Loading...
HomeMy WebLinkAboutIUHN MRI CD 04-25-2017 North Hospital MSKTD & Associates Architecture | Engineering | Interior Design MRI Shell Build-out 1715 Magnavox Way930 North Meridian Fort Wayne, IN 46804Indianapolis, IN 46204 260.432.9337317.917.1190 www.msktd.com Drawing Index ArchitecturalPlumbingMechanicalElectrical G1-1Titlesheet, Drawing Index and General InfoP0-1Plumbing Symbols and AbbreviationsM0-1Mechanical Symbols and AbbreviationsE0-1Electrical Symbols and Abbreviations G1-2Life Safety Plans and Code SummaryP2-1First Floor Plumbing PlansM2-1First Floor Mechanical PlansE1-0Overall Ground Floor Plan M3-0Lower Level Mechanical Piping PlanE1-1Overall First Floor Plan A0-2Overall Floor PlanM3-1First Floor Mechanical Piping PlansE2-1First Floor Lighting Plans No. AR10500075 A1-1First Floor Demo and Structural PlansM4-1Cryogen Vent RoutingE3-1First Floor Power and Systems Plans STATE OF I A2-1First Floor and Reflected Ceiling PlansM6-1Mechanical Schedules and Temp. ControlE6-1Electrical Schedules I Schematics A10-1Casework Elevations and DetailsE6-2Electrical Schedules Date Signed 4-25-17 M7-1Mechanical Details E7-1Electrical Details M7-2Mechanical Details I2-1First Floor Interior Finish Plan M7-3Mechanical Details 2 3 0 6 4 a n a i d n I , l e m r a C General Demolition NotesGeneral Reconstruction NotesGeneral Ceiling NotesGraphic SymbolsContacts | l t Architectural:Structural: e THESE NOTES SHALL APPLY TO ALL DEMOLITION THESE NOTES APPLY TO ALL FLOOR PLANS, AND TO THESE NOTES APPLY TO ALL CONSTRUCTION DRAWINGS AND TO ALL a PROJECT NORTH DRAWINGS AND TO ALL CONTRACTORS AND/OR e ALL CONTRACTORS AND/OR SUBCONTRACTORS CONTRACTORS AND/OR SUBCONTRACTORS THAT WORK WITHIN THIS Kyle HardieJim Schmidt NORTH t r SUBCONTRACTORS THAT WORK ON THIS PROJECT. THAT WORK ON THIS PROJECT. BUILDING. ARROW t i MSKTD & AssociatesMSKTD & Associates TRUE NORTH NEW DOOR 1.ALIGN ALL CEILING AND BULKHEAD REVEALS, CONTROL OR SEISMIC JOINTS WITH S 1.OWNER WILL REMOVE ALL FURNISHINGS, LOOSE EQUIPMENT, SUPPLIES, ETC.... PRIOR 1.CONTRACTORS SHALL BE RESPONSIBLE FOR VISITING THE SITE TO BECOME 101A kfh@msktd.comjrs@msktd.com AND THE ADJACENT REVEAL, CONTROL OR SEISMIC JOINTS IN WALLS INDICATED ON TO CONSTRUCTION COMMENCING.p FAMILIAR WITH AND VERIFY THE EXISTING CONDITIONS. THESE DEMOLITION FRAME ELEVATIONS. 2.ALL EQUIPMENT AND MATERIALS LABELED AS "SALVAGE" OR "RELOCATE AS DIRECTED DRAWINGS SHALL SERVE TO AID THE CONTRACTOR IN HIS EVALUATION OF THE NEW n 317.917.1190260.432.9337 X 2.ALL CEILING AND BULKHEAD HEIGHTS INDICATED ARE TO FINISHED FACE OF r BY OWNER" SHALL BE REMOVED, PROPERLY PROTECTED AND TRANSPORTED TO A EXTENT OF DEMOLITION; BUT SHALL NOT BE HELD TO BE ALL INCLUSIVE. COLUMN s GYPSUM BOARD OR TO THE BOTTOM FACE OF ACOUSTICAL CEILING TILE PAD, SPECIFIC a LOCATION ON THE PREMISES AS DIRECTED BY THE OWNER. 2.CONTRACTORS SHALL BE RESPONSIBLE FOR ALL DEMOLITION REQUIRED FOR THE LINE o 1 i UNLESS NOTED OTHERWISE. CONSTRUCTION 3.ALL GENERAL CONTRACTORS AND THEIR SUBCONTRACTORS SHALL BE RESPONSIBLE INSTALLATION OF NEW CONSTRUCTION AND AS NECESSARY TO FULFILL THE Mechanical & Plumbing:Interiors: 3.CEILING CONTRACTOR TO PROVIDE ALL CEILING GRID TO SUPPORT HVAC SUPPLY NOTES FOR VISITING THE CONSTRUCTION SITE TO BECOME FAMILIAR WITH ALL EXISTING Fd PURPOSE AND INTENT OF THE FINISHED WORK, WHETHER OR NOT IT IS o DIFFUSERS AND RETURN GRILLS. i CONDITIONS WHICH AFFECT THAT SPECIFIC PORTION OF THEIR WORK. ANY CONFLICTS SPECIFICALLY SHOWN OR NOTED IN THESE DOCUMENTS. THE CONTRACTOR Kevin HuttonSarah Savage EXISTING 4.DEVICES OTHER THAN LIGHTING AND DIFFUSERS ARE SHOW IN APPROXIMATE r OR APPARENT DEFICIENCIES MUST BE SUBMITTED TO THE ARCHITECT IN WRITING X SHALL BE RESPONSIBLE FOR ALL ITEMS CALLED TO BE REMOVED THROUGH OUT n COLUMN LINE LOCATIONS, FINAL LOCATION TO BE COORDINATED WITH ALL TRADES AND SPECIFIC PRIOR TO BIDDING. THE ENTIRE SET OF DOCUMENTS. e MSKTD & Associates 1 Genesis Engineering ARCHITECT. DEMOLITION 4.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMING IN WRITING THE o H 3.CONTRACTORS SHALL FIELD INSPECT ALL DEMOLITION WORK PRIOR TO REMOVAL, 5.AT LOCATIONS WHERE GYPSUM BOARD CEILINGS ARE INDICATED, THE NOTES i OWNER ON A WEEKLY BASIS OF THE CONSTRUCTION SCHEDULE FOR THE TO INSURE SUCH REMOVAL DOES NOT IMPAIR STRUCTURAL INTEGRITY OF THE khutton@genesis-sjs@msktd.com t CONTRACTOR HAS THE OPTION TO USE LIGHT GAGE METAL FRAMING OR M APPROACHING TWO WEEKS CONSTRUCTION ACTIVITY. ANY STORAGE OF MATERIALS, EXISTING BUILDING. IF THE INSPECTION INDICATES THAT THE STRUCTURAL SUSPENDED GYPSUM BOARD GRID UNLESS OTHERWISE DETAILED. THE DETAIL NUMBER SIM ACCESS OR EGRESS PROBLEMS, TRAFFIC FLOW OR NORMAL OWNER OPERATIONS a INTEGRITY MAY BE IMPAIRED, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY. . engineering.com317.917.1190 ROOM NAME 1 CONTRACTOR WILL COORDINATE ANY MODIFICATIONS WITH THE OTHER TRADES ROOM WHICH ARE TO BE AFFECTED MUST BE PROTECTED AND/OR AGREED UPON BY THE SECTION 4.REMOVE ALL DAMAGED OR EXISTING FINISH MATERIALS FROM REMAINING WALLS, 101 h v ON THE PROJECT. THE CEILING CONTRACTOR'S FINAL MEANS AND METHODS WILL NAME OWNER. ALL COSTS SHALL BE INCURRED BY THE GENERAL CONTRACTOR.A5-1 PARTITIONS AND COLUMNS (GYPSUM BOARD,WALL FABRIC, PANELING, TILE, 317.501.9737 N NOT CONFLICT WITH THE WORK OF OTHERS OR THE INTENT OF THESE AND SHEET NUMBER t 5.THE GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY WOOD BLOCKING FOR MASONRY, CONCRETE, ETC...). PATCH WALLS AND COLUMNS AS REQUIRED TO o DOCUMENTS. NUMBER ALL TRADES. THIS BLOCKING SHALL BE FIRE RETARDANT. RECEIVE NEW FINISH MATERIALS. r 6.WHERE EXISTING SUSPENDED ACOUSTICAL CEILINGS ARE SCHEDULED TO n 0 6.ANY PLASTER WORK REQUIRING NEW FINISH SHALL BE SMOOTH, SOUND AND IN A 5.CONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING, INSTALLING AND Electrical:Construction Manager: REMAIN, CUT AND PREP THE CEILING GRID IN PREPARATION FOR REPAIRING. FLUSH PLANE BEFORE FINISH APPLICATION. CONTRACTOR SHALL REPAIR THE MAINTAINING DUST TIGHT TEMPORARY CONSTRUCTION BARRIERS TO ALL AREAS e 0 SALVAGE ENOUGH CEILING PADS FOR RECONSTRUCTION. STORE AND PROTECTx /Xx-xELEVATION 3.5A SURFACE FOR THE NEW FINISH AS SCHEDULED. 1i PARTITION TYPE WITHIN THE CONSTRUCTION LIMIT LINES, DURING THE CONSTRUCTION PROCESS. Josh WalkeCarl Dennin o ALL MATERIALS. USE NEW MATCHING MATERIALS FOR RECONSTRUCTION AS SYMBOL 7.ALL FIRE RATED WALLS AND FLOOR PENETRATIONS MUST COMPLY WITH ASTME-814. 7 LOCATIONS SHALL BE COORDINATED WITH THE OWNER AND ARCHITECT. R REQUIRED. SHEET NUMBER 8.ITEMS SHOWN IN LIGHTER PEN WEIGHT ARE EXISTING TO REMAIN. Genesis EngineeringMesser Construction Co. 6.ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED 1 7.SEE THE ROOM FINISH SCHEDULE FOR ADDITIONAL COMMENTS REGARDING 9.REMOVE ALL DAMAGED GYPSUM BOARD, MASONRY, CONCRETE, PLASTER, ETC... WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTORS DAILY. MATERIALS AND FINISHES. DETAIL NUMBER FROM EXISTING SURFACES AND REPAIR TO MATCH ADJACENT CONSTRUCTION PRIOR WINDOW khutton@genesis-CDennin@messer.com 7.PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO 1t A N 1 8.THE DESIGNATION 'CJ' INDICATES GYPSUM BOARD CONTROL JOINTS. WHERE TO REFINISHING. ALL SURFACES SHALL BE SMOOTH AND IN A FLUSH PLANE. ELEVATION REMAIN" FIXTURES AND EQUIPMENT REQUIRED TO REMAIN IN PLACE DURING INDICATED PROVIDE USG #093 ZINC CONTROL TYPICAL. INSTALL JOINT THROUGH 10.ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED SYMBOL engineering.com317.576.9250 CONSTRUCTION. DETAIL NUMBER SIM THE FULL EXTENTS OF ANY GYPSUM CEILING OR BULKHEAD. WHERE THE GYPSUM PROJECT NO.DATE WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTORS DAILY. 1 8.REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION. ALL CONTRACTORS CEILING COMPONENT MEETS A GYPSUM WALL, EXTEND THE CONTROL JOINT PLAN DETAIL 11.PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO 317.927.8307 ext. 5 A2-1 SHALL COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK, TO BE TOILET ACCESSORY 70474-25-17 A DOWN TO THE FLOOR TYPICAL. REMAIN" FIXTURES AND EQUIPMENT REQUIRED TO REMAIN IN PLACE DURING SHEET NUMBER ASSURED THAT THEIR WORK IS COMPLIMENTARY TO THE WORK OF ALL OTHER 9.THE GENERAL CONTRACTOR WILL PROVIDE AND INSTALL ALL SUPPLEMENTAL CONSTRUCTION. Brad Bastin CONTRACTORS AND COMPLETE IN ALL RESPECTS. AND/ OR MISCELLANEOUS STEEL FRAMING AS REQUIRED BY THEMSELVES OR BY 12.REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION. ALL CONTRACTORS SHALL REV.DATE 9.UNLESS NOTED OTHERWISE ALL DEMOLITION MATERIAL BECOMES THE PROPERTY THEIR SUBCONTRACTORS FOR THE INSTALLATION OF THE EQUIPMENT BBastin@messer.com COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK, TO BE ASSURED THAT OF THE CONTRACTORS AND IS TO BE REMOVED FROM THE PROPERTY, IN A LEGAL XXX SCHEDULED AND SPECIFIED. NOT ALL OF THE REQUIRED SUPPORT STEEL MAY BE TAG IDEQUIPMENT TAG WORK IN EITHER OF THESE AREAS IS COMPLEMENTARY TO THE OTHER AND MANNER. THE OWNER RESERVES THE RIGHT AND SHALL BE GIVEN THE DETAILED OR CALLED OUT FOR IN THESE DOCUMENTS. COORDINATE ALL 317.576.9250 COMPLETE IN ALL RESPECTS. ANY CONFLICTS OR APPARENT DEFICIENCIES MUST BE OPPORTUNITY TO CLAIM ITEMS WHETHER OR NOT THOSE ITEMS WERE REQUIREMENTS WITH THE SPECIFICATIONS, EQUIPMENT SUPPLIERS AND SUBMITTED TO THE ARCHITECT IN WRITING PRIOR TO BIDDING. SPECIFICALLY NOTED FOR REMOVAL, RELOCATION, OR AS RETURNED TO SUBCONTRACTORS. THERE WILL BE NO CHANGE ORDERS TO THE PROJECT FOR 13.ALL WALL HUNG CASEWORK REQUIRES CONTINUOUS HORIZONTAL WOOD BLOCKING XX-YYYx 1 TAG IDFURNITURE TAG OWNER AND SAME SHALL BE RETURNED TO OWNER. SUPPLEMENTAL STEEL WHERE OMISSIONS MAY OCCUR IN THE BIDDING BETWEEN STUDS AT TOP AND BOTTOM OF CASEWORK. BRACE WALL TO DECK AS x QUANTITY 10.THE CONTRACTOR RESPONSIBLE FOR GENERAL DEMOLITION WORK SHALL DOCUMENTS. REQUIRED. COORDINATE ANY AND ALL ASBESTOS REMOVAL WITH THE OWNER. ALL ASBESTOS 14.ALL DIMENSIONS ARE FROM FACE OF BASE MATERIAL (STUD/CMU) TO FACE OF BASE REMOVAL WILL BE PREFORMED BY A LICENSED ASBESTOS REMOVAL MATERIAL (STUD/CMU) UNLESS NOTED OTHERWISE. CONTRACTOR. THIS TYPICALLY INCLUDES FLOOR TILE, TILE MASTIC AND PIPE 15.PORTIONS OF THE BUILDING SHALL BE OCCUPIED DURING CONSTRUCTION. THE INSULATION. Partition Types GENERAL CONTRACTOR SHALL FOLLOW THE FOLLOWING LIFE SAFETY ISSUES. 11.ITEMS SHOWN IN LIGHTER PEN WEIGHTS ARE EXISTING TO REMAIN. FAILURE TO LIST ALL LIFE SAFETY ISSUES DOES NOT RELIEVE THE CONTRACTORS 12.GENERAL CONTRACTOR RESPONSIBLE FOR PATCHING ALL REMOVED ELECTRICAL NOTE: FLOOR TO FLOOR HEIGHT FROM FIRST TO SECOND IS 15'- 4" FROM COMPLYING WITH FEDERAL, STATE AND LOCAL CODES, THE CONTRACTUAL OUTLETS. ELECTRICAL CONTRACTOR TO PROVIDE GENERAL CONTRACTOR WITHa.INSURE ALL EXITS PROVIDE FREE AND UNOBSTRUCTED EGRESS. STAFF AGREEMENT BETWEEN THE CONTRACTOR AND OWNER, AND OTHER GOVERNING QUANTITIES.AND PERSONNEL SHALL RECEIVE TRAINING AND WRITTEN NOTIFICATION IF 5 7/8" 4 7/8"4 1/4"5 3/8" BODIES WHICH HAVE JURISDICTION ON THIS PROJECT. THE FOLLOWING ARE INTERIM 13.REMOVE EXISTING FINISHES AS REQUIRED TO INSTALL NEW FINISHES. PREPARE ALTERNATIVE EXITS MUST BE DESIGNATED. LIFE SAFETY CODE ISSUES WHICH ARE SPECIFIC TO THIS PROJECT AND MUST BE SURFACES TO RECEIVE NEW FINISH AS PER FINISH MANUFACTURER'S PRINTEDb.INSURE FREE AND UNOBSTRUCTED ACCESS TO EMERGENCY ADDRESSED: INSTRUCTIONS, SEE FINISH SCHEDULE FOR NEW FINISHES.DEPARTMENTS OR SERVICES FOR EMERGENCY FORCES. COORDINATE SET DESCRIPTION 14.REMOVE EXISTING CEILINGS AND CEILING SUPPORT SYSTEM WHERE NEW WITH OWNER AND ARCHITECT. 5/8" GYPSUM BOARD CEILINGS ARE INDICATED, UNLESS OTHERWISE NOTED.c.INSURE FIRE ALARM, DETECTION AND SUPPRESSION SYSTEMS ARE NOT 3 5/8" METAL STUD3 5/8" METAL STUD3 5/8" METAL STUD (BOTH SIDES) IMPAIRED. A TEMPORARY, BUT EQUIVALENT, SYSTEM SHALL BE PROVIDED, AT 16" O.C.AT 16" O.C.AT 16" O.C. Construction INSTALLED AND TESTED PRIOR TO ANY EXISTING FIRE SYSTEM BEING INDICATES EXISTING WALL TO BE REMOVED IN ITS 5/8" GYPSUM BOARD5/8" GYPSUM BOARD5/8" GYPSUM BOARD IMPAIRED. ENTIRETY.1 1/2" FURRING Documents (BOTH SIDES)(ONE SIDE)(BOTH SIDES) d.INSURE TEMPORARY CONSTRUCTION PARTITIONS ARE SMOKE TIGHT AND 1 3/4" RF WALL BUILT OF NON COMBUSTIBLE MATERIALS. THESE PARTITIONS SHALL BE INDICATES EXISTING DOOR, FRAME AND ASSOCIATED SHEET TITLE 1/2" GYPSUM BOARD PANEL WITH 2" COORDINATED WITH THE OWNER AND ARCHITECT. HARDWARE TO BE REMOVED IN ITS ENTIRETY. SEE DOOR (CORRIDOR SIDE ONLY-EXTEND INSULATION e.SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS OF THE SCHEDULE FOR ITEMS TO BE SALVAGED AND REUSED IN TO 6" ABOVE FINISHED CEILING) Titlesheet, Drawing BUILDING. OTHER AREAS. 2" AIR GAP f.DEVELOP AND ENFORCE STORAGE, HOUSEKEEPING AND DEBRIS REMOVAL M Index and General Info P PROCEDURES THAT REDUCE THE FLAMMABLE AND COMBUSTIBLE FIRE SOUND ATTENUATIONSOUND ATTENUATIONSOUND ATTENUATION EXISTING WALL 7 LOAD TO THE LOWEST LEVEL NECESSARY FOR DAILY OPERATIONS. BLANKET INSULATIONBLANKET INSULATIONBLANKET INSULATION 4 CONSTRUCTION : g.IOSHA REQUIRES MATERIAL SAFETY DATA SHEETS (MSDS) FOR ALL 1 MATERIALS BEING USED OR STORED ON THIS PROJECT BE MADE 4 : SHEET NUMBER AVAILABLE TO ALL WORKERS ON THIS JOBSITE. COPIES MUST BE 2 1 HR RATED PROVIDED TO THE OWNER'S DIRECTOR OF SECURITY, IMMEDIATELY, AS 7 1.5A1.5B1.5C1.5NRF Wall 1 (UL DESIGN # U419) WORK BEGINS. 