HomeMy WebLinkAboutIUHN MRI CD 04-25-2017
North Hospital
MSKTD
& Associates
Architecture | Engineering | Interior Design
MRI Shell Build-out
1715 Magnavox Way930 North Meridian
Fort Wayne, IN 46804Indianapolis, IN 46204
260.432.9337317.917.1190
www.msktd.com
Drawing Index
ArchitecturalPlumbingMechanicalElectrical
G1-1Titlesheet, Drawing Index and General InfoP0-1Plumbing Symbols and AbbreviationsM0-1Mechanical Symbols and AbbreviationsE0-1Electrical Symbols and Abbreviations
G1-2Life Safety Plans and Code SummaryP2-1First Floor Plumbing PlansM2-1First Floor Mechanical PlansE1-0Overall Ground Floor Plan
M3-0Lower Level Mechanical Piping PlanE1-1Overall First Floor Plan
A0-2Overall Floor PlanM3-1First Floor Mechanical Piping PlansE2-1First Floor Lighting Plans
No.
AR10500075
A1-1First Floor Demo and Structural PlansM4-1Cryogen Vent RoutingE3-1First Floor Power and Systems Plans
STATE OF
I
A2-1First Floor and Reflected Ceiling PlansM6-1Mechanical Schedules and Temp. ControlE6-1Electrical Schedules
I
Schematics
A10-1Casework Elevations and DetailsE6-2Electrical Schedules
Date Signed 4-25-17
M7-1Mechanical Details
E7-1Electrical Details
M7-2Mechanical Details
I2-1First Floor Interior Finish Plan
M7-3Mechanical Details
2
3
0
6
4
a
n
a
i
d
n
I
,
l
e
m
r
a
C
General Demolition NotesGeneral Reconstruction NotesGeneral Ceiling NotesGraphic SymbolsContacts
|
l
t
Architectural:Structural:
e
THESE NOTES SHALL APPLY TO ALL DEMOLITION
THESE NOTES APPLY TO ALL FLOOR PLANS, AND TO
THESE NOTES APPLY TO ALL CONSTRUCTION DRAWINGS AND TO ALL
a
PROJECT NORTH
DRAWINGS AND TO ALL CONTRACTORS AND/OR
e
ALL CONTRACTORS AND/OR SUBCONTRACTORS
CONTRACTORS AND/OR SUBCONTRACTORS THAT WORK WITHIN THIS
Kyle HardieJim Schmidt
NORTH
t
r
SUBCONTRACTORS THAT WORK ON THIS PROJECT.
THAT WORK ON THIS PROJECT.
BUILDING.
ARROW
t
i
MSKTD & AssociatesMSKTD & Associates
TRUE NORTH
NEW DOOR
1.ALIGN ALL CEILING AND BULKHEAD REVEALS, CONTROL OR SEISMIC JOINTS WITH
S
1.OWNER WILL REMOVE ALL FURNISHINGS, LOOSE EQUIPMENT, SUPPLIES, ETC.... PRIOR
1.CONTRACTORS SHALL BE RESPONSIBLE FOR VISITING THE SITE TO BECOME
101A
kfh@msktd.comjrs@msktd.com
AND
THE ADJACENT REVEAL, CONTROL OR SEISMIC JOINTS IN WALLS INDICATED ON
TO CONSTRUCTION COMMENCING.p
FAMILIAR WITH AND VERIFY THE EXISTING CONDITIONS. THESE DEMOLITION
FRAME
ELEVATIONS.
2.ALL EQUIPMENT AND MATERIALS LABELED AS "SALVAGE" OR "RELOCATE AS DIRECTED
DRAWINGS SHALL SERVE TO AID THE CONTRACTOR IN HIS EVALUATION OF THE
NEW
n
317.917.1190260.432.9337
X
2.ALL CEILING AND BULKHEAD HEIGHTS INDICATED ARE TO FINISHED FACE OF
r
BY OWNER" SHALL BE REMOVED, PROPERLY PROTECTED AND TRANSPORTED TO A
EXTENT OF DEMOLITION; BUT SHALL NOT BE HELD TO BE ALL INCLUSIVE.
COLUMN
s
GYPSUM BOARD OR TO THE BOTTOM FACE OF ACOUSTICAL CEILING TILE PAD,
SPECIFIC
a
LOCATION ON THE PREMISES AS DIRECTED BY THE OWNER.
2.CONTRACTORS SHALL BE RESPONSIBLE FOR ALL DEMOLITION REQUIRED FOR THE
LINE
o
1
i
UNLESS NOTED OTHERWISE.
CONSTRUCTION
3.ALL GENERAL CONTRACTORS AND THEIR SUBCONTRACTORS SHALL BE RESPONSIBLE
INSTALLATION OF NEW CONSTRUCTION AND AS NECESSARY TO FULFILL THE
Mechanical & Plumbing:Interiors:
3.CEILING CONTRACTOR TO PROVIDE ALL CEILING GRID TO SUPPORT HVAC SUPPLY
NOTES
FOR VISITING THE CONSTRUCTION SITE TO BECOME FAMILIAR WITH ALL EXISTING
Fd
PURPOSE AND INTENT OF THE FINISHED WORK, WHETHER OR NOT IT IS
o
DIFFUSERS AND RETURN GRILLS.
i
CONDITIONS WHICH AFFECT THAT SPECIFIC PORTION OF THEIR WORK. ANY CONFLICTS
SPECIFICALLY SHOWN OR NOTED IN THESE DOCUMENTS. THE CONTRACTOR
Kevin HuttonSarah Savage
EXISTING
4.DEVICES OTHER THAN LIGHTING AND DIFFUSERS ARE SHOW IN APPROXIMATE
r
OR APPARENT DEFICIENCIES MUST BE SUBMITTED TO THE ARCHITECT IN WRITING
X
SHALL BE RESPONSIBLE FOR ALL ITEMS CALLED TO BE REMOVED THROUGH OUT
n
COLUMN LINE
LOCATIONS, FINAL LOCATION TO BE COORDINATED WITH ALL TRADES AND
SPECIFIC
PRIOR TO BIDDING.
THE ENTIRE SET OF DOCUMENTS.
e
MSKTD & Associates
1 Genesis Engineering
ARCHITECT.
DEMOLITION
4.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMING IN WRITING THE
o
H
3.CONTRACTORS SHALL FIELD INSPECT ALL DEMOLITION WORK PRIOR TO REMOVAL,
5.AT LOCATIONS WHERE GYPSUM BOARD CEILINGS ARE INDICATED, THE
NOTES
i
OWNER ON A WEEKLY BASIS OF THE CONSTRUCTION SCHEDULE FOR THE
TO INSURE SUCH REMOVAL DOES NOT IMPAIR STRUCTURAL INTEGRITY OF THE
khutton@genesis-sjs@msktd.com
t
CONTRACTOR HAS THE OPTION TO USE LIGHT GAGE METAL FRAMING OR
M
APPROACHING TWO WEEKS CONSTRUCTION ACTIVITY. ANY STORAGE OF MATERIALS,
EXISTING BUILDING. IF THE INSPECTION INDICATES THAT THE STRUCTURAL
SUSPENDED GYPSUM BOARD GRID UNLESS OTHERWISE DETAILED. THE
DETAIL NUMBER
SIM
ACCESS OR EGRESS PROBLEMS, TRAFFIC FLOW OR NORMAL OWNER OPERATIONS
a
INTEGRITY MAY BE IMPAIRED, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY.
.
engineering.com317.917.1190
ROOM NAME
1
CONTRACTOR WILL COORDINATE ANY MODIFICATIONS WITH THE OTHER TRADES
ROOM
WHICH ARE TO BE AFFECTED MUST BE PROTECTED AND/OR AGREED UPON BY THE
SECTION
4.REMOVE ALL DAMAGED OR EXISTING FINISH MATERIALS FROM REMAINING WALLS,
101
h
v
ON THE PROJECT. THE CEILING CONTRACTOR'S FINAL MEANS AND METHODS WILL
NAME
OWNER. ALL COSTS SHALL BE INCURRED BY THE GENERAL CONTRACTOR.A5-1
PARTITIONS AND COLUMNS (GYPSUM BOARD,WALL FABRIC, PANELING, TILE,
317.501.9737
N
NOT CONFLICT WITH THE WORK OF OTHERS OR THE INTENT OF THESE
AND
SHEET NUMBER
t
5.THE GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY WOOD BLOCKING FOR
MASONRY, CONCRETE, ETC...). PATCH WALLS AND COLUMNS AS REQUIRED TO
o
DOCUMENTS.
NUMBER
ALL TRADES. THIS BLOCKING SHALL BE FIRE RETARDANT.
RECEIVE NEW FINISH MATERIALS.
r
6.WHERE EXISTING SUSPENDED ACOUSTICAL CEILINGS ARE SCHEDULED TO
n
0
6.ANY PLASTER WORK REQUIRING NEW FINISH SHALL BE SMOOTH, SOUND AND IN A
5.CONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING, INSTALLING AND
Electrical:Construction Manager:
REMAIN, CUT AND PREP THE CEILING GRID IN PREPARATION FOR REPAIRING.
FLUSH PLANE BEFORE FINISH APPLICATION. CONTRACTOR SHALL REPAIR THE
MAINTAINING DUST TIGHT TEMPORARY CONSTRUCTION BARRIERS TO ALL AREAS
e
0
SALVAGE ENOUGH CEILING PADS FOR RECONSTRUCTION. STORE AND PROTECTx /Xx-xELEVATION
3.5A
SURFACE FOR THE NEW FINISH AS SCHEDULED.
1i
PARTITION TYPE
WITHIN THE CONSTRUCTION LIMIT LINES, DURING THE CONSTRUCTION PROCESS.
Josh WalkeCarl Dennin
o
ALL MATERIALS. USE NEW MATCHING MATERIALS FOR RECONSTRUCTION AS
SYMBOL
7.ALL FIRE RATED WALLS AND FLOOR PENETRATIONS MUST COMPLY WITH ASTME-814.
7
LOCATIONS SHALL BE COORDINATED WITH THE OWNER AND ARCHITECT.
R
REQUIRED.
SHEET NUMBER
8.ITEMS SHOWN IN LIGHTER PEN WEIGHT ARE EXISTING TO REMAIN.
Genesis EngineeringMesser Construction Co.
6.ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED
1
7.SEE THE ROOM FINISH SCHEDULE FOR ADDITIONAL COMMENTS REGARDING
9.REMOVE ALL DAMAGED GYPSUM BOARD, MASONRY, CONCRETE, PLASTER, ETC...
WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTORS DAILY.
