319219 11/30/17 CITY OF CARMEL, INDIANA VENDOR: 131135
; ® ONE CIVIC SQUARE HOOSIER FIRE EQUIPMENT INC CHECK AMOUNT: $*****3,145.50*
CARMEL, INDIANA 46032 4009 MONTDALE PARK DRIVE CHECK NUMBER: 319219
4 �rriN�. VALPARAISO IN 46383 CHECK DATE: 11/30/17
DEPARTMENT ACCOUNT PO NUMBER INVOICE NUMBER AMOUNT DESCRIPTION
1120 4351000 98400IN 3,145.50 AUTO REPAIR & MAINTEN
VOUCHER NO. WARRANT NO. Prescribed by State Board of Accounts city Form No.Pot (Rev.1995)
ALLOWED 20 ACCOUNTS PAYABLE VOUCHER
Vendor# 131135
I
HOOSIER FIRE EQUIPMENT INC N SUM OF$ CITY OF CARMEL
4009 MONTDALE PARK DRIVE An invoice or bill to be properly itemized must show:kind of service,where performed,dates service
rendered,by whom,rates per day,number of hours,rate per hour,number of units,price per unit,etc.
VALPARAISO, IN 46383
Payee
$3,145.50
Purchase Order#
ON ACCOUNT OF APPROPRIATION FOR
Carmel Fire Terms
Date Due
PO# ACCT# DATE INVOICE# DESCRIPTION
DEPT# INVOICE# Fund# AMOUNT Board Members DEPT# FUND# (or note attached invoice(s)or bill(s)) AMOUNT
98400-IN 43-510.00 $3,145.50 1 hereby certify that the attached invoice(s),or 11/28/17 98400-IN $3,145.50
1120 101 1120 101
bill(s)is(are)true and correct and that the
materials or services itemized thereon for
which charge is made were ordered and
received except
Tuesday, November 28,2017
David Haboush
Fire Chief
I hereby certify that the attached invoice(s),or bill(s),is(are)true and correct and I have
audited same in accordance with IC 5-11-10-1.6
120—
Cost
20Cost distribution ledger classification if claim paid motor vehicle highway fund. Clerk-Treasurer
Page: 1
Invoice
Hoosier Fire Equipment,Inc. Invoice Number: 0098400-IN
4009 Montdale Park Drive Invoice Date: 11/21/2017
Valparaiso,Indiana 46383
(219)462-1707
Order Number:
Order Date
Salesperson: 0000 House
Customer Number: CARM01
Sold To: Ship To:
Carmel Fire Department Carmel Fire Department
2 Civic Square 2 Civic Square
Carmel,IN 46032-7543 Carmel, IN 46032-7543
Confirm To:
Customer P.O. Ship VIA F.O.B. Terms
OUR DELIVERY DESTINATION Net 10
Item Code Unit Ordered Shipped Back Ordered Price Amount
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 2003 KME PUMPER AS PER ATTACHED;
SN:5340.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 2011 SEAGRAVE PUMPER AS PER
ATTACHED;SN:78G45.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S ALF 75'QUINT AS PER ATTACHED;SN:
0108975.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 2002 KME PUMPER AS PER ATTACHED;
SN:5016.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 2011 SEAGRAVE PUMPER AS PER
ATTACHED;SN:78G46.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 1996 KME PUMPER AS PER ATTACHED;
SN:2930.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 1989 GRUMMAN 102'TOWER AS PER
ATTACHED;SN: 18125.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 2016 PIERCE PUMPER AS PER
ATTACHED;SN:29584-01.
/SERVICE EACH 1.00 1.00 0.00 349.50 349.50
PERFORMED ANNUAL PUMP TEST ON CUSTOMER'S 2016 PIERCE PUMPER AS PER
ATTACHED;SN:29584-02.
r�
I�
Net Invoice: 3,145.50
Less Discount: 0.00
Freight: 0.00
Sales Tax: 0.00
Invoice Total: 3,145.50
❑ HOOSIER FIRE EQUIPMENT, INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
PART,NQ"ANR/ORDESCRIPTION, � PRICE; 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/16/2017 DATE: 11/16/2017
ADDRESS: 2 Civic Square PROMISED: CUSTOMER 058675
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
KME Pumper 2003 5340 [Engine 34J 93,894.0 8955
LABOR REPAIR ORDER INSTRUCTIONS LABOR
HOURS
CHARGE
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK —4
PARTS TOTAL n=* $
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
X TOTAL LABOR: $ 344.50
TOTAL PARTS: $ —
MILES TRAVEL RATE PRICE ���a SUBLE7��1�1QRK $
NOT RESPONSIBLE FOR �."
