HomeMy WebLinkAbout17100001.15SYMBOLS
CONTROL SYMBOLS
THERMOSTAT
OT
THERMOSTAT IN LOCK BOX
OT
SENSOR
SO
CARBON MONOXIDE SENSOR
CO '°
NITROGEN OXIDE SENSOR
NO
ROUND MOTORIZED DAMPER
M
RECTANGULAR MOTORIZED DAMPER
M
DUCT SYMBOLS
COMBUSTION AIR
CFM
CUBIC FEET PER MINUTE
DEG F
DEGREES FARENHEIT
SHEET METAL DUCT WIDTH BY DEPTH
W/D
LINED SHEET METAL DUCT FREE AREA WIDTH
BY DEPTH.
_ W/D7
SQUARE SHEET METAL 90 DOUBLE
THICKNESS TURNING VANES REQUIRED
�J
RADIUS SHEET METAL 90, R=1.5"D
1:z�
SQUARE SHEET METAL 90 PROVIDE WITH
DOUBLE THICKNESS TURNING VANES.
E�]]
TURNING VANES DOUBLE THICKNESS
ENTERING AIR WET BULB
ROUND HIGH EFFICIENCY BRANCH DUCT
TAKE OFF ON ROUND DUCT.
ELECTRICAL CONTRACTOR
ROUND TAP BRANCH DUCT TAKE OFF ON
ROUND DUCT.
EXHAUSTFAN
HIGH EFFICIENCY BRANCH DUCT TAKE OFF
ON RECTANGULAR.
ELECTRIC WALL HEATER
STANDARD ROUND TAP BRANCH DUCT TAKE
OFF ON ROUND DUCT.
ELECTRIC WATER COOLER
MANUAL VOLUME DAMPER LOCKING WITH SHAFT
ELECTRIC REHEAT COIL
CENTERED SQUARE TO ROUND TRANSITION
EXTERNAL STATIC PRESSURE
ECCENTRIC SQUARE TO ROUND TRANSITION
EXPANSION TANK
RECTANGULAR CENTERED DUCT TRANSISTION
ED
RECTANGULAR ECCENTRIC DUCT TRANSITION
FAN COIL UNIT
FULL BODY ROUND TEE FITTING
FIRE DAMPER OR FLOOR DRAIN
EQUIPMENT SYMBOLS
FIRE AND SMOKE DAMPER
FPM
FEET PER MINUTE
AIR COOLED CONDENSING UNIT
® ACCU
FT
FOOT
ROOF MOUNTED INTAKE/EXHAUST HOOD
RECTANGULAR
IH
RH
ROOF MOUNTED INTAKE/EXHAUST HOOD
ROUND
IH
• RH
HORIZONTAL FURNACE OR FC WITH
DRAIN PAN
FC
F
HORIZONTAL AIR COOLED CONDENSING UNIT
AC
CEILING MOUNTED EXHAUST FAN
EF
ELECTRIC WALL HEATER
�] EWH
DIFFUSER SYMBOLS
INCH
IR
INFRA -RED
LAY -IN SUPPLY AIR DIFFUSER
LAVATORY
LAY -IN RETURN AIR REGISTER OR GRILLE
LEAVING AIR TEMPERATURE
LINEAR OR SLOT DIFFUSER
LIQUID LINE SOLENOID VALVE
DIRECT DUCT MOUNTED REGISTER
LINEAR SLOT DIFFUSER
BOOT MOUNTED REGISTER
El
DIFFUSER TAG
X-# MARK
XXX CFM
ABBREVIATIONS
AFF
ABOVE FINISH FLOOR
ACCU
AIR COOLED CONDENSING UNIT
AHU
AIR HANDLING UNIT
BDD
BACKDRAFT DAMPER
BOD
BOTTOM OF DUCT
CO
CLEAN OUT
CW
COLD WATER DOMESTIC
CA
COMBUSTION AIR
CFM
CUBIC FEET PER MINUTE
DEG F
DEGREES FARENHEIT
DB
DRY BULB
0
ROUND
EA
EACH
EG
EXHAUST GRILLE OR REGISTER
EADB
ENTERING AIR DRY BULB
EAWB
ENTERING AIR WET BULB
EC
ELECTRICAL CONTRACTOR
EF
EXHAUSTFAN
EWH
ELECTRIC WALL HEATER
EWC
ELECTRIC WATER COOLER
ERC
ELECTRIC REHEAT COIL
ESP
EXTERNAL STATIC PRESSURE
ET
EXPANSION TANK
F
FURNACE
FCU
FAN COIL UNIT
FD
FIRE DAMPER OR FLOOR DRAIN
FD/SD
FIRE AND SMOKE DAMPER
FPM
FEET PER MINUTE
FPVAV
FAN POWERED VAV BOX
FT
FOOT
FSK
FOIL SCRIM VAPOR BARRIER
GC
GENERAL CONTRACTOR
GPM
GALLONS PER MINUTE
H
HOOD
HWR
HOT WATER RETURN DOMESTIC
HWS
HOT WATER SUPPLY DOMESTIC
