HomeMy WebLinkAbout17050048 Building PlansRevision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV1.0
TITLE
SHEET
ROOF MOUNTED SOLAR ARRAY FOR
502 East Event Centre
502 East Carmel Drive
Carmel, IN 46032
NORTH
not to scale
VICINITY MAP
NORTH
not to scale
SITE PLAN
DRAWING INDEX
PV1.0 Title Sheet
PV2.0 Roof Layout
PV3.0 270.7 kW System
DC Array Diagrams (1 of 2)
PV3.1 270.7 kW System
DC Array Diagrams (2 of 2)
PV3.2 48.2 kW System
DC Array Diagrams
PV4.0 AC 1-Line Diagrams (1 of 2)
PV4.1 AC 1-Line Diagrams (2 of 2)
PV5.0 Details
PV6.0 Data Sheets
LOCATION OF WORK
270.7 kW SYSTEM
= 808 MODULES
48.2 kW SYSTEM
= 144 MODULE
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV2.0
ROOF
LAYOUT
NORTH
1" = 100'
Roof Layout
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 19
+
-
+
-
+
-
+
-
+
-
+
-
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
+
-
+
-
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
PV INVERTER #5 PV INVERTER #6
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
STRING OF 18
STRING OF 18
STRING OF 18
STRING OF 18
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
STRING OF 18
+
-
10 AWG COPPER
STRING OF 18
STRING OF 18
STRING OF 18
PV INVERTER #1
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
PLAN NOTES
2 SETS, (4) 750 KCMIL AL, 3/0 GND 4"C
(4) 400 KCMIL AL, 1/0 GND, 3"C
(3) #6 AWG COPPER, #10 GND, 1" C
(4) 2/0 AWG AL, #4 GND, 2"C
60 A 60A FUSE
60A Disconnect
36 kW
INVERTER
#1
60 A
60 A
60 A
60 A
60 A
NEW AC COMBINER PANEL
"PV-AC"
277 / 480V, 3PH, 4W, NEMA 1
60A FUSE
60A Disconnect
60A FUSE
60A Disconnect
60A FUSE
60A Disconnect
60A FUSE
60A Disconnect
60A FUSE
60A Disconnect
EXISTING MAIN
DISTRIBUTION PANEL
TO EXISTING LOADS
TO EXISTING LOADS
TO EXISTING LOADS
TO EXISTING LOADS
TO EXISTING LOADS
TO EXISTING LOADS
SUPPLY CB IN
EXISTING MAIN DISTRIBUTION
PANEL (MDP)
3-POLE
DISCONNECT
SWITCH
60 A
60 A
60 A
60 A
60 A
60 A
300 KVA
480/208 VAC
1000A CB
IN EXISTING MDP
NEW BIDIRECTIONAL
CT-RATED UTILITY
METER
UTILITY GRID
208/120V
3PH, 4W
Not to Scale
270.7 kW System - AC Electrical 1-Line Diagram
TO EXISTING MAIN
DISTRIBUTION
PANEL (MDP)
STRING CONDUCTORS
FROM ROOF
DATA
MONITORING
WALL MOUNTED
DC TO AC INVERTER #1
WALL MOUNTED
DC TO AC INVERTER #2
WALL MOUNTED
DC TO AC INVERTER #3
1'-0" MIN. 1'-0" MIN.
WIRE WAY
NEW AC VOLTAGE
COMBINER PANEL
WALL MOUNTED
DC TO AC INVERTER #4
WALL MOUNTED
DC TO AC INVERTER #5
WALL MOUNTED
DC TO AC INVERTER #6
1'-0" MIN. 1'-0" MIN.
WIRE WAY
AC
SWITCH
300 KVA
TRANSFORMER
Panel Layout for
270.7 kW System
Panel Layout for
48.2 kW System
45 KVA
TRANSFORMER
AC
SWITCH
WIRE WAY
WALL MOUNTED
DC TO AC INVERTER #1
STRING CONDUCTORS
FROM ROOF
AC
SWITCH
TO EXISTING MAIN
DISTRIBUTION
PANEL (MDP)
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
UNISTRUT CONDUIT CLAMP
12 GA GALVANIZED STEEL
SIZED AS APPROPRIATE
DURA-BLOK
SUPPORT BASE
WIT CHANNEL
OR EQUAL
EATON XJG-EMT (OR EQUAL) CONDUIT EXPANSION
JOINT WITH INTERNAL GROUNDING FOR EMT CONDUIT.
INSTALL EVERY 30 FEET OR STRAIGHT CONDUIT RUN
CONDUIT
10'
MAX.