0 2 h.SECURE ALL TOOLS AND CONSTRUCTION MATERIALS DURING BREAKS AND / EXTEND TO BOTTOMEXTEND TO BOTTOM OF DECK ABOVEEXTEND TO BOTTOMEXTEND TO BOTTOMFURNISHED AND INSTALLED BY RF SHIELDING 5 NON-CONSTRUCTION HOURS. OF DECK ABOVEEXCEPTION W/ TYPE 'X' GYPSUM BOARDOF DECK ABOVEOF DECK ABOVEVENDOR UNLESSS OTHERWISE NOTED 2 / 4 G1-1 Code SummaryLife Safety Legend Code Citations APPLICABLE CODES: LIFE SAFETY CODE REVIEW (Per NFPA 101, 2012 Edition) Chapter 18: New Healthcare NFPA 101 Life Safety Code2012 Edition. Chapter 18 New Healthcare Occupancies. SUITES (Non-Rated (Smoke Resistant) Corridors): Chapter 19: Existing Healthcare BUILDING/DWELLING CODE2014 Indiana Building Code (675 IAC 13-2.6) STRUCTURAL CODE2014 Indiana Building Code (2012 IBC, ANSI A-117.1-2009, ASCE-7-2005) MECHANICAL CODE2014 Indiana Mechanical Code (2012 IMC with state amendments) 18.2.5.7.1.1- Suites shall be separated from the remainder of the building, and from other ELECTRICAL CODE2009 Indiana Electrical Code (2008 NEC with state amendments) suites, by walls and doors meeting corridor wall construction requirements. CONSTRUCTION LEGEND FIRE/LIFE SAFETY CODE2014 Fire Code (675 1AC 22-2.5) consisting of 2012 IFC with state amendments ACCESSIBILITY CODE2014 Indiana Building Code, Chapter 11, and ICC standard A117.1 2009 edition 19.2.5.7.1.1- Suites shall be separated from the remainder of the building, and from other ENERGY CODE2010 Indiana Energy Conservation Code (ASHRAE 90.1- 2007 with state amendments) suites, by walls and doors meeting corridor wall construction requirements. BUILDING:Hospital 2-HOUR FIRE BARRIER(Occupancy Separation) 18.2.5.7.1.3 (A)- Intervening rooms shall not be hazardous areas as defined by 18.3.2. OCCUPANCY:Group I-2, InstitutionalIBC sec. 308.4 19.1.3.4- Occupancy separation. 19.2.5.7.1.3 (A)- Intervening rooms shall not be hazardous areas as defined by 18.3.2. CONSTRUCTION TYPEType I-AIBC Table 601 MSKTD 18.1.3.4.1- Occupancy separation. 18.2.5.7.2.1- (A) Sleeping Suites shall have access directly to exit corridor. (B) Where two AUTOMATIC SPRINKLERS:Yes– Fully-Sprinkled & Associates or more exit access doors are required from a suite, one of the exit doors shall be permitted 19.2.2.4 Smokeproof Enclosures- "Smokeproof enclosures complying with 7.2.3 shall be AREA P to be directly to an exit stair, exit passageway or exit door to the exterior. (C) Sleeping permitted." Architecture | Engineering | Interior Design suites shall be provided with constant staff supervision within the suite. (D) Sleeping suites ALLOWABLE BUILDING AREA:UnlimitedIBC Table 503 shall be arranged to provide one of the following (a) The patient sleeping rooms shall be 7.2.3.3- "A smokeproof enclosure shall be continuously enclosed by barriers having a 2- FLOOR AREAS (GROSS): arranged to allow for direct supervision form a normally attended location within the suite or hour fire resistance rating from the highest level of exit discharge. Where a vestibule is 1715 Magnavox Way930 North Meridian (b) any patient rooms without direct supervision shall be provided by automatic smoke Fort Wayne, IN 46804Indianapolis, IN 46204 used, it shall be within the 2-hour rated enclosure and shall be considered part of the EXISTING:RENOVATION: detection. 260.432.9337317.917.1190 Lower Level:83,364 SFN/A smokeproof enclosure." First Floor:88,200 SF1,940 SF www.msktd.com Second Floor:87,990 SFN/A 19.2.5.7.2.1- (A) Sleeping Suites shall have access directly to exit corridor. (B) Where two 18.2.2.4 Smokeproof Enclosures- "Smokeproof enclosures complying with 7.2.3 shall be Third Floor:73,802 SFN/A or more exit access doors are required from a suite, one of the exit doors shall be permitted Fourth Floor:71,365 SFN/A permitted." to be directly to an exit stair, exit passageway or exit door to the exterior. (C) Sleeping Fifth Floor:70,255 SFN/A Sixth Floor:30,038 SFN/A suites shall be provided with constant staff supervision within the suite. (D) Sleeping suites 8.3.4.2 (table)- 1½-hour opening rating (doors). Seventh Floor: 3,656 SFN/A shall be arranged to provide one of the following (a) The patient sleeping rooms shall be (Penthouse) arranged to allow for direct supervision form a normally attended location within the suite or (b) any patient rooms without direct supervision shall be provided by automatic smoke TOTAL GROSS AREA:508,670 SF 1,940 SF detection. 2-HOUR FIRE BARRIER (Vertical Openings): HEIGHT: 18.2.5.7.2.2- Sleeping suites of more than 1000 sq. ft. shall have not less than two exit 18.3.1.1- "Any vertical opening shall be enclosed or protected in accordance with 8.2.5." UnlimitedIBC Table 503 ALLOWABLE STORIES: access doors remotely located from one another. One means of egress shall be directly to a corridor. One means of egress shall be permitted to be through another suite, provided 8.6.5– Enclosures connecting four stories or more in new construction– 2 hour fire STORIES:Seven (7) including a Lower Level (Basement), plus Penthouse that the suite separation complies with corridor construction requirements. barriers Other enclosures in new construction: 1-hour fire barriers. FIRE RESISTANT REQUIREMENTS : (NON-COMBUSTIBLE) 19.2.5.7.2.2- Sleeping suites of more than 1000 sq. ft. shall have not less than two exit access doors remotely located from one another. One means of egress shall be directly to Structural Framing3-HourIBC Table 601 8.6.7- Atriums are separated from the adjacent spaces by fire barriers with not less than 1- No. a corridor. One means of egress shall be permitted to be through another suite, provided Floor– Ceiling2-HourIBC Table 601 hour fire resistance rating with opening protective for corridor walls. See exceptions in AR10500075 Roof1 1/2-HourIBC Table 601 that the suite separation complies with corridor construction requirements. section. STATE OF SHAFT ENCLOSURES: I 18.2.5.7.2.3 (B)- Sleeping suites shall not exceed 7500 sq. ft. Sleeping Suites larger than 3 Stories or Less2-HourNFPA 101; 8.3.4.2/IBC 713.4 8.3.4.2 (table)- 1½-hour opening rating (doors). 7500 sq. ft. and not exceeding 10,000 sq. ft. shall be permitted where both direct visual 4 Stories or More2-Hour I supervisiion is provided and automatic smoke detection is provided. VERTICAL CIRCULATION: 2-HourNFPA 101; 8.3.4.2Date Signed 4-25-17 2-HOUR FIRE BARRIER ( Exit Passageways): 19.2.5.7.2.3- (B) Sleeping suites shall not exceed 7500 sq. ft. without having an OCCUPANCY SEPARATION:B Occ. and I-2 Occupancy2-Hour electrically supervised sprinkler system and automatic smoke detection. Sleeping Suites REF. 19.2.2.7 Exit Passageways- "Exit passageways complying with 7.2.6 shall be permitted." larger than 7500 sq. ft. and not exceeding 10,000 sq. ft. shall be permitted where both FE SMOKE BARRIERS:(I-2 Occupancy and in B Occupancy located within 1-floor of I-2) direct visual supervisiion is provided and automatic smoke detection is provided. Max Area:22,500 SF 7.2.6.2 Enclosure- "An exit passageway shall be separated from other parts of the building Max Travel Distance:200 Ft. as specified in 7.1.3.2." 18.2.5.7.2.4- Suite Travel Distance between any point in a sleeping suite and the exit TRAVEL DISTANCE TO AN EXIT: access door from that suite shall not exceed 100 ft. Travel distance between any point in B Occupancy300 Ft. 7.1.3.2.1 (b)- 2-hour fire resistive rating for four or more stories. a sleeping suite and the exit shall not exceed 200 ft. I-2 Occupancy200 Ft. 18.2.2.7 Exit Passageways- "Exit passageways complying with 7.2.6 shall be permitted." 