SPECIFICATIONS AND GENERAL NOTES
0
0.1
ARCHITECT:
kkamcso
600 E. 96TH STREET, SUITE 550
i LPA INDIANAPOLIS, INDIANA 46240
(317) 848.7800 (317) 574.1869 FAX
0.2
CONTRACTOR: 0.3
44WA
Duke
RNWTION
4225 NAPERVILLE ROAD
SUITE 150
LSILE, IL 60532
PHONE: (630)577-7900
C1 moo °O� h�0R
f p7' pFstwe ana
ancc_ S�R�IJ
OP
.;01
P
INDEX OF DRAWINGS
❑ ,wvw�n ks sue�rtrhn ❑ ,aPawtn a raim ❑cim
KEYPLAN
SCALE: NOT TO SCALE
NORTH
0.4
0.5
0.6
0.7
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
CONTRACT CONDITIONS
THE GENERAL CONDMONS SHALL BE AIA DOCUMENT A201 - 1987 EDITION,
ENTITLED "GENERAL CONDMONS OF THE CONTRACT FOR
CONSTRUCTION'. THIS DOCUMENT MAY BE OBSERVED IN THE OFFICE OF
THE ARCHITECT. INCLUDED IN THE GENERAL CONDITIONS ARE
RESPONS181LMES OF THE CONTRACTOR WHICH MAY BE PARAPHRASED
AS FOLLOWS:
3.2 STUDY THE CONTRACT DOCUMENTS, VERIFY DIMENSIONS AND
FIELD CONDITIONS AND REPORT DISCREPANCIES BEFORE
PROCEEDING WITH CONSTRUCTION.
3.3 SUPERVISE, DIRECT AND COORDINATE THE WORK, WITH SOLE
RESPONSIBILITY AND CONTROL OVER CONSTRUCTION MEANS,
METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES.
3.7 OBTAIN AND PAY FOR THE BUILDING PERMIT AND NECESSARY
GOVERNMENTAL FEES, LICENSES AND INSPECTIONS.
3.14 CUT AND PATCH EXISTING SURFACES TO MATCH EXISTING
ADJACENT SURFACES, USING EQUAL QUALITY MATERIALS AND
WORKMANSHIP.
10.1 INMATE, MAINTAIN AND SUPERVISE PROJECT SAFETY
PRECAUTIONS AND PROGRAMS, WHICH ARE SOLELY THE
CONTRACTOR'S RESPONSIBILITY.
WORK MUST COMPLY WITH APPLICABLE LAWS, CODES, ORDINANCES,
RULES AND REGULATIONS.
ALL MATERIALS AND EQUIPMENT SHALL BE OF INDUSTRY STANDARD
QUALITY, WHETHER SPECIFIED OR NOT, AND WITHIN THE LIMITATIONS OF
THE CONTRACT DOCUMENTS, TO CAUSE THE INSTALLATION TO FUNCTION
IN ACCORDANCE WITH THE INTENTION AND OBJECTIVE OF THE FINISHED
PROJECT.
WHEN NOT INDICATED IN THE CONTRACT DOCUMENTS, PROVIDE THE
SIZING OF INTERCONNECTING FACILITIES, SUCH AS PIPING, DUCTS AND
WIRING, BETWEEN PIECES OF EQUIPMENT IN ORDER TO UTILIZE THE
SPECIFIED CAPACITIES OF THE EQUIPMENT.
WHEN NOT INDICATED IN THE CONTRACT DOCUMENTS, THE STANDARDS
ESTABLISHED BY THE RECOGNIZED TRADE ASSOCIATION HAVING
JURISDICTION FOR THE PRODUCT INCLUDED IN THE PROJECT SHALL
GOVERN THE WORK.
NOT ALL ITEMS INDICATED ON THE DRAWINGS ARE INCLUDED IN THESE
SPECIFICATIONS. IN THE CASE OF AN INCONSISTENCY BETWEEN
DRAWINGS AND SPECIFICATIONS OR WITHIN EITHER ELEMENT NOT
CLARIFIED BY ADDENDUM, THE BETTER QUALITY OR GREATER QUANTITY
OF WORK SHALL BE PROVIDED IN ACCORDANCE WITH THE ARCHITECT'S
INTERPRETATION.
INSTALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
GENERAL REQUIREMENTS
WORK SHALL BE PERFORMED DURING REGULAR BUSINESS HOURS
WHENEVER POSSIBLE. WORK INVOLVING OVERTIME, NON -REGULAR
BUSINESS HOURS SHALL BE COORDINATED WITH BUILDING MANAGEMENT.
