Loading...
HomeMy WebLinkAbout03070151.7GENERAL STRUCTURAL NOTES GOVERNING CODE UBC 1997, WITH 1998 INDIANA AMENDMENTS DESIGN LOADS 1. ROOF LOAD: A. MINIMUM LIVE LOAD, RAIN LOAD, OR SNOW LOAD (Pf) 20 PSF* B. ROOF MEMBRANE 1 PSF C. INSULATION 2 PSF D. SHEATHING 2 PSF E. FRAMING LOAD 3 PSF F. CEILING 2 PSF G. SPRINKLERS 2 PSF H. DUCTS, LIGHTS, MISC. 3 PSF G. TOTAL LOAD 35 PSF MIN. (*GROUND SNOW Pg = 20 PSF MODIFIED BY APPLICABLE DRIFT COEFFICIENTS. SNOW LOAD IMPORTANCE FACTOR I = 1.0. SNOW EXPOSURE FACTOR Ce = 0.7. SECONDARY ROOF DRAINAGE VIA SCUPPERS OR OVERFLOW DRAINS SHALL BE PROVIDED IN ACCORDANCE WITH UBC SECTION 1506.3 AND ASCE 7-98.) 2. FLOOR LOAD: A. OFFICE LIVE LOAD 50 PSF*** CORRIDOR LIVE LOAD 100 PSF*** B. PARTITIONS (OFFICE ONLY) 20 PSF C. SHEATHING 3 PSF D. FRAMING LOAD 3 PSF E. CEILING 2 PSF F. SPRINKLERS 1 PSF G. DUCTS, LIGHTS, MISC. 2 PSF TOTAL LOAD 81 PSF MIN. @ OFFICES 111 PSF MIN. @ CORRIDORS (*** LIVE LOAD REDUCTION USED WHERE APPLICABLE) 3. WIND LOAD: A. MAIN WINDFORCE - RESISTING SYSTEM: 71 MPH, EXPOSURE B, WIND LOAD IMPORTANCE FACTOR I = 1.0. BASIC VELOCITY PRESSURE Pv = 13 PSF. 4. SEISMIC LOAD: A. SEISMIC COEFFICIENT (Cv) = 0.18 B. SEISMIC COEFFICIENT (Ca) = 0.12 C. SEISMIC ZONE = 1 D. SEISMIC ZONE FACTOR (Z) = 0.075 E. SOIL PROFILE TYPE = SD F. BASIC STRUCTURAL SYSTEM = LOAD BEARING WALL SYSTEM G. SEISMIC -RESISTING SYSTEM = LIGHT -FRAMED SHEAR PANELS H. RESPONSE MODIFICATION FACTOR (R) = 5.5 I. DEFLECTION AMPLIFICATION FACTOR (Wo) = 2.8 J. ANALYSIS PROCEDURE = STATIC FORCE PROCEDURE 5. CONCENTRATED LOADS: 2000 POUNDS OVER 2.5 FEET SQUARE. CONSTRUCTION AND SAFETY 1. CONTRACTOR SHALL BRACE ENTIRE STRUCTURE AS REQUIRED TO MAINTAIN STABILITY UNTIL COMPLETE AND FUNCTIONING AS THE DESIGNED UNIT, 2. ARCHITECT/ENGINEER SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES OF CONSTRUCTION SELECTED BY CONTRACTOR. 3. THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. WHEN ON SITE, THE ARCHITECT/ENGINEER IS RESPONSIBLE FOR HIS/HER OWN SAFETY BUT HAS NO RESPONSIBILITY FOR THE SAFETY OF OTHER PERSONNEL OR SAFETY CONDITIONS AT THE SITE. 4. ANCHOR RODS/BOLTS SHALL NOT BE REPAIRED, REPLACED OR FIELD - MODIFIED WITHOUT THE WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD. FOUNDATIONS 1. PER CLIENT'S REQUEST, THE FOUNDATION DESIGN AND GENERAL FOUNDATION NOTES ARE BASED ON THE ASSUMPTION OF FAVORABLE SOIL CONDITIONS. THE CONTRACTOR SHALL RETAIN A GEOTECHNICAL ENGINEER TO