19.2.5.7.2.4- Suite Travel Distance between any point in a sleeping suite and the exit access door from that suite shall not exceed 100 ft. Travel distance between any point in 8.3.4.2 (table)- 1½-hour opening rating (doors). a sleeping suite and the exit shall not exceed 200 ft if the building is protected by a 2 sprinkler system. Without a sprinkler system, distance is limited to 150 ft. 3 FE 1-HOUR FIRE BARRIER(Hazardous Areas) 0 18.2.5.7.3-Patient Care Non-Sleeping Suites shall have direct access to an exit access 6 corridor. 18.3.2.1 Hazardous Areas- "Any hazardous area shall be protected in accordance with 4 c Section 8.4. The areas described in Table 18.3.2.1 shall be protected as indicated." Life Safety Legend 19.2.5.7.3.1-Patient Care Non-Sleeping Suites shall have direct access to an exit access 1. Boiler and fuel-fired heater rooms corridor. a 2. Central/bulk laundries larger than 100 square feet. (9.3 square meters) c n 3. Paint shops 18.2.5.7.3.2- Non-sleeping suites of more than 2500 sq ft shall have not less than two exit 2 HOUR FIRE BARRIER(Occupancy Separation) a 4. Repair Shops access doors remotely located from one another. For suites requiring two means of i 5. Soiled linen rooms SUITE egress, one means of egress from the suite shall be permitted to be through another suite d 2 HOUR FIRE BARRIER(Vertical Openings) 6. Trash Collection rooms 1,005 SF provide dthat the suite separation complies with corridor wall construction. n 7. Rooms or spaces larger than 50 square feet (4.6 square meters) including repair shops, I 2 HOUR FIRE BARRIER(Exit Passageways / Horizontal Exit) used for storage of combustible supplies and equipments in quantities deemed hazardous 19.2.5.7.3.2- Non-sleeping suites of more than 2500 sq ft shall have not less than two exit , by the authority having jurisdiction. l access doors remotely located from one another. For suites requiring two means of 1 HOUR FIRE BARRIER(Hazardous Rooms) 8. Laboratories employing flammable or combustible materials in quantities less than those egress, one means of egress from the suite shall be permitted to be through another suite e FEFE that would be considered a severe hazard. provide dthat the suite separation complies with corridor wall construction. SMOKE BARRIER WALL(1 Hour Rated Walls, 20 Min. Rated Doors) m 18.3.6.3.11- "Door-closing devices shall not be required on doors in corridor wall openings r SMOKE PARTITION(Hazardous Rooms) 18.2.5.7.3.3- Patient Care Non-Sleeping Suites shall not exceed 10,000 sq. ft. other than those serving required exits, smoke barriers or enclosures of vertical openings a and hazardous areas." TRAVEL DISTANCE(Distance to Exit) 19.2.5.7.3.3- Patient Care Non-Sleeping Suites shall not exceed 10,000 sq. ft. C FE P TRAVEL DISTANCE(Distance to Smoke Barrier) 18.2.6.1- Travel distance between any point in a room and an exit shall not exceed 200 ft. | SMOKE BARRIER WALL (1-hour Rated Existing): SUITE(Bounding walls to be Smoke Resistant) l 19.2.6.1- Travel distance between any point in a room and an exit shall not exceed 150 ft. UPUP t 19.3.7.3- "Any required smoke barrier shall be constructed in accordance with e Section 8.3 and shall have a minimum 1/2 hour fire resistance rating....." a FIRE RESISTIVE CEILING(Bounding walls to be 1 Hour Rated Fire Barrier) DNDN e SMOKE RESISTANT CORRIDORS (Non-Rated Corridors): t r 19.3.7.6- 19.3.7.8- Doors shall have a 20 minute fire rating and shall be self-closing or t i automatic closing. Doors are not required to swing with egress travel and positive latching 19.3.6.2.4- "In smoke compartments protected throughout by an approved, supervised FIRE RESISTIVE CEILING(Bounding walls to be 2 Hour Rated Fire Barrier) S hardware is not required. automatic sprinkler system in accordance with 19.3.5.7, a corridor shall be permitted to be p separated from all other areas by non-fire-rated partitions and shall be permitted to n 18.3.7.3- "Any required smoke barrier shall be constructed in accordance with Section r SMOKE TIGHT EXIT ACCESS CORRIDOR terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke." s a 8.3 and shall a minumum 1-hour fire resistance rating....dampers shall not be required in (Non-Rated Corridors; Hazardous Areas) o i fully ducted system....." 18.3.6.2- "Corridor walls shall form a barrier to limit the transfer of smoke. Such walls shall Fd o i NFPA 101 LIFE SAFETY CODE (2000) CHAPTER 18 be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer r 18.3.7.6- 18.3.7.8- Doors shall have a 20 minute fire rating and shall be self-closing or (New Healthcare Occupancy) of smoke. No fire resistance rating is required for corridor walls." n automatic closing, and permitted to be held open only by an automatic releasing device. e o H Doors IMAGING NFPA 101 LIFE SAFETY CODE (2000) CHAPTER 38 i 19.3.6.3.4- Door closing devices not required. t EQUIPMENT (New Business Occupancy) shall be dual egress but positive latching hardware is not required. M B133A a . 408 SF 18.3.6.3.4- Door closing devices not required. EXIT SMOKE ZONES (Not to Exceed 22,500 s.f.): h v N t o P 19.3.7.1- "To divide every story used by inpatients for sleeping by more than 30 patients MANUAL FIRE ALARM PULL STATION TRAVEL DISTANCES TO EXIT r n 0 into not less than two smoke compartments;(1) To limit the size of each smoke STANDPIPE OUTLET e 0 compartment to an area not exceeding 22,500 sq. ft. (2) Where neither the length nor 18.2.6.2.1- "The travel distance between any point in a room and an exit shall not exceed o width of the smoke compartment exceeds 150 ft, the travel distance to each the smoke 7 c 200 feet." R CHUTE (TRASH & LINEN) barrier door shall not be limited. 1 FIRE EXTINGUISHER FE 19.2.6.2.2- The travel distance between any point in a room and an exit shall not exceed A N 1 18.3.7.1- "(1) To divide every story used by inpatients for sleeping or treatment into not (Exception: The maximum travel distance shall be permitted to be increased by 50 ft. 150. less than two smoke compartments; (2) To divide every story having an occupant load of MRI #2STORAGE / ES in buildings protected throughout by an approved, supervised automatic sprinkler system.) PROJECT NO.DATE B134 CLOSET 50 or more persons, regardless of use, into not less than two smoke compartments; (3) To SUITE 464 SF B142 70474-25-17 limit the size of each smoke compartment to an area not exceeding 22,500 sq. ft. (4) To 340 SF 79 SF limit the travel distance from any point to reach a door in the required smoke barrier to a TRAVEL DISTANCES TO SMOKE Rated Wall Priority REV.DATE distance not exceeding 200 ft. 19.3.7.1- "The size of any such smoke compartment shall not exceed 22,500 s.f., and the FE travel distance from any point to reach a door in the required smoke barrier shall not exceed 200 feet. (Exception No. 1: Where neither the length nor width of the smoke RATINGPRIORITY SMOKE PARTITION (Hazardous Areas): compartment exceeds 150 feet, the travel distance to reach the smoke barrier door shall not be limited." 