Loading...
HomeMy WebLinkAbout04040190 Building PlansSECTION 15010 - BASIC MECHANICAL REQUIREMENTS A. DEFINITIONS AND TERMS . 1. THE WORD "OWNER" SHALL MEAN "CELADON TRUCKING SERVICES, INC.", OR ANY REPRESENTATIVE OF HIS PARTY DULY AUTHORIZED TO ACT IN HIS BEHALF IN THE EXECUTION OF THE WORK. 2. THE WORD "CONTRACTOR" SHALL MEAN THE PERSON, FIRM OR CORPORATION ENTERING INTO A CONTRACT OR AGREEMENT WITH THE OWNER TO CONSTRUCT AND COMPLETE THE WORK AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN. 3. THE WORD "ARCHITECT AND ENGINEER" SHALL MEAN "PETERSON ARCHITECTURE" AND ' FROST ENGINEERS, INC" AND THEIR REPRESENTATIVES ACTING AS THE OWNER'S APPOINTED AGENT. 4. THE WORD "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION AND SIMILAR SUBSEQUENT REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND CALLED ON THE DRAWINGS AND SPECIFIED HEREIN. 5. THE WORD 'INSTALL SHALL MEAN OPERATIONS AT THE PROJECT SITE, INCLUDING, BUT NOT LIMITED TO, UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND ON THE DRAWINGS AND SPECIFIED HEREIN. 6. THE TERM "PROVIDED" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED" BY THIS CONTRACTOR WITH THE EXCEPTION WHERE ITEMS ARE "PROVIDED BY THE OWNER" WHICH MEANS "FURNISHED ONLY" AND INSTALLED BY THIS CONTRACTOR, UNLESS NOTED OTHERWISE. B. SUMMARY OF WORK 1. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES NECESSARY FOR AND REASONABLY IMPLIED, AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION, TESTING AND BALANCING OF ALL THE WORK FOR ALL INSTALLED SYSTEMS AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS. THESE CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING: A. A COMPLETE HVAC SYSTEM INCLUDING SUPPLY, RETURN AND EXHAUST AIR DUCTWORK, SUPPLY AIR DIFFUSERS, RETURN AIR GRILLES, EXHAUST AIR GRILLES, DUCTWORK INSULATION, FITTINGS, HVAC EQUIPMENT, DAMPERS, ROOF CURBS AND CAPS, EXHAUST FANS, CONTROL WIRING, ETC„ AND ALL RELATED COMPONENTS NECESSARY FOR A COMPLETE INSTALLATION AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. B. A COMPLETE PLUMBING SYSTEM INCLUDING SANITARY WASTE, VENTS, DRAINS, DOMESTIC COLD AND HOT WATER PIPING SYSTEM, PIPE HANGERS, PIPE INSULATION, VALVES, PLUMBING FIXTURES AND EQUIPMENT, NATURAL GAS PIPING, ETC., AND ALL RELATED COMPONENTS NECESSARY FOR A COMPLETE INSTALLATION AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. C. GENERAL REQUIREMENTS 1. THIS CONTRACTOR SHALL VERIFY THE EXTENT OF ALL EXISTING CONDITIONS, UTILITY CONNECTION POINTS, EQUIPMENT PROVIDED BY OTHERS, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS BY VISITING THE SITE PRIOR TO BIDDING DOES NOT RELIEVE THIS CONTRACTOR OF RESPONSIBILITY IN WORK OR WORKMANSHIP. 2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK, AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THIS CONTRACT. 3. RELOCATION OF ANY EXISTING WATER, GAS, WASTE, VENT, DRAINAGE LINES, DUCTWORK, EQUIPMENT, ETC., TO FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN BID PROPOSAL. THIS CONTRACTOR SHALL NOT REMOVE OR RELOCATE ANY LANDLORD EQUIPMENT, PIPING, ETC., WITHOUT PRIOR WRITTEN APPROVAL FROM THE LANDLORD. 4. ALL WORK BY THIS CONTRACTOR SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE OF THE EQUIPMENT AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES. 5, ALL ROOF CUTTING, PATCHING AND FLASHING SHALL BE BY THE OWNER'S ROOFING CONTRACTOR OR OWNER'S APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ALL ROOF PENETRATIONS WITH THE OWNER. MAINTAIN ALL CODE REQUIRED CLEARANCES FROM ALL OUTSIDE AIR OR FRESH AIR INTAKES LOCATED ON THE ROOF. 6. THIS CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL OR SUPPORTS TO SUPPORT ANY INSTALLED EQUIPMENT AS SHOWN AND CALLED FOR ON THE DRAWINGS OR IN THE SPECIFICATIONS. THIS CONTRACTOR SHALL COORDINATE ALL ADDITIONAL STEEL OR SUPPORT LOCATIONS WITH THE OWNER PRIOR TO BIDDING AND INSTALLATION. 7. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF OF THE FLOOR FOR ALL INSTALLED PIPING, DRAINS, SLEEVES, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. COORDINATE ALL FLOOR CUTS WITH THE OWNER AND ANY AFFECTED TENANTS. CUTTING AND PATCHING SHALL BE HELD TO A MINIMUM. 8. THIS CONTRACTOR SHALL COORDINATE ALL ROOF MOUNTED EQUIPMENT LOCATIONS WITH THE OWNER PRIOR TO INSTALLATION. 9. ALL ROOF TOP MECHANICAL EQUIPMENT SHALL BE IDENTIFIED WITH A MINIMUM TWO REFER( TO THE AMERICANGNATIONALIN TANDARDST INDSTI UTE O(ANSI) FOR LETTERING SIZE, LENGTH OF COLOR FIELD, COLORS AND VIEWING ANGLES OF IDENTIFICATION DEVICES. D. CODES. FEES AND MISCELLANEOUS COSTS 1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER REQUIREMENTS AND UTILITY COMPANY REGULATIONS.. 2. IN CASES OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND THE CONTRACT DOCUMENTS, THE MOST STRINGENT SHALL GOVERN. THIS CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT IN WRITING OF ANY SUCH DIFFERENCE. 3. NON-COMPLIANCE: SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICAB! E BUILDING CODES, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, LANDLORD REQUIREMENTS, UTILITY COMPANY REGULATIONS OR THE CONTRACT DOCUMENTS, THIS CONTRACTOR SHALL BEAR ALL COSTS ARISING FOR THE CORRECTION OF NON -COMPLYING ITEMS. 4. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL FEDERAL AND STATE LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. THOSE REQUIREMENTS ARE TO BE CONSIDERED A MINIMUM AND ARE TO BE EXCEED WHEN SO INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES AND STANDARDS AND ANY CHANGES OR MODIFICATIONS TO THE DRAWINGS OR SPECIFICATIONS AS REQUIRED BY THE CODES SHALL BE INCLUDED IN THE BID. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THE CONTRACTOR FOR FAILURE OF CODE INQUIRY OR COMPLIANCE. 5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PAYMENT OF ALL FEES, NECESSARY DRAWINGS AND ARRANGING AND PAYING FOR ALL INSPECTIONS, TESTS, ETC., WHICH MAY BE REQUIRED BY ANY AUTHORITY OR UTILITY COMPANY IN CONNECTION WITH THE FURNISHING OR INSTALLATION OF ANY OF HIS RESPECTIVE WORK. E. WORK AND WORKMANSHIP 1. ALL MATERIALS AND EQUIPMENT SHALL BE OF THE HIGHEST QUALITY IN EVERY RESPECT. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, OF THE LATEST DESIGN AND FREE OF DEFECTS. 2. WORKMANSHIP SHALL BE BY SKILLED WORKMEN OF HIGHEST STANDARD IN STRICT ACCORDANCE WITH ALL APPLICABLE MANUFACTURERS PRINTED SPECIFICATIONS, PERFORMED UNDER SUPERVISION OF COMPETENT FOREMAN AT ALL TIMES. 3. THE OWNER AND THE ARCHITECT HAVE FULL POWER TO CONDEMN OR REJECT ANY WORK, MATERIALS OR EQUIPMENT NOT IN ACCORDANCE WITH THESE SPECIFICATIONS AND DRAWINGS OR ARE NOT IN CONFORMANCE WITH THE MANUFACTURES SPECIFICATIONS OR DRAWINGS WHICH WERE APPROVED BY THE OWNER OR ENGINEER. 4. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE REMOVED AND REPLACED TO THE SATISFACTION OF THE OWNER OR ARCHITECT AT THIS CONTRACTORS EXPENSE. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE SO STATED IN WRITING BY THE OWNER OR THE ENGINEER. 5. SUCH DECISIONS AS THE OWNER OR THE ENGINEER MAY MAKE WITH RESPECT TO QUESTIONS CONCERNING THE QUALITY, FITNESS OF MATERIALS, EQUIPMENT AND WORKMANSHIP SHALL BE BINDING UPON THE PARTIES THERETO. F. DEVIATIONS FROM DRAWINGS 1. THE DRAWINGS SHOW THE INTENDED ARRANGEMENT AND ROUTING OF ALL PIPING, DUCTWORK, EQUIPMENT AND APPURTENANCES. THEY SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT. 2. THIS CONTRACTOR SHALL INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND SHALL PROVIDE ANY FITTINGS, OFFSETS AND ACCESSORIES REQUIRED TO ACCOMMODATE SAID CONDITIONS IN THE BID PROPOSAL. 3. WHERE TRADE NAMES AND MANUFACTURES ARE USED ON THE DRAWINGS OR SPECIFIED HEREIN THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURES CONSIDERED AS AN E UAL OR BETTER I A Q N LL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY THE OWNER OR THE ARCHITECT PRIOR THROUGH SHOP DRAWING OR SUBMITTAL PROCESS, TO ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THIS CONTRACTORS EXPENSE. 4. THE DRAWINGS INDICATE AN INSTALLED SYSTEM BASED UPON SELECTED MANUFACTURERS OF EQUIPMENT. ELECTRICAL SERVICES, SIZE, CONFIGURATIONS, ETC., ARE CONSISTENT WITH THE MANUFACTURER'S RECOMMENDATIONS. OTHER MANUFACTURERS ARE ENCOURAGED TO FURNISH EQUIPMENT FOR THIS PROJECT; HOWEVER, IT SHALL BE THIS CONTRACTORS RESPONSIBILITY TO ASSURE THAT THE EQUIPMENT IS CONSISTENT WITH THE DESIGN BASE. NO ADDITIONAL COMPENSATION SHALL BE AWARDED FOR REVISIONS, MODIFICATIONS, ETC., TO ELECTRICAL SERVICES, WIRING, BREAKERS, SPACE, CLEARANCE, DUCTWORK, PIPING, ETC., REQUIRED BY OTHER MANUFACTURES. G. OCCUPATIONAL SAFETY AND HEALTH ACT 1. ALL WORK SHALL BE COMPLY WITH THE CURRENT REQUIREMENTS OF THE U.S. DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, ENTITLED OCCUPATIONAL SAFETY AND HEALTH STANDARDS; NATIONAL CONSENSUS STANDARDS AND ESTABLISHED FEDERAL STANDARDS. H. COORDINATION BETWEEN CONTRACTORS 1. BEFORE THE COMMENCEMENT OF ANY WORK, THIS CONTRACTOR SHALL EXAMINE ALL THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS COMPONENTS OF THE INSTALLED SYSTEMS, MATERIALS, PIPING, EQUIPMENT, ETC., WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES AND CONFLICTS. 2. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR .TO LEAVE THE REQUIRED, NECESSARY ROOM FOR OTHER TRADES. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE TO COORDINATE WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES, CONFLICTS, RELOCATION OF DUCTWORK, PIPING, EQUIPMENT, ETC., FOUND ENCROACHING ON SPACE REQUIRED BY OTHERS. 3. THIS CONTRACTOR SHALL PROVIDE COMPLETE INFORMATION AND COOPERATION TO THE OTHER CONTRACTORS AND TRADES PERTAINING TO HIS WORK TO ACCOMPLISH COORDINATION OF THE COMPLETED PROJECT. I. EQUIPMENT DRAWINGS 1. THIS CONTRACTOR SHALL PROVIDE EQUIPMENT DRAWINGS OF PROVIDED EQUIPMENT AS SPECIFIED HEREIN. 2. THE FOLLOWING ITEMS ARE A MINIMUM REQUIREMENT FOR EACH EQUIPMENT DRAWING SUBMITTAL: A. SHEET SIZE 8-1/2" X 11 B, MANUFACTURE'S STANDARD SCHEMATIC DRAWINGS: 1. MODIFY DRAWINGS TO DELETE INFORMATION THAT IS NOT APPLICABLE TO THIS PROJECT. 2. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION APPLICABLE TO THIS PROJECT. C. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES, - PERFORMANCE CHARTS, ILLUSTRATIONS AND OTHER STANDARD DESCRIPTIVE DATA. 1. CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS, MODELS, ETC. 2, SHOW EQUIPMENT DIMENSIONS AND MAINTENANCE OR CONSTRUCTION CLEARANCES REQUIRED. 3. SHOW PERFORMANCE CHARACTERISTICS AND CAPABILITIES. 4. SHOW WIRING DIAGRAMS AND CONTROLS. 5. MATERIAL AND SAFETY DATA SHEETS. 6. THE FULL MANUFACTURE'S MODEL NUMBER OF EACH ITEM. 7, IDENTIFICATION OF COLOR OR FINISHES. . 8. THIS CONTRACTOR'S STAMP, SIGNATURE AND DATA SHALL BE AFFIXED TO EACH COPY OF THE SHOP DRAWINGS WITH INDICATION OF HIS REVIEW. 3. COPIES OF THE EQUIPMENT DRAWINGS AND ALL OTHER RELATED INFORMATION MUST APPEAR IN THE OPERATIONS MANUAL LEFT ON SITE AFTER PROJECT COMPLETION. J. RECORD DRAWINGS 1. DURING CONSTRUCTION THIS CONTRACTOR SHALL MAINTAIN A COMPLETE AND LEGIBLE SET OF DRAWINGS SHOWING CHANGES AND DEVIATIONS BETWEEN ACTUAL CONSTRUCTION AND THE ENGINEER'S DRAWINGS. 2. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE, THIS CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO THE DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT WITH THIS CONTRACTOR'S STAMP AND SIGNATURE THEREON. THIS COPY OF THE RECORD DRAWINGS SHALL BE PLACED IN A DRAWING TUBE AND MARKED "RECORD DRAWINGS - DO NOT REMOVE FROM PREMISES' AND SHALL BE KEPT WITH THE OPERATIONS MANUAL. K. OPERATIONS MANUAL 1. THREE COPIES OF THE OPERATIONS AND MAINTENANCE MANUAL FOR ALL EQUIPMENT FURNISHED FOR THE PROJECT SHALL BE COLLECTED AND INSERTED IN LABELED THREE INCH (3") THREE (3) RING BINDERS. 2. OPERATIONS AND MAINTENANCE MANUALS SHALL BE ASSEMBLED AS FOLLOWS: A. SECTION 1 1. TITLE OF PROJECT 2. LOCATION OF PROJECT 3. NAME AND ADDRESS OF OWNER 4. NAME AND ADDRESS OF ENGINEER 5, NAME AND ADDRESS OF THIS CONTRACTOR. B. SECTION 2 1. SHOP DRAWINGS OF ALL APPROVED EQUIPMENT. C. SECTION 3 1. A LISTING OF ALL EQUIPMENT WARRANTIES INDICATING THE EQUIPMENT MODEL NUMBER, SERIAL NUMBER, START AND ENDING DATE OF THE WARRANTY, ETC. D. SECTION 4 1. COPIES OF ALL AIR AND WATER BALANCE REPORTS. 3. EACH SECTION SHALL BE SEPARATED BY A PASTEBOARD TABBED DIVIDER. 4. ALL INFORMATION SHALL BE ARRANGED IN AS MANY BINDERS AS NECESSARY, 5. OPERATION AND MAINTENANCE MANUAL AND DRAWING TUBE SHALL BE SENT TO THE ENGINEER. L. INSPECTIONS, FINAL REPORTS AND GUARANTEE 1. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL INFORM THE LOCAL AND STATE AUTHORITIES AND THE OWNER TO ARRANGE FOR FINAL INSPECTIONS OF THIS WORK. 2. THIS CONTRACTOR SHALL FURNISH TO THE OWNER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT THE COMPLETION OF THIS PROJECT. 3. THIS CONTRACTOR SHALL SUBMIT TO THE OWNER UPON COMPLETION OF THIS WORK A LETTER CERTIFYING THAT THIS WORK IS IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. 4. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT, WORK, ETC., UNDER THIS CONTRACT FOR ONE (1_) YEAR AFTER THE ACCEPTANCE OF ALL SYSTEMS INSTALLED BY THIS CONTRACTOR UND RR THIS CONTRACT, THIS CONTRACTOR SHALL MAKE GOOD, REPAIR OR REPLACE AT THIS CONTRACTORS OWN EXPENSE, ANY DEFECTIVE WORK, MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED FORM THE DATE OF ACCEPTANCE, IN WRITING. EXTENDED WARRANTIES ARE AS SPECIFIED WITH THE INDIVIDUAL EQUIPMENT. 