MATERIALS AND FINISHES.
DETAIL NUMBER
FROM EXISTING SURFACES AND REPAIR TO MATCH ADJACENT CONSTRUCTION PRIOR
WINDOW
khutton@genesis-CDennin@messer.com
7.PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO
1t A N 1
8.THE DESIGNATION 'CJ' INDICATES GYPSUM BOARD CONTROL JOINTS. WHERE
TO REFINISHING. ALL SURFACES SHALL BE SMOOTH AND IN A FLUSH PLANE.
ELEVATION
REMAIN" FIXTURES AND EQUIPMENT REQUIRED TO REMAIN IN PLACE DURING
INDICATED PROVIDE USG #093 ZINC CONTROL TYPICAL. INSTALL JOINT THROUGH
10.ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED
SYMBOL
engineering.com317.576.9250
CONSTRUCTION.
DETAIL NUMBER SIM
THE FULL EXTENTS OF ANY GYPSUM CEILING OR BULKHEAD. WHERE THE GYPSUM
PROJECT NO.DATE
WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTORS DAILY.
1
8.REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION. ALL CONTRACTORS
CEILING COMPONENT MEETS A GYPSUM WALL, EXTEND THE CONTROL JOINT
PLAN DETAIL
11.PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO
317.927.8307 ext. 5
A2-1
SHALL COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK, TO BE
TOILET ACCESSORY 70474-25-17
A
DOWN TO THE FLOOR TYPICAL.
REMAIN" FIXTURES AND EQUIPMENT REQUIRED TO REMAIN IN PLACE DURING
SHEET NUMBER
ASSURED THAT THEIR WORK IS COMPLIMENTARY TO THE WORK OF ALL OTHER
9.THE GENERAL CONTRACTOR WILL PROVIDE AND INSTALL ALL SUPPLEMENTAL
CONSTRUCTION.
Brad Bastin
CONTRACTORS AND COMPLETE IN ALL RESPECTS.
AND/ OR MISCELLANEOUS STEEL FRAMING AS REQUIRED BY THEMSELVES OR BY
12.REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION. ALL CONTRACTORS SHALL
REV.DATE
9.UNLESS NOTED OTHERWISE ALL DEMOLITION MATERIAL BECOMES THE PROPERTY
THEIR SUBCONTRACTORS FOR THE INSTALLATION OF THE EQUIPMENT
BBastin@messer.com
COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK, TO BE ASSURED THAT
OF THE CONTRACTORS AND IS TO BE REMOVED FROM THE PROPERTY, IN A LEGAL
XXX
SCHEDULED AND SPECIFIED. NOT ALL OF THE REQUIRED SUPPORT STEEL MAY BE
TAG IDEQUIPMENT TAG
WORK IN EITHER OF THESE AREAS IS COMPLEMENTARY TO THE OTHER AND
MANNER. THE OWNER RESERVES THE RIGHT AND SHALL BE GIVEN THE
DETAILED OR CALLED OUT FOR IN THESE DOCUMENTS. COORDINATE ALL
317.576.9250
COMPLETE IN ALL RESPECTS. ANY CONFLICTS OR APPARENT DEFICIENCIES MUST BE
OPPORTUNITY TO CLAIM ITEMS WHETHER OR NOT THOSE ITEMS WERE
REQUIREMENTS WITH THE SPECIFICATIONS, EQUIPMENT SUPPLIERS AND
SUBMITTED TO THE ARCHITECT IN WRITING PRIOR TO BIDDING.
SPECIFICALLY NOTED FOR REMOVAL, RELOCATION, OR AS RETURNED TO
SUBCONTRACTORS. THERE WILL BE NO CHANGE ORDERS TO THE PROJECT FOR
13.ALL WALL HUNG CASEWORK REQUIRES CONTINUOUS HORIZONTAL WOOD BLOCKING
XX-YYYx 1
TAG IDFURNITURE TAG
OWNER AND SAME SHALL BE RETURNED TO OWNER.
SUPPLEMENTAL STEEL WHERE OMISSIONS MAY OCCUR IN THE BIDDING
BETWEEN STUDS AT TOP AND BOTTOM OF CASEWORK. BRACE WALL TO DECK AS
x QUANTITY
10.THE CONTRACTOR RESPONSIBLE FOR GENERAL DEMOLITION WORK SHALL
DOCUMENTS.
REQUIRED.
COORDINATE ANY AND ALL ASBESTOS REMOVAL WITH THE OWNER. ALL ASBESTOS
14.ALL DIMENSIONS ARE FROM FACE OF BASE MATERIAL (STUD/CMU) TO FACE OF BASE
REMOVAL WILL BE PREFORMED BY A LICENSED ASBESTOS REMOVAL
MATERIAL (STUD/CMU) UNLESS NOTED OTHERWISE.
CONTRACTOR. THIS TYPICALLY INCLUDES FLOOR TILE, TILE MASTIC AND PIPE
15.PORTIONS OF THE BUILDING SHALL BE OCCUPIED DURING CONSTRUCTION. THE
INSULATION.
Partition Types
GENERAL CONTRACTOR SHALL FOLLOW THE FOLLOWING LIFE SAFETY ISSUES.
11.ITEMS SHOWN IN LIGHTER PEN WEIGHTS ARE EXISTING TO REMAIN.
FAILURE TO LIST ALL LIFE SAFETY ISSUES DOES NOT RELIEVE THE CONTRACTORS
12.GENERAL CONTRACTOR RESPONSIBLE FOR PATCHING ALL REMOVED ELECTRICAL
NOTE: FLOOR TO FLOOR HEIGHT FROM FIRST TO SECOND IS 15'- 4"
FROM COMPLYING WITH FEDERAL, STATE AND LOCAL CODES, THE CONTRACTUAL
OUTLETS. ELECTRICAL CONTRACTOR TO PROVIDE GENERAL CONTRACTOR WITHa.INSURE ALL EXITS PROVIDE FREE AND UNOBSTRUCTED EGRESS. STAFF
AGREEMENT BETWEEN THE CONTRACTOR AND OWNER, AND OTHER GOVERNING
QUANTITIES.AND PERSONNEL SHALL RECEIVE TRAINING AND WRITTEN NOTIFICATION IF
5 7/8"
4 7/8"4 1/4"5 3/8"
BODIES WHICH HAVE JURISDICTION ON THIS PROJECT. THE FOLLOWING ARE INTERIM
13.REMOVE EXISTING FINISHES AS REQUIRED TO INSTALL NEW FINISHES. PREPARE
ALTERNATIVE EXITS MUST BE DESIGNATED.
LIFE SAFETY CODE ISSUES WHICH ARE SPECIFIC TO THIS PROJECT AND MUST BE
SURFACES TO RECEIVE NEW FINISH AS PER FINISH MANUFACTURER'S PRINTEDb.INSURE FREE AND UNOBSTRUCTED ACCESS TO EMERGENCY
ADDRESSED:
INSTRUCTIONS, SEE FINISH SCHEDULE FOR NEW FINISHES.DEPARTMENTS OR SERVICES FOR EMERGENCY FORCES. COORDINATE
SET DESCRIPTION
14.REMOVE EXISTING CEILINGS AND CEILING SUPPORT SYSTEM WHERE NEW
WITH OWNER AND ARCHITECT.
5/8" GYPSUM BOARD
CEILINGS ARE INDICATED, UNLESS OTHERWISE NOTED.c.INSURE FIRE ALARM, DETECTION AND SUPPRESSION SYSTEMS ARE NOT
3 5/8" METAL STUD3 5/8" METAL STUD3 5/8" METAL STUD
(BOTH SIDES)
IMPAIRED. A TEMPORARY, BUT EQUIVALENT, SYSTEM SHALL BE PROVIDED,
AT 16" O.C.AT 16" O.C.AT 16" O.C.
Construction
INSTALLED AND TESTED PRIOR TO ANY EXISTING FIRE SYSTEM BEING
INDICATES EXISTING WALL TO BE REMOVED IN ITS
5/8" GYPSUM BOARD5/8" GYPSUM BOARD5/8" GYPSUM BOARD
IMPAIRED.
ENTIRETY.1 1/2" FURRING
Documents
(BOTH SIDES)(ONE SIDE)(BOTH SIDES)
d.INSURE TEMPORARY CONSTRUCTION PARTITIONS ARE SMOKE TIGHT AND
1 3/4" RF WALL
BUILT OF NON COMBUSTIBLE MATERIALS. THESE PARTITIONS SHALL BE
INDICATES EXISTING DOOR, FRAME AND ASSOCIATED
SHEET TITLE
1/2" GYPSUM BOARD
PANEL WITH 2"
COORDINATED WITH THE OWNER AND ARCHITECT.
HARDWARE TO BE REMOVED IN ITS ENTIRETY. SEE DOOR
(CORRIDOR SIDE ONLY-EXTEND
INSULATION
e.SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS OF THE
SCHEDULE FOR ITEMS TO BE SALVAGED AND REUSED IN
TO 6" ABOVE FINISHED CEILING)
Titlesheet, Drawing
BUILDING.
OTHER AREAS.
2" AIR GAP
f.DEVELOP AND ENFORCE STORAGE, HOUSEKEEPING AND DEBRIS REMOVAL
M
Index and General Info
P
PROCEDURES THAT REDUCE THE FLAMMABLE AND COMBUSTIBLE FIRE
SOUND ATTENUATIONSOUND ATTENUATIONSOUND ATTENUATION
EXISTING WALL
7
LOAD TO THE LOWEST LEVEL NECESSARY FOR DAILY OPERATIONS.
BLANKET INSULATIONBLANKET INSULATIONBLANKET INSULATION
4
CONSTRUCTION
:
g.IOSHA REQUIRES MATERIAL SAFETY DATA SHEETS (MSDS) FOR ALL
1
MATERIALS BEING USED OR STORED ON THIS PROJECT BE MADE
4
:
SHEET NUMBER
AVAILABLE TO ALL WORKERS ON THIS JOBSITE. COPIES MUST BE
2
1 HR RATED
PROVIDED TO THE OWNER'S DIRECTOR OF SECURITY, IMMEDIATELY, AS
7
1.5A1.5B1.5C1.5NRF Wall
1
(UL DESIGN # U419)
WORK BEGINS.
0
2
h.SECURE ALL TOOLS AND CONSTRUCTION MATERIALS DURING BREAKS AND
/
EXTEND TO BOTTOMEXTEND TO BOTTOM OF DECK ABOVEEXTEND TO BOTTOMEXTEND TO BOTTOMFURNISHED AND INSTALLED BY RF SHIELDING
5
NON-CONSTRUCTION HOURS.