3 HOUR WALL1HIGHER PRIORITY 19.3.2.1 Hazardous Areas- Any hazardous area shall be safe-guarded by a fire barrier 2 HOUR WALL2 having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing 18.3.7.1 (4)- "To limit the travel distance from any point to reach a door in the required 1 HOUR WALL3 system in accordance with 8.7.1. The automatic extinguishing shall be permitted to be in smoke barrier to a distance not exceeding 200 feet." SMOKE PARTITION4 AREA OF CONSTRUCTION accordance with NON RATED PARTITION5LOWER PRIORITY 19.3.5.9.Where the sprinkler option of 19.3.2.1 is used, the areas shall be separated from other spaces by smoke-resisting partitions and doors. SMOKE ZONE 1.3 GYPSUM BOARD CONTINUES 19.3.2.1.5Hazardous areas shall include, but shall not be restricted to, the following: 13,868 SF THROUGH STUD CAVITY OF KEY PLANSET DESCRIPTION 1. Boiler and fuel-fired heater rooms LOWER PRIORITY WALL HIGHER PRIORITY 2. Central/bulk laundries larger than 100 square feet. (9.3 square meters) PARTITION Construction LOWER PRIORITY 3. Paint shops PARTITION 4. Repair Shops Documents MOB 5. Soiled linen rooms SHEET TITLE 6. Trash Collection rooms 7. Rooms or spaces larger than 50 square feet (4.6 square meters) including repair shops, AREA OF Life Safety Plans and used for storage of combustible supplies and equipments in quantities deemed hazardous HOSPITAL M CONSTRUCTION by the authority having jurisdiction. Code Summary P 2 8. Laboratories employing flammable or combustible materials in quantities less than those 0 : that would be considered a severe hazard. 5 5 : NOTE: CONTRACTOR IS RESPONSIBLE FOR MAINTAINING NEW AND EXISTING Partial First Floor Life Safety Plan SHEET NUMBER 1 FIRE RESISTIVE WALLS THAT ARE CONTINUOUS AND NOT INTERRUPTED BY NON- Exception: Doors in rated enclosures shall be permitted to have non-rated, factory- or field 7 CENTRAL RATED WALLS. 1 1/8" = 1'-0" True North applied protective plates extending not more than 48in.(122cm) above the bottom of the PLANT 0 2 / door. 5 2 / 4 G1-2 A# Specific Plan Notes A16REMOVE EXISTING DOUBLE EGRESS DOORS AND RAISE HEAD HEIGHT FOR NEW 8'-0"H DOORS. DOORS TO RECEIVE ALL NEW HARDWARE. REFER TO DOOR SCHEDULE AND DETAILS FOR ADDITIONAL INFORMATION. MSKTD & Associates 2344.34.6567899.19.39.79.9101111.31212.51314 Architecture | Engineering | Interior Design 1715 Magnavox Way930 North Meridian Fort Wayne, IN 46804Indianapolis, IN 46204 260.432.9337317.917.1190 www.msktd.com D.9 E E.2 UPUP E.4 DNDN F No. AR10500075 STATE OF I I Date Signed 4-25-17 F.6 . F E R G REF. G.3 2 3 0 6 4 a n H a i d n I , l e m r a C J | UPUP UPUP l t DNDN DNDN e a e t r t i S p n r s a o i DUST PARTITION WALL Fd o i REF. r n K e o H i t M a . h v N t o MRI #2 B134 r n 0 K.5 e 0 o 7 R 1 DUST PARTITION WALLDUST PARTITION WALLDUST PARTITION WALL C1C16 C1C17 DUST PARTITION A N 1 WALL A16 A16 PROJECT NO.DATE L REF. 70474-25-17 AREA OF CONSTRUCTION DNDN REV.DATE MRI #2 - REFER TO SHEET UPUP A2-1 FOR DETAILS M M.2 MAGNET DELIVERY ROUTE KEY PLANSET DESCRIPTION Partial First Floor Plan 3/32" = 1'-0" Construction Documents MOB SHEET TITLE AREA OF Overall Floor Plan HOSPITAL M CONSTRUCTION (INFECTIOUS CONTROL) CONSTRUCTION AND DUST SEPARATION WALL. 6" METAL STUD WITH 5/8" P VINYL FACED GYPSUM BOARD AND SOUND ATTENUATION BLANKET. EXTEND TO CEILING. TAPE 8 0 SEAMS. REFER TO IU HEALTH MANDATORY CONTRACTOR'S ORIENTATION REQUIREMENTS AND : 5 SPECIFICATION SECTION. MAINTAIN A MINIMUM OF 5'-0" AT EXISTING CORRIDORS AND OWNER 5 : OCCUPIED SPACES FOR EGRESS. CONTRATOR IS RESPONSIBLE FOR SUPPLYING AND SHEET NUMBER 1 DETERMINING WALL LOCATIONS AND NUMBER AND SIZE OF CONSTRUCTION DOORS WITHIN 7 CENTRAL SEPARATION WALL. REPAIR FLOOR AND WALLS AS NEEDED AFTER REMOVAL OF WALLS. REFER TO 1 True North PLANT 0 CONSTRUCTION MANAGER'S LOGISTICS PLAN FOR ADDITIONAL INFORMATION. 2 / 5 2 / 4 A0-2 1212.51314 S# Specific Structural Notes S110 1/2" THICK CONCRETE SLAB INFILL. DEPRESS SLAB IN MRI ROOM AS REQUIRED PER MRI UNIT SPECIFICATIONS FOR RF SHIELDING INSTALLATION. SLAB LEVELNESS MUST MEET MRI UNIT SPECIFICATIONS. REFER TO 'TYPICAL FLOOR SLAB INFILL DETAIL' 1/A1-1. S2EXISTING 12" RECESSED 5 1/4" COMPOSITE SLAB WITH ACCESS FLOOR S3 S3EXISTING 5 1/4" COMPOSITE SLAB AT 100'-0" S4 S4EXISTING STEEL BEAMS. IMAGING EQUIPMENT CONTROLOFFICE EXISTING 12" RECESSED SLAB BELOW 100'-0" A.F.F. WITH 18' - 9" B133B133AB146 CORRIDOR MSKTD PROPOSED NEW 10 1/2" CONCRETE INFILL. REFER TO PLAN NOTE 1 B1C10 S2 & Associates S3 1 3 Architecture | Engineering | Interior Design 5 . 0 0 ° K 1715 Magnavox Way930 North Meridian Fort Wayne, IN 46804Indianapolis, IN 46204 260.432.9337317.917.1190 www.msktd.com S3 °READING 0 0 B144 . 5 PATIENT TOILETOFFICE 3 1 B131AB147 S1S4 ISOCENTER MRI #2 STORAGE / ES B134 CLOSET B142 K.5 OFFICE WAITING S3 B148 No. B131 AR10500075 S3 STATE OF #4 STAINLESS STEEL REINF. I @ 10" O.C. BOTH WAYS I 1 1/2" NORMAL WEIGHT CONCRETE TOPPING Date Signed 4-25-17 10 1/2" NORMAL WEIGHT CONCRETE INFILL 10' - 2" S3 26' - 0 1/4" CORRIDOR B1C15 S4 AREA OF CONSTRUCTION CORRIDOR B1C09 L 2 3 0 AREA OF CONSTRUCTION EXISTING 5 1/4" 6 CONCRETE BASE SLAB 4 a n a i First Floor Structural PlanTypical Floor Slab Infill Detail 1 d 1/4" = 1'-0" 1 1/2" = 1'-0" n I , l e 1212.51314 m r a D# Specific Demo Notes C D1REMOVE DOOR AND PORTION OF EXISTING CORRIDOR WALL, PROVIDE OPENING 8'-0" WIDE x 8'-0" TALL FOR DELIVERY OF MAGNET. RECONSTRUCT WALL AFTER DELIVERY AND PROVIDE OPENING FOR NEW DOOR. REFER TO DOOR SCHEDULE. | D2REMOVE PORTION OF WALL FOR NEW DOOR AND FRAME. REFER TO DOOR SCHEDULE. D3REMOVE PORTION OF WALL FOR NEW WINDOW AND FRAME. REFER TO WINDOW AND FRAME ELEVATIONS. l t D4REMOVE COUNTERTOP, SPLASHES, AND ALL ASSOCIATED UNDERCOUNTER BRACING. PREP WALLS TO RECEIVE NEW FINISHES. D7D5REMOVE PORTION OF EXISTING WALL. e a D6EXISTING PORTION OF WALL TO BECOME 1-HOUR SMOKE BARRIER. EXTEND ALL GYPSUM BOARD TO DECK AND PATCH ALL PENETRATIONS. PROVIDE IMAGINGOFFICE D12 e CONTROL APPROPRIATE FIREPROOFING AT ALL PENETRATIONS AND AT OVERHEAD DECK JOINT. PROVIDE ENGINEERING JUDGEMENT THAT EXISTING GYPSUM B146 EQUIPMENT t r B133 BOARD ON EACH SIDE OF WALL IS EQUIVALENT TO TYPE-X GYPSUM BOARD. B133ACORRIDOR t i D8 B1C10 D7REMOVE PORTION OF LAY-IN CEILING AS REQUIRED FOR NEW OVERHEAD MECHANICAL, ELECTRICAL, AND PLUMBING. REFER TO MEP DWGS. (WORK TO BE PERFORMED INSIDE CONTAINMENT CART). S p D8EXISTING FLOORING AND RUBBER BASE TO REMAIN. PROTECT D9REMOVE PORTION OF CHAIR BUMP AND HANDRAIL. SALVAGE FOR REINSTALLATION. n r D10REMOVE BUILT-UP REBAR FLOORING AND LOOSE LAID PLYWOOD FLOORING AND PREP FOR NEW CONCRETE SLAB INFILL. REFER TO STRUCTURAL DWG s a AND DETAILS. o i K D11REMOVE PORTION OF EXISTING FLOOR AND PREP FOR NEW FINISHES. REFER TO FINISH DWGS. D4 Fd o D5 D12REMOVE EXISTING LAY-IN CEILING IN ITS ENTIRETY. PREP TO RECEIVE NEW LAY-IN CEILING SYSTEM TO ALIGN WITH EXISTING ADJACENT CEILING GRID. i r D11 n e o H D3 i D6 t M READING D12 OFFICE B144 a PATIENT TOILET. B147 B131A h v N t o D2 r n 0 MRI SHELL B134 e 0 o D10 7 R D12 