THE CONTRACTOR SHALL COORDINATE AND SCHEDULE WORK BY OTHERS
INCLUDING BUT NOT LIMITED TO TELEPHONE/DATA, SECURITY, FURNITURE
AND 'FURNISHED AND/OR INSTALLED' ITEMS. CONTRACTOR SHALL
COORDINATE EXACT LOCATIONS AND SHALL DO THE CUTTING, FITTING,
AND PATCHING THAT MAY BE REQUIRED TO MAKE THE PARTS OF THE
WORK WHICH WILL RECEIVE THE WORK OF OTHERS AS SHOWN OR
REASONABLY IMPLIED BY THE DRAWINGS AND SPECIFICATIONS.
CUTTING OF EXISTING SURFACES SHALL BE PATCHED TO MATCH EXISTING
ADJACENT SURFACES, INCLUDING WITH REGARD TO MATERIALS AND
WORKMANSHIP.
SUBMIT SHOP DRAWINGS ( OR SUBMITTALS ) TO THE ARCHITECT FOR THE
FOLLOWING ITEMS:
.1 METAL FABRICATIONS.
.2 ARCHITECTURAL WOODWORK, INCLUDING TRIM AND CABINETS.
.3 DOORS, FRAMES AND HARDWARE.
.4 SUSPENDED ACOUSTICAL CEILING SYSTEMS ( 6' X 6' ACOUSTICAL
PANEL ).
.5 VCT FLOORING AND BASE ( COLOR SAMPLES ).
.6 CARPET ( DYE LOT CUTTING AND SEAMING DIAGRAMS ).
.7 PAINT ( 6' X 6' ON ACTUAL SURFACE ).
.8 WALLCOVERINGS ( 9' X 9' DYE LOT CUTTING ).
.9 SIGNAGE ( SAMPLE SIGN ).
.10 LIGHT FIXTURES ( CATALOG CUTS ).
TEMPORARY UTILITIES, INCLUDING WATER, SANITARY FACILITIES,
TEMPORARY ENCLOSURES, FIRE PROTECTION, HEAT AND POWER
WILL BE PROVIDED BY THE OWNER, SUBJECT TO THE OWNER OR
THE OWNER'S AGENT'S DIRECTION. COMPLY WITH SPECIFIC BUILDING
CONSTRUCTION RULES PUBUSHED BY THE OWNER OR THE OWNER'S
AGENT.
THE CONTRACTOR SHALL PROTECT THE BUILDING PREMISES AND
OCCUPANTS ON THE PROJECT SITE FROM DAMAGE. THE CONTRACTOR
SHALL PROVIDE AND MAINTAIN NECESSARY COVERINGS, BOARDS,
TEMPORARY PARTITIONS, AND DOORS AS REQUIRED TO PROTECT
EXISTING WORK, MATERIALS, AND FINISHES TO REMAIN AT THE JOB SITE.
THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR DAMAGES
ATTRIBUTABLE TO HIS OPERATION, REPAIRS, OR REPLACEMENT WITHOUT
ADDITIONAL CHARGE TO THE PARTY AFFECTED.
THE CONTRACTOR SHALL MAINTAIN FOR THE ENTIRE LENGTH OF HIS
CONTRACT EXITS, EXIT LIGHTING, FIRE PROTECTIVE DEVICES AND ALARMS
TO CONFORM TO LOCAL BUILDING CODE REQUIREMENTS.
SUBSTITUTION FOR NAMED PRODUCTS WILL NOT BE ALLOWED WITHOUT
PRIOR APPROVAL OF THE ARCHITECT. IF A SUBSTITUTION IS PROPOSED,
SUBMIT THE FOLLOWING INFORMATION:
.1 PROVIDE COMPLETE PRODUCT DATA, DRAWINGS AND DESCRIPTIONS OF
PRODUCTS, AND FABRICATION AND INSTALLATION PROCEDURES.
.2 PROVIDE SAMPLES WHERE APPLICABLE OR REQUESTED.
.3 PROVIDE COMPLETE COORDINATION INFORMATION, INCLUDING ALL
CHANGES REQUIRED IN OTHER ELEMENTS OF THE WORK TO
ACCOMMODATE THE SUBSTITUTION.
.4 PROVIDE A STATEMENT INDICATING HOW THE SUBSTMAON WILL
AFFECT THE CONTRACT SUM AND CONTRACT TIME.
STORE MATERIALS ON SITE PRIOR TO INSTALLATION, AND ALLOW TIME
FOR THEIR ADJUSTMENT TO AVOID SHRINKAGE OR SWELUNG.
THE CONTRACTOR SHALL INCLUDE IN HIS BID AND SHALL ARRANGE FOR
HOISTING, CARTING, STANDARD AND OVERTIME SERVICES BY THE
BUILDING MANAGEMENT AND OVERTIME CHARGES AND EXPENSES WHEN
REQUIRED DUE TO BUILDING MANAGEMENT REQUIREMENTS.