SCALE 1-1/2" = 1'-0"
CONDUIT EXPANSION JOINT
MODULE FRAME
(ALUMINUM)
PHOTOVOLTAIC MODULE
MINIMUM 10MM GAP
BETWEEN MODULES
SS WIRE MANAGEMENT CLIP
SCALE 1-1/2" = 1'-0"
CONDUIT EXPANSION JOINT
SCALE 1/2" = 1'-0"
ROOF MODULE SECTION
14.31
63.36
6.73 6.73
26.92
28.40
32.20
25% 25%
SHADE LINE
WINTER SOLSTICE
9AM SOLAR TIME
2.25 X 14.31 = 32.2
CONDUIT
TOP OF ROOF
DURA-BLOK
SUPPORT BASE WITH
CHANNEL OR EQUAL
SUPPORT CONDUIT CLAMP
12 GA GALVANIZED STEEL
SIZED AS APPROPRIATE
4"
MIN.
SCALE 3" = 1'-0"
CONDUIT ROOF SUPPORT
SCHLETTER TOP-DOWN CLAMP
W/ INTEGRATED EGC BOND
MODULE TO RAIL BOND
SCHLETTER TOP DOWN MOUNT
STAINLESS STEEL
HARDWARE
PHOTOVOLTAIC MODULE
MINIMUM 10MM GAP
BETWEEN MODULES
MODULE FRAME
(ALUMINUM)
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV6.0
DATA
SHEETS
Mono-Crystalline Photovoltaic Module DC to AC Inverter
ALUMINUM, RAIL
1 EGG GROUND LUG INSTALLATION FOR ARRAY: USE ONLY UL467 LISTED
"DIRECT BURY" LUGS, ILSCO GBL-467 OR BURNDY CL50-1TN. MOUNT THE LUGS
WITH S.S. #10X32 HARDWARE. TORQUE TO MANUFACTURER'S INSTRUCTIONS.
RAIL OR PURLIN SPLICE IS NOT AN ELECTRICAL BOND
BONDING BETWEEN SECTIONS OF TRAIL OR PURLIN MAY BE MADE VIA THE
EGC OR THROUGH THE USE OF UL LISTED JUMPERS. USE ONLY UL467 LISTED
"DIRECT BURY" LUGS, ILSCO GBL-467 OR BURNDY CL50-1TN. (OR EQUIVALENT).
2
3
2 1
3
N.T.S.
RAIL GROUNDING DETAIL
#6 AWG BRAIDED
GROUNDING STRAP
(E.G. ILSCO) TO BOND
RAIL SPLICES
STAINLESS STEEL
HARDWARE
ALUMINUM, RAIL
NTS
RAIL TO RAIL BOND
EGC BARE COPPER
STAINLESS STEEL WASHER
WITH UL-LISTED BOND TO
ANODIZED RAIL
STAINLESS STEEL
HARDWARE
ALUMINUM RAIL
BY OTHERS
GROUND LUG INSTALLATION FOR
ARRAY: INSTALL TO THE RAIL PER
MANUFACTURERS INSTRUCTIONS. USE
ONLY UL467 LISTED "DIRECT BURY
LUGS, ILSCO GBL-67 OR BURNDY
CL50-1TN. (OR EQUIVALENT)
N.T.S.
EGC TO RAIL BOND
CROSS SECTION
3"
EVERY 50'-0" MAX.
0'-1"
EVERY 50'-0" MAX.
#6 AWG BRAIDED GROUNDING STRAP
(E.G. ILSCO) TO BOND RAIL SPLICES.
PROVIDE SLACK FOR RAIL EXPANSION
AND CONTRACTION.
STAINLESS STEEL HARDWARE
ALUMINUM RAIL
PHOTOVOLTAIC MODULE
MINIMUM 10MM GAP
BETWEEN MODULES
MODULE FRAME
(ALUMINUM)
RAIL SPLICE
FASTEN SPLICE TO RAIL
(ONE SIDE ONLY AT
EXPANSION JOINT)
GROUND ROD
GEC
ENGINEERED SUBGRADE
EXOTHERMIC WELD OR
MECHANICAL CONNECTION
CAST IRON COVER MARKED
"GROUND ROD"
FINISHED GRADE
OR PAVING
N.T.S.
GROUND ROD DETAIL
N.T.S.
RAIL SPLICE AT EXPANSION JOINT
N.T.S.
GROUNDING/ MOUNTING DETAIL
GROUNDING ELECTRODE
[690.47D]
FINISHED PAVING.
SEE TRENCH DETAIL AT
SWEEP. THIS SHEET.
DC COMBINER
TO ARRAY DC CONDUIT
CANOPY POST BY OTHERS
TO INVERTER IN BUILDING
MIN. #6 COPPER BARE GROUND FROM
LISTED LUG TO GROUNDING
ELECTRODE. PLACE LUG AT
LOCATION LEAST TO BE EXPOSED TO
DAMAGE. EXOTHERMIC WELD OR
EQUIVALENT.
