HomeMy WebLinkAbout03100149.15I. SECTION 16010 - BASIC ELECTRICAL REQUIREMENTS A. THE WORK INCLUDES FURNISHING AND INSTALLING THE MATERIAL, EQUIPMENT AND SYSTEMS COMPLETE AS SPECIFIED AND/OR INDICATED ON THE DRAWINGS. THE ELECTRICAL INSTALLATIONS, WHEN FINISHED, SHALL BE COMPLETE AND C40RDINATED AND READY FOR SATISFACTORY SERVICE. B. ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT ACCORDANCE WITH ALL APPLICABLE MUNICIPAL, STATE, BOLA AND LOCAL ELECTRICAL CODES THAT GOVERN EACH PARTICULAR TRADE AND THE 2002 NATIONAL ELECTRICAL CODE. G. THE CONTRACTOR SHALL MAKE APPLICATION AND PAY ALL CHARGES FOR ALL NECESSARY PERMITS, LICENSES AND INSPECTIONS AS REQUIRED UNDER THE ABOVE CODES. UPON COMPLETION OF THE WORK, THE CUSTOMARY CERTIFICATIONS OF APPROVAL SHALL BE FURNISHED. D. NO MATERIALS OR EQUIPMENT SHALL BE USED IN THE WORK UNTIL APPROVED. ALL MATERIALS SHALL BE U.L. LISTED. E. THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND SPECIFICATIONS AND SHALL INSPECT THE EXISTING CONDITIONS OF THE SITE. FAILURE TO COMPLY WITH THIS REQUIREMENT WILL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR COMPLYING WITH THE CONTRACT DOCUMENTS. F. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF THE ELEGTRIGAL INSTALLATIONS. DETAILS OF PROPOSED DEPARTURES DUE TO ACTUAL FIELD CONDITIONS OR OTHER CAUSES SHALL BE SUBMITTED FOR APPROVAL PRIOR TO INSTALLATION. REWORK OF COMPLETED ITEMS DUE TO IMPROPER FIELD COORDINATION SHALL BE AT THE CONTRACTOR'S EXPENSE. G. PROVIDE SUFFICIENT ACCESS AND CLEARANCE FOR ALL ITEMS OF EQUIPMENT REQUIRING SERVICING AND MAINTENANCE. H. THE CONTRACTOR SHALL PERFORM ALL NECESSARY GUTTING AND PATCHING AS REQUIRED TO COMPLETE THE INSTALLATIONS. PATCHING OF WALLS, FLOORS, CEILINGS, ETC. SHALL MATCH THE ADJACENT SURFACES. I. THE CONTRACTOR SHALL PREPARE THREE (3) COPIES OF A RECORD AND INFORMATION BOOKLET. THE BOOKLET SHALL BE BOUND IN A THREE- RING LOOSE-LEAF BINDER AND INCLUDE ALL ITEMS OF ELECTRICAL EQUIPMENT. (I.E. PANELBOARDS, LIGHTING FIXTURES, LAMPS, ETCJ. J. UPON COMPLETION OF THE ELECTRICAL INSTALLATION, THE CONTRACTOR SHALL PROVIDE A COMPLETE SET OF PRINTS OF THE ELEGTRIGAL CONTRACT DRAWINGS WHICH SHALL BE LEGIBLY MARKED IN RED TO SHOW ALL CHANGES AND DEPARTURES OF THE I NSTALLATI ONS COMPARED WITH THE ORIGINAL DESIGN. THEY SHALL BE SUITABLE FOR USE IN PREPARATION OF RECORD DRAWINGS. K. ALL NEW ELECTRICAL INSTALLATIONS SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR. THE ABOVE SHALL NOT IN ANY WAY VOID OR ABROGATE EQUIPMENT MANUFAGTUREWS GUARANTEE OR WARRANTY. CERTIFICATES OF GUARANTEE SHALL BE DELIVERED TO THE OWNER. L. ANY ELECTRICAL WORK WHICH WILL INTERFERE WITH THE NORMAL USE OF THE