PGE: E.C. SHALL FURN. &INST. GROUND ROD (POWER GROUND
ELECTRODE) AT 36" BELOW FIN. GRADE.
TBG: E.C. SHALL FURN. &INST. 1- #2 AWG BARE SOLID TINNED COPPER GND.
WIRE FROM TOWER LEG BASE PLATE TO (EER). CONNECTION TO TOWER
LEG BASE PLATE SHALL BE MECHANICAL AND (EER) SHALL BE CADWELD.
TEG: E.C. SHALL FURN. &INST. #2 AWG BARE SOLID TINNED COPPER GND.
WIRE (TELEPHONE ENTRANCE GROUND) FROM (TGE) THRU INSTALLED 3"
PVC CONDUIT TO PLYWOOD TELEPHONE MOUNTING BOARD LOCATED ON
BLDG. INTERIOR WALL. CONNECTION TO (TGE) SHALL BE CADWELD AND
LOOP AND ATTACH TO PLYWOOD BOARD.
TGE: E.C. SHALL FURN. & INST. GROUND ROD (TELCO GROUND
ELECTRODE) AT 36" BELOW FIN. GRADE.
TWG: E.C. SHALL FURN. & INST. 2 - #2 AWG BARE SOLI
oo'
TWGG - SEE
DETAIL 5 ON
E-2.
CONTRACTOR SHALL VERIFY
EXISTING TOWER SACC f%0ni inln
EXISTING TOWE
GROUND RING
EXISTING MON,
NEW ICE BRIDGE
SUPPORT (TYP.3)
/ +V
l
\ / x
x Ll - E-3
x NEW PREFABRICATED RADIO
EQUIPMENT BUILDING (BUILDING
DWGS. SUPPLIED BY MFR.)
x
IBOND
x x x x x IRDL x I
TWG -
TO TOWER GROUND
RING (TYP. OF 2)
TO BE CADWELD.
CONTRACTOR SHALL INSTALL NEW
GPS ANTENNA, COAX AND DIN
FEMALE CONNECTOR GROUND
COAX AND ALL ICE BRIDGE
POSTS.
-x x x x x x/---X-X1
x
x SEE INTERIOR/EXTERIOR
TWG
x CADWELD
SG CONNECTION
(TYP-)
A H x
-� SG ACH IRDL GROUND TEST WELL
- SEE DETAIL 8 ON E-2.
x
CEPSG
GRE (TYP.)
x
CSG
IBSG HALO FURNISHED WITH
BBO TEG x PREFABRICATED RADIO
TGE BBG EQUIPMENT BUILDING
IRDL IN EER
CONDUIT I (TYP )
'-MG
B
PGE
C
IRDL
EXISTING TELCO PEDESTAL
(5490F)
GROUNDING DETAIL 1 ON E-2.
x
x
FG
ELECTRICAL SITE PLAN
1' = 5'
NEW UNDERGROUND ELECTRIC SERVICE
- SEE DETAILS ON SHEET E-2, & E-3.
- SEE GENERAL NOTE 6 ON SHT. A-2
SEE SERVICE
ENTRANCE
DETAIL 4 ON
SHT. E-2,
NEW POWER &TELCO
METER BOARD STRUCTURE.
- INSTALLED BY CONTRACTOR.
- SEE GROUNDING DETAIL 3 ON E-3.
CONTRACTOR SHALL STUB UP
CONDUIT FOR TELCO & ELEC SERVICE,
EXISTING POWER POLE
EXISTING TRANSFORMER
(25-1 Bl)
NEW UNDERGROUND TELEPHONE SERVICE.
- SEE DETAIL ON E-2 & E-3.
- SEE GENERAL NOTE 6 ON SHT. A-2
7, GROUND BARS (TWGG &CEPSG) SHALL BE 1/4' x 4" x 24" SOLID COPPER.
PROVIDE LUG HOLES PER VERIZON STANDARDS.
8. BARE COPPER CONDUCTORS SHALL NOT BE INSTALLED WHERE THEY MAY BE IN
CONTACT WITH GALVANIZED METALS. THE CONDUCTORS SHALL BE INSULATED OR
ENCLOSED IN PVC CONDUIT OR INSTALLED WITH STANDOFF SUCH THAT NO CONTACT
BETWEEN DISSIMILAR METALS MAY TAKE PLACE.
