HomeMy WebLinkAbout03070074.9HVAC GENERAL NOTESI
1, CONTRACTOR SHALL PROVIDE ALL LABOR MATERIALS, TOOLS AND
EQUIPMENT TO INSTALL A COMPLETE AND OPERATING HEATING
ARID COOLIWI SYSTEM.
2. CONTRACTOR SHALL PROVIDE ALL REQUIRED HVAC PER; I ITS.
3. THE CONTRACTOR SHALL COMPLY WITH NFPA-WA AND ALL
APPLICABLE CODES.
4. ALL HVAC WORK TO BE PERFORMED SHALL BE IN COMPLIANCE WITH
ALL STATE AND LOCAL CODES.
5. FLEXIBLE DUCT SHALL COMPLY WITH SMACNA, ALL LOCAL
CODES, U.L. RATMG, AND NOT EXCEED FIVE FEET IN LENGTH. SHEET
METAL DUCT SHALL BE LINED WITH 1' MATT FACED DUCTLINER DUCT-
WORK MATERIAL TO BE VERIFIED WITH CEILING ASSEMBLY RATING.
FIBERGLASS DUCTBOARD DUCTWORK IS NOT ACCEPTABLE.
6. CONTRACTOR SHALL PROVIDE ALL CONTACTORS, RELAYS AND
THERMOSTATS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL
SWITCHES, DISCONNECTS AND CONTROL WIRING. THERMOSTATS SHALL
BE BY THE EQUIPMENT MANUFACTURER
1. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS, ALLOW FOR DUCT INSULATION.
S. THE CONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE THAT SHALL
WARRANT ALL WORKMANSHIP AND MATERIALS FOR ONE (l) YEAR FROM
THE FINAL WORK ACCEPTANCE BY THE 010, ER AND A FIVE YEAR WARRANTY
ON THE COMPRESS
9 FILTERS SHALL BE OF THE DISPOSABLE TYPE AND HAVE INITIAL SHARE
WEIGHT ARRESTANCE OF 10% AND A CLEAN PRESSURE DROP OF 0.15
WC. PROVIDE TWO SETS, ONE DURING CONSTRUCTION AND ONE FOR
USE AFTER OCCUPANCY.
10. CONTRACTOR SHALL INSTALL ALL NECESSARY OFFSETS, BENDS, AND
TRANSITIONS REQUIRED TO PROVIDE A COMPLETE SYSTEM AT NO
ADDITIONAL. COST TO THE OWNER
1 I. COORDINATE LOCATION OF ALL CEILING DIFFUSERS, GRILLES AND REGISTERS
IN THE FIELD WITH THE ELECTRICIAN TO PR>=VENT CONFLICT WITH LIGHTS
AND ARCHITECTURAL. ELEMENTS.
12. CONTRACTOR TO FURNISH SHOP DRAWINGS FOR DUCTIIIORIK AND AIR DEVICES.
13. ALL WORK OF THIS TRADE SHALL BE COORDINATED WITH ALL OTHER TRADES TO
AVOID ANY fNTERFER!ENCES THAT MAY DELAY PROGRESS DURING CONSTRUCTION.
14. THERMOSTAT TO HAVE AUTOMATIC HEATMG/COOLING CHANGEOVER FAN
TO RN CONTINUOUSLY DURING BUSINESS HOURS.
15. AN INDEPENDANT AIR BALANCE CONTRACTOR SHALL TEST AND BALANCE TO THE AIR
QUANTITIES ON THE PLAN AND PROVIDE A T t B REPORT, IN ACCORDANCE WITH AIR
BALANCE COUNCIL STANDARDS.
16. CONTRACTOR SHALL INSTALL THERMOSTAT AT 60' ABOVE THE FINISHED FLOOR
i1. CONTRACTOR SHALL INSTALL MANUAL. BALANCING DAMPERS AT ALL SUPPLY AIR
BRANC44 DUCTWORK RUN OUTS.
15. CONTRACTOR SHALL INSTALL TURNING VANES AT ALL DUCTWORK TEES AND W
DEGREE ELBOWS.
a CONTRACTOR SHALL INSTALL A DUCT -TYPE MCkNTED SMOKE DETECTOR IN THE
SUPPLY t RETURN AIR DUCTWORK PLENUM AT RTU. THE CONTRACTOR
SHALL VERIFY THE COMPATIBLE TYPE OF DETECTION DEVICE TO USE WITH THE
BUILDING OPERATIONS MANAGER
20. ALL SHEET METAL DUCTWORK SHALL COMPLY WITH SMACNA STANDARDS. ALL
DUCTWORK JOINTS SHALL BE TAPED AND SEALED.
21. CONTRACTOR SHALL PROVIDE EQUIPMENT OF THE SCHEDULED CAPACITIES DESIGNED.
GRILLE, REGISTER & DIFFUSER SCHEDULE
MARK
MFGR
MODEL
MATERIAL
DEVICE
SIZE
RANrsE
MINj`MAX
INLET
SIZE
AIR
PATTERN
MOUNTING
TYPE
LOCATION
6-1
TITUS
TMS -AA
ALUMINUM
24' x 24'
0/100
6'4
4 -WAY
LAY -IN
SUPPLY
REST ROOM
5-2
TITUS
TMS -AA
ALUMINUM
24' x 24'
100/110
8'0
4 -WAY
LAY -IN
SUPPLY
OFFICE / BACK
6-3
TITUS
TMS -AA
ALUMINUM
24' x 24'
110(115
10'0
4 -WAY
LAY -IN
SUPPLY
5ACKROOM
5-4
TITUS
TMS -AA
ALUMINUM
24' x 24'
215/400
12'4
4 -WAY
LAY -IN
SUPPLY
SALES
R -I
TITUS
I 50F
ALUMM V
24' x 24'
22' x 22'
HORIZ
LAY -IN
RETURN
I SALES
NEW EXHAUST GAN SCHEDULE
MARK
AREA SERVED
MANUFACTURER
MODEL
CFM
E.SP.
('W.CJ
MOTOR
BAROMETRIC
DAMPER
REMARKS
AMPS
V/PH
EF -I
TOILET
BROAN
684
80
0315
0.15
120A
YES
CONNECT TO LIGHT SWITCH
HVAC SPECS
SCALE: 1/49$ - V-091
-0"
DATE: 07/07/03
INTERIOR AREA: 1,400 SQ. FT.
EMR PROJ #: 3100
HAZEL DELL COMMONS
CARMEL, IN.
SALON OWNER: TOM & KATHY
REVISIONS:
MURRAY
OWNER APPROVAL:
GCI HAS CONSENTED
TO SITE:
DRAWN BY: STAFF
IL Great Clips for hair.
s-�
7700 FRANCE ATVENUE SOUTH SUITE 425
MIlVNEAPO1_IS,1IE' 55435
Phone (952) 893-9088 Fax (952) 844-3445
PO Box 213 (Mailing)
4020 HWY 30 W.
Annville, KY 40402
Phone (606)-364-2886
Fax (606)-364-5100
E—Mail: matt®emrengineers.com
Web Address: emrengineers.com