Level Lighting PlanREV. DATE
REF.42SVICCRCRCRCRCRCRCRCRCRCRCRCRSSSSSSVVSSSSSSMSSSSSSSDSSDSSD SDSSDSSDSDSSDSCRMSSDSDSSDSDSSSDSSDSDSSDSSDSSDSDSSDSDSDSSVVSSSSDSDSDSMSJ2S224SSSSJJJJ6102J22DDSDDRREF.JJJ4VSVICICVVICJ222SSSSARARAR222M31VFD-AHUPH44.34.64.74.95678HJKLK.5HIGH HAZARDBUFFERC025BCORRIDORC0C09PICKSTATIONC025DPHARMACISTC025OFFICEC025EANTEC025ANON-HAZARDBUFFERC025CGHNSBA1GHNSBA1GHNSBA2XGLNSBA1GLNSBA1GHNLA5GHCRA1GLCRA3GLEQA2GHEQA1GLLSA1GHLSA1GLNRA7GLNRA1GHNLA1UNPACKINGC026CORRIDORC0C03LINENC027OFFICEC029CORRIDORC0C04LOUNGEC026ASTAFF TOILETC026BREPAIR AREAC030AELECTRICALROOMC032CORRIDORC0C10CORRIDORC0C01CORRIDORC0C02ELEVATORELEV 8ELEVATORLOBBYC0C06ELEVATORELEV 9CORRIDORC0C05STAIRC3-LLBED STORAGEC030MECHANICALROOMC031TYP./SEE DETAIL2E3-0/SEE DETAIL2E3-0/SEE DETAIL2E3-01312121216FIREALARMPANEL(S)GLNRA312171920AHU-PH480V,3P5HPEMERGENCYVFD-AHUPH14GHEQA1- 2,4,61522GLEQA2- 5GLCRA3- 21,23,25GLNRA1- 1GLNRA1- 1GLNRA1- 1GLNRA1- 1GLNRA1- 3GLNRA1- 3GLNRA1- 3GLCRA3- 27,29,31GLNRA1- 5GLNRA1- 5GLCRA3- 338GLCRA3- 35GLCRA3- 37WAP423GLCRA3- 39GLCRA3- 412425GLCRA3- 8GLCRA3- 10GLCRA3- 102625GLEQA2- 11GLEQA2- 1127GLCRA3- 12GLCRA3- 122528284.34.64.74.95J256789101112HIGH HAZARDBUFFERC025BANTEC025ANON-HAZARDBUFFERC025C22566668111110101212121818518GLLSA1- 29GLLSA1- 29GLLSA1- 29GLCRA3- 1GLCRA3- 3GLCRA3- 5GLCRA3- 7GLCRA3- 9GLCRA3- 9GLCRA3- 9GLCRA3- 11GLCRA3- 11GLCRA3- 11GLCRA3- 11GLCRA3- 13GLCRA3- 1321GLCRA3- 15GLCRA3- 17GLCRA3- 17GLCRA3- 172525True NorthPlan NorthMOBHOSPITALCENTRAL PLANTArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesKEY PLANPharmacy RenovationAREA OF CONSTRUCTION91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:09 PMLower Level Power andSystems PlanE3-011700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Lower Level Power and Systems PlanPLAN NOTES1 EXISTING TO REMAIN.2 CONNECT INTERCOM WALL STATION COMPLETE. PROVIDE ADAPTORS, ALL ASSOCIATED ROUGH-INS ANDWIRING IN CONDUIT AS REQUIRED. INTERCOM WALL STATION SHALL BE AI-PHONE LE-SS-1G OR APPROVEDEQUAL. REFER TO DETAILS ON SHEET E7-1 FOR ADDITIONAL INFORMATION.3 CONNECT INTERCOM MASTER STATION COMPLETE. PROVIDE POWER SUPPLY AND ADAPTORS AS REQUIRED.PROVIDE ALL ASSOCIATED ROUGH-INS AND WIRING IN CONDUIT AS REQUIRED. INTERCOM SYSTEM SHALL BEAIPHONE LEF-3 OR APPROVED EQUAL. REFER TO DETAILS ON SHEET E7-1 FOR ADDITIONAL INFORMATION.4 TELE-POWER POLE PROVIDED WITH SYSTEMS FURNITURE. PROVIDE POWER AND TELECOMMUNICATIONCABLES AS REQUIRED FOR FURNITURE SYSTEM CONNECTION. COORDINATE EXACT LOCATION WITHFURNITURE SYSTEM SUPPLIER.5 CONNECT AUTO OPERATORS COMPLETE TO 120V, 20A, 1P LIFE SAFETY CIRCUIT SHOWN. PROVIDETOUCHLESS WAVE SENSOR PLATES. PROVIDE ALL ASSOCIATED ROUGH-INS AND CONTROL WIRING INCONDUIT AS REQUIRED. PROVIDE TOGGLE DISCONNECT SWITCH. DOORS SHALL BE INTERLOCKED SO THATONLY ONE DOOR CAN OPERATE AT A TIME.6 CONNECT FIRE ALARM DEVICES TO EXISTING FIRE ALARM SYSTEM COMPLETE. PROVIDE MODIFICATION TOEXISTING SYSTEM INCLUDING BUT NOT LIMITED TO PROGRAMMING, NAC PANELS, AND POWER TO NACPANELS. REFER TO DETAILS ON SHEET E7-1 FOR ADDITIONAL INFORMATION.7 RECEPTACLE AT +36" FOR REFRIGERATOR.8 ROUGH-IN AND CABLING FOR REFRIGERATOR MONITORING SYSTEM BY DIVISION 23.9 CONNECT REFRIGERATOR PASS-THRU COMPLETE TO 120V, 20A, 1P CRITICAL POWER CIRCUIT SHOWN PERMANUFACTURER'S REQUIREMENTS. VERIFY EXACT MOUNTING LOCATION AND HEIGHT WITH OWNER PRIORTO ROUGH-IN.10 CONNECT COMPLETE HOOD LIGHTS AND RECEPTACLES TO 120V, 20A, 1P CRITICAL CIRCUIT SHOWN PERMANUFACTURER'S REQUIREMENTS. VERIFY EXACT MOUNTING LOCATION AND HEIGHT WITH OWNER PRIORTO ROUGH-IN.11 RECEPTACLE AND TELECOM OUTLET FOR INTEGRAL HOOD MONITOR AND EQUIPMENT. CONNECT COMPLETEPER MANUFACTURER'S REQUIREMENTS. VERIFY EXACT MOUNTING LOCATION AND HEIGHT WITH OWNERPRIOR TO ROUGH-IN.12 CONNECT SPEAKERS TO EXISTING SOUND SYSTEM COMPLETE. REFER TO DETAILS ON SHEET E7-1 FORADDITIONAL INFORMATION.13 CONNECT PNEUMATIC TUBE STATION COMPLETE PER MANUFACTURER'S REQUIREMENTS 120V, 20A, 1PEQUIPMENT POWER CIRCUIT FROM PANEL 'GLEQA2' THAT WAS MAINTAINED DURING DEMOLITION.14 DISCONNECT PROVIDED BY EQUIPMENT MANUFACTURER. CONNECT AUXILIARY SET OF CONTACTS INDISCONNECT SWITCH TO VARIABLE FREQUENCY CONTROLLER ASSOCIATED WITH SPECIFIC MOTOR.PROVIDE CONTROL WIRING IN CONDUIT AS REQUIRED. PROVIDE ADDITIONAL SUPPORT STRUCTURE ASREQUIRED.15 AHU-PH LOCATED IN BED STORAGE ROOM, REFER TO MECHANICAL DRAWINGS FOR ADDITIONALINFORMATION. CONNECT TO 480V, 3P, 20A EQUIPMENT POWER CIRCUIT.16 AHU-PH VARIABLE FREQUENCY CONTROLLER LOCATED