9. CONNECTION OF COPPER CONDUCTORS TO GALVANIZED METAL OR ALUMINUM SHALL BE
AVOIDED. BRASS OR STAINLESS STEEL LUGS OR BARS SHALL BE USED FOR THESE
CONNECTIONS.
10. NO SHARP 90' BENDS SHALL BE USED. A MINIMUM 12" RADIUS BEND IS ACCEPTABLE.
11. ANTENNA CLAMP RING SHALL BE GROUNDED TO TOWER.
12. ALL GROUNDING SHALL BE IN ACCORDANCE WITH VERIZON WIRELESS SPECIFICATIONS.
ACH: E.C. SHALL FURN. &INST. 1 - #2 AWG BARE SOLID TINNED COPPER
GND. WIRE FROM THE 2 EXISTING HVAC UNITS TO (EER). CONNECTION
TO HVAC UNITS SHALL BE MECHANICAL AND CADWELD TO (EER).
BBG: E.C. SHALL PROVIDE AND INSTALL INSULATED #2 AWG STRANDED COPPER
GROUND WIRE FROM THE BATTERY BUSS BAR TO THE SHELTER HALO LEAD.
CONNECTIONS TO THE HALO LEAD TO BE THREE POINT COMPRESSION
CONNECTIONS, CONNECTION TO BATTERY BUSS BAR TO BE MECHANICAL.
CONNECTIONS TO GROUND RING TO BE CADWELD. SEE BATTERY BUSS
GROUNDING DETAIL ON E-2.
BBD: E.C. SHALL FURN. &INST. #2 AWG BARE SOLID TINNED COPPER GND.
WIRE, ONE FROM POWER CO. GROUND ELECTRODE (PGE) &ONE
TELEPHONE ENTRANCE GROUND (TEG) BOTH TO (EER). CONNECTIONS
TO (PGE), (TEG) & (EER) SHALL BE CADWELD.
CSG: E.C. SHALL FURN. &INST. 1 - #2 AWG BARE SOLID TINNED COPPER
GND WIRE FROM ICE BRIDGE CHANNEL TO (EER). CONNECTION TO ICE
BRIDGE CHANNEL AND (EER) SHALL BE CADWELD.
CEPSG: E.C. SHALL ATTACH THE GROUND BAR FOR THE COAX ENTRY
PROTECTION SYSTEM (AS MFG'D. BY "POLYPHASER CORP., AND
SUPPLIED WITH THE BUILDING) TO THE EXTERIOR ELECTRODE GROUND
RING (EER) USING CADWELD. REFER TO THE GENERAL INSTALLATION
GUIDE AS SUPPLIED WITH SAID POLYPHASER ENTRY ASSEMBLY.
EER: E.C. SHALL FURN. &INST. #2 AWG BARE SOLID TINNED COPPER
BURIED EXTERIOR ELECTRODE GROUND RING (EER) BURIED AT 36"
FG: E.C. SHALL FURN. &INST. 1 - #2 AWG BARE SOLID TINNED COPPER
GND WIRE FROM NEW FENCING TO GROUND RING (EER). CONNECTION
TO FENCING SHALL BE AT THE BASE OF FENCE POST USING CADWELD
AND WEAVE GND. WIRE THRU FABRIC AND ATTACH TO TOP RAIL WITH
CADWELD. CONNECTION TO (EER) SHALL BE CADWELD.
GG: E.C. SHALL FURN. &INST. 1 - #
GROUND NOTES
1. ALL UNDERGROUND CONNECTIONS ON THE LIGHTNING PROTECTION SYSTEM SHALL BE
EXOTHERMIC WELDED USING THE CADWELD PROCESS. THE E.C. SHALL FURN. & INST.
ALL THESE CONNECTIONS, INCLUDING WELD METALS, MOLDS AND TOOLS. THE E.C.
SHALL FURN. & INST. 5/8" x 8' COPPER CLAD STEEL (COPPER JACKET 0.0012" MIN.)
GROUND RODS, DRIVEN VERTICAL AND TO BE 36" ® 16'-0" O.C. BELOW FIN. GRADE
(OR FROSTLINE, WHICHEVER IS GREATER).
