HomeMy WebLinkAbout04040190 Building PlansSECTION 15010 - BASIC MECHANICAL REQUIREMENTS
A. DEFINITIONS AND TERMS .
1. THE WORD "OWNER" SHALL MEAN "CELADON TRUCKING SERVICES, INC.", OR
ANY REPRESENTATIVE OF HIS PARTY DULY AUTHORIZED TO ACT IN HIS BEHALF
IN THE EXECUTION OF THE WORK.
2. THE WORD "CONTRACTOR" SHALL MEAN THE PERSON, FIRM OR CORPORATION
ENTERING INTO A CONTRACT OR AGREEMENT WITH THE OWNER TO CONSTRUCT
AND COMPLETE THE WORK AS SHOWN ON THE DRAWINGS AND SPECIFIED
HEREIN.
3. THE WORD "ARCHITECT AND ENGINEER" SHALL MEAN "PETERSON ARCHITECTURE"
AND ' FROST ENGINEERS, INC" AND THEIR REPRESENTATIVES ACTING AS THE
OWNER'S APPOINTED AGENT.
4. THE WORD "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE PROJECT
SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION AND SIMILAR
SUBSEQUENT REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND CALLED
ON THE DRAWINGS AND SPECIFIED HEREIN.
5. THE WORD 'INSTALL SHALL MEAN OPERATIONS AT THE PROJECT SITE, INCLUDING,
BUT NOT LIMITED TO, UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING,
ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING,
CLEANING, AND SIMILAR REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND
ON THE DRAWINGS AND SPECIFIED HEREIN.
6. THE TERM "PROVIDED" SHALL BE INTERPRETED AS MEANING "FURNISHED AND
INSTALLED" BY THIS CONTRACTOR WITH THE EXCEPTION WHERE ITEMS ARE
"PROVIDED BY THE OWNER" WHICH MEANS "FURNISHED ONLY" AND INSTALLED
BY THIS CONTRACTOR, UNLESS NOTED OTHERWISE.
B. SUMMARY OF WORK
1. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT,
PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES
NECESSARY FOR AND REASONABLY IMPLIED, AND INCIDENTAL TO, THE
FURNISHING, INSTALLATION, COMPLETION, TESTING AND BALANCING OF ALL
THE WORK FOR ALL INSTALLED SYSTEMS AS SHOWN AND CALLED FOR ON
THE DRAWINGS AND SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS.
THESE CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
A. A COMPLETE HVAC SYSTEM INCLUDING SUPPLY, RETURN AND EXHAUST AIR
DUCTWORK, SUPPLY AIR DIFFUSERS, RETURN AIR GRILLES, EXHAUST AIR
GRILLES, DUCTWORK INSULATION, FITTINGS, HVAC EQUIPMENT, DAMPERS, ROOF
CURBS AND CAPS, EXHAUST FANS, CONTROL WIRING, ETC„ AND ALL RELATED
COMPONENTS NECESSARY FOR A COMPLETE INSTALLATION AS SHOWN AND
CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN.
B. A COMPLETE PLUMBING SYSTEM INCLUDING SANITARY WASTE, VENTS,
DRAINS, DOMESTIC COLD AND HOT WATER PIPING SYSTEM, PIPE HANGERS,
PIPE INSULATION, VALVES, PLUMBING FIXTURES AND EQUIPMENT, NATURAL
GAS PIPING, ETC., AND ALL RELATED COMPONENTS NECESSARY FOR A
COMPLETE INSTALLATION AS SHOWN AND CALLED FOR ON THE DRAWINGS
AND SPECIFIED HEREIN.
C. GENERAL REQUIREMENTS
1. THIS CONTRACTOR SHALL VERIFY THE EXTENT OF ALL EXISTING CONDITIONS,
UTILITY CONNECTION POINTS, EQUIPMENT PROVIDED BY OTHERS, ETC., AS
SHOWN AND CALLED FOR ON THE DRAWINGS AND REPORT ANY DISCREPANCIES
TO THE ENGINEER PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF
KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE
REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. NO
ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE
OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE
REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE
OF KNOWLEDGE OF EXISTING CONDITIONS BY VISITING THE SITE PRIOR TO BIDDING
DOES NOT RELIEVE THIS CONTRACTOR OF RESPONSIBILITY IN WORK OR WORKMANSHIP.
2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER
AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN
THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR
WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE
SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK,
AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE
PROVIDED AS PART OF THIS CONTRACT.
3. RELOCATION OF ANY EXISTING WATER, GAS, WASTE, VENT, DRAINAGE LINES, DUCTWORK,
EQUIPMENT, ETC., TO FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN BID
PROPOSAL. THIS CONTRACTOR SHALL NOT REMOVE OR RELOCATE ANY LANDLORD
EQUIPMENT, PIPING, ETC., WITHOUT PRIOR WRITTEN APPROVAL FROM THE LANDLORD.
4. ALL WORK BY THIS CONTRACTOR SHALL BE INSTALLED SO AS TO BE READILY
ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS
CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE
OF THE EQUIPMENT AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES.