1.12
2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
5
5.1
6
6.1
6.2
6.3
6.4
6.5
6.6
SUITE 175
PERFORM FINAL CLEANING, EMPLOYING EXPERIENCED PROFESSIONAL
CLEANERS. CLEAN EACH SURFACE OR UNIT OF WORK TO THE CONDITION
EXPECTED FROM A COMMERCIAL BUILDING CLEANING AND MAINTENANCE
PROGRAM IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
PROVIDE OPERATING AND MAINTENANCE MANUALS WITH INFORMATION
NECESSARY FOR THE SAFE AND EFFICIENT OPERATION AND
MAINTENANCE OF EQUIPMENT AND OPERATING SYSTEMS CALLED FOR IN
THE CONTRACT DOCUMENTS, AND INFORMATION RELATIVE TO THE
INSPECTION, CARE AND MAINTENANCE OR REPAIR OF ARCHITECTURAL
PRODUCTS AND FINISHES WHICH ARE OTHER THAN BUILDING STANDARD.
COORDINATE DEMOLITION WITH CONSTRUCTION PLANS TO DETERMINE
EXTENT OF WORK. PROVIDE DEMOLITION SUFFICIENT FOR SUITABLE
BONDING/PATCHING OF EXISTING CONSTRUCTION TO REMAIN WITH NEW
WORK.
WHERE WORK INCLUDES REMOVAL OF EXISTING CONSTRUCTION OR
EQUIPMENT, OR REMOVAL AND PATCHING, REMOVAL AND REPLPCEMENT,
OR REMOVAL AND RELOCATION, SURFACES LEFT EXPOSED IN RELATION
TO SUCH WORK SHALL HAVE ANY EXCESS MATERIALS REMOVED, AND
SURFACES SHALL BE PREPPED AND FINISHED TO MATCH EXISTING
ADJACENT SURFACES, INCLUDING WITH REGARD TO MATERIALS AND
WORKMANSHIP. ADJACENT ITEMS SHALL BE REMOVED AND RELOCATED
TO ALLOW SUCH WORK. NO CHANGE ORDER WILL BE ISSUED FOR
ADDITIONAL WORK RELATED TO SUCH ACTIVITIES.
WHERE WORK INCLUDES REMOVAL AND RELOCATION, RELATED
MECHANICAL AND ELECTRICAL CONNECTIONS AND TERMINATIONS SHALL
BE INCLUDED.
REPAIR DEMOLITION PERFORMED IN EXCESS OF THAT REQUIRED BY THE
DRAWINGS.
ON EXISTING -CONSTRUCTION -TO -REMAIN, THOROUGHLY REMOVE
ADHESIVE RESULTING FROM THE REMOVAL OF SURFACE APPLIED
FINISHES, INCLUDING VINYL BASE, CARPET TILES, ETC. CHEMICALS AND
METHODS TO REMOVE THE ADHESIVE SHALL BE COMPATIBLE WITH NEW
FINISHES.
EXISTING ACOUSTICAL CEILING GRID, SUPPORT SYSTEM AND TILES SHALL
REMAIN, EXCEPT IN THOSE AREAS DAMAGED DURING CONSTRUCTION OR
NOTED TO BE REPAIRED.
SALVAGE AND TURN OVER TO THE OWNER ALL REMOVED ITEMS.
REPAIR AND RESTORE DESIGNATED REUSED EXISTING PRODUCTS AS
REQUIRED TO MEET IN FINISHED FORM THE TYPE AND QUALITY OF WORK
IN SCOPE OF CONTRACT.
PROVIDE AND MAINTAIN CARPET MATS IN FRONT OF ALL BUILDING
DOORWAYS USED BY CONSTRUCTION WORKERS FOR ACCESS SUCH AS
ELEVATOR DOORWAYS, EXIT STAIR DOORWAYS, ETC, CARPET MATS
SHALL BE LARGE ENOUGH TO PREVENT THE HAUUNG/SPREADING OF DIRT
THROUGH THE BASE BUILDING PREMISES AND ELEVATOR CABS.
CONTRACTOR SHALL INSPECT, TEST AND DISCONNECT UTILITY SERVICES
AT MAIN SOURCE OR MAIN BRANCH WITHOUT DISRUPTING UTILITY
SERVICES IN USE. CONTRACTOR SHALL SECURELY CAP AND/OR VALVE -
OFF LMUTY SERVICE BEHIND FINAL FINISHED SURFACES OF INTENDED
CONSTRUCTION OR, ONLY WHEN NOTED, AT FINISHED FACE PRIOR TO
DEMOLITION OPERATIONS. UTILITY SERVICE SHALL BE DEFINED AS
PLUMBING, HVAC, ELECTRICAL, AND FIRE PROTECTION SYSTEMS.