5. UNDER THE ONE (1) YEAR GUARANTEE PERIOD THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE PREMISES CAUSED BY DEFECTS IN ANY WORKMANSHIP OR ANY EQUIPMENT FURNISHES AND/OR INSTALLED BY THIS CONTRACTOR. M. SLEEVES 1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE INSTALLATION, EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND TWO INCHES (2") ABOVE THE FLOOR. 2. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM. N, FIRE STOPPING 1. ALL OPENINGS THROUGH FIRE RATED WALLS AND10R FLOORS FOR CONDUITS SHALL BE FIRE SEALED IN ACCORDANCE WITH NFPA 101 WIITH CALCIUM SILICATE, SILICONE RTV" FOAM, 3M FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE RATING. PROVIDE SLEEVES AS REQUIRED BY ALL APPLICABLE CODES OR OWNER REQUIREMENTS. (INCLUDING FACTORY MUTUAL FIELD VERIFY ALL EXISTING PENETRATIONS THROUGH FIRE WALLS AND/OR FLOORS AND SEAL A REQUIRED IN ACCORDANCE WITH NFPA 101 AS LISTED ABOVE. 0. PHASING REQUIREMENTS 1. THIS CONTRACTOR SHALL INCLUDE IN HIS BID ALL NECESSARY SERVICES REQUIRED TO KEEP THE OPERATING PHASE OF THE OWNER'S HVAC, PLUMBING OR FIRE PROTECTION, SYSTEMS EIC., IN OPERATION. THIS CONTRACTOR SHALL SCHEDULE SHUT DOWNS OF THE OWNER'S HVAC, PLUMBING, FIRE PROTECTION OR ELECTRICAL SYSTEMS ONE WEEK PRIOR TO THE SHUT DOWN. SECTION 15145 - HANGERS AND SUPPORTS A. RELATED WORK 1. MECHANICAL INSULATION: SECTION 15250 B. MANUFACTURES 1. BI -LINE 2. FEE AND MASON 3. GRINNELL 4. MICHIGAN HANGER COMPANY C. INSTALLATION 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE COMPLETE INSTALLATION OF WORK. 2. HANGERS SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO EQUIPMENT OR PIPING. HANGING FROM METAL DECK SHALL NOT BE PERMITTED. HANGERS SHALL BE ATTACHED TO THE UPPER CHORD OF THE BAR JOIST. WHERE INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT DUCTWORK OR PIPING, THIS CONTRACTOR SHALL INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS DOORS TO FIRE DAMPERS, VALVES, EQUIPMENT, ETC. HANGER TYPES AND INSTALLATION METHODS SHALL BE SUBJECT TO ALL APPLICABLE CODES AND THE LANDLORD. REQUIREMENTS. VERIFY ANY LANDLORD REQUIREMENTS PRIOR TO BIDDING. 3. HANGERS OR SUPPORTS FOR EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL NOT BE SUPPORTED FROM THE LANDLORD'S CEILING, SOFFITS, NEUTRAL PIERS, PIPING, DUCTWORK, METAL ROOF DECK, LATERAL BRACING, BRIDGING, ELECTRICAL CONDUITS, ETC. 4. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF INSULATION. INSTALL SIX INCH (6" LONG SPLIT CIRCLE GALVANIZED SADD E BETW T ) L EEN HE HANGER AND THE PIPE INSULATION. REFER TO TH E DRAWINGS FOR PIPE HANGER DETAILS. 5. HANGERS AND PIPING OF'DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED. 6. PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY THE OWNER OR CODE. END OF SECTION 15145 SECTION 15241 - VIBRATION ISOLATION A. RELATED WORK 1. HANGERS AND SUPPORTS: SECTION 15145 2. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 B. MANUFACTURES 1. AMBER/BOOTH COMPANY 2. KORFU D DYNAMICS CORPORATION 3. MASON INDUSTRIES, INCORPORATED 4. PEABODY NOISE CONTROL, INCORPORATED 5. KINETICS NOISE CONTROL, INCORPORATED C. INSTALLATION 1. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS BETWEEN VIBRATING EQUIPMENT, FANS, ROOF TOP AIR CONDITIONING EQUIPMENT, EXHAUST FANS, ETC., AND THE BUILDING STRUCTURE. 2. VIBRATING EQUIPMENT HUNG FROM THE STRUCTURE SHALL BE ISOLATED WITH RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORT FROM THE FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES. 3. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES. ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID 'GROUNDING" THE ISOLATOR. 4. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND AT THE UPPER AND LOWER ATTACHMENTS TO THE STRUCTURES, EQUIPMENT,ETC. 5. CONSULT MANUFACTURER FOR FURTHER APPLICATION AND INSTALLATION DATA. END OF SECTION 15241 SECTION 15250 MECHANICAL INSULATION A. RELATED WORK 1. HANGERS AND SUPPORTS: SECTION 15145 2. PLUMBING: SECTION 15400 3. HYDRONIC/REFRIGERANT PIPING: SECTION 15500 4. HEATING, VVENTILATION AND AIR CONDITIONING: SECTION 15800 B. PRODUCTS 1. BLANKET INSULATION W'iTH ALUMINUM FOIL FACING A. CERTAIN TEED CORPORATION. B. KNAUF FIBERGLASS C. MANVILLE D. OWENS-CORING FIBERGLASS CORPORATION 2. FLEXIBLE ELASTOMERIC A, ARMSTRONG WORLD INDUSTRIES B. PITTSBURGH CORNING PRODUCTS C. RUBATEX CORPORATION --- CITY OF CARMEL/CLAY TOWNSHIP Dept. of Community Services -- Building & Code Enforcement One Civic Square I" Floor; Carmel, IN 46032 PLAN AUTHENTICATION CERTIFICATIONS AND AGREEMENT As the authorized agent responsible for obtaining a permit or permits', I certify that these plans are IDENTICAL to those released for construction by the Indiana Depart. of Fire & Building Services. I also understand that if it is determined that these plans are not identical, a STOP WORK ORDER will be served, s requ' ed and the Ordinances referenc, bellow. 'r ��l 55 � u� (A S 6E Ctrj A horized Signature Printed Name 'Required under Chapter 7, Section 10 of the Carmel City Code, entitled "Building Code' and Section 29.4.2 and Section 29.4.3 entitled "Administration". Required by Carmel / Clay Township Zoning Ordinance, Section 31.1 entitled "Violations and Penalties". S:Permi is / Forms /AuthentStickerl 1-01 C. INSULATION SCHEDULES TYPE OF DUCTWORK FORM THICKNESS JACKET INTERIOR SUPPLY, RETURN, RELIEF AND OUTSIDE AIR DUCTWORK BLANKET 1-1/2" - INTERIOR EXPOSED SUPPLY, RETURN, - 1/2" - INTERIOR HYDRONIC (35' - 99') BOARD 1" - RELIEF AND OUTSIDE AIR DUCTWORK 1„ - INTERIOR HYDRONIC (100' - 250') ALL DUCTWORK RISERS 3/4" - INTERIOR REFRIGERANT (LIQUID AND SUCTION ONLY) TO ROOF MOUNTED EQUIPMENT BLANKET 1-1/2" - (SEE NOTE 3 BELOW) - EXTERIOR EXPOSED REFRIGERANT (LIQUID AND SUCTION ONLY) 1/2" - 1-1/4" TYPE OF PIPING PIPE SIZE THICKNESS JACKET INTERIOR DOMESTIC HOT WATER 1/2" - 4" 1/2" - SANITARY DRAINS AND TRAPS EXPOSED AT FIXTURES FOR THE DISABLED (SEE NOTE 1 BELOW) - 1/2" - INTERIOR HYDRONIC (35' - 99') 1/2" - 1-1/4" 3/4' - 1-1/2" - 4" 1„ - INTERIOR HYDRONIC (100' - 250') 1/2" - 2" 3/4" - INTERIOR REFRIGERANT (LIQUID AND SUCTION ONLY) 1/2" - 3/4" - ,1--1/4" 1-1 2' - 4" / 1 - EXTERIOR EXPOSED REFRIGERANT (LIQUID AND SUCTION ONLY) 1/2" - 1-1/4" 3/4" ALUM. 1-1 /2" - 4" 1 " ALUM. SANITARY DRAINS LOCATED IN THE CEILING SPACE OF OTHER TENANTS ALL SIZES 1/2" - INTERIOR DOMESTIC COLD WATER 1/2" - 4" 1/2" - EXTERIOR EXPOSED NATURAL GAS (SEE NOTE 2 BELOW) 1/2" - 1--1/4" 3/4" ALUM. 1-1 /2" - 4" 1 " ALUM. INTERIOR CONDENSATE DRAIN ALL SIZES - - EXTERIOR CONDENSATE DRAIN 3/4" - 4" i-1/2" ALUM. 1. PIPING INSULATION IS BASED UPON FLEXIBLE ELASTOMERIC TYPE. 2. ALL INSULATION SHALL MEET LOCAL CODE REQUIREMENTS AND UL FLAME SPREAD AND SMOKE DEVELOPED RATINGS. NOTES: 1. TRUEBRO MODEL 102W "HANDI LAV GUARD" INSULATION KIT SHALL BE USED UNDER ADA LAVATORIES, 2. CORROSION -RESISTANT POLYETHYLENE COATING MAY BE SUBSTITUTED. END OF SECTION 15250 SECTION 15300 - FIRE PROTECTION SECTION 15400 - PLUMBING A. RELATED WORK 1. VALVES: SECTION 15100 2. HANGERS AND SUPPORTS: SECTION 15145 3. MECHANICAL INSULATION: SECTION 15250 4. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 B. EQUIPMENT AND MATERIALS 1. REFER TO THE DRAWINGS FOR PLUMBING FIXTURE SPECIFICATIONS. 2. SANITARY WASTE AND VENT PIPING SHALL BE AS FOLLOWS: A. SERVICE WEIGHT CAST IRON PIPE, VENT PIPING ABOVE THE FLOOR TWO INCHES (2") OR SMALLER MAY BE GALVANIZED STEEL. PVC PIPING SHALL BE ALLOWED AS A SUBSTITUTE WHEN PERMITTED BY THE LOCAL CODES, AND BUILDING DEPARTMENT OFFICIALS AND IT DOES NOT AFFECT OTHER TRADES. PROVIDE DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. 3. CONDENSATE DRAIN PIPING SHALL BE AS FOLLOWS: A. TYPE "L' DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY SOLDERED JOINTS AND WROUGHT COPPER FITTINGS WITH DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. B. ALL CONDENSATE DRAIN PENETRATIONS SHALL BE MADE WITHIN THE ROOF CURB OF THE ROOF TOP AIR CONDITIONING UNIT. TERMINATE CONDENSATE DRAINS AT CODE APPROVED TERMINATION POINTS. CONDENSATE DRAINS SHALL NOT TERMINATE ABOVE THE ROOF LEVEL. 4. DOMESTIC HOT AND COLD WATER PIPING SHALL BE AS FOLLOWS: A. TYPE "K" ANNEALED TEMPERED COPPER TUBE FOR PIPE SIZES TWO INCH (2") AND SMALLER BELOW GRADE. BRAZE ALL JOINTS. DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. B. TYPE "L" DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY SOLDERED JOINTS AND WROUGHT FITTINGS FOR ALL OTHER PIPING. DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. 5. NATURAL GAS PIPING SHALL BE AS FOLLOWS: A. BLACK STEEL, SCHEDULE 40, ASTM A-120, WITH MALLEABLE THREADED FITTINGS FOR TWO INCH (2") AND SMALLER AND WELDED JOINTS FOR TWO AND ONE-HALF INCH (2-1/2") AND LARGER. 6. INSTALL WATER HAMMER ARRESTORS ON EACH HOT AND COLD WATER SUPPLY TO EACH FIXTURE. WATER HAMMER ARRESTORS SHALL BE SIMILAR JAY R. SMITH "HYDROTROL" SERIES 5000 OR EQUAL. REFER TO THE PLUMBING DRAWINGS FOR SHOCK ABSORBER SCHEDULE, 7. BACKFLOW PREVENTERS SHALL BE AS FOLLOWS: A. BRONZE BODY WITH THREADED ENDS, 150 PSIG MINIMUM WORKING PRESSURE UNLESS NOTED OTHERWISE, CORROSION RESISTANT INTERIOR COMPONENTS AND STRAINER ON INLET. 8. ESCUTCHEONS SHALL BE CHROME PLATED, SIZE AS REQUIRED AND PLACED AT ALL PIPE PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, ETC., IN ALL FINISHED AREAS. 9. INSTALL FIXTURE CARRIERS OR SUPPORT FOR ALL WALL MOUNTED PLUMBING FIXTURES. FIXTURE CARRIERS OR SUPPORTS SHALL BE AS FOLLOWS: A. JAY R. SMITH MANUFACTURING COMPANY B. JOSAM COMPANY C. WADE DIVISION; TYLER PIPE D. ZURN INDUSTRIES, INCORPORATED; HYDROMECHANICS DIVISION C. INSTALLATION 1. VALVE LOCATIONS SHALL BE AS FOLLOWS: .. A. PROVIDE A SHUT OFF VALVE IN THE SUPPLY PIPING TO EACH FIXTURE. PROVIDE A MINIMUM 24' X 24" ACCESS DOOR WHERE REQUIRED FOR VALVE ACCESS. B. PROVIDE A GAS COCK IN THE SUPPLY PIPING TO EACH PIECE OF EQUIPMENT REQUIRING GAS SERVICE. 2. PROVIDE A DIRT LEG AND UNION CONNECTION TO EACH PIECE OF EQUIPMENT REQUIRING GAS SERVICE. 3. PITCH GAS PIPING AT A UNIFORM GRADE OF 1/4" IN FIFTEEN FEET (15'-0") UPWARD IN THE DIRECTION OF FLOW. 4. GAS PIPING INSTALLED IN RETURN AIR PLENUMS SHALL BE SLEEVED AND VENTED OR WELDED IN ACCORDANCE WITH UTILITY COMPANY REGULATIONS, LOCAL CODES A. RELATED WORK AND ALL APPLICABLE NFPA CODES. 1. BASIC MECHANICAL REQUIREMENTS: SECTION 15010 5. PROVIDE FLOOR DRAINS AND CLEAN -OUTS PER CODE REQUIREMENTS. B. SUMMARY OF WORK NO SCALE D. TEST OF SYSTEMS 1. THE FIRE PROTECTION CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, MSF PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES NECESSARY 1. PRIOR TO THE INSTALLATION OF THE SANITARY PIPING SYSTEM SNAKE THE FOR AND REASONABLY IMPLIED, AND INCIDENTAL T0, THE FURNISHING, INSTALLATION, SANITARY SYSTEM A MINIMUM OF FIFTY FEET (50'-0") AND REPORT ANY BLOCKAGE. COMPLETION AND TESTING OF ALL THE WORK FOR A COMPLETE FIRE PROTECTION SYSTEM AS SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS. THESE 2. TEST WATER PRESSURE TO INSURE MINIMUM PSI MATCHES MOST DEMANDING CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING: EQUIPMENT SUPPLIED. A. A COMPLETE FIRE PROTECTION SYSTEM AS REQUIRED BY NFPA, LOCAL CODES, OWNER'S CRITERIA AND THE OWNER'S INSURANCE CARRIER INCLUDING 3. STERILIZE WATER SYSTEM PIPING IN ACCORDANCE WITH ALL CODE REGULATIONS. SPRINKLER PIPING, TAPS, RISERS, LATERALS, BRANCHES, VALVES, ALARMS, SPRINKLER 4. TEST THE WATER PIPING SYSTEM AT 100 PSIG FOR FOUR (4 HOURS OR AS REQUIRED HEADS, ETC., FIRE PUMPS AND ALL RELATED COMPONENTS NECESSARY FOR A BY THE LANDLORD, UTILITY COMPANY REGULATIONS OR BY CODE REQUIREMENTS. COMPLETE INSTALLATION AS SPECIFIED HEREIN. B. DESIGN DRAWINGS, HYDRAULIC CALCULATIONS, SUBMITTALS AND APPROVALS. 5. TEST THE SANITARY WASTE, VENT AND DRAIN PIPING BY A TEN FOOT (10') WATER C. TESTS AND TEST CERTIFICATES. COLUMN FOR ONE HOUR OR AS REQUIRED BY THE UTILITY COMPANY REGULATIONS OR BY CODE REQUIREMENTS. D. FIRE EXTINGUISHER(S). 6. TEST AND PURGE THE GAS PIPING SYSTEM AS PER THE REQUIREMENTS OF THE C. GENERAL REQUIREMENTS UTILITY COMPANY REGULATIONS, LOCAL CODES AND APPLICABLE NFPA CODES. 1. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER END OF SECTION 15400 AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR i� WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SECTION 15530 - REFRIGERANT PIPING SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK, AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDE AS PAST OF THIS CONTRACT. A. RELATED WORK 2. ALL WORK BY THE FIRE PROTECTION CONTRACTOR SHALL BE INSTALLED SO AS TO BE 1. HANGERS AND SUPPORTS: SECTION 15145 READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS 2. MECHANICAL INSULATION: SECTION 15250 CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE OF THE EQUIPMENT 3. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES. 3. RELOCATION OF ANY EXISTING FIRE PROTECTION PIPING, EQUIPMENT, VALVES, B, REFRIGERANT EQUIPMENT AND MATERIALS SPRINKLER HEADS, ETC., TO FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN THE BID PROPOSAL. THE FIRE PROTECTION CONTRACTOR SHALL NOT REMOVE OR 1. REFRIGERANT PIPING SHALL BE AS FOLLOWS: RELOCATE ANY LANDLORD EQUIPMENT, PIPING, ETC., WITHOUT PRIOR WRITTEN APPROVAL A. TYPE "L" HARD DRAWN COPPER TUBING (ASTM B88). TUBING SHALL BE CLEAN, CAPPED FROM THE LANDLORD. AND NITROGEN CHARGED. 4. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED, FULLY SUPERVISED AND INSTALLED ACCORDING TO NFPA 13. SUPERVISION WILL INCLUDE VALVE TAMPER 2. REFRIGERANT PIPING FITTINGS SHALL BE AS FOLLOWS: SWITCHES AND WATER FLOW INDICATORS WHICH SHALL TRANSMIT CONDITIONS TO A. WROUGHT COPPER OR CAST BRONZE (_ANSI B16.22). ALL COPPER TO COPPER JOINTS THE MASTER FIRE ALARM PANEL. SHALL BE BRAZED WITH SILOS -5 ALLOY. 5. THIS CONTRACTOR SHALL ASSUME FINANCIAL RESPONSIBILITY FOR COMPLIANCE OF ALL 3. REFRIGERANT PIPING SPECIALTIES SHALL BE FURNISHED AS PART OF THE CONDENSING CODES AND REGULATIONS OF GOVERNING STANDARDS AND AGENCIES. UNIT BY THE CONDENSING UNIT MANUFACTURER. REFER TO AIR COOLED CONDENSING 6. ALL SPRINKLER PIPING SHALL BE INSTALLED CONCEALED, AVOIDING INTERFERENCE WITH UNIT DX COIL PIPING DETAIL FOR REFRIGERANT PIPING SPECIALTIES FURNISHED BY THIS CONTRACTOR. LIGHTS, DUCTWORK, PIPING, ETC. THE FIRE PROTECTION CONTRACTOR SHALL . PREPARE COORDINATED SHOP DRAWINGS INDICATING THE LOCATIONS OF ALL SPRINKLER C. INSTALLATION HEADS, SPRINKLER PIPING, LIGHTS AND DIFFUSERS; GRILLES, REGISTET;S, ETC., PRIOR TO INSTALLATION OR MODIFICATION. 1. SUCTION LINES SHALL HAVE ADEQUATE LIFT TRAPS AND/OR DOUBLE SUCTION RISERS TO 7. PROPERLY COMPLETED AND SIGNED TEST CERTIFICATES SHALL BE FURNISHED TO THE MEET THE REQUIREMENTS OF FIELD CONDITIONS AND UNIT MANUFACTURES RECOMMENDATIONS. OWNER, AUTHORITIES HAVING JURISDICTION, THE OWNER'S INSURANCE CARRIER, ETC. UNIT MANUFACTURER SHALL VERIFY ALL REFRIGERANT PIPING SIZES BEFORE INSTALLATION AND -. :p THE INSTALLATION HAS BEEN MADE TO THE UNIT MANUFACTURES SPECIFICATIONS AND 8. CONCEALED SPRINKLER HEADS SHALL BE INSTALLED IN CEILINGS BELOW 8'-O" . RECOMMENDATIONS. D. QUALITY ASSURANCE 2. BRAZE ALL REFRIGERANT PIPING JOINTS WITH SILOS -5 STARTING AT THE INDOOR UNIT AND WORKING TOWARD THE OUTDOOR UNIT. THE SEALS ON THE OUTDOOR UNIT SHALL BE 1. ALL MATERIALS AND DEVICES USED ARE TO BE NEW AND ARE TO BE LISTED FOR USE BY BROKEN LAST. A NITROGEN BLEED SHALL BE USED DURING ALL BRAZING AND ANY TIME THE UNDERWRITERS LABORATORIES, INCORPORATED" AND SHALL BEAR THEIR LABEL WHENEVER "LABEL THE SYSTEM IS OPEN. ALL OPEN LINES SHALL BE CAPPED AND SEALED WHENEVER THIS SERVICE' IS A REQUIREMENT OR IS AVAILABLE, CONTRACTOR IS NOT ON THE PREMISES, 2. THE FIRE PROTECTION SYSTEM SHALL COMPLY WITH ALL REGULATING AGENCIES, ORGANIZATIONS, D. TEST OF SYSTEM PUBLICATIONS, ETC. E. SHOP DRAWINGS 1. PRESSURE TEST FOR LEAKAGE OF SYSTEM WITH AN INERT GAS UP TO 245 PSI. SEAL ANY LEAKING JOINTS AND RETEST UNTIL THE SYSTEM IS LEAK FREE. CHARGE THE SYSTEM 1. THE FIRE PROTECTION CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS AND WITH 25 PSI OF THE SYSTEM REFRIGERANT AND INERT GAS MIXTURE UP TO 245 PSI MAXIMUM AND RETEST SYSTEM WITH A HALIDE LEAK DETECTOR. SEAL ANY LEAKING JOINTS CALCULATIONS OF THE NECESSARY WORK REQUIRED. SUBMIT ALL REQUIRED COPIES TO THE STATE FIRE MARSHALL FOR APPROVAL PRIOR TO THE SUBMISSION TO THE OWNER. AND RETEST UNTIL THE SYSTEM IS LEAK FREE. CRANK CASE HEATERS SHALL BE ENERGIZED TWENTY FOUR (24) HOURS PRIOR TO COMPRESSOR ACTIVATION TO ENSURE ALL REFRIGERANT 2. DRAWINGS SUBMITTED TO THE OWNER SHALL BEAR THE "APPROVAL" OR "RELEASE" STAMP IS OUT OF THE COMPRESSOR. FROM THE SUBMITTED SO ATE FIREAMARSHALLIASHALL A SO BE ATR THIS IMECOMMENiS 2, UPON COMPLETION OF TESTING, THE REFRIGERANT PIPING SYSTEM SHALL BE INSPECTED BY 3. APPROVAL FROM THE OWNER'S INSURANCE CARRIER AND GOVERNING AGENCIES SHALL BE OBTAINED THE AUTHORITY HAVING JURISDICTION AS REQUIRED. AFTER SYSTEM APPROVAL BY THE GOVERNING AUTHORITY THIS CONTRACTOR SHALL INSTALL ALL REFRIGERANT PIPING INSULATION. PRIOR TO FABRICATION, INSTALLATION, MODIFICATION, ETC., OF THE FIRE PROTECTION SYSTEM BY THIS CONTRACTOR. END OF SECTION 15530 4. THE FIRE PROTECTION CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ALL WORK PERFORMED ON THE FIRE PROTECTION SYSTEM PRIOR TO RECEIVING SAID APPROVALS. NO SECTION 15800 - HEATING, VENTILATION AND AIR CONDITIONING ADDITIONAL COMPENSATION SHALL BE AWARDED TO THE FIRE PROTECTION CONTRACTOR FOR WORK DONE PRIOR TO THE RECEIPT OF SAID APPROVALS IF WORK PERFORMED IS NOT IN A. RELATED WORK COMPLIANCE WITH SAID APPROVALS, F. EQUIPMENT AND MATERIALS 1. HANGERS AND SUPPORTS: SECTION 15145 2. VIBRATION ISOLATION: SECTION 15241 1. FIRE PROTECTION PIPING MATERIALS SHALL BE AS FOLLOWS: 3. MECHANICAL INSULATION: SECTION 15250 4. HYDRONIC PIPING: SECTION 15510 A. SCHEDULE 40, BLACK STEEL PIPE, ASTM A-53 FOR FERROUS PIPING, WELDED AND 5. REFRIGERANT PIPING: SECTION 15530 SEAMLESS, ANSI B-36-10-70 FOR WROUGHT IRON STEEL PIPE. , 6. TEMPERATURE CONTROL: SECTION 15900 B. CAST IRON OR MALLEABLE IRON SCREWED FITTINGS FOR PIPES TWO INCHES (2") 7. TESTING, ADJUSTING AND BALANCING: SECTION 15990 AND SMALLER. SCREWED OR CAST IRON FLANGED JOINTS FOR PIPES LARGER THE TWO INCHES (2"). B. EQUIPMENT AND MATERIALS C. GALVANIZED OR BLACK MALLEABLE IRON WITH BRASS SEAT SCREWED UNIONS FOR PIPES TWO INCHES (2") AND SMALLER. 1. ROOFTOP AIR CONDITIONING UNITS SHALL BE AS FOLLOWS: A. REFER TO THE DRAWINGS FOR ROOFTOP AIR CONDITIONING UNIT SCHEDULE. ALL UNITS D. VICTAULIC TYPE COUPLINGS ARE ACCEPTABLE WHERE APPROVED BY CODE AND THE SHALL BE FURNISHED WITH AN EXTENDED FIVE (5) YEAR COMPRESSOR WARRANTY. OWNER. E. FIRE PROTECTION PIPING MANUFACTURES B. ROOF TOP AIR CONDITIONING UNIT MANUFACTURERS 1. CARRIER AIR CONDITIONING; DIVISION OF CARRIER CORPORATION 1. ALLIED TUBE AND CONDUIT CORPORATION 2. MC QUAY INTERNATIONAL 2. BERGER INDUSTRIES 3. JONES AND LAUGHLIN 3. TRANE (THE) COMPANY; DIVISION OF AMERICAN STANDARD, INCORPORATED 4. U.S. STEEL 4. BRYANT AIRCONDITIONING 5. REPUBLIC C. ALL UNITS SHALL BE FURNISHED WITH A MINIMUM SIXTEEN INCH (16") HIGH ROOF F. FIRE PROTECTION FITTING MANUFACTURES CURB BY THE UNIT MANUFACTURER. UNIT MANUFACTURER SHALL ALSO PROVIDE ALL 1. CRANE NECESSARY VIBRATION ISOLATION EQUIPMENT TO ISOLATE ALL MOVING EQUIPMENT FROM 2. GUSTIN-BACON THE BUILDING STRUCTURE. 3. ITT GRINNELL-GRUVLOK 4. STOCKHAM D, ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES, 5. VICTAULIC ACCESSORIES, ETC. PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN 2. SPRINKLER HEADS SHALL BE AS FOLLOWS: AND CALLEb FOR ON THE DRAWINGS AND SPECIFIED HEREIN. A. ALL SPRINKLER HEADS SHALL BE NEW AND RATED FOR 165' F. OR AS REQUIRED BY THE E. THE ROOFTOP AIR CONDITIONING EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE LANDLORD, THE OWNERS INSURANCE CARRIER OR THE AUTHORITY HAVING JURISDICTION. WITH THE UNIT MANUFACTURERS REQUIREMENTS. MAINTAIN ALL UNIT MANUFACTURER B. SPRINKLER LOCATED IN A FINISHED CEILING AREA SHALL BE PENDANT MOUNTED ON REQUIRED CLEARANCES. CONCEALED PIPING. C. SPRINKLER HEADS SHALL BE AS FOLLOWS: F. OUTSIDE, RELIEF AND RETURN AIR DAMPERS SHALL BE OPPOSED BLADE TYPE AND LOW 1. OFFICE: RECESSED PENDANT TYPE, BRIGHT CHROME WITH BRIGHT CHROME ESCUTCHEON, LEAKAGE. 2. WAREHOUSE & SERVICE GARAGE (NO CEILING): UPRIGHT PENDANT TYPE, ROUGH BRASS. 2. VARIABLE AIR VOLUME (VAV)/FAN POWERED VARIABLE AIR VOLUME (FPVAV) BOXES SHALL BE 3. SPRINKLER HEADS SHALL HAVE A MINIMUM ORIFICE SIZE OF 1/2 OR 17/32 AND BE AS FOLLOWS: SHALL BE UL LISTED. D. THE FIRE PROTECTION CONTRACTOR SHALL VERIFY THE SPRINKLER HEAD REQUIREMENTS A. REFER TO THE DRAWINGS FOR VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME PRIOR TO BIDDING. BOX SCHEDULE. E. PROVIDE SPARE HEADS AS REQUIRED BY NFPA, B. VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME BOX MANUFACTURERS: F. SPRINKLER HEAD MANUFACTURES 1. CARRIER AIR CONDDITIONING; DIVISION OF UNITED TECHNOLOGIES 1. CENTRAL SPRINKLER CORPORATION 2. TITUS PRODUCTS DIVISION 2. GRINNELL FIRE PROTECTION SYSTEMS COMPANY, INCORPORATED 3. TRANE (THE) COMPANY; DIVISION OF AMERICAN STANDARD, INCORPORATED 3. RELIABLE AUTOMATIC SPRINKLER COMPANY, INCORPORATED 4. ENVIRONMENTAL TECHNOLOGIES 4. VIKING CORPORATION C. ALL EQUIPMENT SHALL] BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES, G. HANGERS AND SUPPORTS ACCESSORIES, ETC., PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. 1. ALL HANGER AND SUPPORT COMPONENTS SHALL BE PER NEPA. 2. HANGER AND SUPPORT SPACING SHALL BE PER NFPA. D. THE VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME BOX SHALL BE INSTALLED 3. WHEN MECHANICAL GROOVES OR PUSH ON FITTINGS ARE USED, HANGERS AND SUPPORTS IN STRICT ACCORDANCE WITH THE UNIT MANUFACTURES REQUIREMENTS. MAINTAIN ALL UNIT MANUFACTURERS REQUIRED CLEARANCES. SHALL NOT EXCEED THE MAXIMUM SPACING RECOMMENDED BY THE MANUFACTURE. H. TEST OF SYSTEM E. CONTROLS SHALL BE PROVIDED BY THIS CONTRACTOR. 1. THE FIRE PROTECTION CONTRACTOR SHALL FLUSH AND TEST TH(E FI��R//E PROTECTION SYSTEM F. PROVIDE CONTROLS ACCURATE TO 1.5' F. AND ADJUSTABLE FROM 65' F. TO 85' F. NFPASTANDARDS. TEOSTHAND PRESSU RESULTSOSHALL I COMPLY OWITHQNFPA. OR PER ED G. PROVIDE DUCT PRESSURE POWERED CONTROLS, DESIGNED TO OPERATE WITH DUCT 2. ALL TESTS SHALL BE MADE IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE PRESSURES FROM 1.0" W.G. TO 5.0" W.G. OF THE INSURANCE INTEREST. A COMPLETE WRITTEN REPORT OF THE TEST RESULTS SHALL BE SENT TO THE OWNER OR ARCHITECT WITHIN TEN (10) DAYS OF THE H. FAN POWERED VARIABLE AIR VOLUME BOX FILTERS SHALL BE ONE INCH (1 ") 30% EFFICIENT COMPLETION OF THE TESTS STATING THE RESULTS OF THE TEST AND THE NAME OF THE REPRESENTATIVES THROWAWAY TYPE WITH MOUNTING CLIPS AND FRAMES FOR HOLDING DISPOSAL MEDIA. PRESENT DURING THE TEST PRIOR TO FINAL ACCEPTANCE. 3. ANY ALTERATIONS OR REPAIRS SHALL BE MADE IMMEDIATELY AND THE TESTS SHALL BE RERUN TO PROVE FINAL SECURITY OF THE SYSTEM. END OF SECTION 15300 1. ALL UNITS SHALL HAVE CERTIFIED SOUND DATA RATINGS AT OR BELOW AN NC LEVEL OF 35. 3. DUCTWORK SHALL BE AS FOLLOWS: A. ONE INCH (1 ") THICK FOIL FACED FIBERGLASS DUCT BOARD SHALL BE USED IN LIEU OF GALVANIZED SHEET METAL DUCTWORK WHEN PERMITTED BY ALL APPLICABLE CODES. B. VERIFY ALL EXISTING CONDITIONS PRIOR TO THE FABRICATION OF SHEET METAL DUCTWORK. C. ALL DUCTWORK DIMENSIONS ARE INSIDE CLEAR DIMENSIONS. D. FABRICATE ALL RECTANGULAR DUCTWORK WITH GALVANIZED SHEET METAL STEEL IN ACCORDANCE WITH SMANCA, "HVAC DUCT CONSTRUCTION STANDARDS AND ALL REQUIRED APPLICABLE CODES. E. FABRICATE ALL ROUND DUCTWORK WITH GALVANIZED SHEET METAL STEEL IN ACCORDANCE WITH SMANCA, "HVAC DUCT CONSTRUCTION STANDARDS" AND ALL REQUIRED APPLICABLE CODES, FOR SIZES FOURTEEN INCHES (14") OR LARGER USE SPIRAL LOCKSEAM CONSTRUCTION. SIZES LESS THAN FOURTEEN INCHES (14'') OR SMALLER MAY BE SNAP -LOCK CONSTRUCTION. ALL SNAP -LOCK SEAMS SHALL BE SEALED AS SPECIFIED HEREIN. ROUND FITTINGS SHALL BE GALVANIZED STEEL WITH SPOT WELDED AND BONDED CONSTRUCTION. F. ROUND SPIRAL DUCTWORK MAY BE USED IN PLACE OF RECTANGULAR DUCTWORK WHEN CEILING HEIGHTS PERMIT AND EQUIVALENT FREE AREA IS MAINTAINED. ALL SUPPLY AND RETURN AIR DUCTWORK WITHIN TEN FEET (10'-0") OF THE AIR CONDITIONING UNIT SHALL BE RECTANGULAR DUCTWORK AND INTERNALLY INSULATED. G. DUCTWORK CLASSIFICATION SHALL BE AS FOLLOWS: A. LOW PRESSURE 1. SUPPLY AND RELIEF AIR DUCTWORK: 2" W.G. POSITIVE 2. RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK: 2" W.G. NEGATIVE B, MEDIUM PRESSURE 1. SUPPLY AIR DUCTWORK: 3" W.G. POSITIVE H. INSTALL TURNING VANES IN ALL SUPPLY AIR RIGHT ANGLE ELBOWS. 1. INSTALL ALL DUCTWORK SUPPORTS IN ACCORDANCE WITH SMACNA STANDARDS, AND ALL APPLICABLE CODES. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY APPLICABLE CODES. J. DUCTWORK TRANSITIONS SHALL NOT EXCEED THIRTY DEGREE (30') SLOPE UNLESS NOTED OTHERWISE. K. PROVIDE ACCESS TO ALL MANUAL VOLUME DAMPERS, MOTORIZED DAMPERS, FIRE DAMPERS, CONTROLS, ETC., THAT REQUIRE SERVICE OR INSPECTION. MINIMUM ACCESS PANEL SIZE SHALL BE 24" X 24". SUPPLY AIR DIFFUSERS AND RETURN AND EXHAUST AIR GRILLES OR REGISTERS WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS. L. PROVIDE CONICAL OR "BELL -MOUTH" TAKE -OFFS FROM MAIN DUCTWORK TO BRANCH DUCTWORK. 4. FLEXIBLE CONNECTIONS SHALL BE AS FOLLOWS: A. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT ALL CONNECTIONS B EEN VIBRATING EQUIPMENT AND DUCTWORK OR CASINGS. PROVIDE FLEXIBLE CONNEC IONS WHERE DUCTWORK CROSSES BUILDING EXPANSION JOINTS. B. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE COAT FLAMEPROOF FABRIC. PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR MOVEM T AND PREVENT THE TRANSMISSION OF VIBRATION. 5. FLEXIBLE DUCTWORK SHALL BE AS FOLLOWS: A. FLEXIBLE DUCTWORK SHALL BE ONE INCH _(1 ") INSULATED CLASS 1 A, D RATED FOR THE OPERATING PRESSURE OF THE SYSTEM, DUUCTWORK CONSTRUCTION M TERIAL SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES. VERIFY ALL REQUIREMENTS PRIOR TO BIDDING. B. FLEXIBLE DUCTWORK MANUFACTURERS 1. GENFLEX #SLR -25C 2. NORFLEX 3. OWENS CORNING INL=-25 4. THERMAFLEX #G- M 5. WIREMOLD C. FLEXIBLE DUCTWORK SHALL NOT EXTEND OVER THREE FEET (3'--0" IN LENGTH AT ANY ONE (1) LOCATION, AND SHALL NOT BE USED AS A REPLACEMENT FOR ELBOWS. 6. MANUAL VOLUME DAMPERS SHALL BE AS FOLLOWS: A. LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH DUCTWORK TO THE SUPPLY AIR DIFFUSER. B. MANUAL VOLUME DAMPERS MANUFACTURERS 1. AMERICAN WARMING AND VENTILATING, INCORPORATED 2. LOUVERS AND DAMPERS, INCORPORATED FC 3. NAILOR HART �/ C��® 5. RUSIO NAL CONTROLLED AIR ,�r��,`C.a o o , , „- i 4 VL C. OPERATING HANDLES ON ALL DAMPERS SHALL BE A MINIMUM EIGHTEEN INCHES (18) LCiRG. QF ,. 