IN
INCH
IR
INFRA -RED
LAV
LAVATORY
LAT
LEAVING AIR TEMPERATURE
LLSV
LIQUID LINE SOLENOID VALVE
LS
LINEAR SLOT DIFFUSER
MAN
MANUAL
MFR
MANUFACTURER
MBH
1000 BTU
MC
MECHANICAL CONTRACTOR
MCC
MOTOR CONTROL CENTER
MS
MOP SINK
OA
OUTSIDE AIR
PC
PLUMBING CONTRACTOR
PRV
PRESSURE RELEIF VALVE
PSI
POUNDS PER SQUARE INCH
PD
PRESSURE DROP
PDU
POOL DEHUMIDIFICATION UNIT
PRV
PRESSURE RELEIF VALVE
PSI
POUNDS PER SQUARE INCH
PTAC
PACKAGE TERMINAL AIR CONDITIONER
RA
RETURN AIR
RJ
ROOF JACK, MATCH ROOF COLOR
RPZB
REDUCED PRESSURE ZONED BACKFLOW
RPM
REVOLUTIONS PER MINUTE
RTU
ROOF TOP UNIT
SA
SUPPLY AIR
SAF
SUPPLY AIR FAN
SCRN
GALVNIZED WIRE SCREEN, 1/2X1/2
SP
STATIC PRESSURE
SAN
SANITARY SEWER
SD
STORM DRAIN
ST
STORAGE TANK
SK
SINK
TCC
TEMPERATURE CONTROL CONTRACTOR
TMV
THERMOSTATIC MIXING VALVE
TSP
TOTAL STATIC PRESSURE
UR
URINAL
UON
UNLESS OTHERWISE NOTED
VAV
VARIABLE AIR VOLUME BOX
VTR
VENT THROUGH ROOF
WC
WALL CAP
WC
WATER CLOSET
WH
WATER HEATER
WIC
WALK IN COOLER
WIF
WALK IN FREEZER
MECHANICAL SPECIFICATIONS
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE
BASE BID IN STRICT ACCORDANCE WITH DESIGN
BASIS EQUIPMENT AND MATERIALS. PROJECT DOES
ENCOURAGE COMPETITIVE PRICING AND ALLOWS
FOR SUBSTITUTIONS OF EQUIPMENT AND
MATERIALS AS ALTERNATE DEDUCTS TO BASIS OF
DESIGN BIDS. LIST ALL SUBSTITUTIONS ALONG WITH
DEDUCTS OFFERED ON BID. ENGINEER RESERVES
THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT
TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS.
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL
SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL
ENERGY CONSUMING OR PRODUCING ITEMS AND
FOR ALL DUCT ACCESSORIES. INSULATION. VAV
BOXES. REGISTERS. GRILLES. DIFFUSERS AND
LOUVERS. SUBMITTALS SHALL BE DELINEATED WITH
TAGS INDICATED ON PRINTS, CONTRACTORS NAME.
PROJECT NAME. CLEARLY INDICATE ALL MODEL
NUMBERS AND ALL ACCESSORIES AND OPTIONS
BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF
FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER
DESIGN BASIS OR APPROVED EQUAL. ENGINEER
RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE
ITEM.
3. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE
SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY
WAY AFFECT THE EXECUTION OF HIS WORK. HE
SHALL ALSO EXAMINE THE DRAWINGS AND
SPECIFICATIONS FOR OTHER BRANCHES OF WORK
MAKING REFERENCE TO THEM FOR DETAILS OF
EXISTING BUILDING CONDITIONS. NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO INCLUDE ALL
REQUIRED WORK IN THE BID. CONTRACTOR SHALL
GUARANTEE ALL LABOR AND MATERIALS ENTERING
INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR
FROM DATE OF ACCEPTANCE.