BUILDING IN ANY MANNER SHALL BE DONE AT SUCH TIME OR TIMES AS SHALL BE MUTUALLY AGREED UPON BETWEEN THE CONTRACTOR AND THE OWNER'S REPRESENTATIVE. M. ALL EXISTING ELECTRICAL SYSTEMS IN OCCUPIED AREAS SHALL BE KEPT IN OPERATION DURING THE PROGRESS OF WORK. TEMPORARY ELECTRICAL CONNECTIONS SHALL BE PROVIDED TO ALL SYSTEMS OR EQUIPMENT, WHERE NECESSARY TO MAINTAIN CONTINUOUS OPERATION UNTIL THE NEW SYSTEMS AND EQUIPMENT ARE READY FOR OPERATION. N. WHEN THE WORK SPECIFIED HEREUNDER CONNECTS TO ANY EXISTING CONDUIT, WIRING OR OTHER EQUIPMENT, THE CONTRACTOR SHALL PERFORM ALL NECESSARY ALTERATIONS, GUTTING AND FITTING OF THE EXISTING WORK AS MAY BE NECESSARY OR REQUIRED TO MAKE SATISFACTORY CONNECTIONS BETWEEN THE NEW AND EXISTING WORK AND SHALL LEAVE COMPLETED WORK IN A FINISHED AND WORKMANLIKE CONDITION, TO THE ENTIRE SATISFACTION OF THE ENGINEER. O. ALL REMOVAL WORK SHALL BE PREFORMED IN A NEAT AND WORKMANLIKE MANNER AND SHALL BE EXECUTED WITH THE LEAST POSSIBLE DISTURBANCE TO THE BUILDING. THE SCHEDULING OF ALL REMOVAL WORK SHALL BE COORDINATED WITH OTHER TRADES AND WITH THE OPERATION OF THE OWNER'S FACILITY. WHERE REMOVAL WORK IS PERFORMED, THE CONTRACTOR SHALL REPAIR ALL BUILDING SURFACES DAMAGED BY SUCH WORK. PROVIDE FINISHES TO MATCH EXISTING ADJACENT SURFACES. P. IN AREAS INDICATED TO BE RENOVATED, REMOVE THAT PORTION OF THE EXISTING ELECTRICAL INSTALLATION TO COMPLETE THE NEW WORK AND ALL EQUIPMENT, WIRING, CONDUITS AND APPURTENANCES NOT REQUIRED IN THE COMPLETED INSTALLATION. ALL UNUSED CONDUIT AND WIRING EXPOSED AFTER DEMOLITION SHALL BE REMOVED BACK TO SOURCE NEAREST POINT OF USAGE). Q. WHERE ELECTRICAL SYSTEMS PASS THROUGH THE RENOVATED AREAS TO SERVE OTHER PORTIONS OF THE PREMISES, THEY SHALL BE SUITABLY RELOCATED AND THE SYSTEM RESTORED TO NORMAL OPERATION. ANY OUTAGES IN SYSTEMS SHALL BE COORDINATED WITH THE OWNER'S REPRESENTATIVE. WHERE DURATION OF PROPOSED OUTAGES CANNOT BE TOLERATED BY THE OWNER, PROVIDE TEMPORARY CONNECTION AS REQUIRED TO MAINTAIN SERVICE WITH THE MINIMUM DISRUPTION POSSIBLE. R. MARK AND PERMANENTLY IDENTIFY ALL 5WTGHE5, CONTROLS, PANELBOARDS, TERMINAL BOARDS AND OTHER EQUIPMENT IN ACCORDANCE WITH THE PROJECT NOMENCLATURE. INDENTIFICATION PLATES SHALL BE LAMINATED PLASTIC, BLACK AND WHITE ENGRAVED LETTERS. LETTERING SHALL BE 3/8" HIGH. ATTACH PLATES WITH CHROME PLATED OR 316 STAINLESS STEEL SCREWS APPROVED FOR THE PURPOSE. S. CONTRACTOR SHALL COORDINATE EXACT OVERCURRENT PROTECTION, PROVISION REQUIRED, WIRE SIZE, CONDUIT, ETC. WITH MECHANICAL CONTRACTOR AND SHOP DRAWINGS OF ALL MECHANICAL EQUIPMENT PRIOR TO ROUGH -IN. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THE ELEGTRIGAL FLOOR PLANS AND MECHANICAL SHOP DRAWINGS. 