LOSS OR DAMAGE TO
CARS OR ARTICLES $ 5.0000.���
LEFT IN CARS IN CASE TAX:
OF FIRE,THEFT OR ANY
OTHER CAUSE BEYOND
SUBLET WORK TOTAL ,$ - "' OUR CONTROL. TOTAL'TRAVEL EXPENSES: $ .,` ', 5.00 TOTAL
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/16/2017
Address: 2 Civic Square Unit No#: Engine 340
City&St: Carmel, IN 46032 Engine: Gas: M Diesel: X❑
Place of Test: Carmel Maintenance Facility Temperature: 32
Serial# 5340 Apparatus Year&Make: 2003 KME Pumper
Miles: 93,894.0 Engine Hrs: 9,825.4
Pump Model: QMAX150-23L Serial No: 84575 Pump Hours: 960.2
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 12 Sec.
Vacuum Test: 22.5 In.with 8 Inches drop in 5 minutes Test Auxiliary Cooler: yes
Auto Pressure Control Type: governor Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1504 GPM at 150 PSI at 1381 RPM
1051 GPM at 200 PSI at 1480 RPM
750 GPM at 250 PSI at 1665 RPM
Recommended Governed Engine Speed: 2400 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2" Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
14:20 1380 150 flowmeter 1510
14:25 1400 150 flowmeter 1510
14:30 1388 150 flowmeter 1510
14:35 1379 150 flowmeter 1510
Overload Test:
14:40 1 1 1449 165 flowmeter 1560
Oil Pressure: 40 PSI Water Temp: 190 F. Vacuum: 10 In. Volts 13.5
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
14:45 1509 200 flowmeter 1050
14:50 1504 200 flowmeter 1050
14:55 1506 200 flowmeter 1050
Oil Pressure: 38 PSI Water Temp: 185 F. Vacuum: 5.5 In. Volts 13.4
50% Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
15:00 1667 250 flowmeter 750
15:05 1665 250 flowmeter 750
15:10 1669 250 flowmeter 750
Oil Pressure: 39 PSI Water Temp: 183 F. Vacuum: 3 In. Volts 13.1
Barometric Pressure 30.23 Test Water Temperature 68
CERTIFIED Bl Troy Harmon TESTING ENGINEER
❑ HOOSIER FIRE EQUIPMENT, INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
QTY. PART NO.AND/OR DESCRIPTION PRICE 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/15/2017 DATE: 11/15/2017
ADDRESS: 2 CIVIC Square PROMISED: CUSTOMER ST2029
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT I MILEAGE AR#
Seagrave Pumper 2011 78G45 Engine 14111 56,175.0 8955
LABOR OURS REPAIR ORDER INSTRUCTIONS LABOR
CHARGE
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK —4
PARTS TOTAL 10-111, $ -
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
X TOTAL LABOR: $ 344.50
TOTAL PARTS: $ -
MILES TRAVEL RATE PRICE SUBLET WORK: $;NOT RESPONSIBLE FOR
LOSS OR DAMAGE TO $ 5.00 _ TRAVEL EXP. $ 5.00
CARS OR ARTICLES
LEFT IN CARS IN CASE
T '
OF FIRE,THEFT OR ANY
OTHER CAUSE BEYOND
SUBLET WORK TOTAL $ - OURCONTROL. TOTAL TRAVEL EXPENSES: $ 5.00 TOTAL $ 349.50
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
® 4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/15/2017
Address: 2 Civic Square Unit No#: Engine 341
City&St: Carmel, IN 46032 Engine: Gas: ❑ Diesel: X❑
Place of Test: Carmel Maintenance Facility Temperature: 44
Serial# 78G45 Apparatus Year&Make: 2011 Seagrave Pumper
Miles: 56,175.0 Engine Hrs: 5,426.6
Pump Model: QMAX150-23L Serial No: A6794 Pump Hours: unknown
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 8 Sec.