CONTRACTOR SHALL INDICATE PERMANENTLY ABANDONED UTILITIES ON A
RECORD SEPIA TO SERVE AS PART OF THE "AS -BUILT' SET.
PROVIDE SHORING AND BRACING, OR SUPPORT TO PREVENT MOVEMENT,
SETTLEMENT OR COLLAPSE OF STRUCTURE OR ELEMENT TO BE
DEMOLISHED, AND ADJACENT FACILITIES OR WORK TO REMAIN.
METAL FABRICATIONS
PROVIDE STEEL FRAMING AND SUPPORTS FOR APPUCATIONS INDICATED
OR WHICH ARE NOT A PART OF STRUCTURAL STEEL FRAMEWORK, AS
REQUIRED TO COMPLETE WORK.
WOOD AND PLASTIC
CONCEALED ROUGH FRAMING AND BLOCKING: PROVIDE 'CONSTRUCTION
GRADE" LUMBER OF ANY SPECIES WITH MAXIMUM 19% MOISTURE
CONTENT.
PLYWOOD BACKING PANELS: FOR MOUNTING ELECTRICAL OR TELEPHONE
EQUIPMENT, PROVIDE FIRE -RETARDANT TREATED PLYWOOD PANELS, APA
C -D PLUGGED INT WITH EXTERIOR GLUE, NOT LESS THAN 15/32'.
FIRE -RETARDANT TREATMENT: PRESSURE IMPREGNATE LUMBER AND
PLYWOOD WITH FIRE -RETARDANT CHEMICALS TO COMPLY WITH AWPA
C20 AND C27, RESPECTIVELY, AND IDENTIFY LUMBER WITH
CLASSIFICATION MARKING ACCEPTABLE TO AUTHORITIES HAVING
JURISDICTION.
FINISH CARPENTRY AND MILLWORK: COMPLY WITH 'PREMIUM GRADE' AWI
STANDARDS.
.1 PROVIDE A FULL SCALE MOCK-UP FOR OWNER'S APPROVAL PRIOR
TO FABRICATION OF MULTIPLE UNITS.
COUNTERS: HIGH PRESSURE DECORATIVE LAMINATE COMPLYING WITH
NEMA LD 3 AND GP -50 (0.050" NOMINAL THICKNESS).
.1 EDGE TREATMENT: SAME AS LAMINATE CLADDING ON HORIZONTAL
SURFACES.
.2 PROVIDE 2' DIAMETER PLASTIC GROMMET IN COUNTERTOP ABOVE
ELECTRICAL OR DATA OUTLET LOCATIONS.
CABINETS: COMPLY WITH AWI SECTION 400 AND ITS DIVISION 400B FOR
PREMIUM GRADE NEMA LD3 LAMINATE CLAD CABINETS.
.1 EXPOSED SURFACES: HORIZONTAL SURFACES OTHER THAN TOPS:
GP -50 (0.050' NOMINAL THICKNESS); VERTICAL SURFACES: GP -28
(0.028' NOMINAL THICKNESS); EDGES: GP -28 (0.028' NOMINAL
THICKNESS).
.2 SEMI -EXPOSED SURFACES: HIGH PRESSURE LAMINATE, GP -28.
.3 CABINET HARDWARE SCHEDULE:
.1 HINGES: FULLY CONCEALED, SELF-CLOSING '1000 SERIES'
BY GRASS OR EQUAL
.2 PULLS: WIRE PROJECTING TYPE, DRILLING 4' ON CENTER,
14483 OR EQUAL AS MANUFACTURED BY STANLEY.
.3 CABINET CATCHES: ADJUSTABLE MAGNETIC CATCHES WMH
MINIMUM 8 LBS. PULL; # SP 45 OR SP 46 OR EQUAL AS
MANUFACTURED BY STANLEY.
.4 DRAWER GLIDES: SIDE AND BOTTOM MOUNTED SLIDES
WITH POSITIVE STOP AND LOCKOUT POSITION, WITH
HEAVY-DUTY FULL EXTENSION; 11429 OR EQUAL AS
MANUFACTURED BY KNAPE & VOGT.
.5 SHELF SUPPORTS AND STANDARDS: ADJUSTABLE SHELF
SUPPORTS CONSTRUCTED OF HIGH IMPACT INJECTION
MOLDED NYLON AND WITH HEAVY DUTY TWIN SLOTTED
SHELVING STANDARDS AS PRODUCED BY KNAPE & VOGT
OR EQUAL
INDIANAPOLIS, INDIANA
6.7 MILLWORK SHALL BE FABRICATED FROM FIELD MEASUREMENTS WITH
PROVISIONS FOR SCRIBING AS REQUIRED TO MEET BUILT-IN CONDMONS.
