HomeMy WebLinkAboutConstruction Drawings 3.13.2017RATIO Architects, Inc.
ARCHITECT
PROJECT NAMERATIO PROJECT NO.PACKAGEDATESET NO.VOLUMEVOL: 1VOLUME
RATIO PROJECT NO.
OWNER PROJECT NO.
DATE
VOL: 1
n/a
PACKAGE
KBSO Consulting, Inc.
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46032
(317) 344-8046
MECH / ELEC / PLUMBING / FP ENGINEER
First Busey Corporation
201 West Main Street
Urbana, Illinois 61801
(217) 365-4500
OWNER
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
PROJECT ADDRESS
ISSUED FOR REVIEW / BID
11550 N. Meridian Street
Carmel, IN 46032 Busey Bank Tenant Improvement Indy16071.001ISSUED FOR REVIEW / BID03.13.1703.13.17
16071.001
Busey Bank Tenant Improvement Indy
Carmel, IN
03.13.2017
3S 3S3S
2 22
1 11
DW2 22222 2 22 22 222 2 22222222 22 2 2
2 22 2 2 2222PROJECT LOCATION
PROJECT LOCATION
EXIT POPULATION
EXIT CAPACITY [POPULATION]
EXIT DIRECTION ARROW
45
120
ROOM NAME, AREA &
OCCUPANT CAPACITY
FIRE RATED WALL
SMOKE BARRIER
RATING REQUIRED..30-MIN, 1-HR,
2-HR, ETC.
FIRE SEPARATION AND OTHER
ANNOTATION SO NOTED
FIRE BA....
RATING IF REQUIRED..1-HR, 2-HR, ETC.
FIRE RATED WALL
PATTERN INDICATES CODE REQUIRED
SEPARATION AS NOTED
PATH OF TRAVEL
FIRE RATED CEILING. RATING AS
NOTED...1-HR, 2-HR, ETC.1-HR
RM NAME
20
150 SF
32
180
32
180
TRAVEL DIST. A
TRAVEL DIST. BTRAVEL DIST. C
6338 SF
FIRST LEVEL
AREA
64
32
360
32
360
F.E.C.
F.E.C.
F.E.
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/17/2017 11:09:31 AMG-002
SHEET INDEX, PROJ
LOCATION, CODE
SUMMARY, AND LIFE
SAFETY PLAN
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
DRAWING INDEX
Sheet # Sheet Name
GENERAL
G-002 SHEET INDEX, PROJ LOCATION, CODE SUMMARY, AND LIFE
SAFETY PLAN
ARCHITECTURAL
A-001 GENERAL NOTES, SYMBOLS, STD. MOUNTING HEIGHTS
A-002 PARTITION TYPES & DETAILS, FINISH SCHEDULE & DETAILS
AD-101 FIRST FLOOR DEMO PLAN
A-101 FIRST LEVEL FLOOR PLAN
A-131 FIRST LEVEL REFLECTED CEILING PLAN
A-141 FIRST LEVEL FURNITURE PLAN (FOR REFERENCE ONLY)
A-151 FIRST LEVEL FINISH PLAN
A-220 INTERIOR ELEVATIONS
A-401 ENLARGED PLANS & ELEVATIONS
A-520 INTERIOR DETAILS
A-521 MILLWORK DETAILS
A-601 DOOR SCHEDULE AND DETAILS
A-901 3D REPRESENTATIONS
MECHANICAL
MD-101 FIRST FLOOR DEMO PLAN - MECHANICAL
MP-000 MECHANICAL & PLUMBING SYMBOLS & ABBREVIATIONS
M-101 MECHANICAL FLOOR PLAN
M-601 MECHANICAL SCHEDULES AND DETAILS
PLUMBING
PD-100 PLUMBING FOUNDATION DEMOLITION PLAN
PD-101 PLUMBING FLOOR DEMOLITION PLAN
P-100 PLUMBING FOUNDATION PLAN
P-101 PLUMBING FLOOR PLAN
P-501 PLUMBING DETAILS & SCHEDULE
ELECTRICAL
E-000 ELECTRICAL SYMBOLS AND ABGREVIATIONS
ED-101 ELECTRICAL DEMOLITION PLAN
EL-101 ELECTRICAL LIGHTING FLOOR PLAN
EP-101 ELECTRICAL POWER AND SYSTEMS FLOOR PLAN
E-601 ELECTRICAL SCHEDULES
PROJECT LOCATION
GENERAL PROJECT NOTES
A THE FOLLOWING GENERAL NOTES APPLY TO THESE CONTRACT DOCUMENTS AND ARE NOT
SPECIFIC TO ANY ONE DISCIPLINE.
B IT IS THE CONTRACTORS RESPONSIBILITY TO REVIEW AND COORDINATE THE WORK OF ALL
SUB-CONTRACTORS, TRADES AND SUPPLIERS WITH THE REQUIREMENTS OF THE CONTRACT
BEFORE COMMENCING CONSTRUCTION, AND TO ASSURE THAT ALL PARTIES ARE AWARE OF ALL
REQUIREMENTS, REGARDLESS OF WHERE THE REQUIREMENTS OCCUR IN THE CONTRACT
DOCUMENTS, WHICH MIGHT AFFECT THE WORK OF THAT PARTY.
C PARTIAL SETS OF DRAWINGS ARE INCOMPLETE AND SHOULD NOT BE DISTRIBUTED OR UTILIZED
BY THE CONTRACTOR.
D THE CONSTRUCTION DOCUMENTS ESTABLISH DETAILED MINIMUM REQUIREMENTS FOR THE
CONSTRUCTION OF THE PROJECT.
E THE GENERAL NOTES, SYMBOLS AND DEFINITIONS APPLICABLE ONLY TO EACH DISCIPLINE CAN
BE FOUND AT THE FRONT OF EACH DISCIPLINES PORTION OF THE SET OF DRAWINGS AND IS
LISTED AS PART OF THE OVERALL PROJECT INDEX OF DRAW INGS.
F BASIC FIRE PROTECTION AND THE EXITING SCHEME ARE ILLUSTRATED BY THE EGRESS PLAN(S)
AND APPLICABLE FIRE AND BUILDING CODE SUMMARY ON THIS SHEET.
G THE ARCHITECTURAL DRAWINGS ESTABLISH, COORDINATE AS WELL AS TAKE PRECEDENCE FOR
THE FINISH APPEARANCE OF ALL EXPOSED ELEMENTS OF THE WORK OF ALL TRADES INCLUDING
THAT WORK WHICH IS ILLUSTRATED PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES
H THE DRAWINGS MAY MAKE REFERENCE TO AND/OR ILLUSTRATE ITEMS WHICH ARE NOT PART OF
THE WORK OF THE CONTRACT. THESE "NOT IN CONTRACT" ITEMS ARE REFERENCED AND/OR
ILLUSTRATED FOR THE CONTRACTORS REFERENCE, INFORMATION AND COORDINATION ONLY.
J THE CONTRACTOR IS RESPONSIBLE TO COMPLY WITH APPLICABLE LAWS, CODES, REGULATIONS
AND ORDINANCES OF THE PLACE (CITY, COUNTY, DISTRICT AND STATE) WHERE THE PROJECT IS
LOCATED - ALTHOUGH SUCH REQUIREMENTS MAY NOT BE REFLECTED BY THESE CONTRACT
DOCUMENTS.
K EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND OR VISUAL FIELD
SURVEYS. THE CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT THE SITE PRIOR
TO SUBMITTING A BID. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
L THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND SIMILAR RELEASES REQUIRED
FOR THE CONSTRUCTION AND OCCUPANCY OF THE PROJECT. THE CONTRACTOR SHALL FURNISH
COPIES OF ALL SUCH ITEMS TO THE OWNER AND ARCHITECT WITHIN 10 DAYS OF RECEIPT OF
SUCH ITEMS. IF PERMITS ARE ISSUED SUBJECT TO CERTAIN CONDITIONS OR REVISIONS TO THE
WORK OR IF PERMITS ARE DELAYED FOR ANY REASON, THE CONTRACTOR SHALL NOTIFY THE
OWNER AND ARCHITECT.
M THE CONTRACTOR SHALL TAKE PRECAUTIONS TO MAINTAIN AND PROTECT NEW WORK AS WELL
AS EXISTING SYSTEMS AND ELEMENTS WHICH ARE TO REMAIN. ANY DAMAGE TO SUCH SYSTEMS
AND ELEMENTS SHALL BE IMMEDIATELY REPAIRED IN A MANNER ACCEPTABLE TO THE
ARCHITECT. IF SATISFACTORY REPAIRS CANNOT BE MADE, THE CONTRACTOR SHALL REPLACE
SYSTEMS AND ELEMENTS WITH "LIKE NEW" QUALITY ACCEPTABLE TO THE ARCHITECT. ALL
REPAIRS AND REPLACEMENT COST SHALL BE THE FINANCIAL RESPONSIBILITY OF THE
CONTRACTOR.
REV. 03/31/09
REGION MAP
CODE SUMMARY
LIFE SAFETY PLAN LEGEND
1/16" = 1'-0"G-002
1 FIRST LEVEL LIFE SAFETY PLAN
OCCUPANT LOAD SCHEDULE
FLOOR LEVEL OCCUPANT LOAD
FIRST LEVEL 64
64
TRAVEL DISTANCE SCHEDULE
EXIT ROUTE DISTANCE
TRAVEL DIST. A 125' - 0"
TRAVEL DIST. B 122' - 5"
TRAVEL DIST. C 158' - 6"
APPROVED VARIANCES
VARIANCE
NUMBER DESCRIPTION
13-xx-xx(a)
13-xx-xx(b)
13-xx-xx(c)
13-xx-xx(d)
13-xx-xx(e)
< 300' = OKAY
< 300' = OKAY
< 300' = OKAY
03.13.2017
CL OF SLOTPAPER TOWEL
DISPENSER/
WASTE
RECEPTACLE CL OF BARSOAP DISPENSERGRAB BAR BOTTOM EDGE OFREFLECTIVE SURFACEMIRROR
SURFACE MOUNTTOP OF UNITCLOTHES
HOOKTOP OF HOOK34"@ COUNTER & LAVS40"54"ACCESSORYSYMBOL TAG:ITEM: MOUNTINGHEIGHT:DIMENSION FROMFINISH FLOOR TO:01A 02 05 08 1006B44"MAX. 48"RECESSED25"15" MIN.TOILET PAPER
HOLDER BOTTOM OF UNIT30"SANITARY
NAPKIN
DISPOSALTOP OF UNIT0370"12"42"
56" MIN. @ WALL-HUNG TOILET
58" MIN. @ FLOOR-MOUNTED TOILET
18" MIN1 1/2" MIN.7" - 9"9"7"
12"24"34"59" MIN.9"7"
24"60"24" STD.17" MAX. H.C.15" MIN.34" MAX.18"
TOILET PARTITION
WHERE OCCURS
1 1/2" DIA. GRAB
BAR W/ 1 1/2" MIN.
GAP FROM WALL
TOILET PAPER
MOUNTING AREA
URINAL SCREEN
WHERE OCCURS
TOE CLEARANCE
SPACE
TOE CLEARANCE
SPACE
ACCESSIBLE SINK
BOWL - 6 1/2" DEEP
9"MIN. ACCESSIBLE
KNEE CLEARANCE
WATER CLOSET
SIDE WALL
WATER CLOSET
BACK WALL
URINAL LAVATORY OR
VANITY SINK
ELECTRIC WATER
COOLER27"8"
11"15" STD.17" H.C.18"40"40"
TRANSFER ADA
SHOWER36" max27" min. clear18"33"- 36"18"46"HAND HELD ADJUSTABLE
SHOWER HEAD (ADA)
CONTROL AREA
SOAP SHELF, WHERE
INDICATED
1 1/2" DIAMETER GRAB
BAR, 1 1/2" MIN. GAP
FROM WALL (TYPICAL)
FOLD DOWN
SHOWER SEAT
1 1/2" DIAMETER GRAB
BAR, 1 1/2" MIN. GAP
FROM WALL (TYPICAL)18"40"38" max48".ENLARGED DRAWING REFERENCE
ELEVATION DATUM REFERENCE
NORTH ARROW
DRAWING NUMBER
SHEET NUMBER
BUILDING SECTION CUT REFERENCE
W10 101A101
1
1
Room Name
101
-
KEY NOTE (SHAPE VARIES)
ALIGN DESIGNATED
SURFACES
REVISION REFERENCE
WINDOW NUMBER
DOOR / DOOR NUMBER
ROOM NAME AND NUMBER
NEW
A
DRAWING NUMBER
SHEET NUMBER
WALL SECTION CUT REFERENCE
DRAWING NUMBER
SHEET NUMBER
ELEVATION REFERENCE
EXISTING
ROOF SLOPE - ARROW
POINTS TOWARD DRAIN
1/4" / FOOT
1
PARTITION TYPE SYMBOL*
M8A.D.2.A
S2A.P
*REFER TO INTERIOR PARTITION LEGEND
COLUMN GRIDS
INDICATES NORTH DIRECTION
1
A101
1
A101
1
A101
CT-1
EARTH
NOTE: PATTERNS SHOWN REPRESENT CUT MATERIALS IN PLAN
OR SECTION, UNLESS NOTED OTHERWISE ABOVE.
GRANULAR FILL
CAST-IN-PLACE CONCRETE
PRECAST CONCRETE, CAST
STONE
CONCRETE MASONRY UNIT
BRICK MASONRY
STONE: LIMESTONE, GRANITE,
MARBLE OR AS NOTED
METAL: TYPE AS NOTED
METAL: ROLLED SHAPES
WOOD FRAMING / BLOCKING:
CONTINOUS
WOOD SHIM
FINISHED WOOD
SHOWN CUT AND ELEVATION
PLYWOOD
PARTICLEBOARD
EIFS
SPRAYED FIREPROOFING
SHOWN ON ROLLED SHAPE
BATT INSULATION: THERMAL
OR ACOUSTICAL, UNO
RIGID INSULATION: THERMAL,
ACOUSTICAL, OR SAFING
SHEATHING: GYPSUM, OR AS
NOTED
GYPSUM WALL BOARD
TILE: CERAMIC, QUARRY, UNO
RESINOUS FLOORING:
TERRAZO, TROWEL-ON, UNO
ACOUSTICAL CEILING TILE
GRATING
SHOWN IN PLAN
INSULATED GLASS:
(SMALL SCALE)
GRATING
MEMBRANE: WATERPROOF,
ROOF, DAMPPROOFING
AIR BARRIER SYSTEM
INSULATED GLASS:
(DETAIL)
TERRA COTTA, STRUCTURAL
CLAY TILE
CARPET, CARPET TILE (DETAIL)
SAND, GROUT
AS NOTED
GLASS FIBER REINFORCED
CONCRETE SIDING OR TRIM
ENGINEERED WOOD: GLUE
LAMINATED
PLASTER ON METAL LATH
WOOD FLOOR, WOOD
SHINGLES, OR SIDING
ANGLE
MISCELLANEOUS
CENTER LINE
NUMBER#4'-0"FIRE EXTINGUISHERFIRE EXTINGUISHERCABINET, FIREHOSECABINET, HOSE VALVECABINET, OR ANYCOMBINATION OF THEABOVE6"ELECTRICAL, SWITCHESOR RECEPTACLES OVERCOUNTERS OR SIMILARWORK SURFACES2"2"
2"2"1'-3"ELECTRICAL ORRECEPTACLE TRIM PLATESDOOR FRAME OR
WINDOW FRAME
4'-0"6"6'-8"WALL END OR
EDGE (WHERE
OCCURS)
FIRE ALARM
THERMOSTAT OR
TEMPERATURE CONTROL
TELEPHONES, DOOR SWITCHES,
DOOR CONTROLLERS, FIRE ALARM
PULL SWITCHES AND SIMILAR ITEMS
(THE INTENT IS TO ALIGN TOPS OF ALL
OPERABLE ITEMS WHILE ALLOWING
THE OPERABLE PARTS TO BE LESS
THAN 4'-0" AFF)
ELECTRICAL RECEPTACLES - SINGLE,
GANGED, OR SEPARATED BY 2"
WINDOW, DOOR OR
"FEATURE" THAT
SEPARATES WALL
INTO SEGMENTS
EQEQ
WALL END OR
EDGE (WHERE
OCCURS)
WALL SEGMENT 24" WIDE OR LESS
2"2"
NOTES:
1. USE THIS DETAIL TO LOCATE DEVICES THAT ARE INDICATED ON THE DRAWINGS BUT NOT LOCATED BY DIMENSION, OR TO LOCATE REQUIRED
DEVICES THAT ARE NOT INDICATED ON THE DRAWINGS.
2. ALIGN MULTIPLE DEVICES HORIZONTALLY AND/OR VERTICALLY AS DETAILED.
3. ITEMS OTHER THAN ELECTRICAL RECEPTACLES SHALL BE MOUNTED NEAR DOORWAYS OR INTERSECTING WALLS AS DETAILED SO AS NOT TO
INTERFERE WITH THE PLACEMENT OF ART OR FUNITURE - EXCEPT THAT WHERE THE WALL SEGMENT IS LESS THAN 24" WIDE, CENTER THE DEVICES
AS DETAILED.
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:08 PMA-001
GENERAL NOTES,
SYMBOLS, STD.
MOUNTING HEIGHTS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
STANDARD TOILET ROOM ACCESSORY MOUNTING HEIGHTS
STANDARD-PLUMBING FIXTURE REQUIREMENTS
ARCHITECTURAL SYMBOLS LEGEND
ARCHITECTURAL MATERIAL LEGEND GENERAL ARCHITECTURAL
NOTES
A THESE GENERAL NOTES APPLY TO ARCHITECTURAL
DRAWINGS.
B WORK SHOWN ON THE DRAWINGS SHALL BE BASE BID
UNLESS SPECIFICALLY NOTED TO BE BY ALTERNATE BID.
C FIELD VERIFY EXISTING FINISH FLOOR ELEVATIONS PRIOR TO
STARTING CONSTRUCTION. MATCH NEW FLOOR ELEVATIONS
WITH EXISTING UNLESS NOTED OTHERWISE.
D DIMENSIONS TO EXISTING CONSTRUCTION ARE TO FINISH
SURFACE. DIMENSIONS TO NEW CONSTRUCTION ARE TO
FACE OF STUD UNLESS NOTED OTHERWISE. FIELD VERIFY
ALL CONDITIONS AND DIMENSIONS PRIOR TO STARTING
WORK AND NOTIFY ARCHITECT IMMEDIATELY IF
DISCREPANCIES ARE FOUND BETWEEN CONTRACT
DOCUMENTS AND ACTUAL FIELD CONDITIONS.
E DO NOT SCALE DRAWINGS. REFER DIMENSION QUESTIONS
TO ARCHITECT FOR INTERPRETATION.
F DOOR AND FRAME NUMBERS CORRESPOND TO RESPECTIVE
ROOM NUMBERS. IN ROOMS WITH MULTIPLE OPENINGS, A
SUFFIX HAS BEEN ADDED TO DOOR NUMBERS, I.E., A101-B.
G LOCATE INSIDE FACE OF DOOR FRAME JAMBS 6 INCHES
FROM FINISH FACE OF ADJACENT WALLS UNLESS NOTED
OTHERWISE.
H COORDINATE EQUIPMENT WORK WITH MANUFACTURERS AND
SUPPLIERS TO INSURE PROPER ROUGH-IN CLEARANCES FOR
INSTALLATION, USE AND MAINTENANCE.
J PROTECT EXISTING SURFACES TO REMAIN THAT ARE NOT
INCLUDED IN SCOPE OF WORK BUT THAT ARE WITHIN AREAS
OF CONSTRUCTION ACTIVITY.
K PATCH, REPAIR AND RESTORE EXISTING FINISHES AND
SURFACES TO "AS NEW CONDITION" AS REQUIRED TO MATCH
SURROUNDING MATERIALS OR TO PROVIDE APPROPRIATE
SUBSTRATE PRIOR TO INSTALLING NEW FINISHES. AREAS
NOTED TO BE PATCHED OR REPAIRED ON THE DRAWINGS
ARE GIVEN FOR REFERENCE AND SHALL NOT BE
INTERPRETED TO LIMIT THE SCOPE OF WORK.
L PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD WALL
CONSTRUCTION AS INDICATED. WHERE NOT SHOWN,
PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0".
VERIFY FINAL CONTROL JOINT LOCATIONS WHETHER OR NOT
INDICATED ON THE DRAWINGS WITH ARCHITECT PRIOR TO
STARTING WORK.
M METAL STUD SPACING SHALL BE 16" ON CENTER UNLESS
NOTED OTHERWISE.
N PROVIDE WATER-RESISTANT GYPSUM BOARD ON WALLS
WITH OPERABLE PLUMBING FIXTURES AND WITHIN 4'-0" OF
DRINKING FOUNTAINS OR WATER COOLERS.
O PROVIDE FINISHED END PANELS, FILLERS, SUPPORTS, ETC.
REQUIRED FOR A COMPLETE CABINETRY INSTALLATION.
PROVIDE CUTOUTS, ACCESS PANELS AND REMOVABLE
COMPONENTS AS REQUIRED BY NEW OR EXISTING
CONDITIONS SUCH AS ELECTRICAL OUTLETS, JUNCTION
BOXES, CLEANOUTS, ETC. MOUNT TOP OF WALL CABINETS
AT +7'-0" A.F.F. UNLESS OTHERWISE INDICATED.
P VERIFY MOUNTING HEIGHTS OF ACCESSORIES, EQUIPMENT,
DOOR HARDWARE, CASEWORK, ETC., AND PROVIDE SOLID
BLOCKING BEHIND ITEMS REQUIRING ANCHORAGE. PROVIDE
FIRE TREATED WOOD BLOCKING OR METAL STRAPS
BETWEEN FRAMING MEMBERS AS REQUIRED TO SUPPORT
WEIGHT AND USE OF ITEMS TO BE SUPPORTED. WHERE
MOUNTING HEIGHTS ARE NOT INDICATED, MOUNT ITEMS IN
ACCORDANCE WITH RECOGNIZED INDUSTRY STANDARDS,
COORDINATE LOCATIONS WITH MANUFACTURER OR
SUPPLIER AND REFER MOUNTING HEIGHT QUESTIONS TO
ARCHITECT FOR INTERPRETATION.
Q PROVIDE SEALANT BETWEEN HOLLOW METAL FRAME
PERIMETERS AND SURROUNDING WALL CONSTRUCTION
UNLESS OTHERWISE INDICATED.
R PROVIDE SEALANT BETWEEN INTERIOR STOREFRONT FRAME
PERIMETERS AND SURROUNDING CONSTRUCTION UNLESS
OTHERWISE INDICATED.
S PROVIDE SEALANT BETWEEN DISSIMILAR MATERIALS SUCH
AS GYPSUM BOARD AND MASONRY, MASONRY AND
CONCRETE, COUNTERTOPS AND WALLS, ETC.
T REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP
MATERIALS WHERE DAMAGED DUE TO INSTALLATION OF NEW
MATERIALS TO RESTORE SPECIFIED FIRE RATING.
U THESE NOTES ARE APPLICABLE TO THIS BID PACKAGE ONLY
AND MAY NOT BE APPLICABLE TO FUTURE BID PACKAGES.
V DO NOT BEGIN WORK THAT MAY REQUIRE COORDINATION,
SUCH AS CEILING INSTALLATION, PRIOR TO FINAL SUBMITTAL
OF MECHANICAL AND ELECTRICAL COORDINATION DRAWINGS
TO ARCHITECT NOR PRIOR TO RESOLUTION AND APPROVAL
OF COORDINATION ISSUES.
W REFER TO LIFE SAFETY PLAN DRAWINGS AND CODE
SUMMARY FOR FIRE-RATED FLOOR, WALL, CEILING AND ROOF
LOCATIONS. INSTALL FIRESTOPPING AT PENETRATIONS IN
RATED CONSTRUCTION AND AT TOPS OF RATED WALLS.
X REFER TO A-002 FOR PARTITION CONSTRUCTION TYPE.
U
U.N.O. UNLESS NOTED OTHERWISE
UTIL. UTILITY
U.V. UNIT VENTILATOR
V
V.C.T. VINYL COMPOSITION TILE
VERT. VERTICAL
VEST. VESTIBULE
VIF VERIFY IN FIELD
W
W WIDE/WIDTH
W/ WITH
W.C. WATER CLOSET
WD. WOOD
W.H. WATER HEATER
W/O WITHOUT
WT. WEIGHT
W.W.F. WELDED WIRE FABRIC
N
N.A.F. NO APPLIED FININSH
N.I.C. NOT IN CONTRACT
NO. NUMBER
N.T.S. NOT TO SCALE
O
O.A. OVER ALL
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F.C.I. OWNER FURNISHED-CONTRACTOR
INSTALLED
O.F.O.I. OWNER FURNISHED-OWNER
INSTALLED
O.H. OPPOSITE HAND
OPG. OPENING
OPP. OPPOSITE
P
P.L. PROPERTY LINE
P. LAM PLASTIC LAMINATE
PLAS. PLASTER
PR. PAIR
PREFAB. PREFABRICATED
PT. BD. PARTICLE BOARD
PTD. PAINTED
PWD. PLYWOOD
Q
Q.T. QUARRY TILE
R
R RADIUS
R.C.P. REFLECTED CEILING PLAN
R.D. ROOF DRAIN
REF. REFERENCE
REFL. REFLECTED
REINF. REINFORCED
RESIL. RESILIENT
R.H. RIGHT HAND
RM ROOM
R.O. ROUGH OPENING
S
SCHED. SCHEDULE
S.D. SOAP DISPENSER
SECT. SECTION
S.F. SQUARE FEET
SHT. SHEET
SIM. SIMILAR
SPEC. SPECIFICATION
SQ. SQUARE
S.S. STAINLESS STEEL
STD. STANDARD
STL. STEEL
STOR. STORAGE
STRUCT. STRUCTURAL
SUSP. SUSPEND(ED)
SYM. SYMMETRICAL
T
T. THICKNESS
T.B. TACK BOARD
TBD TO BE DETERMINED
T.C. TOP OF CURB
T.D. TOP OF DECK
TECH. TECHNICAL
TEL. TELEPHONE
TEMP. TEMPORARY
T&G TONGUE AND GROOVE
T.M. TOP OF MASONRY
TMPRD. TEMPERED
T/O TOP OF
T.P. TOP OF PAVEMENT
T.S. TOP OF STEEL
T.W. TOP OF WALL
TYP. TYPICAL
F
F-R FIRE RESISTIVE
FAB. FABRICATE/FABRICATOR
F.C.U. FAN COIL UNIT
F.D. FLOOR DRAIN
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
F.F.E. FINISH FLOOR ELEVATION
F.F.&E. FURNISHINGS, FIXTURES AND
EQUIPMENT
F.H.C. FIRE HOSE CABINET
FIN. FINISH(ED)
FLR. FLOOR
FLUOR. FLUORESCENT
F/O FACE OF
F.O. FINISH OPENING
F.O.B. FACE OF BLOCK
F.O.BR. FACE OF BRICK
F.O.C. FACE OF CONCRETE
F.O.F. FACE OF FINISH
F.O.G. FACE OF GYPSUM BD.
F.O.S. FACE OF STUD
FPRF. FIREPROOF
FT. FOOT/FEET
F.V. FIELD VERIFY
G
GA. GAUGE
G.C. GENERAL CONTRACTOR
GEN. GENERAL
GL. GLASS
G.W.B./
GWB
GYPSUM WALL BOARD
H
H. HEIGHT
HB HOSE BIBB
HDWR. HARDWARE
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
HT. HEIGHT
HVAC. HEATING, VENTILATION & A.C.
