ENTRY SLAB DETAIL
3„ I,
Sheet Number
4,
Job No.:
AA4-d
0 6'
2'
81
V 1 �
CONSTRUCTION NOTES, TH15 SHEET:
1. 4" concrete slab w/42# w.w. mesh & 6 mil. vapor barrier over 6" granular
base over well compacted subgrade. Hold down top of wall 8" and carry
slab through as Shown.
2. Concrete elevator pit walls w/ #4 0 12" o.c. each way.
3. 12" deep x 24" wide concrete footing w/ (2) #5 cont. on undisturbed
earth.
4. Min. 18" granular backfill over drain tile.
5. Drain tile, see Site Plan.
6. Foundation waterproofing.
7. Sump pump pit, coordinate size and location w/ elevator manufacturer.
Coordinate piping with manufacturer.
8. Provide weep holes 0 32" o.c. above continuous flashing.
9. 16" pre-engineered wood floor trusses 0 12" o.c.
10. 3/4" tongue and groove 0513 subflooring or plywood at tile locations.
11. Parapet wall construction consisting of 2x4 wood studs 0 16" o.c.,
3 1/2" batt insulation with vapor barrier, 1/2" exterior grade
sheathing (both sides), tyvek building wrap and 3 5/8" face brick on
exterior (unless noted otherwise).
12. Metal coping over 2x wood blocking, flash and seal each side.
13. 1/2" gypsum board ceiling over 3/4" furring @ 3rd Floor and 1/2" K. C.
channels @ lot and 2nd Floors.
14. 2x4's @ 12" o.c. this wall only.
15. Interior wall construction consisting of 2x4 wood Studs @ 16" o.c. and
1/7" n\inGiim hnarA hni-k GI/lPG (IIVIIOGG vnntoA nt.hvrwic,v
16. Batt insulation.
Al"�17. Ledger: (1) 1 3/4x16" LVL. Provide expansion bolts to bond beam or
grouted cell CMU w/ 2" bolts 0 8" o.c., staggered, embedded 5"
into block. 1 1/2" nails required for hangers at these locations.
18. Pre-engineered wood roof trusses 0 24" o.c.
19. Beam: (3) 1 3/4x16" LVL, flush.
20. Firestone EPPM roofing over 11/2" insulation and 5/8" plywood
substrate.
21. Suspended acoustical tile ceiling.
22. 2x8's 0 12" o.c., joist hanger ea. end.
23.12" deep concrete footing w/ #5 0 12" o.c. each way.
24. 8" CMU wall w/furring and 1/2" drywall, as shown.
25. Face brick Color Type 2, see elevations for locations.
26. 2x8 rafters @ 24" o.c.
27. Curtain wall System, see plans for type and locations.
25.1/2" expansion joint.
29. 2" perimeter inoulation.
30. [)cubic stud plumbing wall consisting of (2) 2x4 studs @ 16" o.c.
(unless otherwise noted), with 1/2" drywall on office side and 1/2"
greerlboard on toilet room side.
31. 2x6s C@ 16" o.c. this wall only.
n32.Ledger: 2x8 expansion bolted to bond beam or grouted cell CMU
w/bolts @ 24 o.c., embedded 5 into block. 11/2" nails
.,.--..: A Ic- L--- 'i- t kl '5c v nr.at.InYI G,
33. W8xl8 hoist beam, center over elevator Shaft.
34. 5/8" gyp. bd., 1 -hr. Shaft assembly termination.
35. Precast concrete lintel.
36. 2x8 attached to truss ends.
37. Steel angle sill Support.
38. Elevator entrance frame.
39. 2x4 kickers 0 48" o.c.
40. 2x8 rafters 9 16" o.c., use double sill plate @ one
end to slope roof as shown, slope min. of 1/4" per foot.
41. W8x21 w/ 2x6 top and bottom, bolted 3'-O" o.c.
42. W10x39 w/ 2x6 top and bottom. bolted 3'-0" o.c.
43. Temp. glass in steel frame railing, see sheet A4.4.
44. W16x26 w/ 2x6 top and bottom, bolted 3'-0" O.G.
45. Steel lintel: L 8x4x2", rolled to match opening Shape
w/ 8" horizontal bearing leg on each side. Provide
weep holes @ 32" o.c above angle and backer rod &
sealant below angle, typical.
46. Beam: T5 10x4xl/4", flush, w/ 2x4 top and bottom.
47. Header: (2) 1 3/4x11 1/4" LVL, flush.
48. 4" face brick over 4" block.
49. GE Zoneline thru-wall HVAC unit.
50.4" exterior concrete slab, slope away from building
maximum of 1:20.
51. 12"x24" concrete footing, sleeve for plumbing linea.
Kevised / Issued:
9-6-02 looued for Permit
1-8-03 Addendum L
arc ?[ii ecrure
planning
i.r,kcr.ior dceig,n
1:159 Kemper l.;ine
Cinc.ir,rtati, Oil 4520
TEL: 51:1.751..1221
FAX: 511,751.0922
STEVEN
SCHAEFER
ASSOCIATES, INC.
CONSULTING ENGINEERS
10411 MEDALLION DRIVE, SUITE 121
CINCINNATI, OHIO 45241
(513) 542-3300 FAX: (513) 542-5540
Cornette
and Associates
Design Consultants
2142 Alpine Place
Cincinnati, Ohio 45206
Phone (513) 221-6600
Fax (513) 221-6606
W
c0 2002 CMC Properties
Thio document and the ideas and
designs incorporated herein are the
property of Speer & Associates. They
are not to be used or reproduced in
whole or in part for any other project
or purpose without the written
authorization of CMC Properties.
Date:
Sheet Number
MAR, 2002
Job No.:
AA4-d