Vacuum Test: 22.5 In.with 2 Inches drop in 5 minutes Test Auxiliary Cooler: yes
Auto Pressure Control Type: valve Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1510 GPM at 150 PSI at 1354 RPM
1051 GPM at 200 PSI at 1496 RPM
750 GPM at 250 PSI at 1636 RPM
Recommended Governed Engine Speed: 2200 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2"Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
13:25 1358 150 flowmeter 1510
13:30 1360 150 flowmeter 1510
13:35 1358 150 flowmeter 1510
13:40 1360 150 flowmeter 1510
Overload Test:
13:45 1 1 1423 165 flowmeter 1580
Oil Pressure: 50 PSI Water Temp: 180 1 F. Vacuum: 8.5 In. Volts 14.5
70% Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 1,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
13:50 1 1480 200 flowmeter 1060
13:55 1478 200 flowmeter 1060
14:00 1 1482 200 flowmeter 1060
Oil Pressure: 51 PSI Water Temp: 181 F. Vacuum: 4.5 In. Volts 14.3
50%Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 1,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
14:05 1636 250 flowmeter 750
14:10 1637 250 flowmeter 750
14:15 1636 250 flowmeter 750
Oil Pressure: 52 PSI Water Temp: 183 F. Vacuum: 3 In. Volts 14.3
Barometric Pressure 29.88 Test Water Temperature 68
CERTIFIED 13 r Troy Harmon TESTING ENGINEER
❑ HOOSIER FIRE EQUIPMENT, INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
QT„Y: PART NO.AND/OR DESCRIPTION PRICE 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/15/2017 DATE: 1115/2017
ADDRESS: 2 Civic Square PROMISED: CUSTOMER K92637
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
ALF 75'Quint 2003 0108975 Engine 34 101,463.0 8955
LABOR REPAIR ORDER INSTRUCTIONS LABOR
e �H06RS
CHARGE
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK ®►
PARTS 1TOTAL $
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
X TOTAL i:ABOR: $ 344.50a
TOTAL PARTS: $.
MILES TRAVEL RATE PRICE SUBLET WORK: $ -
NOT RESPONSIBLE FOR - -
LOSS OR DAMAGE TO
CARS OR ARTICLES $ 5.00 .TRAVEL EXP. $ 5.00
LEFT IN CARS IN CASE AX
OF FIRE,THEFT OR ANY
OTHER CAUSE BEYOND
SUBLET WORK`TQTAL „ ? ouRcoNTROL. r TOTAL TRAVEL EXPENSES $ 5 OOe TOTAL ®� $,° '349 50
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/15/2017
Address: 2 Civic Square Unit No#: Engine 342
City&St: Carmel, IN 46032 Engine: Gas: [] Diesel: X❑
Place of Test: Carmel Maintenance Facility Temperature: 45
Serial# 0108975 Apparatus Year&Make: 2003 ALF 75'Quint
Miles: 101,463.0 Engine Hrs: 8,270.1
Pump Model: QMAX150-23S Serial No: 82481 Pump Hours: unknown
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: 2.3
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 14 Sec.
Vacuum Test: 22.5 In.with 2 Inches drop in 5 minutes Test Auxiliary Cooler: yes
Auto Pressure Control Type: governor Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1504 GPM at 150 PSI at 1352 RPM
1051 GPM at 200 PSI at 1482 RPM
750 GPM at 250 PSI at 1629 RPM
Recommended Governed Engine Speed: 2225 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2"Lines: 3 Pump Control Position: 1,2,4
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
14:30 1358 150 flowmeter 1510
14:35 1370 150 flowmeter 1510
14:40 1365 150 flowmeter 1510
14:45 1368 150 flowmeter 1510
Overload Test:
14:50 1 1 1432 165 flowmeter 1570
Oil Pressure: 36 PSI Water Temp: 185 F. Vacuum: 9.5 In. Volts 13.9
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 2,4
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
14:55 1 1489 200 flowmeter 1060
15:00 1 1486 200 flowmeter 1060
15:05 1 1487 200 1 flowmeter 1060
Oil Pressure: 36 PSI Water Temp: 189 F. Vacuum: 5.5 In. Volts, 13.9
50% Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 2,4
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
15:10 1 1638 250 flowmeter 750
15:15 1642 250 flowmeter 750
15:20 1637 250 flowmeter 1 750
Oil Pressure: 37 PSI Water Temp: 183 F. Vacuum: 4 In. Volts 13.9
Barometric Pressure 29.86 Test Water Temperature 72
CERTIFIED 13� Troy Harmon TESTING ENGINEER
F-1HOOSIERFIRE EQUIPMENT INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
;;GlT,Y ,,PART,,NO� AND/OR;DE�SCR�PTIQN o p„a PRICE 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/15/2017 DATE: 11/15/2017
ADDRESS: 2 CIVIC Square PROMISED: CUSTOMER N058489
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
KME Pumper 2002 5016 Engine 3431 98,093.0 8955
LABOR REPAIR ORDER INSTRUCTIONS BOR
HOURS
CHARGE,
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK -4
PARTS TOTAL $
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
X TOTAL LABOR: $ 344.50
TOTAL PARTS:
MILES TRAVEL RATE PRICE °�"�� �`u SUBLET ORK ���� °�
NOT RESPONSIBLE FOR 't � $������ft��y a��a���
LOSS OR DAMAGE TO Q; a ��„ • @��h �'\"
CARS OR ARTICLES $ 5.00
LEFT IN CARS IN CASE
OF FIRE,THEFT OR ANY TAX:
OTHER CAUSE BEYOND
SUBLET'WORKTOTAL $ = OURCONTROL. TOTAL TRAVEL EXPENSES:' $,' 5.00 TOTAL --I $ 349.50
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/15/2017
Address: 2 Civic Square Unit No#: Engine 343
City&St: Carmel, IN 46032 Engine: Gas: 1-1 Diesel: MR
Place of Test: Carmel Maintenance Facility Temperature: 41
Serial# 5016 Apparatus Year&Make: 2002 KME Pumper
Miles: 98,093.0 Engine Hrs: 10,053.0
Pump Model: QMAX150-23L Serial No: 82415 Pump Hours: unknown
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 14 Sec.