H.W. HOT WATER
I
I.D. INSIDE DIAMETER
INCAN. INCANDESCENT
INFO. INFORMATION
INSUL. INSULATION
INT. INTERIOR
J
JAN. JANITOR
J.C. JANITOR CLOSET
JST. BRG. JOIST BEARING
JT. JOINT
L
L LENGTH
LAV. LAVATORY
LB. POUND
L.H. LEFT HAND
L.L.H. LONG LEG HORIZONTAL
L.L.O. LONG LEG OUT
L.L.V. LONG LEG VERTICAL
M
MAX. MAXIMUM
MB. MARKER BOARD
M.C. MECHANICAL CONTRACTOR
M.D.F. MEDIUM DENSITY FIBERBOARD
MECH. MECHANICAL
M.E.P. MECH./ELECT./PLUMBING
MFR. MANUFACTURER(ING)
M.H. MANHOLE
MIN. MINIMUM
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
MTL. METAL
A
A/C AIR CONDITIONING
ACOUS. ACOUSTICAL
A.C.T. ACOUSTICAL CEILING TILE
ACP ACOUSTICAL CEILING PANEL
ADA AMERICANS W/DISABILITIES ACT
ADAAG AMERICANS W/DISABILITIES
ACCESSIBILITY GUIDELINES
ADJ. ADJUSTABLE
A/E ARCHITECT/ENGINEER
A.F.F. ABOVE FINISHED FLOOR
ALT. ALTERNATE
ALUM. ALUMINUM
A.P. ACCESS PANEL
ARCH. ARCHITECT/ARCHITECTURAL
A.V. AUDIO/VISUAL
B
BD. BOARD
BITUM. BITUMINOUS
BLDG. BUILDING
B/O BOTTOM OF
B.O.W. BOTTOM OF WALL
BSMT. BASEMENT
C
CAB. CABINET
C.F.C.I. CONTRACTOR
FURNISHED-CONTRACTOR INSTALLED
C.G. CORNER GUARD
C.I.P. CAST-IN-PLACE
C.J. CONTROL JOINT
CL. CENTERLINE
CLG. CEILING
CLR CLEAR(ANCE)
C.M CONSTRUCTION MANAGER
CMP COMPOSITE METAL PANEL
C.M.U. CONCRETE MASONRY UNIT
COL. COLUMN
CONC. CONCRETE
CONST. CONSTRUCTION
CONT. CONTINUOUS
CONTR. CONTRACTOR
CONTRACTOR
COOR. COORDINATE
CPT. CARPET
C.T. CERAMIC TILE
C.W. COLD WATER
D
D.E.F.S. DIERCT EXTERIOR FINISH SYSTEM
DEPT. DEPARTMENT
DET. DETAIL
D.F. DRINKING FOUNTAIN
DIA. DIAMETER
DIM. DIMENSION
DISP. DISPENSER
D.M.B. DRY MARKER BOARD
DN DOWN
DS DOWNSPOUT
DWG. DRAWING
E
EA. EACH
E.C. ELECTRICAL CONTRACTOR
E.I.F.S. EXTERIOR INSULATION FINISH SYSTEM
E.J. EXPANSION JOINT
EL ELEVATION
ELEC. ELECTRIC/ELECTRICAL
ELEV. ELEVATOR/ELEVATION
ENGR. ENGINEER
E.P. ELECTRICAL PANEL
EQ. EQUAL
EQUIP. EQUIPMENT
E.W.C. ELECTRIC WATER COOLER
EXIST. EXISTING
EXP. EXPOSED
EXT. EXTERIOR
ABBREVIATIONS
STANDARD-DEVICE MOUNTING GUIDELINES
03.13.2017
PARTITION TYPE SYMBOL
PARTITION TYPE
FIRE RATING (I.E. 1= 1 HOUR)
PARTITION HEIGHT CODE
NEW PARTITIONS
EXISTING PARTITIONS TO REMAIN
PARTITIONS TO BE DEMOLISHED
M8A.D.2.A
S2A.P
ADDITIONAL PARTITION
DESIGNATION, WHERE OCCURS
PARTITION DESIGNATION
ACOUSTICAL ATTENUATION REQ'D
HEIGHT AS
INDICATED IN
INCHES OR (V)
INDICATES HEIGHT
THAT VARIES
(C) TERMINATE AT CEILING
(P) TERMINATE 6" ABOVE CEILING
(D) TERMINATE AT FLOOR / ROOF DECK
6"REFER TO WALL SECTION FOR CONSTRUCTIONWS
* FIRE RATING AND ACOUSTICAL ATTENUATION
WHEN REQUIRED BY PARTITION SYMBOL
4 7/8"S3A 3 5/8" METAL STUDS WITH (1) LAYER 5/8" TYPE
X GYPSUM WALL BOARD EACH SIDE
* 1 HR RATED UL419
* ACOUSTIC ATTEN. COMPONENTS STC-6 1/8"S3B 3 5/8" METAL STUDS WITH (2) LAYERS 5/8"
TYPE X GYPSUM WALL BOARD EACH SIDE
* 2 HR RATED U419
* ACOUSTIC ATTEN. COMPONENTS STC-50
7 1/4"S6A 6" METAL STUDS WITH (1) LAYER 5/8" GYPSUM
WALL BOARD EACH SIDE
* ACOUSTIC ATTEN. COMPONENTS STC-44 2 1/8"S1FA 1 1/2" METAL 'Z' FURRING WITH (1) LAYER 5/8"
GYPSUM WALL BOARD ONE SIDE
S2C 2 1/2" METAL STUDS WITH (1) LAYER 5/8"
GYPSUM WALL BOARD ONE SIDE
3 1/8"6 5/8"S6C 6" METAL STUDS WITH (1) LAYER 5/8" GYPSUM
WALL BOARD ONE SIDE
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:09 PMA-002
PARTITION TYPES &
DETAILS, FINISH
SCHEDULE &
DETAILS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
INTERIOR PARTITION NOTES
A ALL WALLS ARE TYPE S3A.D.A UNLESS NOTED OTHERWISE.
B PARTITION SYMBOLS APPEAR ON LARGEST SCALE FLOOR
PLAN PROVIDED FOR AREA.
C REFER TO FINISH AND CEILING PLANS FOR WALL FINISH,
BASE, AND CEILING INFORMATION.
D REFER TO WALL SECTIONS FOR EXTERIOR WALL
CONSTRUCTION.
E PROVIDE WATER RESISTANT GWB IN ALL ROOMS CONTAINING
OPERABLE PLUMBING FIXTURES AND WITHIN 4 FEET OF
DRINKING FOUNTAINS / WATER COOLERS, U.N.O.
F PROVIDE LATERAL BRACING FOR PARTITIONS WHICH EXTEND
ABOVE CEILING.
G PROVIDE FIRE RESISTIVE RATED GYPSUM WALL BOARD AT
ALL RATED ASSEMBLIES TO MEET ASSEMBLY
REQUIREMENTS.
H PROVIDE FIRE RESISTIVE JOINT SYSTEMS EQUAL TO WALL
RATING AT ALL PENETRATIONS AND AT HEAD / FLOOR
INTERSECTIONS WITH RATED ASSEMBLIES.
J PROVIDE ACOUSTICAL SEALANT AT WALL SILL, HEAD,
PENETRATIONS AND ADDITIONAL SPECIFIED SOUND
ATTENUATION COMPONENTS AT SOUND RATED WALLS.
K PROVIDE SPECIFIED TILE BACKER BOARD AT ALL WALLS
SCHEDULED TO HAVE CERAMIC TILE.
L ISOLATE NON-LOAD-BEARING STUD FRAMING FROM BUILDING
STRUCTURE TO PREVENT TRANSFER OF VERTICAL LOADS
WHILE PROVIDING LATERAL SUPPORT AS SPECIFIED.
M STUD SPACING 16" O.C. UNLESS NOTED OTHERWISE
REV. 04/03/09
INTERIOR PARTITION LEGEND
INTERIOR PARTITION HEIGHT CODES
INTERIOR PARTITION TYPESFINISH SCHEDULE
LOCATION FINISH TYPE TAG MANUFACTURER
FINISH DESCRIPTION
COMMENTSSTYLE SIZE
PRODUCT
NUMBER COLOR INSTALL NOTES
CEILING ACOUSTICAL CEILING
TILE
ACT-1 ARMSTRONG SEE SPEC. SECT. 09 51 23
CEILING ACOUSTIC GRILLE AG-1 ARMSTRONG SEE SPEC. SECT. 09 51 23
WALL PAINT PT-1 SHERWIN WILLIAMS EGGSHELL, LATEX N/A SW 7004 SNOWBOUND
WALL PAINT PT-1A SHERWIN WILLIAMS SEMI-GLOSS,
DIRECT-TO-METAL
ACRYLIC
N/A SW 7004 SNOWBOUND EXIST. DOOR FRAMES
WALL PAINT PT-2 SHERWIN WILLIAMS SEMI-GLOSS, LATEX N/A SW 0077 CLASSIC FRENCH
GRAY
DOORS
WALL PAINT PT-3 SHERWIN WILLIAMS EPOXY N/A SW 7064 PASSIVE RESTROOMS
WALL PAINT (ACCENT) PT-4 SHERWIN WILLIAMS EGGSHELL, LATEX N/A t.b.d t.b.d.
WALL PAINT (ACCENT) PT-5 SHERWIN WILLIAMS EPOXY N/A t.b.d. t.b.d.
WALL PAINT PT-6 SHERWIN WILLIAMS FLAT, LATEX N/A SW 6258 TRICORN BLACK REVEALS
BASE RUBBER WALL BASE RB-1 ROPPE ROLLED GOODS, COVE
BASE
4" H 123 CHARCOAL
BASE WOOD WALL BASE WB-1 BROOKSIDE VENEERS WALNUT (QTR.) PER DRAWINGS AW.07 FINISH: WAX EFFECT PER DRAWINGS
FLOOR WALK-OFF CARPET TILE CPT-1 INTERFACE 6090002504 50 CM X 50 CM 609009 MOUSE GREY QUARTERTURN
FLOOR CARPET TILE CPT-2 INTERFACE 128200AK00 25 CM X 1 M WW880 105364 NATURAL
LOOM
ASHLAR & AS SHOWN
ON FINISH PLAN
TACTILE METHOD
FLOOR CARPET TILE CPT-4 INTERFACE 128240AK00 25 CM X 1 M WW890 105338 NATURAL
DOBBY
ASHLAR & AS SHOWN
ON FINISH PLAN
TACTILE METHOD
FLOOR LUXURY VINYL TILE LVT-1 INTERFACE 2103009 25 CM X 1 M MOD. RESILIENT
FLOORING
256173 STORM ASHLAR & AS SHOWN
ON FINISH PLAN
TACTILE METHOD
FLOOR TRANSITION T-1 SCHLUTER SCHIENE COOR. W/
FLOORING HEIGHTS
ANODIZED ALUM
FLOOR TRANSITION T-2 ROPPE REDUCER OR TRANSITION COOR. W/
FLOORING HEIGHTS
123 CHARCOAL
FLOOR TRANSITION T-3 SCHLUTER RENO-V COOR. W/
FLOORING HEIGHTS
ANODIZED ALUM
FLOOR TRANSITION T-4 SCHLUTER RENO-U COOR. W/
FLOORING HEIGHTS
ANODIZED ALUM
MILLWORK/CASEWORK PLASTIC LAMINATE PL-1 WILSONART PER DRAWINGS 4886-38 PEARL SOAPSTONE COUNTERTOPS
MILLWORK/CASEWORK PLASTIC LAMINATE PL-2 WILSONART PER DRAWINGS 7964K-12 SKYLINE WALNUT CABINETS
MILLWORK/CASEWORK PLASTIC LAMINATE PL-3 WILSONART PER DRAWINGS 1573-60 FROSTY WHITE TELLER
MILLWORK/CASEWORK QUARTZ QTZ-1 DIRESCO QUARTZ 2 CM OR PER
DETAILS
A-200 VELVET FINISH BEACH WHITE
MILLWORK/CASEWORK SOLID SURFACE SS-1 CORIAN SOLID SURFACE THICKNESS PER
DETAILS
N/A GRAYLITE
MILLWORK/CASEWORK SOLID SURFACE SS-2 CORIAN SOLID SURFACE THICKNESS PER
DETAILS
N/A ANTARCTICA
MILLWORK/CASEWORK VENEERED WOOD WALL
PANELS
WD-1 BROOKSIDE VENEERS WALNUT (QTR.) PER DRAWINGS AW.07 FINISH: WAX EFFECT PER DRAWINGS
GLAZING FILMS / GLASS FINISHES F-1 3M FASARA FORST/MAT COLLECTION 60"W ROLL SH2MAML MILANO / MILKY
WHITE
03.13.2017
EXISTING
STAIR
ENTRY
VESTIBULE
EXISTING
ELEVATOR
EXISTING
SECONDARY
ENTRY
VESTIBULE
EXISTING
BLDG. STOR.
EXISTING
BLDG. PHONE
EXISTING
BLDG. ELECT.
EXISTING
STAIRWOMEN
(EXIST.)
MEN (EXIST.)
JAN. / SUPPLY
EXISTING
BLDG.
TRANSFORMER
01
02
03
05
07
07
07 07
07
07
07
0707
07
07
07
08
08
08
08
08
08
08
08
08
08
08 08
08
08
08
0808
08
08
08
08
02
02
02
0203
03
06
03
03
03
03
03
03
03
03
03
03
03
03
06
161616 06
16
05
05
05
05
05
05
05
06
06
01 01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
15
01
01
06 01
01
01
10
11
12
01
(MASONRY PIER
& STL COLUMN)
10
10
07070707
13
13
13
04
04
14
02
02
02
02
02
02
02 02
02
02
02
02
02
02
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15 15
15
15
15
15
15
15
06
06
04
17
CONTRACTOR OPTION TO
KEEP THESE EXISTING WALLS
18
MAIN
ENTRY
19
19
19
19
19
19
1919
19
19
19
19
19
EXISTING
DRIVE-UP
LANES EXISTING
VAULT
F2
AD-101
08
FIRST LEVEL
100'-0"
CAST-IN-CONC VAULT LID
CAST-IN-CONC VAULT
WALL TO REMAIN 1'-6"8'-1"1'-6"VAULT
CAST-IN-CONC VAULT
FLOOR TO REMAIN
1'-6"
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:33:55 PMAD-101
FIRST FLOOR DEMO
PLAN
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
3/16" = 1'-0"AD-101
A1 FIRST LEVEL DEMOLITION PLAN
GENERAL DEMOLITION NOTES
A THESE GENERAL DEMOLITION NOTES APPLY TO DEMOLITION
DRAWINGS.
B FIELD VERIFY CONDITIONS AND COORDINATE DEMOLITION OR
REMOVAL WORK WITH CORRESPONDING NEW
CONSTRUCTION AND WITH APPROPRIATE TRADES PRIOR TO
STARTING DEMOLITION WORK. IF DISCREPANCIES ARE
FOUND BETWEEN CONTRACT DOCUMENTS AND ACTUAL
FIELD CONDITIONS, NOTIFY ARCHITECT IMMEDIATELY.
C OWNER WILL REMOVE LOOSE SALVAGEABLE ITEMS, I.E.,
EQUIPMENT, FURNITURE, FILE CABINETS, WALL-MOUNTED
PROJECTION SCREENS, ARTWORK, PLAQUES, ETC., PRIOR TO
CONTRACTOR STARTING DEMOLITION WORK IN EACH AREA.
OWNER WILL STORE AND REINSTALL SUCH ITEMS.
D DEMOLISHED MATERIALS ARE THE PROPERTY OF THE
CONTRACTOR UNLESS NOTED OTHERWISE AND SHALL BE
PROMPTLY DISPOSED OF OFF-SITE.
E ITEMS NOTED TO BE REMOVED AND TURNED OVER TO
OWNER SHALL BE DELIVERED AS DIRECTED BY OWNER.
F REMOVE ITEMS IN THEIR ENTIRETY UNLESS OTHERWISE
INDICATED. DESCRIPTION OF PRIMARY ITEMS TO BE
REMOVED IS GENERAL IN NATURE, AND REMOVAL OF
SECONDARY COMPONENTS SUCH AS BLOCKING, SUPPORTS,
ANCHORS, TRIM, ADHESIVE, PIPING, WIRING, ETC., RELATED
TO PRIMARY ITEMS SHALL BE INCLUDED.
G PROTECT EXISTING SURFACES TO REMAIN IN AREAS
ADJACENT TO DEMOLITION WORK.
H REPAIR FINISHES AND SURFACES LEFT EXPOSED BY
DEMOLITION OR REMOVAL OF EQUIPMENT, USING NEW
MATERIALS TO MATCH SURROUNDING SURFACES. REPAIR
EXISTING FLOOR, BASE, WAINSCOT, WALL AND CEILING
FINISHES TO CORRECT DEFECTS EITHER CAUSED OR
EXPOSED BY DEMOLITION WORK OR EQUIPMENT REMOVAL.
REPAIRED SURFACES SHALL BE SMOOTH AND
UNDETECTABLE UNDER FINAL FINISHES. AREAS NOTED ON
THE DRAWINGS TO BE REPAIRED OR PATCHED ARE GIVEN
FOR REFERENCE AND SHALL NOT BE INTERPRETED TO LIMIT
THE SCOPE OF WORK.
J PATCH EXISTING FLOOR, WALL, CEILING AND ROOF
CONSTRUCTION AT ABANDONED PENETRATION LOCATIONS
WITH NEW MATERIALS AS REQUIRED TO RECEIVE NEW
FINISHES AND TO MAINTAIN ORIGINAL FIRE RATING OF
ASSEMBLY WHERE APPLICABLE.
K PORTIONS OF EXISTING MASONRY WALLS NOTED TO BE
REMOVED AND OPENINGS TO BE CUT INTO EXISTING
MASONRY WALLS SHALL BE REMOVED BACK TO THE
NEAREST VERTICAL MORTAR JOINT. PROVIDE A MINIMUM
BEARING OF 8" AT EACH END FOR NEW MASONRY LINTELS
AND FIELD VERIFY FINAL LENGTH. ALLOW A MINIMUM OF 4"
NEW MASONRY AT JAMB CONDITIONS OR END WALL
CONDITIONS OF MASONRY WALLS. REFER TO DEMOLITION
PLANS FOR LOCATIONS OF WALL, FLOOR, CEILING OR ROOF
OPENINGS.
L PROVIDE SMOOTH TRANSITIONS BETWEEN FLOOR, WALL AND
CEILING SURFACES PRIOR TO INSTALLING NEW FINISHES
WHERE WALLS OR OTHER ITEMS ARE REMOVED. FILL FLOOR
VOIDS WITH CONCRETE OR MATERIAL MATCHING ADJACENT
MATERIALS AND LEVEL FLOOR SURFACES TO PROVIDE A
SMOOTH TRANSITION FROM ONE SIDE OF WALL TO THE
OTHER WHERE PORTIONS OF WALLS ARE REMOVED.
M ADDITIONAL FLOOR TILE MAY BE PRESENT BENEATH
FINISHES IN ROOMS WITH EXISTING FLOOR TILE OR CARPET.
REMOVE ALL LAYERS OF EXISTING FLOOR COVERINGS TO
PROVIDE APPROPRIATE SUBSTRATE FOR NEW FLOOR
FINISHES.
N SELECTIVE DEMOLITION FOR INSTALLATION OF NEW
MECHANICAL OR ELECTRICAL WORK SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR OR TRADE REQUIRING
THE DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED TO,
FLOOR SLAB AND PAVEMENT CUTTING FOR UNDERGROUND
PIPING, CORING FOR WALL AND FLOOR PENETRATIONS,
ROOF PENETRATIONS, ETC. REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION
INFORMATION.
O DISCONNECT AND CAP-OFF OR REMOVE OBSOLETE EXISTING
UTILITY AND SERVICE LINES PRIOR TO STARTING DEMOLITION
WORK.
P REMOVE ABANDONED UNDERGROUND UTILITIES AND INSTALL
ENGINEERED FILL.
Q IF EXISTING ITEMS TO BE REMOVED OR DISTURBED ARE
SUSPECTED OR DISCOVERED TO CONTAIN ASBESTOS OR
OTHER HAZARDOUS MATERIALS, STOP DEMOLITION AND
NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
R REPAIR AND PATCH SPRAYED FIRE-RESISTIVE AND FIRESTOP
MATERIALS WHERE DAMAGED DUE TO SELECTIVE
DEMOLITION ACTIVITIES TO RESTORE ORIGINAL FIRE RATING
UNLESS OTHERWISE INDICATED.
S REFER TO WALL SECTIONS NOTED ON DEMOLITION PLANS
FOR ADDITIONAL DEMOLITION INFORMATION.
KEYNOTES - DEMOLITION
01 EXISTING WALL TO REMAIN
02 EXISTING WALL TO BE REMOVED
03 REMOVE EXISTING STOREFRONT, WINDOW, OR DOOR &
FRAME
04 EXISTING CASEWORK TO BE REMOVED
05 EXISTING STOREFRONT TO REMAIN
06 EXISTING DOOR & FRAME TO REMAIN
07 NO WORK IN THIS AREA
08 REMOVE EXISTING CEILING IN ITS ENTIRETY
10 EXTENT OF EXISTING FLOORING REMOVAL
11 REMOVE EXISTING WOOD TRANSITION AT PERIMETER OF
RAISED FLOOR
12 PROTECT EXISTING BRICK FLOOR IN THIS AREA
13 EXISTING BANK, ELECTRICAL, DATA, OR TELEPHONE
EQUIPMENT TO REMAIN
14 EXISTING DRINKING FOUNTAIN TO REMAIN
15 REMOVE EXISTING FINISH FLOORING
16 REMOVE EXISTING DOOR & HARDWARE. EXISTING FRAME TO
REMAIN
17 REMOVE EXISTING FIRE EXTINGUISHER & BRACKET.
SALVAGE FOR REINSTALLATION ELSEWHERE. PATCH WALL
AS REQ'D TO RECEIVE NEW FINISHES
18 EXISTING COUNTERTOP TO BE REMOVED
19 REMOVE EXISTING VINYL WALL COVERING FROM WALLS TO
REMAIN EXPOSED
3/8" = 1'-0"AD-101
F2 SECT THRU VAULT WALL
03.13.2017
DWLOUNGE
111
SUPPLIES
108
MEN
109
WOMEN
110
OFFICE
105
OFFICE
103
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
120
OFFICE
119
OFFICE
122
OFFICE
123
OFFICE
124
OFFICE
115
CONFERENCE
116
I.T.
107
Teller 1 Teller 2
JAN. / SUPPLY
MEN (EXIST.)WOMEN
(EXIST.)
EXISTING
STAIR
EXISTING
STAIR
STOR.
113
EXISTING
BLDG.
TRANSFORMER
EXISTING
BLDG. STOR.
EXISTING
BLDG. PHONE
EXISTING
BLDG. ELECT.
STORAGE
101A
LOBBY
101
ENTRY
VESTIBULE
EXISTING
SECONDARY
ENTRY
VESTIBULE
HALL
101B
EXISTING
ELEVATOR
A-220
D1
A-220
A6
A-220
E1122 123124101A108109110101C
119
120
106-2 113101BB1
+/- 5'-3"1'-6"107S6C.84
S2C.102
S3C.P
S3C.D.A
S3A.D
S3C.D
S3A.D.A
A-401
F1 EQEQOFFICE
118
OFFICE
121
OFFICE
117
OFFICE
114
D6
+/- 6'-0"121114117
S3A.D.A
S3C.PS3C.P
S3A.D.A S3A.D.A
S3A.D.A
S3A.D.A
S2C.D
S2C.D
S3A.D.A
S3A.D.A
S3A.D.A
S3A.D.AS3A.D.A
S3A.D.A
S3A.D.A
S3A.D.A
S3A.D.A
S3A.D
S3A.D
S3A.D
S3A.D.A
S3A.D.A
S3A.D.A
S3A.D.A
S3A.D.A
S3C.P
S3A.D S3A.D.1.A
S3A.D.1.A
S3C.D.A
A-601
B4
A-601
D4
118
115A-601
D4
A-601
D4
ALIGND7
A-220
ENTRY AREA
101C
HALL
101D
HALL
125
A-220 F5
Drive-Thru
Tellers
A7
A-520
A-520
C1
CHECK COUNTER
INFILL
OPENING IN
EXISTING
MASONRY
A-601
A4
OPP.
S3C.P
DN
1:20
F.E.C.
F.E.C.
116
S3A.D.A4'-4 1/4"4'-1"4'-1 3/4"4'-1"4'-1"4'-4 1/4"ADMIN. ASST.
101G
S3C.P
RELOCATED EXIST.
FIRE EXT. & BRACKET
(CONFIRM ACTUAL
LOCATION W/ ARCH.)
X-2 X-3
X-4
A-220 A1
ADMIN. ASST.
101F
RECEPTIONIST
101H
8'-2 3/4" +/-6'-1 1/2"9'-8" +/- (V.I.F.)9'-8 1/2" +/- (V.I.F.)9'-9"4'-5 13/16" +/-5'-1" +/-6'-10" +/-10 3/8" +/-EXISTING
CORRIDOR
ADJACENT
TENANT
SPACE
ADJACENT
TENANT
SPACE
ALIGN
ALIGN
A-601
E1
A-601
E1
1'-10"103
104
106-1
A-220F6 A-220
B510'-4"1'-11 1/2"4'-0 1/2"4'-0 1/2"8'-2 7/8" +/-2'-7"
A1
A-521
A3
A-521
C1
A-521
B7
A-220
E3
A-220
E5
A-220 E6 A-220E8
VERT. TUBE @
CENTER OF COUNTER
(REF. DETAIL)4"CASH DISP.
ALIGN9'-9 1/4"12'-0 3/8"EQ 12'-0"EQ 8'-1 1/4"
5'-0" MIN.
5'-0 3/8"+/- 8'-9 1/4"+/- 10'-1 7/32"
E5
A-521
E1
A-521
6 1/2"9 1/2"9'-0"11'-8 3/4"
E3
A-521
S3A.72.A
S3A.72.A
S3A.72.A
S3A.72.A
S3A.72.A
S3C.P
S3C.D
S3A.D.A
S3A.D.A
S3A.D.A
A-601
D4
SIM.
A-220D4
101E
S3A.D.A
103-1A-601
A4
S3C.D.A
A-521
E7
A-521
E7
SIM.
(5) 16" DEEP
MELAMINE ADJ.
SHELVES, ON
H.D. STANDARDS
CLOSET
103A
A-220
F8
(5) 16" DEEP
MELAMINE ADJ.
SHELVES, ON
H.D. STANDARDS
NEW PL-1 PLASTIC
LAMINATE
COUNTERTOP W/
GROMMETS
NEW TELLER
EQUIP, OWNER-
FURNISHED,
CONTRACTOR-
INSTALLED
S3A.D.A
S3C.D.A
S2C.D
20'-0"CORRIDOR
101E
A-520
C5
6'-5 1/4" +/-9'-6 5/8" +/-9'-0 9/16"5'-0" MIN.8'-8 1/2"8'-6"12'-1"4'-11"2'-0"
2'-2"
+/- 9'-6"+/- 3'-3"3'-4 1/2"
A-220A5
S3C.28.5
EXTEND
COUNTERTOP
OVER TOP OF
KNEE WALL
INSTALL F-1 FILMS
ON LOWER
PORTION OF
WINDOWS (UP
TO 2'-10" A.F.F.)
7'-3 27/32"10'-5 1/2"9'-6"5'-8 1/2"4'-0"
A1
A-401
S2C.102
S3C.53.A
PRINTERS, N.I.C.
BANK EQUIPMENT, N.I.C.
S2C.P
100'-1 1/4"
100'-0"
100'-1 3/4"100'-1 3/4"
(V.I.F.)
2'-1" +/-
3'-10"
EXISTING VAULT DOOR
FIXED IN THE OPEN
POSITION
1-6" MIN.
F3
S2C.84
CHASE1'-8"4'-0" MIN.15'-11"A-520 A1
10'-7 7/16"10"S3C.D
S3C.P
S2C.P
S3C.D.A
S3C.D
S3A.D.A
S3C.D.A
S3C.D
S3A.D.A
S3C.P
S3C.P
S1FA.97
S3C.D
S3C.D.A S3C.D.A
S2C.D
S2C.D
S3C.D.A
C7
A-520
S1FA.97
EQ EQ
X-1
A-520
G5
2 EQ. WD PANELS
1'-7 1/8"3'-0"2'-2"A-520
F5
WALLS ARE PART
OF FURNITURE
SYSTEMS (BY OTHERS)
AG-1 PER SPEC 09 51 23
APPLIED TO WALL - REFER TO ELEVATION
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:11 PMA-101
FIRST LEVEL FLOOR
PLAN
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
KEYNOTE LEGEND
00 10 00.A1 CENTER WALL ON COLUMN LINE
1/4" = 1'-0"A-101
A1 FIRST LEVEL FLOOR PLAN
03.13.2017
GYB BOARD CEILING
(REFER TO PLAN FOR
SUSPENSION TYPE)
ACOUSTIC CEILING TILE
2 x 4 LIGHT FIXTURE
DOWNLIGHT
MECHANICAL RETURN REGISTER
MECHANICAL AIR SUPPLY DIFFUSER
SPOT ELEVATION MARKER
XXX-01
28'-10" A.F.F.
CEILING TAG
CEILING TYPE
CEILING HEIGHT
(ABOVE FINISH FLOOR)
ACT-1
10'-0" A.F.F.
ACT-1
10'-0" A.F.F.
ACT-1
10'-0" A.F.F.
ACT-1
10'-0" A.F.F.
ACT-1
10'-0" A.F.F.
ACT-1
8'-0" A.F.F.
ACT-1
9'-0" A.F.F.
ACT-1
9'-0" A.F.F.
ACT-1
9'-0" A.F.F.
ACT-1
9'-0" A.F.F.
ACT-1
10'-0" A.F.F.
ACT-1
8'-0" A.F.F.ACT-1
10'-0" A.F.F.
ACT-1
8'-0" A.F.F.
ACT-1
8'-0" A.F.F.
ACT-1
8'-0" A.F.F.ACT-1
8'-0" A.F.F.
ACT-1
8'-0" A.F.F.
ACT-1
9'-0" A.F.F.
2'-3"30'-0"+/- 1'-7 5/16"+/- 4'-0"30'-0"+/- 4'-0"S3A.D
S3C.D
ACT-1
10'-0" A.F.F.
GWB-X1
10'-0" A.F.F.S3C.A
GWB-X1
7'-11" A.F.F.V.I.F.EXIST. TUBES
TO REMAIN
S3A.D
107'-11"24'-0"8'-0"
40'-8"8'-0"8'-0"AG-1
AG-1
8'-0" A.F.F.
8'-0" A.F.F.
GWB-X1
8'-0" A.F.F.
ACT-1
9'-0" A.F.F.
ACT-1
9'-0" A.F.F.
S3A.D.A
S3A.D.A
(ABOVE)
(ABOVE)
S3C.A
S3A.D.A (ABOVE)
S3A.D.A
(ABOVE)
S3A.D.A
S3A.D.A
(ABOVE)
(ABOVE)
S3A.D.A
(ABOVE)
S3A.D.A
(ABOVE)S3A.D.A
(ABOVE)
ACT-1
10'-0" A.F.F.
GWB-X1
7'-0" A.F.F.
GWB-X1
7'-6" A.F.F.EQ2'-0"2'-0"EQACT-1
8'-0" A.F.F.
LOUNGE
111
SUPPLIES
108
MEN
109
WOMEN
110
OFFICE
105
OFFICE
103
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
120
OFFICE
119
OFFICE
122
OFFICE
123
OFFICE
124
OFFICE
115
CONFERENCE
116
I.T.
107
JAN. / SUPPLY
199
MEN (EXIST.)
198
WOMEN
(EXIST.)
197
EXISTING
STAIR
196
EXISTING
STAIR
190
STOR.
113
EXISTING
BLDG.
TRANSFORMER
195
EXISTING
BLDG. STOR.
193
EXISTING
BLDG. PHONE
191
EXISTING
BLDG. ELECT.
