HomeMy WebLinkAbout17100001.1645 DEG. RECTANGULAR DUCT BRANCH OCL CONNECTION TAKE OFF. HAMMER LOCKED OR FLANGED AND FULLY SEALED ROUND SHEET METAL DUCT TO DIFFUSER V.D. 0 J Of Q �- 30' MAX ECCENTRIC TRANSITION MAX, 30 DEG. 0 J 45 DEG. HIGH EFFICIENCY TAKE OFF COMPLETELY SEALED 30' MAX OFFSET PROVIDE MINIMUM 2" STRAIGHT SECTION AT EACH END. MAX 30 DEG. NOTE IN GENERAL, ELBOWS TO HAVE FULL TURNING RADIUS (R=A). WHERE "R" IS EQUAL TO OR GREATER THAN "A" MINIMUM RADIUS (R) = 4 INCHES. CONCENTRIC TRANSITION MAX, 45 DEG. DIVERGING AND 60 DEG. CONVERGING EQUIP MANUFACTURER SUPPLIED CONCENTRIC VENT TERMINAL NOTE MAINTAIN ALL CLEARANCES PER IFGC DIRECT VENTING SECTIONS. 10' FROM RUBBER BOOT DECK FLASHING SPECIFICALLY FORCED AIR INTAKES. DESIGN FOR METAL PANEL SYSTEM. IN - SEAL WITH POLYURETHANE BASED SEALER, 12" SIKAFLEX-221 OR EQUAL SILICONE SEALANT IS NOT ACCEPTABLE METAL WALL PANEL 11 STRUCTURAL MEMBER FIELD INSTALL PIPE SUPPORT. BRACE TO STRUCTURE FIELD ROUTE PVC VENTING IN STRICT 4ACCORDANCE WITH EQUIP. MANUF. RECOMMENDATIONS, SLOPE AT MIN .25% METAL WALL CONCENTRIC FLUE PIPING DETAIL NO SCALE NOTE. TXV METERING DEVICE DOUBLE THICKNESS TURNING VANES TO BE USED MANDATORY WHERE NORMAL RADIUS ELBOW IS IMPRACTICAL IS WITHIN & WHERE ELBOW 5 FT OF A PITCH SUCTION LINE BRANCH TAKE -OFF. TOWARD COMPRESSOR. SIZE OIL RETURN TRAPS PER MANUFACTURES PIPING TIONS DUCT CONSTRUCTION DETAILS RECOMMENDA SCALE: NONE SEE SPECIFICATIONS FOR MAXIMUM LENGTH OF FLEX, NO SECURE FLEXIBLE DUCT TO KINKS SUPPORT WITH MINIMUM SUPPLY DIFFUSER ELBOW 2" NYLON STRAP. FITTING WITH DRAWBANDS.� SHEET METAL ELBOW 1-112" DUCT WRAP COVER ENTIRE BACK SIDE OF DIFFUSER TO T BARS. SUPPLY DIFFUSER LAY -IN DIFFUSER DETAIL NO SCALE MATCHING WIDTH CASED EVAPORATOR COIL SEALED TO FURNACE AND SUPPLY . AIR DUCT. REFRIGERATION GRADE TYPE L COPPER LINE SET WITH 1/2" WALL ARMAFLEX SIZE PER MANUFACTURE --�� TRAPPED PRIMARY AND INDEPENDENT SECONDARY 3/4" PVC DRAIN LINE. ROUTE SECONDARY TO DRAIN PAN. PROVIDE OPEN SITE DRAIN CONNECTION TO PROTECT COMBUSTION BLOWER PROVIDE LINED SHEET METAL RETURN AIR FURNACE BOX UNDER ALL FURNACES. NO SIDE FURNACE CONNECTIONS ALLOWED. ROUTE PRIMARY DRAIN TO HUB DRAIN AT WALL. F— MINIMUM SLOPE 14" PER / FOOT. SECURE LINE AND TIE G/ CEILING SARA DUCTS SEAL TIGHT AT CEILING PENETRATIONS. M FRESH AIR DUCT WITH MOTORIZED DAMPER INTERLOCKED TO FURNACE BLOWER PROVIDE MANUAL VD AND BALANCE TO CEILING SCHEDULED CFM PVC VENT AND COMBUSTION AIR PIPING ROUTED TO CONCENTRIC WALL VENT. PITCH TOWARD FURNACE MINIMUM 1/4" PER FOOT. INSTALL PER MANUFACTURERS