Vacuum Test: 22.5 In.with 6.5 Inches drop in 5 minutes Test Auxiliary Cooler: pass
Auto Pressure Control Type: governor Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1504 GPM at 150 PSI at 1325 RPM
1051 GPM at 200 PSI at 1498 RPM
750 GPM at 250 PSI at 1662 RPM
Recommended Governed Engine Speed: 2400 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2" Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
11:10 1380 150 flowmeter 1510
11:15 1376 150 flowmeter 1510
11:20 1380 150 flowmeter 1510
11:25 1380 150 flowmeter 1510
Overload Test:
11:30 1 1 1450 165 flowmeter 1590
Oil Pressure: 35 PSI Water Temp: 180 F. Vacuum: 12 In. Volts 13.8
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
11:35 1500 200 1 flowmeter 1050
11:40 1505 200 flowmeter 1050
11:45 1501 200 flowmeter 1050
Oil Pressure: 35 PSI Water Temp: 185 F. Vacuum: 7 In. Volts 13.7
50% Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
11:50 1655 250 flowmeter 750
11:55 165-4 -1 250 1 flowmeter 750
12:00 1656 1 250 1 flowmeter 750
Oil Pressure: 35 PSI Water Temp: 185 F. Vacuum: 5 In. Volts 13.7
Barometric Pressure 29.94 Test Water Temperature 70
CERTIFIED 13 r Troy Harmon TESTING ENGINEER
❑ HOOSIER FIRE EQUIPMENT, INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
<PART ANO ,AND LORaDES,CRI,PTION 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/16/2017 DATE: 11/16/2017
ADDRESS: 2 CIVIC Square PROMISED: CUSTOMER ST2030
0RnFR it
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
Seagrave Pumper 2011 78G46 Engine 3441 49,770.0 8955
LABOR REPAIR ORDER INSTRUCTIONS LABOR
HOURS CHARGE
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK am#
PARTS TOTAL $
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
X TOTAL LABOR: $ 344.50
TOTAL PARTS: $_,`b -,
MILES TRAVEL RATE PRICE a' �` SUBETIAIORK $ '� �
NOT RESPONSIBLE FOR
LOSS OR DAMAGE TO a ' " @
CARS OR ARTICLES $ 500 ' ,TIVEL EXP $ ��`,' S;OO
LEFT IN CARS IN CASE
OF FIRE,THEFT OR ANY TAX:
OTHER CAUSE BEYOND -
SUBLET WORK TOTAL $ - ,. OUR CONTROL. TOTAL TRAVEL EXPENSES; „$, 5.00• TOTAL —111, $ 349.50
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/16/2017
Address: 2 Civic Square Unit No#: Engine 344
City&St: Carmel, IN 46032 Engine: Gas: Diesel: X❑
Place of Test: Carmel Maintenance Facility Temperature: 32
Serial# 78G46 Apparatus Year&Make: 2011 Seagrave Pumper
Miles: 49,770.0 Engine Hrs: 4,029.1
Pump Model: QMAX150 Serial No: A6793 Pump Hours: unknown
Rated Capacity: . 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 2/6" In. Length: 10/25' Ft. Lift: 2 Ft. Primed: 13 Sec.
