HomeMy WebLinkAboutAddendum 2RATIO ARCHITECTS, INC. ADDENDUM NO. 2 – PAGE 1
BUSEY BANK TENANT IMPROVEMENT INDY
04/11/2017 BUSEY BANK TENANT IMPROVEMENT INDY 16071.000
ADDENDUM NO. 1
DATE: April 11, 2017
PROJECT: BUSEY BANK TENANT IMPROVEMENT INDY
RATIO PROJECT NUMBER: 16071.000
OWNER: First Busey Corporation
ARCHITECT:
RATIO ARCHITECTS, INC.
301 N. Neil Street
Suite 102
Champaign, IL 61820
217-352-7696
KBSO Consulting
1344 S. Rangeline Road
Suite 202
Carmel, IN 46031
317-344-8046
This Addendum is issued in accordance with the provisions of The General Conditions of the Contract for
Construction, Article 1 Contract Documents, and becomes a part of the Contract Documents as provided therein.
The information contained herein modifies the original Bidding Documents dated 03.13.2017. Requirements of the
original Bidding Documents and previous Addenda remain in effect except as modified by this Addendum.
Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject the
Bidder to disqualification.
PART 1 – PROJECT MANUAL CHANGES
1. n/a
PART 2 – DRAWING CHANGES
1. SHEET E-601 – ELECTRICAL SCHEDULES
a. Light fixture schedule has been revised. Replace existing sheet with new attached sheet.
PART 3 – CLARIFICATIONS
1. n/a
PART 4 – ATTACHMENTS
1. Drawing E-601 – ELECTRICAL SCHEDULES.
END OF ADDENDUM NO. 2
CHECKED BY
APPROVED BY
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO
ARCHITECTS, INC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT
OF RATIO ARCHITECTS, INC. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND
OTHERWISE ARE HEREBY SPECIFICALLY
RESERVED.
SHEET TITLE
SHEET NUMBER
First Busey Corporation
201 W. Main St.
Urbana, Illinois 61801
(217) 365-4500
Owner
RATIO Architects, Inc.
Architect
301 North Neil Street, Suite 102
Champaign, Illinois 61820
(217) 352-7696
Mech / Elec / Plumbing / FP Engineer
KBSO Consulting, Inc.
1344 S. Rangeline Rd.
Indianapolis, Indiana 46032
(317) 973 0874
PROJECT NO.
REISSUE
ISSUE FOR REVIEW / BID
03.13.2017
4/11/2017 11:00:17 AME-601
ELECTRICAL
SCHEDULES
16071.001
SJB
JAS
Busey Bank
Tenant
Improvement Indy
11550 N. Meridian
Street
Carmel, IN 46032
LIGHT SOURCE DRIVER/BALLAST INSTALLATION
LIGHTING FIXTURE SCHEDULE
FIXTURE
TYPE DESCRIPTION LUMENS COLOR
LAMP
TYPE EFFICACY WATTS BALLAST VOLTS MOUNTING MANUFACTURER EQUAL MANUFACTURER Count
L1 2'x4' PARABOLIC (EXISTING TO BE RE-USED) 8256 lm 3500 K T8 86 lm/W 96 W N/A 120V GRID N/A 60
L2 4" RECESSED CAN LIGHT 1189 lm 3500 K LED 93 lm/W 13 W ELECTRONIC
(0-10V DIM.)
120V RECESSED GOTHAM (EVO R 4) PORTFOLIO (LD4B), VANTAGE
(A4VOCLED)
33
L3 6" PENDANT CAN LIGHT 1573 lm 3500 K LED 85 lm/W 19 W ELECTRONIC
(0-10V DIM.)
120V SUSPENDED GOTHAM (EVO CYL
6)
PORTFOLIO (LSR6B 15),
VANTAGE (VP614LED)
4
L4 COVE STRIP LIGHT 1156 lm 3500 K LED 76 lm/W 15 W ELECTRONIC
(0-10V DIM.)
120V WALL LUMINII (KENDO S) ACCLAIM (ACE) 25
L5 LINEAR WALL WASH 1219 lm 3500 K LED 53 lm/W 23 W ELECTRONIC
(0-10V DIM.)
120V WALL FOCAL POINT
(FOCUS)
ALW (HYMGR), MARK (SPR
LED)
4
L6 LED STRIP LIGHT 2151 lm 3500 K LED 115 lm/W 19 W ELECTRONIC
(0-10V DIM.)
120V SURFACE LITHONIA (WL4) METALUX SW LED, CREE (LS) 1
X1 DIECAST LED EXIT SIGN (GREEN)LED 120V CEILING LITHONIA (LE) SURE-LITES (CX), MULE (MD B
U)
4
X2 DIECAST LED EXIT SIGN (GREEN)LED 120V WALL LITHONIA (LE) SURE-LITES (CX), MULE (MD B
U)
3
CONTRACTOR TO FIELD VERIFY ALL EXISTING CIRCUITS TO REMAIN AND BALANCE PANEL ACCORDINGLY. PROVIDE NEW PRINTED PANEL SCHEDULE FOR PANEL DOOR UPON COMPLETION
OF WORK.