VERIFY DESIGN ASSUMPTIONS PRIOR TO FOUNDATION INSTALLATION. THE COST FOR THE GEOTECHNICAL ENGINEER SHALL BE LISTED AS A SEPARATE ITEM ON THE CONTRACTOR'S BID. THE CONTRACTOR SHALL SUBMIT COPIES OF THE GEOTECHNICAL ENGINEER'S REPORT TO THE ARCHITECT. ALL FOOTINGS SHALL BEAR ON LEVEL (WITHIN 1 IN 12) UNDISTURBED SOIL OR APPROVED ENGINEERED FILL. FOUNDATIONS HAVE BEEN DESIGNED FOR A MAXIMUM SOIL BEARING PRESSURE OF 3000 PSF. 2. FOUNDATION ELEVATIONS SHOWN ARE FOR BIDDING PURPOSES AND MAY VARY TO SUIT SUB -SURFACE SOIL CONDITION. ELEVATION AND BEARING STRATA SHALL BE APPROVED BY A GEOTECHNICAL ENGINEER PRIOR TO PLACING CONCRETE. PROVIDE ENGINEERED FILL OR LOW STRENGTH CONCRETE (500 PSI) UNDER FOUNDATIONS AT SOFT SPOTS AND FOR EXTENDING EXCAVATION TO ADEQUATE BEARING MATERIAL. INSTALL FOUNDATIONS AT DESIGNED ELEVATIONS. 3. FOOTINGS MAY BE PLACED WITHOUT SIDE FORMS IF EXCAVATED WALLS STAND APPROXIMATELY VERTICAL. 4. LATERAL SOIL PRESSURE USED FOR DESIGN OF: A. RETAINING WALLS: 45 PCF EQUIVALENT FLUID PRESSURE, TRIANGULAR DISTRIBUTION. 5. CONTRACTOR SHALL CONTACT UTILITY COMPANIES FOR LOCATING UNDERGROUND SERVICES AND IS RESPONSIBLE FOR THEIR PROTECTION AND SUPPORT. 6. FILL AND BACK FILL: A. ALL FILL MATERIALS SHALL BE APPROVED BY A GEOTECHNICAL CONSULTANT. B. ENGINEERED FILL BENEATH FOOTINGS: MINIMUM COMPACTION 98% STANDARD PROCTOR DENSITY AT THE OPTIMUM MOISTURE CONTENT. C. BACKFILL AGAINST WALLS: 1. BACKFILL ALONG INTERIOR FACE OF FOUNDATION WALLS SHALL BE: a. CLAYEY MATERIAL COMPACTED IN 6" LIFTS TO 95% STANDARD PROCTOR DENSITY OR CONCRETE WITH A COMPRESSIVE STRENGTH OF f'c = 500 PSI OR b. WELL GRADED GRANULAR MATERIAL COMPACTED IN 6» LIFTS; AT THE BOTTOM OF THE GRANULAR BACKFILL PLACE A 4" DIAMETER PERFORATED FOUNDATION DRAIN PIPE. PROVIDE A POSITIVE SLOPE TO DAYLIGHT OR TO SUMP. 2. BACKFILL ALONG RETAINING TYPE WALLS SHALL BE A WELL GRADED GRANULAR MATERIAL COMPACTED TO 95% STANDARD PROCTOR DENSITY UP TO WITHIN 24 INCHES OF THE FINISHED GRADE. TOP 24" OF BACKFILL SHALL BE COMPACTED CLAYEY MATERIAL. AT THE BOTTOM OF THE GRANULAR MATERIAL, PLACE A 4" DIAMETER PERFORATED FOUNDATION DRAIN PIPE WITH POSITIVE DRAINAGE TO SUMP OR TO DAYLIGHT. 