TW = odo'o.00'
6'-6"
1 5/8" GALVANIZED UNISTRUT
2VNUTSAND
2" GALVANIZED U -BOLTS
WI WASHERS
ZILLED CONCRETE PIERS
(FURNISHED AND INSTALLED BY E.C.)
METER BOARD STRUCTURE 1
N.T.S. — E — 1
METER BOARD STRUCTURE - TELCO SIDE 2 2
N.T.S. — E
E.C. TO FURN.
& INST. COPPER
BONDING LUG
E.C. TO FURN
& INST.
#2 AWG SOLID
COPPER GND.
AND
5/8" x 8'-0"
COPPER CLAD
GND. ROD DRIVEN.
PER NOTE #2.
FINISH GRADE
—�
TO NEW PREFABRICATED
RADIO EQUIPMENT BUILDING
E.C. SHALL FURN. & INST.
3 - #3/0 & 1 - #4 GND.
IN 1 - 4" PVC CONDUIT FROM
METER TO BUILDING.
TELCO
DEMARCATION POINT.
REFER TO VENDOR DRAWINGS TO
VERIFY CONDUIT QUANTITY. SIZE
AND LOCATION PRIOR TO POURING
OF CONCRETE PAD
METAL TO PVC ADAPTOR (TYP.)
PVC REDUCER (TYP.)
4" DIA. SCH. 40 PVC CONDUIT
SELF CONTAINED METER SOCKET
FURNISHED, INSTALLED AND WIRED
BY E.C. (VERIFY METER SOCKET WILL
ACCEPT 3" CONDUIT)
METER FURNISHED & INSTALLED
BY ELECTRIC PROVIDER.
NEW METER PEDESTAL BY E.C.
E.C. SHALL FURN. & INST. 1 - 3"0 GALV.
STL. CONDUIT (LINE SIDE)
E.C. SHALL FURN. & INST. 1 — 3"0 GALV.
STL. CONDUIT (LOAD SIDE)
PLASTIC TO STEEL ADAPTORS
(FURN. & INST. BY E.C.)
4" TO 3" PLASTIC REDUCER
(FURN. & INST. BY E.C.)
5/8" x 8'-0" COPPER CLAD �-- CYNERGY SHALL FURN. & INST. CABLE FROM
GND ROD, FURN. & INST. THE EXISTING RISER POLE TO THE
BY E.C. NEW METER PEDESTAL. FINAL
CONNECTION AT THE METER SOCKET
BY E.C. AND FINAL CONNECTIONS AT
TRANSFORMER BY CYNERGY.
METER BOARD STRUCTURE - ELECTRIC SIDE 2 2
N.T.S. — E — 1
1'-6"
#2 SOLID GROUND t6" ABOVE
BOTTOM OF METER BOARD FASTEN
W/UV RATED PLASTIC FASTENERS
® 24" CTRS. (TELCO GROUND)
8'-0"
GROUND ROD
TO SITE GROUND RING
8"
TAKE GROUND WIRE
TO NEAREST FENCE
AND CADWELD
#2 SOLID W/±10' -O- LONG
TAIL AT THIS LOCATION FOR
ELECTRIC GROUND
MATCH EXISTING
EXISTING GRADE ----�"
TRENCHING AND BACKFILLING
BY G.C. (SEE GENERAL NOTES
6 & 10 ON DWG. A-2)
WARNING TAPE O 12" BURIAL.
CLEAN BACKFILL
3 -.#3/0. 1 #4 GND,
IN 4" PVC CONDUIT—!-- �
AS REQ'D.
GRADE7-\.
M CADWELD---\GROUND RING
\ #2 AWG BCW (TINNED)
GROUND RO
N.T.S.
MATCH EXISTING
EXISTING GRADE
Z TRENCHING AND BACKFILLING
BY G.C. (SEE GENERAL NOTES
6 & 10 ON DWG. A-2)
N
d'
WARNING TAPE ® 12" BURIAL.
#6 SOLID GND. WIRE
CLEAN BACKFILL
4" PVC CONDUIT W/
PULL WIRE (TELCO
CABLES BY TELEPHONE
Co.)
GROUND ROD
COPPERWELD
5/8"0 x 8'-0" LONG
NOTE:
10'-0" MIN. SPACING BETWEEN RODS
DETAIL
AS REQ'D.
TRENCH DETAIL SECTION
N.T.S.
6
wWli2001006.24
= eN0.o
QtiG�Q Fo�� = 060033977
$s STATE OF
STATE OF �� � '•,�9 1 Ate,• ,` 1
Ill' wireless
'iiiu
MATCH EXISTING ��i�11�JAi ���` 24 F3E R CENTE PARKWAY ATLANTA, GEORGIA 30346
GLAUS "LE SCHOMER BURNS & M"AVEN INC.
EXISTING GRADE G PD ASSOCIATES
TRENCHING AND BACKFILLING z 2647 Waterfront Parkway East Dr. Suite 150
BY G.C. (SEE GENERAL NOTE 6 &10 — - K Indianapolis, Indiana 46214
ON DWG. A-2) 2 317-299-2996, Fax 317-293-1331
M 4
04
WARNING TAPE 0 12" BURIAL. PROJECT TITLE:
#6 SOLID GROUND WIRE — _ 126th & HAZEL DEL CELL SITE
CLEAN BACKFILLI � Z`J•
_ CARMEL, INDIANA
4" PVC CONDUIT W/ PULL - DESIGN BY:
WIRE (TELCO CABLES BY— — — TTP ELECTRICAL DETAILS
TELEPHONE Co. II= DRAWN BY:
TTP
3 - #3/0, 1 #4 CHECKED BY:
GND, IN 4" PVC AS RE 'D. TGP SHEET NO.
CONDUIT DATE: 11 _4_02 SPRINT LEASE AREA
OF E-31TRENCH DETAIL SECTION("09 9 SCALE: AS NOTED WORK ORDER No. CGSA
N.T.S. — — 3 REVISIONS: APPROVALS:
SUBJECT: DATE:
MGR. LAND & BLDGS. I DIRECTOR - OPERATIONS
DIRECTOR - NETWORK SERVICE
GENERAL MANAGER I PRESIDENT