Notes:
R 0 VA 0.00% 0 VA Total Est. Demand:80 A
Other 26940 VA 100.00% 26940 VA Total Conn.:80 A
Heating 54 VA 100.00% 54 VA Total Est. Demand:28644 VA
HVAC 0 VA 0.00% 0 VA Total Conn. Load:28644 VA
Appliance - Dwelling Unit 1650 VA 100.00% 1650 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:92 A 66 A 85 A
Total Load:10768 VA 7978 VA 9898 VA
41 42
39 40
37 38
35 ---- --18 VA 36
33 ---- -- 18 VA 34
31 COIL HEATER EDC-1 20 A 3 18 VA 32
29 114 RADIANT PANEL 20 A 1 380 VA 380 VA 1 20 A 115 RADIANT PANEL 30
27 RESTROOM EXHAUST FAN 20 A 1 0 VA 380 VA 1 20 A 117 RADIANT PANEL 28
25 GARBAGE DISPOSAL 20 A 1 1000... 1650...1 30 A WATER HEATER 26
23 OFFICE 105 & WRR RECEPTACLES 20 A 1 1660... 1440... 1 20 A SUPPLIES & MRR RECEPTACLES 24
21 IT EQUIPMENT 20 A 1 180 VA 1260... 1 20 A IT ROOM RECEPTACLES 22
19 LOBBY RECEPTACLES 20 A 1 720 VA 1440...1 20 A WORK ROOM RECEPTACLES 20
17 LOUNGE REFRIGERATOR 20 A 1 180 VA 1080... 1 20 A LOUNGE RECEPTACLES 18
15 LOUNGE MICROWAVE 20 A 1 1000... 1000... 1 20 A LOUNGE DISHWASHER 16
13 TELLER RECEPTACLES 20 A 1 1880... 1000...1 20 A LOUGE MICROWAVE 14
11 OFFICE 117 RECEPTACLES 20 A 1 720 VA 1520... 1 20 A OFFICE 103&104 RECEPTACLES 12
9 STOR. 113 COPIER 20 A 1 180 VA 1260... 1 20 A OFFICE 118&121 RECEPTACLES 10
7 VESTIBUILE 100 & OFFICE 120 RECEPTACLES 20 A 1 720 VA 180 VA 1 20 A STORAGE 101A COPIER 8
5 CUBICLE 101F&WALL RECEPTACLES 20 A 1 1440... 1080... 1 20 A CUBICLE 101H&101G RECEPTACLES 6
3 OFFICE 123&124 RECEPTACLES 20 A 1 1440... 1260... 1 20 A OFFICE 119&122 RECEPTACLES 4
1 OFFICE 114 & 115 RECEPTACLES 20 A 1 1080... 1080...1 20 A CONFERENCE ROOM RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Recessed Wires:4 Mains Rating:100 A
Supply From:Phases:3 Mains Type:
Location:EXISTING BLDG. PHONE 191 Volts:120/208 Wye A.I.C. Rating:
Branch Panel: LP1
CONTRACTOR TO FIELD VERIFY ALL EXISTING CIRCUITS TO REMAIN AND BALANCE PANEL ACCORDINGLY. PROVIDE NEW PRINTED PANEL SCHEDULE FOR PANEL DOOR UPON COMPLETION
OF WORK.
Notes:
Total Est. Demand:22 A
Total Conn.:18 A
L 0 VA 0.00% 0 VA Total Est. Demand:7998 VA
Other 0 VA 100.00% 0 VA Total Conn. Load:6398 VA
Lighting 6398 VA 125.00% 7998 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:15 A 22 A 16 A
Total Load:1834 VA 2607 VA 1957 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 LOBBY, CORRIDOR, RECEPTION LIGHITNG 20 A 1 394 VA 8
5 101B, 102, 105, 108-111 LIGHTS 20 A 1 1416... 541 VA 1 20 A CORRIDOR LIGHITING 6
3 ROOMS 101D, 114-118, AND 121 LIGHTS 20 A 1 1440... 1167... 1 20 A ROOMS 103, 104, 106, 107 LIGHTS 4
1 EMERGENCY LIGHTING 20 A 1 288 VA 1152...1 20 A 101A, 119-124 LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Recessed Wires:4 Mains Rating:100 A
Supply From:Phases:3 Mains Type:
Location:EXISTING BLDG. PHONE 191 Volts:120/208 Wye A.I.C. Rating:
Branch Panel: LP2
1 ADDENDUM NO. 2 4-11-17
1