4. THE DRAWINGS IN THIS SECTION ARE
DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE
EXACT QUANTITIES, LOCATIONS OR CODIFIED
REQUIREMENTS. DRAWINGS SHOW GENERAL
INTENT OF SYSTEMS. M.C. SHALL PROVIDE AND PAY
FOR ALL REQUIRED PERMITS.
5. UPON COMPLETION OF THE MECHANICAL
INSTALLATION, DEMONSTRATE TO THE ENGINEER
AND THE OWNER'S SATISFACTION THAT THE
SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE
WITH THE DRAWINGS, SPECIFICATIONS AND
APPLICABLE CODES. DEMONSTRATE THE DYNAMIC
OPERATION OF EACH SYSTEM. VERIFY PROPER
OPERATION OF EQUIPMENT, FILTERS ARE CLEAN
AND COMPONENTS OF THE SYSTEM ARE INSTALLED
AND ADJUSTED IN FULL ACCORDANCE WITH
MANUFACTURER RECOMMENDATIONS.
6. ALL WORK SHALL BE IN FULL ACCORDANCE WITH
2014 INDIANA MECHANICAL CODE (2012
INTERNATIONAL MECHANICAL CODE). INDIANA
ENERGY CODE (ASHRAE 90.1-2007) PERTINENT
STATE, COUNTY.. CITY CODES AND ORDINANCES AND
INDIANA AMENDMENTS
7. MECHANICAL CONTRACTOR SHALL ENSURE
EMPLOYEES ARE MEETING AND DOCUMENTING ALL
OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS
REQUIRED BY LAW AND BY CONTRACT. PERSONAL
PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND
UTILIZED AS REQUIRED, MECHANICAL CONTRACTOR
SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE
TO COMPLY WITH OSHA REQUIREMENTS.
DUCTWORK
1. ROUND DUCT SHALL BE LINDAB OR EQUAL
GALVANIZED STEEL CONFORMING TO ASTM
STANDARDS A653 AND A924 GASKETED SPIRAL
DUCTING WITH NO SEALER. EDPM RUBBER GASKET
SHALL BE U.L. CLASSIFIED RATING OF FLAME
SPREAD 0 AND SMOKE DEVELOPED 5 IN
ACCORDANCE WITH ASTM STANDARD E84 -91A
SMACNA LEAKAGE CLASS 3. FITTINGS SHALL BE
MANUFACTURED USING ONE OR MORE OF THE
FOLLOWING CONSTRUCTION METHODS:
OVERLAPPED EDGES STITCH WELDED ALONG THE
ENTIRE LENGTH OF THE FITTING. STANDING SEAM
GORE LOCKED AND INTERNALLY SEALED, BUTTON
PUNCHED AND INTERNALLY SEALED. ELBOWS 3 -INCH
THROUGH 12 -INCH DIAMETER WILL BE DIE STAMPED
AND CONTINUOUSLY STITCH WELDED.
3. PROVIDE SHEET METAL 90 FOR ALL TURNS DO NOT
USE FLEXIBLE DUCT FOR GREATER THAN 45 DEG
CHANGES IN DIRECTION. PROVIDE MANUAL
BALANCING DAMPERS FOR ALL SUPPLY AIR RUNS.
ROUND DAMPERS SHALL BE SECURED ON BOTH
SIDES OF DUCT AND SHALL CONTAIN LOCKING
HANDLE. SPIRAL DUCTS SHALL USE SPIRAL STYLE
DAMPERS WITH FULL WIDTH SHAFT AND NYLON
BEARINGS AT EACH END. RECTANGULAR DUCTS
SHALL USE MULTI OR SINGLE BLADE WELDED
FRAMED DAMPERS WITH JACK SHAFTS AND LOCKING
HANDLE. INSTALL NYLON RIBBON ON ALL DAMPER
HANDLES TO AID IN LOCATION OF DAMPER.