192
STORAGE
101A
EXISTING
ELEVATOR
189
HALL
101B
LOBBY
101
ENTRY
VESTIBULE
100
EXISTING
SECONDARY
ENTRY
VESTIBULE
OFFICE
118 OFFICE
121
OFFICE
117
OFFICE
114
ADJACENT
TENANT
SPACE
ADJACENT
TENANT
SPACE
EXISTING
CORRIDOR
ENTRY AREA
101C
HALL
101D
HALL
125
CLOSET
103A
CORRIDOR
101E
EQ 2'-0"EQ
1'-2"EQ4'-0"EQEQ10'-0"EQ0"EQ 12'-0"EQ
ALIGN
GWB-X1
7'-0" A.F.F.EQ2'-0"EQACT-1
8'-0" A.F.F.
1'-0"
2'-6"1'-6"GWB-X1
7'-0" A.F.F.
2'-6"1'-6"GWB-X1
9'-0" A.F.F.GWB-X19'-0" A.F.F.GWB-X1
9'-0" A.F.F.
GWB-X1
9'-0" A.F.F.
GWB-X1
9'-0" A.F.F.
ACT-1
7'-8" A.F.F.
3'-5"+/- 33'-10 5/16"3'-5"
S3C.A
S3C.A
S3C.A
S3C.A
S3C.A
(ABOVE)
(ABOVE)
(ABOVE)
(ABOVE)
(ABOVE)
S3C.A (ABOVE)
6"6"6"6"
ACT-1
8'-0" A.F.F.
ACT-1
8'-0" A.F.F.
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:15 PMA-131
FIRST LEVEL
REFLECTED CEILING
PLAN
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
GENERAL CEILING PLAN NOTES
A THESE GENERAL NOTES APPLY TO [SERIES 300] REFLECTED
CEILING DRAWINGS.
B INSTALL NEW CEILINGS AT ▐►+8'-0"◄▌ A.F.F. UNLESS NOTED
OTHERWISE.
C CENTER CEILING GRIDS WITHIN ROOMS EACH DIRECTION
UNLESS NOTED OTHERWISE.
D LOCATE CEILING GRIDS WITHIN ROOMS SUCH THAT BORDERS
CONTAIN NOT LESS THAN 1/2 TILE WIDTH, UNLESS
OTHERWISE INDICATED.
E CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS
WITHIN INDIVIDUAL CEILING PANELS, SUCH AS SPRINKLER
HEADS, DIFFUSERS, LIGHT FIXTURES, ETC., UNLESS
OTHERWISE INDICATED.
F PAINT EXPOSED GYPSUM BOARD AND PLASTER CEILING
SURFACES UNLESS OTHERWISE INDICATED.
G PROVIDE CONTROL JOINTS (C.J.) IN GYPSUM BOARD CEILING
CONSTRUCTION AS INDICATED. WHERE NOT SHOWN,
PROVIDE MAXIMUM SPACING BETWEEN JOINTS OF 30'-0."
VERIFY FINAL CONTROL JOINT LOCATIONS WITH ARCHITECT
PRIOR TO STARTING WORK WHETHER OR NOT INDICATED ON
THE DRAWINGS.
H CEILING ACCESS PANELS INDICATED ARE NOT INTENDED TO
LIMIT NUMBER OF PANELS REQUIRED. PANEL QUANTITY
SHALL BE SUFFICIENT TO PROVIDE REQUIRED ACCESS
WHETHER OR NOT INDICATED ON THE DRAWINGS. VERIFY
FINAL LOCATIONS WITH ARCHITECT PRIOR TO STARTING
WORK.
J REFER TO ▐►SERIES 000◄▌ GENERAL INFORMATION
DRAWINGS FOR MATERIAL SYMBOL KEY.
K REFER TO ▐►SERIES 900◄▌ FINISH PLANS FOR ADDITIONAL
CEILING FINISH INFORMATION.
L REFER TO ELECTRICAL DRAWINGS FOR CEILING-MOUNTED
LIGHT FIXTURE TYPES AND QUANTITIES.
M REFER TO MECHANICAL DRAWINGS FOR CEILING-MOUNTED
DIFFUSERS, GRILLE TYPES AND QUANTITIES.
N REFER TO FIRE PROTECTION DRAWINGS FOR SPRINKLER
HEAD TYPES AND QUANTITIES. HEADS HAVE BEEN
INTENTIONALLY OMITTED FROM REFLECTED CEILING PLANS
FOR CLARITY.
REV. 03/31/09
CEILING LEGEND
KEYNOTE LEGEND
1/4" = 1'-0"A-131
A1 FIRST LEVEL RCP
03.13.2017
DWLOBBY
101
TELLERS
102
WORK ROOM
106
I.T.
107
SUPPLIES
108
MEN
109
WOMEN
110
OFFICE
105
OFFICE
104
OFFICE
103
HALL
101B
LOUNGE
111
ENTRY AREA
101C
HALL
101D
CONFERENCE
116
OFFICE
115
OFFICE
114
OFFICE
117
OFFICE
118
OFFICE
121
HALL
125
OFFICE
124
OFFICE
123
OFFICE
122
OFFICE
119
OFFICE
120
STORAGE
101A
STOR.
113
EXISTING
STAIR
ENTRY
VESTIBULE
EXISTING
ELEVATOR
EXISTING
BLDG. PHONE
EXISTING
BLDG. ELECT.
EXISTING
BLDG. STOR.
EXISTING
SECONDARY
ENTRY
VESTIBULE
EXISTING
STAIR
WOMEN
(EXIST.)MEN (EXIST.)
JAN. / SUPPLY
EXISTING
BLDG.
TRANSFORMER
ADJACENT
TENANT
SPACE
EXISTING
CORRIDOR
ADJACENT
TENANT
SPACE
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:17 PMA-141
FIRST LEVEL
FURNITURE PLAN
(FOR REFERENCE
ONLY)
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"A-141
1 FIRST LEVEL FURNITURE PLAN (FOR REFERENCE ONLY)
03.13.2017
DWA7
A-520
W
B
F
WB-1
LVT-1/CPT-2&4
PT-1 / WD-1
LOBBY
101
W
B
F
WB-1
CPT-2
PT-1 / WD-1
TELLERS
102
W
B
F
WORK ROOM
106
RB-1
CPT-2
PT-1
W
B
F
I.T.
107
RB-1
CPT-1
PT-1
W
B
F
RB-1
LVT-1
PT-1
HALL
101B
W
B
F
RB-1
LVT-1
PT-1
SUPPLIES
108
W
B
F
RB-1
LVT-1
PT-3
MEN
109
W
B
F
RB-1
LVT-1
PT-3
WOMEN
110
W
B
F
RB-1
CPT-2
PT-1
OFFICE
105
W
B
F
RB-1
CPT-2
PT-1
OFFICE
104
W
B
F
RB-1
CPT-2
PT-1
OFFICE
103
W
B
F
RB-1
CPT-2
PT-1
STORAGE
101A
W
B
F
RB-1
CPT-2
PT-1
OFFICE
120
W
B
F
RB-1
CPT-2
PT-1
OFFICE
119
W
B
F
RB-1
CPT-2
PT-1
OFFICE
122
W
B
F
RB-1
CPT-2
PT-1
OFFICE
123
W
B
F
RB-1
CPT-2
PT-1
OFFICE
124
W
B
F
RB-1
CPT-2
PT-1
OFFICE
118
W
B
F
RB-1
CPT-2
PT-1
OFFICE
121
W
B
F
RB-1
CPT-2
PT-1
OFFICE
114
W
B
F
RB-1
CPT-2
PT-1
OFFICE
117
W
B
F
RB-1
CPT-2
PT-1
OFFICE
115
W
B
F
RB-1
CPT-2 / CPT-4
PT-1
CONFERENCE
116
W
B
F
RB-1
CPT-2
PT-1
HALL
101D
W
B
F
WB-1
CPT-2
PT-1
ENTRY AREA
101C
W
B
F
RB-1
LVT-1
PT-1
LOUNGE
111
W
B
F
HALL
125
RB-1
CPT-2 / EXIST.
PT-1
EXISTING
BLDG. PHONE EXISTING
BLDG. ELECT.
EXISTING
BLDG. STOR.
EXISTING
SECONDARY
ENTRY
VESTIBULE
EXISTING
STAIRWOMEN
(EXIST.)MEN (EXIST.)
JAN. / SUPPLY
EXISTING
BLDG.
TRANSFORMER
W
B
F
EXISTING
CPT-1
EXISTING
ENTRY
VESTIBULE
100
EXISTING
STAIR
EXISTING
ELEVATOR
W
B
F
RB-1
CPT-2
PT-1
STOR.
113
ADJACENT
TENANT
SPACE
EXISTING
CORRIDOR
ADJACENT
TENANT
SPACE
W
B
F
RB-1
CPT-2
PT-1
RECEPTIONIST
101H
W
B
F
RB-1
CPT-2
PT-1
ADMIN. ASST.
101G
W
B
F
RB-1
CPT-2
PT-1
ADMIN. ASST.
101F8'-0"EQEQCPT-4
T-2EXISTING
BRICK
PAVERS
WT-3D
WT-3D
WT-1A
WT-1A
1 1 1 1 1
11
1
1
1
1 1 1
11
1
1
1
1
WT-1C
WT-1C
WT-1B WT-1B WT-1B WT-1B WT-1B WT-1B
1
W
B
F
RB-1
CPT-2
PT-1
CLOSET
103A
CPT-2
CPT-4
SEAM BUT NO
TRANSITION,
ALIGN CPT
JOINTS AND
LVT JOINTS
CENTER
FIRST TILE EQTILEFULLEQEQ
TILE
FULL EQ
INSTALL CARPET TILE
AT 45 DEGREE ANGLE
SEAM BUT NO
TRANSITION,
ALIGN CPT AND
LVT JOINTS
WB-1
RB-1
WB-1RB-1
WB-1WB-1WB-1RB-1WB-1RB-1
PAINT (E) DOOR
FRAME PT-1A
NO NEW
FINISHES
PAINT DOOR
FRAME PT-1A
NO NEW
FINISHES
W
B
F
CORRIDOR
101E
WD-1
LVT-1
PT-1
WT-2B
WT-2B
ACOUSTIC GRILLE
CEILING ABOVE
C.L. OF WOOD
GRILLE
FLOORING
STARTING
POINT
PT-4PT-4PT-4
PT-4 PT-4PT-4
PT-4PT-4PT-4PT-4PT-4PT-51 1 1 1 1 T-3T-2DN
1:20
EQ EQ
SKIM-COAT OVER EXISTING BRICK TO
CREATE A SMOOTH SURFACE FOR
INSTALLING NEW CARPET
T-4 T-4 T-4 T-1CPTCPTLVT
LVTCPTCPTLVTCPTLVTXX-01 FLOORING TRANSITION -
REFER TO FINISH SCHEDULE
W
B
F
Room name
XXXXX
Base Fin
Floor Fin
Wall Fin
150 SF
ROOM NAME AND
ROOM FINISHES
PT-XX ACCENT WALL FINISH
DESIGNATION
FLOORING DIRECTION
LVT-1 OR CPT-2 PER FINISH
SCHEDULE
CPT-4 PER FINISH SCHEDULE
= COAT HOOK MOUNTED TO FACE OF DOOR
THAT SWINGS AGAINST THE WALL
BASIS OF DESIGN:
MFR: GAMCO
PROD: 76827 HAT AND COAT HOOK
FINISH: SATIN
1
WT-#X = 1 = SHADE BAND MATERIAL (5% OPENESS)
2 = SHADE BAND MATERIAL (1% OPENESS)
3 = OPAQUE FABRIC
A = 3'-9" WIDE X 9'-6" HIGH
B = 5'-4" WIDE X 9'-6" HIGH
C = 3'-0" WIDE X 8'-0" HIGH
D = 4'-8" WIDE X 3'-6" HIGH
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:19 PMA-151
FIRST LEVEL FINISH
PLAN
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
GENERAL FINISH PLAN NOTES
A THESE GENERAL NOTES APPLY TO ▐►SERIES 900◄▌ FINISH
DRAWINGS.
B
PAINT NEW AND EXISTING HOLLOW METAL DOORS,
DOORFRAMES AND LINTELS EXPOSED TO VIEW IN FINISHED
AREAS AND AT EXTERIOR LOCATIONS UNLESS OTHERWISE
INDICATED.
C PAINT STEEL COLUMNS, BEAMS, STRUCTURE, ETC., EXPOSED
TO VIEW IN FINISHED AREAS UNLESS OTHERWISE INDICATED.
D
PAINT EXISTING FIRE EXTINGUISHER CABINETS, METAL
ACCESS PANELS, LOUVERS, UNIT VENTILATORS AND OTHER
PAINTABLE SURFACES IN ROOMS TO BE FINISHED UNLESS
OTHERWISE INDICATED.
E
FINISH SOFFITS, BULKHEADS, AND SIMILAR CONDITIONS TO
MATCH SURROUNDING SURFACES UNLESS OTHERWISE
INDICATED.
F
IN STAIRWELLS, PAINT STEEL STAIR AND LANDING PARTS
EXPOSED TO VIEW INCLUDING RISERS AND TREADS,
STRINGERS, UNDERSIDE OF STAIR STRUCTURE, HANDRAILS,
WALL BRACKETS, COMPONENTS VISIBLE FROM EXTERIOR,
ETC., UNLESS OTHERWISE INDICATED.
G
▐►DO NOT APPLY◄▌ ▐►PROVIDE◄▌ FINISHES BEHIND
FIXED EQUIPMENT SUCH AS CABINETRY, CASEWORK, CHALK
AND TACKBOARDS, LOCKERS, ETC.
H
ALIGN FLOOR FINISH TRANSITIONS AT DOOR LOCATIONS
WITH CENTERLINE OF DOOR SUCH THAT TRANSITION
MATERIALS ARE NOT VISIBLE FROM EITHER SIDE WHEN DOOR
IS IN CLOSED POSITION.
J REFER TO REFLECTED CEILING PLANS AND INTERIOR
ELEVATIONS FOR ADDITIONAL FINISH INFORMATION.
K
REFER TO PROJECT MANUAL DIVISION 9 FOR FINISH LEVEL
REQUIREMENTS FOR GYPSUM BOARD SURFACES UNLESS
OTHERWISE INDICATED.
REV. 03/31/09
1/4" = 1'-0"A-151
C3 FIRST LEVEL FINISH PLAN
FINISHES-SYMBOLS LEGEND
KEYNOTE LEGEND
ACCESSORIES
WINDOW TREATMENTS 03.13.2017
FIRST LEVEL
100'-0"
B3
A-601
D1
A-601
B1
A-601
A1
A-601
GL-2 TYP.
GL-1 TYP.5'-6"F-1 FILM APPLIED
TO GLAZING
FIRST LEVEL
100'-0"
D4
A-601
SIM.
A6
A-601
B1
A-601
SIM.
D1
A-601
A1
A-601
OPP.
GL-2 TYP.
GL-1 TYP.5'-6"F-1 FILMS APPLIED
TO GLAZING
FIRST LEVEL
100'-0"
A3
A-601
D1
A-601
B1
A-601
OPP.
A4
A-601
SIM.
GL-2 TYP.
GL-1 TYP.5'-6"F-1 FILMS APPLIED TO
GLAZING
FIRST LEVEL
100'-0"
A-520
A7
F.E.C.4'-0"D4
A-601
D4
A-601
SIM.
D1
A-601
D1
A-601
B3
A-601B4
A-601
B3
A-601
A1
A-601
TYP.
A1
A-601
TYP.
OPP.OPP.
GL-2 TYP.
GL-1 TYP.
GL-2 TYP.
GL-1 TYP.5'-6"F-1 FILMS APPLIED
TO GLAZING
F-1 FILMS APPLIED
TO GLAZING (TYP.)
ALIGN TOP OF FILM
FIRST LEVEL
100'-0"
D4
A-601
SIM.
A4
A-601
SIM.
A4
A-601
SIM.
A1
A-601
GL-2 TYP.
GL-1 TYP.5'-6"F-1 FILMS APPLIED TO
GLAZING (TYP.)
FIRST LEVEL
100'-0"
A4
A-601
OPP.
A4
A-601
A1
A-521
A3
A-521 C1
A-521
MITER CORNERS
OF PANELS
2'-6"1'-6"D1
A-601
OPP.
GL-2 TYP.
GL-1 TYP.
5/16" LAM. GL.
5/16"
LAM. GL.
QUARTZ
COUNTERTOP
MAT'L (QTZ-1)5'-6"F-1 FILMS APPLIED
TO GLAZING
FIRST LEVEL
100'-0"
3'-0"3'-0"3'-0"2'-9"1" FILLER2'-6"1'-8"2'-10"ALL CABINETS TO BE
PL-2
PL-1 COUNTER
ADJ. SHELVES (TYP.)
FIRST LEVEL
100'-0"
D4
A-601
B4
A-601
A4
A-601
D4
A-601
A4
A-601
OPP.
A1
A-601
A1
A-601
B3
A-601 SIM.
B3
A-601 SIM.
D1
A-601
OPP.
D1
A-601
7'-0 3/4"GL-2 TYP.
GL-1 TYP.
GL-2 TYP.
GL-1 TYP.5'-6"F-1 FILMS APPLIED
TO GLAZING (TYP.)
F-1 FILMS APPLIED
TO GLAZING (TYP.)
FIRST LEVEL
100'-0"
TCD
UNDERCOUNTER
PEDESTALS
KNEE
SPACE
KNEE
SPACE
APRON CASE
2'-6"2'-6"4'-0"3'-6"10"11'-4 1/4"10"4'-1 1/4" +/-3'-0"
A1
A-521
A3
A-521C1
A-521
ROUT QUARTZ SIDE
PANEL TO ACCEPT
END OF LAM. GLASS.
NOTCH TO STOP @
BOTTOM OF GLASS
ROUT QUARTZ
SIDE PANEL TO
ACCEPT END OF
LAM. GLASS
1'-2"4"FIRST LEVEL
100'-0"4"4 EQ. PANELS1/2" GAP @
PERIMETER
1/2" REVEAL
BETWEEN PANELS
(TYP.). PAINT COLOR ON WALL
SURFACE BEHIND PANELS PER
ARCHITECT
CONFIRM W/OWNER5'-4" +/-TV BY
OWNER
EQ 4'-4"4'-4"4'-4"EQ
+/- 20'-1 1/2"6'-1 1/4"DIMENSION PER PLAN
2'-10"3/4" WD-1 WOOD
VENEER PANELS
ON Z-CLIPS
QTZ-1 COUNTER
WOOD CABINET
(MATCH WD-1)
SCHEDULED
BASE
FIRST LEVEL
100'-0"2'-6"2'-0"2'-6"KNEE
SPACE
17"D OPEN
SHELVING
(PL-2)
2'-6"3'-1"2'-9"2'-9"
1" FILLERLEDGER AS REQ'D
FINISHED
END
APPLY F-1 FILM
TO EXIST. GLAZING
UP TO 2'-10" A.F.F.
PL-1 COUNTER &
BACKSPLASH
PL-2 CABINETS
FIRST LEVEL
100'-0"2'-6"4"QUARTZ COUNTERTOP
MAT'L (QTZ-1)
WD-1 WOOD VENEER
PANELS (MITER @
CORNERS)FIRST LEVEL
100'-0"2'-6"4"1'-8"
QUARTZ COUNTERTOP
MAT'L (QTZ-1) TO WRAP
DOWN END OF DESK
SCHEDULED BASE
FIRST LEVEL
100'-0"2'-6"4"12'-0"
1'-3"2'-10"7'-2"
E5
A-521
E1
A-521
OPEN
3 1/2"
QUARTZ COUNTER
MAT'L (QTZ-1)
WOOD VENEER
PANELS (WD-1)
6 1/2"
9 1/2"
TRASH SLOT
DIMENSIONS
HINGED WD-1 PANEL
W/ FLUSH PULL
E3
A-521
FIRST LEVEL
100'-0"
12'-0"
1'-3"2'-10"7'-2"8"2'-10"E5
A-521 E1
A-521
OPEN
E3
A-521
9"1'-6 1/4"3'-6 1/2"1'-6 1/4"
FIRST LEVEL
100'-0"
D1
A-601
A6
A-601
SIM.
A1
A-601
GL-2 TYP.
FIRST LEVEL
100'-0"
+/- 4" FILLER 3'-0"2'-6"2'-6"2'-0"3'-0"3'-0"1 1/2" FILLER
FULL-HEIGHT
FILLER PANEL 2'-6"1'-8"2'-10"ADA-COMPLIANT
DISHWASHER
ALL CABINETS TO
BE PL-2
SS-2 COUNTER &
BACKSPLASH / SIDE-
SPLASH
ADJ. SHELVES
(TYP.)
REF.
M.W.M.W.
FIRST LEVEL
100'-0"2'-6"1'-8"2'-10"3 EQ. CABINETS
FILLER EA.
END
PL-2 CABINETS
ADJ. SHELVES
(TYP.)
PL-1 COUNTER
FIRST LEVEL
100'-0"
EQ 2'-4 1/2"2'-4 1/2"EQ
GWB SOFFIT
2'-6"1'-8"2'-10"WOOD CABINETS
(MATCH WD-1)
QTZ-1 COUNTER
ADJ. SHELVES
(TYP.)
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:23 PMA-220
INTERIOR
ELEVATIONS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"A-220
D7 CONF. ROOM ENTRY ELEVATION
1/4" = 1'-0"A-220
E1 HALL 101D NORTH ELEVATION
1/4" = 1'-0"A-220
D6 HALL 101E SOUTH ELEVATION
1/4" = 1'-0"A-220
D1 HALL 125 NORTH ELEVATION
1/4" = 1'-0"A-220
B1 LOBBY - WEST ELEVATION
1/4" = 1'-0"A-220
A6 LOBBY - SOUTH ELEVATION / TELLER AREA
1/4" = 1'-0"A-220
F5 I.T. ROOM ELEVATION
1/4" = 1'-0"A-220
A1 CORRIDOR - EAST ELEVATION
1/4" = 1'-0"A-220
B5 TELLER AREA - BACK OF COUNTER
1/4" = 1'-0"A-220
B7 TELLER AREA - BACK WALL
1/4" = 1'-0"A-220
F6 WORK ROOM ELEVATION
1/4" = 1'-0"A-220
E8 CHECK DESK END ELEV. 2
1/4" = 1'-0"A-220
E6 CHECK DESK END ELEV. 1
1/4" = 1'-0"A-220
E5 CHECK DESK SOUTH ELEV.
1/4" = 1'-0"A-220
E3 CHECK DESK NORTH ELEV.
1/4" = 1'-0"A-220
D4 HALL 101E NEW DOOR & SIDELITES
1/4" = 1'-0"A-220
F3 LOUNGE - WEST ELEVATION
1/4" = 1'-0"A-220
F8 SUPPLY ROOM CASEWORK
1/4" = 1'-0"A-220
A5 ENTRY AREA 101C
03.13.2017
1'-5"8'-1 1/8"4 7/8"8'-1 1/8"7'-8 1/4"109110A-401F6WOMEN
110
MEN
109
7"
F5
F3
0303
05B
01A01A
05B
05D
05A 05D
05A
08
08
06B06B
S3C.D.A
S3A.D.A
S3A.D.A
S3A.D.A
A-401 F6
F3
F5
OPP. SIM.
OPP.
OPP.
02
5'-0" CLEAR7"
D1
A-401
S3A.D.A
S3C.D.A3'-0"FIRST LEVEL
100'-0"2'-0"3'-0"6"2'-10"06B 05D
05A
03
05B
3"
1'-4 1/8"
D1
A-4013'-10"3'-2"MIRROR
2'-8 1/4"5'-0"
SS-1 COUNTER
& SPLASHES
PL-2 PANELS
FIRST LEVEL
100'-0"
2'-8"4'-0"01A
06B
FINISHED END PANEL (PL-2)
MIRROR
FIRST LEVEL
100'-0"2'-10"1'-6"6"3'-4"
3'-6"1'-0"2'-0"7"
05D
05A
03
05B
02 6'-6"08
01A
03
05A
05B
PAPER TOWEL DISPENSER & WASTE RECEPTACLE
COMBINATION - RECESSED
MANU: GAMCO
PROD: TD-3
TOILET PAPER HOLDER - DOUBLE ROLL
MANU: GAMCO
PROD: 76867
GRAB BAR - 36" HORIZONTAL
MANU: GAMCO
PROD: 125S - SNAP
GRAB BAR - 42" HORIZONTAL
MANU: GAMCO
PROD: 125S - SNAP
05D GRAB BAR - 18" VERTICAL
MANU: GAMCO
PROD: 125S - SNAP
08 MIRROR - FULL LENGTH
MANU: GAMCO
PROD: C-SERIES, 24" x 72"
06B SOAP DISPENSER - SURFACE MOUNT
MANU: GAMCO
PROD: G-16AP
02 SANITARY NAPKIN DISPOSAL - SURFACE MOUNTED
MANU: GAMCO
PROD: ND-5
FIRST LEVEL
100'-0"
HALL
101B
LOUNGE
1118'-0"OPENING1'-0"7'-1"CHASE
7'-0" TO B.O. SOFFITB.O. SUSP. CEILING ON
OTHER SIDE OF SOFFIT
DUCT
OPENING+/- 6"+/- 4"PIPE
COORDINATE THESE
DIMENSIONS WITH MEP
FIRST LEVEL
100'-0"2'-10"1'-11"5"1 1/2"1'-3 1/2"6" MAX.1 1/2"SOLID SURFACE COUNTER
& BACKSPLASH (SS-1)
3/4" PANEL, PLASTIC LAMINATE
(PL-2)
GLIDEWALL CLEAT WITH ROLLER
CATCH
FINISHED END PANEL (PL-2)9" MIN.2"MIRROR
4"CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:25 PMA-401
ENLARGED PLANS &
ELEVATIONS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/2" = 1'-0"A-401
F1 ENLARGED PLAN AT RESTROOMS
1/2" = 1'-0"A-401
F6 TOILET ROOM ELEVATION
1/2" = 1'-0"A-401
F5 TOILET ROOM SOUTH ELEVATION
1/2" = 1'-0"A-401
F3 TOILET ROOM NORTH ELEVATION
TOILET ACCESSORY LEGEND
1" = 1'-0"A-401
A1 SECT THRU NORTH WALL OF LOUNGE
1 1/2" = 1'-0"A-401
D1 VANITY SECTION
03.13.2017
FIRST LEVEL
100'-0"
GRAPHICS
BY
OWNER
N.I.C.
GRAPHICS
BY
OWNER
N.I.C.3'-7"2'-10"EQ 2'-7"8"2'-7"
T.V. BY OWNER
EQ COOR. W/ OWNER EQ8'-2"3'-6"COOR. W/ OWNERWB-1 WB-1
1/2" REVEAL (TYP.)
3/4" WD-1 WOOD VENEER WALL
PANELS ON Z-CLIPS
WOOD TRIM
FINISHED TO
MATCH PANELS
F4
A-520
1/2" REGLET IN GYP.
BD. WALL TO MATCH
WOOD PANEL REVEAL
(FRY REGLET). PAINT
W/ WALL
WOODWORKS GRILLE CEILING
& WALL
3'-1 1/2"2'-6"4"ACOUSTIC GRILLE AG-1 PER SPEC SECT 09 51 23
APPLIED TO WALL
PAINT WALL SURFACE PT-6 BEHIND ACOUSTIC GRILLE
PAINT WALL SURFACE PT-6 BEHIND
WOOD PANELS AT REVEALS, TYP.
FIRST LEVEL
100'-0"
FRAMELESS
GLAZING
3'-10 3/4"3'-4"1'-0 1/2"6'-0 3/4"6'-0 3/4"8'-3 1/4"
MITER PANELS
@ CORNERS
WB-1
1/2" REVEAL
(TYP.)
F7
A-520
GL-1
WOOD TRIM
1x WOOD CAP
TO MATCH
PANEL FINISH
3/4" WD-1 WOOD
VENEER PANELS
ON Z-CLIPS
FIRST LEVEL
100'-0"
WB-1 6'-0 3/4"+/- 25'-3 7/8"
EQ 4'-0"4'-0"4'-0"4'-0"4'-0"EQ
C7
A-520
MITER PANELS @
CORNERS (TYP.)
1x WOOD CAP TO
MATCH PANEL
FINISH
1/2" REVEAL
(TYP.)
WOODWORKS GRILLE CEILING
WD-1 WOOD VENEER PANELS ON Z-CLIPS
FIRST LEVEL
100'-0"
1 :20
EXIST. BRICK PAVERS
TO REMAIN
EXISTING CONC. SLAB
FIELD VERIFY
FIRST LEVEL
100'-0"
3/4" WD-1 WOOD VENEER
PANELS ON Z-CLIPS
SCHEDULED PARTITION3/4"1/2"3'-1"1/2"2'-5 1/2"1/2"4"WOOD BASE WB-1
(ALIGN W/ FACE OF
WOOD PANELS)6'-0 3/4"1x WOOD CAP TO
MATCH PANEL FINSH
PAINTED WD. STRIP
@ EA. REVEAL
(PAINT PT-6)
103'-6"
103'-5 1/4"1'-0"2 3/4"3/4"1/2"3/4"1/2"3/4" WD-1 WOOD
VENEER PANELS
ON Z-CLIPS
1x WOOD TRIM
TO MATCH
PANEL FINISH
1x1 WOOD GLAZING
STOP. MATCH
PANEL FINISH
GL-1
SCHEDULED PARTITION
PAINTED WOOD STRIP
@ EA. REVEAL
(PT-6)
J-MOLD W/
BACKER ROD &
SEALANT
3/4" WD-1 WOOD VENEER
PANELS ON Z-CLIPS
1x WOOD CAP
TO MATCH PANEL
FINISH
SCHEDULED PARTITION
1/2" REVEAL W/ PT-6
PAINTED WOOD STRIP
(TYP.)3'-5"1x WOOD TRIM @
PERIMETER OF
RECESS. FINISH
TO MATCH WOOD
PANELS
1/2" REVEAL W/ PT-6
PAINTED WOOD STRIP
(TYP. @ HORIZ. &
VERT. REVEALS)
3/4" WD-1 WOOD VENEER
PANELS ON Z-CLIPS
SCHEDULED PARTITION
EXIST. WALL
PAINT EXIST.