Vacuum Test: 22.5 In.with 7 Inches drop in 5 minutes Test Auxiliary Cooler: yes
Auto Pressure Control Type: valve Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1510 GPM at 150 PSI at 1376 RPM
1051 GPM at 200 PSI at 1503 RPM
750 GPM at 250 PSI at 1644 RPM
Recommended Governed Engine Speed: 2200 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2"Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
8:40 1358 150 flowmeter 1510
8:45 1359 150 flowmeter 1510
8:50 1360 150 flowmeter 1510
8:55 1360 150 flowmeter 1510
Overload Test:
9:00 1 1 1428 165 flowmeter 1600
Oil Pressure: 52 PSI Water Temp: 185 F. Vacuum: 8.5 In. Volts 14.2
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
9:05 1491 200 flowmeter 1060
9:10 1494 200 flowmeter 1060
9:15 1490 200 flowmeter 1060
Oil Pressure: 53 PSI Water Temp: 186 F. Vacuum: 5 In. Volts 13.9
50%Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
9:20 1642 250 flowmeter 750
9:25 1 1639 250 flowmeter 750
9:30 1 1643 250 flowmeter 750
Oil Pressure: 55 PSI Water Temp: 188 F. Vacuum: 3 In. Volts 14
Barometric Pressure 30.16 Test Water Temperature 58
CERTIFIED 13� Troy Harmon TESTING ENGINEER
�J HOOSIER FIRE EQUIPMENT, INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
eutT°Y � ' � P+k? NtO;"f1Npa/C7R`DSCRIRt �QN v� k;PRICEa'
\, 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/16/2017 DATE: 11/162017
ADDRESS: 2 Civic Square PROMISED: CUSTOMER 058491
ORDFR it
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
KME Pumper 1996 2930 Engine 349 106,160.0 8955
E
\�? ::':.Q J..m,.,.. \ 3 ?:a \a�\\�.: ��a \.'^",.a. �.a �,a. � ^ ..:mm ..: .�\ti:,a \. �i?x s,...:.re�\ �+`��. c..� \„a� \ \\\� ,..'.:�Ap�7i=•�W:a,.r.
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK
a\\\, \qo \iaRm T,�.^a TvvOvYret\ai0u�.W .2�vJ \�
\
„Ae
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
\\�xx \\ \\\\a \\a ata\\\ o ,\344 50
X TOTAL aoR "$
W1w4 Xh &&w n\\� " \SU„ 41 ?4RK� °`a wart u
MILES TRAVEL RATE PRICE
NOT RESPONSIBLE FOR +A a vA A v4 as v VV v aWav a V va vW a v A sx a
v$
LOSS OR DAMAGE TO Q; 500a \ a
n:
LEFT IN CARS IN CASE a aqga' fva ,�\” ?x`V A��\ pv`y` W �"x,7,,',,7,_\7,y.a g\ '
OF FIRE,THEFT OR ANYa"aa:;a„u.
OTHER CAUSE .....�,. 1w,.,.a
OUR CONTROL \a . \ q\uW�...x,a.,\..�;.\\\,..,.:�,,.\,,\ax a\.\\a\as\..\"\\\\\..h..�....:..`.F#.,5,,\.�a..,,Q na a,„,,,•.... TOTAL
\.,\
:
a...
a ^
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/16/2017
Address: 2 Civic Square Unit No#: Engine 349
City&St: Carmel, IN 46032 Engine: Gas: 1-1 Diesel: XD
Place of Test: Carmel Maintenance Facility Temperature: 32
Serial# 2930 Apparatus Year&Make: 1996 KME Pumper
Miles: 106,160.0 Engine Hrs: 11,224.4
Pump Model: QSMG150-23L Serial No: 69971 Pump Hours: 1,247.2
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 2/6" In. Length: 10/25' Ft. Lift: 2 Ft. Primed: 11 Sec.
Vacuum Test: 22.5 In.with 5 Inches drop in 5 minutes Test Auxiliary Cooler: yes
Auto Pressure Control Type: valve Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1504 GPM at 150 PSI at 1417 RPM
1051 GPM at 200 PSI at 1533 RPM
750 GPM at 250 PSI at 1678 RPM
Recommended Governed Engine Speed: 2400 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2" Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
10:05 1420 150 flowmeter 1510
10:10 1420 150 flowmeter 1510
10:15 1420 150 flowmeter 1510
10:20 1420 150 flowmeter 1510
Overload Test:
10:25 1 1 1510 165 flowmeter 1570
Oil Pressure: 40 PSI Water Temp: 170 F. Vacuum: 10 In. Volts 13
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
10:30 1530 200 flowmeter 1060
10:35 1530 200 flowmeter 1060
10:40 1530 200 flowmeter 1060
Oil Pressure: 28 PSI Water Temp: 190 F. Vacuum: 7.5 In. Volts 13.5
50%Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
10:45 1670 250 flowmeter 750
10:50 1 1670 250 flowmeter 750
10:55 1 1670 250 flowmeter 750
Oil Pressure: 28 PSI Water Temp: 190 F. Vacuum: 4.5 In. Volts 13.5
Barometric Pressure 30.19 Test Water Temperature 68
CERTIFIED Bl Troy Harmon TESTING ENGINEER
HOOSIER FIRE EQUIPMENT, INC. HOOSIER FIRE EQUIPMENT, INC.
TY q��\, SPAR NONND(pRtpISCRIP ION44
r? ICE 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/16/2017 DATE: 11/16/2017
ADDRESS: 2 Civic Square PROMISED: CUSTOMER 088012
npnF=p it
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
Grumman 102'Tower 1989 18125 Ladder 340 54,997.0 8955
..... \ `.'�1\\. \ k \.R(2` \ :.:C\ \ 1. !'�..R• ((+� l'� .\\\ \\ \ �5.. r\\\\... \�x baa g\\\ :,.,...