IN MECHANICAL ROOM. REFER TO MECHANICALDRAWINGS FOR ADDITIONAL INFORMATION. VERIFY EXACT LOCATION WITH OWNER PRIOR TO INSTALLATION.CONNECT TO 480V, 3P, 20A EQUIPMENT POWER CIRCUIT SHOWN. PROVIDE CONTROL WIRING IN CONDUIT ASREQUIRED. PROVIDE SUPPORT STRUCTURE AS REQUIRED.17 CONNECT NEW CAMERA TO EXISTING CCTV SYSTEM COMPLETE.18 PROVIDE FIRE ALARM ADDRESSABLE RELAY FOR AUTO OPERATORS. CONNECT TO EXISTING FIRE ALARMSYSTEM COMPLETE. PROVIDE ALL ASSOCIATED ROUGH-INS AND CONTROL WIRING IN CONDUIT ASREQUIRED.19 RECEPTACLE FOR NARCOTICS REFRIGERATOR. DEVICE(S) INSTALLED ABOVE COUNTER TOP AT +2" ABOVEBACKSPLASH TO BOTTOM OF DEVICE(S). COORDINATE EXACT MOUNTING HEIGHT WITH EQUIPMENT TO BEINSTALLED.20 POWER AND TELECOMMUNICATION BOXES FOR FURNITURE SYSTEM CONNECTION. PROVIDE (2) BOXES FORFURNITURE SYSTEM. ONE BOX FOR POWER CONNECTION AND ONE BOX FOR TELECOMMUNICATION WIRING.PROVIDE 1-1/4" CONDUIT FROM TELECOMMUNICATION BOX TO ABOVE CEILING WITH BUSHING. PROVIDE FLEXCONNECTIONS TO FURNITURE SYSTEM AS REQUIRED. COORDINATE COVER TO BE INSTALLED AND VERIFYCOVER TYPE WITH OWNER. COORDINATE EXACT LOCATION OF BOXES WITH FURNITURE SYSTEM SUPPLIER.21 CONNECT WALL PHONE COMPLETE TO EXISTING TELECOM SYSTEM.22 DISCONNECT AND REMOVE EXISTING AUTODOOR OPERATOR CIRCUITS FROM PANEL 'GLEQA2' ANDRECONNECT TO PANEL 'GLLSA1'. MODIFY / EXTEND EXISTING WIRING / CONDUIT AS REQUIRED. CONTRACTORSHALL FIELD VERIFY ALL AUTODOORS THAT ARE CONNECTED TO PANEL 'GLEQA2' AND COORDINATE ALLDOWNTIME WITH OWNER PRIOR TO ANY MODIFICATIONS.23 RECEPTACLE AT +36" FOR NARCOTICS CABINET.24 RECEPTACLE FOR NARCOTICS PRINTER. DEVICE(S) INSTALLED ABOVE COUNTER TOP AT +2" ABOVEBACKSPLASH TO BOTTOM OF DEVICE(S). COORDINATE EXACT MOUNTING HEIGHT WITH EQUIPMENT TO BEINSTALLED.25 DEVICE(S) INSTALLED ABOVE COUNTER TOP OR SINK AT +2" ABOVE BACKSPLASH TO BOTTOM OF DEVICE(S).COORDINATE EXACT MOUNTING HEIGHT WITH CASEWORK SUPPLIER.26 CONNECT TEMPERATURE CONTROL PANEL TO 120V,1P,20A EQUIPMENT POWER CIRCUIT SHOWN. PROVIDESINGLE-POLE DISCONNECT SWITCH.27 NEW SUPERVISORY CONTROL PANEL PROVIDED BY DIV 23. COORDINATE EXACT LOCATION WITHTEMPERATURE CONTROL CONTRACTOR PRIOR TO INSTALLATION.28 INSTALL DUCT MOUNTED SMOKE DETECTOR IN SUPPLY / RETURN DUCT WORK. PROVIDE 120V POWER ASREQUIRED FROM PANEL GLLSA1. 1/4" = 1'-0"2Enlarged Pharmacy Power and Systems PlanREV. DATE
J2278GG.3HELECTRICALROOMC6025X6LCRSBC16HCRSBC16LCRSBC16LLSDPC1X6LLSDPC16HLSDPC16HESBC1X6LEQDPC16LEQDPC16LLSC16LNRC26LEQC1ATSCRC1ATSLSC1ATSEQC1ATSEQMCCC1ATSEQMCCC26HEQDPC15MECHANICALROOMC6006HEQMCCC2678HJJ.41MECHANICALROOMC700STAIRC3-778HJJ.4EF-15278HJJ.43VFD-EF156HEQMCCC2- 5MECHANICALROOMC700STAIRC3-778HJJ.44480V,3P1.5HPEMERGENCYVFD-EF15EF-15EF-18Architecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:11 PMSeventh Floor andPenthouse Power andSystems PlanE3-711700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For 1/8" = 1'-0"1Sixth Floor Power and Systems Plan 1/8" = 1'-0"2Seventh Floor / Roof Electrical Demolition Plan 1/8" = 1'-0"3Penthouse Roof Electrical Demolition Plan 1/8" = 1'-0"4Seventh Floor / Roof Power and Systems Plan 1/8" = 1'-0"5Penthouse Roof Power and Systems Plan1. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDED CHANGES MAY HAVETAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Connected Load (Amps):2.0Total Connected Load (kVA):1.7222120191817161514131211 PROVISION-- -- -- -- -- -- -- -- -- -- 0.0 --10 PROVISION-- -- -- -- -- -- -- -- -- -- 0.0 --9 PROVISION-- -- -- -- -- -- -- -- -- -- 0.0 --8 PROVISION-- -- -- -- -- -- -- -- -- -- 0.0 --7 PROVISION-- -- -- -- -- -- -- -- -- -- 0.0 --6 AHU-HR1 RETURN*-- -- -- -- -- -- -- 3 -- 200 A 0.0 --5 EF-15 (VFD-EF15)*3 200 A 20 A 1.74 AHU-HR1 SUPPLY*-- -- -- -- -- -- -- 3 -- 200 A 0.0 --3 BC-2*-- -- -- -- -- -- -- 3 -- 200 A 0.0 --2 EF-8*-- -- -- -- -- -- -- 3 -- 200 A 0.0 --1 EF-7*-- -- -- -- -- -- -- 3 -- 200 A 0.0 --CKT Circuit Description FixedAdj.Inst.L S I G100%RatedPolesFrameSizeTripRatingLoad(kVA)Remarks:Thermal Mag Electronic TripBreaker InformationGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:800 AMounting:SurfaceWire:4Main Type:MCBSupplied From:Phase:3A.I.C. Rating:Location:MECHANICAL ROOM C600Voltage:480/277 WyeBranch:EquipmentDistribution Panel: 6HEQMCCC2PLAN NOTES1 DISCONNECT AND REMOVE EXISTING EXHAUST FAN MOTOR STARTER / DISCONNECT. MAINTAINALL ASSOCIATED WIRING AND CONDUIT IN AREA FOR REUSE.2 DISCONNECT AND REMOVE EXISTING EXHAUST FAN WIRING / CONDUIT AND CONTROL WIRINGBACK TO NEAREST POINT TO