1 A N 1 D7 D8 ES CLOSET PROJECT NO.DATE B142 70474-25-17 K.5 WAITINGOFFICE +/- 6' - 0"8' - 0" REV.DATE B131B148 D1 D9 CORRIDORCORRIDOR B1C15B1C09 D12D12 KEY PLANSET DESCRIPTION Construction Documents MOB L SHEET TITLE AREA OF First Floor Demo and AREA OF CONSTRUCTION HOSPITAL M CONSTRUCTION Structural Plans P 1 1 : 5 5 : SHEET NUMBER 1 7 CENTRAL 1 First Floor Demo Plan True North PLANT 0 2 / 5 1/4" = 1'-0" 2 / 4 A1-1 RC# Specific Reflected Ceiling Plan Notes RC1EXISTING LAY-IN CEILING TO REMAIN. RC2NEW 24" x 24" LAY-IN CEILING. REFER TO FINISH SCHEDULE FOR ADDITIONAL INFORMATION. RC3NEW 24" x 24" ACOUSTICAL LAY-IN CEILING w/ NON-FERROUS GRID (MRI SAFE). REFER TO FINISH SCHEDULE FOR 1212.51314 ADDITIONAL INFORMATION. RC4(HATCHED AREA) LAMINATE FASCIA PANEL ABOVE FULL-HEIGHT CABINET. ACCESS PANEL TERMINATES AT LAY-IN CEILING 10'-0" A.F.F. RC5ISOCENTER OF MRI MAGNET. RC6TURRET COVER FROM TOP OF MRI UNIT TO CEILING TO CONCEAL QUENCH VENT AND CABLES. REFER TO MRI MAGNET MANUFACTURER FOR EXACT LOCATION AND SIZE. RC7WALL MOUNTED "NURSE CALL - DOME LIGHT" INDICATION LIGHT (OWNER FURNISHED AND OWNER INSTALLED) . CENTER OVER CORRESPONDING DOOR. MOUNT AT HEIGHT MATCHING EXISTING, ADJACENT SYSTEM. REFER TO ELECTRICAL DWGS FOR ROUGH-IN AND CONDUIT INFORMATION. RC8RF SHIELD PENETRATION PLATE PROVIDED BY SHIELDING VENDOR. OFFICE B146 RC9RF SHIELDING ABOVE ACT / BULKHEAD BY SHIELDING VENDOR. CONTROL RC11NEW METAL FRAMING WITH GYPSUM BOARD BULKHEAD AT 8'-8" B133 RC12QUENCH TUBE EXIT WITHIN EXISTING MASONRY WALL. PROVIDE LINTEL AND FLASHING AS NECESSARY. COORDINATE HEIGHT, OPENING SIZE, AND LOCATION w/ RF SHIELDING AND MRI VENDOR DWGS. IMAGING MSKTD EQUIPMENT RC2 B133A RC1 & Associates RC11 Architecture | Engineering | Interior Design General Ceiling Notes K 1.REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING 1715 Magnavox Way930 North Meridian DRAWINGS FOR FIXTURE TYPES AND LOCATIONS. Fort Wayne, IN 46804Indianapolis, IN 46204 RC2 2.UNLESS OTHERWISE NOTED, ALL CEILINGS SHALL BE 8'-10" 260.432.9337317.917.1190 OFFICE A.F.F. (MATCH EXISTING). MRI #2 B147 www.msktd.com B134 2' x 2' LAY-IN CEILING 10' - 0" A.F.F. CORRIDOR GYPSUM BOARD CEILING / BULKHEAD B1C10 RC4 LAMINATE BULKHEAD / ACCESS PANEL RC8 PATIENT TOILET 10' - 0" RC6 B131A A.F.F. READING B144 RC5 7047 - Door and Opening Schedule STORAGE / ES RC3 CLOSET DoorFrameDetails OpeningDoorPower RC1RC9 B142OFFICE No.GlassReq'd SizeMat.Ele.Mat.Ele.HeadJambLabelHdw. SetRemarks B148 RC2 7047 - MRI Build-out K.5 B134A4'-0" x 7'-0" x 1 3/4"P-LAMF-1------------------No---1, 3, 5 No. B134B3'-0" x 7'-0" x 1-3/4"P-LAMF-1------------------No---1 WAITING AR10500075 C1C16(2) 3'-8" x 8'-0" x 1 3/4"SCWDNL-2FW-HM11/A2-11/A2-1 SIM.20-MIN.20-MIN.Yes16 B131 C1C17(2) 3'-8" x 8'-0" x 1 3/4"SCWDNL-2FW-HM11/A2-11/A2-1 SIM.20-MIN.20-MIN.Yes27 STATE OF I I Date Signed 4-25-17 Door Schedule RemarksDoor Elevations 10' - 2" 1.DOOR, FRAME, AND HARDWARE SHALL BE DESIGNED AND PROVIDED BY RF CORRIDOR RC7 SEE SCHEDULESEE SCHEDULE CORRIDOR SHIELDING VENDOR. SCHEDULE ONLY INDICATES ARCHITECT'S INTENT FOR B1C09 B1C15 SIZE, FINISH MATERIAL, AND LOCKSET AND HARDWARE. REFER TO RF EQ9"EQEQ9"EQ SHIELDING VENDOR DRAWINGS. 2.RECONNECT EXISTING CARD READER WITH ELECTRIC STRIKE. RC2 RC2 3.DOOR TO RECEIVE CONTINUOUS HINGE. 4.DOOR TO RECEIVE CLOSER. 5.DOOR TO RECEIVE 42" PROTECTION PLATE (CORRIDOR SIDE) AND DOOR EDGE GUARD (BOTH ENDS). 6.REUSE ALL EXISTING HARDWARE, EXIT DEVICES, AND AUTO OPERATOR. REINSTALL HARDWARE AND AUTO OPERATOR AT NEW REQUIRED HEIGHTS. PROVIDE NEW CONTINUOUS HINGES. L 7.REUSE ALL EXISTING HARDWARE, EXIT DEVICES, AND MAGNETIC HOLD OPEN 2 DEVICES. REINSTALL HARDWARE AND MAG HOLD OPEN DEVICES AT NEW 3 REQUIRED HEIGHTS. PROVIDE NEW CONTINUOUS HINGES. 0 AREA OF CONSTRUCTION RC12 6 4 F-1NL-2 General Door Remarks a n 1.WOOD (SCWD) DOORS SHALL BE CHERRY, QUARTER-SLICES, WITH CUSTOM a FINISH EQUAL TO MARSHFIELD #237555C. i First Floor Reflected Ceiling Plan d 1/4" = 1'-0" Frame Elevations n I , l 2"SEE SCHEDULE2" e 1212.51314 m r REFER TO PARTITION TYPE FOR WALL a CONSTRUCTION C CONTINUOUS SEALANT EACH SIDE OF FRAME | GROUT FILLED HOLLOW l t METAL DOOR FRAME HOLLOW METAL DOOR AS SCHEDULED e IMAGING a 2 EQUIPMENT CONTROL e t B133 A10-1 B133A r 1A t i A12 9' - 11 5/8"8' - 8 1/8" DOUBLE-EGRESS(WINDOW BY RF SHIELDING S Door Head Detail p VENDOR- FRAME ELEVATION 1 A11A1 n SHOWN FOR INTENT ONLY) r 1 1/2" = 1'-0" EPO s a o i K Fd o 1 3 i 5 . 0 0 ° A# r Specific Plan Notes IN1 A18 n A A2 A23 e A1INFILL WALL ASSEMBLY. INFILL TO BE FLUSH AND LEVEL w/ EXISTING ADJACENT CONSTRUCTION. A2 ° A3 4' - 0" o H A18 0 i A2RF SHIELDING WALL ASSEMBLY PROVIDED BY CONTRACTOR/SHIELDING VENDOR. CONTRACTOR TO PROVIDE 5/8" GYPSUM BOARD ON MRI ROOM SIDE FOLLOWING 0 . 5 t M SHIELDING VENDOR INSTALLATION. REFER TO RF SHIELDING DWGS. 3 3/ A10-1 1 A3CLEAR VIEW WINDOW ASSEMBLY PROVIDED BY CONTRACTOR/SHIELDING VENDOR. REFER TO RF SHIELDING DWGS. a A14 . EPO PATIENT TOILET A4DOOR, FRAME, AND HARDWARE PROVIDED BY CONTRACTOR/SHIELDING VENDOR. REFER TO RF SHIELDING DWGS. B131A h v 1 - A5ISOCENTER OF MRI MAGNET. 0 N t 1 o A11 A A63T MAGNET FURNISHED AND INSTALLED BY OWNER. REFER TO SIEMENS VENDOR DWGS FOR BASE DETAIL AND B134B / 4 FLOOR LEVELING REQUIREMENTS. r n 0 A7A10 A7MOBILE PATIENT TABLE FURNISHED AND INSTALLED BY OWNER. REFER TO SIEMENS VENDOR DWGS FOR RECESSED e 0 A4 MOUNTING PLATE. EPO o A9 A8TURRET COVER FROM TOP OF MRI UNIT TO CEILING TO CONCEAL QUENCH VENT AND CABLES. REFER TO MRI MAGNET 7 A11 R A8 MS MANUFACTURER FOR EXACT LOCATION AND SIZE. 1 A9RF SHIELD PENETRATION PLATE PROVIDED BY SHIELDING VENDOR. A13 A N 1 A10MRI EQUIPMENT/CABINETS FURNISHED AND INSTALLED BY OWNER. REFER TO SIEMENS VENDOR DWGS. A5 ° 0 A11'EPO' EMERGENCY POWER OFF BUTTON. MOUNTED AT 5'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL MRI #2 0 A2 . STORAGE / ES DWGS. 5 PROJECT NO.DATE B134 A6 2 RF CLOSET A12'AB' ALARM BOX. MOUNTED AT 5'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL DWGS. 464 SF A22 B142 70474-25-17 A13'MS' MAGNET STOP. MOUNTED AT 6'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL DWGS. K.5 A14(2) FULL-HEIGHT CABINETS w/ REAR AND TOP ACCESS TO RF SHIELDING PENETRATION PLATE. REFER TO ELEVATION AND WAITING SECTION ON A10-1. REV.DATE B131 6/ A10-1 A15QUENCH TUBE EXIT WITHIN EXISTING MASONRY WALL. PROVIDE LINTEL AND FLASHING AS NECESSARY. COORDINATE HEIGHT, OPENING SIZE, AND LOCATION w/ RF RF SHIELDING AND MRI VENDOR DWGS. 14' - 0" A16REMOVE EXISTING DOUBLE EGRESS DOORS AND RAISE HEAD HEIGHT FOR NEW 8'-0"H DOORS. DOORS TO RECEIVE ALL NEW HARDWARE. REFER TO DOOR A2 A4 SCHEDULE AND DETAILS FOR ADDITIONAL INFORMATION. A17EXISTING MEDICAL GAS ZONE VALVE BOX B134A A18'IN#' PULL BOX. MOUNTED 2'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL DWGS. A20REMOVE AND REINSTALL EXISTING CHAIR BUMP AND HANDRAIL (HIGH/LOW) . PROVIDE NEW FASTENER DOWEL PLUGS STAINED TO MATCH. A21MRI KNOCK OUT PANEL. REMOVE 8'-0" X 8'-0" AREA OF EXISTING CORRIDOR WALL FOR MRI TRANSFER. INFILL WALL OPENING WITH LIKE CONSTRUCTION INCLUDING A17 A21A20 AN ADDITIONAL 1/2" LAYER OF GYPSUM BOARD ON CORRIDOR SIDE. 4"5' - 2"8' - 0"10' - 2" A22AT CONDUIT PENETRATIONS IN FLOOR, FULLY GROUT AROUND CONDUIT. 