7. FIRE DAMPERS SHALL BE AS FOLLOWS: `� 10 0� O�V A. PROVIDE FIRE DAMPERS AS SHOWN AND CALLED FOR ON THE DRAWINGS, SPECIFIED REQUIRE BY APPLICABLE CODE. B. FIRE DAMPER MANUFACTURERS 1. AMERICAN WARMING AND VENTILATING, INCORPORATED 2. LOUVERS AND DAMPERS, INCORPORATED 3. NAILOR HART 4. NATIONAL CONTROLLED AIR 5. RUSKIN C. ALL FIRE DAMPERS SHALL BE UL LABELED. D. THIS CONTRACTOR SHALL PROVIDE ALL NECESSARY LINTELS, FRAMING, SLEEVES, ETC., AS REQUIRED FOR FIRE DAMPER INSTALLATION. E. REFER TO THE FIRE DAMPER DETAIL ON THE DRAWINGS. 8. DIFFUSERS, REGISTER AND GRILLES SHALL BE AS FOLLOWS: A. REFER TO THE DRAWINGS FOR THE DIFFUSER, REGISTER AND GRILLE SCHEDULE. B. DIFFUSERS, REGISTER AND GRILLE MANUFACTURERS 1: ANEMOSTAT 2. PRICE 3. TITUS 9. ?OOF/EQUIPMENT CURB AND PIPE SUPPORT CURB SHALL BE AS FOLLOWS: F,. THIS CONTRACTOR SHALL PROVIDE ALL THE NECESSARY CURBING AND FRAMING AS REQUIRED TO INSTALL ALL ROOF MOUNTED EQUIPMENT AND PIPING ABOVE THE ROOF AS DESCRIBED, IMPLIED OR SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. ROOF/PIPE CURB HEIGHT SHALL BE A MINIMUM OF SIXTEEN INCHES ��(16" ABOVE ROOFING MEMBBRANE. ALL CURBS MUST BE INSTALLED SO THAT THE TOP IS DEAD LEVEL. ALL ROOF CURBS SHALL BE FULL PERIMETER. END OF SECTION 15800 SECTION 15900 - TEMPERATURE CONTROL A. RELATED WORK 1. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 B. EQUIPMENT AND MATERIALS 1. THIS CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE TEMPERATURE CONTROL SYSTEM TO AUTOMATICALLY CONTROL THE HEATING, VENTILATION, AND AIR CONDITIONING EQUIPMENT AND OTHER COMPONENTS AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. FAILURE TO MENTION ANY SPECIFIC DEVICE DOES NOT RELIEVE THE MECHANICAL CONTRACTOR OF THE RESPONSIBILITY FOR THE FURNISHING OR INSTALLATION OR PROVIDING THE DEVICES OR ITEMS NECESSARY IN ORDER TO ACHIEVE THE INTENT OF THE DRAWING OR SPECIFICATIONS, 2. ALL CONTROL WIRING SHALL BE TWENTY FOUR VOLT (24 V.) AND SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES. ALL CONTROL WIRING SHALL BE IN CONDUIT, 3. ZERO TO ONE HUNDRED PERCENT (O - 100%) OUTSIDE AIR ECONOMIZER CONTROL SHALL CONSIST OF LOW LEAKAGE OUTSIDE, RETURN AND EXHAUST AIR DAMPERS, MOTOR AND ADJUSTABLE ENTHALPY CONTROLLER MOUNTED IN THE OUTSIDE AIR STREAM OF EACH UNIT. AN ENTHALPY CONTROLLER SHALL BE PROVIDED TO SENSE THE DRY BULB TEMPERATURE AND RELATIVE HUMIDITY OF THE OUTSIDE AIR FOR USE IN THE COOLING CYCLE. THE ENTHALPY CONTROLLER SHALL PREVENT THE COMPRESSOR OPERATION WHEN THE OUTSIDE AIR AND HUMIDITY CAN SATISFY THE COOLING LOAD. THE OUTSIDE AND RELIEF AIR DAMPER MOTORS SHALL BE OF THE MODULATING SPRING TYPE TO CLOSE WHENEVER THE UNIT IS IN UNOCCUPIED MODE. SECTION 15990 -TESTING, ADJUSTING AND BALANCING A. REL ATED WORK 1. HYDRONIC PIPING: SECTION 15510 2. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 B. GENERAL REQUIREMENTS 1. TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE MADE BY A SEPARATE AND INDEPENDENT CONTRACTOR WHO IS CURRENTLY A LICENSED ASSOCIATED AIR BALANCING COUNCIL �AABC) OR A NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB) BALANCING CONTRACTOR. Ivo OTTHER BALANCE REPORTS SHALL BE ACCEPTED OR REVIEWED. ALL BALANCING WORK SHALL BE DONE IN ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR THE TESTING AND BALANCING SHALL BE INCLUDED IN THE MECHANICAL CONTRACTORS BID. 2. ALL TESTING, ADJUSTING AND BALANCING AND REPORTS MUST BE COMPLETED AND SUBMITTED TO THE ENGINEER PRIOR TO THE FINAL ACCEPTANCE OF THE SYSTEMS. 3. THE MECHANICAL CONTRACTOR SHALL BE PRESENT FOR THE AIR BALANCE TO VERIFY ACCESSIBILITY TO ALL DEVICES, VERIFY ALL OPERATING SEQUENCES AND INSTALL NEW FILTERS PACE WITH THE OUTSIIDE AIR DAMPERSBIN�THE MINIMUM OPOSITION,AIUNBLESSNNOTED OT ERWISE. 4. AIR AND WATER QUANTITIES SHALL BE BALANCED TO WITHIN (+ -) TEN PERCENT (10%) OF THE INDICATED QUANTITY AS SHOWN AND CALLED FOR ON THE DRAWINGS. ANY R'QUIRED CHANGES IN SHEAVES BELTS, PULLEYS OR THE ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RATES SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR AT NO ADDITIONAL COMPENSATION TO THE OWNER. 5. THE BALANCE REPORT SHALL BE ON THE AABC NATIONAL STANDARD REPORT FORMS OR THE NEBB CERTIFIED REPORT FORMS AS PUBLISHED IN THEIR MOST CURRENT EDITIONS HND SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION: (WHERE APPLICABLE) A. AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF SEPARATE AND INDEPENDENT BALANCING CONTRACTOR. B. A COPY OF A CERTIFICATE OF CONFORMANCE WITH NATIONAL STANDARDS FOR THIS PROJECT. C. INSTRUMENTATION LIST WITH LAST CALIBRATION DATES. D. MAKE AND MODEL NUMBER OF ALL HVAC EQUIPMENT TESTED. E. CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY PITOT TUBE DUCT TRAVERSE AT EACH UNIT, F. MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR EACH LEG. G. MOTOR AND FAN RPMS, SHEAVE SIZES, AND BELT SIZES, H. OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AND VOLUMES SHALL BE MEASURED AT FULL COOLING WITH MINIMUM OUTSIDE AIR. RETURN AND RELIEF SHALL BE BALANCED AND MEASUREMENTS RECORDED BY PITOT DUCT TRAVERSE AT FULL ECONOMIZER AND POWER EXHAUST. I. WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE AND PRESSURE READINGS. J. MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT. K. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHEN DUCTED). 6. ALL CONTROL SEQUENCES SHALL BE TESTED (INTERLOCKED EQUIPMENT, SMOKE DETECTORS, SMOKE EVACUATION, ECONOMIZER, ETC.) AND OPERATING STATUS RECORDED IN THE REPORT. 7. THREE (3) COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED TO THE ENGINEER FOR AP ROVAL. THE OWNER OR ARCHITECT SHALL RETURN ONE (_1) APPROVED BALANCE REPORT TO THE MECHANICAL CONTRACTOR. THIS BALANCE REPORTT SHALL APPEAR IN THE OPERATIONS MANUAL. 8. THE BALANCING CONTRACTOR SHALL MAK A RETURN INSPECTION OF THE SYSTEM DURING THE NEXT SEASON (HEATING OR COOLING CYCLE. END OF SECTION 15990 FROST ENGINEERS 920 N. Shadeland Ave., Suite G -I IA Indianapolis, Indiana 46219 Phone 317.359.0901 Fax 317.359.0902 mfrost@frostengineers.,6om Seal ,`` %J111Jtllf,11�� ��,,, P, S. F,q� ' ��� G 1 S7*tk s%' iii �� No. �� 2 * * :60910220: CC = .. CTATC nC _ ft Revision Project No. DD04001 Date 4-13-04 Scale NO SCALE ---- �. Checked By MSF ,''; I I_� =_i_ rfl _ __ �- ; � _ 1-1 �.�,' i� - (�i F_ _ -_ L�_� \ ~i )__ ,_T_I - ,:. - - (�1. =1. �-- ->, ==- r. - l.% �; --- Seal ,`` %J111Jtllf,11�� ��,,, P, S. F,q� ' ��� G 1 S7*tk s%' iii �� No. �� 2 * * :60910220: CC = .. CTATC nC _ ft Revision Project No. DD04001 Date 4-13-04 Scale NO SCALE Drawn By MSF Checked By MSF 9rtA T k MECHAMCAL 3PECIRCATIONS OhmW� MO FROST ENGINEERS 920 N. Shadeland Ave., Suite G-11 A Indianapolis, Indiana 46219 Phone 317.359.0901 Fax 317.359.0902 mfrost@frostengineers.com 1 V � RG 1 r G 10 1000 r P 0 OFFICE 325 >: 10 10 12 ° x SDBD -1 W 10"91 r = 325 CFM o o x BD BD N coD CL 325 CFM x 0 s ( � PQ ® w RG -1 U1 w T ;;Ow LL U w LLZ A 0� HEAT PUMP O HEAT PUMP EXISTING 42,000 BTUH rw 0 N EXISTING 28,000 BTUH 00 CL " MECHANICAL PLAN Wco M SCALE: ,/ MECHANICAL PLAN — DEMO S L : 4" = 1'-0" >- " Z a UJ LU SCALE: 1/4" = 1'-0"he Z 0 NOTES: OREMOVE DUCT WORK TO THIS POINT ORELOCATE EXISTING THERMOSTAT A.) METALLIC FLEXIBLE DUCTWORK SHALL BE ATTACHED USING A MINIMUM OF THREE (3) #8 SHEET METAL SCREWS EQUALLY SPACED AROUND THE DUCTWORK CIRCUMFERENCE. DUCTWORK LARGER THAN 12" SHALL HAVE A MINIMUM OF FIVE (5) 18 SHEET METAL SCREWS. SCREWS SHALL BE LOCATED AT LEAST 1/2" FROM THE DUCTWORK END. B.) NON-METALLIC FLEXIBLE DUCTWORK SHALL BE SECURED TO THE SLEEVE OR COLLAR USING A DRAW BAND. IF THE DUCTWORK COLLAR EXCEEDS 12". THE DRAW BAND MUST BE POSRIONED BEHIND A BEAD ON THE METAL COLLAR. C.) INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY -FABRICATED DUCTWORK SHALL BE FITTED OVER THE CORE CONNECTION AND SHALL BE SUPPLEMENTALLY SECURED WITH A DRAW BAND. D.) FLEXIBLE DUCTWORK SEALING SHALL BE A CLASS "B" SEAL FOR LOW PRESSURE DUCTWORK. E.) SUPPORT SYSTEM SHALL. NOT DAMAGE OR CAUSE OUT OF ROUND SHAPE. F.) ALL DUCTWORK SHALL BE PROVIDED WITH SEISMIC RESTRAINTS WHERE REQUIRED BY CODE OR THE LANDLORD. REFER TO THE "SEISMIC RESTRAINT MANUAL: GUIDELINES FOR MECHANICAL SYSTEMS DATED 1991. AS PUBLISHED BY THE SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC. FOR REQUIREMENTS. G.) REFER TO MECHANICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION. SPIN -IN FITTING, BELLMOUTH WHERE POSSIBLE. INSULATED FLEXIBLE DUCTWORK. MAXIMUM 3'-0" LENGTH AND NO 90' BENDS. SUPPLY AIR DIFFUSER COLLAR WITH VOLUME DAMPER AND LOCK 12" MINIMUM INSULATED FLEXIBLE DUCTWORK SQUARE TO ROUND FITTING BY DIFFUSER MANUFACTURER. REFER TO DIFFUSER, REGISTER AND GRILLE SCHEDULE FOR PROVIDED ACCESSORIES. CEILING DIFFUSER, REGISTER AND GRILLE SCHEDULE TAG NO. PATTERN NECK SIZE FACE SIZE MODULE SIZE FRAME STYLE MATERIAL FINISH CFM RANGE ACCESSORIES MANUFACTURER MODEL NO. NOTES RG -1 - 240X24" 24"X24" - TYPEI3 ALUMINUM WHITE 0 - 1,500 - TITUS 50 F 2 SD -1 T -4 -WAY 10"o 24"X24" 24"X24" TYPE ALUMINUM WHITE 250 - 400 - TTAUS SA - NOTES: 1. REFER TO MECHANICAL DRAWINGS FOR DIFFUSER DISCHARGE ARRANGEMENT PATTERN. 2. 1" X 1" X 1" GRID SIZE Seal *. No. w � :60910220: STATE OF ;i F ��'' �h!0 I ANS•' �� ��: Revision Project No. I DD04001 Date 1 4-13-04 Scale 1/4 n = 1 #-0" Drawn By MSF Checked By MSF Sheet Title MECHANICAL PLANS Sheet No. M1 SECTION 16010 - BASIC ELECTRICAL REQUIREMENTS A. DEFINITIONS ANO TERMS 1. THE WORD "OWNER" SHALL MEAN ANY REPRESENTATIVE OF HIS PARTY DULY AUTHORIZED TO ACT IN HIS BEHALF IN THE EXECUTION OF ANY WORK. 2. THE WORD "CONTRACTOR" SHALL MEAN THE PERSON, FIRM OR CORPORATION ENTERING INTO A CONTRACT OR AGREEMENT WITH THE OWNER TO CONSTRUCT AND COMPLETE THE WORK AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN. 3. THE WORD "ARCHITECT OR ENGINEER" SHALL MEAN REPRESENTATIVES THEIR REPRESENTATIVES ACTING AS THE OWNER APPOINTED AGE 4. THE WORD "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION AND SIMILAR SUBSEQUENT REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND CALLED ON THE DRAWINGS AND SPECIFIED HEREIN. 5. THE WORD "INSTALL" SHALL MEAN OPERATIONS AT THE PROJECT SITE, INCLUDING, BUT NOT LIMITED TO, UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND ON THE DRAWINGS AND SPECIFIED HEREIN. 6. THE TERM "PROVIDED" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED" BY THIS CONTRACTOR WITH THE EXCEPTION WHERE ITEMS ARE PROVIDED BY THE OWNER" WHICH MEANS "FURNISHED ONLY" AND INSTALLED BY THIS CONTRACTOR, UNLESS NOTED OTHERWISE. REFER TO THE RESPONSIBILITY SCHEDULES FOR ADDITIONAL INFORMATION. B. SUMMARY OF WORK 1. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES NECESSARY FOR AND REASONABLY IMPLIED, AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR ALL INSTALLED SYSTEMS AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS. THESE CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING: A. A COMPLETE ELECTRICAL DISTRIBUTION SYSTEM INCLUDING THE INSTALLATION OF PANELBOARDS, SAFETY AND DISCONNECT SWITCHES, MOTOR STARTERS, LIGHTING CONTACTORS AND TRANSFORMER. IT IS THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INCLUDE IN HIS BID THE NECESSARY SERVICE EQUIPMENT OR TO OBTAIN SERVICE FROM THE LOCAL UTILITY COMPANY. THIS CONTRACTOR SHALL ALSO INCLUDE IN THE BID ALL NECESSARY MATERIALS REQUIRED TO COMPLETE THE SYSTEM INCLUDING, BUT NOT LIMITED TO, FEEDERS, BRANCH CIRCUITS, JUNC_i ION BOXES, OUTLET BOXES, WIRING DEVICES, COVERPLATES, CONDUITS, ETC. B. METERING AND CURRENT TRANSFORMERS AS REQUIRED BY THE DRAWINGS OR SPECIFIED HEREIN, THE UTILITY COMPANY REGULATIONS. C. THE WIRING OF MECHANICAL EQUIPMENT AS OUTLINED ON THE DRAWINGS OR SPECIFIED HEREIN. WORK SHALL INCLUDE ALL STARTERS, DISCONNECTS, AND POWER WIRING OF MECHANICAL EQUIPMENT EXCEPT UNLESS NOTED OTHERWISE. ALL LOW VOLTAGE (24 VOLT) TEMPERATURE CONTROL WIRING SHALL BE BY THE MECHANICAL CONTRACTOR UNLESS NOTED OTHERWISE. D. THE INSTALLATION OF LIGHT FIXTURES AND LAMPS AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN, INCLUDING ALL DEVICES, EQUIPMENT, ETC., REQUIRED FOR MOUNTING. E. A CONDUIT SYSTEMFOR TELEPHONE/DATA INCLUDING THE TERMINAL BOARD, BRANCH CONDUITS, OUTLET BOXES, PULL WIRES, GROUND CONDUCTORS, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. F. A COMPLETE EMERGENCY AND EXIT LIGHTING SYSTEM AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. G. TEMPORARY SERVICE AS SPECIFIED HEREIN AND ITS REMOVAL. H. ALL FINAL CONNECTIONS TO SIGNS, LIGHTING, OWNER PROVIDED EQUIPMENT, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. I. THE INSTALLATION AND WIRING OF SPEAKERS, CONDUIT, ETC., FOR A SOUND SYSTEM AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. J. ALL SMOKE/FIRE ALARM WIRING, DEVICES, CONDUITS, ETC., AS REQUIRED TO MEET ALL FEDERAL, STATE AND LOCAL APPLICABLE CODES AND INSURANCE AND FIRE DEPARTMENT REQUIREMENTS AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. K. THE INSTALLATION OF CONDUITS STUBBED ABOVE THE CEILING FOR HVAC AND/OR LIGHTING CONTROL PANELS AND ANY ADDITIONAL CONDUIT FOR HVAC EQUIPMENT CONTROL WIRING WHERE PLENUM RATED CABLES ARE NOT PERMITTED. 