HomeMy WebLinkAbout17100001.22SYMBOLS
ABOVE FINISH FLOOR
PIPING LINETYPES
AIR COOLED CONDENSING UNIT
CONDENSATE DRAIN
CND
COLD WATER DOMESTIC
CW
COMPRESSED AIR
CA
GREASE/OIL/DIRT DRAIN LINE
GL
GAS NATURAL OR PROPANE
GAS
HEATING WATER RETURN DOMESTIC
HWR
HEATING WATER SUPPLY DOMESTIC
HW
ROOF DRAIN
RD
SANITARY SEWER
SAN
STORM DRAIN
SD
PIPING SYMBOLS
EXHAUST AIR OR EACH
REFERENCE. COORDINATE ALL INTERLOCKS AS
EXHAUST GRILLE OR REGISTER
ANCHOR/HANGER
ENTERING AIR DR`( BULB
BALL VALVE
ENTERING AIR WET BULB
BUTTERFLY VALVE
ELECTRICAL CONTRACTOR
CHECK, SWING VALVE
--(�-
DROP
E
EXPANSION JOINT
ELECTRIC WATER COOLER
FLANGED CONNECTION
- i �-
FLEXIBLE PUMP CONNECTION
EXTERNAL STATIC PRESSURE
GAS METER
GM
GATE VALVE
FURNACE
GLOBE VALVE
H� I
BALANCING VALVE
FIRE DAMPER OR FLOOR DRAIN
"P" TRAP
J
PENDANT STYLE FIRE SUPPRESSION HEAD
O
PIPE GUIDE
FAN POWERED VAV BOX
PITCH DOWN IN DIRECTION OF ARROW
FOOT
PLUG VALVE
I
PRESSURE GAUGE
Q
GAS REGULATOR
FRI
RISER
HOOD
RUN OUT OFF BOTTOM OF MAIN
T
RUN OUT OFF TOP OF MAIN
HOT WATER SUPPLY DOMESTIC
TEE OFF SIDE OF MAIN
INCH
TEST PLUG
INFRA -RED
THERMOMETER
LAVATORY
UNION
LEAVING AIR TEMPERATURE
LS
WATER METER
O
"Y" STRAINER
MFR
MANUFACTURER
MBH
ABBREVIATIONS
AFF
ABOVE FINISH FLOOR
ACCU
AIR COOLED CONDENSING UNIT
AHU
AIR HANDLING UNIT
BDD
BACKDRAFT DAMPER
BOD
BOTTOM OF DUCT
CO
CLEAN OUT
CW
COLD WATER DOMESTIC
CA
COMBUSTION AIR
CFM
CUBIC FEET PER MINUTE
DEG F
DEGREES FARENHEIT
DB
DRY BULB
0
DIAMETER
EA
EXHAUST AIR OR EACH
REFERENCE. COORDINATE ALL INTERLOCKS AS
EXHAUST GRILLE OR REGISTER
EADB
ENTERING AIR DR`( BULB
EAWB
ENTERING AIR WET BULB
EC
ELECTRICAL CONTRACTOR
EF
EXHAUSTFAN
EWH
ELECTRIC WALL HEATER
EWC
ELECTRIC WATER COOLER
ERC
ELECTRIC REHEAT COIL
ESP
EXTERNAL STATIC PRESSURE
ET
EXPANSION TANK
F
FURNACE
FCU
FAN COIL UNIT
FD
FIRE DAMPER OR FLOOR DRAIN
FD/SD
FIRE AND SMOKE [CAMPER
FPM
FEET PER MINUTE
FPVAV
FAN POWERED VAV BOX
FT
FOOT
FSK
FOIL SCRIM VAPOR BARRIER
GC
GENERAL CONTRACTOR
GPM
GALLONS PER MINUTE
H
HOOD
HWR
HOT WATER RETURN DOMESTIC
HWS
HOT WATER SUPPLY DOMESTIC
IN
INCH
IR
INFRA -RED
LAV
LAVATORY
LAT
LEAVING AIR TEMPERATURE
LS
LINEAR SLOT DIFFUSER
MAN
MANUAL
MFR
MANUFACTURER
MBH
1000 BTUH
MC
MECHANICAL CONTRACTOR
MCC
MOTOR CONTROL CENTER
MS
MOP SINK
OA
OUTSIDE AIR
PC
PLUMBING CONTRACTOR
PRV
PRESSURE RELEIF VALVE
PSI
POUNDS PER SQUARE INCH
PD
PRESSURE DROP
PDU
POOL DEHUMIDIFICATION UNIT
PRV
PRESSURE RELEIF VALVE
PSI