REMAIN. MAINTAIN ALL ASSOCIATED WIRING AND CONDUIT INAREA FOR REUSE.3 NEW EXHAUST FAN VARIABLE FREQUENCY CONTROLLER. PROVIDE ADDITIONAL SUPPORTSTRUCTURE AS REQUIRED TO MOUNT CONTROLLER. REFER TO MECHANICAL SCHEDULE SHEETFOR ADDITIONAL INFORMATION. VERIFY EXACT LOCATION PRIOR TO INSTALLATION.4 DISCONNECT PROVIDED BY EQUIPMENT MANUFACTURER. CONNECT AUXILIARY SET OFCONTACTS IN DISCONNECT SWITCH TO VARIABLE FREQUENCY CONTROLLER ASSOCIATED WITHSPECIFIC MOTOR. PROVIDE CONTROL WIRING IN CONDUIT AS REQUIRED. PROVIDE ADDITIONALSUPPORT STRUCTURE AS REQUIRED.5 ALL ELECTRICAL EQUIPMENT AND DEVICES IN THIS ROOM ARE EXISTING TO REMAIN.6 NEW SUPERVISORY CONTROL PANEL PROVIDED BY DIV 23. COORDINATE EXACT LOCATIONWITH TEMPERATURE CONTROL CONTRACTOR PRIOR TO INSTALLATION. CONNECT TO SPARE120V, 20A, 1P EQUIPMENT POWER CIRCUIT IN PANEL '6LEQC1'.ATSEQMCCC2REV. DATE
100AMLOGHNLA13P-4W480/277VF100GHNSBA21LOWER LEVEL 100AMLOGHLSA13P-4W480/277VF1006HLSDPB1100AMLOGHCRA13P-4W480/277VF1006HCRDPA1100AMLOGHEQA13P-4W480/277VF100GHEQDPA1200AMLOGLNRA13P-4W120/208VF200GLNSBA1200AMLOGLNRA73P-4W120/208VF200100AMLOGLLSA13P-4W120/208VF1006LLSDPB1100AMLOGLCRA33P-4W120/208VF1001LCRDPA1100AMLOGLEQA23P-4W120/208VF100GLEQDPA111111111FIRST FLOORSECOND FLOORTHIRD FLOORFOURTH FLOOR FIFTH FLOOR SIXTH FLOOR 277/4803P-4W6HEQMCCC2MCB800AF800ATSEQMCCC21CONDUIT SIZE AND QUANTITYFEEDER SIZING TABLEF20DESIGNATION12CONDUCTOR SIZE PER CONDUITNEUTRALPHASE &2P, 1G1P, 1N, 1GOR3P, 1G2P, 1N, 1GOR3P, 1N, 1G3P, 3N, 1G3P, 1N, 2G3/4"3/4"3/4"3/4"3/4"F30103/4"3/4"3/4"3/4"3/4"F40-F50F60F70-F80F90-F100F110F125F150F175F200F225F25083/4"3/4"3/4"1"3/4"63/4"3/4"1"1"1"43/4"1"1-1/4"1-1/4"1-1/4"31"1"1-1/4"1-1/2"1-1/4"21"1-1/4"1-1/4"1-1/2"1-1/4"11-1/4"1-1/4"1-1/2"2"1-1/2"1/01-1/4"1-1/2"1-1/2"2"2"2/01-1/4"1-1/2"2"2-1/2"2"3/01-1/4"2"2"2-1/2"2"4/01-1/2"2"2-1/2"2-1/2"2-1/2"2502"2"2-1/2"3"2-1/2"F3003502"2-1/2"3"3-1/2"3"F3505002-1/2"3"3"4"3"F4003/0(2) 2"(2) 2-1/2"(2) 3"(2) 2-1/2"F4504/0(2) 2"(2) 2-1/2"(2) 3"(2) 2-1/2"F500250(2) 2"(2) 2-1/2"(2) 3"(2) 2-1/2"F600350(2) 2-1/2"(2) 3"(2) 3-1/2"(2) 3"F700500(2) 3"(2) 3"(2) 4"(2) 3-1/2"F800350(3) 2-1/2"(3) 3"(3) 3-1/2"(3) 3"F900350(3) 2-1/2"(3) 3"(3) 3-1/2"(3) 3"F1000500(3) 3"(3) 3"(3) 4"(3) 3-1/2"F1200350(4) 2-1/2"(4) 3"(4) 3-1/2"(4) 3"F1600500(5) 3"(5) 3"(5) 4"(5) 3-1/2"F2000500(6) 3"(6) 3-1/2"(6) 4"(6) 3-1/2"F3013502-1/2"3"3"4"3"F4013/0(2) 2-1/2"(2) 3"(2) 3-1/2"(2) 3"FXXXF2500500(7) 4"(7) 4"(7) 4"(7) 4"F3000500(8) 4"(8) 4"(8) 4"(8) 4"GROUND12BUILDING1010108866666444332211/01/02/02/03/04/025021/0350500NOTES:1.20 AMP BRANCH CIRCUITS SHALL BE SIZED FOR VOLTAGE DROP. WIRE SIZES ARE NOT INDICATED ON THE DRAWINGS TO COMPENSATE FOR VOLTAGE DROP. FOR THESE CIRCUITS, CONTRACTOR SHALL UTILIZE WIRE SIZE SHOWN ABOVE FOR DISTANCES LISTED ABOVE.2.VOLTAGE DROP WIRE SIZES WILL BE STRICTLY INFORCED. CONTRACTOR SHALL SUBMIT A LIST OF CIRCUITS THAT WILL EXCEED THE DISTANCES ALLOWED AND INDICATE WIRE SIZE TO BE USED PRIOR TO ANY WIRE BEING INSTALLED.3.DO NOT SHARE NEUTRAL CONDUCTORS FOR ANY BRANCH CIRCUITS. ALL BRANCH CIRCUIT SHALL HAVE SEPARATE, INDEPENDENT NEUTRAL CONDUCTORS.4.ALL NORMAL POWER BRANCH CIRCUIT WIRING SHALL BE INSTALLED IN CONDUIT COMPLETE. 5.ALL EMGERGENCY POWER CIRCUIT WIRING SHALL BE INSTALLED IN CONDUIT COMPLETE.6.ALL CONDUIT PENETRATIONS THRU THE FLOOR SLAB SHALL BE MADE WITH CAUTION. CONTRACTOR SHALL COORDINATE ALL HOLE LOCATIONS WITH STRUCTURAL ENGINEER PRIOR TO CUTTING ANY NEW HOLES. NEW HOLES SHALL BE ADJUSTED AS REQUIRED TO MISS REBAR AS DETERMINED BY THE STRUCTURAL ENGINEER.7.VOLTAGE DROP IN NOT SHOWN ON THE DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR ADJUSTING ALL BRANCH CIRCUIT AND FEEDER SIZES TO COMPLY WITH STATE AND LOCAL VOLTAGE DROP REQUIREMENTS.A.VOLTAGE DROP ON ALL BRANCH CIRCUITS SHALL NOT EXCEED 3%.B.VOLTAGE DROP ON ALL FEEDERS SHALL NOT EXCEED 2%.277V200 FEET360 FEET120VFEEDER SIZE TO USEF20F30VOLTAGE DROP FOR 20A BRANCH CIRCUITS100 FEET150 FEETMAXIMUM DISTANCE ALLOWED550 FEET885 FEETF40-50F60240 FEET385 FEETArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:14 PMElectrical One-Line RiserDiagram and SchedulesE5-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForNO SCALE1ELECTRICAL ONELINE RISER DIAGRAMLIGHT FIXTURE SCHEDULE1FIXTURE TYPE FIXTURE NAMEDESCRIPTIONVOLTAGE LAMP MANFUACTURERF1 ARCHITECTURAL TROFFER 24"W X 48'L X 4"D DIE FORMED 20 GAUGE COLD ROLLED STEEL HOUSING. DIRECT / INDIRECT ANGLED RAILFIXTURE, FROSTED ACRYLIC CENTER OPTIC, 0-10V DIMMING DRIVER (10%-100%).277V LED4000 