2. WORK NOT INCLUDED OR TO BE PROVIDED BY THIS CONTRACTOR SHALL BE AS FOLLOWS: A. LOW VOLTAGE (24 VOLT) TEMPERATURE CONTROL WIRING FOR HVAC EQUIPMENT. B. TELEPHONE DEVICES AND WIRING UNLESS NOTED OTHERWISE ON THE DRAWINGS. C. DATA LINE WIRING. C. GENERAL REQUIREMENTS 1. THIS CONTRACTOR SHALL VERIFY THE EXTENT OF ALL EXISTING CONDITIONS, UTILITY CONNECTION POINTS, EQUIPMENT PROVIDED BY OTHERS, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS BY VISITING THE SITE PRIOR TO BIDDING DOES NOT RELIEVE THIS CONTRACTOR OF RESPONSIBILITY IN WORK OR WORKMANSHIP. 2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK, AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THIS CONTRACT. 3. ALL WORK BY THIS CONTRACTOR SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE OF THE EQUIPMENT AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES. 4. ALL ROOF CUTTING, PATCHING AND FLASHING SHALL BE BY THE OWNER'S ROOFING CONTRACTOR OR OWNER'S APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE, COORDINATE ALL ROOF PENETRATIONS, 5. THIS CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL OR SUPPORTS TO SUPPORT ANY INSTALLED EQUIPMENT AS SHOWN AND CALLED FOR ON THE DRAWINGS OR IN THE SPECIFICATIONS. THIS CONTRACTOR SHALL COORDINATE ALL ADDITIONAL STEEL OR SUPPORT LOCATIONS WITH THE OWNER PRIOR TO BIDDING AND INSTALLATION. 6. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF OF THE FLOOR FOR ALL INSTALLED CONDUIT, SLEEVES, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. COORDINATE ALL FLOOR CUTS WITH THE OWNER. CUTTING AND PATCHING SHALL BE HELD TO A MINIMUM. 7. ALL SWITCH GEAR, CIRCUIT BREAKERS AND DISCONNECTS IN SWITCH GEAR, PANELBOARDS, TRANSFORMERS, TIME CLOCKS, THERMAL OVERLOAD FAN SWITCHES, EQUIPMENT CONTROL SWITCHES, SAFETY SWITCHES, MOTOR STARTERS, AND SIMILAR ITEMS SHALL BE IDENTIFIED BY NAME, FUNCTION, AND/OR CONTROL. N NAMEPLATES SHALL BE AT LEAST 1" X 3" WITH CHARACTERS NOT LESS THAN 1/4". THEY SHALL BE MADE UP OF PLASTIC - LAMINATED TAGS AND CHARACTERS ENGRAVED TO ENGRAVER'S STANDARD THICKNESS AND LETTER STYLE WITH WHITE CORE AND BLACK BACKGROUND. NAMEPLATES SHALL BE FASTENED WITH POP RIVETS OR SCREWS. 8. PROVIDE TYPED DIRECTORIES IN PANELBOARDS TO DEPICT ACTUAL EQUIPMENT CONNECTED TO INDIVIDUAL BREAKERS/SWITCHES. D. CODES, FEES AND MISCELLANEOUS COSTS 1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, REQUIREMENTS AND UTILITY COMPANY REGULATIONS. 2. IN CASES OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND THE CONTRACT DOCUMENTS, THE MOST STRINGENT SHALL GOVERN. THIS CONTRACTOR SHALL PROMPTLY NOTIFY THE ENGINEER IN WRITING OF ANY SUCH DIFFERENCE. 3. NON-COMPLIANCE: SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE BUILDING CODES, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS OR THE CONTRACT DOCUMENTS, THIS CONTRACTOR SHALL BEAR ALL COSTS ARISING FOR THE CORRECTION OF NON -COMPLYING ITEMS. 4. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL FEDERAL AND STATE LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. THOSE REQUIREMENTS ARE TO BE CONSIDERED A MINIMUM AND ARE TO BE EXCEEDED WHEN SO INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES AND STANDARDS AND ANY CHANGES OR MODIFICATIONS TO THE DRAWINGS OR SPECIFICATIONS AS REQUIRED BY THE CODES SHALL BE INCLUDED IN THE BID. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THE CONTRACTOR FOR FAILURE OF CODE INQUIRY OR COMPLIANCE. 5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PAYMENT OF ALL FEES, NECESSARY DRAWINGS AND ARRANGING AND PAYING FOR ALL INSPECTIONS, TESTS, ETC., WHICH MAY BE REQUIRED BY ANY AUTHORITY OR UTILITY COMPANY IN CONNECTION WITH THE FURNISHING OR INSTALLATION OF ANY OF HIS RESPECTIVE WORK. E. WORK AND -WORKMANSHIP 1. ALL MATERIALS AND EQUIPMENT SHALL BE OF THE HIGHEST QUALITY IN EVERY RESPECT. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, OF THE LATEST DESIGN AND FREE OF DEFECTS. 2. WORKMANSHIP SHALL BE BY SKILLED WORKMEN OF HIGHEST STANDARD IN STRICT ACCORDANCE WITH ALL APPLICABLE MANUFACTURERS PRINTED SPECIFICATIONS, PERFORMED UNDER SUPERVISION OF COMPETENT FOREMAN AT ALL TIMES. 3. THE OWNER AND THE ARCHITECT HAVE FULL POWER TO CONDEMN OR REJECT ANY WORK, MATERIALS OR EQUIPMENT NOT IN ACCORDANCE WITH THESE SPECIFICATIONS AND DRAWINGS OR ARE NOT IN CONFORMANCE WITH THE MANUFACTURES SPECIFICATIONS OR DRAWINGS WHICH WERE APPROVED BY THE OWNER OR ARCHITECT. 4. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE REMOVED AND REPLACED TO THE SATISFACTION OF THE OWNER OR ARCHITECT AT THIS CONTRACTORS EXPENSE. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE SO STATED IN WRITING BY THE OWNER OR THE ARCHITECT. 5. SUCH DECISIONS AS THE OWNER OR THE ARCHITECT MAY MAKE WITH RESPECT TO QUESTIONS CONCERNING THE QUALITY, FITNESS OF MATERIALS, EQUIPMENT AND WORKMANSHIP SHALL BE BINDING UPON THE PARTIES THERETO, F. DEVIATIONS FROM DRAWINGS 1. THE DRAWINGS SHOW THE INTENDED ARRANGEMENT OF ALL CONDUITS, LIGHT FIXTURES, PANELBOARDS, EQUIPMENT AND APPURTENANCES. THEY SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT. 2. THIS CONTRACTOR SHALL INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND SHALL PROVIDE ANY FITTINGS, OFFSETS AND ACCESSORIES REQUIRED TO ACCOMMODATE SAID CONDITIONS IN THE BID PROPOSAL. 3. WHERE TRADE NAMES AND MANUFACTURES ARE USED ON THE DRAWINGS OR SPECIFIED HEREIN, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURES CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY THE OWNER OR THE ENGINEER PRIOR THROUGH SHOP DRAWING OR SUBMITTAL PROCESS, TO ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THIS CONTRACTORS EXPENSE. 4. THE DRAWINGS INDICATE AN INSTALLED SYSTEM BASED UPON SELECTED MANUFACTURERS OF EQUIPMENT, ELECTRICAL SERVICES, SIZE, CONFIGURATIONS, ETC., ARE CONSISTENT WITH THE MANUFACTURER'S RECOMMENDATIONS. OTHER MANUFACTURERS ARE ENCOURAGED TO FURNISH EQUIPMENT FOR THIS PROJECT; HOWEVER, IT SHALL BE THIS CONTRACTORS RESPONSIBILITY TO ASSURE THAT THE EQUIPMENT IS CONSISTENT WITH THE DESIGN BASE. NO ADDITIONAL COMPENSATION SHALL BE AWARDED FOR REVISIONS, MODIFICATIONS, ETC., TO ELECTRICAL SERVICES, WIRING, BREAKERS, SPACE, CLEARANCE, CONDUIT, PANELBOARDS, ETC., REQUIRED BY OTHER MANUFACTURES. 5. THE LOCATION OF OUTLETS, PANELBOARDS, ELECTRICAL EQUIPMENT, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS IS APPROXIMATE AND THE OWNER OR THE LANDLORD SHALL HAVE THE RIGHT TO RELOCATE ANY SAID EQUIPMENT, RECEPTACLES, LIGHT FIXTURES, ETC., UPON THEIR REQUEST AT NO ADDITIONAL COMPENSATION TO THIS CONTRACTOR. G. HANGERS AND _SUPPORTS 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, WIRE, UNISTRUT, C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK. 2. HANGERS AND SUPPORTS SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE OR MASONRY, BUT NOT TO OR FROM OTHER CONDUIT, PIPING, EQUIPMENT, DUCTWORK, SOFFIT, NEUTRAL PIERS, PIPING DUCTWORK, METAL ROOF DECK, LATERAL BRACING, BRIDGING, OR CONDUIT. HANGERS SHALL BE ATTACHED TO THE UPPER CHORD OF THE BAR JOIST. HANGING FROM THE METAL DECK IS NOT PERMITTED. WHERE INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT CONDUIT, THIS CONTRACTOR SHALL INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS DOORS TO FIRE DAMPERS, VALVES, JUNCTION BOXES, ACCESS DOORS, EQUIPMENT, ETC. HANGER TYPES AND INSTALLATION METHODS SHALL BE SUBJECT TO ALL APPLICABLE CODES. H. OCCUPATIONAL SAFETY AND HEALTH ACT 1. ALL WORK SHALL BE COMPLY WITH THE CURRENT REQUIREMENTS OF THE U.S. DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, ENTITLED OCCUPATIONAL SAFETY AND HEALTH STANDARDS; NATIONAL CONSENSUS STANDARDS AND ESTABLISHED FEDERAL STANDARDS. I. COORDINATION BETWEEN CONTRACTORS 1. BEFORE THE COMMENCEMENT OF ANY WORK, THIS CONTRACTOR SHALL EXAMINE ALL THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS COMPONENTS OF THE INSTALLED SYSTEMS, MATERIALS, CONDUIT, EQUIPMENT, ETC., WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES AND CONFLICTS. 2. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO LEAVE THE REQUIRED, NECESSARY ROOM FOR OTHER TRADES. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE TO COORDINATE WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES, CONFLICTS, RELOCATION OF PANELBOARDS, CONDUIT, EQUIPMENT, ETC., FOUND ENCROACHING ON SPACE REQUIRED BY OTHERS. 3. THIS CONTRACTOR SHALL PROVIDE COMPLETE INFORMATION AND COOPERATION TO THE OTHER CONTRACTORS AND TRADES PERTAINING TO HIS WORK TO ACCOMPLISH COORDINATION OF THE COMPLETED PROJECT. J. EQUIPMENT DRAWINGS 1. THIS CONTRACTOR SHALL PROVIDE EQUIPMENT DRAWINGS OF PROVIDED EQUIPMENT AS SPECIFIED HEREIN. 2. THE FOLLOWING ITEMS ARE A MINIMUM REQUIREMENT FOR EACH EQUIPMENT DRAWING SUBMITTAL: A. SHEET SIZE 8-1/2" X 1 1 ". B. MANUFACTURE'S STANDARD SCHEMATIC DRAWINGS: 1. MODIFY DRAWINGS TO DELETE INFORMATION THAT IS NOT APPLICABLE TO APPLICABLE TO THIS PROJECT. 2. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION C. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES, PERFORMANCE CHARTS, ILLUSTRATIONS AND OTHER STANDARD DESCRIPTIVE DATA. 1, CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS, REQUIRED. 2. SHOW EQUIPMENT DIMENSIONS AND MAINTENANCE OR CONSTRUCTION CLEARANCES 3. SHOW PERFORMANCE CHARACTERISTICS AND CAPABILITIES. 4. SHOW WIRING DIAGRAMS AND CONTROLS. 5. MATERIAL AND SAFETY DATA SHEETS. 6. THE FULL MANUFACTURE'S MODEL NUMBER OF EACH ITEM. 7. IDENTIFICATION OF COLOR OR FINISHES. 8. THIS CONTRACTOR'S STAMP, SIGNATURE AND DATA SHALL BE AFFIXED TO EACH 3. COPIES OF THE EQUIPMENT DRAWINGS AND ALL OTHER RELATED INFORMATION MUST APPEAR IN THE OPERATIONS MANUAL LEFT ON SITE AFTER PROJECT COMPLETION. K. RECORD DRAWINGS 1. DURING CONSTRUCTION THIS CONTRACTOR SHALL MAINTAIN A COMPLETE AND LEGIBLE SET OF DRAWINGS SHOWING CHANGES AND DEVIATIONS BETWEEN ACTUAL CONSTRUCTION AND THE ENGINEER'S DRAWINGS. 2. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE, THIS CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO THE DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT WITH THIS CONTRACTOR'S STAMP AND SIGNATURE THEREON. THIS COPY OF THE RECORD DRAWINGS SHALL BE PLACED IN A DRAWING TUBE AND MARKED "RECORD DRAWINGS - DO NOT REMOVE FROM PREMISES" AND SHALL BE KEPT WITH THE OPERATIONS MANUAL, L. OPERATIONS MANUAL 1. ONE COPY OF AN OPERATIONS AND MAINTENANCE MANUAL FOR ALL EQUIPMENT FURNISHED (3) RING BINDER. SHALL BE COLLECTED AND INSERTED IN A LABELED THREE INCH (3") THREE 2. OPERATIONS AND MAINTENANCE MANUALS SHALL BE ASSEMBLED AS FOLLOWS: A. SECTION 1 1. TITLE OF PROJECT 2. LOCATION OF PROJECT 3. NAME AND ADDRESS OF OWNER 4. NAME AND ADDRESS OF ENGINEER 5. NAME AND ADDRESS OF THIS CONTRACTOR. B. SECTION 2 1. SHOP DRAWINGS OF ALL APPROVED EQUIPMENT, C. SECTION 3 1. A LISTING OF ALL EQUIPMENT WARRANTIES INDICATING THE EQUIPMENT MODEL NUMBER, SERIAL NUMBER, START AND ENDING DATE OF THE WARRANTY, ETC. 3. EACH SECTION SHALL BE SEPARATED BY A PASTEBOARD TABBED DIVIDER. 4. ALL INFORMATION SHALL BE ARRANGED IN AS MANY BINDERS AS NECESSARY. 5. OPERATION AND MAINTENANCE MANUAL AND DRAWING TUBE SHALL BE LEFT WITH THE STORE MANAGER. M. TESTS, ADJUSTMENTS, INSTRUCTIONS AND CLEANING 1. ALL CONNECTIONS AT PANELS AND SWITCHES ARE TO BE MADE, ALL SPICES COMPLETE, ALL FUSES IN PLACE, AND ALL CIRCUITS CONTINUOUS FROM POINT OF SERVICE CONNECTION TO ITS FINAL DESTINATION, AND ALL COVERS AND PLATES INSTALLED PRIOR TO THE TIME OF FINAL INSPECTION BY THE OWNER'S CONSTRUCTION MANAGER. 2. TEST FOR GROUNDS, SHORT CIRCUITS AND PROPER FUNCTION OF ALL EQUIPMENT AFTER INSTALLATION IS COMPLETE. FAULTS IN THE INSTALLATION SHALL BE CORRECTED AT THIS CONTRACTORS EXPENSE. 3. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL BE TESTED AND PROVED FREE OF UNWANTED GROUNDS AND OTHER DEFECTS. 4. ALL OVERLOAD DEVICES, INCLUDING EQUIPMENT, FURNISHED UNDER OTHER CONTRACTS, SHALL BE SET AND ADJUSTED TO SUIT THE LOAD CONDITIONS. 5. TEST AND MAKE CORRECTIONS/ADJUSTMENTS FOR PHASE BALANCING. 6. AFTER ALL TESTS AND ADJUSTMENTS HAVE BEEN MADE, THIS CONTRACTOR SHALL FULLY INSTRUCT THE REPRESENTATIVES OF THE OWNER IN ALL DETAILS OF OPERATION AND MAINTENANCE OF THE EQUIPMENT INSTALLED UNDER THIS CONTRACT. INSTRUCTION SHALL BE FURNISHED UNTIL THE OWNER IS SATISFIED. FURNISH THE OWNER WITH TWO INSTRUCTION MANUALS ON EACH SYSTEM. INSTRUCTION MANUALS SHALL CONTAIN ALL SHOP DRAWINGS, MANUFACTURERS INSTALLATION AND OPERATION INSTRUCTION, GUARANTEES, MAINTENANCE SCHEDULE, ETC. 7. AT THE END OF THE PROJECT, THIS CONTRACTOR SHALL CLEAN ALL EQUIPMENT, INCLUDING LIGHT FIXTURES, TO THE SATISFACTION OF THE OWNER. ALL DUST, DIRT, DEBRIS, AND FOREIGN MATTER SHALL BE REMOVED FROM ALL EQUIPMENT. N. INSPECTIONS, FINAL REPORTS AND GUARANTEE 1. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL INFORM THE LOCAL AND STATE AUTHORITIES AND THE OWNER TO ARRANGE FOR FINAL INSPECTIONS OF THIS WORK. 2. THIS CONTRACTOR SHALL FURNISH TO THE OWNER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT THE COMPLETION OF THIS PROJECT. 3. THIS CONTRACTOR SHALL SUBMIT TO THE OWNER UPON COMPLETION OF THIS WORK A LETTER CERTIFYING THAT THIS WORK IS IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. 4. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT, WORK, ETC., UNDER THIS CONTRACT FOR ONE (1) YEAR AFTER THE ACCEPTANCE OF ALL SYSTEMS INSTALLED BY THIS CONTRACTOR UNDER THIS CONTRACT. THIS CONTRACTOR SHALL MAKE GOOD, REPAIR OR REPLACE AT THIS CONTRACTORS OWN EXPENSE, ANY DEFECTIVE WORK, MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED FORM THE DATE OF ACCEPTANCE, IN WRITING. EXTENDED WARRANTIES ARE AS SPECIFIED WITH THE INDIVIDUAL EQUIPMENT, 5. UNDER THE ONE (1) YEAR GUARANTEE PERIOD THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE PREMISES CAUSED BY DEFECTS IN ANY WORKMANSHIP OR ANY EQUIPMENT FURNISHES AND/OR INSTALLED BY THIS CONTRACTOR. 0. SLEEVES 1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND TWO INCHES (2") ABOVE THE FLOOR. 2. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM. P. FIRE STOPPING 1. ALL OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS FOR CONDUITS SHALL BE FIRE SEALED IN ACCORDANCE WITH NFPA 101 WITH CALCIUM SILICATE, SILICONE "RTV" FOAM, 3M FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE RATING. PROVIDE SLEEVES AS REQUIRED BY ALL APPLICABLE CODES OR LANDLORD REQUIREMENTS. END OF SECTION 16010 SECTION 16111 - CONDUIT A. THIS CONTRACTOR SHALL PROVIDE ALL CONDUITS SERVING ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO, LIGHTING, RECEPTACLES, HEATING, AIR CONDITIONING, PLUMBING EQUIPMENT, TELEPHONE, SPEAKERS, AND ELECTRICAL EQUIPMENT. B. ALL CONDUITS SHALL BE GALVANIZED IMC OR MC UNLESS OTHERWISE SPECIFIED IN SPECIFICATIONS OR ON DRAWINGS. ALL CONDUIT IS TO BE UL LABELED. MC CONNECTORS SHALL BE STEEL COMPRESSION OR SET SCREW TYPE. CONDUIT UNDER SLAB ON GRADE SHALL BE RIGID STEEL. C. MINIMUM SIZES OF CONDUIT SHALL BE 1/2" FOR INDIVIDUAL LIGHTING FIXTURES CONNECTIONS OR TO INDIVIDUAL LIGHT SWITCHES (IF ACCEPTABLE BY THE LANDLORD AND LOCAL CODE OFFICIALS) AND 3/4" FOR ALL OTHER LOCATIONS, HVAC CONTROL WIRING, SPEAKER WIRING AND FIRE ALARM WIRING SHALL BE RUN IN CONDUIT AND SHALL BE A MINIMUM OF 3/4" SIZE, UNLESS NOTED OTHERWISE ON DRAWINGS. ALL IN AND/OR UNDER FLOOR SLAB CONDUIT SHALL BE OF MINIMUM 1 " SIZE. D. SUPPORT ALL CONDUIT, INCLUDING SEISMIC AND SWAY BRACING, IN ACCORDANCE WITH THE N.E.C. AND LOCAL CODES. E. GENERALLY, ALL CONDUIT SHALL BE CONCEALED EXCEPT FOR UNFINISHED AREAS, SUCH AS EQUIPMENT ROOMS. EXPOSED CONDUIT SHALL BE ALLOWED ONLY AS NOTED ON PLAN. PAINTING OF CONDUITS IN FINISHED AREAS, NOTED ON DRAWINGS OR SPECIFICATIONS WILL BY GENERAL CONTRACTOR. F. FLEXIBLE METAL CONDUIT OR MC TYPE CABLE. 1. FLEXIBLE CONDUIT OR MC TYPE CABLE SHALL BE ACCEPTABLE FOR THE FOLLOWING APPLICATIONS ONLY: A. FINAL CONNECTIONS TO MOTORS. B. FINAL CONNECTIONS INTO AND OUT OF THE TRANSFORMER. C. FINAL CONNECTIONS TO VIBRATING EQUIPMENT. D. INTERCONNECTIONS BETWEEN ALL LIGHT FIXTURES. (NOT TO INCLUDE HOME RUN TO PANEL BOARD WHICH MUST BE RIGID.) E. FINAL CONNECTIONS WHERE RIGID CONDUIT IS NOT PRACTICAL. F. IN WALLS (FOR LIGHT SWITCHES AND 120 VOLT POWER RECEPTACLES AND HVAC CONTROL EQUIPMENT. 2. FLEXIBLE METAL CONDUIT OR MC TYPE CABLE MUST BE THE SAME SIZE AS THE IMC OR MC CONDUIT TO WHICH IT IS CONNECTED. BOTH THE FLEXIBLE METAL CONDUIT AND ITS FITTINGS ARE TO BE LISTED FOR GROUNDING. A GREEN GROUNDING CONDUCTOR SHALL BE INSTALLED. ALL CONNECTORS ARE TO BE OF A NEMA APPROVED TYPE. 3. THE USE OF ROMEX, BX, ETC. IS NOT PERMITTED. 4. CONNECTION TO OUTDOOR EQUIPMENT MUST BE WEATHERPROOF, I.E. LIQUIDTIGHT OR SEALTIGHT. 5. MAXIMUM LENGTH OF FLEXIBLE METAL CONDUIT SHALL BE 3'-0", G. PROVED AS A MINIMUM #10 AWG PULL -WIRE IN ALL EMPTY CONDUITS EXCEPT AS NOTED OTHERWISE ON DRAWINGS. H. HOME RUNS AND MAIN CONDUIT RUNS ARE TO BE HELD TIGHT TO STRUCTURE ABOVE OR AS REQUIRED TO ALLOW PROPER SERVICE ACCESS AND OTHER TRADES WORK. CONDUIT MUST BE TRAPEZED TO ALLOW 3 FEET MINIMUM CLEARANCE ABOVE CEILING. 1. ALL CONDUIT SHALL BE RUN PARALLEL OR PERPENDICULAR TO COLUMN LINES. J. ALL CONDUITS MUST BE SIZED PER N.E.C., LOCAL CODES AND LANDLORD REQUIREMENTS. K. PVC CONDUIT SHALL NOT BE PERMITTED. L. CONDUIT SHALL NOT BE INSTALLED IN OR THROUGH ANY DUCTWORK. M. ANCHOR ALL CONDUITS INSTALLED HORIZONTALLY IN STEEL STUDS TO PREVENT VIBRATION. END OF SECTION 16111 SECTION 16120 - WIRING A. CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS SHALL BE COPPER AND THE AWG SIZE AND TYPE AS SHOWN ON DRAWINGS. MINIMUM WIRE SIZE #12. THE CONDUCTORS SHALL BE 600 VOLT INSULATION, TYPE THW, THWN OR THHN. (CONDUIT SIZE BASED ON THHN AND THWN). B. MINIMUM WIRE SIZE - 20 AMP BRANCH CIRCUIT SHALL BE AWG LISTED SIZE PER DISTANCE SHOWN BELOW. DISTANCE SHALL BE MEASURED FROM THE PANELBOARD CIRCUIT BREAKER TO THE FURTHEST OUTLET. 1. J12 LESS THAN 100 FEET 2. 10 BETWEEN 100-150 FEET 3. 8 BETWEEN 150-250 FEET 4. 6 OVER 250 FEET NOTE: THE ELECTRICAL CONTRACTOR MAY SUBMIT VOLTAGE DROP CALCULATIONS OR ACTUAL FIELD READINGS FOR EACH RECEPTACLE CIRCUIT TO THE OWNER FOR APPROVAL OF SMALLER W!RE SIZE THAN THOSE LISTED ABOVE. MAXIMUM VOLTAGE DROP SHALL BE 3% PER N.E.C. C. ON ALL 20 AMP BRANCH CIRCUITS, CONDUCTORS LARGER THAN #10 AWG SHALL BE REDUCED TO #10 AWG WITHIN 10 FEET OF PANEL BOARD AND DEVICE IN JUNCTION BOXES ON RATED TERMINAL STRIPS, D. CONDUCTORS MAY BE STRANDED FOR SIZES #10 AWG AND LARGER. CONDUCTORS SIZE #12 SHALL BE SOLID (NOT STRANDED). E. ALUMINUM CONDUCTORS ARE NOT PERMITTED, EXCEPT AT SERVICE ENTRANCE, WHERE REQUIRED BY LANDLORD. CONDUCTOR CONNECTION MUST BE PER MANUFACTURER'S REQUIREMENTS. F. HVAC CONTROL WIRING SHALL BE 8-#16 MULTI -COLORED CABLE WITH 600 V. INSULATION. G. ALL WIRING AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE SITE IN UNBROKEN PACKAGES. H. ALL WIRING SHALL BE CONDUIT, UNLESS SPECIFICALLY NOTED OTHERWISE (I.E. LOW VOLTAGE, PLENUM RATED WIRE). I. THE USE OF SHARED NEUTRALS IS NOT ALLOWED FOR LIGHTING CIRCUITS, SHARED NEUTRALS FOR POWER CIRCUITS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL CODES. ALL OTHER EQUIPMENT REQUIRING A NEUTRAL CONDUCTOR SHALL HAVE A DEDICATED FULL SIZE NEUTRAL. J. THE USE OF ROMEX, BX, ETC. IS NOT PERMITTED. K. WIRE CONNECTORS SHALL BE EQUAL TO "SCOTCH LOCK" FOR #8 AWG WIRE AND SMALLER AND EQUAL TO T & B "LOCKTIGHT" FOR #6 AWG AND LARGER. L. ALL WIRING TO BE COLOR -CODED AS FOLLOWS: 120/208 VOLT SYSTEM 277/480 VOLT SYSTEM NEUTRAL - WHITE NEUTRAL - GRAY PHASE A OR L1 - BLACK PHASE 1 OR L1 - BROWN PHASE B OR L2 - REO PHASE B OR L2 - ORANGE PHASE C OR L3 - BLUE PHASE C OR L3 - YELLOW GROUND - GREEN GROUND - GREEN M. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED POWER AND CONTROL INTERLOCK FOR ALL FIRE SUPPRESSION SYSTEMS. N. LOW VOLTAGE WIRING FOR SIGNALLING OR CONTROL SYSTEMS OR DEVICES WHICH ARE ENCLOSED IN PARTITIONS, WALLS, OR ANY WAY MADE INACCESSIBLE BY BUILDING CONSTRUCTION SHALL BE ENCASED IN A RACEWAY. THE ABOVE RACEWAY NEED NOT TERMINATE IN A BOX OR FITTING SO LONG AS NORMAL PRECAUTIONS ARE TAKEN TO PROTECT THE CONDUCTORS AGAINST INJURY OR DAMAGE (N.E.C. 725-38B AND 760-28C). THIS ALSO SHALL INCLUDE COAXIAL CABLE ASSEMBLIES (N.E.C. 820-50). 0. HEATING, VENTILATING & AIR CONDITIONING, PLUMBING, AND FIRE PROTECTION WIRING 1.ELECTRICAL CONTRACTOR SHALL REFER TO MECHANICAL DRAWINGS FOR FOR ADDITIONAL ELECTRICAL WORK TO BE INCLUDED IN THIS BID. 2. ELECTRICAL CONTRACTOR SHALL DO ALL POWER WIRING, LINE VOLTAGE WIRING, AND LINE VOLTAGE CONTROL WIRING INDICATED UNDER THE HEATING, VENTILATION AND AIR CONDITIONING, PLUMBING AND FIRE PROTECTION SPECIFICATIONS AND DRAWINGS. THIS CONTRACTOR SHALL ALSO DO ALL INTERCONNECTING LINE VOLTAGE WIRING BETWEEN RELAYS AND SWITCHES AS REQUIRED. 3, ELECTRICAL CONTRACTOR SHALL PROVIDE AS A MINIMUM, ONE (1) CONDUIT STUBBED FROM HVAC AND/OR LIGHTING CONTROL PANEL TO 12" ABOVE CEILING WITH PLASTIC CONDUIT BUSHING TO PREVENT WIRE CHAFFING. 4. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING CONDUIT FOR HVAC CONTROL WIRING WHERE REQUIRED BY CODE TO BE IN CONDUIT. 5. REFER TO MECHANICAL DRAWINGS FOR AVAILABLE SCHEMATIC WIRING DIAGRAMS OF EQUIPMENT. 6. ROUTE ELECTRIC POWER AND CONTROL FOR ROOF MOUNTED HVAC EQUIPMENT THROUGH A SEPARATE ROOF PENETRATION FOR THE ELECTRIC POWER AND CONTROL CONDUITS. DO NOT ROUTE CONDUIT THROUGH HVAC ROOF MOUNTED EQUIPMENT CURB. DO NOT DRILL HOLES IN CONDENSATE PAN OR COMPRESSOR OR CONDENSER SECTION FLOOR. 7. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL SMOKE DETECTORS AS REQUIRED BY ALL APPLICABLE CODES. VERIFY CONNECTION REQUIREMENTS TO THE FIRE ALARM SYSTEM PRIOR TO BIDDING. PROVIDE A RESET/TEST AND ALARM LIGHT FOR ALL INSTALLED SMOKE DETECTORS. VERIFY RESET/TEST AND ALARM LIGHT LOCATION WITH THE OWNER PRIOR TO INSTALLATION. P. GENERAL WIRING REQUIREMENTS 1. ALL EQUIPMENT FURNISHED AND INSTALLED UNDER CONTRACTS OTHER THAN THE ELECTRIC CONTRACT SHALL BE FURNISHED WITH FULL COMPLEMENT OF CONTROL EQUIPMENT AND CONTROL WIRING DIAGRAMS NECESSARY FOR SATISFACTORY OPERATION. 2. THE ELECTRICAL CONTRACTOR SHALL COMPLETE ALL ELECTRICAL CONNECTIONS THROUGH THE DISCONNECT, STARTER AND MOTOR TERMINALS. 3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER ROTATION OF ALL THREE PHASE EQUIPMENT. 4. EQUIPMENT FURNISHED BY OTHERS SHALL BE ROUGHED IN WITH CONDUIT AND BOXES BY MANUFACTURER. INTERNAL WIRING SHALL BE COMPLETED ACCORDING TO THE MANUFACTURER'S SHOP DRAWINGS OF THE EQUIPMENT BY ELECTRICAL CONTRACTOR. THIS CONTRACTOR IS TO WIRE TO ALL LINES VOLTAGE CONTROLS AND CONTROLLERS. END OF SECTION 16120 SECTION 16131 - JUNCTION AND PULL BOXES A. THE PLANS INDICATE ONLY SCHEMATIC ROUTINGS FOR CONDUIT RUNS. THIS CONTRACTOR SHALL PROVIDE ADDITIONAL BOXES WHERE REQUIRED BY FIELD CONDITIONS OR BY CODE. B. BOXES AND COVERS SHALL BE GALVANIZED STEEL OF CODE GAUGE SIZE. C. INSTALL BOXES RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE AND SUPPORTED INDEPENDENT OF THE CONDUIT SYSTEM D. ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION BOXES ABOVE DRYWALL CEILING SHALL BE LIMITED TO LOCATIONS NEAR ACCESS FRAMES USED FOR DIFFUSERS AND RETURN AIR GRILLES OF ACCESS PANELS AS LOCATED ON PLANS. E. JUNCTION AND PULL BOXES MUST BE LABELED WITH CIRCUIT NUMBER IDENTIFICATION AND SYSTEM TYPE ON COVER. END OF SECTION 16131 SECTION 16134 - OUTLET BOXES A. ALL OUTLET BOXES SHALL BE GALVANIZED PRESSED STEEL OF THE STANDARD KNOCKOUT TYPE. NO ROUND OUTLET BOXES SHALL BE PERMITTED, EXCEPT AS SPECIFICALLY NOTES ON DRAWINGS. CONCEALED BOXES SHALL NOT BE LESS THAN 4 INCHES SQUARE AND 1 1/2" DEEP, WITH PLASTIC RINGS, B. ALL KNOCKOUT BOXES, UPON WHICH LIGHTING FIXTURES ARE TO BE INSTALLED, SHALL BE EQUIPPED WITH 3/4" FIXTURE STUDS. C. EXTERIOR BOXES SHALL BE CAST RUST -RESISTING METAL WITH GASKETED COVERS. D. INSTALL BOXES RIGIDLY FROM BUILDING STRUCTURE AND SUPPORT INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE SUITABLE BOX EXTENSIONS TO EXTEND BOXES TO FINISHED FACES OF FLOORS, CEILINGS, WALLS, ETC. ALL OUTLET BOXES TO HAVE SUITABLE BLOCKING BEHIND THEM TO MINIMIZE THE DEFLECTION THAT OCCURS WHEN PLUGGING/.UNPLUGGING INTO THESE DEVICES. E. UNLESS OTHERWISE NOTED ON DRAWINGS OR OTHERWISE REQUIRED BY NATIONAL ELECTRICAL CODE, HANDICAP CODES OR LOCAL CODES, OUTLET HEIGHTS SHALL BE AS FOLLOWS: 1. SWITCH HEIGHT 48" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET. 2. CONVENIENCE OUTLETS A. SALES - HORIZONTALLY IN BASEBOARD BENEATH CABINETS, AS SHOWN ON DRAWINGS, OR AS REQUIRED BY LOCAL CODES. B. NON -SALES - 18" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET. 3. TELEPHONE OUTLETS SHALL BE LOCATED AS NOTED ON DRAWINGS. END OF SECTION 16134 SECTION 16140 - WIRING DEVICES A. THIS CONTRACTOR SHALL FURNISH AND INSTALL SWITCHES AND RECEPTACLES AS SHOWN ON THE DRAWINGS AND AS NECESSARY FOR A COMPLETE INSTALLATION. COLOR OF DEVICES AND PLATES SHALL BE SELECTED BY THE ARCHITECT. THE DEVICES SHALL BE OF THE TYPES AND RATINGS LISTED, OR EQUALS BY ARROW - HART, GENERAL ELECTRIC OR PASS & SEYMOUR. WEATHERPROOF G.F.I. RECEPTACLES SHALL BE INSTALLED WHERE SHOWN ON DRAWINGS OR AS REQUIRED BY CODE. 1. SINGLE POLE SWITCHES: 20 A - 125 V HUBBELL - 1221 2. THREE WAY SWITCHES: 20 A - 125 V HUBBELL - 1223 3. FOUR WAY SWITCHES: 20 A - 125 V HUBBELL - 1224 4. DUPLEX RECEPTACLES: 20 A - 125 V HUBBELL - 5362 5. ISOLATED GROUND RECEPTACLES: 20 A - 125 V HUBBELL - IG5362 6. FLOOR OUTLET BOX: STEEL CITY #841 7. FLOOR OUTLET BRASS COVER: STEEL CITY #P-64-1 OR P -64-D7, ADD "AL" FOR ALUMINUM 8. GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLES: 20 A-125 V HUBBELL-CF5352 9. DIMMERS: LUTRON 10, MOTOR STARTERS: SQUARE D 11. EXHAUST FAN TIMER: MARK TIME 12. LIGHTING TIMERS: PARAGON 7007-0 (24 HOUR - 7 DAY TYPE) B. ALL DEVICE COVERPLATES SHALL BE PASS AND SEYMOUR SERIES "RP" OR EQUAL. END OF SECTION 16140 SECTION 16155 - MOTOR STARTERS A. MANUAL MOTOR STARTERS WITH OVERLOAD PROTECTION MAY BE USED FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REQUIRE AUXILIARY CONTROL. THREE PHASE STARTERS SHALL BE PROVIDED WITH OVERLOAD DEVICE IN EACH PHASE MATCHED TO MOTOR NAMEPLATE RATING. MAGNETIC MOTOR STARTERS SHALL BE ELECTRICALLY HELD (MINIMUM SIZE #1) AND BE USED FOR ALL SINGLE PHASE AND THREE PHASE MOTORS RATED ABOVE 1/2 HP OR THAT REQUIRED AUXILIARY CONTROL, PROVIDE CONTROL DEVICES (AUXILIARY CONTACTS, TRANSFORMERS, ETC.) IN STARTERS AS REQUIRED FOR INTERLOCKS. COORDINATE WITH MECHANICAL CONTRACTORS. COMBINATION STARTERS SHALL CONTAIN FUSIBLE SWITCHES AND ONLY USED WHERE INDICATED ON DRAWINGS. B. MANUFACTURER SHALL BE SQUARE "D" OR EQUAL. END OF SECTION 16155 SECTION 16160 PANELBOARDS A. ALL PANELBOARDS