POUNDS PER SQUARE INCH
PTAC
PACKAGE TERMINAL AIR CONDITIONER
RA
RETURN AIR
RJ
ROOF JACK. MATCH ROOF COLOR
RPZB
REDUCED PRESSURE ZONED BACKFLOW
RPM
REVOLUTIONS PER MINUTE
RTU
ROOF TOP UNIT
SA
SUPPLY AIR
SAF
SUPPLY AIR FAN
SP
STATIC PRESSURE
SAN
SANITARY SEWER
SD
STORM DRAIN
ST
STORAGE TANK
SK
SINK
TCC
TEMPERATURE CONTROL CONTRACTOR
TMV
THERMOSTATIC MIXING VALVE
TSP
TOTAL STATIC PRESSURE
UR
URINAL
LION
UNLESS OTHERWISE NOTED
VAV
VARIABLE AIR VOLUME BOX
VTR
VENT THROUGH ROOF
WC
WALL CAP
WC
WATER CLOSET
WH
WATER HEATER
WIC
WALK IN COOLER
WIF
WALK IN FREEZER
PLUMBING SPECIFICATIONS
GENERAL
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE
BASE BID IN STRICT ACCORDANCE WITH DESIGN
BASIS EQUIPMENT AND MATERIALS. PROJECT DOES
ENCOURAGE COMPETITIVE PRICING AND ALLOWS
FOR SUBSTITUTIONS OF EQUIPMENT AND
MATERIALS AS ALTERNATE DEDUCTS TO BASIS OF
DESIGN BIDS. LIST ALL SUBSTITUTIONS ALONG WITH
DEDUCTS OFFERED ON BID. ENGINEER RESERVES
THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT
TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS.
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL
SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL
ENERGY CONSUMING OR PRODUCING ITEMS AND
FOR ALL PLUMBING FIXTURES, VALVES, DRAINS.
CLEAN OUTS. PIPING, PIPING ACCESSORIES,
INSULATION AND PIPING HANGERS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON
PRINTS, CONTRACTORS NAME. PROJECT NAME.
CLEARLY INDICATE ALL MODEL NUMBERS AND ALL
ACCESSORIES AND OPTIONS BEING PROVIDED.
SUBMISSIONS SHALL BE IN PDF FORMAT.ENGINEER
RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE
ITEM.
3. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE
SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY
WAY AFFECT THE EXECUTION OF HIS WORK HE
SHALL ALSO EXAMINE THE DRAWINGS AND
SPECIFICATIONS FOR OTHER BRANCHES OF WORK
MAKING REFERENCE TO THEM FOR DETAILS OF
EXISTING BUILDING CONDITIONS, NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO INCLUDE ALL
REQUIRED WORK IN THE BID. CONTRACTOR SHALL
GUARANTEE ALL LABOR AND MATERIALS ENTERING
INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR
FROM DATE OF ACCEPTANCE.
4. THE DRAWINGS IN THIS SECTION ARE
DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE
EXACT QUANTITIES, LOCATIONS OR CODIFIED
REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT
OF SYSTEMS. P.C. SHALL PROVIDE AND PAY FOR ALL
REQUIRED PERMITS.