WALL (COLOR BY
ARCH.)5 1/4"1/2"1/2"EXIST. WALL
1x WOOD TRIM
@ PERIMETER
OF OPENING &
GRAPHICS
RECESSES.
FINISH TO MATCH
WD PANELS
SCHEDULED
PARTITION
3/4" WD-1 WOOD VENEER
PANELS ON Z-CLIPS
1/2" REVEAL (TYP.)
WD. STRIP @ EA.
REVEAL, PAINTED
(PT-6)
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:27 PMA-520
INTERIOR DETAILS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/2" = 1'-0"A-520
C1 WAITING AREA ELEVATION
1/2" = 1'-0"A-520
C5 WOOD WALL - NORTH ELEVATION
1/2" = 1'-0"A-520
A1 WOOD WALL - WEST ELEVATION
3" = 1'-0"A-520
A7 SLOPING FLOOR TRANSITION
1 1/2" = 1'-0"A-520
C7 TYP. WOOD WALL SECTION
1 1/2" = 1'-0"A-520
F7 DETAIL - WINDOW IN WOOD WALL
1 1/2" = 1'-0"A-520
G5 WOOD JAMB @ WD. PANEL WALL
1 1/2" = 1'-0"A-520
F4 GRAPHICS RECESS @ WOOD WALL
1 1/2" = 1'-0"A-520
F5 PLAN DETAIL - WAITING AREA WOOD WALL
03.13.2017
FIRST LEVEL
100'-0"
10"1'-8 1/2"5"4"(REMOVABLE PANEL)2'-8"1 1/2"3'-6"4"1'-2"4"1'-6"4"4"5 1/2"
4"
2'-0"3/4"3"1/2" PLYWOOD W/
BLACK MELAMINE
(REMOVABLE PANELS)
PLASTIC LAMINATE
COUNTERTOP &
BACKSPLASH (PL-3)
QTZ-1 QUARTZ
WALL BEYOND
LINE OF ACCESSIBLE
COUNTER BEYOND
3/4" QTZ-1 QUARTZ COUNTER
MATERIAL OVER 3/4" PLYWOOD
2x TOP PLATE, GLUED &
SCREWED TO TOP OF STUD
WALL
3/4" QUARTZ (QTZ-1) OVER
BLOCKING AS REQ'D
3/4" QTZ-1 QUARTZ OVER
BLOCKING AS REQ'D
1/2"W REVEAL (TYP. HORIZ.
& VERT.). PROVIDE BLOCKING
@ EA. REVEAL, PAINTED BLACK
1/2" PLYWOOD. PAINT BLACK
@ VERTICAL REVEALS
4'-0"C7
A-521
RAKKS EH-181FM
BRACKET MOUNTED
TO WOOD STUDS @
32" O.C.
MIN. 37.75" CLEARANCE
FOR CASH DISPENSER
(VERIFY W/ SUPPLIER)
3/4" QTZ-1 QUARTZ CAP
ON END OF WALL
4" x 2 1/2" x 1/8" STEEL TUBE
@ CENTER OF COUNTER
W/ 10" x 3 1/2" x 1/8" BASE
PLATE. WELD TUBE TO
BASE PLATE & ANCHOR
TO FLOOR. ANCHOR
VERT. STUD TO EA. SIDE
OF TUBE
3/4" WD-1 WOOD VENEER PANELS
MOUNTED TO PLYWOOD
3/4" WD-1 WOOD VENEER PANELS
OVER 2x4 FURRING
2 1/2" DIA. S.S. GROMMET
W/ COVER (SEE PLAN FOR
LOCATIONS)
3 1/2"
1/2"
SCHEDULED BASE
2x4 WOOD STUD
FRAMING @ 16" O.C.
FIRST LEVEL
100'-0"4"1'-6"4"4"2'-6"4"
2'-10 3/4"2 1/4"(REMOVABLE PANEL)1'-9"4"BLACK MELAMINE OVER
1/2" PLYWOOD
WOOD LEDGER @ WALL
AS REQ'D. PAINT W/ WALL
3/4" QUARTZ COUNTER
MATERIAL (QTZ-1) OVER
3/4" PLYWOOD
REFER TO DETAIL A1, THIS SHEET, FOR ADDITIONAL NOTES
3 1/2"
1'-3"4"1.5" x 2.5" NOTCHED
WOOD GLAZING RECEPTOR
W/ BEVELED EDGES
ATTACHED TO WALL.
PAINT W/ WALL1'-2"5/16" LAMINATED GLASS
W/ CLEAR INTERLAYER.
GLASS EDGES: POLISHED
DOUBLE ARRIS
2x4 WOOD STUDS @
16" O.C.
POLISHED
DOUBLE
ARRIS
FIRST LEVEL
100'-0"
10"1'-6"P. LAM. COUNTERTOP
(PL-3)
3/4" QTZ-1 QUARTZ
COUNTER MATERIAL
OVER (2) LAYERS 3/4"
PLYWOOD6"3"BLACK MELAMINE
OVER 1/2" PLYWOOD
2x4 FURRING OVER 1/2"
PLYWOOD
2x6 WOOD STUD FRAMING
2x TOP PLATE, GLUED
& SCREWED TO 2x6
FRAMING
3/4" PLYWOOD
3/4" QUARTZ COUNTER
MAT'L (QTZ-1)
LINE OF QUARTZ CAP
@ END OF WALL
LAM. GLASS
FIRST LEVEL
100'-0"
C5
A-521
C4
A-521
2'-6"2 1/4"10 1/4"1'-6"4"1'-2"4"1'-6"4"4"4"
3/4"
SCHEDULED BASE
5/8" GYP. BD.,
PAINTED
J-MOLD W/ BACKER ROD
& SEALANT. PROVIDE
J-MOLD & SEALANT @
VERT. JOINT BETWEEN
GYP. BD. & QUARTZ WALL
ALSO
QTZ-1 QUARTZ END,
FULL HEIGHT
3/4" QUARTZ COUNTER
MAT'L (QTZ-1) OVER BLOCKING
AS REQ'D
3/4" WD-1 WOOD VENEER
PANELS OVER 1x FURRING.
PROVIDE FURRING @ HORIZ.
& VERT. REVEALS, PAINTED
BLACK8 3/4"1/2"8 3/4"1/2"W REVEAL (TYP.)
REFER TO DETAIL A1, THIS SHEET, FOR ADDITIONAL NOTES
3 1/2"
4'-10 3/4"
7"
5/16" LAMINATED GLASS
W/ CLEAR INTERLAYER
& POLISHED DOUBLE ARRIS
EDGE TREATMENT. NOTCH
QUARTZ END WALL TO RECEIVE GLASS.
PROVIDE WOOD RECEPTOR
@ OPP. END, FULL HT., PAINTED
W/ WALL
QUARTZ COUNTERTOP
MATERIAL (QTZ-1)
MITER CORNERS
OF PANELS
SCHEDULED
BASE
2x4 WOOD STUDS
FIRST LEVEL
100'-0"3"3"3'-6"1'-6"0"4"1'-6"4"4"4'-0"4"
REFER TO DETAIL A1, THIS SHEET, FOR ADDITIONAL NOTES
P. LAM. COUNTERTOP (PL-3)
BLACK MELAMINE OVER
1/2" PLYWOOD
2x6 STUD FRAMING
2x4 FURRING OVER
1/2" PLYWOOD
10"
3 1/2"
1 3/4"
FIRST LEVEL
100'-0"
COUNTERTOP
BEYOND
J-MOLD W/
BACKER ROD
& SEALANT
LINE OF QUARTZ
END CAP
SCHEDULED
BASE
5/8" GYP. BD.,
PAINTED. INSTALL
J-MOLD ON VERTICAL
END WHERE GYP. BD.
ABUTS MELAMINE
(EDGE OF COUNTER)
2x6 STUD FRAMING
2x4 FURRING OVER
1/2" PLYWOOD
10"
REFER TO DETAIL A1, THIS SHEET, FOR ADDITIONAL NOTES4'-0"3"3"4"1'-6"4"1'-6"4"4"5"
3/4"
1/2"1 1/2"
1/2"
5 1/2"
1 3/4"
3/4" WOOD VENEER
PANELS (WD-1) OVER
WD. FURRING.
PROVIDE FURRING
@ HORIZ. & VERT.
REVEALS, PAINTED
BLACK
3/4" QUARTZ
COUNTERTOP
MAT'L (QTZ-1)
FIRST LEVEL
100'-0"2 1/2"1 1/2"1'-10"4"4"2'-10"9"
1 3/4"1'-4 1/2"1 3/4"
1/4" TEMPERED GLASS
@ PAPER SLOTS
3/4" QTZ-1 QUARTZ
MATERIAL @
BOTTOM OF SLOTS
3/4" QTZ-1 QUARTZ COUNTERTOP
MAT'L (TYP.) OVER 3/4"
PLYWOOD / BLOCKING
AS REQ'D
3/4" PLYWOOD
3/4" WD-1 WOOD VENEER
PANELS EA. SIDE OVER
1/2" PLYWOOD. PAINT
PLYWOOD BLACK @
HORIZ. & VERT. REVEALS
1/2" REVEAL (TYP.)
3/4" QTZ-1 QUARTZ OVER
1/2" PLYWOOD
SCHEDULED BASE
1/2"1/4"
3/4" QTZ-1 QUARTZ DIVIDERS
(TOP OF DIVIDER @
BOTTOM OF GLASS)
FRAMING AS REQ'D
1'-8"4"FIRST LEVEL
100'-0"
10 1/2"2 1/2"7"
1 3/4"1'-4 1/2"1 3/4"
LOCKING WOOD
VENEER DOOR (WD-1)
W/ EDGE
PULL THIS SIDE
FIXED 3/4" WOOD
VENEER PANEL
(WD-1) THIS SIDE &
EXPOSED END
2 1/2" x 9" TRASH
SLOT. FINISH
EXPOSED EDGES
W/ QUARTZ
COUNTER MAT'L
(QTZ-1)
TRASH CAN BY
OWNER
NOTCH BOTTOM
BLOCKING AS REQ'D
FOR TRASH CAN4"1'-10"4"4"2'-10"1'-8"
SCHEDULED BASE
3/4" QUARTZ
COUNTERTOP MAT'L
(QTZ-1) OVER 3/4"
PLYWOOD & BLOCKING
AS REQ'D
2 3/4"2 3/4"1'-2 1/2"
FIRST LEVEL
100'-0"
SCHEDULED BASE
3/4" QTZ-1 QUARTZ
COUNTERTOP MAT'L
OVER 3/4" PLYWOOD
& BLOCKING AS REQ'D
4"1'-10"4"4"2'-10"1 3/4"1'-4 1/2"1 3/4"
1'-8"
1/2"W REVEAL
(TYP.)
3/4" QTZ-1 QUARTZ
COUNTERTOP MAT'L
OVER 1/2" PLYWOOD
& BLOCKING AS REQ'D
MITERED CORNER
(TYP.)
2 3/4"1'-2 1/2"2 3/4"
E5
A-521
1/4" TEMPERED
GLASS COVER
4"3/4"4"3/4"4"3/4"4"1/4"1/4"1/4"8 1/2"1/2"
ROUT 1/4"x1/4"
@ EDGE OF
QUARTZ MAT'L
LINE OF DIVIDERS
BELOW. HOLD
BACK 1/2" FROM
EDGE OF COUNTER
LINE OF COUNTER
@ BOTTOM OF
SLOTS 1'-6 1/4"9"DO NOT ROUT
OUT TO EDGE OF
COUNTER @ ENDS
EDGE OF COUNTER
BELOW
3/4"W QTZ-1 QUARTZ
DIVIDERS (TOP OF
DIVIDERS TO BE
1/4" BELOW COUNTER
FOR GLASS SUPPORT)
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:29 PMA-521
MILLWORK DETAILS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1 1/2" = 1'-0"A-521
A1 SECTION @ TELLER COUNTER
1 1/2" = 1'-0"A-521
A3 SECTION @ ACCESSIBLE TELLER COUNTER
1 1/2" = 1'-0"A-521
C7 DETAIL OF WALL @ ACCESSIBLE COUNTER
1 1/2" = 1'-0"A-521
C1 SECTION @ LOW WALL
1 1/2" = 1'-0"A-521
C5 DETAIL @ WEST END OF TELLER COUNTER
1 1/2" = 1'-0"A-521
C4 DETAIL @ WEST END OF TELLER COUNTER (@ WALL)
1 1/2" = 1'-0"A-521
E5 CHECK DESK SECTION 3
1 1/2" = 1'-0"A-521
E1 CHECK DESK SECTION 1
1 1/2" = 1'-0"A-521
E3 CHECK DESK SECTION 2
1 1/2" = 1'-0"A-521
E7 CHECK DESK PLAN DETAIL @ SLOTS
03.13.2017
F FG N1
6"6"3"6"6"15"32"12"F1 7'-0"3'-0"SCHEDULED
WIDTH
SCHEDULED HEIGHT1 1/2"SCHEDULED DOOR
ALUM. JAMB
SCHEDULED GLAZING
4 7/8"1 1/2"SCHEDULED GLAZING
ALUM. FRAME
SCHEDULED PARTITION
(REF. PLAN & PARTITION
TYPES)
4 7/8"
SCHEDULED
GLAZING
SILL STARTER
(MATCH FRAME
FINISH)
ALUM. SILL
1 1/2"(V.I.F.)1" +/-OFFICE SIDEHALL SIDE
SLOPING FLOOR
TRANSITION
4 7/8"4 7/8"1 1/2"
SCHEDULED PARTITION
(REF. PLAN & WALL
TYPES)ALUM. FRAME
SCHEDULED GLAZING
1/2"4 7/8"4 7/8"1 1/2"
SCHEDULED PARTITION
(REF. PLAN & WALL
TYPES)ALUM. FRAME
SCHEDULED GLAZING
1/2"
SHIM AS REQ'D
SCHEDULED
GLAZING
SILL STARTER
(MATCH FRAME
FINISH)
ALUM. SILL
1 1/2"4 7/8"7 5/16"1 1/2"STUD CORNER FRAMING
UP TO WALL ABOVE
LINE OF STUD FRAMING
ABOVE (TYP.)
LINE OF GYP. BD.
WALL ABOVE (TYP.)
HORIZ. APPLIED TRIM
(SEE ELEV.).
MITER @ CORNER
1 1/2" ALUM. TRIM (TYP.)
ALUM. BRAKE METAL
CLOSURE. COLOR
BY ARCH.
ALUM. BRAKE METAL
CLOSURE. COLOR
BY ARCH.
SCHEDULED GLAZING
(TYP.)
4 7/8"
ALUM. BRAKE METAL CLOSURE.
COLOR BY ARCH.
LINE OF GYP. BD. ABOVE
LINE OF STUD FRAMING ABOVE
SCHEDULED DOOR
(TYP.)
PARTITION - REF.
PLAN & PARTITION TYPES
HORIZ. APPLIED TRIM (SEE ELEV.)
1 1/2" ALUM. TRIM (TYP.)
ALUM. HINGE JAMB (TYP.)
SHIM AS REQ'D (TYP.)9"EQEQ1 1/2"4 7/8"
SCHEDULED DOORALUM. FRAME
SCHEDULED PARTITION
(REF. PLAN & PARTITION
TYPES)1 1/2"SCHEDULED GLAZING
ALUM. FRAME
SEALANT EACH SIDE
DOOR FRAME
SCHEDULED DOOR
JAMB STUDS AS
REQUIRED BY
OPENING WIDTH
PER FRAME ELEVATIONPER PARTITION TYPE1/2"1/2"SEALANT EACH SIDE
DOOR FRAME
SCHEDULED DOORPER FRAME ELEVATIONPER PARTITION TYPE
1/2"1/2"
EXIST. STOREFRONT
2"BRAKE METAL
FILLER TO MATCH
MULLIONS. CLIP
TO BACK OF
MULLION & ATTACH
TO STUD
SCHEDULED
PARTITION
SEALANT & BACKER
ROD EA. SIDE
FILL VOID W/ INSUL.
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:28:31 PMA-601
DOOR SCHEDULE
AND DETAILS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
DOOR
NUMBER PAIR
DOOR FRAME
FIRE
RATING REMARKS
SIZE
MTRL. ELEV. GLASS
HDWR.
SET MTRL. ELEV.
DETAILS
W H T HEAD JAMB THRESHOLD
FIRST LEVEL
101A 3'-0" 7'-0" 1 3/4" W.D. F - 07 ALUM. F1 B1/A-601 SIM. B1/A-601 -
101B 3'-0" 7'-0" 1 3/4" W.D. F - 06 ALUM. F1 B1/A-601 SIM. B1/A-601 -
101C Yes 3'-0" 7'-0" 1 3/4" W.D. N1 GL-2 02 H.M. F1 D6/A-601 B6/A-601 45 MIN.
101E 3'-0" 6'-10 3/4" 1 3/4" ALUM. FG GL-2 01 ALUM. ALUM. D1/A-601 SIM. D1/A-601
103 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & B4/A-601 SIM.
103-1 3'-0" 7'-0" 1 3/4" W.D. F - 10 ALUM. F1 -
104 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601
106-1 3'-0" 7'-0" 1 3/4" W.D. F - 12 ALUM. F1 B1/A-601 SIM. B1/A-601 -
106-2 3'-0" 7'-0" 1 3/4" W.D. F - 06 ALUM. F1 B1/A-601 SIM. B1/A-601 -
107 3'-0" 7'-0" 1 3/4" W.D. F - 06 ALUM. F1 B1/A-601 SIM. B1/A-601 -
108 3'-0" 7'-0" 1 3/4" W.D. F - 06 ALUM. F1 B1/A-601 SIM. B1/A-601 -
109 3'-0" 7'-0" 1 3/4" W.D. F - 03 ALUM. F1 B1/A-601 SIM. B1/A-601 -
110 3'-0" 7'-0" 1 3/4" W.D. F - 03 ALUM. F1 B1/A-601 SIM. B1/A-601 -
113 3'-0" 7'-0" 1 3/4" W.D. F - 07 ALUM. F1 B1/A-601 SIM. B1/A-601 -
114 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1/A-601
115 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601
116 3'-0" 7'-0" 1 3/4" W.D. F - 09 ALUM. ALUM. D1/A-601 SIM. D1/A-601
117 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601
118 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601
119 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601
120 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601
121 3'-0" 7'-0" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1/A-601
122 3'-0" 6'-10 3/4" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1/A-601 FIELD VERIFY DOOR HEIGHT BASED ON BRICK PAVER THICKNESS
123 3'-0" 6'-10 3/4" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601 FIELD VERIFY DOOR HEIGHT BASED ON BRICK PAVER THICKNESS
124 3'-0" 6'-10 3/4" 1 3/4" W.D. F - 08 ALUM. ALUM. D1/A-601 SIM. D1 & D4/A-601 FIELD VERIFY DOOR HEIGHT BASED ON BRICK PAVER THICKNESS
X-1 2'-6" 7'-0" 1 3/4" W.D. F - 04 H.M. F1 - NEW DOOR IN EXISTING FRAME. FIELD VERIFY SIZE. MATCH EXIST. HARDWARE FUNCTIONS. HARDWARE TO MATCH NEW DOORS
X-2 2'-6" 7'-0" 1 3/4" W.D. F - 04 H.M. F1 - NEW DOOR IN EXISTING FRAME. FIELD VERIFY SIZE. MATCH EXIST. HARDWARE FUNCTIONS. HARDWARE TO MATCH NEW DOORS
X-3 2'-6" 7'-0" 1 3/4" W.D. F - 05 H.M. F1 - NEW DOOR IN EXISTING FRAME. FIELD VERIFY SIZE. MATCH EXIST. HARDWARE FUNCTIONS. HARDWARE TO MATCH NEW DOORS
X-4 3'-0" 7'-0" 1 3/4" W.D. F - 05 H.M. F1 - NEW DOOR IN EXISTING FRAME. FIELD VERIFY SIZE. MATCH EXIST. HARDWARE FUNCTIONS. HARDWARE TO MATCH NEW DOORS. ADD
STC-RATED SOUND KIT.
1/4" = 1'-0"
DOOR PANEL LEGEND
DOOR SCHEDULE
GENERAL DOOR SCHEDULE
NOTES
A THESE GENERAL NOTES APPLY TO SERIES 600 DOOR
SCHEDULE DRAWINGS.
B UNDERCUT DOORS AS REQUIRED BY FINAL FLOOR FINISH.
C PROVIDE SEALANT BETWEEN HOLLOW METAL FRAME
PERIMETERS AND SURROUNDING WALL CONSTRUCTION
UNLESS OTHERWISE INDICATED.
D PROVIDE SEALANT BETWEEN INTERIOR STOREFRONT FRAME
PERIMETERS AND SURROUNDING WALL CONSTRUCTION
UNLESS OTHERWISE INDICATED.
E SPOT GROUT NEW HOLLOW METAL DOORFRAMES IN GYPSUM
BOARD WALL CONSTRUCTION.
F WHERE A FIRE RATING IS INDICATED ON THE DOOR
SCHEDULE, HARDWARE AND DOOR ASSEMBLY COMPONENTS
SHALL MEET THE REQUIREMENTS OF THAT LABEL.
G INSTALL DOOR GLASS USING WET-GLAZING METHOD. REFER
TO PROJECT MANUAL DIVISION 8 FOR GLAZING.
H REFER TO PROJECT MANUAL DIVISION 8 FOR HARDWARE
SCHEDULE.
1/4" = 1'-0"
DOOR FRAME LEGEND
3" = 1'-0"A-601
D1 DOOR JAMB AT SIDELITE DETAIL (HEAD SIM.)
3" = 1'-0"A-601
B3 ALUM. JAMB DETAIL (HEAD SIM.)
3" = 1'-0"A-601
A3 ALUM. SILL DETAIL @ SLOPING FLOOR
3" = 1'-0"A-601
A4 JAMB DETAIL @ CORNER WALL
3" = 1'-0"A-601
A6 JAMB DETAIL @ PERPENDICULAR WALL
3" = 1'-0"A-601
A1 TYP. ALUM. SILL DETAIL
3" = 1'-0"A-601
B4 ALUM. CORNER PLAN DETAIL
3" = 1'-0"A-601
D4 ALUM. PLAN DETAIL @ INTERSECTING WALL
3" = 1'-0"A-601
B1 DOOR JAMB DETAIL @ GWB (HEAD SIM.)
3" = 1'-0"A-601
D3 TYP. INTERMEDIATE MULLION DETAIL
3" = 1'-0"A-601
B6 JAMB DETAIL - H.M. FRAME
3" = 1'-0"A-601
D6 HEAD DETAIL - H.M. FRAME
3" = 1'-0"A-601
E1 END OF WALL @ EXIST. STOREFRONT
03.13.2017
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting
1344 South Rangeline Road, Suite 202
Carmel, Indiana 46031
(317) 344-8046
PROJECT NO.
REISSUE
3/16/2017 9:33:54 PMA-901
3D
REPRESENTATIONS
ISSUED FOR REVIEW / BID
03.13.2017
16071.001
EJS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
A-901
A4 VIEW FROM MAIN ENTRY
A-901
A7 VIEW OF CHECK COUNTER
A-901
C7 VIEW OF TELLER STATIONS
A-901
C4 VIEW OF LOBBY SEATING
03.13.2017
TTTTTT12/6
14/8
18/8
24/14
12/8
12/6
22/14
22/1422/1016/1014/8
14/6
EX. RP
EX. RP
EX. VAV-1
EX. VAV-2
EX. VAV-1
EX. RP
RP-1
EX. RTU-5
UP TO EX. RTU-5
UP TO EX. RTU-2
26/16
26/12
20/12
20/12
12/8
30/20
30/14
24/12
24/10
30/14
12/8
?
?
UP TO EX. RTU-1
EX. VAV-2
EX. RTU-1
EX. RTU-2
EX. UH
EX. UHEX. UH
EX. UH
EX. UH
1
1
1
3
4
2
1
1
1
1
6
7
7
7
7
7
2
M-101
30/18
5
5
5
3
M-101
A.REFER TO DRAWING M-000 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS.
B.REFER TO DRAWING M-600 FOR MECHANICAL SCHEDULES AND DETAILS.
C.ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL, STATE AND LOCAL
CODES AND STANDARDS.
D.CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BIDDING
OR BEGINNING WORK ON THIS PROJECT.
E.PROTECT ALL SURFACES, FINISHES, AND EQUIPMENT TO REMAIN AS REQUIRED,
PATCH, REPAR, OR REPLACE AS REQUIRED.
F.REMOVE COMPLETE ALL ITEMS AS REQUIRED TO CONFORM TO FINAL DESIGN
INTENT, INCLUDING BUT NOT LIMITED TO PIPING, ASSOCIATED HANGERS,
CONTROLS, AND SUBASSEMBLIES.
G.THE CONTRACTOR SHALL CUT, PATCH, REPAIR OR REPLACE EXISTING WALLS AND
FLOORS WITH NEW AS REQUIRED TO ACHIEVE LIKE NEW CONDITION IN ALL
LOCATIONS, WHERE REQUIRED FOR THE DEMOLITION OR REMOVAL OF EXISTING
ITEMS, TO COMPLETE THE SCOPE OF WORK.
H.THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COST REQUIRED TO
COMPLELETLY AND PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT
AND SHALL EXAMINE THE SCOPE OF WORK OF OTHER TRADES PRIOR TO
SUBMITTING A BID PROPOSAL.
I.CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND DRAWINGS
AND BOTH ARE INTENDED TO BE COMPLIMENTARY - ANYTHING APPEARING ON
EITHER MUST BE EXECTUED THE SAME AS IF SHOWN ON BOTH.
J.COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTION IN ORDER TO
DETERMINE THE EXACT LIMITS OF REMOVAL.
K.UNLESS OTHERWISE NOTED, NO EQUIPMENT, DUCTWORK, PIPING, MATERIALS
AND/OR CONTROLS SHALL BE ABANDONED IN PLACE.
L.CONTRACTOR IS RESPONSIBLE FOR DEMOLITION OF ALL DUCTWORK, PIPE,
MATERIALS AND EQUIPMENT BACK TO THE POINT OF ORIGIN OR POINT OF COMMON
USE.
M.THE PREMISES SHALL BE KEPT IN A CLEAN AND ORDERLY CONDITION DURING
CONSTRUCTION. ALL WASTE AND UNUSABLE MATERIALS SHALL BE PROMPTLY
REMOVED FROM THE SITE.
N.ALL SALVAGE SHALL REMAIN PROPERTY OF THE OWNER, HOWEVER, THE
CONTRACTOR SHALL DISPOSE OF ANY OR ALL SALVAGE THE OWNER ELECTS NOT
TO KEEP.
O.REFER TO ARCHITECTURAL DRAWINGS FOR WALLS, CEILINGS, ETC. THAT ARE TO
BE REMOVED. ALL EXISTING PIPING THAT IS EXPOSED SHALL BE REMOVED OR
RELOCATED.
P.ENGINEER WILL ISSUE CFM CLARIFICATION UPON RECEIPT OF BALANCE REPORT
PRIOR TO DEMOLITION
GENERAL SHEET DEMO NOTES
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:26 PMMD101
MECHANICAL FLOOR
DEMOLITION PLAN
16071.001
TCR
KSB
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
MECHANICAL FLOOR DEMOLITION PLAN1
SHEET KEYNOTES
1 DEMO ALL DUCTWORK, DUCT ACCESSORIES, AND AIR TERMINALS BACK TO
THIS POINT.