SHALL BE FACTORY ASSEMBLED OF THE BOLTED CIRCUIT BREAKER TYPE WITH SOLID COPPER BUSSING, FULL SIZED COPPER NEUTRAL, 100% GROUND BUSSING, AND OVERALL HINGED/LOCKABLE DOOR. ALL CIRCUIT BREAKERS SHALL BE OF THE QUICK -MAKE AND QUICK -BREAK DESIGN, THERMAL - MAGNETIC TYPE, TRIP FREE AND TRIP -INDICATING. ALL PANELS SHALL BE DEAD FRONT AND FLUSH OR SURFACE MOUNTED AS SHOWN AND SHALL BE FURNISHED WITH A TYPEWRITTEN DIRECTOR CARD OF THE CIRCUITS AND AN ENGRAVED NAMEPLATE. B. CIRCUIT BREAKER PANELBOARDS SHALL HAVE FULL LENGTH NON-TAPERED BUS BARS ARRANGED AND DRILLED FOR SEQUENCE PHASING. C. ALL PANELS SHALL HAVE DOORS FLUSH WITH THE TRIM, EQUIPPED WITH LOCKS, AND KEYED ALIKE. ALL MULTI -POLE BREAKERS SHALL BE COMMON TRIP. D. ALL PANELBOARDS PHASE AMPERAGE SHALL BE BALANCED TO WITHIN 7 PERCENT MAX. TO MIN. REARRANGE NON -LIGHTING BRANCH CIRCUITS AS REQUIRED AND NOTE CHANGES ON RECORD DRAWINGS. LIGHTING PANEL CIRCUIT BREAKERS MUST BE INSTALLED AND WIRED EXACTLY AS SHOWN ON DRAWINGS. E. PANELS SHALL BE AS INDICATED ON THE DRAWINGS. ALL BRANCH CIRCUIT BREAKERS (C/B) SHALL BE RATED 20 AMPERES SINGLE POLE MINIMUM, EXCEPT AS NOTED OR REQUIRED BY LOCAL CODES. F. PROVIDE LOCKOUT CLIPS ON NIGHT LIGHT, TIME CLOCK CONTROLLED, LIFE SAFETY, AND ALL OTHER CIRCUIT BREAKERS WHERE INDICATED ON PANEL SCHEDULE. PROVIDE 5 ADDITIONAL CLIPS TO BE INSTALLED AS DIRECTED BY THE OWNER. G. PROVIDE ONE SPARE 1" CONDUIT FOR EACH SIX SPACES OR SPARE CIRCUIT BREAKERS IN EACH RECESSED MOUNTED PANEL. MINIMUM 1 SPARE CONDUIT PER PANEL. RUN CONDUIT TO A LOCATED JUST ABOVE CEILING. H. ALL CIRCUIT BREAKERS FEEDING LIGHTING LOADS SHALL BE LISTED AND SHALL BE MARKED "SWD" (SWITCHING DUTY). REFER TO ELECTRICAL RISER DIAGRAM AND DRAWINGS FOR ADDITIONAL INFORMATION I. CIRCUIT BREAKERS SERVING HEATING, VENTILATION, AND/OR AIR CONDITIONING (HVAC) EQUIPMENT SHALL BE RATED AND MARKED "HACR", IF FUSING IS NOT PROVIDED AT PIECE OF HVAC EQUIPMENT. FIELD VERIFY EXACT "HACR" BREAKER REQUIREMENTS WITH HVAC EQUIPMENT NAMEPLATE AND MANUFACTURER'S REQUIREMENTS PRIOR TO INSTALLATION. J. IN SERVICE ENTRANCE APPLICATIONS, PANELS, SHALL BEAR THE MANUFACTURER'S LABEL INDICATING THE EQUIPMENT IS RATED FOR SUCH APPLICATION IN ACCORDANCE WITH THE N.E.C. AND AS INDICATED ON DRAWINGS. K. PANELBOARDS MUST BE MOUNTED ON MINIMUM 3/4" A/D PLYWOOD AND PAINED TO A COLOR TO MATCH THE SURROUNDING WALLS OR A COLOR AS REQUIRED BY LOCAL CODE. PLYWOOD SHALL EXTEND 1 FOOT MINIMUM BEYOND EDGE OF EQUIPMENT. L. PANELBOARDS SHALL HAVE A MINIMUM SHORT CIRCUIT CURRENT RATING AND LUG CONNECTIONS AS FOLLOWS: 1. 120/208 VOLT PANELBOARDS: 10,000 A.I.C. 2. 277/480 VOLT PANELBOARDS: 14,000 A.I.C. 3. FUSIBLE DISTRIBUTION PANELBOARDS: 100,000 A.I.C. M. VERIFY ACTUAL A.I.C. SHORT CIRCUIT CURRENT REQUIREMENTS WITH UTILITY COMPANY PRIOR TO ORDERING EQUIPMENT. N. ALL LUG CONNECTIONS TO BE 75"C 0. PANELS SHALL BE MANUFACTURED BY SQUARE "D" OR EQUAL. END OF SECTION 16160 SECTION 16170 - SAFETY AND DISCONNECT SWITCHES A. SAFETY AND DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, QUICK -MAKE, QUICK -BREAK FUSED OR NON -FUSIBLE WITH RATINGS AND SIZES AS NOTED ON PLANS AND REQUIRED BY CODES. B. SWITCHES SHALL BE WEATHERPROOF IN OUTDOOR LOCATIONS OR AS REQUIRED BY LOCAL CODES. C. DISCONNECT SWITCHES THAT ARE INSTALLED AT HEATING, VENTILATING AND AIR CONDITIONING (HVAC) EQUIPMENT SHALL BE FUSED IF NOT PROTECTED WITH A "HACR" BREAKER IN ACCORDANCE WITH THE EQUIPMENT'S NAMEPLATE AND MANUFACTURER'S REQUIREMENTS PER THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES. D. AT SERVICE ENTRANCE, DISCONNECT SHALL BEAR MANUFACTURER'S LABEL INDICATING THE EQUIPMENT IS UL RATED FOR APPLICATION IN ACCORDANCE WITH ALL CODES. E. MANUFACTURER SHALL BE SQUARE "D" OR EQUAL. END OF SECTION 16170 SECTION 16450 - GROUNDING A. PROVIDE COMPLETE WIRED GROUNDING CONDUCTOR SYSTEM, #12 AWG MINIMUM, SIZED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES, THE LANDLORD'S TENANT CRITERIA AND AS NOTED IN THE SPECIFICATIONS AND AS INDICATED ON THE DRAWINGS. B. ALL CONDUIT, INCLUDING FLEXIBLE CONDUIT, SHALL BE GROUNDED WITH A GREEN GROUNDING CONDUCTOR, C. GROUNDING CONNECTIONS MADE TO THE WATER PIPING SYSTEM SHALL BE COORDINATED WITH THE PLUMBING CONTRACTOR AND BONDING JUMPERS SHALL BE INSTALLED PER CODES AND AS INDICATED ON DRAWINGS, D. ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. USE A BONDING JUMPER BETWEEN THE OUTLET BOX AND THE DEVICE GROUNDING TERMINAL. METAL -TO -METAL CONTRACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS NOT ACCEPTABLE AS A BOND FOR EITHER SURFACE MOUNTED BOXES OR FLUSH TYPE BOXES. ALL JUNCTION BOXES, OUTLET BOXES, AND PULL BOXES SHALL BE BONDED TO THE CONDUIT SYSTEM. E. RUN A SEPARATE ISOLATED GROUNDING CONDUCTOR, #12 AWG MINIMUM, IN EACH CONDUIT FEEDING THE HVAC CONTROL PANEL, AND OTHER COMPUTERIZED EQUIPMENT AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS, BOND THE GROUNDING CONDUCTOR TO THE CONDUIT, WHERE ENTERING AND LEAVE THE CONDUIT. THE GROUNDING CONDUCTOR SHALL BE SIZED PER CODE, GREEN COLORED, COPPER WIRE. F. ALL ENCLOSURES AND NON-CURRENT CARRYING METAL PARTS ARE TO BE GROUNDED. CONDUIT SYSTEM IS TO BE ELECTRICALLY CONTINUOUS. ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES. WHERE ENCLOSURES AND NON-CURRENT CARRYING METAL PARTS ARE ISOLATED FROM THE CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED CLAMPS. ALL GROUND CLAMPS SHALL BE "PENN -UNION" OR EQUAL, SIMILAR TO "GPL" TYPE. END OF SECTION 16450 SECTION 16477 - FUSES A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY FUSES FOR A COMPLETE INSTALLATION. B. FUSES FOR FEEDER CIRCUITS AND PANELBOARDS SHALL BE U.L. CLASS RKI FAST - ACTING TYPE. C. FUSES FOR MOTOR OVERCURRENT AND TRANSFORMER PROTECTION SHALL BE DUAL ELEMENT, U.L. CLASS RKI TIME DELAY TYPE. D. FUSES MANUFACTURES: 1. BUSSMANN DIVISION 2. GENERAL ELECTRIC COMPANY 3. GOULD, INC. 4. LITTELFUSE, INC. END OF SECTION 16477 SECTION 16500 - LIGHTING FIXTURES AND LAMPS A. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL LIGHTING FIXTURES AND LAMPS AS SHOWN ON THE DRAWINGS. ALL FIRE RATED ENCLOSURES FOR ELECTRICAL LIGHTING FIXTURES, SPEAKERS, EQUIPMENT, ETC., SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. B. ALL RECESSED INCANDESCENT FIXTURES SHALL BE PROVIDED WITH APPLICABLE THERMAL PROTECTION. C. WHERE FLUORESCENT FIXTURES ARE SPECIFIED, THEY SHALL BE PROVIDED WITH HIGH POWER FACTOR RAPID START BALLASTS, U.L. LISTED, C.B.M. CERTIFIED AND E.T.L. APPROVED. D. THIS CONTRACTOR SHALL FURNISH ADDITIONAL AUXILIARY SUPPORT STEEL HANGER WIRED ADEQUATELY SIZED TO SUPPORT THE WEIGHT OF THE FIXTURE FASTENED TO THE BUILDING STRUCTURE (MINIMUM TWO PER FIXTURE) FOR ALL FIXTURES IN LAY -IN CEILINGS AND OTHER FIXTURES AS REQUIRED BY THE LOCAL CODE OFFICIALS. E. THIS CONTRACTOR SHALL VERIFY THE MODEL NUMBERS AND QUANTITY OF ALL LIGHT AND FIXTURES PROVIDED BY THE OWNER. CONTACT THE OWNER'S CONSTRUCTION MANAGER IMMEDIATELY IF THE MODELS DIFFER FROM THOSE LISTED ON THE LIGHTING FIXTURE SCHEDULE OR IF THEY DO NOT HAVE PROPER THERMAL PROTECTION. F. PROVIDE APPLICABLE FIRE RATED DRYWALL BOXES OVER RECESSED FIXTURES IN FIRE RATED CEILINGS AS REQUIRED BY CODES. FIELD COORDINATE AS REQUIRED TO AVOID CONFLICTS. END OF SECTION 16500 SECTION 16740 -TELEPHONE DATA AND COMPUTER WIRING A. PROVIDE A SYSTEM OF CONDUIT RACEWAYS, OUTLET BOXES, PULL WIRES, AND TERMINAL BOARDS AS SHOWN ON THE DRAWINGS UNLESS OTHERWISE NOTED ON PLANS. TELEPHONE SWITCHING APPARATUS, CONDUCTORS, INSTRUMENTS, MISCELLANEOUS EQUIPMENT AND APPURTENANCES ARE NOT PART OF THIS CONTRACT AND WILL BE PROVIDED AND INSTALLED BY THE OWNER. B. OUTLET BOXES TO BE 4" SQUARE MINIMUM WITH SINGLE FOR DEVICE COVER AND TELEPHONE PLATE WITH CONDUIT DROP AND PULL WIRE TO ABOVE CEILING. C. ALL PULL WIRES ARE TO BE LABELED FOR PURPOSE DESIGNATED. D. NO OTHER CIRCUITS ARE TO BE RUN IN SAME CONDUIT FEEDING ISOLATED GROUND RECEPTACLES. E. PROVIDE A 3/4" THK X 36" X 72" ACX PLYWOOD BOARD MOUNTED VERTICALLY AT 12" A.F.F. FOR MOUNTING TELEPHONE EQUIPMENT. PLYWOOD SHOULD BE PAINTED WITH HIGH QUALITY GRAY OIL BASE PAINT ON BOTH SIDES, FRONT, AND BACK. END OF SECTION 16740 ig �4t � )7q- nrlia FROST ENGINEERS 920 N. Shadeland Ave., Suite G-11 A Indianapolis, Indiana 46219 Phone 317.359.0901 Fax 317.359.0902 mfrost@frostengineers.com H W ov 004O PQ w ��PQ A Z CODO w PQ a a 0 H Seal 0,`%III I I 1111 %%SFRos ' " 15T4Pi �. Iqt'•• ,� V p No. '- - *i:6:0i Revision Project No. DD04001 Date 4-13-04 Scale NO SCALE Drawn By MSF Checked By MSF Sheet T k ELECiAICAL SPECIFICA71ONS Sheet No. POWER PLAN SCALE: 1/4" = 1'- o" - NOTES: REMOVE RECEPTACLE AND WIRING BACK TO PANEL OR JUNCTION BOX, FILL, SPACKLE AND PAINT WALL TO LIKE NEW. REMOVE DATA/TELEPHONE BOX AND WIRING. FILL, SPACKLE AND PAINT WALL TO LIKE NEW. C C Q C C C C POWER PLAN SCALE: 1/4" = 1'-0" NOTES: 1 RECEPTACLE TO REMAIN UNCHANGED, 2 EXISTING RECEPTACLE TO REMAIN, RECIRCUIT AS NOTED, DO NOT ABANDON ANY WIRE. 3 NEW RECEPTACLE. CIRCUIT AS NOTED, 4 PROVIDE NEW DATA OUTLET. ELECTRIC PANEL SCHEDULE SYMBOL PANEL : 1 C (EXISTING) LUGS : 125 120/208 VOLT 1 PHASE 3 WIRE MAIN BREAKER MLO 4--13-04 CKT NO. DESCRIPTION BRKR SIZE POLE KW MSF POLE BRKR SIZE DESCRIPTION CKT NO. PHASE A PH+4SE B 1 RECEPTACLES SUITE 120 20 1 0.8 - FOUR PLEX OUTLET +15 ABOVE FINISHED FLOOR. TYPICAL - - SPACE 2 3 UNDETERMINED 20 1 1.5 - - - SPACE 4 5 UNDETERMINED 20 1 11.5 0.6 1 20 RECEPTACLES SUITE 120 6 7 RECEPTACLES SUITE 120 20 1 0.6 1.5 1 20 UNDETERMINED 8 9 UNDETERMINED 20 1 1,5 1.5 1 20 UNDETERMINED 10 11 RECEPTACLES SUITE 120 20 1 0.8 1.5 1 20 UNDETERMINED 12 13 SUITE 120 WATER HEATER 20 1 1.5 - - - SPACE 14 15 RECEPTACLES SUITE 120 20 1 0.6 0.4 1 20 NIGHT/EMERG SUITE 120 16 17 RECEPTACLES SUITE 120 20 1 1.2 1.1 1 20 UGH71NG SUITE 120 18 191 REFRIGERATOR SUITE 120 20 1 0.7 1.1 1 20 1 LIGHTING SUITE 120 120 TOTAL KW : 18.4 9.7 8.7 TOTAL AMPS : 88.5 ELECTRICAL PANEL REQUIREMENTS 1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TYPED PANEL DIRECTORY IDENTIFYING ALL CIRCUITS. 2. THE ELECTRICAL CONTRACTOR SHALL BALANCE THE THREE PHASES WITHIN 10% OF EACH OTHER. 3. ALL BREAKERS SHALL BE BOLT -ON, 4. PANELBOARD SHAD_ BE SQUARE D. 5. PANEL.BOARD SHALL BE SERVICE ENTRANCE RATED. ELECTRICAL PANEL KEY NOTES O PROVIDE "DO NOT TURN OFF!" LABEL AND LOCK—ON CUPS FOR CIRCUIT BREAKER. EXISTING CIRCUIT FOR OTHER SUITE TO REMAIN. O NEW BREAKER REQUIRED. PANEL IC IS LOCATED IN SECOND FLOOR MECHANICAL ROOM. 23 23 3 D@ D 30 ELECTRICAL SYMBOLS SYMBOL DESCRIPTION 4--13-04 ELEC ICAL PANEL, FIELD RIFY LOCATION. SEE ELECTRICAL RISER DIAGRAM IS�79 FOR MORE INFORMATION AND WORK RESPONSIBILITY C* SWITCH D=DIMMER M=MOTION SENSOR MSF sw DUPLEX OUTLET +150 E FINISHED FLOOR, TYPICAL UNLESS NOTED OTHERWISE OUTLETS SHALL NOT BE IN MIRRORS, ADJUST LOCATIONS ACCORDINGLY VERIFY CHANGES WITH TMW OR ARCHITECT. GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. . GA WP=WEATHER PROOF COVER FOUR PLEX OUTLET +15 ABOVE FINISHED FLOOR. TYPICAL Cn UNLESS NOTED OTHERWISE. NO MORE THAN 3 PER CIRCUIT. FLOOR MOUNTED DUPLEX AND DATA OUTLET. Z JUNCTION BOX TELDWINIE/BATA BOX MOUNTED AT 15" AFF WITH CONDUIT TO ABOVE CEILING. >10 PROVIDE PULL STRING. AFROST ENGINEERS 920 N. Shadeland Ave., Suite G-1 I Indianapolis, Indiana 46219 Phone 317.559.0901 Fax 317.359.0902 mfrost@frostengineers.com Seal `,\111111 fill., *: No. : *= -� 60910220. STATE OF lee ZONAL Milt% Revision Project No. DD04001 Date 4--13-04 Scale 1/4" = 1'-0" Drawn By C* Checked By MSF sw LL.1 I --- �J CL Cn LU Z 0 < >10 LL p ,i - iw --_ — L! 1 l m —j - 0 L Seal `,\111111 fill., *: No. : *= -� 60910220. STATE OF lee ZONAL Milt% Revision Project No. DD04001 Date 4--13-04 Scale 1/4" = 1'-0" Drawn By MSF Checked By MSF srven nk POWER PLANS Sheet No. Ag-. FROST ENGINEERS 920 N. Shadeland Ave., Suite G-11 A Indianapolis, Indiana 46219 Phone 317.359.0901 Fax 317.359.0902 mfrost@frostengineers.com Hyl a�-IF 1c -2o � O O Ff F C CON ;r-; NL 101 w he U J C\1 108 w, F- 1 C-20 PD 1C-16 1C- 0 vd -0 O Q 2 1C 1s 104 0 W ®U® 3 > L, L W �L Z Z M 0 �- 0 N N 00 LIGHTING PLAN — DEMO LIGHTING PLAN Cn 0)>- . z SCALE: = 1 4 -0 1 " '" W U / SCALE: 1 /4" = 1'-0" OSe I— NOTES: E"4 OREMOVE LIGHT AND WIRING BACK TO PANEL OR JUNCTION BOX, CLEAN FIXTURE AND TURN OVER TO OWNER FOR REUSE. OREMOVE EXISTING SWITCH AND WIRING. FILL, SPACKLE AND PAINT WALL TO LIKE NEW. LIGHT FIXTURE SCHEDULE SYMBOL MANUFACTURER CATALOG # DESCRIPTION MOUNTING VOLTS NOTES LAMPS DAY-BRITE 2P4GA332R-365L- 120-1/3EB 3 TUBE, 18 CELL, 2' X 4' FLUORESCENT PARALOUVER LAY -IN 120 FIXTURES MARKED NL FOR NIGHTLIGHT USE CHECK WITH MM FOR EXISTING (3) 38 W T8 GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. . rfl�GF1 WP=WEATHER PROOF OVER FOUR PLEX OUTLET +15 ABOVF FINISHED FLOOR, TYPICAL STOCK OF LIGHTS UNLESS NOTED OTHERWISE NO MORE THAN 3 PER CIRCUIT. LITHONIA LHQM SW 3R 120 COMBINATION EXIT/EMERG, WITH BATTERY PACK SURFACE 120 LLD ELECTRICAL SYMBOLS SYMBOL DESCRIPTION ELECTRICAL PANEL, FIELD VERIFY LOCATION. SEE ELECTRICAL RISER DIAGRAM ® FOR MORE INFORMATION AND WORK RESPONSIBILRY SWITCH D=DIMMER M=MOTION SENSOR DUPLEX OUTLET +150 ABOVE FINISHED FLOOR, TYPICAL UNLESS NOTED OTHERWISE OUTLETS SHALL NOT BE IN MIRRORS, ADJUST LOCATIONS ACCORDINGLY VERIFY CHANGES WITH TMW OR ARCHITECT. GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. . rfl�GF1 WP=WEATHER PROOF OVER FOUR PLEX OUTLET +15 ABOVF FINISHED FLOOR, TYPICAL UNLESS NOTED OTHERWISE NO MORE THAN 3 PER CIRCUIT. FLOOR MOUNTED DUPLEX AND DATA OUTLET. • O OJUNCTION J BOX TELEPHONE/DATA BOX MOUNTED AT 15' AFF WITH CONDUIT TO ABOVE CEILING. PROVIDE PULL STRING. Seal S. Fq,'�.,� -� 60910220. w STATE OF ` �inu Revision Project No. DD04001 Date 4-13-04 Scale 1/4" = 1'-0" Drawn By MSF Checked By MSF Sheet Title LIGI-17"ING PLANS Sheet No. E2 � GENERAL NOTES 1, SEE KEYSTONE OFFICE PARK BUILDING STANDARDS FOR ALL GENERAL INFORMATION. 