5. UPON COMPLETION OF THE PLUMBING
INSTALLATION, DEMONSTRATE TO THE ENGINEER
AND/OR THE OWNER'S SATISFACTION THAT THE
SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE
WITH THE DRAWINGS, SPECIFICATIONS AND
APPLICABLE CODES, DEMONSTRATE THE DYNAMIC
OPERATION OF EACH SYSTEM. VERIFY PROPER
OPERATION OF EQUIPMENT, FILTERS ARE CLEAN
AND COMPONENTS OF THE SYSTEM ARE INSTALLED
AND ADJUSTED IN FULL ACCORDANCE WITH
MANUFACTURER RECOMMENDATIONS.
6. PLUMBING WORK SHALL BE COMPLETE IN EVERY
DETAIL AND ALL MISCELLANEOUS ITEMS OF
MATERIAL AND LABOR NECESSARY TO COMPLETE
THE WORK DESCRIBED. SHOWN OR REASONABLY
IMPLIED ON DRAWINGS OR SPECIFICATIONS SHALL
BE INCLUDED IN THE CONTRACT. CONTRACTOR
SHALL MAKE MINOR ADJUSTMENTS TO THE WORK
WHERE REQUIRED. WHEN SUCH ADJUSTMENTS ARE
NECESSARY FOR PROPER OPERATION AND WITHIN
THE INTENT OF THE CONTRACT. CONTRACTOR
SHALL GUARANTEE ALL LABOR AND MATERIALS
ENTERING INTO CONTRACT FOR A PERIOD OF ONE
(1) YEAR FROM DATE OF ACCEPTANCE.
7. ALL WORK SHALL BE IN FULL ACCORDANCE WITH
2012 INDIANA PLUMBING CODE (INTERNATIONAL
PLUMBING CODE 2006). 2010 INDIANA ENERGY CODE
(2007 ASHRAE 90.1), 2014 INDIANA FUEL GAS CODE
(2012 INTERNATIONAL FUEL GAS CODE) AND ALL
PERTINENT STATE, COUNTY, CITY CODES AND
ORDINANCES WITH INDIANA AMENDMENTS.
8. PLUMBING CONTRACTOR SHALL VISIT THE SITE AND
VIEW ALL EXISTING CONDITIONS BEFORE
SUBMITTING A PROPOSAL FOR THE WORK AS
DESCRIBED AND SHOWN. NO EXTRAS WILL BE
ENTERTAINED FOR FAILURE TO MAKE THIS VISIT
9. PLUMBING CONTRACTOR SHALL ACCEPT SOLE AND
COMPLETE RESPONSIBILITY FOR CONDITIONS OF
THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS
AND PROPERTY DURING PERFORMANCE OF THE
WORK.
10. PLUMBING CONTRACTOR SHALL VERIFY AND BE
RESPONSIBLE FOR ALL WATER. GAS, STORM AND
SEWER UTILITY ROUGH -INS AND SHALL CONSULT
WITH THE CIVIL PLANS AND WITH LOCAL UTILITY
COMPANY(S) PROVIDING ALL MATERIALS AND LABOR
AND PAYING ALL COSTS NOT BORNE BY THE LOCAL
UTILITY COMPANY(S) FOR INSTALLATION OF
SERVICES INCLUDING SECURING AND PAYING FOR
ALL REQUIRED PERMITS.
11. PLUMBING CONTRACTOR SHALL ENSURE
EMPLOYEES ARE MEETING AND DOCUMENTING ALL
OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS
REQUIRED BY LAW AND BY CONTRACT. PERSONAL
PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND
UTILIZED AS REQUIRED, MECHANICAL CONTRACTOR
SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE
TO COMPLY WITH OSHA REQUIREMENTS.
12. ALL PLUMBING MATERIALS INSTALLED IN RETURN
AIR PLENUMS SHALL BE INSTALLED OR COVERED
WITH MATERIALS AS REQUIRED TO PROVIDE FLAME
RATING OF NOT MORE THAN 25 AND A SMOKE
DEVELOPED INDEX OF NOT MORE THAN 50. PRIOR
TO ROUGH -IN CONSULT WITH M.C. TO VERIFY ALL
LOCATIONS OF RETURN AIR PLENUMS.