6.8 DO NOT DELIVER CASEWORK AND FINISH CARPENTRY UNTIL PAINTING,
WET WORK AND SIMILAR OPERATIONS WHICH COULD DAMAGE FINISHED
WORK HAS BEEN COMPLETED AND HVAC SYSTEMS HAVE BEEN PROPERLY
OPERATING FOR TEN DAYS.
6.9 INSTALL CASEWORK AND FINISH CARPENTRY PLUMB, LEVEL, TRUE AND
STRAIGHT WITH NO DISTORTIONS.
6.10 JOINTS BETWEEN MILLWORK DRAWERS, DOORS, ETC., TO BE OF UNIFORM
WIDTH NOT TO EXCEED 1/8 U.O.N.
6.11 GROMMETS ARE TO BE FIELD CUT FOR COORDINATION WITH ELECTRICAL
OUTLETS.
7 JOINT SEALERS
7.1 ONE -PART MILDEW -RESISTANT SILICONE SEALANT - AT COUNTERS
AND FIXTURES:
.1 'DOW CORNING 786'; DOW CORNING CORP.
.2 'SCS 1702 SANITARY'; GENERAL ELECTRIC CO.
.3 '863 1345 WHITE"; PECORA CORP.
.4 "PROGLAZE WHITE"; TREMCO CORP.
.5 'OMNIPLUS'; SONNEBORN BUILDING PRODUCTS
7.2 ACRYUC-EMULSION SEALANT - AT INTERIOR UNLIKE ADJOINING
SURFACES:
.1 'CHEM -CALK 600"; BOSTIK CONSTRUCTION PRODUCTS DIV,
.2 'AC -20'; PECORA CORP.
.3 'SONOLAC'; SONNEBORN BUILDING PRODUCTS
.4 'TREMCO ACRYLIC LATEX 834"; TREMCO, INC.
8 DOORS AND WINDOWS
8.1 INTERIOR DOOR FRAMES: PROVIDE BUILDING STANDARD FRAMES UNLESS
NOTED OTHERWISE. COLOR TO BE SELECTED BY DESIGNER.
8.2 INTERIOR DOORS: PROVIDE BUILDING STANDARD DOORS UNLESS NOTED
OTHERWISE. DOORS TO BE BUILDING STANDARD FINISH.
8.3 DOOR HARDWARE: BUILDING STANDARD WITH ADA LEVER HANDLE LATCH
AND LOCKSETS.
8.4 GLASS: MEET ASTM C1036 REQUIREMENTS FOR GLASS AND ASTM C1048
REQUIREMENTS FOR HEAT -STRENGTHENED GLASS.
9 FINISHES
9.1 GYPSUM BOARD WALL FRAMING: COMPLY WITH ASTM C645.
,1 INSTALL 'EUMINATOR' TYPE HEAD TRACK AT WALLS TERMINATING
AT CEILING. USE PREFORMED OUTSIDE CORNERS.
9.2 GYPSUM BOARD: PROVIDE 5/8" THICK REGULAR AND TYPE 'X' TAPERED
EDGE GYPSUM BOARD WITH GALVANIZED STEEL TRIM ACCESSORIES AND
JOINT COMPOUND COMPLYING WITH ASTM C475. FINISH IN ACCORDANCE
WITH ASTM C840 TO THE HIGHEST QUALITY STANDARDS.
.1 DRYWALL FINISHING: COMPLY WITH MANUFACTURER'S PRINTED
INSTRUCTIONS AND SPECIFICATIONS. EXCEPTION: COMPLY WITH
MORE STRINGENT REQUIREMENTS OF GYPSUM ASSOCIATION GA -
216 RECOMMENDED SPECIFICATION FOR THE APPLICATION AND
FINISHING OF GYPSUM BOARD.
9.4 CEILINGS: FINISHED CEILING SHALL BE LEVEL, TRUE AND FREE FROM
DAMAGED OR SOILED TILES.
.1 COORDINATE PLACEMENT OF MECHANICAL AND ELECTRICAL ITEMS
IN CEILING. WHERE CONFLICTS OCCUR, THE ARCHITECTURAL
REFLECTED CEIUNG PLAN SHALL GOVERN.
.2 CENTER CEIUNG ELEMENTS IN CEILING TILE, INCLUDING DOWN
LIGHTS, SMOKE DETECTORS, SPRINKLER HEADS AND EXIT SIGNS
UNLESS NOTED OTHERWISE.