\ Y �R5
a
Perform annual pump testing $ 325.00
Set up fee $ 19.50
yy ADDITIONAL PARTS SEELISTLIST ON BACK
0-0
'1—Ar1T,�`\TO! 4:: \\ \ k\ � \��\\�\�1>� � �.
u\\ :".`„ia� \ a\�\�:� �\9a;\\ Z \2\Cog,\� agg
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
A,
$ vA v \A 1111,11 avw vy �” tc v�\\�� +
X
\\\�OAi LA�o $\ 344 5a,,
a�, x„Ae vao,av ,aa. a \a a0avu ,a\k
jv
MILES TRAVEL RATE PRICE � �v�� B at/1�G1R{{
NOT RESPONSIBLE FOR �>" a\su tr'( .11A, 9.. .
LOSS OR DAMAGE TO5.00
A\�V\ S a�G\Mada\� m VAVvAQFA ovA6ApAVvpvvv "�fx c
CARS OR ARTICLESLEFT IN $ 5 00 � .�
OF FIARS IN CASE
RECTHEFT OR ANY
\`.
\ a \\... .\. \\;t
�. \ \
\ "\ ,�a.. �\\ a m... :. \ \, c� ..... OTHER CAUSE BEY ND ..� \. \.. ,
a., a r..< \, x.\ \;. „ a, ,..a\. x.. v..\.. r \. � ..., \ \ .� \ ,\�....„ ,. .�. a\\ , x,. ,.
,a \ .. \ \.: ., a \ ::�
ar ,\ \ .r,o �\ \ :e,.w, ak9 \\..,\\\ \\
as�: h \ �..'\o w \a:>u, a.. .. a. � a \\ \.....< \�\:,,.. .. ,. .. ...„. a",�. ,. \\a\ �
\\ ,......4 ,. „a ;,a .::,OUR CONTROL. 0. ,.. .y\. \, a\ x, u ;. TOTAL �
� .a \, \,.SUBLET\ ":O K TOTAL \ OT,.LTR VEL EXP `NS�S., as .00,
\a � \1IV R \ r �\��\Xa /� F \\ � �
\W w��.«:sx:a, ,-R\sv \v. .�a� �,.x'�\v�a..� S.y\\,.m vev. ;P'_x.a Aa,�.va,.; „a, .A"aaw"�\. ..vvA ,u,e"aa0ti a,��;�,�a sono,;a\
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/16/2017
Address: 2 Civic Square Unit No#: Ladder 340
City&St: Carmel, IN 46032 Engine: Gas: Diesel: El
Place of Test: Carmel Maintenance Facility Temperature: 34
Serial# 18125 Apparatus Year&Make: 1989 Grumman 102'Tower
Miles: 54,997.0 Engine Hrs: 6,666.5
Pump Model: CMU YBX Serial No: 13977W Pump Hours: unknown
Rated Capacity: 1500 GPM Stages: 2 Pump Ratio: 2.48
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 8 Sec.
Vacuum Test: 22.5 In.with 1 Inches drop in 5 minutes Test Auxiliary Cooler: yes
Auto Pressure Control Type: valve Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1500 GPM at 150 PSI at 1468 RPM VOLUME MODE
1050 GPM at 200 PSI at 1563 RPM VOLUME MODE
750 GPM at 250 PSI at 1360 RPM PRESSURE MODE
Recommended Governed Engine Speed: unknown RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2" Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
13:15 1430 150 flowmeter 1500 VOLUME MODE
13:20 1430 150 flowmeter 1500 VOLUME MODE
13:25 1430 150 flowmeter 1500 VOLUME MODE
13:30 1430 150 flowmeter 1500 VOLUME MODE
Overload Test:
13:35 1 1 1510 165 flowmeter 1590 VOLUME MODE
Oil Pressure: 45 PSI Water Temp: 190 F. Vacuum: 12 In. Volts 12.8
70% Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
13:40 1 1560 200 flowmeter 1060 VOLUME MODE
13:45 1560 200 flowmeter 1050_LL VOLUME MODE
13:50 1560 200 flowmeter 1060 1 VOLUME MODE
Oil Pressure: 40 PSI Water Temp: 210 F. Vacuum: 6.5 In. Volts 13.2
50% Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No. 2-1/2" Lines: 2 Pump Control Position: 2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
13:55 1420 250 1 flowmeter 750 PRESSURE MODE
14:00 1420 250 flowmeter 750 PRESSURE MODE
14:05 1420 250 flowmeter 750 PRESSURE MODE
Oil Pressure: 35 PSI Water Temp: 210 F. Vacuum: 4 In. Volts 13.2
Barometric Pressure 30.22 Test Water Temperature 72
CERTIFIED B`r Troy Harmon TESTING ENGINEER
❑ HOOSIER FIRE EQUIPMENT, INC. Fj HOOSIER FIRE EQUIPMENT, INC.