13. FURNISH AND INSTALL ACCESS PANELS FOR ALL
CONCEALED EQUIPMENT, PIPING VALVES,
CLEANOUTS, ETC. ACCESS PANELS SHALL BE OF
SUFFICIENT SIZE TO PROVIDE ADEQUATE WORKING
CLEARANCE AND ACCESS.
14, PLUMBING CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL REQUIRED CUTTING AND PATCHING
INCLUDING SAW CUTTING AND PATCHING OF
EXISTING FLOORS AS REQUIRED TO ACCEPT NEW
FLOORING.
MECHANICAL ROOMS SHALL BE DONE WITH
MECHANICAL SEALS LIKE LINK SEAL OR EQUAL. ALL
EXTERIOR PENETRATIONS OF BUILDING WALLS OR
ROOFS SHALL BE SLEEVED AND SEALED WATER
TIGHT
3. PROVIDE BELLOWS TYPE WATER HAMMER
ARRESTERS, STAINLESS STEEL CASHING AND
BELLOWS, 250 PSI, INSTALL PER PDI STANDARD
WH2O1.
PIPING
1. ALL EXPOSED SUPPLY PIPES AND METAL TRIM IN
CONNECTION WITH THE FIXTURES SHALL BE
CHROME PLATED RED BRASS OR BRONZE, PROVIDE
CHROME PLATED STOP VALVES IN ALL SUPPLIES TO
ALL FIXTURES. CAULK ALL FIXTURES WITH
WATERPROOF SILICONE CAULK, TRAPS SHALL HAVE
CLEANOUT PLUGS. INSTALL ONE PIECE CHROME
ESCUTCHEON PLATE WITH SET SCREW AT WALL
PENETRATIONS.
2. WASTE AND VENT PIPING MAINS SHALL BE PITCHED
AT 1/8" PER FOOT. LATERAL BRANCHES SHALL BE
PITCHED 1/4" PER FOOT TOWARD THE SANITARY
SEWER MAIN. THEY SHALL BE INSTALLED AND
TESTED IN ACCORDANCE WITH THE CURRENT
INDIANA PLUMBING CODE AND TESTED PER
AUTHORITY HAVING JURISDICTION.
3 VERIFY LOCATION, DEPTH AND SIZE OF SANITARY
SEWER CONNECTION POINTS. CONNECT AS
REQUIRED. OUTSIDE SEWER SHALL BE INSTALLED
WITH MINIMUM OF T-0" COVER. COORDINATE
CONNECTIONS WITH SITE CONTRACTOR AND LOCAL
UTILITY
4. ALL OUTSIDE WATER PIPING SHALL BE COVERED
WITH A MINIMUM OF 52".
5. ALL PIPING INTERIOR PENETRATIONS OF WALLS AND
FLOORS SHALL BE SLEEVED, SEALED AND FIRE
RATED WHERE REQUIRED. ALL EXTERIOR
UNDERGROUND PENETRATIONS OF BUILDING WALLS
OR FOUNDATIONS INTO BASEMENTS OR
PLUMBING INSULATION
1. ALL PIPING INSULATION MATERIALS SHALL HAVE A
FLAME SPREAD RATING OF 25 OR LESS (ON THE
FLAME SPREAD TEST SCALE) AND SMOKE
DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST
SCALE) OR AS DEFINED BY NFPA 255 STANDARD
METHOD OF TESTING OF SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS, LOCAL
CODES ANQ LOCAL AUTHORITIES HAVING
JURISDICTION. ALL PVC PIPING LOCATED IN RETURN
AIR PLENUM SPACES OR EXPOSED SHALL BE
INSULATED.
2. INSULATION: INSTALL ALL INSULATION IN STRICT
ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO
SAGGING, FRAYED OR TORN INSULATION WILL BE
EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS
PIPING SHALL BE INSULATED AS FOLLOWS:
HW FLEXIBLE UNICELLULAR PIPE INSULATION,
ASTM C534, TYPE 1. MINIMUM THICKNESS
;HALL BE 1/2" FOR PIPE SIZES 1-1/4" AND
LESS AND SHALL BE 1" FOR 1-1/2" AND
C3REATER.