2 EXISTING THERMOSTAT TO BE RELOCATED.
3 EXISTING THERMOSTAT TO REMAIN.
4 DEMO EXISTING THERMOSTAT SERVING REHEAT PANNELS.
5 DEMO EXISTING THERMOSTAT SERVING ROOFTOP UNIT.
6 EXISTING DUCTWORK, GRILLES, AND EXHAUST FAN TO REMAIN.
7 EXISTING UNIT HEATER TO REMAIN.
RECTANGULAR DUCTWORK
DESIGNATION IN INCHES, FIRST
DIMENSION IS SIDE SHOWN
ROUND SPIRAL DUCTWORK
DESIGNATION IN INCHES
FLAT OVAL DUCTWORK
DESIGNATION IN INCHES, FIRST
DIMENSION IS SIDE SHOWN
RECTANGULAR SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE
ROUND SPIRAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE
FLAT OVAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE
RECTANGULAR SUPPLY AIR,
OUTSIDE AIR DUCTWORK
DROP
ROUND SPIRAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK
DROP
FLAT OVAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK
DROP
RECTANGULAR RETURN AIR,
TRANSFER AIR DUCTWORK
RISE
ROUND SPIRAL RETURN AIR,
TRANSFER AIR DUCTWORK
RISE
FLAT OVAL RETURN AIR,
TRANSFER AIR DUCTWORK
RISE
RECTANGULAR RETURN AIR,
TRANSFER AIR DUCTWORK
DROP
ROUND SPIRAL RETURN AIR,
TRANSFER AIR DUCTWORK
DROP
FLAT OVAL RETURN AIR,
TRANSFER AIR DUCTWORK
DROP
RECTANGULAR EXHAUST AIR,
RELIEF AIR DUCTWORK RISE
ROUND SPIRAL EXHAUST
AIR, RELIEF AIR DUCTWORK
RISE
FLAT OVAL EXHAUST AIR,
RELIEF AIR DUCTWORK RISE
RECTANGULAR EXHAUST AIR,
RELIEF AIR DUCTWORK DROP
ROUND SPIRAL EXHAUST
AIR, RELIEF AIR DUCTWORK
DROP
FLAT OVAL EXHAUST AIR,
RELIEF AIR DUCTWORK DROP
DUCTWORK CONSTRUCTED
OF ALUMINUM, STAINLESS
STEEL
DUCTWORK RISE IN
DIRECTION OF FLOW
DUCTWORK DROP IN
DIRECTION OF FLOW
STANDARD DEGREE ANGLE
TRANSITION IN DIRECTION
OF FLOW
SUPPLY AIR, OUTSIDE AIR IN
DIRECTION OF FLOW
RETURN AIR, EXHAUST AIR,
TRANSFER AIR, RELIEF AIR
IN DIRECTION OF FLOW
ECCENTRIC DUCT
TRANSITION
CONCENTRIC DUCT
TRANSITION
RECTANGULAR TO ROUND,
FLAT OVAL DUCT TRANSITION
VOLUME DAMPER ACCESS DOOR DUCTWORK CAP
MOTORIZED DAMPER WITH
ACCESS DOOR
FIRE DAMPER WITH ACCESS
DOOR
SMOKE DAMPER WITH
ACCESS DOOR
BACK DRAFT DAMPER WITH
ACCESS DOOR
AIRFLOW MEASURING STATION
WITH ACCESS DOOR
FIRE AND SMOKE DAMPER
WITH ACCESS DOOR
PRESSURE SENSOR WITH
ACCESS DOOR
TEMPERATURE SENSOR WITH
ACCESS DOOR
SMOKE DETECTOR WITH
ACCESS DOOR
STATIC PRESSURE CHANGE
IN INCHES
FLEXIBLE DUCTWORK
CONNECTION
DUCTWORK LINING OR
DOUBLE WALL DUCTWORK,
DESIGNATION SHOWN IS
FREE AREA
45° BEVELED FITTING FOR
RECTANGULAR TO
RECTANGULAR DUCTWORK
RADIUS DUCTWORK ELBOW
(CENTERLINE RADIUS 1.5xW)SOUND ATTENUATOR
CONICAL FITTING FOR
ROUND OR FLAT OVAL TO
RECTANGULAR DUCTWORK
RADIUS DUCTWORK ELBOW
WITH TURNING VANES
MITERED DUCTWORK
ELBOW
CONICAL FITTING FOR
ROUND OR FLAT OVAL TO
ROUND OR FLAT OVAL
DUCTWORK
WYE RADIUS DUCTWORK
ELBOW
MITERED DUCTWORK ELBOW
WITH TURNING VANES
45° RADIUS DUCTWORK
ELBOW (CENTERLINE RADIUS
1.5xW)
TRANSFER AIR ELBOW WITH
DUCTWORK STUBS FOR
SOUND ATTENUATION
SPIN-IN FITTING FOR
ROUND TO RECTANGULAR
DUCTWORK, LOW PRESSURE
DUCTWORK
CEILING PANEL SUPPLY AIR
DIFFUSER
ROUND SUPPLY AIR
DIFFUSER
FLEXIBLE DUCTWORK
CONNECTION TO DIFFUSER,
MAXIMUM SIX FEET
RECTANGULAR SUPPLY AIR
REGISTER
RETURN AIR, EXHAUST AIR,
TRANSFER AIR REGISTER OR
GRILLE
SIDEWALL SUPPLY AIR
REGISTER OR GRILLE
SIDEWALL RETURN AIR,
EXHAUST AIR, TRANSFER AIR
REGISTER OR GRILLE
LINEAR SLOT SUPPLY AIR
DIFFUSER
THERMOSTAT WITH
ASSOCIATED EQUIPMENT
DESIGNATION (OPTIONAL)
TEMPERATURE SENSOR DOOR GRILLE OR UNDERCUT
DOOR
HUMIDISTAT WITH
ASSOCIATED EQUIPMENT
DESIGNATION (OPTIONAL)
CARBON DIOXIDE SENSOR CEILING DESTRATIFICATION
FAN
TEMPERATURE CONTROL
PANEL
VARIABLE FREQUENCY
DRIVE
CENTRIFUGAL ROOF
EXHAUST FAN
HYDRONIC REHEAT COIL
WITH ACCESS DOOR
TERMINAL UNIT WITH
HYDRONIC REHEAT COIL INLINE FAN
ELECTRIC REHEAT COIL
WITH ACCESS DOOR
TERMINAL UNIT WITH
ELECTRIC REHEAT COIL
SERIES/PARALLEL FAN
POWERED TERMINAL UNIT
BASE MOUNTED PUMP UNIT VENTILATOR UNIT HEATER
HEAT EXCHANGER AIR SEPARATOR FINNED TUBE RADIATION
HVAC IDENTITY SYMBOLS GENERAL HVAC NOTES
HIGH PRESSURE STEAM (>61 PSIG)STORM DRAIN
MEDIUM PRESSURE STEAM (16-60 PSIG)FOOTING/FOUNDATION DRAIN
LOW PRESSURE STEAM (<15 PSIG)SANITARY WASTE (W)
HIGH PRESSURE CONDENSATE SANITARY GREASE
MEDIUM PRESSURE CONDENSATE SANITARY FORCED MAIN
LOW PRESSURE CONDENSATE SANITARY VENT (V)
BOILER BLOW DOWN ACID WASTE
BOILER FEED ACID VENT
PUMPED CONDENSATE DRAIN
VACUUM PUMP DISCHARGE INDIRECT WASTE
HUMIDIFICATION PUMP DISCHARGE
MAKE UP WATER DOMESTIC COLD WATER (CW)
AIR RELIEF VENT DOMESTIC HOT WATER SUPPLY (HW)
HEAT RECLAIM PIPING DOMESTIC HOT WATER RETURN (HWR)
HEATING WATER SUPPLY 140°F HOT WATER
HEATING WATER RETURN 140°F HOT WATER RETURN
REFRIGERANT DISCHARGE NON-POTABLE WATER
REFRIGERANT SUCTION DRINKING WATER SUPPLY
REFRIGERANT LIQUID DRINKING WATER RETURN
REFRIGERANT HOT GAS SOFT WATER
BRINE SUPPLY CHLORINATED WATER
BRINE RETURN DISTILLED WATER
CONDENSER WATER SUPPLY DEIONIZED WATER
CONDENSER WATER RETURN FIRE SUPPRESSION
CHILLED WATER SUPPLY NATURAL GAS (WC OR PSIG)
CHILLED WATER RETURN GAS VENT
DUAL TEMPERATURE SUPPLY LIQUID PETROLEUM
DUAL TEMPERATURE RETURN MEDICAL COMPRESSED AIR (WC OR PSIG)
HEAT PUMP WATER SUPPLY MEDICAL VACUUM
HEAT PUMP WATER RETURN OXYGEN
GLYCOL HEATING SUPPLY NITROGEN
GLYCOL HEATING RETURN NITROUS OXIDE
FUEL OIL SUPPLY CARBON DIOXIDE
FUEL OIL RETURN WET VACUUM CLEANING
FUEL OIL VENT DRY VACUUM CLEANING
CONDENSATE DRAIN COMPRESSED AIR (WC OR PSIG)
CONTROL WIRING TEMPERED WATER SUPPLY
TEMPERED WATER RETURN
SECTION INDICATOR:REFERENCE SECTION LOCATION THROUGH AN AREA
FOR ADDITIONAL INFORMATION.
KEYNOTE INDICATOR:REFERENCE SHEET KEYNOTE LOCATION FOR
ADDITIONAL INFORMATION.
DETAIL INDICATOR:REFERENCE DETAIL LOCATION FOR ADDITIONAL
INFORMATION.
DRAWING BLOCK TITLE
INDICATOR:
REFERENCE DRAWING MODULE LOCATION FOR
ADDITIONAL INFORMATION.
MATCH LINE INDICATOR:REFERENCE SHEET LOCATION FOR ADDITIONAL
INFORMATION.
REVISION INDICATOR:REFERENCE TITLE BLOCK LOCATION FOR ADDITIONAL
INFORMATION.
EQUIPMENT INDICATOR:REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
DIFFUSER, GRILLE,
REGISTER INDICATOR:
REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
TU-XL.##
ø DIAMETER, PHASE ET EXPANSION TANK OAT OUTSIDE AIR TEMPERATURE (°F)
°F DEGREES FAHRENHEIT EW EMERGENCY EYEWASH OBD OPPOSED BLADE DAMPER
A/C AIR CONDITIONING EWC ELECTRIC WATER COOLER OD OUTSIDE DIAMETER, OVERFLOW DRAIN
ACC AIR COOLED CONDENSER EWT ENTERING WATER TEMPERATURE (°F)OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
ACCU AIR COOLED CONDENSING UNIT EXH EXHAUST OSD OPEN SITE DRAIN
AD AREA DRAIN, ACCESS DOOR EXIST EXISTING OZ OUNCE
AFF ABOVE FINISHED FLOOR F FURNACE P PUMP
AFMS AIR FLOW MEASURING STATION F&T FLOAT AND THERMOSTATIC STEAM TRAP PBD PARALLEL BLADE DAMPER
AGA AMERICAN GAS ASSOCIATION FCO FLOOR CLEANOUT PC PLUMBING CONTRACTOR
AHU AIR HANDLING UNIT FCU FAN COIL UNIT PD PRESSURE DROP
AL ACOUSTICALLY LINED, ALUMINUM FD FLOOR DRAIN, FIRE DAMPER PE PNEUMATIC ELECTRIC
AMB AMBIENT FDC FIRE DEPARTMENT CONNECTION PH PHASE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE FDTN FOUNDATION PIV POST INDICATOR VALVE
AO ANALOG OUTPUT FE FIRE EXTINGUISHER PPM PARTS PER MILLION
AP ACID PROOF, ACCESS PANEL FHC FIRE HOSE CABINET PRV PRESSURE REDUCING VALVE
APD AIR PRESSURE DROP (IN. WC.)FLR FLOOR PSI POUNDS PER SQUARE INCH
ARCH ARCHITECT FM FACTORY MUTUAL PSIA POUNDS PER SQUARE INCH ABSOLUTE
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE FOV FUEL OIL VENT PSIG POUNDS PER SQUARE INCH GAUGE
ARV AIR RELIEF VALVE FPM FEET PER MINUTE PTAC PACKAGED TERMINAL AIR CONDITIONER
AS AIR SEPARATOR FPVAV FAN POWERED VAV UNIT PVC POLYVINYL CHLORIDE
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING FS FLOOR SINK R REGISTER
AND AIR CONDITIONING ENGINEERS FSC FIRE SUPPRESSION CONTRACTOR R12 REFRIGERANT (12, 22, ETC.)
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS FSD COMBINATION FIRE/SMOKE DAMPER RA RETURN AIR
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS FT FOOT, FEET RADN RADIATION
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS FTG FOOTING RAT RETURN AIR TEMPERATURE (°F)
ATM ATMOSPHERE FTR FINNED TUBE RADIATION RCP REINFORCED CONCRETE PIPE
AUTO AUTOMATIC G NATURAL GAS RD ROOF DRAIN
AVG AVERAGE GA GAGE OR GAUGE REV REVOLUTIONS
AVS ACID VENT STACK GAL GALLON RF RETURN FAN
AW ACID WASTE GC GENERAL CONTRACTOR RG RETURN GRILLE
AWWA AMERICAN WATER WORKS ASSOCIATION GIV GRAVITY INTAKE VENTILATOR RH RELATIVE HUMIDITY, RODDING HOLE
BD BUTTERFLY DAMPER GPD GALLONS PER DAY RM ROOM
BDD BACKDRAFT DAMPER GPH GALLONS PER HOUR RP RADIANT PANEL
BE BOTTOM ELEVATION GPM GALLONS PER MINUTE RPM REVOLUTIONS PER MINUTE
BF BARRIER FREE GR GRILLE, GRAINS RPS REVOLUTIONS PER SECOND
BFC BELOW FINISHED CEILING GRV GRAVITY RELIEF VENTILATOR RTU ROOF TOP UNIT
BHP BRAKE HORSEPOWER GT GREASE TRAP RV RELIEF VALVE, ROOF VENT
BLDG BUILDING HB HOSE BIBB SA SUPPLY AIR
BOD BOTTOM OF DUCT HD HEAD (FT.)SAN SANITARY
BOP BOTTOM OF PIPING Hg MERCURY SD SUPPLY DIFFUSER, SMOKE DAMPER
BSMT BASEMENT HHWP HEATING HOT WATER PUMP SEER SEASONAL ENERGY EFFICIENCY RATIO
BT BATHTUB HO HUB OUTLET SF SQUARE FOOT, SUPPLY FAN, SAFETY FACTOR
BTM BOTTOM HORIZ HORIZONTAL SG SUPPLY GRILLE
BtuH BRITISH THERMAL UNIT PER HOUR HP HORSEPOWER, HEAT PUMP SH SHOWER
CA COMPRESSED AIR HR HOUR(S)SK SINK
CAV CONSTANT AIR VOLUME HRTU HEATING ONLY ROOFTOP UNIT SMACNA SHEET METAL AND AIR CONDITIONING
CB CATCH BASIN HX HEAT EXCHANGER CONTRACTORS NATIONAL ASSOCIATION
CCW COUNTERCLOCKWISE Hz HERTZ SP STATIC PRESSURE
CD CONDENSATE DRAIN IB INVERTED BUCKET STEAM TRAP SPEC SPECIFICATION
CO₂CARBON DIOXIDE ID INSIDE DIAMETER SQ SQUARE
CF CEILING FAN IE INVERT ELEVATION SR SUPPLY REGISTER
CFM CUBIC FEET PER MINUTE IN INCH, INCHES SRV SAFETY RELIEF VALVE
CH CHILLER INT INTERIOR SS SERVICE SINK, STAINLESS STEEL
CHWP CHILLED WATER PUMP INV INVERT STD STANDARD
CI CAST IRON IPS INTERNATIONAL PIPE STANDARD SV STEAM VENT
CMP CORRUGATED METAL PIPE IW INDIRECT WASTE TCC TEMPERATURE CONTROL CONTRACTOR
CO CLEANOUT K KELVIN TCP TEMPERATURE CONTROL PANEL
COMPR COMPRESSOR KEC KITCHEN EQUIPMENT CONTRACTOR TD TEMPERATURE DIFFERENCE
COND CONDENSER kW KILOWATT TE TOP ELEVATION
CONV CONVECTOR LAB LABORATORY TEMP TEMPERATURE
CP CONDENSATE PUMP LAT LEAVING AIR TEMPERATURE (°F)TF TRANSFER FAN
CPVC CHLORINATED POLYVINYL CHLORIDE LAV LAVATORY TG TRANSFER GRILLE
CT COOLING TOWER LBS POUNDS TMV THERMOSTATIC MIXING VALVE
CU CONDENSING UNIT LD LINEAR DIFFUSER TONS TONS OF REFRIGERATION
CUH CABINET UNIT HEATER LP LIQUID PETROLEUM TP TRAP PRIMER
CUV CLASSROOM UNIT VENTILATOR LTG LIGHTING TRANS TRANSITION
CV CONTROL VALVE LWT LEAVING WATER TEMPERATURE (°F)TS TAMPER SWITCH
CW CLOCKWISE MA MIXED AIR TSP TOTAL STATIC PRESSURE (IN. WC.)
CWP CONDENSER WATER PUMP MAT MIXED AIR TEMPERATURE (°F)TXV THERMAL EXPANSION VALVE
dB DECIBEL MAX MAXIMUM TYP TYPICAL
DB DRY BULB MB MOP BASIN UCD UNDERCUT DOOR
DF DRINKING FOUNTAIN MBH THOUSAND Btu PER HOUR UH UNIT HEATER
DG DOOR GRILLE MC MECHANICAL CONTRACTOR UL UNDERWRITERS LABORATORIES
DH DUCT HEATER MCA MINIMUM CIRCUIT AMPS UON UNLESS OTHERWISE NOTED
DI DIGITAL INPUT MCC MOTOR CONTROL CENTER UR URINAL
DIA DIAMETER MD MOTORIZED DAMPER US UP STREAM
DIFF DIFFUSER MFR MANUFACTURER UV UNIT VENTILATOR
DN DOWN MH MANHOLE V VOLTS, VENT
DO DIGITAL OUTPUT MIN MINIMUM VAC VACUUM
DS DOWNSPOUT, DOWN STREAM MISC MISCELLANEOUS VAV VARIABLE AIR VOLUME
DW DISTILLED WATER MS MOP SINK VB VACUUM BREAKER
DWG DRAWING MTD MOUNTED VD VOLUME DAMPER
DWH DOMESTIC WATER HEATER MV MANUAL VENT VEL VELOCITY
DWV DRAIN, WASTE & VENT N NITROGEN VERT VERTICAL
DX DIRECT EXPANSION NA NOT APPLICABLE VF VENTILATION FAN
EA EXHAUST AIR NC NOISE CRITERIA, NORMALLY CLOSED VFD VARIABLE FREQUENCY DRIVE
EAT ENTERING AIR TEMPERATURE (°F)NEC NATIONAL ELECTRIC CODE VTR VENT THROUGH ROOF
EC ELECTRICAL CONTRACTOR NFC NATIONAL FIRE CODE VUV VERTICAL UNIT VENTILATOR
ECO EXTERIOR CLEANOUT NFPA NATIONAL FIRE PROTECTION ASSOCIATION W WASTE, WATT
EDR EQUIVALENT DIRECT RADIATION NFWH NON-FREEZE WALL HYDRANT WC WATER COLUMN
EER ENERGY EFFICIENCY RATIO NIC NOT IN CONTRACT WB WET BULB
EF EXHAUST FAN NO NORMALLY OPEN, NITROUS OXIDE WC WATER CLOSET
EFF EFFICIENCY NOM NOMINAL WCO WALL CLEANOUT
EG EXHAUST GRILLE NPW NON-POTABLE WATER WH WALL HYDRANT
EL ELEVATION NTS NOT TO SCALE WPD WATER PRESSURE DROP (FT. HD.)
EOM END OF MAIN DRIP O OXYGEN WSHP WATER SOURCE HEAT PUMP
ES EMERGENCY SHOWER OA OUTSIDE AIR YD YARD DRAIN
ESP EXTERNAL STATIC PRESSURE (IN. WG.)OAI OUTSIDE AIR INTAKE
FLOW DIRECTION ARROW, PITCH DIRECTION ARROW
PIPE RISE
PIPE DROP
PIPE CAP
PIPE CONTINUES (REFERENCE ELSEWHERE)
PIPE GUIDE
PIPE ANCHOR
FLEXIBLE CONNECTOR
EXPANSION COMPENSATOR
EXPANSION LOOP
CONCENTRIC, ECCENTRIC FITTINGS
UNION, FLANGED UNION
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
PLUG VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
DOUBLE CHECK BACKFLOW PREVENTER
DOUBLE DETECTOR CHECK VALVE ASSEMBLY
ANGLE VALVE
RELIEF VALVE
VALVE WITH OUTSIDE STEM & YOKE
PNEUMATIC TWO-WAY CONTROL VALVE
PNEUMATIC THREE-WAY CONTROL VALVE
ELECTRIC TWO-WAY CONTROL VALVE
ELECTRIC THREE-WAY CONTROL VALVE
SOLENOID VALVE
FLOW SWITCH
PRESSURE SWITCH
AQUASTAT
ORIFICE FLOW METER
VENTURI FLOW METER
TURBINE FLOW METER
CALIBRATED BALANCE VALVE
AUTOMATIC FLOW CONTROL VALVE
STRAINER
STRAINER WITH CAPPED BLOWDOWN
MANUAL AIR VENT
AUTOMATIC AIR VENT
VACUUM BREAKER
TEMPERATURE/PRESSURE TAP
THERMOMETER
PRESSURE GAUGE
STEAM TRAP WITH DESIGNATION
REFRIGERATION SIGHT GLASS
AIR FILTER/DRYER
REFRIGERATION THERMAL EXPANSION VALVE
INLINE PUMP
DIFFERENTIAL PRESSURE TRANSMITTER
WATER HAMMER ARRESTER WITH SCHEDULE TYPE
P-TRAP AND RISER
FLOOR DRAIN WITH SIZE & SCHEDULE TYPE
END OF PIPE CLEANOUT
FLOOR CLEANOUT
WALL CLEANOUT
EXTERIOR CLEANOUT OR RODDING HOLE
THERMOSTATIC MIXING VALVE WITH SCHEDULE TYPE
HOSE BIBB, WALL HYDRANT WITH SCHEDULE TYPE
WATER METER
GAS METER
ROOF DRAIN, OVERFLOW DRAIN WITH SIZE
POST INDICATOR VALVE
FIRE DEPARTMENT CONNECTION
VALVE TAMPER SWITCH
UPRIGHT SPRINKLER HEAD
PENDANT SPRINKLER HEAD
DRY PENDANT SPRINKLER HEAD
CONCEALED SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
GENERAL NOTES:NOTES THAT APPLY EQUALLY TO ALL DISCIPLINES
WITHIN THE DRAWING SET.
GENERAL
MECHANICAL NOTES:
NOTES THAT APPLY EQUALLY TO ALL SHEETS WITHIN
THE DISCIPLINE.
GENERAL SHEET
NOTES:
NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET
ON WHICH THEY APPEAR.
SHEET KEYNOTES:NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET
ON WHICH THEY APPEAR AND USE A KEYNOTE
INDICATOR TO IDENTIFY ITEMS.
F-000 FIRE SUPPRESSION
P-000 PLUMBING
M-000 MECHANICAL
000 GENERAL (SYMBOLS, ABBREVIATIONS, NOTES)
100 PLANS
200 ELEVATIONS
300 SECTIONS
400 LARGE SCALE VIEWS (PLANS, ELEVATIONS OR SECTIONS)
500 DETAILS
600 SCHEDULES OR DIAGRAMS
700 (USER DEFINED)
800 (USER DEFINED)
900 3D REPRESENTATIONS (ISOMETRICS)
THIN CONTINUOUS LINETYPE INDICATE EXISTING ITEMS TO
REMAIN.
INTERMEDIATE DASHED LINETYPE INDICATE EXISTING ITEMS TO
BE REMOVED.
INTERMEDIATE OR WIDE CONTINUOUS LINETYPE INDICATE NEW
ITEMS.
THIN HALFTONE LINETYPE INDICATE ITEMS BY OTHER
DISCIPLINE.
INDICATES POINT OF NEW CONNECTION TO EXISTING
EQUIPMENT, PIPING OR MATERIALS.
INDICATES POINT OF DISCONNECTION TO EXISTING
EQUIPMENT, PIPING OR MATERIALS.
PIPING LINE SYMBOLS
REFERENCE SYMBOLS
ABBREVIATIONS AND TERMS PIPING IDENTITY SYMBOLS
NOTATION DESIGNATORS
SHEET TYPE DESIGNATORS
LINETYPE DESIGNATORS NOT ALL NOTES, DESIGNATORS, SYMBOLS OR ABBREVIATIONS MAY APPLY TO THIS PROJECTDRAWING BLOCK TITLE
SECTION LOCATION
IN DRAWING MODULE
SECTION LOCATION AT SUBSET SHEET
DETAIL LOCATION IN
DRAWING MODULE
DETAIL LOCATION AT
SUBSET SHEET
LARGE SCALE VIEW
LOCATION IN DRAWING
MODULE
LARGE SCALE VIEW
LOCATION AT SUBSET SHEET
KEYNOTE INDICATORS
SCHEDULE TYPE
AIRFLOW (CUBIC FEET PER MINUTE)
EQUIPMENT TYPE
NUMERIC CHARACTER RELATES TO ITEM
ALPHANUMERIC CHARACTER RELATES
TO ASSOCIATED AIR HANDLER (OPTIONAL)
AREA LEADER
LINE LEADER
POINT LEADER
DRAWING MODULE LOCATION
(IDENTIFYING LOWER LEFT OF MULTIPLE
MODULES)
REVISION CLOUD
REVISION INDICATOR
NUMERIC SCALE
SEE XXXX
REFER TO ADDITIONAL
SHEET FOR CONTINUATION
FLOOR PLAN OVERLAP BEYOND AREA
EXTENSION
PLAN
PLAN
NUMERIC
CHARACTER
RELATES TO ITEM
NORTH ARROW
BEYOND AREA
EXTENSION
MULTIPLIER
(OPTIONAL)
ALPHANUMERIC CHARACTER RELATES
TO BUILDING LEVEL (OPTIONAL)
A.ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY
STANDARDS OF THE TRADE, AND SHALL CONFORM WITH ALL FEDERAL,
STATE, AND LOCAL CODES AND STANDARDS. THE SAME ARE MADE A
PART OF THESE CONTRACT DOCUMENTS AS IF REPEATED HEREIN.
B.CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND
DRAWINGS, AND BOTH ARE INTENDED TO BE COMPLEMENTARY.
ANYTHING APPEARING ON EITHER MUST BE EXECUTED THE SAME AS
IF SHOWN ON BOTH.
C.THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS
REQUIRED TO COMPLETELY AND PROPERLY INSTALL ALL WORK
REQUIRED FOR THE PROJECT, AND SHALL EXAMINE THE SCOPE OF
WORK OF OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
D.CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS
POSSIBLE, HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMATICALLY
AND IN SOME CASES, ENLARGED FOR CLARITY. ANY OFFSETS,
ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE
A COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE
CONTRACTOR.
E.THE ENGINEERING DRAWINGS ARE OF EQUAL IMPORTANCE WITH THE
ARCHITECTURAL DRAWINGS IN DEFINING THE WORK OF THE CONTRACT
DOCUMENTS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO CHECK WITH THE ARCHITECTURAL DRAWINGS BEFORE THE
INSTALLATION OF ENGINEERING WORK. SHOULD THERE BE A
DISCREPANCY BETWEEN THE ARCHITECTURAL DRAWINGS AND THE
ENGINEERING DRAWINGS THAT WOULD CAUSE AN AWKWARD OR
IMPROPER INSTALLATION, THE DISCREPANCY SHALL BE BROUGHT TO
THE ARCHITECTS/ENGINEERS ATTENTION FOR CLARIFICATION PRIOR TO
INSTALLATION OF SAID WORK. ANY WORK INSTALLED IN CONFLICT
WITH THE ARCHITECTURAL DRAWINGS SHALL BE CORRECTED BY THE
CONTRACTOR AT HIS EXPENSE AND AT NO ADDITIONAL COST TO THE
OWNER OR ARCHITECT/ENGINEER.
F.DO NOT SCALE THE DRAWINGS. THE DRAWINGS ARE NOT NECESSARILY
TO SCALE. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE PRIOR TO THE START OF
CONSTRUCTION. IF DISCREPANCIES ARE FOUND, THE
ARCHITECT/ENGINEER SHALL BE NOTIFIED FOR CLARIFICATION BEFORE
COMMENCING THE WORK. EXPLICIT DIMENSIONS SHALL HAVE
PRECEDENCE OVER SCALE.
G.CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
BIDDING OR BEGINNING WORK ON THIS PROJECT.
H.DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE SHOWN.
WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE
DETERMINED, CONSULT THE ARCHITECT/ENGINEER BEFORE
PROCEEDING WITH THE WORK.
I.ANY DETAILS, SYSTEMS AND/OR MATERIALS WHICH ARE PROPOSED TO
BE CHANGED MUST FIRST BE REVIEWED BY THE OWNER AND
ARCHITECT/ENGINEER PRIOR TO THE PREPARATION OF SHOP DRAWINGS.
J.REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
TEMPLATE DRAWINGS FOR ALL MECHANICAL EQUIPMENT SUPPORTS,
BOLT SETTING TEMPLATES, ISOLATORS, SPRING ISOLATION, ETC., NOT
SHOWN ON THE DRAWINGS.
K.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LOCATION OF CEILING MOUNTED MATERIALS INCLUDING ALL DIFFUSERS,
GRILLES, AND REGISTERS.
L.CONTRACTOR SHALL CLOSE ALL UNUSED OPENINGS IN EXISTING
DUCTWORK.
M.ALL DUCTWORK DESIGNATIONS REFER TO NET FREE AREA INSIDE THE
DUCTWORK.
N.VOLUME DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO
THE MAIN.
O.A MAXIMUM OF SIX FEET OF FLEXIBLE DUCTWORK MAY BE USED AT
ALL SUPPLY DIFFUSERS. BRANCH DUCTWORK TO DIFFUSER SHALL
BE SAME SIZE AS DIFFUSER INLET UNLESS SPECIFICALLY LABELED
OTHERWISE. REFER TO DIFFUSER SCHEDULE FOR INLET SIZES.
AVOID SHARP BENDS IN FLEXIBLE DUCTWORK WHICH MAY CAUSE
EXCESSIVE NOISE.
P.BRANCH DUCTWORK TO TERMINAL UNITS SHALL BE SAME SIZE AS
TERMINAL UNIT INLET UNLESS SPECIFICALLY LABELED OTHERWISE.
REFER TO TERMINAL UNIT SCHEDULE FOR INLET SIZES.
SCALE:1/8" = 1'-0"
SA
R DALSS
AD
M
G
CO
4"RD 4"OFD
24/12 24ø 24/12
HR
DTR
BF
DVC
WVC
N0
N
0
MV
MA
GV
LP
G
F
DE
DI
CL
SW
DWR
DWS
140°F
140°F
PD
D
AV
AW
FD
ST
DTS
FOV
FOR
FOS
GHR
GHS
RHG
CD
HPWR
HPWS
RL
H
CWR
CWS
CR
CS
BR
BS
RS
RD
HHR
HHS
ARV
MU
VPD
PC
BBD
LPC
MPC
HPC
LPS
MPS
HPS
FM
SG
IW
A
TWS
TWR
F&T
(TU-12.34)
(TU-12.34)
CO
NPW
FD
HB-1 WH-1
FCO
2"FD-1
WCO
ECO
TMV-1
WHA-A
30°20°øFSD
SD
SD
CO
TS
H
T
TS
AMS
FD
AD
PS
BDD
M
M
S
P
T
F
DPT
T
X
X
X
X
XXXX
X
X
X
X
X X
2
2
STANDOFF DAMPER FOR
ROUND TO RECTANGULAR
DUCTWORK, LOW PRESSURE
DUCTWORK
PD000 PLUMBING DEMOLITION
PG000 PLUMBING GAS
PS000 PLUMBING SANITARY
PW000 PLUMBING WATER
MD000 MECHANICAL DEMOLITION
MH000 MECHANICAL HVAC
MP000 MECHANICAL PIPING
DISCIPLINE DESIGNATORS
N
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:22 PMMP000
MECHANICAL &
PLUMBING SYMBOLS
& ABBREVIATIONS
16071.001
TCR
KSB
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
DWTTTT TTLOUNGE
111
SUPPLIES
108
MEN
109
WOMEN
110
OFFICE
105
OFFICE
103
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
120
OFFICE
119
OFFICE
122
OFFICE
123
OFFICE
124
OFFICE
115
CONFERENCE
116
I.T.