INSTRUCTIONS. SEE VENT TERMINAL DETAIL THIS SHEET. UPFLOW $. FURNACE AGA GAS VALVE 2 PSIG TO 7"W.0 VENTLESS REGULATOR, DIRT LEG AND UNION CONNECTED TO r— FURNACE TTIC SEAL 16" MIN. I- TIGDHT UCT AT CEILINGOPENETRIATION MANUFACTURERFILTER RACK OFF AT HUB DRAIN, PROVIDE MINIMUM 1-1/2 DEEP SEALED WITH 2" PLEATED MERV 8 FILTER. SECONDARY DRAIN PAN WITH MOISTURE SWITCH. WIRE SWITCH TO SHUT DOWN FURNACE IF PRIMARY DRAIN FAILS 107�,OFFICE AREA FURNACE DETAIL SCALE: NOT TO SCALE PROVIDE HARD SHUT OFF LIQUID LINE SOLENOIDS FOR ALL UNITS SLOPE PROVIDE AND INSTALL REFRIGERANT TUBING WITH 1/2" WALL ARMAFLEX INSULATION. ALL FITTINGS SHALL MADE WITH LONG RADIUS BENDS SLOPE WALL SLEEVE SEALED WATER TIGHT CONDENSER DETAIL SCALE: NOT TO SCALE INSTALL ALL REFRIGERATION ACCESSORIES AS RECOMMENDED BY MANUFACTURER FOR LONG LINE SET LENGTHS AS REQUIRED. VERTICAL SUSPENSION CHAIN IDEAL WHERE SUPPORTS ARE INCLINED. MAXIMUM OM X RECOMMENDED ANGLE OF I/ INCLINATION IS 15 DEG. AIR COOLED CONDENSER INSTALL WITH MANUFACTURERS RECOMMENDED CLEARANCES.. INSTALL CONDENSER ON GRADE WITH MANUFACTURE PROVIDED FIBER EQUIPMENT MOUNTING PADS. PIPE INSULATION LOCATED OUTDOORS SHALL BE PAINTED WITH UV RESISTANT ARMAFLEX PAINT. WHERE CHAIN SUPPORTS HAVE AN ANGLE OF INCLINATION GREATER THAN 15 DEG. AN EQUAL AND OPPOSITE SUPPORT IS RECOMMENDED. SLOPE DOWNWARDS TOWARDS BURNER BY APPROXIMATELY 1/2" (Ir I� + 7 )1 �I li ' THESE ANGLES TO BE EQUAL AND NOT MORE THAN 450 NOTE REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS AND INSTALL HEATER IN ACCORDANCE WITH ALL CLEARANCE AND INSTALLATION RECOMMENDATIONS. DRIVE ISLE IR HEATER DETAIL SCALE: NOT TO SCALE SYSTEMS WITH REMOTE SENSORS REQUIRE FIRST SENSOR TO BE LOCATED NEXT TO CONTROLLER CO/NOx _ ARMSTRONG AMD Sensor CO/NO CONTROLLER BY MC (2) SHIELDED STRANDED TWISTED PAIR 4 C 18 AWG CABLES IN 4" EMT BY E.C. SEE PLANS FOR LOCATIONS TYPICAL. CONTROLLER POWER FEED 120 V #12 W/GND BY E.C. / EXHAUST FAN POWER. 120V #12 W/GND WIRED BY E.C. EXHAUST FAN MOTOR STARTER WITH HOA BY MC EXHAUST FAN WITH DISCONNECT BY M.C. POWER TO ROOF MOUNTED EXHAUST FAN BY EC. 120 V INTERLOCK POWER BY EC TO MOTORIZED ACTUATOR ON INTAKE DAMPER SEQUENCE OF OPERATION 1. HAND OFF AUTO SWITCH IN "AUTO" CO/NOx FAN AUTOMATICALLY STARTS ON CO/NOX Sensor CONTROLLER ALARM AT 25 PPM CO OR 1 % NO. 2. HAND OFF AUTO SWITCH IN "MANUAL" FAN RUNS CONTINUOUSLY. 