OF DECK ABOVEEXCEPTION W/ TYPE 'X' GYPSUM BOARDOF DECK ABOVEOF DECK ABOVEVENDOR UNLESSS OTHERWISE NOTED
2
/
4
G1-1
Code SummaryLife Safety Legend Code Citations
APPLICABLE CODES:
LIFE SAFETY CODE REVIEW (Per NFPA 101, 2012 Edition)
Chapter 18: New Healthcare
NFPA 101 Life Safety Code2012 Edition. Chapter 18 New Healthcare Occupancies.
SUITES (Non-Rated (Smoke Resistant) Corridors):
Chapter 19: Existing Healthcare
BUILDING/DWELLING CODE2014 Indiana Building Code (675 IAC 13-2.6)
STRUCTURAL CODE2014 Indiana Building Code (2012 IBC, ANSI A-117.1-2009, ASCE-7-2005)
MECHANICAL CODE2014 Indiana Mechanical Code (2012 IMC with state amendments)
18.2.5.7.1.1- Suites shall be separated from the remainder of the building, and from other
ELECTRICAL CODE2009 Indiana Electrical Code (2008 NEC with state amendments)
suites, by walls and doors meeting corridor wall construction requirements.
CONSTRUCTION LEGEND
FIRE/LIFE SAFETY CODE2014 Fire Code (675 1AC 22-2.5) consisting of 2012 IFC with state amendments
ACCESSIBILITY CODE2014 Indiana Building Code, Chapter 11, and ICC standard A117.1 2009 edition
19.2.5.7.1.1- Suites shall be separated from the remainder of the building, and from other
ENERGY CODE2010 Indiana Energy Conservation Code (ASHRAE 90.1- 2007 with state amendments)
suites, by walls and doors meeting corridor wall construction requirements.
BUILDING:Hospital
2-HOUR FIRE BARRIER(Occupancy Separation)
18.2.5.7.1.3 (A)- Intervening rooms shall not be hazardous areas as defined by 18.3.2.
OCCUPANCY:Group I-2, InstitutionalIBC sec. 308.4
19.1.3.4- Occupancy separation.
19.2.5.7.1.3 (A)- Intervening rooms shall not be hazardous areas as defined by 18.3.2.
CONSTRUCTION TYPEType I-AIBC Table 601
MSKTD
18.1.3.4.1- Occupancy separation.
18.2.5.7.2.1- (A) Sleeping Suites shall have access directly to exit corridor. (B) Where two
AUTOMATIC SPRINKLERS:Yes– Fully-Sprinkled
& Associates
or more exit access doors are required from a suite, one of the exit doors shall be permitted
19.2.2.4 Smokeproof Enclosures- "Smokeproof enclosures complying with 7.2.3 shall be
AREA
P to be directly to an exit stair, exit passageway or exit door to the exterior. (C) Sleeping
permitted."
Architecture | Engineering | Interior Design
suites shall be provided with constant staff supervision within the suite. (D) Sleeping suites
ALLOWABLE BUILDING AREA:UnlimitedIBC Table 503
shall be arranged to provide one of the following (a) The patient sleeping rooms shall be
7.2.3.3- "A smokeproof enclosure shall be continuously enclosed by barriers having a 2-
FLOOR AREAS (GROSS):
arranged to allow for direct supervision form a normally attended location within the suite or
hour fire resistance rating from the highest level of exit discharge. Where a vestibule is
1715 Magnavox Way930 North Meridian
(b) any patient rooms without direct supervision shall be provided by automatic smoke
Fort Wayne, IN 46804Indianapolis, IN 46204
used, it shall be within the 2-hour rated enclosure and shall be considered part of the
EXISTING:RENOVATION:
detection.
260.432.9337317.917.1190
Lower Level:83,364 SFN/A
smokeproof enclosure."
First Floor:88,200 SF1,940 SF
www.msktd.com
Second Floor:87,990 SFN/A
19.2.5.7.2.1- (A) Sleeping Suites shall have access directly to exit corridor. (B) Where two
18.2.2.4 Smokeproof Enclosures- "Smokeproof enclosures complying with 7.2.3 shall be
Third Floor:73,802 SFN/A
or more exit access doors are required from a suite, one of the exit doors shall be permitted
Fourth Floor:71,365 SFN/A
permitted."
to be directly to an exit stair, exit passageway or exit door to the exterior. (C) Sleeping
Fifth Floor:70,255 SFN/A
Sixth Floor:30,038 SFN/A
suites shall be provided with constant staff supervision within the suite. (D) Sleeping suites
8.3.4.2 (table)- 1½-hour opening rating (doors).
Seventh Floor: 3,656 SFN/A
shall be arranged to provide one of the following (a) The patient sleeping rooms shall be
(Penthouse)
arranged to allow for direct supervision form a normally attended location within the suite or
(b) any patient rooms without direct supervision shall be provided by automatic smoke
TOTAL GROSS AREA:508,670 SF 1,940 SF
detection.
2-HOUR FIRE BARRIER (Vertical Openings):
HEIGHT:
18.2.5.7.2.2- Sleeping suites of more than 1000 sq. ft. shall have not less than two exit
18.3.1.1- "Any vertical opening shall be enclosed or protected in accordance with 8.2.5."
UnlimitedIBC Table 503
ALLOWABLE STORIES:
access doors remotely located from one another. One means of egress shall be directly to
a corridor. One means of egress shall be permitted to be through another suite, provided
8.6.5– Enclosures connecting four stories or more in new construction– 2 hour fire
STORIES:Seven (7) including a Lower Level (Basement), plus Penthouse
that the suite separation complies with corridor construction requirements.
barriers
Other enclosures in new construction: 1-hour fire barriers.
FIRE RESISTANT REQUIREMENTS : (NON-COMBUSTIBLE)
19.2.5.7.2.2- Sleeping suites of more than 1000 sq. ft. shall have not less than two exit
access doors remotely located from one another. One means of egress shall be directly to
Structural Framing3-HourIBC Table 601
8.6.7- Atriums are separated from the adjacent spaces by fire barriers with not less than 1-
No.
a corridor. One means of egress shall be permitted to be through another suite, provided
Floor– Ceiling2-HourIBC Table 601
hour fire resistance rating with opening protective for corridor walls. See exceptions in
AR10500075
Roof1 1/2-HourIBC Table 601
that the suite separation complies with corridor construction requirements.
section.
STATE OF
SHAFT ENCLOSURES:
I
18.2.5.7.2.3 (B)- Sleeping suites shall not exceed 7500 sq. ft. Sleeping Suites larger than
3 Stories or Less2-HourNFPA 101; 8.3.4.2/IBC 713.4
8.3.4.2 (table)- 1½-hour opening rating (doors).
7500 sq. ft. and not exceeding 10,000 sq. ft. shall be permitted where both direct visual
4 Stories or More2-Hour
I
supervisiion is provided and automatic smoke detection is provided.
VERTICAL CIRCULATION:
2-HourNFPA 101; 8.3.4.2Date Signed 4-25-17
2-HOUR FIRE BARRIER ( Exit Passageways):
19.2.5.7.2.3- (B) Sleeping suites shall not exceed 7500 sq. ft. without having an
OCCUPANCY SEPARATION:B Occ. and I-2 Occupancy2-Hour electrically supervised sprinkler system and automatic smoke detection. Sleeping Suites
REF.
19.2.2.7 Exit Passageways- "Exit passageways complying with 7.2.6 shall be permitted."
larger than 7500 sq. ft. and not exceeding 10,000 sq. ft. shall be permitted where both
FE
SMOKE BARRIERS:(I-2 Occupancy and in B Occupancy located within 1-floor of I-2)
direct visual supervisiion is provided and automatic smoke detection is provided.
Max Area:22,500 SF
7.2.6.2 Enclosure- "An exit passageway shall be separated from other parts of the building
Max Travel Distance:200 Ft.
as specified in 7.1.3.2."
18.2.5.7.2.4- Suite Travel Distance between any point in a sleeping suite and the exit
TRAVEL DISTANCE TO AN EXIT:
access door from that suite shall not exceed 100 ft. Travel distance between any point in
B Occupancy300 Ft.
7.1.3.2.1 (b)- 2-hour fire resistive rating for four or more stories.
a sleeping suite and the exit shall not exceed 200 ft.
I-2 Occupancy200 Ft.
18.2.2.7 Exit Passageways- "Exit passageways complying with 7.2.6 shall be permitted."
19.2.5.7.2.4- Suite Travel Distance between any point in a sleeping suite and the exit
access door from that suite shall not exceed 100 ft. Travel distance between any point in
8.3.4.2 (table)- 1½-hour opening rating (doors).
a sleeping suite and the exit shall not exceed 200 ft if the building is protected by a
2
sprinkler system. Without a sprinkler system, distance is limited to 150 ft.
3
FE
1-HOUR FIRE BARRIER(Hazardous Areas)
0
18.2.5.7.3-Patient Care Non-Sleeping Suites shall have direct access to an exit access
6
corridor.
18.3.2.1 Hazardous Areas- "Any hazardous area shall be protected in accordance with
4
c
Section 8.4. The areas described in Table 18.3.2.1 shall be protected as indicated."
Life Safety Legend
19.2.5.7.3.1-Patient Care Non-Sleeping Suites shall have direct access to an exit access
1. Boiler and fuel-fired heater rooms
corridor.
a
2. Central/bulk laundries larger than 100 square feet. (9.3 square meters)
c
n
3. Paint shops
18.2.5.7.3.2- Non-sleeping suites of more than 2500 sq ft shall have not less than two exit
2 HOUR FIRE BARRIER(Occupancy Separation)
a
4. Repair Shops
access doors remotely located from one another. For suites requiring two means of
i
5. Soiled linen rooms
SUITE
egress, one means of egress from the suite shall be permitted to be through another suite
d
2 HOUR FIRE BARRIER(Vertical Openings)
6. Trash Collection rooms
1,005 SF
provide dthat the suite separation complies with corridor wall construction.
n
7. Rooms or spaces larger than 50 square feet (4.6 square meters) including repair shops,
I
2 HOUR FIRE BARRIER(Exit Passageways / Horizontal Exit)
used for storage of combustible supplies and equipments in quantities deemed hazardous
19.2.5.7.3.2- Non-sleeping suites of more than 2500 sq ft shall have not less than two exit
,
by the authority having jurisdiction.
l
access doors remotely located from one another. For suites requiring two means of
1 HOUR FIRE BARRIER(Hazardous Rooms)
8. Laboratories employing flammable or combustible materials in quantities less than those
egress, one means of egress from the suite shall be permitted to be through another suite
e
FEFE
that would be considered a severe hazard.
provide dthat the suite separation complies with corridor wall construction.