LUMENS38W3500KFINELITE - HPRFOCAL POINT - FEQLITHONIA - 2ALLCOLUMBIA - SEROR APPROVED EQUALF2 CLEAN ROOM TROFFER 24"W X 48'L X 5"D BAKED WHITE ENAMEL, COLD GAUGE STEEL, FLAT DOOR, 0.125 A12 LENS SMOOTH SIDE OUT,GASKETED, RATED FOR CLASS 10,000 CLEAN ROOM. 0-10V DIMMING DRIVER (10%-100%).277V LED8200 LUMENS70W3500KKURTZON KLKENALL CSEDOFAILSAFE - ENCNEWSTAR STARCLEAN22OR APPROVED EQUALF3 PASS-THRUINDICATOR LIGHTROUND 7" DIAMETER X 2.25"D STAINLESS STEEL FACEPLATE. PROVIDE WITH SQUARE OPTIC, FLUSH OPALACRYLIC LENS AND BRUSHED STAINLESS STEEL FINISH.277V RED LED WINONA - MARKER04FX EXIT SIGN SINGLE AND DOUBLE-FACE, ARCHITECTURAL, ACRYLIC EDGE-LIT EXIT SIGN WITH UNIVERSAL SURFACEMOUNTING CANOPY, END, BACK OR TOP.277V LED3.5WRED LETTERSSURE-LITES - ESLITHONIA - EDGDUAL-LITE - LEOR APPROVED EQUALPLAN NOTES1 EXISTING TO REMAIN.REV. DATE
Architecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:17 PMElectrical PanelSchedulesE6-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation For1. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:8 ATotal Conn. Current:8 ATotal Est. Demand:3000 VAReceptacle1000 VA 100.00% 1000 VATotal Conn. Load:3000 VAHVAC2000 VA 100.00% 2000 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):8.3 ATotal Connected Load (kVA):3.0 kVATotal Load:0.0 kVA 0.0 kVA 3.0 kVA41 ACP 17* 20 A 1 0.0 0.0 1 20 A SHIFTER VALVE MOTOR* 4239 ACP 16* 20 A 1 0.0 0.0 1 20 A SHIFTER VALVE MOTOR* 4037 REHEAT COIL TRANSFOMERS* 20 A 1 0.0 0.0 1 20 A OHD/LTS, BELL, SWING ARM LT DOCK* 3835 EXHAUST FAN* 20 A 1 0.0 0.0 1 20 A BACKUP LIGHTS - LOADING DOCK* 3633 RD PANEL* 20 A 1 0.0 0.0 1 20 A SPARE*3431 RD PANEL* 20 A 1 0.0 0.0 1 20 A CARD READER L211* 3229 CAMERA DOCK 3* 20 A 1 0.0 0.0 1 20 A CARD READER L21074*3027 PUMP P-HL3* 20 A 1 0.0 0.0 1 20 A CARD READER C1-LL* 2825 PUMP P-HL4* 20 A 1 0.0 0.0 1 20 A CARD READER L2001* 2623 LT/RECEPTACLE AHU-HL4* 20 A 1 0.0 0.0 1 20 A CARD READER L2107* 2421 CONTROL PANEL AHU-HL4* 20 A 1 0.0 0.0 1 20 A CARD READER L2110* 2219 SPARE* 20 A 1 0.0 0.0 1 20 A FIRE SHUTTER L2040* 2017 SPARE* 20 A 1 0.0 0.0 1 20 A FIRE SHUTTER C017* 1815 SPARE* 20 A 1 0.0 0.0 1 20 A GAS MANIFOLD C034* 1613 SPARE* 20 A 1 0.0 0.0 1 20 A GAS MANIFOLD C035* 1411 AHU-PH CONTROLS* 20 A 1 2.0 0.0 1 20 A ESS / CAMERA 7* 129 RECEPTACLE - L2083* 20 A 1 0.0 0.0 1 20 A ESS / CAMERA* 107 PTS - C033* 20 A 1 0.0 0.0 1 20 A ESS / CAMERA 8* 85 PTS - PHARMACY* 20 A 1 1.0 0.0 1 20 A ESS*63 PTS- L2040* 20 A 1 0.0 0.0 1 20 A ECS / CAMERA 5* 41 PTS - C017* 20 A 1 0.0 0.0 1 20 A ECS / CAMERA 6* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:120/208 WyeBranch:EquipmentBranch Panel: GLEQA21. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:6 ATotal Conn. Current:6 ATotal Est. Demand:2000 VATotal Conn. Load:2000 VAReceptacle2000 VA 100.00% 2000 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):5.6 ATotal Connected Load (kVA):2.0 kVATotal Load:1.0 kVA 0.6 kVA 0.4 kVA41 SURGICAL SPEC ENTRY SIGN* 20 A 1 0.0 0.0 1 20 A SPARE*4239 PROFES OFFICE ENTRY SIGN* 20 A 1 0.0 0.0 1 20 A SPARE*4037 WOMENS SERV ENTRY SIGN* 20 A 1 0.0 0.0 1 20 A EMERGENCY ENTRY SIGN* 3835 SPARE* 20 A 1 0.0 0.0 1 20 A LT - AHU*3633 SPARE* 20 A 1 0.0 0.0 1 20 A LT - AHU*3431 SPARE* 20 A 1 0.0 0.0 1 20 A L2030 DOCK - EF-19 & EF-20*3229 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*3027 SPARE* 20 A 1 0.0 0.0 1 20 A AHU LT & RECEPTACLES* 2825 SPARE* 20 A 1 0.0 0.0 1 20 A L2030 - RECEPTACLES* 2623 SPARE* 20 A 1 0.0 0.0 1 20 A L2030 - RECEPTACLES* 2421 SPARE* 20 A 1 0.0 0.0 1 20 A L2030 - RECEPTACLES* 2219 SPARE* 20 A 1 0.0 0.0 1 20 A WATER FEATURE VAULT* 2017 ---- -- 0.0 0.0 1 20 A WATER FEATURE VAULT* 1815 ---- -- 0.0 0.0 1 20 A OUTDOOR - RECEPTACLES* 1613 *60 A 3 0.0 0.0 1 20 A OUTDOOR - RECEPTACLES* 1411 L2087 - RECEPTACLES* 20 A 1 0.0 0.0 1 20 A OUTDOOR - RECEPTACLES* 129 L2087 - RECEPTACLES* 20 A 1 0.0 0.0 1 20 A OUTDOOR - RECEPTACLES* 107 L2087 - RECEPTACLES* 20 A 1 0.0 0.0 1 20 A OUTDOOR - RECEPTACLES* 85 PHARMACY RECEPTACLES* 20 A 1 0.4 0.0 1 20 A OUTDOOR - RECEPTACLES* 63 PHARMACY RECEPTACLES* 20 A 1 0.6 0.0 1 20 A OUTDOOR - RECEPTACLES* 41 OFFICE C025E RECEPTACLES* 20 A 1 1.0 0.0 1 20 A SPARE*2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:PANEL PROVIDED WITH DOUBLE LUGS*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:200 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:120/208 WyeBranch:NormalBranch Panel: GLNRA11. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:4 ATotal Conn. Current:4 ATotal Est. Demand:1500 VATotal Conn. Load:1500 VAReceptacle1500 VA 100.00% 1500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):4.2 ATotal Connected Load (kVA):1.5 kVATotal Load:0.0 kVA 0.0 kVA 1.5 kVA29 PHARMACY AUTODOORS* 20 A 1 1.5 0.0 1 20 A PAD 3 PANEL L2107* 3027 AUTODOOR* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 2825 AUTODOOR* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 2623 AUTODOOR* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 2421 AUTODOOR* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 2219 AUTODOOR* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 2017 AUTODOOR* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 1815 PORT* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 1613 CAMERA ON POLE* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107*1411 RUCT* 20 A 1 0.0 0.0 1 20 A PAD 3 PANEL L2107* 129 S.W. LIGHT POLES, CLEARANCE LIGHTS* 20 A 1 0.0 0.0 1 20 A FM200 PANEL L2012 PREACT. PAN... 107 S.E. LIGHT POLES, CLEARANCE LIGHTS* 20 A 1 0.0 0.0 1 20 A SMOKE/FIRE DAMPERS AHU HL3,HL4* 85 SOCK LIGHT CONTROLS* 20 A 1 0.0 0.0 1 20 A AUTODOOR* 63 PAD PERIMETER LIGHTS* 20 A 1 0.0 0.0 1 20 A DOOR HOLD L1060,L1107,L2010,L3010,L4017* 41 VIEW* 20 A 1 0.0 0.0 1 20 A DOOR HOLD L2031,C038,L2067,L2075* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:120/208 WyeBranch:Life SafetyBranch Panel: GLLSA11. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:43 ATotal Conn. Current:48 ATotal Est. Demand:15400 VAReceptacle13600 VA 86.76% 11800 VATotal Conn. Load:17200 VAHVAC3600 VA 100.00% 3600 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):47.7 ATotal Connected Load (kVA):17.2 kVATotal Load:5.5 kVA 5.8 kVA 5.9 kVA41 PHARMACY NARCOTICS REFRIGERATOR* 20 A 1 0.5 0.0 1 20 A SPARE*4239 PHARMACY NARCOTICS PRINTER* 20 A 1 0.8 0.0 1 20 A SPARE*4037 PHARMACY NARC. CAB (AUX)* 20 A 1 1.0 0.0 1 20 A *3835 PHARMACY NARC. CAB (MAIN)* 20 A 1 1.0 0.0 1 20 A *3633 PHARMACY INTERCOM* 20 A 1 0.5 0.0 1 20 A SPARE*3431 PHARMACIST SYSTEMS FURNITURE* 20 A 1 0.5 0.0 1 20 A SPARE*3229 PHARMACIST SYSTEMS FURNITURE* 20 A 1 0.5 0.0 1 20 A SPARE*3027 PHARMACIST SYSTEMS FURNITURE* 20 A 1 0.5 0.0 1 20 A SPARE*2825 PHARMACY PICK STATION FURNITURE* 20 A 1 0.5 0.0 1 20 A LOADING DOCK RECEPTACLES* 2623 PHARMACY PICK STATION FURNITURE* 20 A 1 0.5 0.0 1 20 A MATERIAL MANAGMENT RECEPTACLES* 2421 PHARMACY PICK STATION FURNITURE* 20 A 1 0.5 0.0 1 20 A MATERIAL MANAGMENT RECEPTACLES* 2219 C026 REFRIGERATOR* 20 A 1 0.0 0.0 1 20 A SPARE*2017 PHARMACY NON-HAZARD RECEPTACLES* 20 A 1 0.6 0.0 1 20 A C033C, C033B RECEPETACLES* 1815 PHARMACY ANTE ROOM PASS-THRU REF* 20 A 1 1.3 0.0 1 20 ASPARE*1613 PHARMACY ANTE ROOM PC AND PRINTER* 20 A 1 0.6 0.0 1 20 A SPARE*1411 PHARMACY ANTE ROOM RECEPTACLES* 20 A 1 0.8 0.8 1 20 A PHARMACY PICK STATION RECEPTACLES* 129 PHARMACY HIGH HAZARD RECEPTACLES* 20 A 1 0.6 0.4 1 20 A PHARMACY RECEPTACLES* 107 PHARMACY HIGH HAZARD... 20 A 1 1.5 0.2 1 20 A PHARMACY RECEPTACLES* 85 PHARMACY NON-HAZARD HOOD* 20 A 1 1.2 0.0 1 20 A C026 REFRIGERATOR* 63 PHARMACY NON-HAZARD HOOD* 20 A 1 1.2 0.0 1 20 A C026 REFRIGERATOR* 41 PHARMACY HIGH HAZARD HOOD* 20 A 1 1.2 0.0 1 20 A C026 REFRIGERATOR* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:120/208 WyeBranch:CriticalBranch Panel: GLCRA31. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:0 ATotal Conn. Current:0 ATotal Est. Demand:0 VATotal Conn. Load:0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):0.0 ATotal Connected Load (kVA):0.0 kVATotal Load:0.0 kVA 0.0 kVA 0.0 kVA41 ---- -- 0.0 0.0 -- -- --4239 ---- -- 0.0 0.0 2 20 A SITE LIGHTS* 4037 WATER FEATURE* 50 A 3 0.0 0.0 -- -- --3835 DOCK DOORS* 20 A 1 0.0 0.0 2 20 A SITE LIGHTS* 3633 ---- -- 0.0 0.0 1 20 A EXTERIOR LT AT DOCK* 3431 ---- -- 0.0 0.0 1 20 A LT - L3023* 3229 DOCK LEVELER* 20 A 3 0.0 0.0 -- -- --3027 ---- -- 0.0 0.0 -- -- --2825 DOCK HEATER 6* 20 A 2 0.0 0.0 3 20 A FESTOON SYSTEM RM L2071* 2623 ---- -- 0.0 0.0 1 20 A SIGN 116TH SREET* 2421 DOCK HEATERS 1,2,3* 20 A 2 0.0 0.0 1 30 A CART WASHER* 2219 LT - L2038* 20 A 1 0.0 0.0 1 20 A SPARE*2017 LT - 2054* 20 A 1 0.0 0.0 1 20 A SPARE*1815 LT - DOCK* 20 A 1 0.0 0.0 -- -- --1613 LT - C033B* 20 A 1 0.0 0.0 -- -- --1411 LT - L2031, C033A, C033C* 20 A 1 0.0 0.0 3 20 A TRASH COMPACTOR* 129 C019,C018,L2073 C030,C015,CO16,L2082* 20 A 1 0.0 0.0 1 20 A LT - CORRIDOR L2010* 107 RM L2083, C012, L2034, L2029, C035* 20 A 1 0.0 0.0 1 20 A LT - MAIN COMM.