3. DAMPER ACTUATOR SHALL BE TWO POSITION FAIL OPEN INTERLOCKED TO OPEN ANY TIME FAN IS RUNNING. COMO CONTROLLER WIRING DETAIL SCALE: NONE LINED RA BOX FULL SIZE OF FURNACE OUTLET WITH SCREENED 18X18 OPENING IN TOP -� REFRIGERATION PIPING. INSTALL PER MANUFACTURES RECOMMENDATIONS AC "N" DX COIL INSTALL MANUFACTURES DEFLECTION PLATE FOR HORZ. APPLICATION) �. FILTER RACK INSULATED OUTSIDE AIR DUCT WITH MOTORIZED AND MANUAL DAMPER. BALANCE TO SCHEDULED CFM AND ROUTE TO WALL CAP / , THERMOSTAT INSTALLED AT 10'-0" IN RA PATH NEAR UNIT. T PVC VENT PIPING. ROUTE TO SIDE WALL CONCENTRIC VENT f—TERMINAL PER MANUFACTURES RECOMMENDATIONS, SEE VENT TERMINAL DETAIL THIS SHEET. / 20" MIN WORK AREA CAP AND PROVIDE WATER SHUT OFF SWITCH UNI -STRUT RACKING FOR BOTH DRAIN PAN AND FURNACE, CONNECT TO MANUALSHUTOFF GAS VALVE AND UNION HORIZONTAL HIGH EFFICIENCY FURNACE DETAIL STRUCTURE WITH 9" RODS. GALVANIZED SECONDARY DRAIN PAN. EXTEND MINIMINUM 6" PAST ENTIRE FURNACE AND DX COIL BOX CONDENSATE TRAP WITH TOP a PVC DRAIN. SLOPE AT MIN 4" PER FOOT. CLEAN OUT. INSULATED AND HEAT TRACED MIN. 10'-0 FROM WALL OUTLET. PROVIDE SELF REGULATING PVC HEAT TRACE COAX CABLE. DIRT LEG SCALE NOT TO SCALE 6" MINIMUM RECTANGULAR SADDLE WITH 1" FLANGE FOR REGISTER. CONNECT TO DUCT WITH FULL PERIMETER BUTYL GASKET AND #10 SCREWS 4" O.C. UNIFORM PATTERN. ENSURE CONNECTION IS AIR TIGHT SUPPLY AIR REGISTER WITH OPPOSED BLADE DAMPER. MOUNT TO BOOT WITH MANUFACTURES GASKET ANC COLOR MATCHED SCREWS. 6" MIN Z pa DUCT MOUNT REGISTER WITH BOOT SCALE : NONE djitura ARCHITECTURE PLANNING DESIGN CREATION 55 MONUMENT CIRCLE SUITE 1212 INDIANAPOLIS, INDIANA 46204 — 2910 PH 317-348-1000 FAX 317-951-1213 WWW.ARCHITU PACORP. COM GOODERUM & ASSOCIATES ENGINEERING MEP Engineer 874 Cheltenham Way p Avon, IN 46123 P: 317.506.8151 F: 317.745.5761 E: gnaengineering@aol.com THIS DRAWING AND ALL INFORMATION ON IT IS THE PROPERTY OF ARCHITURA CORPORATION. IT IS CONFIDENTIAL AND ITS SUBMISSION OR DISTRIBUTION TO MEET OFFICIAL REGULATORY REQUIREMENTS OR FOR OTHER PURPOSES IN CONNECTION WITH THIS PROJECT 15 NOT TO BE CONSTRUED AS PUBLICATION IN DEROGATION OF COMMON LAW COPYRIGHT OR OTHER RESERVED RIGHTS. THIS DRAWING NOR ANY PART OF IT NOR ANY INFORMATION CONCERNING IT MAY BE COPIED, EXHIBITED, REPRODUCED OR FURNISHED TO OTHERS NOR MAY PHOTOGRAPHS BE MADE OF ANY ARTICLE FABRICATED OR ASSEMBLED FROM THIS DRAWING WITHOUT WRITTEN CONSENT OF ARCHITURA CORPORATION. m COPYRIGHT 2014 ARCHITURA CORPORATION SIGNATURE SEAL 09-12-2017 \\�uauuiliiillnnu�,,,, =q No, 10200395_l Q' STATE OF "Ill it 1 11 IIWO DATE: 09/12/17 COMMISSION: 17100 DRAWING BY: CHECKED BY: REVISIONS MICHIGAN ROAD SELF STORAGE MICHIGAN ROAD CARMEL, IN 46032 SHEET TITLE HVAC INSTALLATION DETAILS SHEET NUMBER