SMOKE BARRIER WALL(1 Hour Rated Walls, 20 Min. Rated Doors)
m
18.3.6.3.11- "Door-closing devices shall not be required on doors in corridor wall openings
r
SMOKE PARTITION(Hazardous Rooms)
18.2.5.7.3.3- Patient Care Non-Sleeping Suites shall not exceed 10,000 sq. ft.
other than those serving required exits, smoke barriers or enclosures of vertical openings
a
and hazardous areas."
TRAVEL DISTANCE(Distance to Exit)
19.2.5.7.3.3- Patient Care Non-Sleeping Suites shall not exceed 10,000 sq. ft.
C
FE
P
TRAVEL DISTANCE(Distance to Smoke Barrier)
18.2.6.1- Travel distance between any point in a room and an exit shall not exceed 200 ft.
|
SMOKE BARRIER WALL
(1-hour Rated Existing):
SUITE(Bounding walls to be Smoke Resistant)
l
19.2.6.1- Travel distance between any point in a room and an exit shall not exceed 150 ft.
UPUP
t
19.3.7.3- "Any required smoke barrier shall be constructed in accordance with
e
Section 8.3 and shall have a minimum 1/2 hour fire resistance rating....."
a
FIRE RESISTIVE CEILING(Bounding walls to be 1 Hour Rated Fire Barrier)
DNDN
e
SMOKE RESISTANT CORRIDORS (Non-Rated Corridors):
t
r
19.3.7.6- 19.3.7.8- Doors shall have a 20 minute fire rating and shall be self-closing or
t
i
automatic closing. Doors are not required to swing with egress travel and positive latching
19.3.6.2.4- "In smoke compartments protected throughout by an approved, supervised
FIRE RESISTIVE CEILING(Bounding walls to be 2 Hour Rated Fire Barrier)
S
hardware is not required.
automatic sprinkler system in accordance with 19.3.5.7, a corridor shall be permitted to be
p
separated from all other areas by non-fire-rated partitions and shall be permitted to
n
18.3.7.3- "Any required smoke barrier shall be constructed in accordance with Section
r
SMOKE TIGHT EXIT ACCESS CORRIDOR terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke."
s
a
8.3 and shall a minumum 1-hour fire resistance rating....dampers shall not be required in
(Non-Rated Corridors; Hazardous Areas)
o
i
fully ducted system....."
18.3.6.2- "Corridor walls shall form a barrier to limit the transfer of smoke. Such walls shall
Fd
o
i
NFPA 101 LIFE SAFETY CODE (2000) CHAPTER 18
be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer
r
18.3.7.6- 18.3.7.8- Doors shall have a 20 minute fire rating and shall be self-closing or
(New Healthcare Occupancy)
of smoke. No fire resistance rating is required for corridor walls."
n
automatic closing, and permitted to be held open only by an automatic releasing device.
e
o
H
Doors
IMAGING
NFPA 101 LIFE SAFETY CODE (2000) CHAPTER 38
i
19.3.6.3.4- Door closing devices not required.
t
EQUIPMENT
(New Business Occupancy)
shall be dual egress but positive latching hardware is not required.
M
B133A
a
.
408 SF
18.3.6.3.4- Door closing devices not required.
EXIT
SMOKE ZONES (Not to Exceed 22,500 s.f.):
h
v
N
t
o
P
19.3.7.1- "To divide every story used by inpatients for sleeping by more than 30 patients
MANUAL FIRE ALARM PULL STATION
TRAVEL DISTANCES TO EXIT
r
n
0
into not less than two smoke compartments;(1) To limit the size of each smoke
STANDPIPE OUTLET
e
0
compartment to an area not exceeding 22,500 sq. ft. (2) Where neither the length nor
18.2.6.2.1- "The travel distance between any point in a room and an exit shall not exceed
o
width of the smoke compartment exceeds 150 ft, the travel distance to each the smoke
7
c
200 feet."
R
CHUTE (TRASH & LINEN)
barrier door shall not be limited.
1
FIRE EXTINGUISHER
FE
19.2.6.2.2- The travel distance between any point in a room and an exit shall not exceed
A N 1
18.3.7.1- "(1) To divide every story used by inpatients for sleeping or treatment into not
(Exception: The maximum travel distance shall be permitted to be increased by 50 ft.
150.
less than two smoke compartments; (2) To divide every story having an occupant load of
MRI #2STORAGE / ES
in buildings protected throughout by an approved, supervised automatic sprinkler system.)
PROJECT NO.DATE
B134
CLOSET
50 or more persons, regardless of use, into not less than two smoke compartments; (3) To
SUITE
464 SF
B142
70474-25-17
limit the size of each smoke compartment to an area not exceeding 22,500 sq. ft. (4) To
340 SF
79 SF
limit the travel distance from any point to reach a door in the required smoke barrier to a
TRAVEL DISTANCES TO SMOKE
Rated Wall Priority
REV.DATE
distance not exceeding 200 ft.
19.3.7.1- "The size of any such smoke compartment shall not exceed 22,500 s.f., and the
FE
travel distance from any point to reach a door in the required smoke barrier shall not
exceed 200 feet. (Exception No. 1: Where neither the length nor width of the smoke
RATINGPRIORITY
SMOKE PARTITION
(Hazardous Areas):
compartment exceeds 150 feet, the travel distance to reach the smoke barrier door shall
not be limited."
3 HOUR WALL1HIGHER PRIORITY
19.3.2.1 Hazardous Areas- Any hazardous area shall be safe-guarded by a fire barrier
2 HOUR WALL2
having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing
18.3.7.1 (4)- "To limit the travel distance from any point to reach a door in the required
1 HOUR WALL3
system in accordance with 8.7.1. The automatic extinguishing shall be permitted to be in
smoke barrier to a distance not exceeding 200 feet."
SMOKE PARTITION4
AREA OF CONSTRUCTION
accordance with
NON RATED PARTITION5LOWER PRIORITY
19.3.5.9.Where the sprinkler option of 19.3.2.1 is used, the areas shall be separated from
other spaces by smoke-resisting partitions and doors.
SMOKE ZONE 1.3
GYPSUM BOARD CONTINUES
19.3.2.1.5Hazardous areas shall include, but shall not be restricted to, the following:
13,868 SF
THROUGH STUD CAVITY OF
KEY PLANSET DESCRIPTION
1. Boiler and fuel-fired heater rooms
LOWER PRIORITY WALL
HIGHER PRIORITY
2. Central/bulk laundries larger than 100 square feet. (9.3 square meters)
PARTITION
Construction
LOWER PRIORITY
3. Paint shops
PARTITION
4. Repair Shops
Documents
MOB
5. Soiled linen rooms
SHEET TITLE
6. Trash Collection rooms
7. Rooms or spaces larger than 50 square feet (4.6 square meters) including repair shops,
AREA OF
Life Safety Plans and
used for storage of combustible supplies and equipments in quantities deemed hazardous
HOSPITAL
M
CONSTRUCTION
by the authority having jurisdiction.
Code Summary
P
2 8. Laboratories employing flammable or combustible materials in quantities less than those
0
:
that would be considered a severe hazard.
5
5
:
NOTE: CONTRACTOR IS RESPONSIBLE FOR MAINTAINING NEW AND EXISTING
Partial First Floor Life Safety Plan
SHEET NUMBER
1
FIRE RESISTIVE WALLS THAT ARE CONTINUOUS AND NOT INTERRUPTED BY NON-
Exception: Doors in rated enclosures shall be permitted to have non-rated, factory- or field
7
CENTRAL
RATED WALLS.
1
1/8" = 1'-0"
True North
applied protective plates extending not more than 48in.(122cm) above the bottom of the
PLANT
0
2
/
door.
5
2
/
4
G1-2
A#
Specific Plan Notes
A16REMOVE EXISTING DOUBLE EGRESS DOORS AND RAISE HEAD HEIGHT FOR NEW 8'-0"H DOORS. DOORS TO RECEIVE ALL NEW HARDWARE. REFER TO DOOR
SCHEDULE AND DETAILS FOR ADDITIONAL INFORMATION.
MSKTD
& Associates
2344.34.6567899.19.39.79.9101111.31212.51314
Architecture | Engineering | Interior Design
1715 Magnavox Way930 North Meridian
Fort Wayne, IN 46804Indianapolis, IN 46204
260.432.9337317.917.1190
www.msktd.com
D.9
E
E.2
UPUP
E.4
DNDN
F
No.
AR10500075
STATE OF
I
I
Date Signed 4-25-17
F.6
.
F
E
R
G
REF.
G.3
2
3
0
6
4
a
n
H
a
i
d
n
I
,
l
e
m
r
a
C
J
|
UPUP
UPUP
l
t
DNDN
DNDN
e
a
e
t
r
t
i
S
p
n
r
s
a
o
i
DUST PARTITION WALL
Fd
o
i
REF.
r
n
K
e
o
H
i
t
M
a
.
h
v
N
t
o
MRI #2
B134
r
n
0
K.5
e
0
o
7
R
1
DUST PARTITION WALLDUST PARTITION WALLDUST PARTITION WALL
C1C16
C1C17
DUST PARTITION
A N 1
WALL
A16
A16
PROJECT NO.DATE
L
REF.
70474-25-17
AREA OF CONSTRUCTION
DNDN
REV.DATE
MRI #2 - REFER TO SHEET
UPUP
A2-1 FOR DETAILS
M
M.2
MAGNET DELIVERY ROUTE
KEY PLANSET DESCRIPTION
Partial First Floor Plan
3/32" = 1'-0"
Construction
Documents
MOB
SHEET TITLE
AREA OF
Overall Floor Plan
HOSPITAL
M
CONSTRUCTION
(INFECTIOUS CONTROL) CONSTRUCTION AND DUST SEPARATION WALL. 6" METAL STUD WITH 5/8"
P
VINYL FACED GYPSUM BOARD AND SOUND ATTENUATION BLANKET. EXTEND TO CEILING. TAPE
8
0
SEAMS. REFER TO IU HEALTH MANDATORY CONTRACTOR'S ORIENTATION REQUIREMENTS AND
:
5
SPECIFICATION SECTION. MAINTAIN A MINIMUM OF 5'-0" AT EXISTING CORRIDORS AND OWNER
5
:
OCCUPIED SPACES FOR EGRESS. CONTRATOR IS RESPONSIBLE FOR SUPPLYING AND
SHEET NUMBER
1
DETERMINING WALL LOCATIONS AND NUMBER AND SIZE OF CONSTRUCTION DOORS WITHIN
7
CENTRAL
SEPARATION WALL. REPAIR FLOOR AND WALLS AS NEEDED AFTER REMOVAL OF WALLS. REFER TO
1
True North
PLANT
0
CONSTRUCTION MANAGER'S LOGISTICS PLAN FOR ADDITIONAL INFORMATION.