2. THE E.C. SHALL FURN. & INST. No.2 AWG BARE SOLID TINNED COPPER GND. WIRE AT
A DEPTH OF 36" BELOW FIN. GRADE FOR THE BUILDING (EER) AND ICE BRIDGE (CSG).
3. ALL EXTERIOR GND. CONNECTIONS SHALL BE EXOTHERMIC CADWELD.
4. ALL MECHANICAL FASTENERS CONNECTIONS TO ALL GROUND BARS SHALL BE
LUBRICATED WITH A CORROSION INHIBITER ("OXY -GREASE") OR APPROVED EQUAL.
5. UPON COMPLETION OF THE GROUNDING RING AND BEFORE BONDING TO THE EXISTING
RING, THE CONTRACTOR SHALL MEGGER TEST THIS GROUNDING FIELD. THE REQUIRED
RESISTANCE LEVEL IS 5 OHMS OR LESS. THE E.C. SHALL NOTIFY THE ENGINEER IF
THESE REQUIREMENTS ARE NOT ACHIEVED. THE CONTRACTOR SHALL SUBMIT PRICING
TO VERIZON WIRELESS FOR THE INSTALLATION OF ADDITIONAL GROUND RODS REQUIRED FOR
PROPER RESISTANCE. UPON APPROVAL FROM VERIZON WIRELESS, THE CONTRACTOR SHALL
INSTALL ADDITIONAL GROUND RODS AS REQUIRED. AFTER PASSING TEST, THEN THE
CONTRACTOR SHALL BOND THE NEW RING TO THE EXISTING RING. THE CONTRACTOR
SHALL NOTIFY VERIZON WIRELESS 48 HOURS PRIOR TO BACKFILLING TRENCHES, POURING
CONCRETE FOR FOUNDATIONS AND GUY WIRES, TO INSPECT BONDS AND INSPECT
ANY/ALL BREAKS AND REPAIRS TO THE GROUND RING.
6. GROUND SYSTEM SHALL BE VISUALLY INSPECTED BY AN A/E FIRM BEFORE
BACKFILLING.
2 AWG BARE SOLID TINNED COPPER
GND WIRE AT EACH GATE POST AND PROVIDE GROUND WIRE TO
BONDING JUMPER FROM GATE POST TO FENCE POST.
GRE: E.C. SHALL FURN. & INST. GROUND RODS TO 36" BELOW FINISH
GRADE AT A MINIMUM SPACING OF 16'-0". CONNECTION TO (EER)
SHALL BE CADWELD.
D TINNED COPPER
GND. WIRES FROM TOWER WAVEGUIDE GROUND BAR (TWGG) TO (EER).
CONNECTION TO (TWGG) SHALL BE CADWELD AND TO (EER) SHALL
BE CADWELD. SEE DETAIL DWG. E-2.
TWGG: TOWER WAVEGUIDE GROUND BAR. SEE DETAIL DWG. E-2.
TW = o000.00'
GENERAL NOTES
1 • UNLESS NOTED OTHERWISE, ALL WORK ITEMS ON SHEETS E-1, E-2 & E-3
SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR.
2. THE ELECTRICAL CONTRACTOR SHALL BE LICENSED TO PERFORM WORK
IN THE COUNTY OF THIS PROJECT AND SHALL BE RESPONSIBLE
FOR OBTAINING AN ELECTRICAL PERMIT FROM THE COUNTY.
3. UNDERGROUND CONDUIT SHALL BE SCH. 40 PVC PLASTIC DUCT WITH
ALL BENDS SHALL BE 2' RADIUS 90' SWEEP UNLESS OTHERWISE
NOTED ON DRAWINGS.
4. ALL WORK SHALL BE IN ACCORDANCE WITH N.F.P.A. AND N.E.C.
CODES, NEMA STANDARDS AND ALL LOCAL CODES.
5. PRIOR TO TRENCHING AND FOR COORDINATING OF THE TELEPHONE
AND ELECTRICAL SERVICES, SEE SHEET A-2 GENERAL NOTE #2
FOR UTILITY CONTACT NAMES &PHONE NUMBERS.
6. ABOVE GRADE RISER CONDUIT SHALL BE RIGID SCH. 40 PVC WITH
MATCHING FITTINGS.
7. ALL WIRE SHALL BE COPPER, BOON THHN/THWN 90'C UNLESS NOTED
OTHERWISE.