107
JAN. / SUPPLY
199
MEN (EXIST.)
198
WOMEN (EXIST.)
197
EXISTING STAIR
196
EXISTING STAIR
190
STOR.
113
EXISTING BLDG.
TRANSFORMER
195
EXISTING BLDG.
STOR.
193
EXISTING BLDG.
PHONE
191 EXISTING BLDG.
ELECT.
192
STORAGE
101A
ADMIN. ASST.
101F
RECEPTIONIST
101H
EXISTING
ELEVATOR
189
HALL
101B
LOBBY
101
ENTRY
VESTIBULE
100
EXISTING
SECONDARY
ENTRY
VESTIBULE
OFFICE
118
OFFICE
121
OFFICE
117
OFFICE
114
ADJACENT
TENANT SPACE
ADJACENT
TENANT SPACE
EXISTING
CORRIDOR
ENTRY AREA
101C
HALL
101D
HALL
125
ADMIN. ASST.
101G
CLOSET
103A
CORRIDOR
101E
EX. VAV-1
EX. VAV-2
EX. VAV-1
22/14
EX. VAV-1
EX. VAV-2
EX. VAV-1
UP TO EX. RTU-5
UP TO EX. RTU-2
26/16
30/20
UP TO EX. RTU-1
EX. UH
EX. UHEX. UH
EX. UH
EX. UH
EG1
50
EG1
50
2
M-101
EF-1
8ø
8ø
6ø 6ø
30/18
1
EX. VAV-2
8ø8ø
8ø
RTU-2
RTU-1
SG3
200
SG3
200
SG3
200
SG4
300
SG3
180
SG3
175
SG3
175
SG3
175
SG3
175
SG3
175
SG3
175
SD1
130
SD1
130
SG2
150
SG2
150
SG2
150
SG2
150
SG2
150
SG3
180
SG2
120
SG2
120
SG2
120
SG3
250
SG3
250
SG4
300
SG4
300
SG2
90
SG4
290
SG4
290
SG2
100
SG2
100
SG2
130
SG2
120
SG2
130
SG3
160
RG1
RG2
RG2
RG2 RG2 RG2
RG3
RG3
RG2
RG2
RG2
RG3
RG2 RG2 RG2
RG3
RG1
RG2RG3
RG2
RG2
RG2
RG3
SG2
110
SG2
110
LD1
180
LD1
180
SD1
50
5
8ø
8ø
8ø
10/10 8ø
18/14
8ø
8ø
1960
12/10
8ø
24/14
8ø 8ø
30/18
8ø
8ø8ø
6ø
30/18
8ø 8ø 8ø
14/1410ø
10ø 10ø
RG2
8ø
8ø
8ø
8ø 8ø
RG3
8ø 8ø
12/10
10ø
10ø
8ø
8ø
16/12
20/14
20/14
6ø
2
RTU-5
4
4
4
LD1
110
LD1
110
8ø
8ø
8ø
8ø
8ø
8ø
3
3
6
RP-1
EDC-1
RP-1
RP-1
EDC-1
8ø
12/10
SG1
260
SG1
260
14/8
14/8
3
M-101
30/6
RG4
520
7
2
A.REFER TO DRAWING M-000 FOR MECHANICAL SYMBOLS AND ABBREVIATIONS.
B.REFER TO DRAWING M-600 FOR MECHANICAL SCHEDULES AND DETAILS.
C.ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL, STATE AND LOCAL
CODES AND STANDARDS.
D.COORDINATE WITH STRUCTURAL AND FRAMING PLANS PRIOR TO COMMENCING
WORK. COORDINATE ALL ROUTINGS WITH ALL TRADES PRIOR TO FABRICATION.
E.CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BIDDING
OR BEGINNING WORK ON THIS PROJECT.
F.ALL MATERIALS USED TO CLOSE, CAP, PLUG, OR REROUTE EXISTING UTILITIES AND
SERVICES SHALL BE NEW, BE COMPATIBLE WITH AND MATCH EXISTING MATERIALS.
G.PROTECT ALL SURFACES, FINISHES, AND EQUIPMENT TO REMAIN AS REQUIRED,
PATCH, REPAIR, OR REPLACE AS REQUIRED.
H.CONTRACTOR IS TO OBTAIN A FULL SET OF DRAWINGS, INCLUDING BUT NOT
LIMITED TO ARCHITECTURAL AND STRUCTURAL, PRIOR TO SUBMITTING THEIR BID.
I.THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COST REQUIRED TO
COMPLELETLY AND PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT
AND SHALL EXAMINE THE SCOPE OF WORK OF OTHER TRADES PRIOR TO
SUBMITTING A BID PROPOSAL.
J.CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND DRAWINGS
AND BOTH ARE INTENDED TO BE COMPLIMENTARY - ANYTHING APPEARING ON
EITHER MUST BE EXECTUED THE SAME AS IF SHOWN ON BOTH.
K.SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND TYPES OF RATED
CONSTRUCTION TO MAINTAIN CONSTRUCTION RATING.
L.DUCTWORK TO SUPPLY DIFFUSERS TO BE AT LEAST THE DIAMETER INDICATED ON
THE GRILLES OR OTHERWISE NOTED ON PLANS. ALL INDIVIDUAL DIFFUSERS AND
GRILLES ARE TO HAVE A BALANCE DAMPER INSTALLED IN THE BRANCH
DUCTWORK.
M.ALL MECHANICAL SYSTEMS ARE TO BE BALANCED BY CERTIFIED TEST AND
BALANCE CONTRACTOR.
N.ALL THERMOSTATS AND TEMPERATURE SENSORS ARE TO BE MOUNTED 54-INCHES
ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.
O.WHERE DUCTS ARE SHOWN TO BE CROSSING, THE UPPER DUCT IS TO RISE INTO &
BE ROUTED INSIDE THE SPACE BETWEEN JOISTS OR THROUGH THE JOIST
WEBBING.
GENERAL SHEET NOTES
14/8
SG1
260
FIRST LEVEL
100' - 0"
6/30
RG4
520
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 6:43:39 PMM-101
MECHANICAL FLOOR
PLAN
16071.001
TCR
KSB
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
MECHANICAL FLOOR PLAN1
SHEET KEYNOTES
1 PROVIDE A HOODED VENT CAP WITH SCREEN AT WALL PENETRATION.
2 RELOCATED EXISTING VAV THERMOSTAT.
3 MOUNT LINER SLOT ALONG EDGE OF 9'-0" GWB CEILING
4 NEW WIRED 7-DAY PROGRAMMABLE THERMOSTAT WITH RESET OVERRIDE.
5 RECALIBRATE EXISTING VAV TO MAX 500 CFM AND MIN 150 CFM.
6 RECALIBRATE EXISTING VAV TO MAX 360 CFM AND MIN 160 CFM.
7 ROUTE 14/8 SUPPLY AND 30/6 RETURN DUCTWORK DOWN WITHIN WALL
SHAFT AND INTO LOUNGE BULKHEAD.
1/4" = 1'-0"
MECHANICAL LOUNGE BULKHEAD SECTION2
DIFFUSERS & GRILLES SCHEDULE
SPECIFICATION SECTION 233713
MARK MAX CFM
DIMENSIONAL DATA THROW DATA
MOUNT
PRESS.
DROP
(IN. WC.)
MAX NC
SOUND
LEVEL
ACCESSORIES
MANUFACTURER
WITH
MODEL
NUMBER
FACE SIZE SLOT INFO
CONN.
SIZE DIRECTION DISTANCE
@ NOM. CFM
BALANCE
DAMPER
PLENUM
BOOT
TAMPER-
PROOF
SCREWS
SD1 150 12"x12" - 6"ø 4-way 10 SEE PLANS <20 - - - PRICE SPD
SD2 150 24"x24" - 6"ø 4-way 6 0.03 <20 - - - PRICE SPD
SD3 250 24"x24" - 8"ø 4-way 8 0.03 <20 - - - PRICE SPD
SD4 400 24"x24" - 10"ø 4-way 10 0.03 <20 - - - PRICE SPD
SEE PLANS
SEE PLANS
SEE PLANS
0.03
RG2 700 12"x24" 1/2"x1/2"x1/2" - - - SEE PLANS 0.04 20 - - - PRICE 80
RG3 3000 24"x24" 1/2"x1/2"x1/2" - - - SEE PLANS 0.04 20 - - - PRICE 80
NOTES
NOTES:
1.
RG1 450 12"x12" 1/2"x1/2"x1/2" - - - SEE PLANS 0.04 20 - - - PRICE 80
LD1 180 48" 2 @ 3/4" 8"ø 1-way 19 SEE PLANS 0.07 22 - - - PRICE TBD4
SG1 275 14"x6" 3/4" @ 45º - DOUBLE 15 0.02 <20 - - - PRICE 520DSEE PLANS
RG4 535 30"x6" - - - SEE PLANS 0.07 24 - - - PRICE 5303/4" @ 45º
FAN SCHEDULE
SPECIFICATION SECTION 233423
MARK LOCATION
FAN DATA MOTOR DATA ACCESSORIES
UNIT
WEIGHT
(LBS)
MANUFACTURER
WITH
MODEL NUMBER
NOTES
DESCRIPTION
WHEEL
SIZE
(IN)
DRIVE TYPE CFM TSP BHP RPM SONES HP VOLTS PH
ROOF
CURB
DISCONNECT
SWITCH
GRAVITY
BACKDRAFT
DAMPER
VIBRATION
ISOLATORS
BIRD
SCREEN
NOTES:
1.
EF-1 WORK ROOM 106 INLINE - DIRECT 100 0.25 0.02 1725 3.9 1/10 120 1 NO YES YES YES NO 34 GREENHECK SQ-60-VG
1.
PROVIDE UNIT WITH SPEED CONTROLER AND DISCONNECT SWITCH.
A.METALLIC FLEXIBLE DUCT SHALL BE ATTACHED USING A MINIMUM OF THREE #8
SHEET METAL SCREWS EQUALLY SPACED AROUND THE DUCT'S CIRCUMFERENCE;
DUCTS LARGER THAN 12"∅ SHALL HAVE A MINIMUM OF FIVE #8 SHEET METAL
SCREWS. SCREWS SHALL BE LOCATED AT LEAST 1/2" FROM THE DUCT END.
B.NON-METALLIC FLEXIBLE DUCT SHALL BE SECURED TO THE SLEEVE OR COLLAR
USING A DRAW BAND. IF THE DUCT COLLAR EXCEEDS 12"∅, THE DRAW BAND MUST
BE POSITIONED BEHIND A BEAD ON THE METAL COLLAR.
C.INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY-FABRICATED DUCTS
SHALL BE FITTED OVER THE CORE CONNECTION AND SHALL BE SUPPLEMENTALLY
SECURED WITH A DRAW BAND.
D.FLEXIBLE DUCT SEALING SHALL BE A CLASS "B" SEAL FOR LOW PRESSURE SUPPLY.
JOINING AND ATTACHING FLEXIBLE DUCT SPECIFICATION:
RECTANGULAR
SUPPLY DUCT
SPIN-IN FITTING
W/VOLUME DAMPER
FLEX DUCT-MAXIMUM 6'-0"
LENGTH AND NO MORE THAN
ONE (1) 90° BEND.
SQUARE TO ROUND FITTING
CEILING
SUPPLY DIFFUSER
90° METAL
ELBOW
TYPICAL AT ALL
DIFFUSER
CONNECTIONS
1.5 W
8"TYPE "AT" GRILLE-SEE
FLOOR PLANS FOR SIZE.
INTERNALLY LINED DUCTWORK
SEE FLOOR PLANS FOR DUCT SIZE.
W
0.75 W
ALL THREAD ROD TO
STRUCTURE (TYP)
VIBRATION ISOLATORS
(REFER TO SPECIFICATIONS)
FLEXIBLE DUCT
CONNECTION (TYP)
BACKDRAFT DAMPER
REFER TO FLOOR
PLANS FOR DUCT
SIZE
TRANSITION AS
REQUIRED (TYP)
DIRECT DRIVE MOTOR
CROSS
BRACE
FAN
ELECTRIC RADIANT PANEL SCHEDULE
SPECIFICATION SECTION 238201
MARK LOCATION
HEAT
KW
ELECTRICAL DATA
MANUFACTURER
WITH MODEL #
NOTES
VOLTS PH
NOTES:
RP-1 SEE PLANS 0.38 120 1
DISCONNECT
SWITCH
INTEGRAL
THERMOSTAT
YES NO QMARK CP371
1.PROVIDE UNIT WITH DISCONNECT SWITCH.
1.
ELECTRIC DUCT HEATER SCHEDULE
SPECIFICATION SECTION 238201
MARK LOCATION
DUCT
DIMENSIONS CFM MIN KW STAGES
TEMP.
RISE
(°F)
ELECTRICAL DATA MANUFACTURER
WITH
MODEL NUMBER
NOTES
AMPS VOLTS PH
NOTES:
1.
EDC-1 CONFERENCE 116 12/10 150 MODULATING INDEECO QUZ 1.
PROVIDE UNIT WITH SCR CONTROL (CONTROL K), FAN RELAY, AND INSULATED TERMINAL BOX OPTIONS.
4.0 25 33.3 120 1
FLOW
FLOW
30° MAX.
ACCESS DOOR
ACCESS DOOR
COIL
20° MAX.
TOP VIEW SUPPLY
AIR DUCTWORK
SIDE VIEW SUPPLY
AIR DUCTWORK
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:29 PMM-601
MECHANICAL
SCHEDULES AND
DETAILS
16071.001
TCR
KSB
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
NOT TO SCALE
TYPICAL SUPPLY DIFFUSER DETAIL1NOT TO SCALE
AIR TRANSFER DUCT DETAIL2 12" = 1'-0"
CENTRIFUGAL IN-LINE FAN DETAIL3
12" = 1'-0"
DUCT MOUNTING COIL DETAIL4
4" W
4" W
4"
EX 4" W-UP & DN
1
2
FCO
ECO
A.THE ENTIRE PLUMBING SYSTEM SHALL CONFORM TO THE INDIAN PLUMBING
CODE ALONG WITH ALL LOCAL CODES AND AUTHORITIES HAVING
JURISDICTION.
B.ALL PIPING SHOWN IS FROM FIELD OBSERVATIONS, NO EXISTING DRAWINGS
EXIST. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO START OF
CONSTRUCTION BEFORE DEMOLITION OR START OF NEW WORK. IF
CONDITIONS ARE DIFFERENT THAN INDICATED CONTACT THE ARCHITECT /
ENGINEER PRIOR TO CONTINUING WORK. FAILURE TO VERIFY AND REPORT
SHALL CONSTITUTE THE CONTRACTORS ACCEPTANCE OF THE EXISTING
CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THEIR WORK AND WILL
NOT BE ALLOWED ANY ADDITIONAL FEES.
C.THE CONTRACTOR IS RESPONSIBLE FOR REMOVING ALL EXISTING PLUMBING
SYSTEMS MADE OBSOLTE BY NEW CONSTRUCTION, INCLUDING ALL WATER,
WASTE AND VENT PIPING, FIXTIRES, TRIM AND ACCESSORIES. REFERENCE
THE ARCHITECTURAL DOCUMENTS AND FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO BID AND INCLUDE ALL COSTS IN BID.
D.ALL EXISTING SANITARY PIPING TO REMAIN IS TO BE CLEANED AND RODDED
TO ENSURE PROPER FLOW. PIPING INDICATED AS DASHED LINES IS TO BE
REMOVED COMPLETE INCLUDING ALL HANGERS AND PIPE SUPPORTS.
E.CAP ALL OBSOLETE WASTE PIPING BELOW FLOOR SLAB, WATER PIPING BACK
AT MAINS AND VENT PIPING ABOVE FINISHED CEILINGS.
F.THE PLUMBING CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM
SHUT DOWN WITH THE DIRECTOR OF FACILITIES A MINIMUM OF TWO WEEKS
IN ADVANCE.
GENERAL SHEET NOTES
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:38 PMPD100
PLUMBING
FOUNDATION
DEMOLITION PLAN
16071.001
LLP
LLP
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
PLUMBING FOUNDATION DEMOLITION PLAN1
SHEET KEYNOTES
1 REMOVE AND CAP SANITARY BELOW SLAB AND PATCH TO RECEIVE NEW
FINISH
2 REMOVE AND CAP 1 1/2"CW, 1/2"CW AND 1/2" HW LINES BELOW SLAB AND
PATCH TO RECEIVE NEW FINISH
3/4" CW
1 1/2"
1 1/2"
1 1/2"
EX WATER HEATER
ABOVE CEILINGEX WALL
HYDRANT
EX E.C.O.
EX F.C.O.
EX WALL
HYDRANT
2" CW
2" CW
EX WALL
HYDRANT
ABANDONED WELL
SERVICE LINE
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2"
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1/2" CW
1/2" HW
1 1/2" VENT
1 1/2" SANITARY
1 1/2"
2"
1 1/2"
1/2"
1/2"
EX 2"V-UP / 2"W-DN
EX 4" W-UP&DN
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
A.THE ENTIRE PLUMBING SYSTEM SHALL CONFORM TO THE INDIAN PLUMBING
CODE ALONG WITH ALL LOCAL CODES AND AUTHORITIES HAVING
JURISDICTION.
B.ALL PIPING SHOWN IS FROM FIELD OBSERVATIONS, NO EXISTING DRAWINGS
EXIST. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO START OF
CONSTRUCTION BEFORE DEMOLITION OR START OF NEW WORK. IF
CONDITIONS ARE DIFFERENT THAN INDICATED CONTACT THE ARCHITECT /
ENGINEER PRIOR TO CONTINUING WORK. FAILURE TO VERIFY AND REPORT
SHALL CONSTITUTE THE CONTRACTORS ACCEPTANCE OF THE EXISTING
CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THEIR WORK AND WILL
NOT BE ALLOWED ANY ADDITIONAL FEES.
C.THE CONTRACTOR IS RESPONSIBLE FOR REMOVING ALL EXISTING PLUMBING
SYSTEMS MADE OBSOLTE BY NEW CONSTRUCTION, INCLUDING ALL WATER,
WASTE AND VENT PIPING, FIXTIRES, TRIM AND ACCESSORIES. REFERENCE
THE ARCHITECTURAL DOCUMENTS AND FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO BID AND INCLUDE ALL COSTS IN BID.
D.ALL EXISTING SANITARY PIPING TO REMAIN IS TO BE CLEANED AND RODDED
TO ENSURE PROPER FLOW. PIPING INDICATED AS DASHED LINES IS TO BE
REMOVED COMPLETE INCLUDING ALL HANGERS AND PIPE SUPPORTS.
E.CAP ALL OBSOLETE WASTE PIPING BELOW FLOOR SLAB, WATER PIPING BACK
AT MAINS AND VENT PIPING ABOVE FINISHED CEILINGS.
F.THE PLUMBING CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM
SHUT DOWN WITH THE DIRECTOR OF FACILITIES A MINIMUM OF TWO WEEKS
IN ADVANCE.
GENERAL SHEET NOTES
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:41 PMPD101
PLUMBING FLOOR
DEMOLITION PLAN
16071.001
LLP
LLP
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
PLUMBING FLOOR DEMOLITION PLAN1
SHEET KEYNOTES
1 EXISTING WATER HEATER IS TO BE CAREFULLY REMOVED AND STORED FOR
REINSTALLATION ABOVE NEW MENS RESTROOM CEILING. COORDINATE ALL
ELECTRICAL DEMOLITION REQUIREMENTS WITH E.C. PRIOR TO START OF
NEW WORK.
2 ALL ABANDONED AND OBSOLTE WATER, WASTE AND VENT PIPING IS TO BE
REMOVED INCLUDING ALL SUPPORTS AND HANGERS. NO EXISTING
DRAWINGS ARE AVAILABLE - CONTRACTOR TO VERIFY IF ANY LINES ARE
ACTIVE PRIOR TO REMOVAL.
3 REMOVE EXISTING CASEWORK SINK, TRIM AND SUMP PUMP SYSTEM UNDER
COUNTERTOP, WATER, WASTE AND VENT PIPING IS TO BE REMOVED
INCLUDING ALL SUPPORTS AND HANGERS. NO EXISTING DRAWINGS ARE
AVAILABLE - CONTRACTOR TO VERIFY IF ANY LINES ARE ACTIVE PRIOR TO
REMOVAL.
DWEX FCO 4" W
4" W
ECO
4" W
FCO
4" W
4" W2" W
4" W
4" W
2" W
1
2
3
EX 4" W-UP & DN
A.REFER TO DRAWING M-000 FOR MECHANICAL, PLUMING AND FIRE
PROTECTION
SYMBOLS AND ABBREVIATIONS.
B.THE ENTIRE PLUMBING SYSTEM SHALL CONFORM TO THE INDIAN PLUMBING
CODE ALONG WITH ALL LOCAL CODES AND AUTHORITIES HAVING
JURISDICTION.
C.ALL PIPING SHOWN IS FROM FIELD OBSERVATIONS. NO EXISTING
DRAWINGS
EXIST. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO START OF
CONSTRUCTION BEFORE DEMOLITION OR START OF NEW WORK. IF
CONDITIONS
ARE DIFFERENT THAN INDICATED CONTACT THE ARCHITECT / ENGINEER
PRIOR
TO CONTINUING WORK. FAILURE TO VERIFY AND REPORT SHALL
CONSTITUTE THE CONTRACTORS ACCEPTANCE OF THE EXISTING CONDITIONS
AS FIT FOR
THE PROPER EXECUTION OF THEIR WORK AND WILL NOT BE ALLOWED ANY
ADDITIONAL FEES.
D.THESE PLANS ARE DIAGRAMATIC, CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSETS, TEES, ELBOWS, ETC… FOR A COMPLETE AND
OPERABLE
PLUMBING SYSTEM.
E.THE PLUMBING CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM
SHUTDOWN WITH THE OWNER A MINIMUM OF TWO WEEKS IN ADVANCE.
F.ALL PIPING PENETRATIONS THRU NEW OR EXISTING WALLS, FLOORS OR
CEILINGS SHALL BE SEALED TO THE EQUAL RATING OF THE NEW OR
EXISTING
SYSTEM.
G.COORDINATE ALL SANITARY PIPING SIZES, INVERT ELEVATIONS AND
EXACT
LOCATION WHERE THE PIPING EXITS THE BUILDING WITH THE CIVIL SITE
DRAWINGS AND SITE CONTRACTOR PRIOR TO STARTING NEW WORK.
H.THE BUILDING WILL BE FULLY SPRINKLERED. FIRE PROTECTION
CONTRACTOR
SHALL DESIGN THE COMPLETE SYSTEM ACCORDING TO THE CRITERIA
OUTLINED ON THE DRAWINGS, SPECIFICATIONS AND NFPA 13.
I.ALL PIPING, INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND
ADHESIVES SHALL BE PLENUM RATED AND HAVE A 25 / 50 SMOKE FLAME
RATING.
GENERAL SHEET NOTES
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:32 PMP-100
PLUMBING
FOUNDATION PLAN
16071.001
LLP
LLP
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
PLUMBING FOUNDATION PLAN1
SHEET KEYNOTES
1 CONNECT NEW PIPING TO EXISTING. FIELD VERIFY EXISTING LOCATION,
SIZE OF PIPE AND ELEVATION PRIOR TO START OF NEW WORK.
2 2" WASTE UP IN WALL TO SERVE LAVATORIES.
3 2" WASTE UP IN CHASE.
DWLOUNGE
111
SUPPLIES
108
MEN
109 WOMEN
110
OFFICE
105
OFFICE
103
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
120
OFFICE
119
OFFICE
122
OFFICE
123
OFFICE
124
OFFICE
115
CONFERENCE
116
I.T.
107
JAN. / SUPPLY
199
MEN (EXIST.)
198
WOMEN (EXIST.)
197 EXISTING STAIR
196
EXISTING STAIR
190
STOR.
113
EXISTING BLDG.
TRANSFORMER
195
EXISTING BLDG.
STOR.
193
EXISTING BLDG.
PHONE
191
EXISTING BLDG.
ELECT.
192
STORAGE
101A
ADMIN. ASST.
101F
RECEPTIONIST
101H
EXISTING
ELEVATOR
189
HALL
101B
LOBBY
101
ENTRY
VESTIBULE
100
EXISTING
SECONDARY
ENTRY
VESTIBULE
?
OFFICE
118
OFFICE
121
OFFICE
117
OFFICE
114
ADJACENT
TENANT SPACE
?
ADJACENT
TENANT SPACE
?
EXISTING
CORRIDOR
?
ENTRY AREA
101C
HALL
101D
HALL
125
ADMIN. ASST.
101G
CLOSET
103A CORRIDOR
101E
L-1
L-1
WC-1WC-1
EX FCO
EX ECO
1 1/2" V
1 1/2" V
2" V
3" V
3" V
3" V
3" V
FCO
1 1/2" W
2" CW
2" CW
EX WALL
HYDRANT
ABANDONED WELL
SERVICE LINE
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1" CW
WD-1
EWH-1
EX FIXTURE
EX WALL
HYDRANT
EX 4" W-UP & DN
IB-1
1/2" CW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
3/4" CW3/4" CW1
1" CW
1/2" HW
1/2" CW
1 1/2" V
1/2" CW
1/2" HW
1" CW
1" CW
1/2" HW
2
3
4
5
1
EX 4"W-DN
3/4" CW3/4" CW1
A.REFER TO DRAWING M-000 FOR MECHANICAL, PLUMING AND FIRE
PROTECTION
SYMBOLS AND ABBREVIATIONS.
B.THE ENTIRE PLUMBING SYSTEM SHALL CONFORM TO THE INDIAN PLUMBING
CODE ALONG WITH ALL LOCAL CODES AND AUTHORITIES HAVING
JURISDICTION.
C.ALL PIPING SHOWN IS FROM FIELD OBSERVATIONS. NO EXISTING
DRAWINGS
EXIST. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO START OF
CONSTRUCTION BEFORE DEMOLITION OR START OF NEW WORK. IF
CONDITIONS
ARE DIFFERENT THAN INDICATED CONTACT THE ARCHITECT / ENGINEER
PRIOR
TO CONTINUING WORK. FAILURE TO VERIFY AND REPORT SHALL
CONSTITUTE THE CONTRACTORS ACCEPTANCE OF THE EXISTING CONDITIONS
AS FIT FOR
THE PROPER EXECUTION OF THEIR WORK AND WILL NOT BE ALLOWED ANY
ADDITIONAL FEES.
D.THESE PLANS ARE DIAGRAMATIC, CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSETS, TEES, ELBOWS, ETC… FOR A COMPLETE AND
OPERABLE
PLUMBING SYSTEM.
E.THE PLUMBING CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM
SHUTDOWN WITH THE OWNER A MINIMUM OF TWO WEEKS IN ADVANCE.
F.ALL PIPING PENETRATIONS THRU NEW OR EXISTING WALLS, FLOORS OR
CEILINGS SHALL BE SEALED TO THE EQUAL RATING OF THE NEW OR
EXISTING
SYSTEM.
G.COORDINATE ALL SANITARY PIPING SIZES, INVERT ELEVATIONS AND
EXACT
LOCATION WHERE THE PIPING EXITS THE BUILDING WITH THE CIVIL SITE
DRAWINGS AND SITE CONTRACTOR PRIOR TO STARTING NEW WORK.
H.THE BUILDING WILL BE FULLY SPRINKLERED. FIRE PROTECTION
CONTRACTOR
SHALL DESIGN THE COMPLETE SYSTEM ACCORDING TO THE CRITERIA
OUTLINED ON THE DRAWINGS, SPECIFICATIONS AND NFPA 13.
I.ALL PIPING, INSULATION, JACKETS, COVERINGS, SEALERS, MASTICS AND
ADHESIVES SHALL BE PLENUM RATED AND HAVE A 25 / 50 SMOKE FLAME
RATING.
GENERAL SHEET NOTES
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:36 PMP-101
PLUMBING FLOOR
PLAN
16071.001
LLP
LLP
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
PLUMBING FLOOR PLAN1
SHEET KEYNOTES
1 CONNECT NEW PIPING TO EXISTING. FIELD VERIFY EXISTING LOCATION,
SIZE OF PIPE AND ELEVATION PRIOR TO START OF NEW WORK.
2 MOUNT EXISTING WATER HEATER ON SHELF ABOVE CEILING WITH DRAIN
PAN. SEE DETAIL ON SHEET P-501.
3 CORE DRILL DOWN THRU THE 18" THICK CONCRETE VAULT LID TO ROUTE A
1/2"CW, 1/2"HW AND 1 1/2" VENT LINE DOWN IN FURRED OUT WALL TO SERVE
NEW PLUMBING FIXTURES.
4 ROUTE A 1/2" CW LINE THRU FURRED OUT WALL TO SERVE REFRIGERATOR
ICE MACHINE SUPPLY BOX IB-1.
5 2" WASTE DOWN BELOW SLAB. PROVIDE WALL CLEANOUT AT 18" A.F.F.
PLUMBING FIXTURE SCHEDULE
SEE SPECIFICATION SECTION 22400
FIXTURE # DESCRIPTION FIXTURE CONNECTION MOUNTING HEIGHT NOTES:
CW HW WASTE VENT
WC-1 WATER CLOSET: AMERICAN STANDARD "CADET 3 RIGHT HEIGHT"
#270BA.001, FLOOR MOUNTED, TANK TYPE; 1.6 GPF, WITH ADA
COMPLIANT HANDLE.