3. BACKFILL ALONG EXTERIOR FACE OF SHALLOW WALL FOUNDATIONS TO BE: a. COMPACTED CLAYEY MATERIAL; COMPACT TO 95% STANDARD PROCTOR. OR b. COMPACTED GRANULAR MATERIAL WITH 4" DIAMETER FOUNDATION DRAIN AT THE BOTTOM OF THE GRANULAR MATERIAL. DRAIN TO HAVE POSITIVE SLOPE TO DAYLIGHT OR TO SUMP. D. FILL BELOW FLOOR SLABS: 1. PROVIDE 6" OF COMPACTED GRANULAR MATERIAL BELOW FLOOR SLAB. 2. TOP 12" OF SUBBASE BELOW INTERIOR FLOOR SLAB TO BE PROOF ROLLED TO 98% STANDARD PROCTOR DENSITY PRIOR TO PLACEMENT OF SLAB. 7, ALL AREAS WITHIN THE FOOTPRINT OF THE BUILDING, INCLUDING UTILITY TRENCHES, MUST BE FREE OF ANY WET AND/OR SOFT AREAS PRIOR TO PLACEMENT OF FILL MATERIAL OR SLAB. 8. SEAL UTILITY TRENCH AT THE EXTERIOR FOUNDATION WALL BY USING A COMPACTED CLAYEY BACKFILL OR LEAN CONCRETE TO CREATE A DAM TO PREVENT ENTRY OF WATER. 9. FINISHED GRADE SHALL SLOPE AWAY FROM THE PERIMETER FOUNDATION. CONCRETE 1. CONCRETE WORK AND TESTING SHALL CONFORM TO ALL REQUIREMENTS OF ACI 301-99, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS", EXCEPT AS MODIFIED BY THE SUPPLEMENTAL REQUIREMENTS BELOW. REPORTS FROM TESTS REQUIRED BY SECTION 1.6 OF ACI 301-99 SHALL BE SUBMITTED TO STRUCTURAL ENGINEER, ARCHITECT, OWNER, CONTRACTOR, CONCRETE SUPPLIER, AND BUILDING OFFICIAL. 2. CONCRETE WORK IN COLD WEATHER SHALL CONFORM TO ALL REQUIREMENTS OF ACI 306.1-90 "STANDARD SPECIFICATION FOR COLD WEATHER CONCRETING" AND ACI 306R-88 "COLD WEATHER CONCRETING". 3. CONCRETE WORK IN HOT WEATHER SHALL CONFORM TO ALL REQUIREMENTS OF ACI 305R-91 "HOT WEATHER CONCRETING". THE AIR TEMPERATURE, RELATIVE HUMIDITY, CONCRETE TEMPERATURE, AND WIND VELOCITY SHALL BE ENTERED INTO NOMOGRAPH FIGURE 2.1.5 TO DETERMINE IF PRECAUTIONS AGAINST PLASTIC SHRINKAGE ARE REQUIRED. 4. NOT USED. 5. MATERIALS: (f'c BASED ON 28 DAY UNLESS NOTED) A. CONCRETE FOR INTERIOR FLOOR SLABS: f'c = 4000 PSI FT 28 DAYS, 1800 PSI AT 3 DAYS, NORMAL WEIGHT AGGREGATE, MINIMUM PORTLAND CEMENT CONTENT PER ACI 301-99 TABLE 4.2.2.1, PLASTICIZING OR WATER REDUCING ADMIXTURE REQUIRED, MAXIMUM WATER/CEMENTITIOUS RATIO = 0.50. MINIMUM CEMENT CONTENT REQUIREMENT PER TABLE 4.2.2.1 MAY BE WAIVED IF A HISTORY OF FINISHING QUALITY, APPEARANCE, DURABILITY, AND SURFACE HARDNESS IS SUBMITTED OR IF A TEST SLAB OF AT LEAST 8 FEET X 8 FEET IS PLACED AT THE JOB SITE USING JOB MATERIALS, EQUIPMENT, AND PERSONNEL AND EVALUATION RESULTS SUBMITTED. B. CONCRETE FOR EXTERIOR FLAT WORK, WALKS, ETC.: f'c = 4500 PSI, (4.5% TO 7.5% ENTRAINED AIR), MAXIMUM WATER/CEMENTITIOUS RATIO = 0.45. LIMIT POZZOLAN CONTENT PER ACI 301-99 TABLE 4.2.2.8. C. CONCRETE FOR FOUNDATION WALLS AND RETAINING WALLS WITH EXTERIOR EXPOSURE: f'c = 4000 PSI, (4.5% TO 7.5% ENTRAINED