v2YvPARTNQ'/1�1D(QI°ESCR2�TOIp , �PRIG,E 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/15/2017 DATE: 11/15/2017
ADDRESS: 2 Civic Square PROMISED: CUSTOMER 01674
ORDER 9
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR p
Pierce Pumper 2016 29584-01 Engine 346 12,587.0 8955
\\
\a
W',
\ ��PQ�! v:~•.0.
ti
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
vA�:vAA$,aa `:vv a'a v`vaT t sv vilAAApVAaleVvAas 2v`\vvC �' p ac
�'K \ °"^xax ���`
«vAsviaa2v ",t
NOT RESPONSIBLE FOR
MILES TRAVEL RATE PRICE
LOSS OR DAMAGE TO 5.00 "ASSRA^` \��'' y�"' A�•SFI Q@00 A �Aa"pL*\F p \
CARS OR ARTICLES
LEFT IN CARS IN CASE \\\\\`" ?\`p\�\\\,
OF FIRE,THEFT OR ANY
,.".„.u.�a.,..\u.`'\.."..�e.;.w.„S\t\\.lt"y?„,a.e,�.l..\,.s..r....,.�.\v,.,_p...e\Ae�.o�es,�.x°h,}\\.p.,:.,\....:,,.a,tiA u�C\�t xV,�.a�....:.fi..a..\\xr\\1C*aaV`\ev\..„„�\�.,..:+.,:.,.,J..,,,,\\„S.U\teka\1t�tB,,..<...,.,,.,\�T�`Vt\.,0\Wc1ha,.r.e...,A,O\\�,,...:(t�,�.,�,.v,.V,.xi\�.O,,psTu'\.\..i.S,„s a\,c�„.\nv,,.,x.x.,�.\...JVwvuvu,A\\V\A\,\\.a...a..\,..,v�,a\.\\.a.,;\\\..s,.,,..,•..b..:,,..\�,\\OTHER CAUSE BEYOND
Sp\..:,„.$..�.,\\4 EOURCONTROL.A \a
.\\,„ta.ti.pvv4inpa\„:...ti..:.>..5:. 0.,m.\v0\\,0 :,a1...
.dt
;
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
& VALPARAISO, IN 46383 GREENFIELD, IN 46140
800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/15/2017
Address: 2 Civic Square Unit No#: Engine 346
City&St: Carmel, IN 46032 Engine: Gas: Diesel: X7I
Place of Test: Carmel Maintenance Facility Temperature: 39
Serial# 29584-01 Apparatus Year&Make: 2016 Pierce Pumper
Miles: 12,587.0 Engine Hrs: 993.0
Pump Model: QMAX150-23L Serial No: H10562 Pump Hours: 78.0
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 8 Sec.
Vacuum Test: 22.5 In.with 0" Inches drop in 5 minutes Test Auxiliary Cooler: pass
Auto Pressure Control Type: valve Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1509 GPM at 150 PSI at 1418 RPM
1053 GPM at 200 PSI at 1540 RPM
750 GPM at 250 PSI at 1680 RPM
Recommended Governed Engine Speed: 2400 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2"Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
9:35 1390 150 flowmeter 1510
9:40 1400 150 flowmeter 1510
9:45 1400 150 flowmeter 1510
9:50 1406 150 flowmeter 1510
Overload Test:
9:55 1 1 1450 165 flowmeter 1570
Oil Pressure: 50 PSI Water Temp: 180 F. Vacuum: 9 In. Volts 13
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 1,2
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
10:00 1510 200 flowmeter 1060
10:05 1500 200 flowmeter 1060
10:10 1510 200 flowmeter 1060
Oil Pressure: 50 PSI Water Temp: 180 F. Vacuum: 6.5 In. Volts 12.8
50%Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 1,2
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
10:15 1660 250 flowmeter 750
10:20 1680 250 flowmeter 750
10:25 1660 250 flowmeter 750
Oil Pressure: 52 PSI Water Temp: 187 F. Vacuum: 4.5 In. Volts 12.7
Barometric Pressure 29.98 Test Water Temperature 60
CERTIFIED Bti Troy Harmon TESTING ENGINEER
❑ HOOSIER FIRE EQUIPMENT, INC. ❑ HOOSIER FIRE EQUIPMENT, INC.