8. THE CONTRACTOR SHALL ABIDE BY ALL GUIDELINES REQUIRED BY
CROWN CASTLE, INCLUDING BUT NOT LIMITED TO, a) STAGE CONSTRUCTION
AND REPORT WHEN ON AND OFF THE SITE. b) PROVIDE LOG BOOK
RECORDS OF PERSONNEL ON TOWER. c) PROVIDE R.F. MONITORING
DEVICES TO TOWER PERSONNEL. d) CROWN TO INSPECT ALL
TRENCHING BEFORE BACKFILLING.
9. THE ELECTRICAL CONTRACTOR SHALL PERFORM ALL WORK SHOWN ON
THE CABINET DRAWINGS NOTED "FIELDWORK" OR OTHERWISE NOTED AS
WIRING TO BE COMPLETED IN THE FIELD.
10. THE ELECTRICAL CONTRACTOR SHALL VERIFY ELECTRICAL SERVICE
REQUIRED - 120/240V, SINGLE PHASE, 200 AMP BEFORE ROUGH IN.
11. THE COPPER WAVEGUIDE ENTRANCE PANEL AT THE WAVEGUIDE ENTRANCE
PORT SHALL BE ASSEMBLED USING COPPER JOINT COMPOUND AND BOLTED
COMPRESSION CONNECTIONS. THE LOW INDUCTANCE COPPER GROUNDING
STRAPS ARE ATTACHED TO THE EXTERIOR OF THE PANEL USING JOINT
COMPOUND AND BOLTED TO THE PANEL. THE CONNECTIONS OF THE
GROUNDING STRAPS TO THE EARTH ELECTRODE RING ARE VIA A SANDWICH
BAR THAT IS COATED W/COPPER COMPOUND (SEE GROUND STRAPS DETAIL
ON THIS SHEET) AND BOLTED TO THE STRAPS. THE SANDWICH BAR
IS THEN EXOTHERMICALLY WELDED TO THE #2 SOLID BARE TINNED
COPPER EARTH ELECTRODE GROUND RING. THE SANDWICH BAR SHALL BE
SOLDERED TO PREVENT CORROSION OF THE CONNECTION WHEN IT IS
BURIED IN THE GROUND. ALSO IF SOIL CONDITIONS ARE HIGHLY CORROSIVE
(SEE SOIL REPORT), SPECIAL TINNED COPPER GROUNDING STRAPS SHALL
BE USED AND ARE AVAILABLE THROUGH CLIENT RECOMMENDED
MANUFACTURERS.
12. CONTRACTOR SHALL PROVIDE FIRE WATCH DURING ALL WELDING
OPERATIONS. TWO (2) HAND HELD 30 LB. FIRE EXTINGUISHER &
ADEQUATE WATER SUPPLY SHALL BE APPROVED BY THE CLIENT AND
THE TOWNSHIP WATER AUTHORITY.
13. SEAL ALL PENETRATIONS WITH SILICONE SEALANT.
LEGEND
ACH AIR CONDITIONER GROUND
BBG BATTERY BUS GROUND
B80 BOND TO BURIED OBJECTS
CEPSG COAX ENTRY PROTECTION SYSTEM GROUND
CSG CABLE SUPPORT GROUND
EER BURIED EXTERIOR ELECTRODE GROUND RING
FG FENCE GROUND
GG GATE GROUND
GRE GROUND ROD ELECTRODE
IBSG ICE BRIDGE SUPPORT GROUND
IRDL INTERIOR RING GROUND DOWN LEAD
MGN MULTI -GROUND NEUTRAL
PGE POWER GROUND ELECTRODE
TBG TOWER LEG BASE PLATE GROUND
TEG TELCO ENTRANCE GROUND
TGE TELCO GROUND ELECTRODE
TWG TOWER WAVEGUIDE GROUND BAR GND. WIRE
TWGG TOWER WAVEGUIDE GROUND BAR
• CABLE TO CABLE CADWELD CONNECTION
O CABLE TO GND. ROD CADWELD CONNECTION
TEST WELL
2001006.24 1
LR,
G1STF,9
IBSG: E.C. SHALL FURN. &INST. 1 - #2 AWG BARE SOLID TINNED COPPER
GND. WIRE FROM ICE BRIDGE SUPPORT POST TO (EER). CONNECTION
STATE OF 6d88p4Q5
STATE OF
A�D
TO ICE BRIDGE SUPPORT POST & (EER) SHALL BE CADWELD.