CHECK TEST AND START UP REQUIREMENTS
1. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION
AND MAINTENANCE MANUALS AND AS BUILT
DRAWINGS. PROVIDE (1) TRAINING SESSION TO
OWNER SELECTED PERSONNEL AS REQUESTED.
2 FILL SYSTEMS WITH FRESH WATER AND INSPECT
ALL CONNECTIONS FOR LEAKAGE. FIRE ALL WATER
HEATERS AND START ALL PUMPS. CORRECT ALL
LEAKS AND VIBRATIONS AS REQUIRED.
hitura
ARCHITECTURE PLANNING DESIGN CREATION
55 MONUMENT CIRCLE
SUITE 1212
INDIANAPOLIS, INDIANA
46204 - 2910
PH 317-348-1000
FAX 317-951-1213
WWW.AR C H ITU RAC O R P. C O M
GOODERUM & ASSOCIATES ENGINEERING
MEP Engineer
874 Cheltenham Way p
Avon, IN 46123
P: 317.506.8151
F. 317.745.5761
E: gnaengineering@aol.com
THIS DRAWING AND ALL INFORMATION ON IT IS THE
PROPERTY OF ARCHITURA CORPORATION. IT IS
CONFIDENTIAL AND ITS SUBMISSION OR DISTRIBUTION
TO MEET OFFICIAL REGULATORY REQUIREMENTS OR
FOR OTHER PURPOSES IN CONNECTION WITH THIS
PROJECT IS NOT TO BE CONSTRUED AS PUBLICATION
IN DEROGATION OF COMMON LAW COPYRIGHT OR
OTHER RESERVED RIGHTS. THIS DRAWING NOR ANY
PART OF IT NOR ANY INFORMATION CONCERNING IT
MAY BE COPIED, EXHIBITED, REPRODUCED OR
FURNISHED TO OTHERS NOR MAY PHOTOGRAPHS BE
MADE OF ANY ARTICLE FABRICATED OR ASSEMBLED
FROM THIS DRAWING WITHOUT WRITTEN CONSENT
OF ARCHITURA CORPORATION.
O COPYRIGHT 2014 ARCHITURA CORPORATION
SIGNATURE
SEAL 09-12-2017
°,°°���y'sTE'�'DF•pG,
= =`10200395; lz
Q STATE OF 7�6
"ON/till 111111m \\
DATE: 09/12/17
COMMISSION: 17100
DRAWING BY:
CHECKED BY:
REVISIONS
MICHIGAN ROAD
SELF STORAGE
MICHIGAN ROAD
CARMEL, IN 46032
SHEET TITLE
PLUMBING SYMBOLS,
ABBREVIATIONS AND
SPECIFICATIONS.
SHEET NUMBER
Pool
6. NO PLUMBING PIPING SHALL PASS DIRECTLY OVER
EQUIPMENT
ELECTRICAL PANELS OR DISTRIBUTION CABINETS.
PRIOR TO ROUGH IN COORDINATE WITH E.C.
1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT
SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO
4. DIELECTRIC UNIONS SHALL BE USED TO CONNECT
LISTED EQUIPMENT SHALL BE AT RISK OF
DISSIMILAR METALS OR METAL PIPING SHALL HAVE
CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE
METAL CONNECTIONS ON EACH END THREADED TO
ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS.
MATCH THE= ADJACENT PIPING. METAL
COMPONENTS SHALL BE SEPARATED BY A NYLON
2. PROVIDE SUBMITTALS TO ELECTRICIAN AS
INSULATOR TO PREVENT CURRENT FLOW BETWEEN
REQUIRED FOR COORDINATION OF ALL REQUIRED
DISSIMILAR METALS. UNIONS SHALL BE SUITABLE
ELECTRICAL POWER WIRING, INCLUDE WIRING
FOR THE SYSTEM OPERATING PRESSURES AND
DIAGRAMS AND CABLING REQUIREMENTS FOR
TEMPERATURE WELD TYPE: ASTM A-234.