9.5 INSTALL FLOOR FINISH TRANSITION STRIP AT CENTERLINE OF DOOR OR
CASED OPENING UNLESS NOTED OTHERWISE.
.1 INSTALL JOHNSONITE TRIM STRIPS AT DOOR WHERE CARPET
MEETS RESILIENT TILE WITH TRIM STRIP COLOR TO MATCH
CARPET.
9.6 RESILIENT FLOORING:
.1 UNLESS OTHERWISE NOTED, LAY TILE FROM CENTER MARKS
ESTABLISHED WITH PRINCIPAL WALLS, SO THAT TILE AT
OPPOSITES EDGES OF THE ROOM ARE EQUAL WIDTH. ADJUST TO
AVOID USE OF CUT WIDTHS LESS THAN 3' AT ROOM PERIMETER.
.2 BASE: FIT JOINTS TIGHT AND VERTICAL ON CONTINUOUS SOLID
BACKING. INSTALL BASE IN LONGEST PRACTICAL LENGTHS, USING
ROLL STOCK. SCRIBE TO VERTICAL OBSTRUCTIONS.
9.7 USE AN APPROVED CEMENTMOUS FILLER TO PATCH CRACKS, SMALL
HOLES AND LEVELING. ENSURE THAT FLOORS ARE LEVEL WITH MAXIMUM
SURFACE VARIATION OF V IN 10 FEET, NON -CUMULATIVE.
9.8 CARPET: INSTALL CARPETING WHICH MEETS THE FOLLOWING
STANDARDS:
FLAMMABILITY: ASTM 2859
SURFACE BURNING: ASTM E84
SMOKE DENSITY: ASTM E662
SOUND ABSORPTION: ASTM C423
FADE RESISTANCE: AATCC 16E
STATIC RESISTANCE: AATCC 134
WARRANTY: 10 YEARS
.1 INSTALL BROADLOOM CARPET BY DIRECT GLUE.
9.10 PAINT: USE PRIMER COMPATIBLE WITH SUBSTRATE. REMOVE OR
PROTECT HARDWARE, PLATES AND SIMILAR TRIM. AFTER PAINT IS DRY,
REINSTALL SUCH ITEMS.
.1 INTERIOR PAINT SCHEDULE: PROVIDE THE FOLLOWING PAINT
SYSTEMS BASED ON DEVOE TO ESTABLISH QUALITY STANDARD
FOR THE VARIOUS SUBSTRATES, AS INDICATED.
1. FERROUS METAL
A ACRYUC SEMI -GLOSS ENAMEL FINISH:
1. PRIMER: 1 COAT #41702 METALCLAD ACRYLIC
LATEX PRIMER.
2. FINISH: 2 COATS 183XX MIRROLAC-WB ACRYLIC
SEMI -GLOSS ENAMEL.
2. NON-FERROUS METAL
A ACRYLIC SEMI -GLOSS ENAMEL FINISH:
1. PRIMER: 1 COAT #41702 METALCLAD ACRYLIC
LATEX PRIMER.
2. FINISH: 2 COATS 183XX MIRROLACE-WB ACRYUC
SEMI -GLOSS FINISH
3. FERROUS STRUCTURE:
A. ACRYLIC DRY FOG FLAT FINISH:
1. FINISH: 2 COATS 157601 UNI -GRIP -WB WATER
REDUCIBLE ACRYLIC DRY FOG COATING
4. NON-FERROUS STRUCTURE:
A. ACRYLIC DRY FOG FLAT FINISH:
1. FINISH: 2 COATS 157601 UNI -GRIP -WB WATER
REDUCIBLE ACRYLIC DRY FOG COATING.
8. WOOD:
A. ACRYLIC LATEX SEMI -GLOSS ENAMEL FINISH:
1. PRIMER: 1 COAT #51701 WONDER -PRIME LATEX
PRIMER -SEALER.
2. FINISH: 2 COATS 183XX MIRROLAC-WB ACRYLIC
SEMI -GLOSS ENAMEL
B. STAIN -VARNISH RUBBED FINISH:
1. FILLER: 1 COAT 14800 WONDER WOODSTAIN
PASTE WOOD FILLER (OPEN GRAIN WOODS).
2. STAIN: 1 COAT #96XX WONDER WOODSTAIN
ALKYD STAIN.
3. SEALER: 1 COAT #4900 WONDER WOODSEALER
QUICK DRY SEALER.
4. FINISH: 2 COATS #4660 WONDER WOODSTAIN
ALKYD SATIN VARNISH.
10. GYPSUM WALLBOARD:
A ACRYLIC LATEX SATIN ENAMEL FINISH:
1. PRIMER: 1 COAT #50801 WONDER TONES LATEX
PRIMER -SEALER.