4 CONCEALED AREAS: INSULATED FLEXIBLE DUCTING
FOR STRAIGHT CONNECTIONS SHALL NOT EXCEED 7
FEET. FLEXIBLE DUCT EQUAL TO FLEXIBLE DUCT
CLASS 1 AIR DUCT, DOUBLE LAMINATED POLYESTER
FILM ON STEEL WIRE REINFORCING, INSULATED
WITH SCRIM REINFORCED METALIZED POLYESTER
OUTER FIRE RETARDANT JACKET. R-4.2 FOR
CONDITIONED SPACES AND R-6.0 FOR ANY SPACES
OUTSIDE BUILDING THERMAL ENVELOPE.
5. RECTANGULAR DUCTWORK SHALL BE
CONSTRUCTED IN ACCORDANCE WITH SMACNA LOW
PRESSURE DUCT STANDARDS. +/- 1.0" W.C. FROM
ASTM A 653/A 653M G-90 COATED GALVANIZED
SHEET STEEL. SEAMS SHALL BE PITTSBURGH
CONSTRUCTION, NO BUTTON PUNCH OR SNAP LOCK
SEAMS ARE ACCEPTABLE. SEAL ALL TRANSVERSE
AND LONGITUDINAL SEAMS WITH WATER BASED
DUCT SEALER, SEAL CLASS B. GAUGE AND JOINT
CLASSIFICATIONS ACCEPTABLE ARE AS FOLLOWS,
ALL SECTION LENGTHS ARE 48" MAXIMUM, REFER TO
SMACNA RIGIDITY TABLES FOR GAUGES ON LONGER
SECTIONS IF REQUIRED:
< 12" 26 GAUGE, FLAT S AND DRIVE
12"-24" 24 GAUGE. FLAT S AND DRIVE
25"-34" 22 GAUGE. STANDING S AND FLAT
DRIVE
34"-40" 22 GAUGE, STANDING S AND STANDING
DRIVE
>40" REFER TO SMACNA FOR STANDARDS.
6. DUCT HANGERS: COMPLY WITH SMACNA'S "HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE." CHAPTER 5, "HANGERS AND SUPPORTS."
PROVIDE GALVANIZED MINIMUM 22 GAUGE 1" WIDE
STRAP TO HANG RECTANGULAR DUCTWORK
SMALLER THAN 30" WIDE. DUCT HANGERS FOR
RECTANGULAR SHEET METAL DUCTS 30" AND
LARGER SHALL BE TRAPEZE STYLE USING
UNI -STRUT AND 3/8" OR 1/2" ROD, PROVIDE GRIPPLE,
DURODYNE OR EQUAL CABLE HANGERS FOR
HANGING ROUND DUCTWORK. SUPPORT ALL
HANGERS FROM STRUCTURE PER SMACNA
STANDARDS. HANGERS FOR SPIRAL DUCTS GREATER
THAN 28" IN DIAMETER SHALL BE HUNG WITH ROD
AND DUCT CLAMP. FLEXIBLE DUCTING SHALL BE
SUPPORTED USING MINIMUM 2" WIDE NYLON STRAP.
ALL INTERVALS ARE PER SMACNA.
DUCT ACCESSORIES
1. COORDINATE WITH ARCHITECTURAL DRAWINGS AND
PROVIDE FIRE AND FIRE AND SMOKE DAMPERS AT
FIRE RATED ASSEMBLY PENETRATIONS IN
ACCORDANCE WITH THE INTERNATIONAL BUILDING
CODE.
DUCT INSULATION
2. ALL DUCT INSULATION MATERIALS SHALL HAVE A
FLAME SPREAD RATING OF 25 OR LESS (ON THE
FLAME SPREAD TEST SCALE) AND SMOKE
DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST
SCALE) OR AS DEFINED BY NFPA 255 STANDARD
METHOD OF TESTING OF SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS, LOCAL
CODES AND LOCAL AUTHORITIES HAVING
JURISDICTION. DUCT WRAP SHALL BE FIBERGLASS
MATERIAL PER ASTM C-411.ASTM C-1104,ASTM C665,
ASTM C-1338. ASTM E-84, UL723, NFPA 90A,CAN/ULC
S102-1188,ASTM C1290, ASTM C553, ASTM C1136.
3. INSULATION: INSTALL ALL INSULATION IN STRICT
ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO
SAGGING, FRAYED OR TORN INSULATION WILL BE
EXCEPTED, UNLESS OTHERWISE NOTED ON PLANS
DUCTWORK SHALL BE INSULATED ,4S FOLLOWS:
FIRE STOPPED OR CAULKED WATER AND AIR TIGHT.