AIR), MAXIMUM WATER/CEMENTITIOUS RATIO = 0.50. D. CONCRETE FOR FOOTINGS: f'c = 3000 PSI. E. REINFORCING STEEL: ASTM A615 60 KSI YIELD DEFORMED BARS AND ASTM A185 WELDED WIRE FABRIC, FLAT SHEETS ONLY. F. FLY ASH: ASTM C618, TYPE F OR C. WHEN USED, FLY ASH -TO- TOTAL CEMENTITIOUS RATIO SHALL BE 15% MINIMUM. G. GROUND GRANULATED BLAST FURNACE SLAG: ASTM C989. TOTAL GROUND GRANULATED BLAST FURNACE SLAG -TO- TOTAL CEMENTITIOUS RATIO SHALL NOT EXCEED 50% MAXIMUM. H. PLASTICIZING ADMIXTURE: ASTM C1017. I. WATER REDUCING ADMIXTURE: ASTM C494. J. CHLORIDE CONTENT OF CONCRETE: LIMIT TOTAL CHLORIDE ION CONTENT TO AMOUNT INDICATED IN TABLE 4.2.2.6 OF ACI 301-99. ADMIXTURES CONTAINING CHLORIDE ARE NOT PERMITTED IN REINFORCED CONCRETE OR CONCRETE CONTAINING METALS. 6. IF CONCRETE ARRIVES AT THE POINT OF DELIVERY WITH A SLUMP BELOW THAT WHICH WILL RESULT IN THE SPECIFIED SLUMP AT THE POINT OF PLACEMENT AND IS UNSUITABLE FOR PLACING AT THAT SLUMP, THE SLUMP MAY BE ADJUSTED ONCE ONLY TO THE REQUIRED VALUE BY ADDING WATER UP TO THE AMOUNT ALLOWED IN THE ACCEPTED MIXTURE PROPORTIONS. ADDITION OF WATER SHALL BE IN ACCORDANCE WITH ASTM C94. DO NOT EXCEED THE SPECIFIED WATER-CEMENTITIOUS MATERIAL RATIO OR SLUMP IN THE APPROVED MIX DESIGN. DO NOT ADD WATER TO CONCRETE DELIVERED IN EQUIPMENT NOT ACCEPTABLE FOR MIXING. AFTER PLASTICIZING OR HIGH -RANGE WATER REDUCING ADMIXTURES ARE ADDED TO THE CONCRETE AT THE SITE TO ACHIEVE FLOWABLE CONCRETE, DO NOT ADD WATER TO THE CONCRETE. MEASURE SLUMP (AND AIR CONTENT OF AIR ENTRAINED CONCRETE), AFTER SLUMP ADJUSTMENT, TO VERIFY COMPLIANCE WITH SPECIFIED REQUIREMENTS. 7. SLUMP SHALL BE MEASURED PRIOR TO THE ADDITION OF ADMIXTURES AND AFTER THE ADDITION OF ADMIXTURES. 8. LAP SPLICE REINFORCING BARS AS FOLLOWS UNLESS NOTED OTHERWISE: A. BARS WITH MORE THAN 12" OF CONCRETE BELOW - 62 BAR DIAMETERS B. BARS WITH LESS THAN 12" OF CONCRETE BELOW - 48 BAR DIAMETERS 9. REINFORCING BARS SHALL BE FREE OF FORM RELEASE AGENTS. 10. AT CORNERS AND INTERSECTIONS OF FOOTINGS AND WALLS, PROVIDE BENT BARS OF EQUAL SIZE AND AT SAME SPACING AS TYPICAL REINFORCING AROUND CORNER A,-4D/OR INTO ABUTTING FOOTING OR WALL. BARS SHALL HAVE EMBEDMENT OF 30 DIAMETERS (18" MIN.). 11. MACHINE TROWEL FINISH FLOOR SLAB AND CURE USING "CURE AND SEAL" TYPE CURING COMPOUND MEETING FEDERAL SPECIFICATION TT -C-00800, VOC COMPLIANT, 30% MINIMUM SOLIDS CONTENT. FOR APPLICATIONS EXPOSED TO SUNLIGHT USE LIGHT BROOM FINISH AND ACRYLIC BASED CURING COMPOUND. 