2. FINISH: 2 COATS #35XX WONDER TONE ACRYLIC
LATE( SATIN ENAMEL
13, PRECAST CONCRETE:
A. LATEX TEXTURE COATING -SAND FINISH (WET AREAS)
1. PRIMER: 1 COAT 11502 WONDER -SHIELD ACRYLIC
LATEX HOUSE PAINT PRIMER.
2. FINISH: 1 COAT #44101 DEV-VO-TEX LATEX
TEXTURE COATING.
9.11 WALLCOVERING: APPLY WALLCOVERING SECURE, SMOOTH, CLEAN AND
WITHOUT WRINKLES, GAPS OR OVERLAPS.
.1 KEEP SEAMS TO A MINIMUM. HORIZONTAL SEAMS ARE NOT
ACCEPTABLE.
2 SEAMS MUST BE AT LEAST 2' FROM INSIDE CORNERS AND 6' FROM
OUTSIDE CORNERS.
10 SPECIALTIES
10.1 FIRE EXTINGUISHERS AND CABINETS: BUILDING STANDARD, OR IF NO
BUILDING STANDARD, PROVIDE JL INDUSTRIES "AMBASSADOR' SERIES,
SEMI RECESSED, DUO -PANEL, FIELD PAINTED.
12
FURNISHINGS
12.1
CASEWORK:
1 MANUFACTURERS: PROVIDE PRODUCTS BY ONE OF THE
FOLLOWING:
.1 IMPERIAL CABINET CO., INC.
.2 MERILLAT INDUSTRIES, INC.
.3 YORKTOWNE CABINETS
15/16
MECHANICAL AND ELECTRICAL
15/16.1
MECHANICAL (INCLUDING PLUMBING, FIRE PROTECTION AND HVAC) AND
ELECTRICAL SYSTEMS ARE TO BE DESIGNED AND CONSTRUCTED BY THE
RESPECTIVE DESIGN/BUILD CONTRACTORS OR SUBCONTRACTORS
ACCORDING TO CRITERIA DEFINED BY THE TENANT AND AESTHETIC
CRITERIA (ONLY) DEFINED BY THE ARCHITECT. THE CONTRACTOR SHALL
BEAR FULL RESPONSIBILITY FOR ALL DESIGN, PERFORMANCE,
INSTALLATION AND INTER -SYSTEM COORDINATION OF MECHANICAL AND
ELECTRICAL SYSTEMS.
15/16.2
GENERAL CONTRACTOR IS TO PROVIDE A COMPLETE PACKAGE OF
DESIGN/BUILD DRAWINGS FOR FIRE PROTECTION, MECHANICAL, AND
PLUMBING, SIGNED AND STAMPED FOR STATE RUNG PROCESS BY A
CERTIFIED ENGINEER.
15/16.3
IN CASE OF CONFLICT BETWEEN ARCHITECT'S AND ENGINEER'S
DRAWINGS IN LOCATION OF TERMINAL MATERIALS/EQUIPMENT, SUCH AS
DIFFUSERS, GRILLES, LIGHTS (IF SHOWN ON REFLECTED CEILING PLAN)
AND SURFACE MOUNTED ELECTRICAL DEVICES, THE ARCHITECTURAL
DRAWINGS SHALL GOVERN. NOTIFY ARCHITECT OF DISCREPANCIES AND
OBTAIN WRITTEN CLARIFICATION PRIOR TO PROCEEDING WITH WORK.
15/16.4
SUBMIT FIRE SPRINKLER LAYOUT FOR COORDINATION/APPROVAL BY THE
OWNER OR THE OWNER'S AGENT. PATTERN OF SPRINKLER LAYOUT
SHALL COORDINATE WITH PATTERN OF LIGHTING LAYOUT AND SHALL
COORDINATE WITH OTHER CEIUNG COMPONENTS.
15/16.5
DESIGN/BUILD MECHANICAL CONTRACTOR SHALL PROVIDE DRAWINGS
SHOWING THERMOSTAT LOCATION FOR REVIEW BY THE OWNER OR
OWNER'S AGENT.
15/16.6
OUTLET/JUNCTION BOX MOUNTING HEIGHTS SHALL BE COORDINATED
WITH THE EQUIPMENT/APPLIANCE FOR WHICH IT WAS DESIGNATED.
VERIFY EQUIPMENT MOUNTING REQUIREMENTS FOR SCHEDULED
EQUIPMENT.
15/16.7
SWITCHES SHALL BE GANGED UNDER ONE PLATE. DIMMERS SHALL BE
GANGED UNLESS OTHERWISE NOTED BY MANUFACTURER.