2. REFRIGERATION PIPING:
A. SYSTEMS 5 TONS OR LESS, MANUFACTURED
REFRIGERANT LINE SETS: ANNEALED -COPPER
SUCTION AND LIQUID LINES FACTORY CLEANED,
DRIED, PRESSURIZED WITH NITROGEN, SEALED, AND
WITH SUCTION LINE INSULATED. PROVIDE IN
STANDARD LENGTHS FOR INSTALLATION WITH
MINIMUMAL JOINTS. USE WROUGHT -COPPER
FITTINGS BRAZED WITH 15% SILVER SIL-FLOS
BRAZING ROD.
B. INSULATION, SUCTION AND ALL DUCTLESS SPLIT OR
VRF LINES: MINIMUM 1/2" THICK WALL INSULATION
SHALL BE A FLEXIBLE, CLOSED -CELL ELASTOMERIC
PIPE INSULATION. AP ARMAFLEX OR AC ACCOFLEX.
ADHESIVE SHALL BE ARMAFLEX 520, 520 BLACK OR
520 BLV ADHESIVE THE INSULATION MUST
CONFORM TO ASTM C534 GRADE 1, TYPE I
ARMAFLEX AND BE INSTALLED IN STRICT
ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS. (3/8" WALL WILL NOT BE
ACCEPTED).
C. ALL INSULATION EXPOSED TO OUTDOORS SHALL BE
EITHER PVC LAGGED OR SHALL BE PAINTED WITH
ARMA-FINISH FR UV PROTECTING PAINT.
D. LINES SHALL BE RUN KINK FREE AND GENERALLY
CONTINUOUS AND AT 90 DEGREE ANGLES TO
STRUCTURE. AVOID JOINTS WHEN POSSIBLE. ALL
REQUIRED JOINTS SHALL BE MADE IN ACCESSIBLE
LOCATIONS OR M.C. SHALL PROVIDE ACCESS
PANELS AS NEEDED. ALL BENDS SHALL BE MADE
WITH LONG RADIUS FITTINGS OR WITH MECHANICAL
BENDING TOOL TO PROVIDE SMOOTH LONG RADIUS
TURNS. SUPPORT ALL PIPING WITHOUT CRUSHING
OR DEPRESSING INSULATION. USE REFRIGERATION
STYLE CUSH CLAMPS MOUNTED TO STRUT, DO NOT
LAY PIPING ON STRUCTURAL BUILDING MEMBERS
SLEEVE ALL PENETRATIONS AND SEAL WATER
TIGHT.
E. PRESSURE TEST, TRIPLE EVACUATE AND PREPARE
ALL PIPING IN STRICT ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS.
3. CONDENSATE PIPING
SA- OFFICE SYSTEM: 1-1/2" FIBERGLASS A.
DUCT WRAP WITH FSK FACING, 75 #/FT3
MINIMUM APPLIED R-3.5 INSTALLED IN
STRICT ACCORDANCE WITH
MANUFACTURERS REQUIREMENTS,
SARA- EXPOSED IN STORAGE AREAS: NONE
REQUIRED.
RA EQUIPMENT RA PLENUMS AND
FURNACE BOXES; DUCT LINER FOR
DUCTS SHALL BE
MINIMUM 1" THICK, 1-1/2 # DENSITY PER
CU. FT., HAVING MAT FACED OR
MONOLITHIC CONSTRUCTION WITH SKIN
SMOOTH MICROBIAL SURFACE TO
WITHSTAND VELOCITIES TO 4000 FPM.
INSULATION SHALL FIT SNUGLY
AGAINST THE INTERIOR DUCT
SURFACES, AND BE FASTENED TO THE
DUCT WITH A 50% HEAVY COAT OF
RECOMMENDED ADHESIVE AND METAL
FASTENERS WHICH DO NOT PIERCE
THE DUCT, SPACED
ON 12" CENTERS. ALL EXPOSED EDGES
OF THE INSULATION SHALL BE COATED
WITH MANUFACTURED RECOMMENDED
ADHESIVE
EA- NONE REQUIRED UNLESS NOTED ON
PLANS.