IRDL: E.C. SHALL CONNECT EXISTING (SUPPLIED WITH BLDG.) #2 AWG BARE
�
Z
SOLID TINNED COPPER GND WIRE DOWN LEAD FROM EXISTING BLDG.
INTERIOR GND. HALO TO (EER). CONNECTION TO (EER) SHALL BE
GNUS f'YLE SCHOMER BURNS dr pEHAVEN INC.
CADWELD. ALSO EC SHALL SEAL ALL EXISTING WALL PENETRATIONS
CPD ASSOCIATES
WITH WATERPROOF SILICONE SEALANT.
2647 Waterfront Parkway East Dr. Suite 150
Indianapolis, Indiana 46214
MGN: E.C. SHALL FURN. &INST. #2 BARE SOLID TINNED COPPER
317-299-2996, Fax 317-293-1331
CONDUCTOR FROM MAIN A/C SERVICE DISCONNECT SWITCH NEUTRAL
& HAZEL DEL CELL SITE
BUS BAR TO (PGE). CONNECTION TO (PGE) SHALL BE CADWELD AND
CARMEL, INDIANA
TO A/C SERVICE DISCONNECT SWITCH NEUTRAL BUS BAR SHALL BE
GROUNDING SITE PLAN
8c NOTES
MECHANICAL.
D TINNED COPPER
GND. WIRES FROM TOWER WAVEGUIDE GROUND BAR (TWGG) TO (EER).
CONNECTION TO (TWGG) SHALL BE CADWELD AND TO (EER) SHALL
BE CADWELD. SEE DETAIL DWG. E-2.
TWGG: TOWER WAVEGUIDE GROUND BAR. SEE DETAIL DWG. E-2.
TW = o000.00'
GENERAL NOTES
1 • UNLESS NOTED OTHERWISE, ALL WORK ITEMS ON SHEETS E-1, E-2 & E-3
SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR.
2. THE ELECTRICAL CONTRACTOR SHALL BE LICENSED TO PERFORM WORK
IN THE COUNTY OF THIS PROJECT AND SHALL BE RESPONSIBLE
FOR OBTAINING AN ELECTRICAL PERMIT FROM THE COUNTY.
3. UNDERGROUND CONDUIT SHALL BE SCH. 40 PVC PLASTIC DUCT WITH
ALL BENDS SHALL BE 2' RADIUS 90' SWEEP UNLESS OTHERWISE
NOTED ON DRAWINGS.
4. ALL WORK SHALL BE IN ACCORDANCE WITH N.F.P.A. AND N.E.C.
CODES, NEMA STANDARDS AND ALL LOCAL CODES.
5. PRIOR TO TRENCHING AND FOR COORDINATING OF THE TELEPHONE
AND ELECTRICAL SERVICES, SEE SHEET A-2 GENERAL NOTE #2
FOR UTILITY CONTACT NAMES &PHONE NUMBERS.
6. ABOVE GRADE RISER CONDUIT SHALL BE RIGID SCH. 40 PVC WITH
MATCHING FITTINGS.
7. ALL WIRE SHALL BE COPPER, BOON THHN/THWN 90'C UNLESS NOTED
OTHERWISE.
8. THE CONTRACTOR SHALL ABIDE BY ALL GUIDELINES REQUIRED BY
CROWN CASTLE, INCLUDING BUT NOT LIMITED TO, a) STAGE CONSTRUCTION
AND REPORT WHEN ON AND OFF THE SITE. b) PROVIDE LOG BOOK
RECORDS OF PERSONNEL ON TOWER. c) PROVIDE R.F. MONITORING
DEVICES TO TOWER PERSONNEL. d) CROWN TO INSPECT ALL
TRENCHING BEFORE BACKFILLING.
9. THE ELECTRICAL CONTRACTOR SHALL PERFORM ALL WORK SHOWN ON
THE CABINET DRAWINGS NOTED "FIELDWORK" OR OTHERWISE NOTED AS
WIRING TO BE COMPLETED IN THE FIELD.