25' - 0 1/2"+/- 8' - 0" A23EXISTING PORTION OF WALL TO BECOME 1-HOUR SMOKE BARRIER. EXTEND ALL GYPSUM BOARD TO DECK AND PATCH ALL PENETRATIONS. PROVIDE APPROPRIATE FIREPROOFING AT ALL PENETRATIONS AND AT OVERHEAD DECK JOINT. PROVIDE ENGINEERING JUDGEMENT THAT EXISTING GYPSUM BOARD ON EACH SIDE OF WALL IS EQUIVALENT TO TYPE-X GYPSUM BOARD. CORRIDORCORRIDOR KEY PLANSET DESCRIPTION B1C15B1C09 General Plan Notes Construction PP = PUSH PLATE A15 Documents IC = INTERCOM MOB L IL = INDICATOR LIGHT *NOT ALL LOCATIONS MAY BE NOTED. REFER TO ELECTRICAL DRAWINGS. SHEET TITLE 1.ALL WALLS TO BE TYPE 1.5A UNLESS OTHERWISE NOTED. REFER TO AREA OF First Floor and Reflected AREA OF CONSTRUCTION WALL TYPES ON SHEET G1-1. HOSPITAL M 2.WHERE DIMENSION IS PRECEDED BY +/-, THE VALUE GIVEN IS FOR CONSTRUCTION Ceiling Plans P REFERENCE. ACTUAL DIMENSION SHALL BE DETERMINED BY OTHER 1/ A10-1 9 CONSTRAINTS, SUCH AS FINISH ALIGNMENT, OR EXISTING 4 : CONSTRUCTION. SEE PLAN FOR DETAILS AS NOTED. 2 5 3.REFER TO DOOR HARDWARE SCHEDULE FOR OPERATOR TYPE, HOLD : SHEET NUMBER 2 OPEN, CARD READERS AND OTHER DOOR SPECIALTY HARDWARE. 7 CENTRAL 4.REFER TO ENLARGED PLANS, ELEVATIONS, AND SECTIONS FOR First Floor Plan 1 True North PLANT 0 ADDITIONAL DIMENSIONS AND NOTATION. 2 / 1/4" = 1'-0" 5 2 / 4 A2-1 General Casework Notes CABINET MFG. SHALL FIELD VERIFY ALL WALL DIMENSIONS PRIOR TO FABRICATION. ALL GENERAL CASEWORK NOTES APPLY TO ALL CASEWORK THROUGH OUT SET 10 1.CONTRACTOR SHALL PROVIDE WOOD BLOCKING AS REQUIRED FOR A10-1 INSTALLATION OF ALL UPPER AND LOWER UNITS 2.EDGE OF COUNTERTOP TO BE 1 1/2" THICK. 3.CABINET MFG. SHALL COORDINATE WITH OWNER ALL LOCATIONS FOR "GROMMETS" QUANTITY WILL BE IDENTIFIED PER ELEVATION. ALL GROMMETS TO BE 3 1/2" DIA.WITH BLACK PLASTIC TRIM RING- LOCATE AT REAR OF COUNTER. OR AS DIRECTED BY OWNER. ALUMINUM TRIM TO MATCHRF SHIELDED WINDOW AND 4.ALL EXPOSED ENDS AND BACKS OF CASEWORK TO BE FINISHED SAME AS RF WINDOW ASSEMBLY BY RF FRAME BY SHIELDING VENDOR BALANCE OF EXPOSED SURFACE, SEE FINISH SCHEDULE. SHEIDLING VENDOR SEALANT 5.APPLY 1" RAD. ON ALL OUTER CORNERS OF COUNTER TOPS, U.N.O. 6.ALL END PANEL SUPPORT SHALL BE CONSTRUCTED W/ 1 1/2" LAMINATED 3/4" PLASTIC LAMINATE SILL PARTICLE BD. 7.ALL COUNTER TOPS SHALL EXTEND 1" BEYOND FRONT OF CABINET DRAWER MSKTD 3/4" PLASTIC LAMINATE SILL FACE. 2' - 6" 1" 8.ALL DRAWERS AND DOOR HANDLES SHALL BE TYPE " STANLEY, MODEL No. 4484- DIMMER SWITCHES, REFER 1 1/2" PLASTIC LAMINATE & Associates CHROME VS26D TO ELECTRICAL DWGS. COUNTERTOP (POSTFORM) 9.ALL BASE CABINET DEPTH SHALL BE 24" UNLESS NOTED OTHERWISE WITH 4" BACKSPLASH RF SHEILDINGEMERGENCY POWER OFF 10.ALL UPPER CABINET DEPTH SHALL BE 14" UNLESS NOTED OTHERWISE Architecture | Engineering | Interior Design (EPO), REFER TO CONTROL WINDOW 11.APPLY A 4" BACKSPLASH AT PERIMETER OF ALL COUNTER TOPS ELECTRICAL DWGS. 12.APPLY (1) ADJUSTABLE SHELF IN ALL BASE UNITS, AND (2) ADJUSTABLE SHELVES PLASTIC LAMINATE IN ALL. UPPER UNITS W/ EXCEPTION OF SINK BASE UNITS. (UNLESS NOTED COUNTERTOP (POSTFORM) 1715 Magnavox Way930 North Meridian OTHERWISE). ALL SHELVES IN CASEWORK TO BE ADJUSTABLE ON 1" CENTERS w/ 4"H BACKSPLASH Fort Wayne, IN 46804Indianapolis, IN 46204 VERTICALLY. 260.432.9337317.917.1190 13.ALL BASE UNITS SHALL HAVE A 4" H. x 3" D. TOE SPACE WITH RUBBER BASE BY EXISTING WALL RAKKS BRACKET EH-1824 FLOORING CONTRACTOR. BASE TO EXTEND TO ALL EXPOSED SIDES OF PARTITION www.msktd.com POWDER COATED FINISH CASEWORK. 14.REFER TO FLOOR PLAN FOR ALL WALL PARTITION TYPES 6" RADIUSED EDGES (TYP.) BLOCKING- TYPICAL RF SHIELDING 15.PAPER TOWEL DISPENSER LOCATED AT EVERY SINK. SUPPLIED BY OWNER, SS WALLRAKKS BRACKETS EH-1824 INSTALLED BY G.C. PULL BOX ASSEMBLY BYPOWDER COATED FINISH16.FOR ALL FILES DESIGNATED "BY OWNER"- CONTRACTOR TO VERIFY ACTUAL VENDOR HEIGHT OF FILES TO BE PURCHASED FOR COORDINATION, IF USED AS SUPPORT FOR COUNTER TOP 17.INSTALL CLEAR SEALANT CONTINUOUS BETWEEN TOP OF BACKSPLASH AND BASE. REFER TO WALL. EXISTING WALL INTERIOR FINISH PLANS 18.ALL HARDWARE FOR ANCHORING/SUPPORTING CASEWORK SHALL BE EDGE / CORNER CLEARANCE ABOVE FILTER CONCEALED. MOUNTING CLIPS SEE PLAN 19.PROVIDE 2X2 WOOD BLOCKING CONTINUOUS AT PERIMETER FOR COUNTERTOP/SHELF SUPPORT- PAINT TO MATCH WALL. EQ.4' - 0"EQ.6" 20.ALL COUNTERTOPS WITHOUT BACKSPLASH SHALL BE SCRIBED TO ADJACENT SEE PLAN WALLS/CASEWORK. 2' - 8 1/2"+/- 4' - 7"ANGLED TO VIEW 21.4 DIGIT NUMBER ABOVE OR BELOW CASEWORK REFERS TO HEIGHT AND WIDTH OF UNIT. 22.FILLER PANELS BY CABINET MANUFACTURER TO MATCH CABINETS. PROVIDE AND INSTALL. 3/4" PLASTIC LAMINATE REMOVEABLE ACCESS PANEL SIEMENS RF No. Casework SectionCasework Elevation " L " = DOOR/DRAWER TO BE LOCKED WITH KEY CYLINDER. COORDINATE WITH FILTER PLATE AR10500075 105 EDGE OF OPENING OWNER ON KEYING REQUIREMENTS BEYOND 1" = 1'-0" 1/2" = 1'-0" STATE OF " F " = FILE DRAWER, INTERIOR DIMENSIONS SHALL MEET STANDARD FILE DRAWER I DIMENSIONS. INSTALL HANGING FILE HARDWARE. I " UL " = UNDER UPPER CABINET LIGHT, REFER TO ELECTRICAL DRAWINGS, APPLY 2" OPENING LAMINATED APRON. Date Signed 4-25-17 3"1' - 9"3"1 1/8" SETBACK " S " = STRUCTURAL SUPPORT FOR COUNTER AND OR RECEPTION DESK. REFER TO CLEAR " AP " = REMOVABLE ACCESS PANEL. PROVIDE COUNTERSUNK ANCHORS. 3/4" PLASTIC LAMINATE BACK PANEL " K " = KEYBOARD TRAYS PROVIDED BY OWNER - 30" WIDE 1" PLASTIC LAMINATE SHELF 3/4" PLASTIC LAMINATE 4' - 7 1/8" " G " = GROMMETS, VERIFY LOCATION WITH OWNER PANEL DOOR 7 3/4" PLASTIC LAMINATE A10-1 ADJUSTABLE SHELF EXISTING WALLRAKKS BRACKET EH-1212 EXISTING WALL FINISHED WALL OPENING PARTITIONPOWDER COATED FINISH PARTITION (BEYOND)- BOTH SIDES OF MRI ROOM & 2 PROVIDE 1 1/2" LIP ON FRONT EQUIPMENT ROOM RF SHIELDING RF SHIELDING AND BACK OF SHELVING TO WALL 3 WALL LAMINATE FASCIA TRIM SUPPORT COIL WEIGHT TYP. ASSEMBLY BY ASSEMBLY BY PANEL 0 VENDOR PARTIAL SIDESPLASH VENDOR 3/4" PLASTIC LAMINATE 3' - 6 1/2" BEYOND 6 FIXED SHELF SEE PLAN ALL HARDWARE TO BE 4 NON-FERROUS 1" 1 1/2" PLASTIC LAMINATE 4 1" DOOR PULL 5 . COUNTERTOP (POSTFORM) 1 0 a - R 00 1 WITH 4" BACKSPLASH° ° 0 6 A 0 BLOCKING- TYPICAL . / "5 PLASTIC LAMINATE n 3 5 1 ADJUSTABLE SHELVES a BLOCKING- TYPICAL i PLASTIC LAMINATE DOOR PULL d FIXED SHELF 3/4" PLASTIC LAMINATE n 3/4" PLASTIC LAMINATE I BACK PANELPULL HANDLES ADJUSTABLE SHELF IMAGING , l ° EQUIPMENT(2) FULL HEIGHT 2-DOOR MRI #2 3/4" PLASTIC LAMINATE 0 0 . B133AB134CABINETS ADJUSTABLE SHELF 5 e 3 A R 1 6 " ALL HARDWARE TO BE 4 ALL HARDWARE TO BE 5 m . NON-FERROUS 0 0 2' - 3" ° r NON-FERROUS 1' - 9" " (CLEAR) 6 END PANEL / CABINET PLASTIC LAMINATE a (CLEAR) R BEYOND ADJUSTABLE SHELVES C BASE. REFER TO BASE. REFER TO 4"H BASE (REFER TO FINISH PLAN) INTERIOR FINISH PLANS INTERIOR FINISH PLANS | 1' - 0" 3" 2 1/4"3" +/- 2' - 8"2' - 6"2' - 6" SEE PLAN2' - 0"l