* 85 LT - LAB L2054 BLOOD BANK L206* 20 A 1 0.0 0.0 1 20 A LT - MATERIAL MANAGEMENT* 63 SPARE* 20 A 1 0.0 0.0 1 20 A LT - CORR L1026* 41 SPARE* 20 A 1 0.0 0.0 1 20 A LT - CORR. L2027,C011,C014 L2098,0-25B* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:480/277 WyeBranch:NormalBranch Panel: GHNLA11. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:1 ATotal Conn. Current:1 ATotal Est. Demand:488 VATotal Conn. Load:488 VALighting488 VA 100.00% 488 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):0.6 ATotal Connected Load (kVA):0.5 kVATotal Load:0.5 kVA 0.0 kVA 0.0 kVA29 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*3027 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2825 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2623 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2421 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2219 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2017 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*1815 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*1613 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*1411 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*129 LT - STAIR 6* 20 A 1 0.0 0.0 1 20 A SPARE*107 LT - CORRIDOR L2010* 20 A 1 0.0 0.0 1 20 A LT - CO18,L3023* 85 LT - MATERIAL MANAGEMENT* 20 A 1 0.0 0.0 1 20 A LT - STAIR 5* 63 LT-COR,C014,L2072,C013,L2304,C011,C033* 20 A 1 0.0 0.01 20 A LT - STAIR 4* 41 LT - COR. L2054,L2098,L025B,C012,L2083* 20 A 1 0.0 0.51 20 A PHARMACY LIGHTING* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:480/277 WyeBranch:Life SafetyBranch Panel: GHLSA11. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:0 ATotal Conn. Current:0 ATotal Est. Demand:0 VATotal Conn. Load:0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):0.0 ATotal Connected Load (kVA):0.0 kVATotal Load:0.0 kVA 0.0 kVA 0.0 kVA29 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*3027 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2825 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2623 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2421 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2219 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*2017 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*1815 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*1613 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*1411 SPARE* 20 A 1 0.0 0.0 -- -- --129 SPARE* 20 A 1 0.0 0.0 -- -- --107 SPARE* 20 A 1 0.0 0.0 3 60 A *85 SPARE* 20 A 1 0.0 0.0 1 20 A SPARE*63 LT - L2083 ELEC ROOM* 20 A 1 0.0 0.0 1 20 A SPARE*41 LT-MAIN COM & I.S. STORE" 20 A 1 0.0 0.0 1 20 A LT - BLOOD BANK* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:480/277 WyeBranch:CriticalBranch Panel: GHCRA11. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECT.Remarks:Total Est. Demand Current:8 ATotal Conn. Current:8 ATotal Est. Demand:6300 VATotal Conn. Load:6300 VAHVAC6300 VA 100.00% 6300 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):7.6 ATotal Connected Load (kVA):6.3 kVATotal Load:2.1 kVA 2.1 kVA 2.1 kVA29 ---- -- 0.0 0.0 -- -- --3027 ---- -- 0.0 0.0 -- -- --2825 VAC TUBE BLOWER #1* 20 A 3 0.0 0.0 3 20 A VAC TUBE BLOWER #2* 2623 ---- -- 0.0 0.0 -- -- --2421 ---- -- 0.0 0.0 -- -- --2219 TC3B,TC4A,TC5* 30 A 3 0.0 0.0 3 20 A BC-6*2017 SPARE* 20 A 1 0.0 0.0 -- -- --1815 SPARE* 20 A 1 0.0 0.0 -- -- --1613 TC1*20 A 1 0.0 0.0 3 20 A BC-5*1411 ---- -- 0.0 0.0 -- -- --129 ---- -- 0.0 0.0 -- -- --107 TCMOB,TC2C,TC2B* 60 A 3 0.0 0.0 3 20 A BC-4*85 ---- -- 0.0 2.1 -- -- --63 ---- -- 0.0 2.1 -- -- --41 CP-4* 20 A 3 0.0 2.1 3 20 A VFD-AHUPH 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:100 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:480/277 WyeBranch:EquipmentBranch Panel: GHEQA11. EXISTING ELECTRICAL PANEL BRANCH CIRCUITS ARE BASED ON EXISTING CIRCUIT DIRECTORIES WITHIN THE PANELS AND HAVE NOT BEEN FIELD VERIFIED. MANY UNRECORDEDCHANGES MAY HAVE TAKEN PLACE SINCE DIRECTORIES WERE LAST MODIFIED. FIELD VERIFY ALL CIRCUITS PRIOR TO WORK AND / OR MODIFICATIONS.2. PROVIDE A NEW UPDATED PANEL SCHEDULE AT THE COMPLETION OF THE PROJECTRemarks:Total Est. Demand Current:0 ATotal Conn. Current:0 ATotal Est. Demand:0 VATotal Conn. Load:0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Connected Load (Amps):0.0 ATotal Connected Load (kVA):0.0 kVATotal Load:0.0 kVA 0.0 kVA 0.0 kVA41 *20 A 1 0.0 0.0 1 20 A *4239 RECEPTACLES - WALL* 20 A 1 0.0 0.0 1 20 A *4037 RECEPTACLES - WALL* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L3025* 3835 RECEPTACLES - L2034, L2035* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2023 (MW)* 3633 RECEPTACLES - L2038* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L111* 3431 RECEPTACLES - L2038* 20 A 1 0.0 0.0 -- -- --3229 RECEPTACLES - L2046* 20 A 1 0.0 0.0 -- -- --3027 RECEPTACLES - C016, C015* 20 A 1 0.0 0.0 3 30 A RECEPTACLES - C033* 2825 RECEPTACLES - L2082* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2022* 2623 RECEPTACLES - C011* 20 A 1 0.0 0.0 1 20 A RECEPTACLES -C033A (CM)* 2421 RECEPTACLES - OUTDOOR* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2023 (MW)* 2219 RECEPTACLES - L2001* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - C330A (REF)* 2017 RECEPTACLES - C013* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2022* 1815 RECEPTACLES - C013* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2022* 1613 RECEPTACLES - L2094A* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2022* 1411 RECEPTACLES - L2049A* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - PHARMACY AUTOMED* 129 RECEPTACLES - L2083* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - PHARMACY AUTOMED* 107 RECEPTACLES - L2083* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - L2022* 85 RECEPTACLES - C012* 20 A 1 0.0 0.0 1 20 A *63 RECEPTACLES - C2-LL, C025B* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - C033B* 41 RECEPTACLES - 12098, 12051* 20 A 1 0.0 0.0 1 20 A RECEPTACLES - C033C* 2CircuitNumber Circuit Description Trip Poles A B C Poles Trip Circuit DescriptionCircuitNumberGeneral PanelComments:*BREAKER IS EXISITNGEnclosure Type:Type 1Ground:YesMain Rating:200 AMounting:SurfaceWire:4Main Type:MLOSupplied From:Phase:3A.I.C. Rating:Location:ELECTRICAL ROOM C032Voltage:120/208 WyeBranch:NormalBranch Panel: GLNRA7GLNSBA1GLNRA1GHNSBA26HLSDPB16LLSDPB16HCRDPA11LCRDPA1GHEQDPA1GLEQDPA1REV. DATE
SUPPORT STRUCTURENOTE:FOR STEEL STRUCTURAL SYSTEMCOMBINATION BEAM CLAMP ANDCONDUIT HANGER OR EQUIVALENTNOTE:1. FOR STEEL STRUCTURAL SYSTEM. 2. PROVIDE SEISMIC BRACING MINIMUM 40' ON CENTER WHEN THE CONDUITS SUPPORT IS BELOW 12" FROM STRUCTURE.UNISTRUT CHANNELOR EQUIVALENTCONDUIT CLAMP OREQUIVALENT SIZEAS REQUIREDTHREADED RODSIZE AS REQUIREDBEAM CLAMPSTRUTCLAMPOR EQUIVALENTBEAM CLAMPSTEEL CABLEAIRCRAFTHANGER WIRESTEEL CABLEAIRCRAFTHANGER WIRESEXISTING AUDIO PAGING RACKTYPICAL GENERAL PAGE SPEAKERNOTES:1.SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT, DUCTWORK, PIPING, STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER.2.REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY.3.PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS.4.WIRING INSTALLATION:A.WIRING INSTALLED ABOVE ACCESSIBLE CEILINGS MAY BE EXPOSED CABLE.B. WIRING INSTALLED IN WALLS, ABOVE INACCESSIBLE CEILINGS, OR AREAS WITH EXPOSED CEILINGS SHALL BE INSTALLED IN CONDUIT COMPLETE.MAIN COMM. ROOM L2102LOWER LEVELSSSSSSSTYPICAL EMERGENCY PAGE SPEAKERJUNCTION BOX (TYPICAL FOR ALL)CRAUTOMATIC DOOR OPERATOR IFDOOR IS EQUIPPED. INTERLOCKDOOR SECURITY SYSTEM TOOPERATE DOOR AS REQUIREDTYPICAL DOORSWITCH INDOOR FRAMEDOORTYPICALELECTRIC STRIKETYPICAL SECURITY CARD READER PROVIDED BY DOOR HARDWARESUPPLIER AND INSTALLED BY THEE.C. INSTALL AT +46" A.F.F. 2 GANGBACKBOX WITH 1 GANG PLASTER RING3/4"C TO ABOVE CORRIDORACCESSIBLE CEILINGNOTE:1.FOR A DOUBLE DOOR PROVIDE AN ADDITIONAL DOOR SWITCH AND ELECTRIC HINGE ROUGH-IN AND CONNECTION.LOWER LEVELFED FROM MDP120/208V 3P 4WPANEL 1LN1EQUIPMENT SERVEDINFORMATION PLATESOURCE OF POWERVOLTAGELAMACOID PLATENOTE:PROVIDE I.D. PLATE LABEL FOR ELECTRICAL EQUIPMENT SUCH AS MAIN SWITCHGEAR, SWITCHBOARD PANELBOARDS, AND TRANSFORMERS!WARNINGArc Flash HazardAppropriate PPE RequiredEquipment TypeGroundingWork DistanceAvailiable 3-Ph Bolted CurrentFlash Protection BoundaryIncident Energy at 11 inchesRisk CategoryEquipment Name:480V SwitchgearGrounded11 inches (300 mm)25 kA27 inches4.39 cal/cm22SwitchboardNOTE:PROVIDE WARNING LABEL FOR ALL ELECTRICAL EQUIPMENT SUCH AS MAIN SWITCHGEAR, SWITCHBOARDS, PANELBOARDS, AND TRANSFORMERS.MCFFRDRASTVAARSFFEXISTING FIRE ALARM CONTROL PANELTYPICAL FOR EACH FLOOR120VFIRE ALARM POWERPROVIDE SIGNALEXPANDER/AMPLIFIER POWERSUPPLY ON EACH FLOOR FORSIGNAL DEVICES. LOCATEEQUIPMENT IN ELECTRICALROOM.PROVIDE SPARE CAPACITY TOADD (2) SIGNAL DEVICES (TYP.OF EACH SIGNAL CIRCUIT)ADDRESSABLE RELAY FOR CONTROL PROVIDE ONE AT EACH AHU SUPPLY AND RETURN FAN STARTERS, AT EACH FIRE/SMOKE DAMPER AND AT EACH DOOR HOLD RELEASE DEVICEPROVIDE SPARE CAPACITYTO ADD 20% FUTURE DEVICES ON EACH INITIATION LOOPTYPICALFIRE/SMOKEDAMPERTYPICAL DOORHOLD/RELEASEDEVICETYPICALHVAC UNITSTARTERPROVIDE CONTROL WIRINGIN CONDUIT AS REQUIREDTO OTHER DEVICES SEEFLOOR PLANSNOTES:1.ALL FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT COMPLETE.2.REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITIES.3.EXISTING FIRE ALARM PANEL WORK SHALL INCLUDE ALL NEW CARDS, EQUIPMENT AND PROGRAMMING NECESSARY TO SUPPORT THE NEW DEVICES AS INDICATED. 