2. SECTION 16050 - BASIC ELECTRICAL MATERIALS t METHODS A. CONDUIT t BOXES: (1) INSTALL ALL WIRING IN CONDUIT (EXCEPT AS OTHERWISE INDICATED SEE WIRES t CABLE) AND PROVIDE EMPTY CONDUIT FOR SPECIAL SYSTEMS DESCRIBED ELSEWIiERE. MINIMUM CONDUIT SIZE SHALL BE 3/4'. INSTALL ALL CONDUIT CONCEALED UNLESS OTHERWISE INDICATED. SUPPORT ALL CONDUIT SO THAT STRAIN IS NOT TRANSMITTED TO OUTLET BOXES AND PULL BOXES, ETC. SUPPORTS TO BE SUFFICIENTLY RIGID TO PREVENT DISTORTION OF CONDUITS DURING WIRE PULLING. (2) PROVIDE ELECTRICAL METALLIC TUBING (EMT) FOR CONCEALED WORK ABOVE SUSPENDED CEILINGS AND WITHIN INTERIOR PARTITIONS. PROVIDE FLEXIBLE METAL CONDUIT (GREENFIELD) IN SHORT LENGTHS FOR THE CONNECTION OF RECESSED LIGHTING FIXTURES, MOTORS, AND ANY VIBRATING EQUIPMENT. FLEXIBLE CONDUIT MAY NQI BE USED IN INTERIOR DRYWALL PARTITIONS WHERE HORIZONTAL RUNS OCCUR. PROVIDE FULL SIZE EQUIPMENT GROUND WIRE WHERE LENGTHS EXCEED SIX (6) FEET. ALUMINUM CONDUIT IS PROHIBITED. (3) ALL OUTLET, SWITCH AND JUNCTION BOXES, ETC., SHALL BE SHERARDIZED OR GALVANIZED STAMPED STEEL AS MANUFACTURED BY STEEL CITY, RACO, APPLETOR OR GENERAL ELECTRIC. PROVIDE BOX AT EACH OUTLET, SWITCH, EEG. ALL BOXES SHALL BE SIZED PER THE NEC OF A TYPE SUITABLE FOR THE DUTY INTENDED, SUPPLIED WITH APPROPRIATE RINGS. ELECTRICAL SPECIFICATIONS (4) JUNCTION AND PULL BOXES SHALL BE FURNISHED AND INSTALLED AS SHOWN OR WHERE REQUIRED TO FACILITATE PULLING OF WIRES OR GABLES. SUCH BOXES SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS. ALL BOXES FOR CONGEALED WORK SHALL. BE CONSTRUCTED OF #1;12 GAUGE USS GALVANIZED SHEET STEEL MINIMUM, UNLESS OTHERWISE SPECIFIED OR INDICATED AND PROVIDED WITH MOUNTING BRACKETS AND FLAT SCREW COVERS, SECURED IN POSITION BY ROUND HEAD BRASS OR STAINLESS STEEL 300 GRADE MACHINE SCREWS. (5) ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. EXPOSED CONDUIT SHALL BE RUN IN STRAIGHT LINES PARALLEL WITH OR AT RIGHT ANGLES TO COLUMN LINES OR BEAMS AND SEPARATED AT LEAST TWELVE INCHES FROM WATER LINES. (6) ALL CONDUITS ARE TO BE RUN TIGHT TO DECK ABOVE. B. WIRES t GABLE: (1) BUILDING WIRE, UNLESS OTHERWISE INDICATED, SHALL BE 600 VOLT, TYPE THWN OR THHN INSULATION FOR INTERIOR USE. CONDUCTORS SHALL BE SOFT DRAWN COPPER OF NOT LESS THAN 98% CONDUCTIVITY. NO ROMEX OR AG (BX) GABLES PERMITTED. W NO WIRE SMALLER THAN NO. (12) AWS SHALL BE USED UNLESS OTHERWISE INDICATED. CONDUCTORS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET AND FROM TERMINAL BOARD TO POINT OF FINAL CONNECTION, AND NO SPLICE SHALL BE MADE EXCEPT WITHIN OUTLET OR JUNCTION BOXES. ALL CONDUCTORS SHALL BE OF THE SIZES AS INDICATED. ALL WIRES