REFERENCE. COORDINATE ALL INTERLOCKS AS
NEEDED. PROVIDE SINGLE POINT CONNECTION KITS
5. PIPING SLE EVES; INTERIOR OR EXTERIOR ABOVE
AS NEEDED.
GRADE; GALVANIZED -STEEL -PIPE SLEEVES OR
PVC -PIPE SLEEVES. VERIFY, WITH FIRE AUTHORITIES
3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE
HAVING JURISDICTION, THAT PVC MATERIALS ARE
WITH MANUFACTURERS RECOMMENDATIONS AND
ALLOWED FOR SLEEVES. BELOW GRADE, ALL,
CLEARANCE REQUIREMENTS. PROVIDE ALL
MECHANICAL GALVANIZED -STEEL PIPE SLEEVE
REQUIRED MOUNTING OR HOUSEKEEPING PADS.
SYSTEM LIKE LINK -SEAL. ALL SLEEVES SHALL BE
G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR
FIRE STOPPED OR CAULKED. EXTERIOR SLEEVES
MOUNTED EQUIPMENT. P.C. SHALL PROVIDE ALL
SHALL PROVIDE WATER/AIR TIGHT PENETRATION
HOISTING AND RIGGING NEEDED TO SET ALL
SYSTEM.
PLUMBING EQUIPMENT.
6. PROVIDE HANGERS PER MSS AND IPC STANDARDS
4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED
BASED ON PIPING TYPES AND SIZES
TO PREVENT OBJECTIONABLE NOISE AND/OR
VIBRATION. P.C. SHALL PROVIDE VIBRATION PADS.
SPRING ISOLATORS. ATTENUATORS AND
7 PIPING MATERIALS UNLESS OTHERWISE NOTED ON
ACCESSORIES AS NEEDED.
THE PLANS SHALL BE AS FOLLOWS:
5. PROVIDE ALL BLOCKING, HANGERS, SHELVES.
GAS ABOVE GRADE, 2" AND SMALLER; BLACK
'S
BRACKETS ETC. AS REQUIRED TO INSTALL ALL
STEEL SCHEDULE 40 TYPE E ORPIPE
PLUMBING EQUIPMENT.
GRADE B: ASTM A53 / A53M, Al 05 OR Al 20
WITH THREADED ENDS; FITTINGS SHALL
2. INSTALL WATER HEATERS IN ACCORDANCE WITH
BE MALLEABLE IRON THREADED FITTINGS
NFPA-70. AND THE NATIONAL ELECTRICAL CODE.
ASTM 816.3 CLASS 150.
PROVIDE BRASS DRAIN VALVE. 3/4" RELIEF VALVE
WATER BELOW GRADE: HDPE (HIGH DENSITY
AND COLD WATER DIP TUBE. INSTALL HEATERS PER
POLYETHYLENE) 200 PSIG, SDIR-9 NSF
MANUFACTURES INSTALLATION INSTRUCTIONS.
APPROVED FOR POTABLE DRINKING
PROVIDE SHUT-OFF VALVES FOR SERVICE WORK.
WATER.
3. THERMOSTATS ON WATER HEATER SHALL NOT BE
WATER COPPER TUBING (INSIDE UTILITY ROOM):
USED FOR LIMITING HOT WATER TEMPERATURES.
ASTM B 88. TYPE'L' HARD WATER TUBE
PRAWN TEMPER. WITH CAST -COPPER
P.C. SHALL PROVIDE MIXING VALVES FOR HOT
SOLDER -JOINT FITTINGS: ANSI B16.18. OR
WATER TO ALL FAUCETS ACCESSIBLE TO
WROUGHT -COPPER SOLDER JOINT
OCCUPANTS. MIXING VALVE SYSTEMS SHALL LIMIT
FITTINGS: ANSI B16.22
WATER TEMPERATURE AT FAUCETS TO 110 DEG F.
OR LESS.