3/4"- 4" 2"15" FLOOR TO RIM 1
L-1 LAVATORY: AMERICAN STANDARD "AQUALYN" #0476.028; 20" X
18", FAUCET LEDGE, COUNTERTOP MOUNTED. FAUCET: LIKE
CHICAGO FAUCET #802-CP-369 LAVATORY FITTING WITH ADA
COMPLIANT 2 1/2" LEVER HANDLES, GRID DRAIN STRAINER, 1 1/2"
TAILPIECE AND ADJUSTABLE 1 1/2" P-TRAP WITH CLEANOUT;
CHICAGO FAUCET #1006 SUPPLIES WITH LOOSE KEY ANGLE
STOPS.
1/2" 1/2" 1 1/2" 1 1/2" COUNTERTOP MOUNTED
S-1 SINK: DOUBLE COMPARTMENT, 33" X 19" X 7-1/2", LEDGEBACK
DRILLED FOR FITTINGS; UNDERCOATED LIKE: ELKAY
"LUSTERTONE"#LR-3319; FAUCET: 8” CENTERS; 8” CAST BRASS
SWING SPOUT, VANDAL RESISTANT AERATOR OUTLET, COLOR
CODED SINGLE LEVER HANDLES WITH VANDAL RESISTANT
SCREWS LIKE: CHICAGO FAUCET #786-GN8A-369 P-TRAP: 1-1/2” 17
GAUGE CAST BRASS, ADJUSTABLE, WITH CLEANOUT PLUG,
TUBING OUTLET AND WALL FLANGE SUPPLIES: 1/2" ANGLE STOP
WITH LOOSE KEY HANDLE, 12" LONG 1/2" O.D. CHROME PLATED
FLEXIBLE RISER AND WALL FLANGE LIKE: CHICAGO FAUCET #1006.
1/2" 1/2" 1 1/2" 1 1/2" SEE CASEWORK
IMB-1 ICE MAKER SUPPLY BOX: WATER TITE #MIB-1, 20GA. STEEL BOX,
WHITE ENAMEL FINISH, CHROME PLATED 1/4 TURN BALL VALVE
WITH BLUE HANDLE , 1/2" SWEAT CONNECTION, WATER HAMMER
ARRESTER
1/2"- - - 18" A.F.F.
WD-1 FOOD WASTE DISPOSER: LIKE INSINKERATOR BADGER 5; 120V, 1
PH, 60 HZ, 1725 RPM, 1/2 H.P., 6.3 AMPS
NOTES:1. ADA COMPLIANT HEIGHT
PIPE
DOUBLE SUPPORT NUT
LOCKING NUT
HANGER ROD HANGER ROD
LOCKING NUT
SUPPORT NUT
CLEVIS HANGER
14 GAUGE ZINC COATED
SHEET STEEL SADDLE
AT LEAST 12" LONG
PIPE
INSULATION
INSULATION
PREFORMED PIPE SUPPORT INSERT,
SAME THICKNESS AS INSULATION MANUFACTURED FOR THIS PURPOSE.
AT REFRIGERATORS - 12" AFF.VARIESREFRIGERATOR ICE MAKER
RECESSED WALL BOX WITH
FACE PLATE; EQUAL TO OATEY
SERIES RECESSED WALL BOXES.
ANGLE STOP VALVE WITH
THREADED CONNECTION
FOR ICE MAKER TUBING
1/2"CW
FLOOR LINE
NEW WATER, GAS, SEWER,
CONDUITS, ETC.
EXISTING SUBGRADE
EXISTING FINISHED
SURFACE
EXISTING EARTH
NOTE #1NOTE #2
1. IF A REQUIRED AREA OF FLOOR CUTTING OR REMOVAL HAS NOT BEEN NOTED OR
IDENTIFIED ON THE ARCHITECTURAL OR STRUCTURAL DRAWINGS, THE CONTRACTOR
INSTALLING THE NEW UTILITY SERVICE SHALL MAKE THE CUT, EXCAVATE, INSTALL NEW
SERVICE, INSTALL AN APPROVED GRAVEL BACKFILL TO TOP OF SUBGRADE, AND HAUL
AWAY EXCESS MATERIAL.
2. PATCH TO TO RECEIVE NEW FLOOR FINISH.
NOTES:
#3 REBAR @ 18" O.C.
DRILLED AND EPOXY
INTO EXISTING SLAB
TWO LAYERS OF 3/4"
TREATED PLYWOOD
1 1/2" X 1 1/2" ANGLE
TYPICAL UNISTRUT PIPE SUPPORT
WITH CLEVIS HANGER
TYPICAL BALL VALVE
TYPICAL DIELECTRIC UNION
BEAM CLAMP AND 1/2"
TO BOTTOM OF JOIST
ALL-THREAD ROD ATTACHED
B-LINE #B3046, ANGLE IRON
IRON SUPPORT
MIXING VALVE
TMV-1 THERMOSTATIC
(SET @ 120° MAX.)
3/4" COLD WATER SUPPLY
TO WATER HEATER
FINISHED CEILING
3/4" HOT WATER
SUPPLY TO SYSTEM
CHECK VALVE
TYPICAL THERMOMETER
3/4" PAN DRAIN LINE
2" DEEP GALVANIZED
STEEL DRAIN PAN.
WATER HEATER DRAIN VALVE
TO ELECTRICAL POWER SOURCE
ASME RATED TEMPERATURE AND
PRESSURE RELIEF VALVE.
J.R. SMITH #3950 FIXED
AIR GAP DRAIN
1 1/2" WASTE LINE TO
NEAREST SANITARY SYSTEM
1 1/2" P-TRAP
ELECTRIC
(SEE ELECTRICAL PLANS)
WATER HEATER
SINK
SHUT-OFF VALVE
REDUCER
GARBAGE
DISPOSAL
5/8" DRAIN
HOSE
DISHWASHER
1/2" HW
CW SUPPLY
HW SUPPLY
COUNTERTOP
INSTALL AS HIGH AS
POSSIBLE UNDER
THE COUNTERTOP
FCO
L-1
FCOWC-1
WC-1
L-1
1 1/2" V
1 1/2" V
S-1
ECO4" W
2" W
2" W
4" W
4" W
4" W
3" V
3" V
1 1/2" V
1 1/2" W
3" V
2" V
1 1/2" V
2" V
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:05:53 PMP-501
PLUMBING DETAILS
& SCHEDULES
16071.001
LLP
LLP
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
12" = 1'-0"
PIPE HANGER DETAIL1 12" = 1'-0"
ICE MAKER SUPPLY BOX DETAIL2 12" = 1'-0"
FLOOR SLAB CUTTING DETAIL3
12" = 1'-0"
ELECTRIC WATER HEATER PIPING DETAIL4 12" = 1'-0"
DISHWASHER / DISPOSAL DETAIL5
PLUMBING ISOMETRIC DETAIL
EX
T
T
CT
G
M
M
TS
M
FT
DK
K
FAA
FACP
EVAC
FATC
BATT
ASFP
TPR
IAM
ZAM
CR
DH
H
F
S
S D
RTS
S A
S E
S SC
S V
B R
B S
C
F
H
H F
H2
D FS
FS
PS
TS
PIV
EOL
W
TV
TV
M
M
M
S
S
S
P
P
IC
MI
VC
TCC
C
CCTV
MTV
B
B
B
DR
ES
IC
MI
MD
ML
CR
SCP
DC
K
?
?
?
?
DT
G
H
K
KP
LV
LM
MC
P
T
WP
D
OS
CM
D
WM
C
J
#
M
D
S
SP
F
CB
C
AUTO/MANUALNLETRANSFER SWITCH
xxA-xP
XX' xxxV WIRE WAY
XX' xxxV BUS DUCT
xxx KVA
xxxV x∅ xW PRI
Tx
xxxY/xxxV x∅ xW SEC
xxx KW
xxxV x∅
GENERATOR
G
DRAWING BLOCK TITLE
SCALE: 1/8" = 1'-0"
xxAF
yyAT
xxAF
yyAT
xxAF
yyAT
xxAF
yyAT
xxAF
yyAT
zzA
CT
zzA
zzA
zzA
K2
XX-XX-X-X
3
MO
PANEL
ST
1
GFCI
(3)
(3)
400-5A
AFD 3
xx-x-x
A1
E-401
A1
E-501
A1
E-301
GENERAL ELECTRICAL NOTES
E-000 GENERAL (SYMBOLS, ABBREVIATIONS, NOTES)
E-100 PLANS
E-200 ELEVATIONS
E-300 SECTIONS
E-400 LARGE SCALE VIEWS (PLANS, ELEVATIONS OR SECTIONS)
E-500 DETAILS
E-600 SCHEDULES OR DIAGRAMS
E-700 USER DEFINED
E-800 USER DEFINED
E-900 3D REPRESENTATIONS (ISOMETRICS)
GENERAL NOTES: NOTES THAT APPLY EQUALLY TO ALL DISCIPLINES
WITHIN THE DRAWING SET.
GENERAL
ELECTRICAL NOTES:
NOTES THAT APPLY EQUALLY TO ALL SHEETS WITHIN
THE DISCIPLINE.
GENERAL SHEET
NOTES:
NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET
ON WHICH THEY APPEAR.
SHEET KEYNOTES: NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET
ON WHICH THEY APPEAR AND USE A KEYNOTE
INDICATOR TO IDENTIFY ITEMS.
SECTION INDICATOR: REFERENCE SECTION LOCATION THROUGH AN AREA
FOR ADDITIONAL INFORMATION.
KEYNOTE INDICATOR: REFERENCE SHEET KEYNOTE LOCATION FOR
ADDITIONAL INFORMATION.
DETAIL INDICATOR: REFERENCE DETAIL LOCATION FOR ADDITIONAL
INFORMATION.
DRAWING BLOCK
TITLE INDICATOR:
REFERENCE DRAWING MODULE LOCATION FOR
ADDITIONAL INFORMATION.
MATCH LINE
INDICATOR:
REFERENCE SHEET LOCATION FOR ADDITIONAL
INFORMATION.
REVISION INDICATOR: REFERENCE TITLE BLOCK LOCATION FOR ADDITIONAL
INFORMATION.
LIGHTING INDICATOR: REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
"A" = FIXTURE TYPE, REFER TO FIXTURE SCHEDULE,
"2" = CIRCUIT NUMBER, "a" = SWITCH
IDENTIFICATION
G-000 GENERAL
A-000 ARCHITECTURAL
F-000 FIRE PROTECTION
P-000 PLUMBING
M-000 MECHANICAL
E-000 ELECTRICAL
SURFACE MOUNTED 2'x4' FIXTURE
SURFACE MOUNTED 2'x4' EMERGENCY FIXTURE
RECESSED MOUNTED 2'x4' FIXTURE
RECESSED MOUNTED 2'x4' EMERGENCY FIXTURE
SURFACE MOUNTED 1'x4' FIXTURE
SURFACE MOUNTED 1'x4' EMERGENCY FIXTURE
RECESSED MOUNTED 1'x4' FIXTURE
RECESSED MOUNTED 1'x4' EMERGENCY FIXTURE
SURFACE MOUNTED FIXTURE
SURFACE MOUNTED EMERGENCY FIXTURE
RECESSED MOUNTED FIXTURE
RECESSED MOUNTED EMERGENCY FIXTURE
POLE MOUNTED FIXTURE
POLE MOUNTED EMERGENCY FIXTURE
SUSPENDED FIXTURE
SUSPENDED EMERGENCY FIXTURE
WALL MOUNTED FIXTURE
WALL MOUNTED EMERGENCY FIXTURE
WALL MOUNTED FIXTURE
WALL MOUNTED EMERGENCY FIXTURE
LUMINAIRE STRIP TYPE FIXTURE (2 FOOT)
LUMINAIRE STRIP TYPE FIXTURE (3 FOOT)
LUMINAIRE STRIP TYPE FIXTURE (4 FOOT)
EXIT LIGHTING FIXTURE, ARROWS AND EXIT FACE AS
INDICATED ON DWGS (MOUNTING HEIGHTS TO BE
DETERMINED BY JOB SPECIFICATION
FIXTURE-DOUBLE OR SINGLE HEAD SPOT LIGHT
EMERGENCY BATTERY UNIT WITH LIGHTING HEADS
EMERGENCY BATTERY REMOTE LIGHTING HEADS
LIGHT TRACK, LENGTH AS INDICATED ON DWGS WITH
NUMBER OF LIGHTS INDICATED ON DWGS AND SCHEDULE
IN-GROUND OR FLOOR MOUNTED FIXTURE
SINGLE LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
SINGLE LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
SINGLE LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
TWIN LUMINAIRE POLE MOUNTED SITE LIGHTING FIXTURE
ROADWAY LUMINAIRE-COBRA HEAD
BOLLARD TYPE SITE LIGHTING FIXTURE
LIGHTING OR POWER PANEL, RECESSED
LIGHTING OR POWER PANEL, SURFACE
DISTRIBUTION PANEL
LIGHTING OR POWER PANEL ON NORMAL/GENERATOR
FEEDER
DISTRIBUTION PANEL ON NORMAL/GENERATOR FEEDER
MOTOR CONTROL CENTER (MCC)
DRY TYPE TRANSFORMER
TRANSFORMER-PAD MOUNT
CURRENT TRANSFORMER CABINET
GENERATOR
METER
METER AND SOCKET
TRANSFER SWITCH
FIRE ALARM MASTER BOX
FIRE FIGHTER'S PHONE
CODE TRANSMITTER
DRILL KEY SWITCH
KEY REPOSITORY (KNOX BOX)
FIRE ALARM ANNUNCIATOR PANEL, 2 LINES OF 4°
CHARACTERS LCD DISPLAY
FIRE ALARM CONTROL PANEL
VOICE EVACUATION PANEL
FIRE ALARM TERMINAL CABINET
BATTERY PACK AND CHARGER
AIR SAMPLING CONTROL/DETECTOR PANEL WITH
ASSOCIATED AIR SAMPLING PIPING NETWORK
TRANSPONDER
INDIVIDUALLY ADDRESSABLE MODULE- MONITOR
(PROVIDES ADDRESS FOR CONTACT)
INDIVIDUALLY ADDRESSABLE MODULE- RELAY (PROVIDES
CONTACT CLOSURE)
CONTROL RELAY
DOOR HOLDER WITH RELAY
HORN AND STROBE
HORN UNIT ONLY
STROBE UNIT ONLY
SPEAKER AND STROBE
MANUAL PULL STATION
SMOKE DETECTOR
DUCT SMOKE DETECTOR WITH TWO AUXILIARY CONTACTS
REMOTE STATION FOR DUCT DETECTOR USED AT DUCT
WORK OPENING
AREA TYPE SMOKE DETECTOR USED AT DUCT WORK
OPENING
ELEVATOR RECALL WITH AUXILIARY CONTACTS
SELF CONTAINED SMOKE DETECTOR-SINGLE STATION
TYPE
SMOKE DETECTOR-VISUAL AND AUDIBLE SIGNAL
BEAM SMOKE DETECTOR, "R"-INDICATES RECEIVER
BEAM SMOKE DETECTOR, "S" INDICATES SENDING UNIT
CARBON MONOXIDE DETECTOR. LINE VOLTAGE WITH
BATTERY BACKUP
FLAME DETECTOR
AUTOMATIC HEAT DETECTOR, "R" INDICATES RATE OF
RISE
AUTOMATIC HEAT DETECTOR, "F" INDICATES FIXED
TEMPERATURE 190°F
HYDROGEN DETECTOR
MOTOR OPERATED FIRE/SMOKE DUCT DAMPER
WATER FLOW SWITCH, BY DIVISION 15
LOW PRESSURE SWITCH, BY DIVISION 15
TAMPER SWITCH, BY DIVISION 15
POST INDICATOR VALVE, BY DIVISION 15
END-OF-LINE RESISTOR
DATA OUTLET
DATA OUTLET FLOOR TYPE
TELEPHONE/DATA OUTLET
TELEPHONE/DATA OUTLET FLOOR TYPE
TELEPHONE OUTLET
TELEPHONE OUTLET-WALL MOUNTED
TELEPHONE OUTLET FLOOR TYPE
CALL IN SWITCH
CABLE ANTENNA SYSTEM OUTLET (CATV)
MASTER ANTENNA SYSTEM OUTLET (MATV)
MICROPHONE OUTLET-FLOOR MOUNTED
MICROPHONE OUTLET-WALL MOUNTED
SPEAKER-CEILING MOUNTED
SPEAKER-WALL MOUNTED
SPEAKER HORN
SPEAKER BI-DIRECTIONAL PAGING-WALL MOUNTED
SPEAKER BI-DIRECTIONAL PAGING-CEILING MOUNTED
INTERCOM UNIT-FLUSH MOUNTED
MASTER INTERCOM AND DIRECTORY UNIT
VOLUME CONTROL
EQUIPMENT CABINET
EQUIPMENT RACK-WALL MOUNTED
EQUIPMENT RACK-FREE STANDING
TERMINAL CABINET WITH 3/4" PLYWOOD BACKING
PLYWOOD BACKBOARD
CCTV CAMERA "WP" INDICATES WEATHER-PROOF
EXTERIOR CAMERA
CCTV COAXIAL CABLE OUTLET AND POWER OUTLET
CCTV MONITOR OUTLET
DOORBELL
DOOR BUZZER
DOOR CHIME
ELECTRIC DOOR OPENER
ELECTRIC DOOR STRIKE
INTERCOM UNIT - FLUSH MOUNT
MASTER INTERCOM AND DIRECTORY UNIT
MOTION DETECTOR
SECURITY DOOR ALARM MAGNETIC LOCK
SECURITY CARD READER. "WP" INDICATES
WEATHER-PROOF
SECURITY CONTROL PANEL
SECURITY DOOR CONTACTS
SECURITY EXIT PUSH BUTTON
SECURITY KEYPAD
& AND EMT ELECTRICAL METALLIC TUBING OCP OVERCURRENT PROTECTION
∅ PHASE ETR EXISTING TO REMAIN OD OUTSIDE DIAMETER, OVERFLOW DRAIN
°F DEGREES FAHRENHEIT EWC ELECTRIC WATER COOLER OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
A/C AIR CONDITIONING EX EXISTING OL OVERLOAD
A AMPERES FCU FAN COIL UNIT OZ OUNCE
ACCU AIR COOLED CONDENSING UNIT FLR FLOOR P POLE, PHASE, PARALLEL
AF AMPERE FUSE FP FIRE PUMP PE PNEUMATIC ELECTRIC
AFC ABOVE FINISHED COUNTER FPVAV FAN POWERED VAV UNIT PF POWER FACTOR
AFF ABOVE FINISHED FLOOR FT FOOT, FEET PH PHASE
AFG ABOVE FINISHED GRADE FURN FURNACE PTAC PACKAGED TERMINAL AIR CONDITIONER
AHU AIR HANDLING UNIT G GROUND, GALLONS PVC POLYVINYL CHLORIDE CONDUIT/PIPE
AIC AMPERES INTERRUPTING CAPACITY GC GENERAL CONTRACTOR RCPT RECEPTACLE
AL ALUMINUM GFI GROUND FAULT INTERRUPTING REV REVOLUTIONS
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE GFCI GROUND FAULT CIRCUIT RGS RIGID GALVANIZED CONDUIT
ARCH ARCHITECT GRD GROUND RM ROOM
ATS AUTOMATIC TRANSFER SWITCH GND GROUND RPM REVOLUTIONS PER MINUTE
AVG AVERAGE HHWP HEATING HOT WATER PUMP RPS REVOLUTIONS PER SECOND
BAS BUILDING AUTOMATION SYSTEM HOA HAND-OFF-AUTOMATIC RTU ROOF TOP UNIT
B/I BYPASS ISOLATION HORIZ HORIZONTAL SF SQUARE FOOT
BE BOTTOM ELEVATION HP HORSEPOWER SPEC SPECIFICATION
BLDG BUILDING HR HOUR(S)SQ SQUARE
BMS BUILDING MANAGEMENT SYSTEM HRTU HEATING ONLY ROOFTOP UNIT ST SHUNT TRIP
BSMT BASEMENT Hz HERTZ STD STANDARD
C CONDUIT IAC INSTRUMENTATIONS AND CONTROLS SW SWITCH
CB CIRCUIT BREAKER ID INSIDE DIAMETER TBD TO BE DETERMINED
CBA COLOR BY ARCHITECT IN INCH, INCHES TBI TO BE INSTALLED
CCW COUNTERCLOCKWISE INT INTERIOR TBR TO BE REMOVED
CH CHILLER JP JOCKEY PUMP TC TEMPERATURE CONTROLS
CHWP CHILLED WATER PUMP K KELVIN, KEYED TCC TEMPERATURE CONTROLS CONTRACTOR
CLG CEILING kW KILOWATT TR TAMPER RESISTANT
CMT CONDUIT EMPTY KVA KILOVOLT AMPS TEMP TEMPERATURE
COMPR COMPRESSOR LBS POUNDS TF TRANSFER FAN
COND CONDENSER LSI, LSIG TRIP TYPE - LONG, SHORT, INSTANTANEOUS, GROUND FAULT TRANS TRANSITION
CONV CONVECTOR LTG LIGHTING TYP TYPICAL
CT COOLING TOWER MAX MAXIMUM UH UNIT HEATER
CU CONDENSING UNIT, COPPER MC MECHANICAL CONTRACTOR UON UNLESS OTHERWISE NOTED
CUH CABINET UNIT HEATER MCA MINIMUM CIRCUIT AMPS UV UNIT VENTILATOR
CUV CLASSROOM UNIT VENTILATOR MCC MOTOR CONTROL CENTER V VOLTS
CW CLOCKWISE MFR MANUFACTURER VAV VARIABLE AIR VOLUME
CWP CONDENSER WATER PUMP MIN MINIMUM VB VACUUM BREAKER
D DEDICATED CIRCUIT MISC MISCELLANEOUS VERT VERTICAL
DC DIRECT CURRENT MOP MAXIMUM OVERCURRENT PROTECTION VF VENTILATION FAN
DS DISCONNECT SWITCH MTD MOUNTED VFD VARIABLE FREQUENCY DRIVE
DWH DOMESTIC WATER HEATER MV MEDIUM VOLTAGE W WIRE, WATT
DWG DRAWING NA NOT APPLICABLE WP WEATHERPROOF
EA EACH NEC NATIONAL ELECTRIC CODE W/ WITH
EC ELECTRICAL CONTRACTOR NIC NOT IN CONTRACT W/O WITHOUT
EF EXHAUST FAN NL NIGHT LIGHT WSHP WATER SOURCE HEAT PUMP
EFF EFFICIENCY NOM NOMINAL
EL ELEVATION NTS NOT TO SCALE
SINGLE POLE SWITCH
SWITCH (EDIT AS NEEDED FOR 2-WAY, 3-WAY, a
SWITCH LEG ETC.
SWITCH (EDIT AS NEEDED FOR 2-WAY, 3-WAY, OR a
SWITCH LEG ETC.
CIRCUIT BREAKER SWITCH
SINGLE POLE/DOUBLE THROW SWITCH
GLOW SWITCH TOGGLE, GLOWS IN OFF POSITION
HORIZONTALLY MOUNTED-WITH ON POSITION TO THE LEFT
KEY OPERATED SWITCH
KEY OPERATED SWITCH WITH PILOT LIGHT ON WHEN
SWITCH IS ON
LOW VOLTAGE SWITCH
LOW VOLTAGE MASTER SWITCH
MOMENTARY CONTACT SWITCH
SWITCH WITH PILOT LIGHT ON WHEN SWITCH IS ON
TIMER SWITCH
WEATHERPROOF SINGLE POLE SWITCH
DIMMER SWITCH. RATED 1000W, UNLESS OTHERWISE
INDICATED. "LV" = LOW VOLTAGE "FL" = FLUORESCENT
OCCUPANCY SENSOR, WALL MOUNTED WITH OFF-AUTO
OVERRIDE SWITCH
OCCUPANCY SENSOR, CEILING MOUNTED, "2"-
INDICATES MULTIPLE SWITCHES WIRED IN PARALLEL
OCCUPANCY SENSOR, CEILING MOUNTED, "N"-
INDICATES NETWORKED DEVICE.
CUSTOMER METER
DEMAND METER (UTILITY)
WATTHOUR METER (UTILITY)
SINGLE CONVENIENCE RECEPTACLE
DUPLEX CONVENIENCE RECEPTACLE. 20A 125V. WALL
MOUNT DEVICE
DOUBLE DUPLEX CONVENIENCE RECEPTACLE.
DUPLEX RECEPTACLE. 20A 125V. HORIZONTAL WALL
MOUNT DEVICE.
SINGLE CONVENIENCE RECEPTACLE ON
EMERGENCY/STANDBY CIRCUIT
DUPLEX CONVENIENCE RECEPTACLE ON
EMERGENCY/STANDBY CIRCUIT
DOUBLE DUPLEX CONVENIENCE RECEPTACLE ON
EMERGENCY/STANDBY CIRCUIT
SPECIAL RECEPTACLE
CLOCK HANGER OUTLET RECESSED MOUNTED 8'-0"
AFF OR 8" BELOW CEILING AS INDICATED
MULTI-OUTLET ASSEMBLY
MULTI-OUTLET ASSEMBLY
FLOOR DUPLEX CONVENIENCE RECEPTACLE.
FLUSH MOUNT FLOOR BOX, ADJUSTABLE, WITH BOTH
POWER AND VOICE/DATA RECEPTACLES
JUNCTION BOX
MOTOR
PUSH-BUTTON
ON/OFF PUSH-BUTTON STATION
THREE FUNCTION PUSH-BUTTON SWITCH
(UP/DOWN/STOP)
MOTOR STARTER SWITCH
TOGGLE DISCONNECT SWITCH
THERMAL MOTOR SWITCH WITH HANDLE GUARD AND
PADLOCK CAPABILITY, "P"-INDICATES PILOT LIGHT
DISCONNECT SWITCH, UNFUSED TYPE
DISCONNECT SWITCH, FUSED TYPE
ENCLOSED CIRCUIT BREAKER
MAGNETIC CONTACTOR
MAGNETIC MOTOR STARTER
COMBINATION MAGNETIC STARTER AND DISCONNECT
SWITCH
PHASE, NEUTRAL, GROUND
PHASE, PHASE, NEUTRAL, GROUND
PHASE, PHASE, PHASE, NEUTRAL, GROUND
PHASE, PHASE, NEUTRAL, NEUTRAL, GROUND
PHASE, PHASE, GROUND
PHASE, PHASE, PHASE, GROUND
HOMERUN
PHASE, NEUTRAL, GROUND, HOMERUN
GROUND
CONNECTION
3/4"x10' COPPER GROUND ROD
CAPACITOR
CIRCUIT BREAKER (OPEN), "xxAF" INDICATES FRAME
SIZE, "yyAT" INDICATES TRIP SIZE
CIRCUIT BREAKER (ENCLOSED), "xxAF" INDICATES
FRAME SIZE, "yyAT" INDICATES TRIP SIZE
PRIMARY DRAW OUT TYPE CIRCUIT BREAKER, "xxAF"
INDICATES FRAM SIZE, "yyAT" INDICATES TRIP SIZE
LOW VOLTAGE DRAW OUT TYPE CIRCUIT BREAKER,
"xxAF" INDICATES FRAM SIZE, "yyAT" INDICATES TRIP
SIZE
LOW VOLTAGE DRAW OUT TYPE CIRCUIT BREAKER.
WITH CURRENT LIMITING FUSES, "xxAF" INDICATES
FRAME SIZE, "yyAT" INDICATES TRIP SIZE, "zzA"
INDICATES FUSE RATING
CONTACT NORMALLY OPEN (NO) ("TC"-WITH TIMED
CLOSING)
CONTACT NORMALLY CLOSED (NC) ("TO"-WITH TIMED
OPENING)
CURRENT TRANSFORMER CABINET
FUSED CUTOUTS, "zzA" INDICATES FUSE RATING
DISCONNECT SWITCH UNFUSED
DISCONNECT SWITCH AIR BREAK WITH FUSE,"zzA"
INDICATES FUSED RATING
FUSE, "zzA" INDICATES FUSED RATING
OVERLOAD RELAY
GROUNDING CONNECTION-SYSTEM AND OR EQUIPMENT
KIRK KEY INTERLOCK SYSTEM
LIGHTNING ARRESTER AND GROUNDING TO PROTECT ALL
PHASES
MOTOR AND LABEL, "3" DENOTES HORSEPOWER
MOTOR OPERATOR FOR CIRCUIT BREAKERS OR SWITCH
NETWORK PROTECTOR
PANEL BOARD
POTHEAD
STRESS CONE
RESISTOR
SHUNT TRIP
MAGNETIC STARTER WITH NEMA SIZE INDICATED
GROUND FAULT CIRCUIT INTERRUPTER, PERSONNEL
PROTECTION
GENERATOR
TRANSFORMER, DRY TYPE, UNLESS OTHERWISE
INDICATED
POTENTIAL TRANSFORMER, "3" INDICATES QUANTITY
CURRENT TRANSFORMER, "3" INDICATES QUANTITY,
"400-5A" INDICATED RATIO
3-PHASE, 3-WIRE DELTA CONNECTION
CORNER GROUNDED DELTA
3-PHASE, 4-WIRE WYE CONNECTION (GROUNDED
NEUTRAL)
ADJUSTABLE FREQUENCY DRIVE 3 REFERENCES DETAIL
NUMBER
BUS DUCT OR BUS WAY
WIRE WAY
TRANSFER SWITCH
SHEET TYPE DESIGNATORS
NOTATION DESIGNATORS
REFERENCE SYMBOLS
SUBSET DESIGNATORS
LIGHTING IDENTITY
SYMBOLS
DISTRIBUTION IDENTITY
SYMBOLS
FIRE ALARM COMM
IDENTITY SYMBOLS
FIRE ALARM IDENTITY
SYMBOLS
COMMUNICATION
IDENTITY SYMBOLS
SECURITY IDENTITY
SYMBOLS
ABBREVIATIONS AND TERMS
SWITCH IDENTITY
SYMBOLS
SWITCHBOARD METER
IDENTITY SYMBOLS
POWER IDENTITY
SYMBOLS
ONE-LINE IDENTITY
SYMBOLS
S
S
F
1 NOT ALL NOTES, DESIGNATORS, SYMBOLS OR ABBREVIATIONS MAY APPLY TO THIS PROJECTSEE E-102
REFER TO ADDITIONAL
SHEET FOR CONTINUATION
FLOOR PLAN OVERLAP BEYOND AREA
EXTENSION
PLAN
A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE
APPROXIMATE. ALL LOCATIONS SHALL BE FIELD VERIFIED.