QTY: PART NO. AND/OR DESCRIPTION PRICE 4009 Montdale Park Drive 3863 North Commercial Parkway
Valparaiso, IN 46383 Greenfield, IN 46140
Phone: 219-462-1707 Phone: 317-891-8375
Toll Free: 800-552-2691 Toll Free: 888-436-6075
REPAIR ORDER
NAME: Carmel Fire Department RECEIVED: 11/15/2017 DATE: 11/15/2017
ADDRESS: 2 Civic Square PROMISED: CUSTOMER 01675
nRnFR it
CITY: Carmel, IN 46032 TERMS: MECHANIC: MOB-MS
PHONE:
MAKE: MODEL: YR. SERIAL NO. UNIT MILEAGE AR#
Pierce Pumper 2016 29584-02 Engine 345 14,678.0 8955
LABOR LABOR"'
REPAIR ORDER INSTRUCTIONS
10URS `° a CHARGE
Perform annual pump testing $ 325.00
Set up fee $ 19.50
ADDITIONAL PARTS SEE LIST ON BACK —4
PARTS T..OTAL $: -
SUBLET WORK PRICE
I hereby authorize the above repair work to be done w/the necessary material,and hereby grant you and/or your employees
permission to operate the car or truck herein described on streets,highways or elsewhere for the purpose of testing
and/or Inspection. An express mechanic's lien is hereby acknowledged on above car or truck to secure the amt.of repairs thereto.
X TOTAL LABOR: $ 344.50
TOTAL PARTS: $ -
MILES TRAVEL RATE PRICE SUBLET WORK`. $ - -
NOT RESPONSIBLE FOR
LOSS OR DAMAGE TO $ 5.00 "TRAVEL EXP. $ „. '5.00
CARS OR ARTICLES
LEFT IN CARS IN CASE TAX:
OF FIRE,THEFT OR ANY
„ „
SUBLET WORK TOTAL ouRcorlTao�BEYON TOTAL TRAVEL EXPENSES �i 5 OO'a TOTAL 349.50°`
HOOSIER FIRE EQUIPMENT, INC.
MAIN OFFICE MID-STATE OFFICE
4009 MONTDALE PARK DR. 3863 N. COMMERCIAL PKWY
VALPARAISO, IN 46383 GREENFIELD, IN 46140
�� 800-552-2691 888-436-6075
PUMP TEST REPORT
Customer: Carmel Fire Department Date: 11/15/2017
Address: 2 Civic Square Unit No#: Engine 345
City&St: Carmel, IN 46032 Engine: Gas: M Diesel: 0
Place of Test: Carmel Maintenance Facility Temperature: 43
Serial# 29584-02 Apparatus Year&Make: 2016 Pierce Pumper
Miles: 14,678.0 Engine Hrs: 1,236.0
Pump Model: QMAX150-23L Serial No: H10562 Pump Hours: 95.0
Rated Capacity: 1500 GPM Stages: 1 Pump Ratio: unknown
Suction Size: 6 In. Length: 10 Ft. Lift: 2 Ft. Primed: 8 Sec.
Vacuum Test: 22.5 In.with 0.5 Inches drop in 5 minutes Test Auxiliary Cooler: pass
Auto Pressure Control Type: valve Test-Max Increase: 10 P.S.I.
Test Plate Readings: 1509 GPM at 150 PSI at 1410 RPM
1053 GPM at 200 PSI at 1533 RPM
750 GPM at 250 PSI at 1657 RPM
Recommended Governed Engine Speed: 2400 RPM
Capacity test-GPM 1500 PSI: 150 Tip Size: FM In. Test Time: 20 Min.
No.2-1/2"Lines: 3 Pump Control Position: 1,2,3
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
12:05 1400 150 flowmeter 1510
12:10 1405 150 flowmeter 1510
12:15 1395 150 flowmeter 1510
12:20 1400 150 flowmeter 1510
Overload Test:
12:25 1 1 1440 165 flowmeter 1,570
Oil Pressure: 50 PSI Water Temp: 190 F. Vacuum: 10 In. Volts 13.8
70%Cap.Test-GPM 1050 PSI: 200 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2"Lines: 2 Pump Control Position: 1,2
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
12:30 1530 200 flowmeter 1060
12:35 1520 200 flowmeter 1060
12:40 1520 200 flowmeter 1060
Oil Pressure: 50 PSI Water Temp: 180 F. Vacuum: 5.5 In. Volts 13.8
50%Cap.Test-GPM 750 PSI: 250 Tip Size: FM In. Test Time: 10 Min.
No.2-1/2" Lines: 2 Pump Control Position: 1,2
Time Counter Eng. RPM Pump Press. Pitot GPM Notes
12:45 1650 250 flowmeter 750
12:50 1655 250 flowmeter 750
12:55 1650 250 flowmeter 750
Oil Pressure: 50 PSI Water Temp: 190 F. Vacuum: 4 In. Volts 13.8
Barometric Pressure 29.91 Test Water Temperature 70
CERTIFIED 13 r Troy Harmon TESTING ENGINEER