SEE PLAN2' - 6" t (30" DEEP)(30" DEEP) SEE PLAN e SEE PLAN a e t r t i Casework SectionCasework SectionCasework ElevationCasework Detail 9742 S 1" = 1'-0" 1" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0" p n r s a o i Fd o i r n e o H i t M a . h v N 9 8 t 1" PLASTIC LAMINATE o SHELF A10-1 A10-1 8'-0" x 8'-0" KNOCK OUT r n 0 PANEL BEYOND e 0 o 7 R GYPSUM BOARD BULKHEAD (HIGH) 1 EXISTING WALLRAKKS BRACKET EH-1212 PARTITIONPOWDER COATED FINISH A N 1 6' - 0" PROJECT NO.DATE ALL HARDWARE TO BE RF SHIELDING WALLNON-FERROUS (14" DEEP) 70474-25-17 ASSEMBLY BY 13 VENDOR PARTIAL SIDESPLASH 1' - 6"3' - 0"1' - 6" BEYOND REV.DATE MEDICAL GAS OUTLETS, REFER TO PLUMBING DRAWINGS PLASTIC LAMINATE SHELF ON SEE PLAN RAKKS BRACKETS EH-1212 Second Floor 1 1/2" PLASTIC LAMINATE 115' - 4" POWDER COATED FINISH COUNTERTOP (POSTFORM) 5"5"NEW MRI #2 CRYOGEN WITH 4" BACKSPLASH PLASTIC LAMINATE COUNTERTOP SS QUENCH VENT CAP (POSTFORM) w/ 4"H SIDE & BACKSPLASH BLOCKING- TYPICAL MVOMANOWAGD SIDESPLASH TO EXTEND TO EDGE EXISTING MRI #1 SLIDE OF ADJACENT WALL- REFER TO CRYOGEN QUENCH B134A FLOOR PLAN VENT CAP 3/4" PLASTIC LAMINATE BACK PANEL 2-DOOR LOWER CABINET WITH ADJUSTABLE SHELVES 3/4" PLASTIC LAMINATE WP-1WP-1 ADJUSTABLE SHELF EXISTING DEFLECTION OPEN LOWER CABINET WITH JOINT ALL HARDWARE TO BE ADJUSTABLE SHELVES SET DESCRIPTION NON-FERROUS EXISTING ADJACENT 1' - 9 3/4" FINISHED END PANEL (BOTH SIDES) WALL ASSEMBLY Construction END PANEL / CABINET (CLEAR DEPTH) 4"H BASE (REFER TO FINISH PLAN) BEYOND Documents BASE. REFER TO 4"H BASE (REFER TO FINISH PLAN) 8' - 0"5' - 6" INTERIOR FINISH PLANS 2' - 0"2' - 0"2' - 0" SHEET TITLE 14' - 0" 3" (24" DEEP)(24" DEEP)(24" DEEP) Casework Elevations SEE PLAN2' - 0" 6' - 0"First Floor M 100' - 0" and Details P SEE PLAN 9 1 : 5 5 : SHEET NUMBER 1 7 Casework SectionInterior ElevationCasework ElevationPartial East Exterior Elevation 1 8631 0 2 1" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0" 1/4" = 1'-0" / 5 2 / 4 A10-1 MSKTD & Associates Architecture | Engineering | Interior Design 1715 Magnavox Way930 North Meridian Fort Wayne, IN 46804Indianapolis, IN 46204 260.432.9337317.917.1190 www.msktd.com No. AR10500075 STATE OF I I Date Signed 4-25-17 2 3 0 6 4 a n a i d n I , l e 1212.51314 m r a C | l t B133 General RemarksSpecific Remarks CONTROL e ETR a (APPLICABLE THROUGHOUT ALL AREAS OF CONSTRUCTION) (SEE FINISH SCHEDULE FOR LOCATION) B133A ETR,PT-1 e B146 t IMAGING ETR r OFFICE A.FOR ALL FLOORING MATERIALS INSTALLED ON GRADE OR BELOW GRADE: THE FLOORING t i 1.SEE ELEVATIONS FOR CASEWORK DETAILS. EQUIPMENT ETR G CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE IN THEIR BID PRICES ALL REQUIRED 2.SEE FINISH FLOOR PLAN FOR FLOORING PATTERN. 1,6,8ETR,VCT-1 NN II S MATERIALS AND LABOR FOR A COMPLETE INSTALLATION THAT MEETS THE T A 3.INSTALL NEW VCT WHERE INDICATED ON FINISH FLOOR PLAN. INSTALL RESILIENT BASE ETR, RB-1 S TM I MANUFACTURER'S TOTAL SYSTEM PERFORMANCE. THIS INCLUDES ALL PREP MATERIALS p AND PAINT ON NEW WALL TO MATCH EXISTING. ETR, P-1 E XC O AND LABOR REQUIRED TO MEET MANUFACTURER'S WRITTEN SPECIFICATIONS FOR EVTR 4.PATCH VCT WHERE NECESSARY. INSTALL RESILIENT BASE ON NEW WALL TO MATCH n ETR r MOISTURE, PH, SMOOTHNESS OR LEVELNESS OR CLEANLINESS OF NEW OR EXISTING EXISTING. INDICATED WITH DASHED LINE. 3,9 s a SUBSTRATES, ETC. THIS INSTALLATION SHALL INCLUDE THE MANUFACTURER'S SPECIFIED CG 5.INSTALL NEW VINYL WALL COVERING AND RESILIENT BASE AT NEW WALL AND ADJACENT. o i K ADHESIVES, SEALERS, ETC. SEE FINISH FLOOR PLAN FOR LOCATION. INDICATED WITH DASHED LINE. FINISHES ARE B.PAINT ALL HOLLOW METAL DOORS, WINDOW FRAMES, AND DOOR FRAMES P-2, SEMI- TO MATCH EXISTING. HANDRAIL AND BUMP RAILS THAT WERE REMOVED ARE TO BE Fd o CG i GLOSS. 1 REINSTALLED - r T C.PATCH AND MATCH ALL FINISHES DUE TO CONSTRUCTION. 6.INFILL CARPET TILE AT NEW DOOR OPENING. FLOORING TYPE TRANSITION TO OCCUR C n D.SEE REFLECTED CEILING PLAN AND DETAILS FOR LOCATION AND HEIGHT OF CEILINGS. V UNDER DOOR IN THE CLOSED POSITION. e E.EVERY TRANSITIONS BETWEEN FLOORING MATERIALS TO BE FLUSH. IT IS FLOORING 7.INSTALL WP-1 ON EAST AND SOUTH WALLS WHERE INDICATED WITH A HEAVY DASHED o H i CONTRACTOR'S RESPONSIBILITY TO LEVEL SUBSTRATE AS NECESSARY FOR MATERIALS TO LINE ON FINISH FLOOR PLAN. CORNER GUARD TO BE PLASTIC COVER WITH ALUMINUM B131A t M B144TRANSITION AT LEVEL HEIGHT, INCLUDING GRINDING OR BUILDING UP OF CONCRETE. ALL RETAINER, 7'-0" HEIGHT, TO MATCH WALL PROTECTION COLOR. SEE FINISH FLOOR PLAN PATIENT B147 READINGTRANSITION STRIPS TO BE STAINLESS STEEL EQUAL TO SCHLUTER SYSTEMS AND MUST FOR LOCATION MARKED WITH CG SYMBOL. a TOILET . OFFICE MEET ADA; ALL PROFILES TO BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION. 8.INSTALL NEW PAINT ON WALLS INDICATED WITH DASHED LINES ON FINISH FLOOR PLAN. h v TRANSITION STRIPS ARE UNNECESSARY BETWEEN LIKE MATERIALS (CARPET TO CARPET, 9.CORNER GUARD TO BE 7'-0" HIGH STAINLESS STEEL TO MATCH HOSPITAL STANDARD. N t LINOLEUM TO VINYL, ETC). LOCATION MARKED ON FINISH FLOOR PLAN WITH CG SYMBOL. o F.ALL FLOORING MATERIAL TRANSITIONS TO BE CENTERED UNDER DOOR IN CLOSED r n 0 POSITION. G.PAINT VENTS, DIFFUSERS, ELECTRICAL PANELS, FIRE CABINETS (UNLESS THEY ARE e 0 Room Finish Tag Legend PT-1/RB-1 NATURAL ALUMINUM OR STAINLESS STEEL), ETC. TO MATCH WALL COLOR. o 7 R ROOM # AND NAME 1 FLOOR FINISH RB-1 BASE FINISH A N 1 WALL FINISH Color Legend CEILING FINISH PROJECT NO.DATE B142 REMARKS FLOOR STORAGE / ES 70474-25-17 CARPET TILE CLOSET K.5 B131CPT-1ATTIC STOCK OF CORRIDOR CARPET TILE (INTERFACE ZEN WILLOW) ETR,VCT-1 B134 MRI #2 WAITING ETR, RB-1 B148 REV.DATE SV-1,SV-2 SHEET VINYL P-1 OFFICE RB-1 SV-1TEKNOFLOR; FORESTSCAPES; HARVEST CHERRY 52202 ETR PT-3,WP-1 SV-2TEKNOFLOR; FORESTSCAPES; COLONIAL MAPLE 31026 6 4 5 ACT-1 . 0 1' - 5 1/4"1' - 5 1/4" 0 1,2,7 ° VINYL COMPOSITION TILE VCT-1MANNINGTON, ESSENTIALS, WARM BEIGE 127 CPT-X BASE RUBBER RB-1JOHNSONITE- 4" HIGH COVED #29 MOON ROCK VWC-1/RB-1 3' - 0"VWC-1/RB-1 B1C09 WALL B1C15 CORRIDOR PAINT CORRIDOR P-1SHERWIN WILLIAMS; CRISP LINEN SW6378 ETR, CPT-X P-2SHERWIN WILLIAMS; INTERACTIVE CREAM SW6113 ETR, RB-1 P-3SHERWIN WILLIAMS; OYSTER BAY SW6206 ETR,VWC-1 ETR VINYL WALL COVERING KEY PLANSET DESCRIPTION 5,6 VWC-1MDC; VYCON OASIS Y449150A; GRASSCLOTH 40150540 Construction WALL PROTECTION WP-1KOROGUARD; K-3; PORCELAIN; INSTALL FROM TOP OF BASE TO 40" A.F.F. Documents MOB L CASEWORK SHEET TITLE PLASTIC LAMINATE PL-1PIONITE; MILLWORK CHERRY; SUEDE FINISH; WC431-S PL-2PIONITE; IL PALIO PAPEL; SUEDE FINISH; AV981 AREA OF First Floor Interior Finish AREA OF CONSTRUCTION HOSPITAL M CONSTRUCTION CEILING Plan P ACOUSTICAL TILES 1 2 ACT-1ARMSTRONG OPTIMA; 24" x 24" SQUARE LAY-IN #3152; 15/16" ALUMINUM GRID : 5 COMPLIANT WITH MRI ROOM; 5 : First Floor Finish Plan SHEET NUMBER 1 EXISTING FINISHES 7 CENTRAL 1 1/4" = 1'-0" EXISTING TO REMAIN True North PLANT 0 ETREXISTING FINISH IS TO REMAIN; PATCH AND REPAIR AS NECESSARY FOR 2 / NEW CONSTRUCTION 5 2 / 4 I2-1