4.LABEL ALL FIRE ALARM DEVICES AS DIRECTED BY THE OWNER WITH EXTERNAL TAGS AND LABELS ON DEVICE bASES.TYPICAL SMOKEDETECTOR WITHSOUNDER BASEBMS ROOM L4027ICICTYPICAL INTERCOM DOOR STATION LOCATED AT DOORS SHOWN. STATION SHALL BE FLUSH MOUNTED IN WALL. SIMILAR TO AI-PHONE LE-SS-1G.TYPICAL INTERCOMMASTER STATIONLOCATED AS SHOWN ON DRAWINGS. SIMILAR TO AI-PHONE LEF-3. POWER SUPPLYWIRING AS REQUIREDCONDUIT TO ABOVEACCESSIBLE CEILING.TERMINATE CONDUIT WITH BUSHINGMLOWER LEVELNOTES:1.SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT, DUCTWORK, PIPING,STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER.2.REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY.3.WIRING INSTALLATION:A.WIRING INSTALLED ABOVE ACCESSIBLE CEILINGS MAY BE EXPOSED CABLE.B. WIRING INSTALLED IN WALLS, ABOVE INACCESSIBLE CEILINGS, OR AREAS WITH EXPOSED CEILINGS SHALL BE INSTALLED IN CONDUIT COMPLETE.4.PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS.120VTO EMERGENCY POWER AS SHOWN ON DRAWINGS.REFER TO DETAIL ON THIS SHEET FOR ADDITIONAL INFORMATION. LOCATED AS SHOWN ON DRAWINGS. CAT 5E CABLE1-1/4" CONDUIT TO CABLE TRAY. TERMINATE CONDUITS WITH BUSHING. (TYPICAL) LOWER LEVELNOTES:1.SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT, DUCTWORK, PIPING,STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER.2.REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY.3.PROVIDE PLENUM RATED WIRE / CABLE AS REQUIRED.4.PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS.EXISTING DATA RACKNUMBER INDICATES QUANTITY OF CABLES TO BE INSTALLED2EXISTING CABLE TRAYTELECOMMUNICATIONS CABLE TO BE TERMINATED AT IDF BY CONTRACTOR. TELECOM EQUIPMENT PROVIDED BY OWNER AS REQUIRED.1WAPMAIN COMM. ROOM L2102CADDY SCREW GUN BRACKETNOTE: FOR METAL STUD WALL CONSTRUCTION ONLY.4" SQUARE BOXMETAL STUDSCONDUITBOX MOUNTING BRACKETNOTE: COORDINATE WITH GENERAL CONTRACTOR.ROOF DECKINGROOFPITCH POCKETGALVANIZED RAIN CAPGALVANIZED, ADJUSTABLECLAMP WITH ONE SCREWCONDUIT, SIZE AS REQUIREDFACE PLATE CONFIGURATIONDATA ONLY(1) 1-1/4" EMT CONDUIT WITH NYLON BUSHING STUBBED TO ACCESSIBLE CEILING4-11/16" x 4-11/16" SQUARE BOX 2-7/8" DEEP5-8 DATAOUTLETS4-11/16" x 4-11/16" SQUARE BOX2-7/8" DEEP2-GANG TILERING 1/2" DEEP(2) 1-1/4" EMT CONDUITS WITH NYLON BUSHING STUBBED TO ACCESSIBLE CEILING1-4 DATAOUTLETS1/2" DEEP TILE RING WIRING AS REQUIRED (TYP.)LOWER LEVELTO EMERGENCY POWER AS SHOWN ON DRAWINGS.NOTES:1.FLASHING RELAY MODULE SHALL BE 120V, MAXIMUM 60FPM. 2.PROVIDE UL LISTED NEMA 1 ENCLOSURE FOR FLASHING RELAY MODULE ABOVE ACCESSIBLE CEILING.3.REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY.4.PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS.120VWALL INDICATOR LIGHTFLASHING RELAY MODULETHREE WAY SWITCH INSIDE BUFFER ROOMTHREE WAY SWITCH INSIDE PHARMACY12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE SUPPORT CONNECTED TO STRUCTURE ABOVEJUNCTION BOXFLEXIBLE CONDUIT W/ #12 WIRE (6' MAX.)LAY-IN CEILINGSEISMIC CLIPLAY-IN CEILINGLAY-IN CEILINGLAY-IN CEILINGLIGHT FIXTUREArchitecture | Engineering | Interior Design1715 Magnavox WayFort Wayne, IN 46804260.432.9337930 North MeridianIndianapolis, IN 46204317.917.1190www.msktd.comSHEET TITLESHEET NUMBERSET DESCRIPTIONPROJECT NO. DATEMSKTD& AssociatesPharmacy Renovation91 S. Main Street, Suite 200Zionsville, Indiana 46077Phone: 1.317.927.8307www.genesis-engineering.com2/20/2017 12:42:20 PMElectrical DetailsE7-111700 N. Meridian Street | Carmel, Indiana 46032North Hospital6658 02-21-17A Renovation ForNO SCALE12" AND SMALLER CONDUIT SUPPORT DETAILNO SCALE22-1/2" AND LARGER CONDUIT SUPPORT DETAILNO SCALE3AUDIO PAGING DETAILNO SCALE4CARD ACCESS ROUGH-IN DETAILNO SCALE5ELECTRICAL EQUIPMENT I.D. LABELING DETAILNO SCALE6ELECTRICAL EQUIPMENT WARNING LABEL DETAILNO SCALE7FIRE ALARM SYSTEM SCHEMATICNO SCALE9PHARMACY INTERCOM DETAILNO SCALE10TELECOM SYSTEM DETAILNO SCALE11WALL BOX INSTALLATION DETAILNO SCALE12ELECTRICAL ROOF PENETRATION DETAILNO SCALE13FLUSH MOUNTED DATA OUTLETNO SCALE14PHARMACY INDICATOR LIGHT DETAILNO SCALE8LAY-IN LIGHT FIXTURE DETAILREV. DATE