15/16.8
DATA AND COMMUNICATION CABLES ARE PROVIDED BY OTHERS AND
INSTALLED BY OTHERS UNLESS OTHERWISE NOTED. CONTRACTOR SHALL
COORDINATE AT THE BEGINNING OF THE PROJECT WITH THE TENANT AND
TENANT'S VENDORS TO DETERMINE THE PHASE DURING WHICH THE
INSTALLATION SHALL OCCUR.
15/16.9
DIMENSIONS, IF IDENTIFIED, ARE TO CENTERUNE OF OUTLET OR GANG OF
OUTLETS, UNLESS OTHERWISE NOTED.
15/16.10
ALL SWITCHES AND SWTTCHPLATES SHALL BE BUILDING STANDARD
COLOR UNLESS NOTED OTHERWISE. IF NO BUILDING STANDARD, PROVIDE
IVORY.
15/16.11
WHERE FLOOR MONUMENTS ARE SHOWN NEXT TO EACH OTHER, THEY
SHALL BE LOCATED AS CLOSE TOGETHER AS POSSIBLE, WHILE STILL
PROVIDING PROPER ACCESS TO RECEPTACLES.
15/16.12
IF ADDITIONAL OUTLETS REQUIRED, COORDINATE WITH ARCHITECTURAL
FOR SPECIFIC LOCATION.
15/16.13
CONTRACTOR SHALL MARK ALL POWER AND COMMUNICATION OUTLET
LOCATIONS ON SLAB AND PROVIDE ACCESS TO SITE FOR ARCHITECT TO
OBSERVE PRIOR TO ANY COMMENCEMENT OF 'ROUGH -IN'
CONSTRUCTION.
GN
GENERAL NOTES
GN.1
CONTRACTOR TO VERIFY DIMENSIONS AND EXISTING CONDMONS AND
REPORT ANY DISCREPANCIES FROM THIS PLAN TO DESIGNER PRIOR TO
PROCEEDING WITH CONSTRUCTION.
GN.2
DIMENSIONS ARE AS FOLLOWS, UNLESS OTHERWISE NOTED:
A. TO FINISHED FACE OF GYPSUM BOARD.
B. TO INSIDE FACE OF JAMB AT DOORS AND OTHER OPENINGS,
C. TO TOP OF FINISHED FLOORS.
D. TO BOTTOM OF FINISHED CEIUNGS.
GN.3
SEE WALL LEGEND FOR SYMBOLS RELATED TO WALL CONSTRUCTION,
EXISTING CONSTRUCTION AND WALL TYPES.
GNA
TERMINATE WALLS AT UNDERSIDE OF CEILING UNLESS INDICATED
OTHERWISE.
GN.5
DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. PARTITION
LOCATIONS, DIMENSIONS AND TYPES, DOOR AND WINDOW LOCATIONS
SHALL BE AS SHOWN ON CONSTRUCTION PLAN, IN CASE OF CONFLICT,
NOTIFY DESIGNER FOR WRITTEN CLARIFICATION PRIOR TO PROCEEDING
WITH CONSTRUCTION.
GN.6
CONTRACTOR SHALL PROVIDE CHALK LINES DELINEATING WALL LAYOUT
FOR THE ARCHITECT'S OBSERVATION WITH REGARD TO DESIGN INTENT.
DO NOT PROCEED WITH INSTALLATION OF STUDS WITHOUT THIS
OBSERVATION.
GN.7
FOR BUILT-IN WORK SURROUNDED BY PARTITION, INCLUDING BUT NOT
LIMITED TO APPLIANCES AND FILES, CONTRACTOR SHALL CONFIRM THAT
FLOOR SLAB DOES NOT VARY BY MORE THAN 1/4" IN 20'-0' NON-
CUMULATVE, NOTIFY DESIGNER IF TOLERANCE IS EXCEEDED.
GN.8
CONTRACTOR SHALL COORDINATE PLACEMENT OF BLOCKING PRIOR TO
CLOSE -IN OF WALLS.
GN.9
SOUND INSULATED AND FIRE RATED PARTITIONING SHALL BE CAULKED AT
PERIMETER WITH ACOUSTICAL OR ARE RATED SEALANT AS APPLICABLE.
PLACE SEALANT BETWEEN GYPSUM BOARD AND ADJACENT SUBSTRATE.
PROVIDE WITH SOUND ATTENUATING INSULATION SECURELY FASTENED
TO STUD FRAMING. AT THESE PARTITIONS, BACK TO BACK ELECTRICAL
JUNCTION BOXES ARE NOT PERMITTED.
GN.10
ALL APPLIANCES NOTED ON ELEVATIONS SHALL BE SUPPLIED BY
CONTRACTOR.