2. ALL DEMISING WALLS BETWEEN TENANT SUITES AND COMMON AREAS TO BE 3 5/8' METAL STUDS W/ 5/8' GYP. EITHER SIDE FROM FLOOR TO UNDERSIDE OF DECK ABOVE. 3 1/2' INSULATION TO BE INSTALLED BETWEEN STUDS. 3. ALL DOOR ROUGH OPENINGS SHALL BE FRAMED 6' FROM ADJACENT WALL CORNER UNLESS OTHERWISE NOTED, 4. PROVIDE WOOD BLOCKING IN NEW WALLS FOR ALL WALL HUNG ITEMS INCLUDING MILLWORK, WALLSTOPS, CABINETRY, ETC, ALL WOOD BLOCKING MUST BE FIRE TREATED. ALL WALL HUNG ITEMS THAT ARE TO BE HUNG ON EXISTING WALLS SHALL BE FASTENED TO EXISTING STUD FRAMING. 5. ALL PLAN DIMENSIONS ARE TAKEN FROM FACE OF NEW GYPSUM PARTITION OR FACE OF EXISTING CONSTRUCTION UNLESS OTHERWISE NOTED, 6. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD CHECKING ALL DIMENSIONS AND MEASUREMENTS, IF JOB CONDITIONS PREVENT OBTAINING DIMENSI❑NS OR RESULTS AS SHOWN OR SPECIFIED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMING DESIGN/APPLICATIONS, INC. BEFORE ANY CONSTRUCTI❑N IS STARTED. 7, EACH CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AS INDICATED ON THE DRAWINGS AND REPORT ANY DISCREPANCY THAT MAY OCCUR TO THE GENERAL CONTRACTOR, ANY IRREGULARITIES SHALL BE REPORTED TO DESIGN/APPLICATIONS, INC., FROM THE GENERAL CONTRACTOR, 8. SHOP DRAWINGS OR CATALOG CUTS MUST BE SUBMITTED TO DESIGN/APPLICATIONS, INC. FOR APPROVAL, ON ALL MATERIALS OR ITEMS IF THE CONTRACTOR CHOOSES TO DEVIATE FROM THAT SHOWN ON THE DRAWINGS OR IF THE DRAWING DOES NOT INDICATE A SPECIFIC MANUFACTURER OR MODEL NUMBER, 9. GENERAL CONTRACTOR SHALL EXPEDIATE PREPARATION AND SUBMITTAL OF ALL SHOP DRAWINGS TO ALLOW SUFFICIENT TIME FOR FOR CHECKING, FABRICATION, AND/OR ORDERING AND DELIVERY OF MATERIALS & EQUIPMENT. 10. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OVERSEEING THAT ALL MATERIALS AND LABOR SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE RESPECTED TRADE, THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OVERSEEING THAT ALL WORK SHALL BE IN ACCORDANCE WITH THE STATE UNIFORM BUILDING CODES AND STANDARDS FOR ALL GENERAL CONSTRUCTION, MECHANICAL, AND ELECTRICAL WORK AND LOCAL AND FEDERAL CODES AND STANDARDS. 11, ALL DETAILS, MATERIALS, AND INSTALLATIONS OF SAME ARE SUBJECT TO APPROVAL BY DESIGN/ APPLICATIONS, INC. AND FINAL APPROVAL BY THE OWNER. 12. ALL EXISTING BLINDS TO BE CLEANED, ANY DAMAGED BLINDS SHALL BE REPAIRED OR REPLACED IF REQUIRED. 13, NEW WOOD STAINED SILLS ARE TO MATCH EXISTING IN BUILDING W/ OVER HANG OF 3/4'. DESIGN/BUILD NOTES: 1. FIRE PROTECTION CONTRACTOR TO BE RESPONSIBLE FOR LOCATING SPRINKLER HEADS AS REQUIRED BY NFPA AND FILING THE APPROPRIATE DRAWINGS WITH THE CITY AND STATE OFFICIALS. FIRE PROTECTION CONTRACTOR RESPONSIBLE FOR SMOKE DETECTION DEVICES. 2. MECHANICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR FIGURING CFM NUMBERS ON SUPPLY DIFFUSERS, AND FOR LOCATING RETURN AIR OUTLETS. 3. MECHANICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR LOCATING THERMOSTATS AND COORDINATING LOCATION WITH OWNER AND TENANT'S FURNITURE. 4. ELECTRICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR PROVIDING LIFE -SAFETY DEVICES WHERE REQUIRED BY CODE. SUCH AS EXIT SIGNS, HORNS, STROBES AND SPEAKERS. 5. ELECTRICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR ALL CIRCUITING OF OUTLETS AND LIGHT FIXTURES. 6. ELECTRICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR EMERGENCY LIGHTING IN SPACE: EMERGENCY BATTERY PACKS OR NIGHT LIGHTS CONNECTED TO EMERGENCY POWER SOURCE IS REQUIRED IF SPACE CONTAINS 100 PERSONS OR MORE. 7. WHERE MULTIPLE SWITCHES ARE REQUIRED, PROVIDE ONE COVER PLATE. N DEMOLITION PLAN SCALE: 1/8" = 1'-0" WALL LEGEND EXISTING WALL TO REMAIN EXISITING WALL TO BE REMOVED DEMOLITION NOTES: 1. CONT'R TO REMOVE ALL EXISTING CARPET AND BASE. 2. CONT'R TO SALVAGE ALL DOORS AND FRAMES FOR REUSE. 3. REMOVE ALL EXISTING ORBIT STYLE KNOBS ON DOORS AND REPLACE WITH NEW LEVER STYLE. SEE DOOR HARDWARE NOTES FOR DETAILS. 1\ 0 3'W CHERR STAINED W TRIM 00 FIN S.C. WOOD DOOR, CHERRY STAINED �o DOOR TYPES SCALE: 1/4' = F-0' 3"W CHERRY STAINED WOOD TRIM 4 4 - FRAME TYPES �3� D2 3.C. WOOD IOOR, CHERRY STAINED 3/8' TEMPERED GLASS •� 3" 3' F2 D3 >" W SIDELITE /8' TEMPERED LASS " 00 ANODIZED ALUMINUM FRA ANODIZED LUMINUM FRAME 1/2' TEMPERED 3LASS S-6" SCALE: 1/4' = V-0' NOTES: 1. DOOR FRAME TRIM: BUTZ LUMBER, BLC 364, OAK, 3/4" X 3". STAINED ST -1. 2. F2 TO HAVE KAWNEER OR EQUAL, 3/4"X3/4"X1/8" EXTRUDED CLEAR ANODIZED ALUMINUM U CHANNEL TOP & BOTTOM. CLEAR SYLICONE CAULK WHERE GLASS MEETS WALL. WINDOW IS DRYWALL WRAPPED. BOTTOM @ 2'AFF, TOP HT 8'-4", MEETS DOOR NOT FRAME. DOOR SCHEDULE No. DOOR LEGEND FRAME 17 EXISTING \\ EXISTING SALVAGE DDDR AND FRAME TO REMAIN DOOR AND FRAME 1'0 BE REMOVED FOR REUSE MATERIA DEMOLITION NOTES: 1. CONT'R TO REMOVE ALL EXISTING CARPET AND BASE. 2. CONT'R TO SALVAGE ALL DOORS AND FRAMES FOR REUSE. 3. REMOVE ALL EXISTING ORBIT STYLE KNOBS ON DOORS AND REPLACE WITH NEW LEVER STYLE. SEE DOOR HARDWARE NOTES FOR DETAILS. 1\ 0 3'W CHERR STAINED W TRIM 00 FIN S.C. WOOD DOOR, CHERRY STAINED �o DOOR TYPES SCALE: 1/4' = F-0' 3"W CHERRY STAINED WOOD TRIM 4 4 - FRAME TYPES �3� D2 3.C. WOOD IOOR, CHERRY STAINED 3/8' TEMPERED GLASS •� 3" 3' F2 D3 >" W SIDELITE /8' TEMPERED LASS " 00 ANODIZED ALUMINUM FRA ANODIZED LUMINUM FRAME 1/2' TEMPERED 3LASS S-6" SCALE: 1/4' = V-0' NOTES: 1. DOOR FRAME TRIM: BUTZ LUMBER, BLC 364, OAK, 3/4" X 3". STAINED ST -1. 2. F2 TO HAVE KAWNEER OR EQUAL, 3/4"X3/4"X1/8" EXTRUDED CLEAR ANODIZED ALUMINUM U CHANNEL TOP & BOTTOM. CLEAR SYLICONE CAULK WHERE GLASS MEETS WALL. WINDOW IS DRYWALL WRAPPED. BOTTOM @ 2'AFF, TOP HT 8'-4", MEETS DOOR NOT FRAME. DOOR SCHEDULE No. DIMENSIONS DOOR FRAME HDWR. REMARKS MATERIA FINISH TYPE MATERIA FINISH:]SET Ol 3' -0'x8' -4'x1 3/4' D2 WOOD VENEER CHERRY STAINED Fl MAPLE CHERRY STAINED #1 REUSE EXISTING ENTRY DOOR AT SUITE 130. 02 3' -0'x8' -4'x1 3/4' D3 N F3 r =r > #2 ' n rn 03 3' -0'x8' -4'x1 3/4' DI oo 0 00 FI O om C-4 00 0 #2 0 04 EXIST EXIST EXIST � o Q o — EXIST 05 2'-6'x8'-4'xl 3/4' D1 d) 00 c Fi z #2 O 06 3' -0'x8' -4'x1 3/4' DI F1 O W #2 07 3' -0'x8' -4'x1 3/4' DI W O W F2 n O #2 08 3' -0'x8' -4'x1 3/4' Dl a_ n-, F2 W #2 NOTES: CHERRY STAIN IS TO MATCH STAIN IN EXISTING BUILDINGS AT KEYSTONE OFFICE PARK. REUSE EXISTING DOORS WHERE APPLICABLE, TOUCH UP TO LIKE NEW. HARDWARE SETS: HARDWARE S T #1 HARDWARE SET #2 2 PR. BUTT HINGES 2 PR. BUTT HINGES I LOCK SET/THUMB TURN I PASSAGE I DOORSTOP I DOORSTOP I SET SILENCERS I SET SILENCERS SGHLAGE D SERIES, SPARTA SATIN BRASS ELECTRIFIED LOGKSETS: D&O-PD-EU-5PA-6O6 TO BE INSTALLED H/ ELEGTRIFIED HINGE OF 4 1/2 X4 1/2, ALL LOGKS TO BE KEYED TO PRIMUS LOGKS. ALL DOOR HARDWARE TO COMPLY WITH AMERICANS WITH DISABILITIES ACT ACCESSABILITY GUIDELINES AND THE REQUIREMENTS OF UBC CHAPTER 11, 1997 BUILDING CODE. W-1 2 1/2" METAL STUD FRAMING ® 16" O.C. 5/8" GYPSUM WALLBOARD EACH SIDE WALL TO EXTEND TO UNDER SIDE OF FINISHED CEILING. WALL TYPES 3 5/8" METAL STUD FRAMING @ 16" O.C. 5/8" GYPSUM WALLBOARD EACH SIDE SOUND -ATTENUATING BATTS INSIDE WALL & 2 FT EITHER SIDE ADVVE FINISHED CEiLiNG. WALL TO EXTEND TO UNDER SIDE OF FINISHED CEILING. NO SCALE NOTE: ALL WALLS TO BE W-1 UNLESS NOTED OTHERWISE. W-3 IS TO BE 3 EQUAL PANELS OF STORE FRONT 1/2" TEMPERED GLASS W-3 WITH ANODIZED ALUMINUM FRAMES. SYSTEM TO INCLUDE STORE FRONT DOOR. ALL HEIGHTS TO 9'-9" OR EQUAL TO OTHER DOOR HEIGHTS IN OFFICE. 3" 3" N OVERALL FLOOR PLAN SCALE: NONE N ARCHITECTURAL PLAN SCALE: 1/8" = 1'-0" WALL LEGEND EXISTING WALL TO REMAIN NEW WALL CONSTRUCTION. SEE WALL TYPES FOR DETAILS. W DOOR LEGEND EXISTING DOOR AND FRAME TO REMAIN �O NEW DOOR AND FRAME. REFER TO DOOR SCHEDULE ON THIS SHEET. t j ARCHITECTURAL NOTES: O CONT'R TO SUPPLY & INSTALL FLOOR TO CEILING STOREFRONT WALL (10'-0" WIDE) W/ 1 THREE EQUAL PANELS. INCLUDE 1/2' TEMPERED GLASS, FRAMING SYSTEM TO BE BRUSHED ANODIZED ALUMINUM. O SUPPLY & INSTALL 3'-0" PREMANUFACTURED BASE CABINETS, CHERRY STYLE W/ PLASTIC LAMINATE COUNTER TOP, END AND BACK SPLASH. SUPPLY & INSTALL 5'-6" PREMANUFACTURED BASE CABINETS, CHERRY STYLE W/ PLASTIC O LAMINATE COUNTER TOP, END AND BACK SPLASH. SUPPLY SINGLE BOWL STAINLESS STEEL SINK W/ ADA COMPLIANT LEVER FAUCET. ALLOW FOR HOT AND COLD WATER. OSUPPLY & INSTALL WATER LINE FOR ICE MAKER IN TENANT SUPPLIED REFRIGERATOR. Z_ o W N 00 n W O cll� O Q0Q0 Q C'C5 ^_ W C__ Q N o r =r > z ' n rn � w� z oo 0 00 O om C-4 00 0 0 UU) N 00 z � o Q o — O d) 00 c z U Z_ o W N 00 n W O cll� O Q0Q0 Q W W Q U W �cy o wC/� z O w� z z 00 O om 0 0 UU) w z � o — O z U O z O W W O W n O a_ n-, W I— U W W C�d= W U Q:� Q Q Revisions: own.,,�, o i 110.4285 WATE OF 3 t�O 1A�..� ss4f, f �,• Issue: CONST. DOC. Date: MARCH 31 , 04 Sheet: Al D1-01 EXISTING SCALE: 1/8" = 1'-0" EXISTING - --r- �' nl - - - ;-----I---- -f--7 —1h I i 111 I 11 Irl — — -- I I III L� �J I 11 I I i III I 11 II I i I III i 11 I I I I III I 1 Ic—=.p I I I III i 11 1 11 I 11 II a� I i i i it II I I I 11 � — 1 ii II I I jyi REFLECTED CEILING PLAN REFLECTED CEILING NOTFS-- 1. ALL EXISTING LIGHT FIXTURES ARE TO BE REMOVED. 2. ALL EXISTING CEILING TILE IS TO BE REMOVED. 3. REMOVE CEILING GRID AS SHOWN TO MEET NEW LAYOUT REQUIREMENTS. REFLECTED CEILING LEGEND NEW 2'X2' GRID & TILE GTOM ACOUSTIC SUPPLY GRID: ARMSTRONG PRELUDE XL. XL8323 WHITE, 15/16"W TILE: CLEOTEX, CASMERE 2'X2'X3/4", PCM454, W/TAGULAR REVEAL. I I L i - EXISTING 4'X2' TILE TO BE REMOVED, I I I I NEW 2'X4' 18 CELL PARABOLIC FIXTURES, 3000 KELVIN BULB PROPERTY MGM'T HAS 15 IN STOCK, CONT'R TO MATCH REMAINDER. NEW NITE LITE, TO MATCH 2'X4' FIXTURE AS NOTED ABOVE. M NEW SWITCH, DECORA WHITE ROCKER STYLE AT 48" AFF ON CENTER. NEW EXIT SIGNAGE D° NEW 2'X2' SUPPLY DIFFUSER, VERIFY STYLE W/ PROPERTY MGM'T. r -1 PROPOSED REFLECTED CEILING SCALE: 1/8" = 1'-0" REFLECTED CEILING NOTES.- 1. OTES: 1. FINISHED CEILING HEIGHT IS 9'-0" AFF. 2. ALL SPRINKLER HEADS TO BE LOCATED, PROVIDE FULLY RECESSED STYLE W/ COVERS TO MATCH NEW BUILDING STANDARD. 3. ELECTRICIAN RESPONSIBLE FOR ALL FIRE/LIFE SAFETY DEVICE LOCATIONS. Im PLAN W 3'VENT 1/2' V. SINK ��1NOCP�IpN> TYPICAL INASTF. 8, VENT DIAGRAM AT NO SCALE BREAK ROOMS ELECTRICAL PLAN SCALE: 1/8" = 1'-0" ELECTRICAL LEGEND =@E EXISTING DUPLEX RECEPTACLE NEW DUPLEX RECEPTACLE NEW QUADRAPLEX RECEPTACLE NEW GROUNDED DUPLEX RECEPTACLE b NEW DATA/COMMUNICATIONS DROP ►4E EXISTING DATA/COMMUNICATIONS DROP ® NEW FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE & DATA OUTLET ELECTRICAL NOTES: 1. ALL DUPLEX RECEPTACLE PLUGS, COVER PLATES & ROCKER SWITHES TO BE WHITE DECORA STANDARD. 2. ANY DUPLEX RECEPTACLES, DATA BOXES OR BLANK COVER PLATES NOT SHOWN IN EXISTING WALLS ARE TO BE REMOVED. FILL, SPACKLE AND PAINT WALL TO LIKE NEW. IV OVERALL PLAN cT SCALE: NONE N FINISH PLAN SCALE: 1/8" = 1'-0" FINISHES: CARPET: CPT -1 COLOR TO BE DETERMINED CARPET BASE: B-1 4 1/2" HIGH CARPET BASE W/ 1"W X 1-1/2" H WOOD TRIM CHERRY STAINED (ST -1). COLOR TO BE DETERMINED PAINT/WALLCOVERING• PT -1 COLOR TO BE DETERMINED ST -1 CHERRY STAIN TO MATCH EXISTING IN COMMON AREAS OF EXISTING KEYSTONE OFFICE PARK BUILDINGS. NEW WALLS TO RECEIVE 1 COAT PRIMER, 2 COATS CASHMERE FINISH MINIMUM. EXISTING WALLS TO RECEIVE TWO COATS CASHMERE FINISH MINIMUM. COLOR SUBMITTAL SAMPLE REQUIRED PRIOR TO PAINTING. PLASTIC LAMINATE: PL -1 COLOR TO BE DETERMINED CEILING TILE/GRID: CT -1 TILE: 2'X2'X3/4" CELOTEX, CASHMERE PCM -454, W/ TAGULAR REVEAL. GRID: ARMSTRONG PRELUDE XL, XL8323-WHITE 15/16". ii • CAI. .� f%'<F .. FINISH LEGEND W o FLOORING TYPE ## BASE TYPE ## WALL TYPE N FINISHES: CARPET: CPT -1 COLOR TO BE DETERMINED CARPET BASE: B-1 4 1/2" HIGH CARPET BASE W/ 1"W X 1-1/2" H WOOD TRIM CHERRY STAINED (ST -1). COLOR TO BE DETERMINED PAINT/WALLCOVERING• PT -1 COLOR TO BE DETERMINED ST -1 CHERRY STAIN TO MATCH EXISTING IN COMMON AREAS OF EXISTING KEYSTONE OFFICE PARK BUILDINGS. NEW WALLS TO RECEIVE 1 COAT PRIMER, 2 COATS CASHMERE FINISH MINIMUM. EXISTING WALLS TO RECEIVE TWO COATS CASHMERE FINISH MINIMUM. COLOR SUBMITTAL SAMPLE REQUIRED PRIOR TO PAINTING. PLASTIC LAMINATE: PL -1 COLOR TO BE DETERMINED CEILING TILE/GRID: CT -1 TILE: 2'X2'X3/4" CELOTEX, CASHMERE PCM -454, W/ TAGULAR REVEAL. GRID: ARMSTRONG PRELUDE XL, XL8323-WHITE 15/16". ii • CAI. .� f%'<F .. V) �z wQ U n W LL W �z n1 Q _U ►- z U W - � W W U Revisions: 00 W o � N ::D �D (J� _;t Q n. Q W z U GZS Q � o C� (f N f� �� > Vim- � z0 0 0 00 � 0 o 0 o Q ` z N 00 0 � o z n V) �z wQ U n W LL W �z n1 Q _U ►- z U W - � W W U Revisions: Flo, 4285 STATE OF Vol '%0-) I sue: CONST. DOC. F RCH 31 , 04 U W ry W 0 n W W Q Sheet:RCPI E1 %F1 -0 1 00 W o � N ::D �D (J� _;t Q n. Q W z U Q �ry o LL (f z 0 W = z0 J 00-) 0 LLl Q z w � o z n Flo, 4285 STATE OF Vol '%0-) I sue: CONST. DOC. F RCH 31 , 04 U W ry W 0 n W W Q Sheet:RCPI E1 %F1 -0 1