2
/
5
2
/
4
A0-2
1212.51314
S#
Specific Structural Notes
S110 1/2" THICK CONCRETE SLAB INFILL. DEPRESS SLAB IN MRI ROOM AS REQUIRED PER MRI UNIT SPECIFICATIONS FOR RF SHIELDING INSTALLATION.
SLAB LEVELNESS MUST MEET MRI UNIT SPECIFICATIONS. REFER TO 'TYPICAL FLOOR SLAB INFILL DETAIL' 1/A1-1.
S2EXISTING 12" RECESSED 5 1/4" COMPOSITE SLAB WITH ACCESS FLOOR
S3
S3EXISTING 5 1/4" COMPOSITE SLAB AT 100'-0"
S4
S4EXISTING STEEL BEAMS.
IMAGING
EQUIPMENT
CONTROLOFFICE
EXISTING 12" RECESSED SLAB BELOW 100'-0" A.F.F. WITH
18' - 9"
B133B133AB146
CORRIDOR
MSKTD
PROPOSED NEW 10 1/2" CONCRETE INFILL. REFER TO PLAN NOTE 1
B1C10
S2
& Associates
S3
1
3
Architecture | Engineering | Interior Design
5
.
0
0
°
K
1715 Magnavox Way930 North Meridian
Fort Wayne, IN 46804Indianapolis, IN 46204
260.432.9337317.917.1190
www.msktd.com
S3
°READING
0
0
B144
.
5
PATIENT TOILETOFFICE
3
1
B131AB147
S1S4
ISOCENTER
MRI #2
STORAGE / ES
B134
CLOSET
B142
K.5
OFFICE
WAITING
S3
B148
No.
B131
AR10500075
S3
STATE OF
#4 STAINLESS STEEL REINF.
I
@ 10" O.C. BOTH WAYS
I
1 1/2" NORMAL WEIGHT
CONCRETE TOPPING
Date Signed 4-25-17
10 1/2" NORMAL WEIGHT
CONCRETE INFILL
10' - 2"
S3
26' - 0 1/4"
CORRIDOR
B1C15
S4
AREA OF CONSTRUCTION
CORRIDOR
B1C09
L
2
3
0
AREA OF CONSTRUCTION
EXISTING 5 1/4"
6
CONCRETE BASE SLAB
4
a
n
a
i
First Floor Structural PlanTypical Floor Slab Infill Detail
1
d
1/4" = 1'-0" 1 1/2" = 1'-0"
n
I
,
l
e
1212.51314
m
r
a
D#
Specific Demo Notes
C
D1REMOVE DOOR AND PORTION OF EXISTING CORRIDOR WALL, PROVIDE OPENING 8'-0" WIDE x 8'-0" TALL FOR DELIVERY OF MAGNET. RECONSTRUCT WALL
AFTER DELIVERY AND PROVIDE OPENING FOR NEW DOOR. REFER TO DOOR SCHEDULE.
|
D2REMOVE PORTION OF WALL FOR NEW DOOR AND FRAME. REFER TO DOOR SCHEDULE.
D3REMOVE PORTION OF WALL FOR NEW WINDOW AND FRAME. REFER TO WINDOW AND FRAME ELEVATIONS.
l
t
D4REMOVE COUNTERTOP, SPLASHES, AND ALL ASSOCIATED UNDERCOUNTER BRACING. PREP WALLS TO RECEIVE NEW FINISHES.
D7D5REMOVE PORTION OF EXISTING WALL.
e
a
D6EXISTING PORTION OF WALL TO BECOME 1-HOUR SMOKE BARRIER. EXTEND ALL GYPSUM BOARD TO DECK AND PATCH ALL PENETRATIONS. PROVIDE
IMAGINGOFFICE
D12
e
CONTROL
APPROPRIATE FIREPROOFING AT ALL PENETRATIONS AND AT OVERHEAD DECK JOINT. PROVIDE ENGINEERING JUDGEMENT THAT EXISTING GYPSUM
B146
EQUIPMENT
t
r
B133
BOARD ON EACH SIDE OF WALL IS EQUIVALENT TO TYPE-X GYPSUM BOARD.
B133ACORRIDOR
t
i
D8
B1C10
D7REMOVE PORTION OF LAY-IN CEILING AS REQUIRED FOR NEW OVERHEAD MECHANICAL, ELECTRICAL, AND PLUMBING. REFER TO MEP DWGS. (WORK TO
BE PERFORMED INSIDE CONTAINMENT CART).
S
p
D8EXISTING FLOORING AND RUBBER BASE TO REMAIN. PROTECT
D9REMOVE PORTION OF CHAIR BUMP AND HANDRAIL. SALVAGE FOR REINSTALLATION.
n
r
D10REMOVE BUILT-UP REBAR FLOORING AND LOOSE LAID PLYWOOD FLOORING AND PREP FOR NEW CONCRETE SLAB INFILL. REFER TO STRUCTURAL DWG
s
a
AND DETAILS.
o
i
K
D11REMOVE PORTION OF EXISTING FLOOR AND PREP FOR NEW FINISHES. REFER TO FINISH DWGS.
D4
Fd
o
D5
D12REMOVE EXISTING LAY-IN CEILING IN ITS ENTIRETY. PREP TO RECEIVE NEW LAY-IN CEILING SYSTEM TO ALIGN WITH EXISTING ADJACENT CEILING GRID.
i
r
D11
n
e
o
H
D3
i
D6
t
M
READING
D12
OFFICE
B144
a
PATIENT TOILET.
B147
B131A
h
v
N
t
o
D2
r
n
0
MRI SHELL
B134
e
0
o
D10
7
R
D12
1
A N 1
D7
D8
ES CLOSET
PROJECT NO.DATE
B142
70474-25-17
K.5
WAITINGOFFICE
+/- 6' - 0"8' - 0"
REV.DATE
B131B148
D1
D9
CORRIDORCORRIDOR
B1C15B1C09
D12D12
KEY PLANSET DESCRIPTION
Construction
Documents
MOB
L
SHEET TITLE
AREA OF
First Floor Demo and
AREA OF CONSTRUCTION
HOSPITAL
M
CONSTRUCTION
Structural Plans
P
1
1
:
5
5
:
SHEET NUMBER
1
7
CENTRAL
1
First Floor Demo Plan
True North
PLANT
0
2
/
5
1/4" = 1'-0"
2
/
4
A1-1
RC#
Specific Reflected Ceiling Plan Notes
RC1EXISTING LAY-IN CEILING TO REMAIN.
RC2NEW 24" x 24" LAY-IN CEILING. REFER TO FINISH SCHEDULE FOR ADDITIONAL INFORMATION.
RC3NEW 24" x 24" ACOUSTICAL LAY-IN CEILING w/ NON-FERROUS GRID (MRI SAFE). REFER TO FINISH SCHEDULE FOR
1212.51314
ADDITIONAL INFORMATION.
RC4(HATCHED AREA) LAMINATE FASCIA PANEL ABOVE FULL-HEIGHT CABINET. ACCESS PANEL TERMINATES AT LAY-IN CEILING 10'-0" A.F.F.
RC5ISOCENTER OF MRI MAGNET.
RC6TURRET COVER FROM TOP OF MRI UNIT TO CEILING TO CONCEAL QUENCH VENT AND CABLES. REFER TO MRI MAGNET MANUFACTURER FOR EXACT LOCATION AND
SIZE.
RC7WALL MOUNTED "NURSE CALL - DOME LIGHT" INDICATION LIGHT (OWNER FURNISHED AND OWNER INSTALLED) . CENTER OVER CORRESPONDING DOOR. MOUNT AT
HEIGHT MATCHING EXISTING, ADJACENT SYSTEM. REFER TO
ELECTRICAL DWGS FOR ROUGH-IN AND CONDUIT INFORMATION.
RC8RF SHIELD PENETRATION PLATE PROVIDED BY SHIELDING VENDOR.
OFFICE
B146
RC9RF SHIELDING ABOVE ACT / BULKHEAD BY SHIELDING VENDOR.
CONTROL
RC11NEW METAL FRAMING WITH GYPSUM BOARD BULKHEAD AT 8'-8"
B133
RC12QUENCH TUBE EXIT WITHIN EXISTING MASONRY WALL. PROVIDE LINTEL AND FLASHING AS NECESSARY. COORDINATE HEIGHT, OPENING SIZE, AND LOCATION w/ RF
SHIELDING AND MRI VENDOR DWGS.
IMAGING
MSKTD
EQUIPMENT
RC2
B133A
RC1
& Associates
RC11
Architecture | Engineering | Interior Design
General Ceiling Notes
K
1.REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING
1715 Magnavox Way930 North Meridian
DRAWINGS FOR FIXTURE TYPES AND LOCATIONS.
Fort Wayne, IN 46804Indianapolis, IN 46204
RC2
2.UNLESS OTHERWISE NOTED, ALL CEILINGS SHALL BE 8'-10"
260.432.9337317.917.1190
OFFICE
A.F.F. (MATCH EXISTING).
MRI #2
B147
www.msktd.com
B134
2' x 2' LAY-IN CEILING
10' - 0"
A.F.F.
CORRIDOR
GYPSUM BOARD CEILING / BULKHEAD
B1C10
RC4
LAMINATE BULKHEAD / ACCESS PANEL
RC8
PATIENT TOILET
10' - 0"
RC6
B131A
A.F.F.
READING
B144
RC5
7047 - Door and Opening Schedule
STORAGE / ES
RC3
CLOSET
DoorFrameDetails
OpeningDoorPower
RC1RC9
B142OFFICE
No.GlassReq'd
SizeMat.Ele.Mat.Ele.HeadJambLabelHdw. SetRemarks
B148
RC2
7047 - MRI Build-out
K.5
B134A4'-0" x 7'-0" x 1 3/4"P-LAMF-1------------------No---1, 3, 5
No.
B134B3'-0" x 7'-0" x 1-3/4"P-LAMF-1------------------No---1
WAITING
AR10500075
C1C16(2) 3'-8" x 8'-0" x 1 3/4"SCWDNL-2FW-HM11/A2-11/A2-1 SIM.20-MIN.20-MIN.Yes16
B131
C1C17(2) 3'-8" x 8'-0" x 1 3/4"SCWDNL-2FW-HM11/A2-11/A2-1 SIM.20-MIN.20-MIN.Yes27 STATE OF
I
I
Date Signed 4-25-17
Door Schedule RemarksDoor Elevations
10' - 2"
1.DOOR, FRAME, AND HARDWARE SHALL BE DESIGNED AND PROVIDED BY RF
CORRIDOR
RC7
SEE SCHEDULESEE SCHEDULE
CORRIDOR
SHIELDING VENDOR. SCHEDULE ONLY INDICATES ARCHITECT'S INTENT FOR
B1C09
B1C15
SIZE, FINISH MATERIAL, AND LOCKSET AND HARDWARE. REFER TO RF
EQ9"EQEQ9"EQ
SHIELDING VENDOR DRAWINGS.
2.RECONNECT EXISTING CARD READER WITH ELECTRIC STRIKE.
RC2
RC2
3.DOOR TO RECEIVE CONTINUOUS HINGE.
4.DOOR TO RECEIVE CLOSER.
5.DOOR TO RECEIVE 42" PROTECTION PLATE (CORRIDOR SIDE) AND DOOR
EDGE GUARD (BOTH ENDS).
6.REUSE ALL EXISTING HARDWARE, EXIT DEVICES, AND AUTO OPERATOR.
REINSTALL HARDWARE AND AUTO OPERATOR AT NEW REQUIRED HEIGHTS.
PROVIDE NEW CONTINUOUS HINGES.
L
7.REUSE ALL EXISTING HARDWARE, EXIT DEVICES, AND MAGNETIC HOLD OPEN
2
DEVICES. REINSTALL HARDWARE AND MAG HOLD OPEN DEVICES AT NEW
3
REQUIRED HEIGHTS. PROVIDE NEW CONTINUOUS HINGES.
0
AREA OF CONSTRUCTION
RC12
6
4
F-1NL-2
General Door Remarks
a
n
1.WOOD (SCWD) DOORS SHALL BE CHERRY, QUARTER-SLICES, WITH CUSTOM
a
FINISH EQUAL TO MARSHFIELD #237555C.
i
First Floor Reflected Ceiling Plan
d
1/4" = 1'-0"
Frame Elevations
n
I
,
l
2"SEE SCHEDULE2"
e
1212.51314
m
r
REFER TO PARTITION
TYPE FOR WALL
a
CONSTRUCTION
C
CONTINUOUS SEALANT
EACH SIDE OF FRAME
|
GROUT FILLED HOLLOW
l
t
METAL DOOR FRAME
HOLLOW METAL DOOR AS SCHEDULED
e
IMAGING
a
2
EQUIPMENT
CONTROL
e
t
B133 A10-1 B133A
r
1A
t
i
A12
9' - 11 5/8"8' - 8 1/8"
DOUBLE-EGRESS(WINDOW BY RF SHIELDING
S
Door Head Detail
p
VENDOR- FRAME ELEVATION
1
A11A1
n
SHOWN FOR INTENT ONLY)
r
1 1/2" = 1'-0"
EPO
s
a
o
i
K
Fd
o
1
3
i
5
.
0
0
°
A#
r
Specific Plan Notes
IN1
A18 n
A
A2
A23
e
A1INFILL WALL ASSEMBLY. INFILL TO BE FLUSH AND LEVEL w/ EXISTING ADJACENT CONSTRUCTION.
A2
°
A3
4' - 0"
o
H
A18
0
i
A2RF SHIELDING WALL ASSEMBLY PROVIDED BY CONTRACTOR/SHIELDING VENDOR. CONTRACTOR TO PROVIDE 5/8" GYPSUM BOARD ON MRI ROOM SIDE FOLLOWING
0
.
5
t
M
SHIELDING VENDOR INSTALLATION. REFER TO RF SHIELDING DWGS.
3
3/ A10-1
1
A3CLEAR VIEW WINDOW ASSEMBLY PROVIDED BY CONTRACTOR/SHIELDING VENDOR. REFER TO RF SHIELDING DWGS.
a
A14
.
EPO
PATIENT TOILET
A4DOOR, FRAME, AND HARDWARE PROVIDED BY CONTRACTOR/SHIELDING VENDOR. REFER TO RF SHIELDING DWGS.
B131A
h
v
1
-
A5ISOCENTER OF MRI MAGNET.
0 N
t
1
o
A11
A
A63T MAGNET FURNISHED AND INSTALLED BY OWNER. REFER TO SIEMENS VENDOR DWGS FOR BASE DETAIL AND
B134B
/
4
FLOOR LEVELING REQUIREMENTS.
r
n
0
A7A10
A7MOBILE PATIENT TABLE FURNISHED AND INSTALLED BY OWNER. REFER TO SIEMENS VENDOR DWGS FOR RECESSED
e
0
A4
MOUNTING PLATE.
EPO
o
A9
A8TURRET COVER FROM TOP OF MRI UNIT TO CEILING TO CONCEAL QUENCH VENT AND CABLES. REFER TO MRI MAGNET
7
A11
R
A8
MS MANUFACTURER FOR EXACT LOCATION AND SIZE.
1
A9RF SHIELD PENETRATION PLATE PROVIDED BY SHIELDING VENDOR.
A13
A N 1
A10MRI EQUIPMENT/CABINETS FURNISHED AND INSTALLED BY OWNER. REFER TO SIEMENS VENDOR DWGS.
A5
°
0
A11'EPO' EMERGENCY POWER OFF BUTTON. MOUNTED AT 5'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL
MRI #2
0
A2
.
STORAGE / ES
DWGS.
5
PROJECT NO.DATE
B134
A6
2
RF
CLOSET
A12'AB' ALARM BOX. MOUNTED AT 5'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL DWGS.
464 SF
A22
B142
70474-25-17
A13'MS' MAGNET STOP. MOUNTED AT 6'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL DWGS.
K.5
A14(2) FULL-HEIGHT CABINETS w/ REAR AND TOP ACCESS TO RF SHIELDING PENETRATION PLATE. REFER TO ELEVATION AND
WAITING
SECTION ON A10-1.
REV.DATE
B131
6/ A10-1
A15QUENCH TUBE EXIT WITHIN EXISTING MASONRY WALL. PROVIDE LINTEL AND FLASHING AS NECESSARY. COORDINATE HEIGHT, OPENING SIZE, AND LOCATION w/ RF
RF
SHIELDING AND MRI VENDOR DWGS.
14' - 0"
A16REMOVE EXISTING DOUBLE EGRESS DOORS AND RAISE HEAD HEIGHT FOR NEW 8'-0"H DOORS. DOORS TO RECEIVE ALL NEW HARDWARE. REFER TO DOOR
A2
A4
SCHEDULE AND DETAILS FOR ADDITIONAL INFORMATION.
A17EXISTING MEDICAL GAS ZONE VALVE BOX
B134A
A18'IN#' PULL BOX. MOUNTED 2'-0" A.F.F. REFER TO SIEMENS VENDOR AND ELECTRICAL DWGS.
A20REMOVE AND REINSTALL EXISTING CHAIR BUMP AND HANDRAIL (HIGH/LOW) . PROVIDE NEW FASTENER DOWEL PLUGS STAINED TO MATCH.
A21MRI KNOCK OUT PANEL. REMOVE 8'-0" X 8'-0" AREA OF EXISTING CORRIDOR WALL FOR MRI TRANSFER. INFILL WALL OPENING WITH LIKE CONSTRUCTION INCLUDING
A17
A21A20
AN ADDITIONAL 1/2" LAYER OF GYPSUM BOARD ON CORRIDOR SIDE.
4"5' - 2"8' - 0"10' - 2"
A22AT CONDUIT PENETRATIONS IN FLOOR, FULLY GROUT AROUND CONDUIT.
25' - 0 1/2"+/- 8' - 0"
A23EXISTING PORTION OF WALL TO BECOME 1-HOUR SMOKE BARRIER. EXTEND ALL GYPSUM BOARD TO DECK AND PATCH ALL PENETRATIONS. PROVIDE APPROPRIATE
FIREPROOFING AT ALL PENETRATIONS AND AT OVERHEAD DECK JOINT. PROVIDE ENGINEERING JUDGEMENT THAT EXISTING GYPSUM BOARD ON EACH SIDE OF WALL
IS EQUIVALENT TO TYPE-X GYPSUM BOARD.
CORRIDORCORRIDOR
KEY PLANSET DESCRIPTION
B1C15B1C09
General Plan Notes
Construction
PP = PUSH PLATE
A15
Documents
IC = INTERCOM
MOB
L
IL = INDICATOR LIGHT
*NOT ALL LOCATIONS MAY BE NOTED. REFER TO ELECTRICAL DRAWINGS.
SHEET TITLE
1.ALL WALLS TO BE TYPE 1.5A UNLESS OTHERWISE NOTED. REFER TO
AREA OF
First Floor and Reflected
AREA OF CONSTRUCTION
WALL TYPES ON SHEET G1-1.
HOSPITAL
M
2.WHERE DIMENSION IS PRECEDED BY +/-, THE VALUE GIVEN IS FOR
CONSTRUCTION
Ceiling Plans
P
REFERENCE. ACTUAL DIMENSION SHALL BE DETERMINED BY OTHER
1/ A10-1
9
CONSTRAINTS, SUCH AS FINISH ALIGNMENT, OR EXISTING
4
:
CONSTRUCTION. SEE PLAN FOR DETAILS AS NOTED.
2
5
3.REFER TO DOOR HARDWARE SCHEDULE FOR OPERATOR TYPE, HOLD
:
SHEET NUMBER
2
OPEN, CARD READERS AND OTHER DOOR SPECIALTY HARDWARE.
7
CENTRAL
4.REFER TO ENLARGED PLANS, ELEVATIONS, AND SECTIONS FOR
First Floor Plan
1
True North
PLANT
0
ADDITIONAL DIMENSIONS AND NOTATION.
2
/
1/4" = 1'-0"
5
2
/
4
A2-1
General Casework Notes
CABINET MFG. SHALL FIELD VERIFY ALL WALL DIMENSIONS PRIOR
TO FABRICATION. ALL GENERAL CASEWORK NOTES APPLY TO ALL
CASEWORK THROUGH OUT SET
10
1.CONTRACTOR SHALL PROVIDE WOOD BLOCKING AS REQUIRED FOR
A10-1
INSTALLATION OF ALL UPPER AND LOWER UNITS
2.EDGE OF COUNTERTOP TO BE 1 1/2" THICK.