OPTIONAL 1/2" CONDUIT TO
PROTECT GEC. BOND GEC AT EACH
END IF METALLIC
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV5.0
DETAILS
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV4.1
AC 1-LINE
DIAGRAMS
Sheet 2 of 2
150A CB IN
EXISTING MAIN
125A FUSE DISTRIBUTION PANEL
200A Disconnect
45 KVA
480V DELTA / 208V WYE
60A FUSE TRANSFORMER
60A Disconnect
36 kW
INVERTER
#7
36 kW
INVERTER
#2
36 kW
INVERTER
#3
36 kW
INVERTER
#4
36 kW
INVERTER
#5
36 kW
INVERTER
#6
Not to Scale
48.2 kW System - AC Electrical 1-Line Diagram
GENERAL NOTES
A. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR INSTALLING ALL
INDICATED EQUIPMENT TO CODE COMPLIANT CLEARANCES. PROVIDE
SUBMITTALS AS INDICATED IN SPECIFICATIONS TO PROPERLY
COORDINATE PHYSICAL LOCATIONS OF NEW AND/OR EXISTING
EQUIPMENT.
B. REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS AND COMPLETE CONTRACTUAL OBLIGATIONS.
C. THE ELECTRICAL CONTRACTOR SHALL PROVIDE FOR AND
COORDINATE ALL TESTING AND INSPECTIONS REQUIRED BY THE
AUTHORITY HAVING JURISDICTION, AND SHALL PROVIDE WRITTEN
REPORTS TO THE ENGINEER OF ALL RESULTS AND INSPECTION REPORTS
FOR THIS SCOPE.
KEYED NOTES
1. ALL EQUIPMENT SHALL BE INSTALLED AND LABELED IN ACCORDANCE
WITH THE NEC AND ALL APPLICABLE REQUIREMENTS OF THE SERVING
ELECTRICAL UTILITY COMPANY AND OF THE LOCAL AUTHORITY
HAVING JURISDICTION.
2. METALIC CONDUIT SHALL USE RAIN-TIGHT FITTINGS.
3. GEC TO BE INSTALLED AS REQUIRED BY MANUFACTURER'S
INSTRUCTIONS AND NEC 690.47.
DISCONNECT SWITCH
1000A
450A
DISCONNECT SWITCH
WITH FUSE
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV4.0
AC 1-LINE
DIAGRAMS
Sheet 1 of 2
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
G _ +
Not to Scale
PV String of 18 Modules
10 AWG COPPER, 10 AWG COPPER
BARE
KEYED NOTES
1. CONDUCTORS MUST BE SECURED IN PLACE WITH LASTING MEANS
SUCH AS STAINLESS STEEL CLIPS AND S. S. TIE WRAPS. E. G. HEYCO
S.S. CLIPS AND HEYCO SUNBUNDLER CABLE TIE.
2. EGC CONNECTED TO MODULE FRAME BY SELF-GROUNDING
THROUGH RACKING SYSTEM. MODULE BOND TO RAIL EGC MUST BE
UL LISTED. BONDING BETWEEN SECTIONS OF RAIL MAY BE MADE
VIA THE EQUIPMENT GROUNDING CONDUCTOR OR THROUGH UL
LISTED JUMPERS.
3. MC-4 PV CONNECTOR COMPATIBLE WITH CELLS MODULES, LOCATE IN
SHADE.
4. WATER-PROOF STAIN RELIEF MUST BE USED WHEN ENTERING J-BOX OR
RACEWAY.
5. IRREVERSIBLE SPLICE (E.G. ERICO HAMMERLOCK).
6. EXOTERMIC WELD (E.G CADWELD) OR UL LISTED METHOD.
GENERAL NOTES
A. FOLLOW MANUFACTURER'S SUGGESTED INSTALLATION PRACTICES AND
WIRING SPECIFICATIONS.