PROVIDE TRAPS BUILT FROM INDIVIDUAL FITTINGS
ON ALL EVAPORATOR DRAIN PANS MINIMUM DEPTH
1.5 TIMES BLOWER BLOCKED TIGHT STATIC
PRESSURE. ALL TRAPS SHALL BE CONSTRUCTED
WITH PVC 90S (MANUFACTURED RUNNING TRAP
FITTINGS ARE NOT ACCEPTABLE). PROVIDE ALL
TRAPS WITH CLEAN OUTS AND REMOVABLE CAPS AS
NEEDED FOR MAINTAINING LINES.
B. HVAC CONTRACTOR SHALL COORDINATE
CONDENSATE DISPOSAL POINTS WITH P.0 HVAC
CONTRACTOR IS RESPONSIBLE FOR PIPING FROM
EVAPORATOR COILS TO DISPOSAL POINT. P.C. IS
RESPONSIBLE FOR STAND PIPES, FLOOR AND HUB
DRAINS AS NEEDED.
C. POLYVINYL CHLORIDE DRAIN, WASTE AND VENT PIPE
(PVC) SCHEDULE 40 MINIMUM SIZE 3/4". INSULATED
IN RETURN AIR PLENUMS.
D. PROVIDE CONDENSATE PUMPS AS REQUIRED WITH
HIGH LEVEL SHUT DOWN SWITCHES INTERLOCKED
TO A/C UNITS
E. PITCH ALL PIPING MINIMUM4" PER FOOT. SUPPORT
PIPING AT MINIMUM 5'-0'' INTERVALS. SECURE FINAL
CONNECTION AT SEWER WITH MINIMUM 1-1/2" AIR
GAP CONNECTION.
F. INSULATE ALL PIPING IN RA PLENUMS AND ABOVE
HARD CEILINGS WITH MINIMUM 3/8" WALL ARMAFLEX
INSULATION
4. FIRE STOPPING.
A.
OA- ALL: 1-1/2" FIBERGLASS DUCT WRAP
WITH FSK FACING, 75 #/FT3 MINIMUM
APPLIED R-3.5 INSTALLED IN STRICT B
ACCORDANCE WITH MANUFACTURERS
REQUIREMENTS,
C.
CHECK TEST AND START UP REQUIREMENTS
1. LABEL ALL MAJOR PIECES OF EQUIPMENT WITH
LAMACOID PLASTIC, BLACK WITH WHITE LETTERS.
SIZE TO BE CONSISTENT WITH EQUIPMENT BEING
LABELED, LENGTH AND WIDTH VARY FOR REQUIRED
LABEL CONTENT. THERMOSTAT AND SENSOR
LABELS SHALL BE ADJUSTED TO PROVIDE ESTHETIC
APPEARANCE.
2. PROVIDE AIR BALANCE BY CONTRACTOR.
CONTRACTOR SHALL BALANCE SUPPLY, RETURN.
OUTSIDE, RELIEF AND EXHAUST AIR SYSTEMS IN
ACCORDANCE WITH CURRENT SMACNA. NEEB OR
AABC STANDARDS TO DESIGN VALUES AND PROVIDE
WRITTEN REPORT TO ARCHITECT. MECHANICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING ALL DEVICES. DRIVES, SHEAVES, MOTOR
CHANGES AND REWORK AS REQUIRED TO MEET
DESIGN REQUIREMENTS.
791
E
3. TEMPERATURE CONTROL WORK SHALL BE THE
RESPONSIBILITY OF THE HVAC CONTRACTOR. F
PROVIDE ALL COMPONENTS INCLUDING T/S, T/S
WIRE (PLENUM RATED IN RA PLENUMS), SWITCHES,
ACTUATORS ETC, AS REQUIRED FOR A COMPLETE
SYSTEM.
1. PIPING SLEEVES, INTERIOR OR EXTERIOR ABOVE
GRADE; GALVANIZED -STEEL ROUND OR
RECTANGULAR SLEEVES OR PVC -PIPE SLEEVES,
VERIFY, WITH FIRE AUTHORITIES HAVING
JURISDICTION, THAT PVC MATERIALS ARE ALLOWED
FOR SLEEVES. ALL SLEEVES SHALL- BE SEALED AND
FIRE STOPPING SYSTEMS SHALL BE IN FULL
COMPLIANCE WITH SECTIONS 713 OF THE IBC AND
SECTION 607 OF THE IMC.