3.CABINET MFG. SHALL COORDINATE WITH OWNER ALL LOCATIONS FOR
"GROMMETS" QUANTITY WILL BE IDENTIFIED PER ELEVATION. ALL GROMMETS TO
BE 3 1/2" DIA.WITH BLACK PLASTIC TRIM RING- LOCATE AT REAR OF COUNTER. OR
AS DIRECTED BY OWNER.
ALUMINUM TRIM TO MATCHRF SHIELDED WINDOW AND
4.ALL EXPOSED ENDS AND BACKS OF CASEWORK TO BE FINISHED SAME AS
RF WINDOW ASSEMBLY BY RF
FRAME BY SHIELDING VENDOR
BALANCE OF EXPOSED SURFACE, SEE FINISH SCHEDULE.
SHEIDLING VENDOR
SEALANT
5.APPLY 1" RAD. ON ALL OUTER CORNERS OF COUNTER TOPS, U.N.O.
6.ALL END PANEL SUPPORT SHALL BE CONSTRUCTED W/ 1 1/2" LAMINATED
3/4" PLASTIC LAMINATE SILL
PARTICLE BD.
7.ALL COUNTER TOPS SHALL EXTEND 1" BEYOND FRONT OF CABINET DRAWER
MSKTD
3/4" PLASTIC LAMINATE SILL
FACE.
2' - 6"
1"
8.ALL DRAWERS AND DOOR HANDLES SHALL BE TYPE " STANLEY, MODEL No. 4484-
DIMMER SWITCHES, REFER
1 1/2" PLASTIC LAMINATE
& Associates
CHROME VS26D
TO ELECTRICAL DWGS.
COUNTERTOP (POSTFORM)
9.ALL BASE CABINET DEPTH SHALL BE 24" UNLESS NOTED OTHERWISE
WITH 4" BACKSPLASH
RF SHEILDINGEMERGENCY POWER OFF
10.ALL UPPER CABINET DEPTH SHALL BE 14" UNLESS NOTED OTHERWISE
Architecture | Engineering | Interior Design
(EPO), REFER TO
CONTROL WINDOW
11.APPLY A 4" BACKSPLASH AT PERIMETER OF ALL COUNTER TOPS
ELECTRICAL DWGS.
12.APPLY (1) ADJUSTABLE SHELF IN ALL BASE UNITS, AND (2) ADJUSTABLE SHELVES
PLASTIC LAMINATE
IN ALL. UPPER UNITS W/ EXCEPTION OF SINK BASE UNITS. (UNLESS NOTED
COUNTERTOP (POSTFORM)
1715 Magnavox Way930 North Meridian
OTHERWISE). ALL SHELVES IN CASEWORK TO BE ADJUSTABLE ON 1" CENTERS
w/ 4"H BACKSPLASH
Fort Wayne, IN 46804Indianapolis, IN 46204
VERTICALLY.
260.432.9337317.917.1190
13.ALL BASE UNITS SHALL HAVE A 4" H. x 3" D. TOE SPACE WITH RUBBER BASE BY
EXISTING WALL
RAKKS BRACKET EH-1824
FLOORING CONTRACTOR. BASE TO EXTEND TO ALL EXPOSED SIDES OF
PARTITION
www.msktd.com
POWDER COATED FINISH
CASEWORK.
14.REFER TO FLOOR PLAN FOR ALL WALL PARTITION TYPES
6" RADIUSED EDGES (TYP.)
BLOCKING- TYPICAL
RF SHIELDING
15.PAPER TOWEL DISPENSER LOCATED AT EVERY SINK. SUPPLIED BY OWNER,
SS
WALLRAKKS BRACKETS EH-1824
INSTALLED BY G.C.
PULL BOX
ASSEMBLY BYPOWDER COATED FINISH16.FOR ALL FILES DESIGNATED "BY OWNER"- CONTRACTOR TO VERIFY ACTUAL
VENDOR
HEIGHT OF FILES TO BE PURCHASED FOR COORDINATION, IF USED AS SUPPORT
FOR COUNTER TOP
17.INSTALL CLEAR SEALANT CONTINUOUS BETWEEN TOP OF BACKSPLASH AND
BASE. REFER TO
WALL.
EXISTING WALL
INTERIOR FINISH PLANS
18.ALL HARDWARE FOR ANCHORING/SUPPORTING CASEWORK SHALL BE
EDGE / CORNER
CLEARANCE ABOVE FILTER
CONCEALED.
MOUNTING CLIPS
SEE PLAN
19.PROVIDE 2X2 WOOD BLOCKING CONTINUOUS AT PERIMETER FOR
COUNTERTOP/SHELF SUPPORT- PAINT TO MATCH WALL.
EQ.4' - 0"EQ.6"
20.ALL COUNTERTOPS WITHOUT BACKSPLASH SHALL BE SCRIBED TO ADJACENT
SEE PLAN
WALLS/CASEWORK.
2' - 8 1/2"+/- 4' - 7"ANGLED TO VIEW
21.4 DIGIT NUMBER ABOVE OR BELOW CASEWORK REFERS TO HEIGHT AND WIDTH
OF UNIT.
22.FILLER PANELS BY CABINET MANUFACTURER TO MATCH CABINETS. PROVIDE AND
INSTALL.
3/4" PLASTIC LAMINATE
REMOVEABLE ACCESS PANEL
SIEMENS RF
No.
Casework SectionCasework Elevation
" L " = DOOR/DRAWER TO BE LOCKED WITH KEY CYLINDER. COORDINATE WITH
FILTER PLATE
AR10500075
105
EDGE OF OPENING
OWNER ON KEYING REQUIREMENTS
BEYOND
1" = 1'-0" 1/2" = 1'-0"
STATE OF
" F " = FILE DRAWER, INTERIOR DIMENSIONS SHALL MEET STANDARD FILE DRAWER
I
DIMENSIONS. INSTALL HANGING FILE HARDWARE.
I
" UL " = UNDER UPPER CABINET LIGHT, REFER TO ELECTRICAL DRAWINGS, APPLY 2"
OPENING
LAMINATED APRON.
Date Signed 4-25-17
3"1' - 9"3"1 1/8" SETBACK
" S " = STRUCTURAL SUPPORT FOR COUNTER AND OR RECEPTION DESK. REFER TO
CLEAR
" AP " = REMOVABLE ACCESS PANEL. PROVIDE COUNTERSUNK ANCHORS.
3/4" PLASTIC LAMINATE
BACK PANEL
" K " = KEYBOARD TRAYS PROVIDED BY OWNER - 30" WIDE
1" PLASTIC LAMINATE
SHELF
3/4" PLASTIC LAMINATE
4' - 7 1/8"
" G " = GROMMETS, VERIFY LOCATION WITH OWNER
PANEL DOOR
7
3/4" PLASTIC LAMINATE
A10-1
ADJUSTABLE SHELF
EXISTING WALLRAKKS BRACKET EH-1212
EXISTING WALL
FINISHED WALL OPENING
PARTITIONPOWDER COATED FINISH
PARTITION
(BEYOND)- BOTH SIDES
OF MRI ROOM &
2
PROVIDE 1 1/2" LIP ON FRONT
EQUIPMENT ROOM
RF SHIELDING
RF SHIELDING
AND BACK OF SHELVING TO
WALL
3
WALL
LAMINATE FASCIA
TRIM
SUPPORT COIL WEIGHT TYP.
ASSEMBLY BY
ASSEMBLY BY
PANEL
0
VENDOR
PARTIAL SIDESPLASH
VENDOR
3/4" PLASTIC LAMINATE
3' - 6 1/2"
BEYOND
6
FIXED SHELF
SEE PLAN
ALL HARDWARE TO BE
4
NON-FERROUS
1"
1 1/2" PLASTIC LAMINATE
4
1"
DOOR PULL
5
.
COUNTERTOP (POSTFORM)
1
0 a
-
R
00
1
WITH 4" BACKSPLASH°
°
0
6
A
0
BLOCKING- TYPICAL
.
/
"5
PLASTIC LAMINATE n
3
5
1
ADJUSTABLE SHELVES
a
BLOCKING- TYPICAL
i
PLASTIC LAMINATE
DOOR PULL
d
FIXED SHELF
3/4" PLASTIC LAMINATE
n
3/4" PLASTIC LAMINATE
I
BACK PANELPULL HANDLES
ADJUSTABLE SHELF
IMAGING
,
l
°
EQUIPMENT(2) FULL HEIGHT 2-DOOR
MRI #2
3/4" PLASTIC LAMINATE
0
0
.
B133AB134CABINETS
ADJUSTABLE SHELF
5 e
3
A
R
1
6
"
ALL HARDWARE TO BE
4
ALL HARDWARE TO BE
5
m
.
NON-FERROUS 0
0
2' - 3"
°
r
NON-FERROUS
1' - 9"
"
(CLEAR)
6
END PANEL / CABINET
PLASTIC LAMINATE
a
(CLEAR)
R
BEYOND
ADJUSTABLE SHELVES
C
BASE. REFER TO
BASE. REFER TO
4"H BASE (REFER TO FINISH PLAN)
INTERIOR FINISH PLANS
INTERIOR FINISH PLANS
|
1' - 0"
3"
2 1/4"3"
+/- 2' - 8"2' - 6"2' - 6"
SEE PLAN2' - 0"l
SEE PLAN2' - 6"
t
(30" DEEP)(30" DEEP)
SEE PLAN
e
SEE PLAN
a
e
t
r
t
i
Casework SectionCasework SectionCasework ElevationCasework Detail
9742
S
1" = 1'-0" 1" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0"
p
n
r
s
a
o
i
Fd
o
i
r
n
e
o
H
i
t
M
a
.