NO. EIGHT (8) AWG AND LARGER SHALL BE STRANDED. THE CONTRACTOR SHALL MAKE WIRING CONNECTIONS OF ALL ELECTRICAL EQUIPMENT REQUIRING ELECTRICAL SERVICE. WIRES AND GABLES SHALL BE AS MANUFACTURED BY PLASTIC WIRE t GABLE CORPORATION, OKONITE COMPANY, GENERAL ELECTRIC, OR EQUIVALENT. (3) ALL WIRING SHALL BE COLOR CODED, PER LANDLORD CRITERIA. (4) WIRING FOR GENERAL 120 VOLT BRANCH CIRCUITS SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED OR REQUIRED TO LIMIT VOLTAGE DROP TO 3%: WIRE 51ZE • .• #12 • •• •• #10 101, 4 UP #10 G. DISCONNECTS: (1) FURNISH AND INSTALL SAFETY SWITCHES WHERE INDICATED AND AS REQUIRED FOR MOTOR OUTLETS OR OTHER EQUIPMENT. SWITCHES SHALL BE OF SIZE, MJMBER OF POLES AND FUSED OR NON-FUSED, AS REQUIRED FOR JOB CONDITIONS AND THE NATIONAL ELECTRICAL CODE. (2) ALL SAFETY SWITCHES SHALL BE NEMA I ENCLOSURE TYPE "HD" QUICK -MAKE, QUICK -BREAK, AND HAVE INTERLOCKING COVER WITH HANDLE THAT MAY EITHER BE FRONT OR SIDE OPERATING WITH A PADLOCKING PROVISION, AS MANUFACTCRED BY SQUARE "D" OR APPROVED EQUAL. D. WIRING DEVICES: (1) THE FOLLOWING WIRING DEVICES SHALL BE FJRN15HW AND INSTALLED WHERE GALLED FOR ON THE DRAWINGS. MISCELLANEOUS ITEMS NOT INCLUDED BELOW SHALL BE UNDERWRITERS' LABORATORIES STANDARD CONFORMING TO THE NEC. ALL DEVICES SHALL BE OF THE SAME MANUFACTURER. DEVICES SHALL BE ARROW HART, PASS t SEYMOUR, LEVITON, OR HUBBELL AND EQUAL TO THE FOLLOWING ARROW HART NUMBERS: WALL SWITCHES: TOGGLE SWITCHES SHALL BE OF THE SILENT MECHANICAL TYPE RATED 20 AMPERE, 120 VOLT A.G. SINGLE POLE SWITCHES SHALL BE ARROW 199IW FOR 20 AMPERES. THREE-WAY SWITCH SHALL BE OF THE SAME MANUFACTURER AND GRADE. ALL DEVICES SHALL BE WHITE. RECEPTACLES: RECEPTACLES FOR WALL OUTLETS SHALL BE RATED 20 AMPERE, 125 VOLTS, DUPLEX, THREE -WIRE WITH THIRD POLE GROUNDED. OUTLETS SHALL BE ARROW HART 5362 FOR 20 AMPERE. 649CI SHALL BE *Cffw 42 RATED FOR 20 AMPERE. ALL RECEPTACLES MOUNTED IN THE SALES AREA SHALL BE BLACK IN CALOR, ALL RECEPTACLES MOUNTED IN REMAINDER OF THE STORE SHALL BE WHITE IN COLOR. DEVICE PLATES: A DEVICE PLATE SHALL BE PROVIDED FOR EACH OUTLET REQUIRING ONE. ALL PLATES SHALL BE MANUFACTURED BY PA55 t SEYMOUR. WHERE TWO OR MORE DEVICES ARE GROUP MOUNTED, PROVIDE A MULTI -GANG OUTLET BOX AND ASSOCIATED COVERPLATE. ALL COVERPLATES MOUNTED IN THE SALES AREA SHALL BE BLACK IN COLOR, ALL COVERPLATES MOUNTED IN REMAINDER OF THE STORE SHALL BE WHITE IN COLOR. MOUNTING HEIGHT AND LOCATION OF ALL DEVICES SHALL BE CLOSELY COORDINATED WITH MANN t MANN ARCHITECTS AND THE TENANT REPRESENTATIVE PRIOR TO ROUGH -IN. E. GROUNDING: (1) ALL ELECTRICAL SYSTEM GROUNDS SHALL BE PROVIDED AS INDICATED ON THE DRAWINGS, MENTIONED HEREIN