B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL
ELECTRICAL CODE - LATEST EDITION ADOPTED BY INDIANA, THE
INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL/MUNICIPAL CODES,
AND THE AUTHORITY HAVING JURISDICTION.
C.ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR
VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT
LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN LENGTH.
D. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE
CONDUIT SEALING MATERIAL.
E. ALL CABLE SIZES SHALL UTILIZE COPPER CONDUCTORS.
F.FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN
ROUTING CONDUIT. ALL CONDUITS CROSSING EXPANSION JOINTS
SHALL BE INSTALLED WITH EXPANSION FITTINGS. EXPANSION
FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND
MANUFACTURER'S WRITTEN RECOMMENDATIONS.
G.FEEDERS FROM PANEL BOARDS BACK TO MAIN SWITCHBOARD,
BETWEEN AUTO TRANSFER SWITCHES AND THEIR SOURCES/LOADS,
BETWEEN DRY-TRANSFORMERS AND THEIR SOURCES/LOADS. ARE NOT
INDICATED ON THE FLOOR PLAN DRAWINGS. FEEDERS ARE PART OF THE
WORK, AND SHALL BE SIZED AS INDICATED ON THE ONE LINE DIAGRAM.
H.CABLE TRAY IS SHOWN ON THE PLANS. IF PORTIONS OF CABLE
TRAY CANNOT BE INSTALLED DUE TO CONFLICT WITH STRUCTURE
OR OTHER EQUIPMENT, THE CONTRACTOR SHALL PROVIDE (2) 4" C.
WITH INSULATED BUSHINGS THAT OVERLAP 1" INTO THE TRAY TO
AVOID CONFLICTS IN THESE LOCATIONS.
I.HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS
SHOWN ON THE CONTRACT DRAWINGS. SINGLE PHASE BRANCH
CIRCUIT HOME RUNS MAY BE COMBINED AT THE CONTRACTOR'S
DISCRETION NOT GREATER THAN (3) PHASE CONDUCTORS, (3)
NEUTRAL CONDUCTORS, AND A GROUNDING CONDUCTOR.
J. EACH SINGLE PHASE BRANCH CONDUCTOR SHALL HAVE A
DEDICATED NEUTRAL BACK TO THE PANEL.
K.CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL
USE LINK-SEALS.
L.WHERE LOW VOLTAGE (CONTROL) CABLING IS ALLOWED TO BE
INSTALLED WITHOUT A RACEWAY, IT SHALL BE SUPPORTED PER
SECTION 260523 NOT EXCEEDING INTERVALS OF 48 INCHES, AND
NOT MORE THAN 6 INCHES FROM CABINETS, BOXES, FITTINGS,
OUTLETS, RACKS, FRAMES AND TERMINALS.
A
a 2
DRAWING MODULE LOCATION
(IDENTIFYING LOWER LEFT OF MULTIPLE MODULES)
NUMERIC SCALE NORTH ARROW
SECTION LOCATION
IN DRAWING MODULE
SECTION LOCATION AT SUBSET SHEET
PLAN
BEYOND AREA
EXTENSION
DETAIL LOCATION IN
DRAWING MODULE
DETAIL LOCATION AT
SUBSET SHEET
LARGE SCALE VIEW
LOCATION IN DRAWING
MODULE
LARGE SCALE VIEW
LOCATION AT SUBSET SHEET
REVISION CLOUD
REVISION INDICATOR
11 1
KEYNOTE INDICATORS
AREA LEADER
LINE LEADER
POINT LEADER
NUMERICAL CHARACTER
RELATES TO ITEM
CLNG. WALL
CLNG. WALL
CLNG. WALL
A1
OS
2
OS
N
H
S
F S
N
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:07:09 PME000
ELECTRICAL
SYMBOLS AND
ABBREVIATIONS
16071.001
SJB
JAS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
FACP
J
J
CA.REMOVE ALL EXISTING LIGHT FIXTURES AND ASSOCIATED CONTROLS. PARABOLIC
FIXTURES TO BE RE-USED FOR NEW CONSTRUCTION.
B.REMOVE ALL ELECTRICAL DEVICES FROM DEMOLITION WALLS.
C.CONTRACTOR SHALL CONTINUE CONTINUITY OF EXISTING BRANCH CIRCUITS WHERE
EXISTING RECEPTACLES ARE BEING REMOVED.
D.ALL EXISTING ELECTRICAL PANELS ARE TO REMAIN EXCEPT WHERE NOTED
OTHERWISE.
E.REMOVE ALL ABANDONED RACEWAYS AND CABLING FROM ABOVE CEILING.
GENERAL SHEET NOTES
LOUNGE
111
OFFICE
105
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
122
OFFICE
123
OFFICE
124
CONFERENCE
116
I.T.
107
JAN. / SUPPLY
199
MEN (EXIST.)
198
WOMEN (EXIST.)
197
EXISTING STAIR
196
EXISTING STAIR
190
STOR.
113
EXISTING BLDG.
TRANSFORMER
195
EXISTING BLDG.
STOR.
193
EXISTING BLDG.
PHONE
191
EXISTING BLDG.
ELECT.
192
STORAGE
101A
EXISTING
ELEVATOR
189
LOBBY
101
ENTRY
VESTIBULE
100
EXISTING
SECONDARY
ENTRY
VESTIBULE
?
OFFICE
121
OFFICE
117
OFFICE
114
ADJACENT
TENANT SPACE
?
ADJACENT
TENANT SPACE
?
EXISTING
CORRIDOR
?
Office
?Office
?
ENTRY AREA
101C
HALL
101D
HALL
125
CLOSET
103A
U.H.
U.H.
1
2
LP2
LP1
3
4
EWH
5
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:07:12 PMED101
ELECTRICAL
DEMOLITION PLAN
16071.001
SJB
JAS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
ELECTRICAL FIRST FLOOR DEMOLITION PLAN1
SHEET KEYNOTES
1 CONTROL PANELS FOR DRIVE-THRU SYSTEM TO REMAIN PULL BACK LOW
VOLTAGE WIRING AND LEAVE COILED UP ABOVE CEILING.
2 CONTRACTOR TO FIELD VERIFY CIRCUITS THAT NEED TO REMAIN IN
LIGHTING PANELS LP1 AND LP2. REMOVE WIRE AND RACEWAY FOR
DEMOLISHED CIRCUITS BACK TO THE FIRST JUNCTION BOX. REMOVE WIRING
FOR UNUSED CIRCUITS BACK TO PANEL AND MARK BREAKER AS SPARE.
PROVIDE NEW PRINTED PANEL SCHEDULES UPON COMPLETION OF WORK.
3 LEAVE VAULT EMERGENCY INTERFACE SYSTEM IN PLACE.
4 HOT WATER HEATER TO BE RELOCATED. REMOVE CIRCUIT BACK TO FIRST
JUNCTION BOX AND REROUTE TO NEW LOCATION ABOVE MENS RESTROOM.
RE-USE DISCONNECT IF IN ACCEPTABLE CONDITION. SEE POWER PLANS FOR
NEW LOCATION.
5 BUNDLE COMMUNICATION AND LOW VOLTAGE CABLING TO REMAIN AND
SUPPORT UTILIZING J-HOOK SUPPORTS.
M
M
M
M
M
M
M
MM
M
MMMM
M
MMMM
M
A.REFER TO SHEET E000 FOR SYMBOLS AND ABREVIATIONS.
B.REFER TO SHEET E601 FOR LIGHT FIXTURE SCHEDULE.
C.REFER TO SHEET E501 FOR LIGHTIING DETAILS.
D.CONDUIT SYSTEM FOR LIGHTING CIRCUITS SHALL BE IN EMT WITH FLEX CONNECTION TO
LIGHT FIXTURES. FLEXIBLE CODUIT SHALL ONLY BE ALLOWED FROM A JUNCTION BOX TO A
FIXTURE. FIXTURE TO FIXTURE FLEX CONDUIT WILL NOT BE ALLOWED. ALL HOMERUNS TO
PANEL SHALL BE 3/4" EMT CONDUIT. 1/2" EMT CONDUIT SHALL ONLY BE USED ABOVE ROOM
SERVED.
E.ALL JUNCTION BOXES ABOVE CEILIING SHALL BE MARKED WITH PANEL AND CIRCUIT
NUMBERS ROUTING THROUGH BOX.
F.CONTRACTOR SHALL COORDINATE ALL LIGHT FIXTURE LOCATIONS WITH MECHANICAL
CONTRACTOR PRIOR TO ROUGH-IN TO AVOID CONFLICTS OF SPACE ABOVE THE CEILING.
G.ALL LIGHT FIXTURES MARKED (NL) NIGHT LIGHT SHALL HAVE AN EMERGENCY BATTERY
INVERTER BALLAST. THE EMERGENCY BALLAST SHALL CONNECT TO THE NONSWITCHED
LEG OF THE ROOM LIGHTING CIRCUIT. REFER TO DETAILS ON SHEET E501.
H.RACEWAY TO POWER RECEPTACLES SHALL BE EMT WITHIN CAVITY OF WALL. MC CABLE
FROM WALL BOX TO JUNCTION BOX ABOVE CEILING IS ACCEPTABLE.
I.REWORK LIGHTING CIRCUIT(S) FROM EXISTING PANEL LP2. VERIFY EXISTING CIRCUIT AND
LOAD PRIOR TO INSTALLATION.
J.REWORK BRANCH CIRCUITS FROM EXISTING PANEL LP1/LP2 AS NECESSARY TO
ACCOMOADATE NEW RECEPTACLE LAYOUT. CIRCUITS SHALL BE FIELD DETERMINED BY
CONTRACTOR. CIRCUIT NUMBERS SHOWN ARE FOR GROUPING PURPOSES ONLY.
K.FACE PLATE AND DEVICES SHALL MATCH EXISTING DEVICES AND FACEPLATE COLOR IN
ADJACENT SPACES.
GENERAL SHEET NOTES
L1
LP2- 2 L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
L1
LP2- 2
1
1 1 1 1
1
1
1
1
1
1
1
1
1
1 1
1
1
1
1 1
1
1
LOUNGE
111
SUPPLIES
108
MEN
109
WOMEN
110
OFFICE
105
OFFICE
103
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
120
OFFICE
119
OFFICE
122
OFFICE
123
OFFICE
124
OFFICE
115
CONFERENCE
116
I.T.
107
JAN. / SUPPLY
199
MEN (EXIST.)
198
WOMEN (EXIST.)
197
EXISTING STAIR
196
EXISTING STAIR
190
STOR.
113
EXISTING BLDG.
TRANSFORMER
195
EXISTING BLDG.
STOR.
193
EXISTING BLDG.
PHONE
191
EXISTING BLDG.
ELECT.
192
STORAGE
101A
ADMIN. ASST.
101F
RECEPTIONIST
101H
EXISTING
ELEVATOR
189
HALL
101B
LOBBY
101
ENTRY
VESTIBULE
100
EXISTING
SECONDARY
ENTRY
VESTIBULE
?
OFFICE
118
OFFICE
121
OFFICE
117
OFFICE
114
ADJACENT
TENANT SPACE
?
ADJACENT
TENANT SPACE
?
EXISTING
CORRIDOR
?
ENTRY AREA
101C
HALL
101D
HALL
125
ADMIN. ASST.
101G
CLOSET
103A
CORRIDOR
101E
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 3
L1
LP2- 5
L1
LP2- 5
L1
LP2- 4
L1
LP2- 4
L1
LP2- 4
L1
LP2- 4
L1
LP2- 5
L1
LP2- 5L1
LP2- 5
L1
LP2- 4
L1
LP2- 4
L1
LP2- 5
L1
LP2- 5
L1
LP2- 1
L1
LP2- 5
L1
LP2- 5
L1
LP2- 5
L1
LP2- 1
L1
LP2- 5
L1
LP2- 5
L1
LP2- 5
L1
LP2- 4
L1
LP2- 4
L1
LP2- 4
L1
LP2- 4
L1
LP2- 4
L2
LP2- 5
L2
LP2- 1
L1
LP2- 4
L2
LP2- 6
L2
LP2- 1
L2
LP2- 5
L5
LP2- 5
L5
LP2- 5
L5
LP2- 5
L5
LP2- 5
L1
LP2- 6
L1
LP2- 6
L1
LP2- 6
L1
LP2- 1
L1
LP2- 6
L1
LP2- 6
L1
LP2- 3
L1
LP2- 3
2
2
2
2
2
L2
LP2- 6
L2
LP2- 6
L2
LP2- 7
L2
LP2- 6
L2
LP2- 6
L2
LP2- 7
L2
LP2- 1
L2
LP2- 7
L2
LP2- 6
L2
LP2- 1
L3
LP2- 7
L3
LP2- 7
L3
LP2- 7
L3
LP2- 7
L2
LP2- 1
L2
LP2- 1
L2
LP2- 6
L2
LP2- 6
L2
LP2- 6
L2
LP2- 6
L2
LP2- 6
L2
LP2- 6
L2
LP2- 7
L2
LP2- 7
L2
LP2- 7
L2
LP2- 7
L2
LP2- 7
L2
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
L4
LP2- 7
X1
LP2- 1
X2
LP2- 1
X1
LP2- 1
X2
LP2- 1
L2
LP2- 6
L2
LP2- 1
L2
LP2- 1
L2
LP2- 6
3
3 3
3
3
3 3
(ETR)
(ETR)
(ETR)
4
5
L6
LP2- 4
L4
LP2- 6
L4
LP2- 6
L4
LP2- 6
L4
LP2- 6
LIGHTING
CONTROL
PANEL
ENTRY VESTIBULE 100
LOBBY / MAIN CORRIDOR
HALL 126
M S
HALL 126
OCC
SENSOR
CORRIDOR 101E
OVERIDE
SWITCH
SEQUENCE
•HALL 126 LIGHTS CONTROLLED BY HALL 126 OCC SENSOR.
•VESTIBULE LIGHTS SET ON TIME CLOCK (COORDINATE ON/OFF
TIMES WITH OWNER)
•LOBBY AND MAIN CORRIDOR LIGHTS ON TIME CLOCK (COORDINATE
ON/OF TIMES WITH OWNER)
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/14/2017 10:39:10 AMEL101
ELECTRICAL
LIGHTING FLOOR
PLAN
16071.001
SJB
JAS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
SHEET KEYNOTES
1 CONNECT LIGHTING TO EXISTING CIRCUIT WITHIN THIS AREA. PROVIDE NEW
LIGHTING CONTROL SHOWN AND REWORK EXISTING WIRING. VERIFY
EXISTING PANEL AND CIRCUIT PRIOR TO INSTALLATION.
2 FIXTURE USED AS AN EMERGECY LIGHT. ADD EMERGENCY BACKPACK TO
REPURPOSED FIXTURE AS NEEDED. CONTRACTOR TO FIELD VERIFY
EXISTING BATTERY PACK COUNT BEFORE PURCHASING NEW.
3 FIXTURE USED AS AN EMERGECY LIGHT. PURCHASE FIXTURE WITH
EMERGENCY BATTERY PACK.
4 OVERIDE SWITCH FOR LIGHTING CONTROL SYSTEM
5 PROVIDE LIGHTING CONTROL SYSTEM FOR ALL FIXTURES LOCATED WITHIN
AREA ENCLOSED BY DASH LINES. SEE DETAIL 2 FOR SEQUENCE OF
OPERATION.
1/4" = 1'-0"
FIRST FLOOR LIGHTING PLAN1
1 1/2" = 1'-0"
LIGHTING CONTROL SYSTEM2
DWFACP
J
J
C
SSFS D
F
F
F
F S
F
FS FF
F
FF
A.REFER TO SHEET E000 FOR SYMBOLS AND ABREVIATIONS.
B.REFER TO SHEET E601 FOR LIGHT FIXTURE SCHEDULE.
C.REFER TO SHEET E501 FOR LIGHTIING DETAILS.
D.CONDUIT SYSTEM FOR LIGHTING CIRCUITS SHALL BE IN EMT WITH FLEX
CONNECTION TO LIGHT FIXTURES. FLEXIBLE CODUIT SHALL ONLY BE ALLOWED
FROM A JUNCTION BOX TO A FIXTURE. FIXTURE TO FIXTURE FLEX CONDUIT WILL
NOT BE ALLOWED. ALL HOMERUNS TO PANEL SHALL BE 3/4" EMT CONDUIT. 1/2"
EMT CONDUIT SHALL ONLY BE USED ABOVE ROOM SERVED.
E.ALL JUNCTION BOXES ABOVE CEILIING SHALL BE MARKED WITH PANEL AND
CIRCUIT NUMBERS ROUTING THROUGH BOX.
F.CONTRACTOR SHALL COORDINATE ALL LIGHT FIXTURE LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN TO AVOID CONFLICTS OF SPACE
ABOVE THE CEILING.
G.ALL LIGHT FIXTURES MARKED (NL) NIGHT LIGHT SHALL HAVE AN EMERGENCY
BATTERY INVERTER BALLAST. THE EMERGENCY BALLAST SHALL CONNECT TO THE
NONSWITCHED LEG OF THE ROOM LIGHTING CIRCUIT. REFER TO DETAILS ON
SHEET E501.
H.RACEWAY TO POWER RECEPTACLES SHALL BE EMT WITHIN CAVITY OF WALL. MC
CABLE FROM WALL BOX TO JUNCTION BOX ABOVE CEILING IS ACCEPTABLE.
I.REWORK LIGHTING CIRCUIT(S) FROM EXISTING PANEL PP2. VERIFY EXISTING
CIRCUIT AND LOAD PRIOR TO INSTALLATION.
J.REWORK BRANCH CIRCUITS FROM EXISTING PANEL PP1 AS NECESSARY TO
ACCOMOADATE NEW RECEPTACLE LAYOUT. CIRCUITS SHALL BE FIELD
DETERMINED BY CONTRACTOR. CIRCUIT NUMBERS SHOWN ARE FOR GROUPING
PURPOSES ONLY.
K.REUSE EXISTING TELECOMMUNICATIONS CABLING TO ACCOMODATE NEW LAYOUT.
TERMINATE TWO(2) AT EACH OUTLET UNLESS NOTED OTHERWISE.
L.FACE PLATE AND DEVICES SHALL MATCH EXISTING DEVICES AND FACEPLATE
COLOR IN ADJACENT SPACES.
M.NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE TO EXISTING SYSTEM.
N.NO JUNCTION BOXES ARE TO BE LOCATED ABOVE SOLID CEILINGS.
GENERAL SHEET NOTES
LOUNGE
111
SUPPLIES
108 ?
?
WOMEN
110
OFFICE
105
OFFICE
103
OFFICE
104
TELLERS
102
WORK ROOM
106
OFFICE
120
OFFICE
119
OFFICE
122
OFFICE
123
OFFICE
124
OFFICE
115
CONFERENCE
116
I.T.
107
JAN. / SUPPLY
199
MEN (EXIST.)
198
WOMEN (EXIST.)
197
EXISTING STAIR
196
EXISTING STAIR
190
STOR.
113
EXISTING BLDG.
TRANSFORMER
195
EXISTING BLDG.
STOR.
193
EXISTING BLDG.
PHONE
191 EXISTING BLDG.
ELECT.
192
STORAGE
101A
ADMIN. ASST.
101F
RECEPTIONIST
101H
EXISTING
ELEVATOR
189
HALL
101B
LOBBY
101
ENTRY
VESTIBULE
100
EXISTING
SECONDARY
ENTRY
VESTIBULE
?
OFFICE
118
OFFICE
121
OFFICE
117
OFFICE
114
ADJACENT
TENANT SPACE
?
ADJACENT
TENANT SPACE
?
EXISTING
CORRIDOR
?
ENTRY AREA
101C
HALL
101D
HALL
125
ADMIN. ASST.
101G
CLOSET
103A
CORRIDOR
101E
+44"
+44"
+44"
+44"
+44"
+44"
+44"
+44"
+44"
GFI
+44"
GFI
+44"
+44"
+44"
GFI
+44"
GFI
+44"
MICRO
+44"
MICRO
+44"
DISH.
LP1 - 1
+60
1
LP1 - 2
LP1 - 3
LP1 - 4
2
3
LP1 - 5
LP1 - 6
LP1 - 7
LP1 - 8
LP1 - 9
LP1 - 10
LP1 - 11
LP1 - 12
LP1 - 13
LP1 - 18
LP1 - 20
LP1 - 22
LP1 - 23
LP1 - 24
LP1 - 19
+60 +60
LP1 - 21
LP1 - 16
LP1 - 15
LP1 - 14
LP1 - 17
4
DISP.LP1 - 25
5
LP1 - 26
6
LP1 - 27
7
+60
+60
EX. PANEL
LP2
EX. PANEL
LP1
EX. DIST.
MDP
2
EP101
Sim
RP-1
RP-1 RP-1
LP1 - 28
LP1 - 29
LP1 - 30
EF-1
LP1 -
31,33,35
EDC-1
8
MULTI-SERVICE
FLOOR BOX
MULTI-SERVICE
WALL BOX
ACCESS WALL BOX
WITH BLANK COVER
SWITCH TO EMT AFTER
ACCESS BOX
(1) 1-1/2" CONDUIT FOR AV CABLING
(1) 3/4" CONDUIT FOR POWER CIRCUIT
USE SCHEDULE 40 PVC UNDERGROUND1' - 6"5' - 0"CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/14/2017 10:42:26 AMEP101
ELECTRICAL POWER
AND SYSTEMS
FLOOR PLAN
16071.001
SJB
JAS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
1/4" = 1'-0"
ELECTRICAL FIRST FLOOR POWER AND SYSTEMS PLAN1
SHEET KEYNOTES
1 SAW CUT FLOOR AND INSTALL 1-1/2" EMBEDDED CONDUIT FOR VIDEO
CABLING AND 3/4" CONDUIT FOR POWER CIRCUITS FROM FLOOR BOX AND
STUB UP INSIDE WALL. SEE SECTION 1 FOR MORE DETAILS.
2 SAW CUT FLOOR AND INSTALL 2" EMBEDDED CONDUIT FOR DATA CABLES TO
RECEPTIONISTS' CUBICLES
3 SAW CUT FLOOR AND INSTALL 1" EMBEDDED CONDUIT FOR POWER CIRCUITS
TO RECEPTIONISTS' CUBICLES
4 G.C. TO PUNCH NEW ACCESS DUCT THROUGH VAULT WALL. ROUTE ALL
ELECTRICAL TO NEW BREAK ROOM THROUGH DUCT. COORDINATE WITH G.C.
FOR EXACT LOCATION.
5 SAW CUT FLOOR AND INSTALL 1-1/2" EMBEDDED CONDUIT FROM FLOOR BOX
AND STUB UP INSIDE WALL FOR VIDEO CABLES.
6 CONFIRM THAT A DUCT DETECTOR IS PRESENT ON THE RETURN OF THE
ROOFTOP UNIT AND THAT IS INSTALLED ACCORDING TO MANUFACTURERS
RECOMENDATIONS. IF NO DETECTOR EXISTS, SUPPLY AND INSTALL NEW
DETECTOR.
7 PROVIDE POWER CIRCUIT TO IN-LINE EXHAUST FAN SERVICING RESTROOMS
LOCATED ABOVE CEILING.
8 PROVIDE POWER TO ELECTRIC COIL HEATER LOCATED ABOVE CEILING
3/8" = 1'-0"
Floor Box Detail2
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
3/10/2017 5:07:23 PME-601
ELECTRICAL
SCHEDULES
16071.001
SJB
JAS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
LIGHT SOURCE DRIVER/BALLAST INSTALLATION
LIGHTING FIXTURE SCHEDULE
FIXTURE
TYPE DESCRIPTION LUMENS COLOR
LAMP
TYPE EFFICACY WATTS BALLAST VOLTS MOUNTING MANUFACTURER Count
L1 2'x4' PARABOLIC (EXISTING TO BE RE-USED) 8256 lm 3500 K T8 86 lm/W 96 W N/A 120V GRID N/A 60
L2 4" RECESSED CAN LIGHT 1189 lm 3500 K LED 93 lm/W 13 W ELECTRONIC
(0-10V DIM.)
120V RECESSED GOTHAM (EVO R 4) 33
L3 6" PENDANT CAN LIGHT 1573 lm 3500 K LED 85 lm/W 19 W ELECTRONIC
(0-10V DIM.)
120V SUSPENDED GOTHAM (EVO CYL 6) 4
L4 COVE STRIP LIGHT 1156 lm 3500 K LED 76 lm/W 15 W ELECTRONIC
(0-10V DIM.)
120V WALL COOPER (IO .75) 25
L5 LINEAR WALL WASH 1219 lm 3500 K LED 53 lm/W 23 W ELECTRONIC
(0-10V DIM.)
120V WALL FOCAL POINT (TRACE) 4
L6 LED STRIP LIGHT 2151 lm 3500 K LED 115 lm/W 19 W ELECTRONIC
(0-10V DIM.)
120V SURFACE LITHONIA (WL4) 1
X1 DIECAST LED EXIT SIGN (GREEN)LED 120V CEILING LITHONIA (LE) 4
X2 DIECAST LED EXIT SIGN (GREEN)LED 120V WALL LITHONIA (LE) 3
CONTRACTOR TO FIELD VERIFY ALL EXISTING CIRCUITS TO REMAIN AND BALANCE PANEL ACCORDINGLY. PROVIDE NEW PRINTED PANEL SCHEDULE FOR PANEL DOOR UPON COMPLETION
OF WORK.
Notes:
R 0 VA 0.00% 0 VA Total Est. Demand:80 A
Other 26940 VA 100.00% 26940 VA Total Conn.:80 A
Heating 54 VA 100.00% 54 VA Total Est. Demand:28644 VA
HVAC 0 VA 0.00% 0 VA Total Conn. Load:28644 VA
Appliance - Dwelling Unit 1650 VA 100.00% 1650 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:92 A 66 A 85 A
Total Load:10768 VA 7978 VA 9898 VA
41 42
39 40
37 38
35 ---- --18 VA 36
33 ---- -- 18 VA 34
31 COIL HEATER EDC-1 20 A 3 18 VA 32
29 114 RADIANT PANEL 20 A 1 380 VA 380 VA 1 20 A 115 RADIANT PANEL 30
27 RESTROOM EXHAUST FAN 20 A 1 0 VA 380 VA 1 20 A 117 RADIANT PANEL 28
25 GARBAGE DISPOSAL 20 A 1 1000... 1650...1 30 A WATER HEATER 26
23 OFFICE 105 & WRR RECEPTACLES 20 A 1 1660... 1440... 1 20 A SUPPLIES & MRR RECEPTACLES 24
21 IT EQUIPMENT 20 A 1 180 VA 1260... 1 20 A IT ROOM RECEPTACLES 22
19 LOBBY RECEPTACLES 20 A 1 720 VA 1440...1 20 A WORK ROOM RECEPTACLES 20
17 LOUNGE REFRIGERATOR 20 A 1 180 VA 1080... 1 20 A LOUNGE RECEPTACLES 18
15 LOUNGE MICROWAVE 20 A 1 1000... 1000... 1 20 A LOUNGE DISHWASHER 16
13 TELLER RECEPTACLES 20 A 1 1880... 1000...1 20 A LOUGE MICROWAVE 14
11 OFFICE 117 RECEPTACLES 20 A 1 720 VA 1520... 1 20 A OFFICE 103&104 RECEPTACLES 12
9 STOR. 113 COPIER 20 A 1 180 VA 1260... 1 20 A OFFICE 118&121 RECEPTACLES 10
7 VESTIBUILE 100 & OFFICE 120 RECEPTACLES 20 A 1 720 VA 180 VA 1 20 A STORAGE 101A COPIER 8
5 CUBICLE 101F&WALL RECEPTACLES 20 A 1 1440... 1080... 1 20 A CUBICLE 101H&101G RECEPTACLES 6
3 OFFICE 123&124 RECEPTACLES 20 A 1 1440... 1260... 1 20 A OFFICE 119&122 RECEPTACLES 4
1 OFFICE 114 & 115 RECEPTACLES 20 A 1 1080... 1080...1 20 A CONFERENCE ROOM RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Recessed Wires:4 Mains Rating:100 A
Supply From:Phases:3 Mains Type:
Location:EXISTING BLDG. PHONE 191 Volts:120/208 Wye A.I.C. Rating:
Branch Panel: LP1
CONTRACTOR TO FIELD VERIFY ALL EXISTING CIRCUITS TO REMAIN AND BALANCE PANEL ACCORDINGLY. PROVIDE NEW PRINTED PANEL SCHEDULE FOR PANEL DOOR UPON COMPLETION
OF WORK.
Notes:
Total Est. Demand:22 A
Total Conn.:18 A
L 0 VA 0.00% 0 VA Total Est. Demand:7998 VA
Other 0 VA 100.00% 0 VA Total Conn. Load:6398 VA
Lighting 6398 VA 125.00% 7998 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:15 A 22 A 16 A
Total Load:1834 VA 2607 VA 1957 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 LOBBY, CORRIDOR, RECEPTION LIGHITNG 20 A 1 394 VA 8
5 101B, 102, 105, 108-111 LIGHTS 20 A 1 1416... 541 VA 1 20 A CORRIDOR LIGHITING 6
3 ROOMS 101D, 114-118, AND 121 LIGHTS 20 A 1 1440... 1167... 1 20 A ROOMS 103, 104, 106, 107 LIGHTS 4
1 EMERGENCY LIGHTING 20 A 1 288 VA 1152...1 20 A 101A, 119-124 LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Recessed Wires:4 Mains Rating:100 A
Supply From:Phases:3 Mains Type:
Location:EXISTING BLDG. PHONE 191 Volts:120/208 Wye A.I.C. Rating:
Branch Panel: LP2