B. &21'8&72566+$//%(5$7('$1'/$%(/('´681/,*+7
5(6,67$17µ:+(11273527(&7('%<5$&(:$<6
C. WIRING SHALL COMPLY WITH NEC 690.31 (PV WIRING METHODS).
D. EGC MUST BE CONTINUOUS AND INSTALLED TO ALLOW FOR MODULE
REMOVAL WITHOUT INTERRUPTING CONTINUITY >
@
E. MAINTAIN DISTANCE ABOVE ROOF FOR ALL CONDUITS
(310.15B2C)>3.5"
STRING VOLTAGES
INVERTER SPECIFICATION
20 PANELS
19 PANELS
18 PANELS
17 PANELS
920.80 V
874.76 V
828.72 V
782.68 V
6x SUNGROW SG36KU
MAX AC POWER RATING
MAX INPUT VOLTAGE
36 KW
1000 V
WIRE SCHEDULE
STRING 42x 10 AWG 4360 Pt
MODULE SPECIFICATION
808x NEO SOLAR POWER D5H 335 E4A
STC RATING 335 W
Vmp 37.47 V
Imp 8.96 A
Voc 46.04 V
Ioc 9.41 A
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV3.2
48.2 kW System
DC ARRAY
DIAGRAMS
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
G _ +
G _ +
Not to Scale
PV String of 20 Modules
Not to Scale
PV String of 19 Modules
10 AWG COPPER, 10 AWG COPPER
BARE
10 AWG COPPER, 10 AWG COPPER
BARE
+ -
G
STRING OF 19
+
-
10 AWG COPPER
STRING OF 19
+
-
10 AWG COPPER
STRING OF 19
+
-
10 AWG COPPER
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 19
+
-
+
-
+
-
+
-
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
STRING OF 19
+
-
10 AWG COPPER
STRING OF 19
+
-
10 AWG COPPER
STRING OF 19
+
-
10 AWG COPPER
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV3.1
270.7 kW
System
DC ARRAY
DIAGRAMS
Sheet 2 of 2
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
+ -
G
G _ +
G _ +
Not to Scale
PV String of 20 Modules
Not to Scale
PV String of 18 Modules
10 AWG COPPER, 10 AWG COPPER
BARE
10 AWG COPPER, 10 AWG COPPER
BARE
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 18
STRING OF 18
STRING OF 18
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
PV INVERTER #1
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 18
STRING OF 18
STRING OF 18
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 18
STRING OF 18
STRING OF 18
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 20
STRING OF 18
STRING OF 18
STRING OF 18
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
DC SIDE
AC SIDE
R
S
T
N
L1
L2
L3
N
PE
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
10 AWG COPPER
KEYED NOTES
1. CONDUCTORS MUST BE SECURED IN PLACE WITH LASTING MEANS
SUCH AS STAINLESS STEEL CLIPS AND S. S. TIE WRAPS. E. G. HEYCO
S.S. CLIPS AND HEYCO SUNBUNDLER CABLE TIE.
2. EGC CONNECTED TO MODULE FRAME BY SELF-GROUNDING
THROUGH RACKING SYSTEM. MODULE BOND TO RAIL EGC MUST BE
UL LISTED. BONDING BETWEEN SECTIONS OF RAIL MAY BE MADE
VIA THE EQUIPMENT GROUNDING CONDUCTOR OR THROUGH UL
LISTED JUMPERS.
3. MC-4 PV CONNECTOR COMPATIBLE WITH CELLS MODULES, LOCATE IN
SHADE.
4. WATER-PROOF STAIN RELIEF MUST BE USED WHEN ENTERING J-BOX OR
RACEWAY.
5. IRREVERSIBLE SPLICE (E.G. ERICO HAMMERLOCK).
6. EXOTERMIC WELD (E.G CADWELD) OR UL LISTED METHOD.
GENERAL NOTES
A. FOLLOW MANUFACTURER'S SUGGESTED INSTALLATION PRACTICES AND
WIRING SPECIFICATIONS.
B. &21'8&72566+$//%(5$7('$1'/$%(/('´681/,*+7
5(6,67$17µ:+(11273527(&7('%<5$&(:$<6
C. WIRING SHALL COMPLY WITH NEC 690.31 (PV WIRING METHODS).
D. EGC MUST BE CONTINUOUS AND INSTALLED TO ALLOW FOR MODULE
REMOVAL WITHOUT INTERRUPTING CONTINUITY >
@
E. MAINTAIN DISTANCE ABOVE ROOF FOR ALL CONDUITS
(310.15B2C)>3.5"
STRING VOLTAGES
INVERTER SPECIFICATION
20 PANELS
19 PANELS
18 PANELS
17 PANELS
920.80 V
874.76 V
828.72 V
782.68 V
6x SUNGROW SG36KU
MAX AC POWER RATING
MAX INPUT VOLTAGE
36 KW
1000 V
WIRE SCHEDULE
STRING 42x 10 AWG 4360 Pt
MODULE SPECIFICATION
808x NEO SOLAR POWER D5H 335 E4A
STC RATING 335 W
Vmp 37.47 V
Imp 8.96 A
Voc 46.04 V
Ioc 9.41 A
PV INVERTER #2
PV INVERTER #3 PV INVERTER #4
Revision
Project No.
Produced
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of Johnson Melloh
Solutions. They shall be used only with respect to this project and
are not to be used on any other project or work without prior
written permission from the Johnson Melloh Solutions.
3-15-17
2016-463
Date
ISSUED FOR PERMITS
Description
502 East Event Centre
502 E Carmel Drive, Carmel, Indiana
Photovoltaic System for
tmk
PV3.0
270.7 kW
System
DC ARRAY
DIAGRAMS
Sheet 1 of 2