12. FLOOR SLAB -ON -GRADE SHALL CONFORM TO THE FOLLOWING SURFACE PROFILE TOLERANCES PER ASTM E-1155 AND ACI 117: Ff(FLATNESS) FI(LEVELNESS) SPECIFIED OVERALL VALUE 25 20 MINIMUM LOCAL VALUE 18 13 MAXIMUM GAP UNDER 10 FT. UNLEVELED STRAIGHT EDGE = 1/4". 13, SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR VAPOR BARRIER REQUIREMENTS. VAPOR BARRIER, WHERE REQUIRED, SHALL BE PLACED OVER COMPACTED GRANULAR SUBBASE. 14. REINFORCE ALL INTERIOR SLABS ON GROUND WITH 6 X 6 - W2.9 X W2.9 (42#) WELDED WIRE FABRIC. LOCATE WELDED WIRE FABRIC 2" CLEAR BELOW TOP OF SLAB. 15. LAP WELDED WIRE FABRIC MINIMUM 1 FULL SPACE PLUS 2" 16. DO NOT BACKFILL AGAINST RETAINING WALLS UNTIL CONCRETE STRENGTH HAS REACHED 0.75 f'c AND A MINIMUM OF 7 DAYS. 17. FINISH OF CONCRETE HANDICAP RAMPS TO CONFORM WITH THE REQUIREMENTS OF THE AMERICANS WITH DISABILITIES ACT (ADA). 18. CONTROL JOINTS IN SLABS ON GROUND SHALL BE LOCATED AT 12'-0" MAXIMUM SPACING AND SHALL CREATE SECTIONS OF SLAB WITH A MAXIMUM ASPECT RATIO OF 1.5:1. CONTROL JOINTS SHALL BE SAWN AND SHALL BE A MINIMUM OF 1/4 OF THE SLAB THICKNESS DEEP. THE CONTROL JOINTS SHALL BE SAWN AS SOON AS THE SAW BLADE CAN CUT THE CONCRETE WITHOUT DISPLACING THE AGGREGATE. CUT EVERY OTHER MESH WIRE AT THE CONTROL JOINT LOCATION PRIOR TO PLACING CONCRETE. IF AN EARLY -CUTTING SAW IS BE USED AND A SHALLOWER DEPTH OF THE CUT IS DESIRED, CONTACT THE ENGINEER IN ADVANCE FOR APPROVAL. 19. CONSTRUCTION JOINTS IN SLABS ON GROUND MAY BE LOCATED AT ANY CONTROL JOINT LOCATION. CONSTRUCTION JOINTS SHALL HAVE A KEY FORMED AT MID -DEPTH OF THE FIRST CAST SECTION. THE KEY SHALL BE 1-1/2' DEEP AND SHALL BE 1/3 OF THE SLAB THICKNESS HIGH. THE TOP AND BOTTOM OF THE KEY SHALL HAVE 1 VERTICAL TO 3 HORIZONTAL SLOPE. 20. PROVIDE 3/4" CHAMFER AT CORNERS OF EXPOSED CONCRETE. 21. WHERE BRITTLE FLOOR FINISHES ARE TO BE APPLIED TO FLOOR SLABS, COORDINATE CONTROL JOINT LOCATIONS WITH FLOOR FINISH JOINT LOCATIONS AND ARCHITECT. izevioed / 10OUed: 9-6-02 Iooued fo R11 J a re ttit ecI ti pIatituvrig interior ties 2359 K-:mper ci.ncinnitti. OH TEI.: 533.751. FAX. 513.751 �was .■■. .■■mmol■ .MEMO ,■■■■. n■. �■o■■ i Cornette and Asso Design Consul 2142 Alpine P Cincinnati, Oh Phone(513)2. Fax (513) 221 co 2002 CMC Thio document ane deoi,3no incorporate property of Speer & are not to be uoed whole or in part for or purpooe witho authorization of Date: MAR. 2002 Job No.: