RECTANGULAR
DUCT
BRANCH
OCL CONNECTION
TAKE OFF. HAMMER
LOCKED OR FLANGED AND
FULLY SEALED
ROUND SHEET METAL
DUCT TO DIFFUSER V.D.
0
J
Of
Q �-
30' MAX
ECCENTRIC TRANSITION MAX,
30 DEG.
0
J
45 DEG. HIGH EFFICIENCY
TAKE OFF COMPLETELY
SEALED
30' MAX
OFFSET PROVIDE MINIMUM 2"
STRAIGHT SECTION AT EACH
END. MAX 30 DEG.
NOTE
IN GENERAL, ELBOWS TO HAVE
FULL TURNING RADIUS (R=A).
WHERE "R" IS EQUAL TO OR
GREATER THAN "A" MINIMUM
RADIUS (R) = 4 INCHES.
CONCENTRIC
TRANSITION MAX, 45
DEG. DIVERGING AND
60 DEG. CONVERGING
EQUIP MANUFACTURER SUPPLIED
CONCENTRIC VENT TERMINAL
NOTE MAINTAIN ALL
CLEARANCES PER IFGC DIRECT
VENTING SECTIONS. 10' FROM RUBBER BOOT DECK FLASHING SPECIFICALLY
FORCED AIR INTAKES. DESIGN FOR METAL PANEL SYSTEM.
IN -
SEAL WITH POLYURETHANE BASED SEALER,
12" SIKAFLEX-221 OR EQUAL SILICONE SEALANT
IS NOT ACCEPTABLE
METAL WALL PANEL
11
STRUCTURAL MEMBER
FIELD INSTALL PIPE
SUPPORT. BRACE TO
STRUCTURE
FIELD ROUTE PVC VENTING IN STRICT
4ACCORDANCE WITH EQUIP. MANUF.
RECOMMENDATIONS, SLOPE AT MIN .25%
METAL WALL CONCENTRIC FLUE PIPING DETAIL
NO SCALE
NOTE. TXV METERING DEVICE
DOUBLE THICKNESS
TURNING VANES TO BE USED MANDATORY
WHERE NORMAL RADIUS
ELBOW IS IMPRACTICAL
IS WITHIN
& WHERE ELBOW 5
FT OF A PITCH SUCTION LINE
BRANCH TAKE -OFF. TOWARD
COMPRESSOR. SIZE
OIL RETURN TRAPS
PER MANUFACTURES
PIPING
TIONS
DUCT CONSTRUCTION DETAILS RECOMMENDA
SCALE: NONE
SEE SPECIFICATIONS FOR
MAXIMUM LENGTH OF FLEX, NO
SECURE FLEXIBLE DUCT TO KINKS SUPPORT WITH MINIMUM
SUPPLY DIFFUSER ELBOW 2" NYLON STRAP.
FITTING WITH DRAWBANDS.�
SHEET METAL ELBOW
1-112" DUCT WRAP COVER
ENTIRE BACK SIDE OF
DIFFUSER TO T BARS.
SUPPLY DIFFUSER
LAY -IN DIFFUSER DETAIL
NO SCALE
MATCHING WIDTH CASED EVAPORATOR
COIL SEALED TO FURNACE AND SUPPLY .
AIR DUCT.
REFRIGERATION GRADE TYPE L
COPPER LINE SET WITH 1/2" WALL
ARMAFLEX SIZE PER
MANUFACTURE --��
TRAPPED PRIMARY AND
INDEPENDENT SECONDARY 3/4"
PVC DRAIN LINE. ROUTE
SECONDARY TO DRAIN PAN.
PROVIDE OPEN SITE DRAIN
CONNECTION TO PROTECT
COMBUSTION BLOWER
PROVIDE LINED SHEET METAL
RETURN AIR FURNACE BOX
UNDER ALL FURNACES. NO SIDE
FURNACE CONNECTIONS
ALLOWED.
ROUTE PRIMARY DRAIN TO
HUB DRAIN AT WALL. F—
MINIMUM SLOPE 14" PER /
FOOT. SECURE LINE AND TIE G/
CEILING
SARA DUCTS SEAL TIGHT AT
CEILING PENETRATIONS.
M FRESH AIR DUCT WITH MOTORIZED
DAMPER INTERLOCKED TO
FURNACE BLOWER PROVIDE
MANUAL VD AND BALANCE TO
CEILING SCHEDULED CFM
PVC VENT AND COMBUSTION AIR
PIPING ROUTED TO CONCENTRIC
WALL VENT. PITCH TOWARD
FURNACE MINIMUM 1/4" PER FOOT.
INSTALL PER MANUFACTURERS
INSTRUCTIONS. SEE VENT
TERMINAL DETAIL THIS SHEET.
UPFLOW
$.
FURNACE AGA GAS VALVE 2 PSIG TO 7"W.0
VENTLESS REGULATOR, DIRT LEG
AND UNION CONNECTED TO
r— FURNACE
TTIC SEAL
16" MIN. I- TIGDHT UCT AT CEILINGOPENETRIATION
MANUFACTURERFILTER RACK
OFF AT HUB DRAIN, PROVIDE MINIMUM 1-1/2 DEEP SEALED WITH 2" PLEATED MERV 8 FILTER.
SECONDARY DRAIN PAN WITH
MOISTURE SWITCH. WIRE SWITCH TO
SHUT DOWN FURNACE IF PRIMARY
DRAIN FAILS
107�,OFFICE AREA FURNACE DETAIL
SCALE: NOT TO SCALE
PROVIDE HARD SHUT
OFF LIQUID LINE
SOLENOIDS FOR ALL
UNITS
SLOPE
PROVIDE AND INSTALL
REFRIGERANT TUBING WITH
1/2" WALL ARMAFLEX
INSULATION. ALL FITTINGS
SHALL MADE WITH LONG
RADIUS BENDS
SLOPE
WALL SLEEVE
SEALED
WATER TIGHT
CONDENSER DETAIL
SCALE: NOT TO SCALE
INSTALL ALL REFRIGERATION
ACCESSORIES AS RECOMMENDED BY
MANUFACTURER FOR LONG LINE SET
LENGTHS AS REQUIRED.
VERTICAL SUSPENSION CHAIN
IDEAL WHERE SUPPORTS ARE
INCLINED. MAXIMUM
OM X RECOMMENDED ANGLE OF
I/ INCLINATION IS 15 DEG.
AIR COOLED CONDENSER
INSTALL WITH
MANUFACTURERS
RECOMMENDED CLEARANCES..
INSTALL CONDENSER ON
GRADE WITH MANUFACTURE
PROVIDED FIBER EQUIPMENT
MOUNTING PADS.
PIPE INSULATION LOCATED
OUTDOORS SHALL BE
PAINTED WITH UV
RESISTANT ARMAFLEX
PAINT.
WHERE CHAIN SUPPORTS HAVE
AN ANGLE OF INCLINATION
GREATER THAN 15 DEG. AN
EQUAL AND OPPOSITE
SUPPORT IS RECOMMENDED.
SLOPE DOWNWARDS TOWARDS BURNER BY APPROXIMATELY 1/2"
(Ir
I�
+ 7 )1
�I li
' THESE ANGLES TO BE EQUAL
AND NOT MORE THAN 450
NOTE
REFER TO MANUFACTURERS
INSTALLATION INSTRUCTIONS
AND INSTALL HEATER IN
ACCORDANCE WITH ALL
CLEARANCE AND INSTALLATION
RECOMMENDATIONS.
DRIVE ISLE IR HEATER DETAIL
SCALE: NOT TO SCALE
SYSTEMS WITH REMOTE
SENSORS REQUIRE FIRST
SENSOR TO BE LOCATED NEXT
TO CONTROLLER
CO/NOx _ ARMSTRONG AMD
Sensor CO/NO CONTROLLER
BY MC
(2) SHIELDED STRANDED
TWISTED PAIR 4 C 18 AWG
CABLES IN 4" EMT BY E.C.
SEE PLANS FOR
LOCATIONS TYPICAL.
CONTROLLER
POWER FEED
120 V #12
W/GND BY E.C.
/ EXHAUST FAN
POWER. 120V
#12 W/GND
WIRED BY E.C.
EXHAUST FAN
MOTOR STARTER
WITH HOA BY MC
EXHAUST FAN WITH
DISCONNECT BY M.C.
POWER TO ROOF
MOUNTED EXHAUST FAN
BY EC.
120 V INTERLOCK POWER
BY EC TO MOTORIZED
ACTUATOR ON INTAKE
DAMPER
SEQUENCE OF OPERATION
1. HAND OFF AUTO SWITCH IN "AUTO"
CO/NOx FAN AUTOMATICALLY STARTS ON CO/NOX
Sensor CONTROLLER ALARM AT 25 PPM CO OR 1 % NO.
2. HAND OFF AUTO SWITCH IN "MANUAL"
FAN RUNS CONTINUOUSLY.
3. DAMPER ACTUATOR SHALL BE TWO POSITION FAIL
OPEN INTERLOCKED TO OPEN ANY TIME FAN IS
RUNNING.
COMO CONTROLLER WIRING DETAIL
SCALE: NONE
LINED RA BOX FULL SIZE OF
FURNACE OUTLET WITH
SCREENED 18X18 OPENING IN
TOP -�
REFRIGERATION PIPING.
INSTALL PER
MANUFACTURES
RECOMMENDATIONS
AC "N" DX COIL INSTALL
MANUFACTURES DEFLECTION
PLATE FOR HORZ. APPLICATION) �.
FILTER RACK
INSULATED OUTSIDE AIR DUCT
WITH MOTORIZED AND MANUAL
DAMPER. BALANCE TO
SCHEDULED CFM AND ROUTE TO
WALL CAP
/ ,
THERMOSTAT INSTALLED AT 10'-0"
IN RA PATH NEAR UNIT.
T PVC VENT PIPING. ROUTE TO
SIDE WALL CONCENTRIC VENT
f—TERMINAL PER MANUFACTURES
RECOMMENDATIONS, SEE VENT
TERMINAL DETAIL THIS SHEET.
/ 20" MIN
WORK AREA
CAP AND PROVIDE WATER SHUT
OFF SWITCH
UNI -STRUT RACKING FOR BOTH DRAIN
PAN AND FURNACE, CONNECT TO
MANUALSHUTOFF
GAS VALVE AND UNION
HORIZONTAL HIGH EFFICIENCY FURNACE DETAIL
STRUCTURE WITH 9" RODS.
GALVANIZED SECONDARY DRAIN PAN.
EXTEND MINIMINUM 6" PAST ENTIRE
FURNACE AND DX COIL BOX
CONDENSATE
TRAP WITH TOP a PVC DRAIN. SLOPE AT MIN 4" PER FOOT.
CLEAN OUT. INSULATED AND HEAT TRACED MIN. 10'-0
FROM WALL OUTLET. PROVIDE SELF
REGULATING PVC HEAT TRACE COAX CABLE.
DIRT LEG
SCALE NOT TO SCALE
6" MINIMUM RECTANGULAR SADDLE
WITH 1" FLANGE FOR REGISTER.
CONNECT TO DUCT WITH FULL
PERIMETER BUTYL GASKET AND #10
SCREWS 4" O.C. UNIFORM PATTERN.
ENSURE CONNECTION IS AIR TIGHT
SUPPLY AIR REGISTER WITH
OPPOSED BLADE DAMPER.
MOUNT TO BOOT WITH
MANUFACTURES GASKET ANC
COLOR MATCHED SCREWS.
6" MIN
Z
pa
DUCT MOUNT REGISTER WITH BOOT
SCALE : NONE
djitura
ARCHITECTURE PLANNING DESIGN CREATION
55 MONUMENT CIRCLE
SUITE 1212
INDIANAPOLIS, INDIANA
46204 — 2910
PH 317-348-1000
FAX 317-951-1213
WWW.ARCHITU PACORP. COM
GOODERUM & ASSOCIATES ENGINEERING
MEP Engineer
874 Cheltenham Way p
Avon, IN 46123
P: 317.506.8151
F: 317.745.5761
E: gnaengineering@aol.com
THIS DRAWING AND ALL INFORMATION ON IT IS THE
PROPERTY OF ARCHITURA CORPORATION. IT IS
CONFIDENTIAL AND ITS SUBMISSION OR DISTRIBUTION
TO MEET OFFICIAL REGULATORY REQUIREMENTS OR
FOR OTHER PURPOSES IN CONNECTION WITH THIS
PROJECT 15 NOT TO BE CONSTRUED AS PUBLICATION
IN DEROGATION OF COMMON LAW COPYRIGHT OR
OTHER RESERVED RIGHTS. THIS DRAWING NOR ANY
PART OF IT NOR ANY INFORMATION CONCERNING IT
MAY BE COPIED, EXHIBITED, REPRODUCED OR
FURNISHED TO OTHERS NOR MAY PHOTOGRAPHS BE
MADE OF ANY ARTICLE FABRICATED OR ASSEMBLED
FROM THIS DRAWING WITHOUT WRITTEN CONSENT
OF ARCHITURA CORPORATION.
m COPYRIGHT 2014 ARCHITURA CORPORATION
SIGNATURE
SEAL 09-12-2017
\\�uauuiliiillnnu�,,,,
=q No,
10200395_l
Q' STATE OF
"Ill it 1 11 IIWO
DATE: 09/12/17
COMMISSION: 17100
DRAWING BY:
CHECKED BY:
REVISIONS
MICHIGAN ROAD
SELF STORAGE
MICHIGAN ROAD
CARMEL, IN 46032
SHEET TITLE
HVAC INSTALLATION DETAILS
SHEET NUMBER