WATER PEX WATER PIPING (FRONT OFFICE
FIXTURES
RESTROOMS &bREAK ROOM): SHALL BE
WIRSBO OR UPONOR TUBING ASTM F876
AND F877, BLUE FOR COLD AND RED FOR
1. REFERENCE FIXTURE SCHEDULES ON PLANS AND
HOT AND RE -CIRCULATION FITTINGS
PROVIDE ALL REQUIRED CARRIERS BLOCKING,
SHALL BE UPONOR ProPEX SYSTEM C69300
HANGERS. TAIL PIECES, TRAPS, RISERS,
BRASS FITTINGS ASTM F877, F1960.
ESCUTCHEONS, GRIDS, PUTTY. GASKETS, CAULKING,
MANIFOLDS: ProPEX TYPE L TO ASTM F877
ETC. AS REQUIRED TO INSTALL ALL PLUMBING
WITH BRASS BALL VALVES.
FIXTURES.
2. REVIEW SUBMITTALS FOR ALL OWNER PROVIDED
SEWER POLYVINYL CHLORIDE SEWER PIPE (PVC):
EQUIPMENT AND PROVIDE ANY REQUIRED
ASTM D2665 SOLID DRAIN WASTE AND
ACCESSORIES AS NEEDED FOR A COMPLETE
VENT OR ASTM F 891 CELLULAR CORE
INSTALLATION. P.C. SHALL BE RESPONSIBLE TO
5CHEDULE 40 WITH PVC SOCKET WELDED
RECEIVE AND INSTALL ALL OWNER PROVIDED
FITTINGS DESIGNED TO FIT PIPING
FIXTURES.
DIAMETERS. INSULATED IN RETURN AIR
PLENUMS.
2. FIXTURES DESIGNATED FOR HANDICAP
ACCESSIBILITY SHALL COMPLY WITH ANSI A 117.1,
VENTING POLYVINYL CHLORIDE DRAIN, WASTE AND
LATEST EDITION, INCLUDING ADOPTED INDIANA
VENT PIPE (PVC): ASTM D2665,
AMENDMENTS,
INSULATED IN RETURN AIR PLENUMS.
3. PROVIDE BELLOWS TYPE WATER HAMMER
ARRESTERS, STAINLESS STEEL CASHING AND
BELLOWS, 250 PSI, INSTALL PER PDI STANDARD
WH2O1.
PIPING
1. ALL EXPOSED SUPPLY PIPES AND METAL TRIM IN
CONNECTION WITH THE FIXTURES SHALL BE
CHROME PLATED RED BRASS OR BRONZE, PROVIDE
CHROME PLATED STOP VALVES IN ALL SUPPLIES TO
ALL FIXTURES. CAULK ALL FIXTURES WITH
WATERPROOF SILICONE CAULK, TRAPS SHALL HAVE
CLEANOUT PLUGS. INSTALL ONE PIECE CHROME
ESCUTCHEON PLATE WITH SET SCREW AT WALL
PENETRATIONS.
2. WASTE AND VENT PIPING MAINS SHALL BE PITCHED
AT 1/8" PER FOOT. LATERAL BRANCHES SHALL BE
PITCHED 1/4" PER FOOT TOWARD THE SANITARY
SEWER MAIN. THEY SHALL BE INSTALLED AND
TESTED IN ACCORDANCE WITH THE CURRENT
INDIANA PLUMBING CODE AND TESTED PER
AUTHORITY HAVING JURISDICTION.
3 VERIFY LOCATION, DEPTH AND SIZE OF SANITARY
SEWER CONNECTION POINTS. CONNECT AS
REQUIRED. OUTSIDE SEWER SHALL BE INSTALLED
WITH MINIMUM OF T-0" COVER. COORDINATE
CONNECTIONS WITH SITE CONTRACTOR AND LOCAL
UTILITY
4. ALL OUTSIDE WATER PIPING SHALL BE COVERED
WITH A MINIMUM OF 52".