10. THE ELECTRICAL CONTRACTOR SHALL VERIFY ELECTRICAL SERVICE
REQUIRED - 120/240V, SINGLE PHASE, 200 AMP BEFORE ROUGH IN.
11. THE COPPER WAVEGUIDE ENTRANCE PANEL AT THE WAVEGUIDE ENTRANCE
PORT SHALL BE ASSEMBLED USING COPPER JOINT COMPOUND AND BOLTED
COMPRESSION CONNECTIONS. THE LOW INDUCTANCE COPPER GROUNDING
STRAPS ARE ATTACHED TO THE EXTERIOR OF THE PANEL USING JOINT
COMPOUND AND BOLTED TO THE PANEL. THE CONNECTIONS OF THE
GROUNDING STRAPS TO THE EARTH ELECTRODE RING ARE VIA A SANDWICH
BAR THAT IS COATED W/COPPER COMPOUND (SEE GROUND STRAPS DETAIL
ON THIS SHEET) AND BOLTED TO THE STRAPS. THE SANDWICH BAR
IS THEN EXOTHERMICALLY WELDED TO THE #2 SOLID BARE TINNED
COPPER EARTH ELECTRODE GROUND RING. THE SANDWICH BAR SHALL BE
SOLDERED TO PREVENT CORROSION OF THE CONNECTION WHEN IT IS
BURIED IN THE GROUND. ALSO IF SOIL CONDITIONS ARE HIGHLY CORROSIVE
(SEE SOIL REPORT), SPECIAL TINNED COPPER GROUNDING STRAPS SHALL
BE USED AND ARE AVAILABLE THROUGH CLIENT RECOMMENDED
MANUFACTURERS.
12. CONTRACTOR SHALL PROVIDE FIRE WATCH DURING ALL WELDING
OPERATIONS. TWO (2) HAND HELD 30 LB. FIRE EXTINGUISHER &
ADEQUATE WATER SUPPLY SHALL BE APPROVED BY THE CLIENT AND
THE TOWNSHIP WATER AUTHORITY.
13. SEAL ALL PENETRATIONS WITH SILICONE SEALANT.
LEGEND
ACH AIR CONDITIONER GROUND
BBG BATTERY BUS GROUND
B80 BOND TO BURIED OBJECTS
CEPSG COAX ENTRY PROTECTION SYSTEM GROUND
CSG CABLE SUPPORT GROUND
EER BURIED EXTERIOR ELECTRODE GROUND RING
FG FENCE GROUND
GG GATE GROUND
GRE GROUND ROD ELECTRODE
IBSG ICE BRIDGE SUPPORT GROUND
IRDL INTERIOR RING GROUND DOWN LEAD
MGN MULTI -GROUND NEUTRAL
PGE POWER GROUND ELECTRODE
TBG TOWER LEG BASE PLATE GROUND
TEG TELCO ENTRANCE GROUND
TGE TELCO GROUND ELECTRODE
TWG TOWER WAVEGUIDE GROUND BAR GND. WIRE
TWGG TOWER WAVEGUIDE GROUND BAR
• CABLE TO CABLE CADWELD CONNECTION
O CABLE TO GND. ROD CADWELD CONNECTION
TEST WELL
2001006.24 1
LR,
G1STF,9
\ S7 '.
= R
Q� N0.\000
�
STATE OF 6d88p4Q5
STATE OF
A�D
HIT
GNUS f'YLE SCHOMER BURNS dr pEHAVEN INC.
CPD ASSOCIATES
2647 Waterfront Parkway East Dr. Suite 150
Indianapolis, Indiana 46214
317-299-2996, Fax 317-293-1331
PROJECT TI E•
126 h
& HAZEL DEL CELL SITE
CARMEL, INDIANA
DESIGN BY: TTP
GROUNDING SITE PLAN
8c NOTES
DRAWN BY:
TfP
CHECKED BY: TGP
SHEET No.
SPRINT LEASE AREA
DATE:
01_04.02
-
11
of
SCALE:
WORK ORDER No. -TC-GSA
JE
AS NOTED
REVISIONS:
APPROVALS:
SUBJECT:
DATE:
--T
I
I _T
MGR. LAND & BLDGS.
DIRECTOR -OPERATIONS
DIRECTOR - NETWORK SERVICE
GENERAL MANAGER
PRESIDENT