AND/OR AS REQUIRED BY THE NATIONAL ELECTRICAL CODE. THE FOLLOWING SHALL BE SOLIDLY GROUNDED: W CONDUIT SYSTEM AND OUTLET BOXES (B) LIGHTING FIXTURES (C) PANELBOARDS (D) ELECTRIC HEATING EQUIPMENT (E) TRANSFORMERS (F) MOTOR FRAMES (G) WIRING TROUGH AND PULLBOXE5 (H) FIRE ALARM SYSTEM 3. SECTION 16400 - SERVICE t DISTRIBUTION A. ELECTRICAL SERVICE: (1) ELECTRICAL SERVICE 15 EXISTING FROM THE LANDLORD ELECTRIC SWITCHBOARD IN THE MALL ELECTRICAL ROOM. THE SERVICE VOLTAGE IS INDICATED ON THE DRAWIN65. B. PANELBOARDS: (1) ALL PANELBOARDS SHALL BE BALANCED TO WITHIN LOX OF THE LOWEST PHASE AND A REPORT INDICATING AMPERAGE OF EACH PHASE SHALL BE SUBMITTED TO THE MALL OPERATIONS MANAGER. (2) THE CIRCUIT NUMBERS USED ON DRAWINGS ARE FOR IDENTIFICATION ONLY AND THE CIRCUIT NUMBER IN THE PANEL NEED NOT NECESSARILY CORRESPOND. EACH CIRCUIT IN THE PANELS, HOWEVER, SHALL BE ACCURATELY INDEXED AND TYPED AS SPECIFIED HEREIN. (3) THE PANELBOARD SHALL EMPLOY BOLT -ON BREAKERS OF AND NOT LESS THAN 10,000 SYMMETRICAL A.I.G. AT 120 OR 240 VOLTS. (4) ALL PANELBOARD INTERIORS SHALL BE FACTORY ASSEMBLED, COMPLETE WITH CIRCUIT BREAKERS AS SGEHEDULED ON THE DRAWINGS. INTERIORS SHALL BE 0E516NED AND ASSEMBLED SUCH THAT ANY I NDI V I DUAL BREAKER CAN BE REPLACED WITHOUT DISTURBING ADJACENT UNITS OR WITHOUT REMOVING MAIN BUS, AND SHALL EMPLOY SEQUENCE BUSSING. MAIN BUSSES AND BACK PANS OF PANELBOARDS SHALL BE OF SUCH DESIGN THAT BRANCH CIRCUITS MAY BE CHANGED WITHOUT ADDITIONAL MACHINE, DRILLING, OR TAPPING. ALL CIRCUIT BREAKERS SHALL BE QUICK -MAKE AND SHALL BE TRIPPING INDICATING. PANELBOARDS TO BE SQUARE "D" OR GENERAL ELECTRIC. (5) THE MAIN BUS SHALL BE MANUFACTURERS STANDARD GRADE ALUMINUM. MAIN BUS SHALL EXTEND THE ENTIRE LENGTH OF THE ENCLOSURE. (6) UNLESS OTHERWISE NOTED ALL PANEL50ARDS SHALL BE PROVIDED WITH A 50% GROUND BUS BAR. G. FUSES: (1) FUSES FOR FEEDER G I RCUI TS AND PAPELBOARD5 SHALL BE U L. GLASS RKI FAST -ACTING TYPE. (2) FUSES FOR MOTOR OVERGURRENT AND TRANSFORMER PROTECTION SHALL BE DUAL ELEMENT. U.L. GLASS RKI TIME DELAY TYPE. FUSES SHALL BE OF A TRUE DUAL ELEMENT CONSTRUCTION, INCORPORATING A THERMAL OVERLOAD ELEMENT USING A 280 DEGREE F. MELTING POINT ALLOY. THE DESIGN SHALL PROVIDE TIME -DELAY OF NOT LESS THAN 10 SECONDS AT 500% OF AMPERE RATING. THE INTERRUPTING RATING SHALL BE 200,00 AMPERES RMS SYMMETRICAL. PEAK LET-THRU CURRENT AND ENERGY LET-THRU VALUES SHALL NOT EXCEED THE VALUES ESTABLISHED U.L. STANDARDS FOR GLASS RKI FUSES. D. DRY TYPE TRANSFORMERS: (1) PROVIDE SELF COOLED, DRY TYPE TRANSFORMER OF KVA, PHASE AND VOLTAGE RATINGS AS INDICATED ON THE DRAWINGS. (2) TRANSFORMERS SHALL BE ENCLOSED IN A SUITABLE HOUSING ARRANGED