h
v
N
9
8
t
1" PLASTIC LAMINATE
o
SHELF
A10-1
A10-1
8'-0" x 8'-0" KNOCK OUT
r
n
0
PANEL BEYOND
e
0
o
7
R
GYPSUM BOARD BULKHEAD (HIGH)
1
EXISTING WALLRAKKS BRACKET EH-1212
PARTITIONPOWDER COATED FINISH
A N 1
6' - 0"
PROJECT NO.DATE
ALL HARDWARE TO BE
RF SHIELDING
WALLNON-FERROUS
(14" DEEP)
70474-25-17
ASSEMBLY BY
13
VENDOR
PARTIAL SIDESPLASH
1' - 6"3' - 0"1' - 6"
BEYOND
REV.DATE
MEDICAL GAS OUTLETS, REFER TO
PLUMBING DRAWINGS
PLASTIC LAMINATE SHELF ON
SEE PLAN
RAKKS BRACKETS EH-1212 Second Floor
1 1/2" PLASTIC LAMINATE
115' - 4"
POWDER COATED FINISH
COUNTERTOP (POSTFORM)
5"5"NEW MRI #2 CRYOGEN
WITH 4" BACKSPLASH
PLASTIC LAMINATE COUNTERTOP
SS
QUENCH VENT CAP
(POSTFORM) w/ 4"H SIDE &
BACKSPLASH
BLOCKING- TYPICAL
MVOMANOWAGD
SIDESPLASH TO EXTEND TO EDGE
EXISTING MRI #1
SLIDE
OF ADJACENT WALL- REFER TO
CRYOGEN QUENCH
B134A
FLOOR PLAN
VENT CAP
3/4" PLASTIC LAMINATE
BACK PANEL
2-DOOR LOWER CABINET WITH
ADJUSTABLE SHELVES
3/4" PLASTIC LAMINATE
WP-1WP-1
ADJUSTABLE SHELF
EXISTING DEFLECTION
OPEN LOWER CABINET WITH
JOINT
ALL HARDWARE TO BE
ADJUSTABLE SHELVES
SET DESCRIPTION
NON-FERROUS
EXISTING ADJACENT
1' - 9 3/4"
FINISHED END PANEL (BOTH SIDES)
WALL ASSEMBLY
Construction
END PANEL / CABINET
(CLEAR DEPTH)
4"H BASE (REFER TO FINISH PLAN)
BEYOND
Documents
BASE. REFER TO
4"H BASE (REFER TO FINISH PLAN)
8' - 0"5' - 6"
INTERIOR FINISH PLANS
2' - 0"2' - 0"2' - 0"
SHEET TITLE
14' - 0"
3"
(24" DEEP)(24" DEEP)(24" DEEP)
Casework Elevations
SEE PLAN2' - 0"
6' - 0"First Floor
M
100' - 0"
and Details
P
SEE PLAN
9
1
:
5
5
:
SHEET NUMBER
1
7
Casework SectionInterior ElevationCasework ElevationPartial East Exterior Elevation
1
8631
0
2
1" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0" 1/4" = 1'-0"
/
5
2
/
4
A10-1
MSKTD
& Associates
Architecture | Engineering | Interior Design
1715 Magnavox Way930 North Meridian
Fort Wayne, IN 46804Indianapolis, IN 46204
260.432.9337317.917.1190
www.msktd.com
No.
AR10500075
STATE OF
I
I
Date Signed 4-25-17
2
3
0
6
4
a
n
a
i
d
n
I
,
l
e
1212.51314
m
r
a
C
|
l
t
B133
General RemarksSpecific Remarks
CONTROL
e
ETR
a
(APPLICABLE THROUGHOUT ALL AREAS OF CONSTRUCTION)
(SEE FINISH SCHEDULE FOR LOCATION)
B133A
ETR,PT-1
e
B146
t
IMAGING
ETR r
OFFICE
A.FOR ALL FLOORING MATERIALS INSTALLED ON GRADE OR BELOW GRADE: THE FLOORING
t
i
1.SEE ELEVATIONS FOR CASEWORK DETAILS.
EQUIPMENT
ETR
G
CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE IN THEIR BID PRICES ALL REQUIRED
2.SEE FINISH FLOOR PLAN FOR FLOORING PATTERN.
1,6,8ETR,VCT-1
NN
II
S
MATERIALS AND LABOR FOR A COMPLETE INSTALLATION THAT MEETS THE
T
A 3.INSTALL NEW VCT WHERE INDICATED ON FINISH FLOOR PLAN. INSTALL RESILIENT BASE
ETR, RB-1
S
TM
I
MANUFACTURER'S TOTAL SYSTEM PERFORMANCE. THIS INCLUDES ALL PREP MATERIALS p
AND PAINT ON NEW WALL TO MATCH EXISTING.
ETR, P-1
E
XC
O
AND LABOR REQUIRED TO MEET MANUFACTURER'S WRITTEN SPECIFICATIONS FOR
EVTR
4.PATCH VCT WHERE NECESSARY. INSTALL RESILIENT BASE ON NEW WALL TO MATCH
n
ETR
r
MOISTURE, PH, SMOOTHNESS OR LEVELNESS OR CLEANLINESS OF NEW OR EXISTING
EXISTING. INDICATED WITH DASHED LINE.
3,9
s
a
SUBSTRATES, ETC. THIS INSTALLATION SHALL INCLUDE THE MANUFACTURER'S SPECIFIED
CG
5.INSTALL NEW VINYL WALL COVERING AND RESILIENT BASE AT NEW WALL AND ADJACENT.
o
i
K
ADHESIVES, SEALERS, ETC.
SEE FINISH FLOOR PLAN FOR LOCATION. INDICATED WITH DASHED LINE. FINISHES ARE
B.PAINT ALL HOLLOW METAL DOORS, WINDOW FRAMES, AND DOOR FRAMES P-2, SEMI-
TO MATCH EXISTING. HANDRAIL AND BUMP RAILS THAT WERE REMOVED ARE TO BE
Fd
o
CG
i
GLOSS.
1
REINSTALLED
-
r
T
C.PATCH AND MATCH ALL FINISHES DUE TO CONSTRUCTION.
6.INFILL CARPET TILE AT NEW DOOR OPENING. FLOORING TYPE TRANSITION TO OCCUR
C
n
D.SEE REFLECTED CEILING PLAN AND DETAILS FOR LOCATION AND HEIGHT OF CEILINGS.
V
UNDER DOOR IN THE CLOSED POSITION.
e
E.EVERY TRANSITIONS BETWEEN FLOORING MATERIALS TO BE FLUSH. IT IS FLOORING
7.INSTALL WP-1 ON EAST AND SOUTH WALLS WHERE INDICATED WITH A HEAVY DASHED
o
H
i
CONTRACTOR'S RESPONSIBILITY TO LEVEL SUBSTRATE AS NECESSARY FOR MATERIALS TO
LINE ON FINISH FLOOR PLAN. CORNER GUARD TO BE PLASTIC COVER WITH ALUMINUM
B131A
t
M
B144TRANSITION AT LEVEL HEIGHT, INCLUDING GRINDING OR BUILDING UP OF CONCRETE. ALL
RETAINER, 7'-0" HEIGHT, TO MATCH WALL PROTECTION COLOR. SEE FINISH FLOOR PLAN
PATIENT
B147
READINGTRANSITION STRIPS TO BE STAINLESS STEEL EQUAL TO SCHLUTER SYSTEMS AND MUST
FOR LOCATION MARKED WITH CG SYMBOL.
a
TOILET
.
OFFICE
MEET ADA; ALL PROFILES TO BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
8.INSTALL NEW PAINT ON WALLS INDICATED WITH DASHED LINES ON FINISH FLOOR PLAN.
h
v
TRANSITION STRIPS ARE UNNECESSARY BETWEEN LIKE MATERIALS (CARPET TO CARPET,
9.CORNER GUARD TO BE 7'-0" HIGH STAINLESS STEEL TO MATCH HOSPITAL STANDARD.
N
t
LINOLEUM TO VINYL, ETC).
LOCATION MARKED ON FINISH FLOOR PLAN WITH CG SYMBOL.
o
F.ALL FLOORING MATERIAL TRANSITIONS TO BE CENTERED UNDER DOOR IN CLOSED
r
n
0
POSITION.
G.PAINT VENTS, DIFFUSERS, ELECTRICAL PANELS, FIRE CABINETS (UNLESS THEY ARE
e
0
Room Finish Tag Legend
PT-1/RB-1
NATURAL ALUMINUM OR STAINLESS STEEL), ETC. TO MATCH WALL COLOR.
o
7
R
ROOM # AND NAME
1
FLOOR FINISH
RB-1
BASE FINISH
A N 1
WALL FINISH
Color Legend
CEILING FINISH
PROJECT NO.DATE
B142
REMARKS
FLOOR
STORAGE / ES
70474-25-17
CARPET TILE
CLOSET
K.5
B131CPT-1ATTIC STOCK OF CORRIDOR CARPET TILE (INTERFACE ZEN WILLOW)
ETR,VCT-1
B134 MRI #2
WAITING
ETR, RB-1
B148 REV.DATE
SV-1,SV-2
SHEET VINYL
P-1
OFFICE
RB-1
SV-1TEKNOFLOR; FORESTSCAPES; HARVEST CHERRY 52202
ETR
PT-3,WP-1
SV-2TEKNOFLOR; FORESTSCAPES; COLONIAL MAPLE 31026
6
4
5
ACT-1
.
0
1' - 5 1/4"1' - 5 1/4"
0
1,2,7
°
VINYL COMPOSITION TILE
VCT-1MANNINGTON, ESSENTIALS, WARM BEIGE 127
CPT-X
BASE
RUBBER
RB-1JOHNSONITE- 4" HIGH COVED #29 MOON ROCK
VWC-1/RB-1
3' - 0"VWC-1/RB-1
B1C09
WALL
B1C15
CORRIDOR
PAINT
CORRIDOR
P-1SHERWIN WILLIAMS; CRISP LINEN SW6378
ETR, CPT-X
P-2SHERWIN WILLIAMS; INTERACTIVE CREAM SW6113
ETR, RB-1
P-3SHERWIN WILLIAMS; OYSTER BAY SW6206
ETR,VWC-1
ETR
VINYL WALL COVERING
KEY PLANSET DESCRIPTION
5,6
VWC-1MDC; VYCON OASIS Y449150A; GRASSCLOTH 40150540
Construction
WALL PROTECTION
WP-1KOROGUARD; K-3; PORCELAIN; INSTALL FROM TOP OF BASE TO 40" A.F.F.
Documents
MOB
L
CASEWORK
SHEET TITLE
PLASTIC LAMINATE
PL-1PIONITE; MILLWORK CHERRY; SUEDE FINISH; WC431-S
PL-2PIONITE; IL PALIO PAPEL; SUEDE FINISH; AV981
AREA OF
First Floor Interior Finish
AREA OF CONSTRUCTION
HOSPITAL
M
CONSTRUCTION
CEILING
Plan
P
ACOUSTICAL TILES
1
2
ACT-1ARMSTRONG OPTIMA; 24" x 24" SQUARE LAY-IN #3152; 15/16" ALUMINUM GRID
:
5
COMPLIANT WITH MRI ROOM;
5
:
First Floor Finish Plan
SHEET NUMBER
1
EXISTING FINISHES
7
CENTRAL
1
1/4" = 1'-0"
EXISTING TO REMAIN
True North
PLANT
0
ETREXISTING FINISH IS TO REMAIN; PATCH AND REPAIR AS NECESSARY FOR
2
/
NEW CONSTRUCTION
5
2
/
4
I2-1