CONTRACTOR SHALL MAKE REFERENCE TO
ARCHITECTURAL PLANS AND PROVIDE ALL
REQUIRED FIRE STOPPING,
CONTRACTOR SHALL PROVIDE FULL SUBMITTAL
INDICATING METHODS OF CONSTRUCTION AND UL
LISTING OF EACH SYSTEM,
DUCTS AND AIR TRANSFER OPENINGS.
PENETRATIONS OF FIRE -RESISTANCE -RATED WALLS
BY DUCTS THAT ARE NOT PROTECTED WITH
DAMPERS SHALL COMPLY WITH SECTIONS 713.2
THROUGH 713.3.3 OF THE IBC. PENETRATIONS OF
HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A
SHAFT AS PERMITTED BY EXCEPTION 4 OF SECTION
708 2, AND NOT REQUIRED TO BE PROTECTED WITH
FIRE DAMPERS BY OTHER SECTIONS OF THE IBC
CODE. SHALL COMPLY WITH SECTIONS 713.4
THROUGH 713.4.2.2 OF THE IBC. DUCTS AND AIR
TRANSFER OPENINGS THAT ARE PROTECTED WITH
DAMPERS SHALL COMPLY WITH SECTION 716.
FIRE DAMPERS, SMOKE DAMPERS. COMBINATION
FIRE/SMOKE DAMPERS AND CEILING RADIATION
DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND
SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN
ACCORDANCE WITH THE REQUIREMENTS OF
SECTION 607 OF THE IMC. AND THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS
AND LISTING.
ACCESS DOORS SHALL BE PERMITTED IN CEILINGS
OF FIRE -RESISTANCE -RATED FLOOR/CEILING AND
ROOF/CEILING ASSEMBLIES PROVIDED SUCH DOORS
ARE TESTED IN ACCORDANCE WITH ASTM E 119 OR
UL 263 AS HORIZONTAL ASSEMBLIES AND LABELED
BY AN APPROVED AGENCY FOR SUCH PURPOSE. ALL
ACCESS DOORS SHALL BE PROVIDED BY TRADE
MAKING PENETRATIONS.
chltura
ARCHITECTURE PLANNING DESIGN CREATION
55 MONUMENT CIRCLE
SUITE 1212
INDIANAPOLIS, INDIANA
46204 - 2910
PH 317-348-1000
FAX 317-951-1213
WWW .ARCH ITU RAC O R P. C O M
GOODERUM & ASSOCIATES ENGINEERING
MEP Engineer
874 Cheltenham Way Q
Avon. IN 46123
P: 317.506.8151
F: 317.745.5761
E: gnaengineering@aol.com
THIS DRAWING AND ALL INFORMATION ON IT IS THE
PROPERTY OF ARCHITURA CORPORATION. IT IS
CONFIDENTIAL AND ITS SUBMISSION OR DISTRIBUTION
TO MEET OFFICIAL REGULATORY REQUIREMENTS OR
FOR OTHER PURPOSES IN CONNECTION WITH THIS
PROJECT IS NOT TO BE CONSTRUED AS PUBLICATION
IN DEROGATION OF COMMON LAW COPYRIGHT OR
OTHER RESERVED RIGHTS. THIS DRAWING NOR ANY
PART OF IT NOR ANY INFORMATION CONCERNING IT
MAY BE COPIED, EXHIBITED, REPRODUCED OR
FURNISHED TO OTHERS NOR MAY PHOTOGRAPHS BE
MADE OF ANY ARTICLE FABRICATED OR ASSEMBLED
FROM THIS DRAWING WITHOUT WRITTEN CONSENT
OF ARCHTURA CORPORATION.
m COPYRIGHT 2014 ARCHITURA CORPORATION
SIGNATURE
SEAL 09-12-2017
���ouG 11 wwwulnrpgp Wi
qQ: No, G3'
10200395;
Q' STATE OF
DATE: 09/12/17
COMMISSION: 17100
DRAWING BY:
CHECKED BY:
REVISIONS
MICHIGAN ROAD
SELF STORAGE
MICHIGAN ROAD
CARMEL, IN 46032
SHEET TITLE
HVAC SYMBOLS,
ABBREVIATIONS AND
SPECIFICATIONS.
SHEET NUMBER
M001