FOR FOR CONDUIT ENTRANCE ON THE PRIMARY AND SECONDARY SIDE. GASES SHALL BE PROVIDED WITH ADEQUATE LOUVERED OPENINC75 TO ALLOW SUITABLE VENTILATION AND COOLING. TRANSFORMER SHALL HAVE A GLASS H (220 DEGREES G) INSULATION FOR CONTINUOUS OPERATION AT RATED LOAD IN A 40 DEGREE G AMBIENT WITH A TEMPERATURE RISE NOT EXCEEDING 150 DEGREE G. (3) TRANSFORMER SHALL HAVE 2-1/2% FULL CAPACITY TAPS BELOW AND ABOVE RATED PRIMARY VOLTAGE. TRANSFORMER SHALL HAVE A LEVEL NOT EXCEEDING 45 db BASED ON NEMA TEST PROCEDURES. (4) NEUTRALS OF TRANSFORMER SHALL BE GROUNDED IN ACCORDANCE WITH THE N.E.G.. IMMEDIATE CONNECTIONS TO AND FROM TRANSFORMER SHALL BE THROUGH FLEXIBLE CONDUIT. E. COMMUNICATIONS SERVICE: (1) THE CONTRACTOR SHALL PROVIDE AN OUTLET BOX AT EACH TELEPHONE LOCATION CONSISTING OF A SINGLE GANG BOX 2-1/8" DEEP WITH RAISED COVER. EXTEND 1/2" EMPTY CONDUIT FROM EACH OUTLET TO THE CEILING SPACE AND EXTEND BACK TO TENANT'S TELEPHONE BACKBOARD. TERMINATE CONDUIT NYLON BUSHING AND PULLSTRING. (?) WHERE CEILING SPACES ARE USED AS A RETURN AIR PLENUM, THE GABLES INSTALLED BY THE OWNER FOR EACH COMMUNICATIONS SYSTEM WILL BE TEFLON OR SIMILAR APPROVED LOW SMOKE DENSITY TYPE. 4. SECTION 16500 - LIGHTING FIXTURES A. INSTALL A COMPLETE LIGHTING FIXTURE FOR EACH LIGHTING FIXTURE SYMBOL SHOWN ON THE DRAWINGS, OF THE TYPE AND QUALITY DESCRIBED HEREIN. FIXTURES SHALL BE INSTALLED COMPLETE WITH LAMPS OR THE WATTAGE INDICATED, SOCKETS, HOUSING, BALLAST (IF REQUIRED), SHADES, DIFFUSERS, SUPPORTS, ETC., AND WIRED FOR OPERATION. ALL LIGHTING FIXTURES AND LAMPS WILL BE FURNISHED BY THE GENERAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR. B. ALL FIXTURES SHALL BE WIRED FOR POLARIZED SYSTEM WITH ONE WIRE IN EACH FIXTURE TO BE DISTINCTLY MARKED FOR ITS ENTIRE LENGTH. WIRE SHALL BEAR THE LABEL OF APPROVAL OF THE UNDERWRITERS' LABORATORIES, INC.. FIXTURE WIRING FOR FLUORESCENT FIXTURES AND BRANCH CIRCUIT WIRING IN FLUORESCENT FIXTURE CHANNELS SHALL BE TYPE THHN OR THW (90 DEGREES G. RATED). ALL CHANNELS IN FLUORESCENT LIGHTING FIXTURES SHALL BE APPROVED FOR THROUGH WIRING. TYPE AF WIRE SHALL ONLY BE USED FOR INTERIOR INCANDESCENT FIXTURE WIRING. G. EACH FIXTURE SHALL BE COMPLETELY EQUIPPED WITH LAMPS OF THE SIZE, TYPE, WATTAGE AND SHAPE INDICATED AND SPECIFIED. ALL LAMPS SHALL BE MANUFACTURED BY THE GENERAL. ELECTRIC CO., WESTINGHOUSE MFS. CO., SYLVANIA, OR APPROVED EQUAL, OF STANDARD SCHEDULE MAKE. LUMEN OUTPUT AND LIFE OF LAMPS SHALL BE IN ALL RESPECTS EQUIVALENT TO THOSE SPECIFIED. ALL LAMPS SHALL BE PROPER VOLTAGE FOR THE BUILDING. EXACT VOLTAGE SHALL BE CHECKED BEFORE ORDERING LAMPS. D. FLUORESCENT LAMPS SHALL BE GENERAL ELECTRIC RAPID START