5. ALL PIPING INTERIOR PENETRATIONS OF WALLS AND
FLOORS SHALL BE SLEEVED, SEALED AND FIRE
RATED WHERE REQUIRED. ALL EXTERIOR
UNDERGROUND PENETRATIONS OF BUILDING WALLS
OR FOUNDATIONS INTO BASEMENTS OR
PLUMBING INSULATION
1. ALL PIPING INSULATION MATERIALS SHALL HAVE A
FLAME SPREAD RATING OF 25 OR LESS (ON THE
FLAME SPREAD TEST SCALE) AND SMOKE
DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST
SCALE) OR AS DEFINED BY NFPA 255 STANDARD
METHOD OF TESTING OF SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS, LOCAL
CODES ANQ LOCAL AUTHORITIES HAVING
JURISDICTION. ALL PVC PIPING LOCATED IN RETURN
AIR PLENUM SPACES OR EXPOSED SHALL BE
INSULATED.
2. INSULATION: INSTALL ALL INSULATION IN STRICT
ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO
SAGGING, FRAYED OR TORN INSULATION WILL BE
EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS
PIPING SHALL BE INSULATED AS FOLLOWS:
HW FLEXIBLE UNICELLULAR PIPE INSULATION,
ASTM C534, TYPE 1. MINIMUM THICKNESS
;HALL BE 1/2" FOR PIPE SIZES 1-1/4" AND
LESS AND SHALL BE 1" FOR 1-1/2" AND
C3REATER.
CHECK TEST AND START UP REQUIREMENTS
1. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION
AND MAINTENANCE MANUALS AND AS BUILT
DRAWINGS. PROVIDE (1) TRAINING SESSION TO
OWNER SELECTED PERSONNEL AS REQUESTED.
2 FILL SYSTEMS WITH FRESH WATER AND INSPECT
ALL CONNECTIONS FOR LEAKAGE. FIRE ALL WATER
HEATERS AND START ALL PUMPS. CORRECT ALL
LEAKS AND VIBRATIONS AS REQUIRED.
hitura
ARCHITECTURE PLANNING DESIGN CREATION
55 MONUMENT CIRCLE
SUITE 1212
INDIANAPOLIS, INDIANA
46204 - 2910
PH 317-348-1000
FAX 317-951-1213
WWW.AR C H ITU RAC O R P. C O M
GOODERUM & ASSOCIATES ENGINEERING
MEP Engineer
874 Cheltenham Way p
Avon, IN 46123
P: 317.506.8151
F. 317.745.5761
E: gnaengineering@aol.com
THIS DRAWING AND ALL INFORMATION ON IT IS THE
PROPERTY OF ARCHITURA CORPORATION. IT IS
CONFIDENTIAL AND ITS SUBMISSION OR DISTRIBUTION
TO MEET OFFICIAL REGULATORY REQUIREMENTS OR
FOR OTHER PURPOSES IN CONNECTION WITH THIS
PROJECT IS NOT TO BE CONSTRUED AS PUBLICATION
IN DEROGATION OF COMMON LAW COPYRIGHT OR
OTHER RESERVED RIGHTS. THIS DRAWING NOR ANY
PART OF IT NOR ANY INFORMATION CONCERNING IT
MAY BE COPIED, EXHIBITED, REPRODUCED OR
FURNISHED TO OTHERS NOR MAY PHOTOGRAPHS BE
MADE OF ANY ARTICLE FABRICATED OR ASSEMBLED
FROM THIS DRAWING WITHOUT WRITTEN CONSENT
OF ARCHITURA CORPORATION.
O COPYRIGHT 2014 ARCHITURA CORPORATION
SIGNATURE
SEAL 09-12-2017
°,°°���y'sTE'�'DF•pG,
= =`10200395; lz
Q STATE OF 7�6
"ON/till 111111m \\
DATE: 09/12/17
COMMISSION: 17100
DRAWING BY:
CHECKED BY:
REVISIONS
MICHIGAN ROAD
SELF STORAGE
MICHIGAN ROAD
CARMEL, IN 46032
SHEET TITLE
PLUMBING SYMBOLS,
ABBREVIATIONS AND
SPECIFICATIONS.
SHEET NUMBER
Pool