ENERGY SAVER 32 WATT F32T8/5P35/2900 LUMENS, UNLESS OTHERWISE SPECIFIED. E. FLUORESCENT FIXTURES SHALL GENERALLY HAVE TWO LAMP BALLASTS. ALL BALLASTS SHALL BE ELECTRONIC SOLID STATE TYPE GBM AND UL CERTIFIED, HIGH POWER FACTOR ()90X) TYPE WITH SOUND RATING "A". ALL ELECTRONIC BALLASTS SHALL BE DISCRETE WITH INSTANT START AND PROVIDE PARALLEL. OPERATION OF LAMP'. EACH BALLAST SHALL BE INTERNALLY PROTECTED WITH A RESETTABLE THERMAL PROTECTOR TO CONFORM TO UL REQUIREMENTS FOR TYPE "P" BALLASTS. BALLASTS SHALL BE MAGNETEK TRIAD OR APPROVED EQUAL OF ADVANCE, VALMONT, OR MOTOROLA. BALLASTS SHALL NOT EXCEED 90 DEGREES C. CASE TEMPERATURE IN CONTINUOUS OPERATION AND FIXTURE MANUFACTURER SHALL FURNISH TESTS REPORTS CONFIRMING SAME FOR FIXTURE INSTALLATIONS MATCHING JOB CONDITIONS. BALLAST SHALL MEET ALL APPLICABLE ANSI AND IEE STANDARDS REGARDING TOTAL HARMONIC DISTORTION (THD). BALLAST THD SHALL NOT EXCEED 20%. F. AT THE LOCATIONS OF OUTLETS INDICATED ON THE VARIOUS DRAWINGS, THE TYPE OF FIXTURE REQUIRED IS DE516NATED BY A TYPE LETTER. ALL FIXTURES SHALL BE FURNISHED IN THE QUANTITIES, SIZES AND TYPES AS INDICATED ON THE DRAWINGS. 6. RECESSED FLUORESCENT FIXTURES IN CEILINGS MAY NOT BE SUPPORTED FROM THE SUSPENDED CEILING. BOXES AND FIXTURE SUPPORTS SHALL BE FASTENED SECURELY TO CONCRETE SLAB, BAR JOIST OR STRUCTURE EXCEPT AS NOTED. WHERE FIXTURES ARE SURFACE MOUNTED, NEAT HOLES SHALL BE CUT IN THE HUNG CEI L I NGS AS REQUIRED FOR THE FIXTURE SUPPORTS. ALL SUPPORT HANGERS, CHANNELS, BOLTS, ETC., SHALL BE GALVANIZED OR GALV-KROM. H. UNDER THIS SECTION, PROVIDE ADEQUATE SUPPORTS FOR ALL FIXTURES SEPARATE FROM THE SUSPENDED CEILING SYSTEM. CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY ACCESSORIES AS REQUIRED, TO SUPPORT THE FIXTURES. PROVIDE A MINIMUM OF TWO (2) GALVANIZED STEEL #12 GAUGE HANGER WIRES ON ALL RECESSED FIXTURES. I. PROVIDE ALL RECESSED LIGHT FIXTURES WITH A GYPSUM BOARD ENCLOSURE AS REQUIRED BY THE FIRE MARSHALL, TO MAINTAIN A ONE HOUR RATING OF THE CEILING. J. H.I.D. BALLASTS SHALL BE GORE AND COIL TYPE SUITABLE FOR THE CIRCUIT VOLTAGES INDICATED ON THE DRAWINGS. K. PROVIDE ADDITIONAL EXIT LIGHTS AND EMERGENCY BATTERY PACKS WITH DUAL HEADS AS NEEDED TO MEET FIRE MARSHALS WALK THROUGH AND ACCEPTANCE. L DAAYNE A. MANN, ARCHITECT 3801 S CAPITAL OF TEXAS HAY SUITE 330 AU5T I N TX 78-704 TEL: 5I2.aI2."7ga4 FAX: 512.0112.7gg5 DON PENN CONSULTING ENGINEER 3060 HOWAY 3K SURE 101 ORAPEVIN6; TEXAS 70061 89-410 869 FAX 817-251-8411 �M6m rruri��i 4 08.26.05 PERMIT, L.L. REVIEA d BID DATE 155UED FOR Fn ne L/l/L%l'/Vl'IO �OL`�LIL MERCHANT'S SQUARE CARMEL, IN 5PAGE #R7 ELEGTRIGAL 5PEGIFIGATION5 MWA n, #0382 FINL STORE #332 E-6