5, ALL ROOF CUTTING, PATCHING AND FLASHING SHALL BE BY THE OWNER'S
ROOFING CONTRACTOR OR OWNER'S APPROVED ROOFING CONTRACTOR AT THIS
CONTRACTOR'S EXPENSE. COORDINATE ALL ROOF PENETRATIONS WITH THE
OWNER. MAINTAIN ALL CODE REQUIRED CLEARANCES FROM ALL OUTSIDE AIR
OR FRESH AIR INTAKES LOCATED ON THE ROOF.
6. THIS CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL OR SUPPORTS
TO SUPPORT ANY INSTALLED EQUIPMENT AS SHOWN AND CALLED FOR ON THE
DRAWINGS OR IN THE SPECIFICATIONS. THIS CONTRACTOR SHALL COORDINATE ALL
ADDITIONAL STEEL OR SUPPORT LOCATIONS WITH THE OWNER PRIOR TO BIDDING
AND INSTALLATION.
7. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF
OF THE FLOOR FOR ALL INSTALLED PIPING, DRAINS, SLEEVES, ETC., AS SHOWN
AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. COORDINATE ALL
FLOOR CUTS WITH THE OWNER AND ANY AFFECTED TENANTS. CUTTING AND
PATCHING SHALL BE HELD TO A MINIMUM.
8. THIS CONTRACTOR SHALL COORDINATE ALL ROOF MOUNTED EQUIPMENT LOCATIONS
WITH THE OWNER PRIOR TO INSTALLATION.
9. ALL ROOF TOP MECHANICAL EQUIPMENT SHALL BE IDENTIFIED WITH A MINIMUM TWO
REFER( TO THE AMERICANGNATIONALIN TANDARDST INDSTI UTE O(ANSI) FOR LETTERING SIZE,
LENGTH OF COLOR FIELD, COLORS AND VIEWING ANGLES OF IDENTIFICATION DEVICES.
D. CODES. FEES AND MISCELLANEOUS COSTS
1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE
CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER
REQUIREMENTS AND UTILITY COMPANY REGULATIONS..
2. IN CASES OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, STATE
LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER REQUIREMENTS,
UTILITY COMPANY REGULATIONS AND THE CONTRACT DOCUMENTS, THE MOST
STRINGENT SHALL GOVERN. THIS CONTRACTOR SHALL PROMPTLY NOTIFY THE
ARCHITECT IN WRITING OF ANY SUCH DIFFERENCE.
3. NON-COMPLIANCE: SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT
COMPLY WITH THE REQUIREMENTS OF APPLICAB! E BUILDING CODES, STATE LAWS,
LOCAL ORDINANCES, INDUSTRY STANDARDS, LANDLORD REQUIREMENTS, UTILITY COMPANY
REGULATIONS OR THE CONTRACT DOCUMENTS, THIS CONTRACTOR SHALL BEAR ALL
COSTS ARISING FOR THE CORRECTION OF NON -COMPLYING ITEMS.
4. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL FEDERAL AND STATE LAWS,
LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND
APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. THOSE
REQUIREMENTS ARE TO BE CONSIDERED A MINIMUM AND ARE TO BE EXCEED WHEN
SO INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. THIS CONTRACTOR SHALL
INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES AND STANDARDS AND ANY
CHANGES OR MODIFICATIONS TO THE DRAWINGS OR SPECIFICATIONS AS REQUIRED BY
THE CODES SHALL BE INCLUDED IN THE BID. NO ADDITIONAL COMPENSATION SHALL
BE AWARDED TO THE CONTRACTOR FOR FAILURE OF CODE INQUIRY OR COMPLIANCE.
5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PAYMENT OF
ALL FEES, NECESSARY DRAWINGS AND ARRANGING AND PAYING FOR ALL INSPECTIONS,
TESTS, ETC., WHICH MAY BE REQUIRED BY ANY AUTHORITY OR UTILITY COMPANY IN
CONNECTION WITH THE FURNISHING OR INSTALLATION OF ANY OF HIS RESPECTIVE WORK.
E. WORK AND WORKMANSHIP
1. ALL MATERIALS AND EQUIPMENT SHALL BE OF THE HIGHEST QUALITY IN EVERY RESPECT.
ALL MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, OF THE LATEST
DESIGN AND FREE OF DEFECTS.
2. WORKMANSHIP SHALL BE BY SKILLED WORKMEN OF HIGHEST STANDARD IN STRICT
ACCORDANCE WITH ALL APPLICABLE MANUFACTURERS PRINTED SPECIFICATIONS, PERFORMED
UNDER SUPERVISION OF COMPETENT FOREMAN AT ALL TIMES.
3. THE OWNER AND THE ARCHITECT HAVE FULL POWER TO CONDEMN OR REJECT ANY WORK,
MATERIALS OR EQUIPMENT NOT IN ACCORDANCE WITH THESE SPECIFICATIONS AND DRAWINGS
OR ARE NOT IN CONFORMANCE WITH THE MANUFACTURES SPECIFICATIONS OR DRAWINGS
WHICH WERE APPROVED BY THE OWNER OR ENGINEER.
4. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE REMOVED AND REPLACED TO THE
SATISFACTION OF THE OWNER OR ARCHITECT AT THIS CONTRACTORS EXPENSE. WORK
OR EQUIPMENT THAT IS REJECTED SHALL BE SO STATED IN WRITING BY THE OWNER
OR THE ENGINEER.
5. SUCH DECISIONS AS THE OWNER OR THE ENGINEER MAY MAKE WITH RESPECT TO
QUESTIONS CONCERNING THE QUALITY, FITNESS OF MATERIALS, EQUIPMENT AND
WORKMANSHIP SHALL BE BINDING UPON THE PARTIES THERETO.
F. DEVIATIONS FROM DRAWINGS
1. THE DRAWINGS SHOW THE INTENDED ARRANGEMENT AND ROUTING OF ALL PIPING,
DUCTWORK, EQUIPMENT AND APPURTENANCES. THEY SHALL BE FOLLOWED AS
CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL
PERMIT.
2. THIS CONTRACTOR SHALL INVESTIGATE STRUCTURAL AND FINISH CONDITIONS
AFFECTING HIS WORK AND SHALL PROVIDE ANY FITTINGS, OFFSETS AND ACCESSORIES
REQUIRED TO ACCOMMODATE SAID CONDITIONS IN THE BID PROPOSAL.
3. WHERE TRADE NAMES AND MANUFACTURES ARE USED ON THE DRAWINGS OR
SPECIFIED HEREIN THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE
BASE BID. MANUFACTURES CONSIDERED AS AN E UAL OR BETTER I A
Q N LL ASPECTS
TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY THE OWNER OR
THE ARCHITECT PRIOR THROUGH SHOP DRAWING OR SUBMITTAL PROCESS, TO
ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO
REMOVAL AND REPLACEMENT AT THIS CONTRACTORS EXPENSE.
4. THE DRAWINGS INDICATE AN INSTALLED SYSTEM BASED UPON SELECTED MANUFACTURERS
OF EQUIPMENT. ELECTRICAL SERVICES, SIZE, CONFIGURATIONS, ETC., ARE CONSISTENT
WITH THE MANUFACTURER'S RECOMMENDATIONS. OTHER MANUFACTURERS ARE ENCOURAGED
TO FURNISH EQUIPMENT FOR THIS PROJECT; HOWEVER, IT SHALL BE THIS CONTRACTORS
RESPONSIBILITY TO ASSURE THAT THE EQUIPMENT IS CONSISTENT WITH THE DESIGN BASE.
NO ADDITIONAL COMPENSATION SHALL BE AWARDED FOR REVISIONS, MODIFICATIONS, ETC.,
TO ELECTRICAL SERVICES, WIRING, BREAKERS, SPACE, CLEARANCE, DUCTWORK, PIPING,
ETC., REQUIRED BY OTHER MANUFACTURES.
G. OCCUPATIONAL SAFETY AND HEALTH ACT
1. ALL WORK SHALL BE COMPLY WITH THE CURRENT REQUIREMENTS OF THE U.S.
DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, ENTITLED
OCCUPATIONAL SAFETY AND HEALTH STANDARDS; NATIONAL CONSENSUS STANDARDS
AND ESTABLISHED FEDERAL STANDARDS.
H. COORDINATION BETWEEN CONTRACTORS
1. BEFORE THE COMMENCEMENT OF ANY WORK, THIS CONTRACTOR SHALL EXAMINE
ALL THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS
COMPONENTS OF THE INSTALLED SYSTEMS, MATERIALS, PIPING, EQUIPMENT, ETC.,
WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES
AND CONFLICTS.
2. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR .TO LEAVE THE REQUIRED, NECESSARY
ROOM FOR OTHER TRADES. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO
THIS CONTRACTOR FOR FAILURE TO COORDINATE WITH OTHER TRADE CONTRACTORS
TO AVOID OTHER TRADE INTERFERENCES, CONFLICTS, RELOCATION OF DUCTWORK,
PIPING, EQUIPMENT, ETC., FOUND ENCROACHING ON SPACE REQUIRED BY OTHERS.
3. THIS CONTRACTOR SHALL PROVIDE COMPLETE INFORMATION AND COOPERATION TO
THE OTHER CONTRACTORS AND TRADES PERTAINING TO HIS WORK TO ACCOMPLISH
COORDINATION OF THE COMPLETED PROJECT.
I. EQUIPMENT DRAWINGS
1. THIS CONTRACTOR SHALL PROVIDE EQUIPMENT DRAWINGS OF PROVIDED EQUIPMENT
AS SPECIFIED HEREIN.
2. THE FOLLOWING ITEMS ARE A MINIMUM REQUIREMENT FOR EACH EQUIPMENT DRAWING
SUBMITTAL:
A. SHEET SIZE 8-1/2" X 11
B, MANUFACTURE'S STANDARD SCHEMATIC DRAWINGS:
1. MODIFY DRAWINGS TO DELETE INFORMATION THAT IS NOT APPLICABLE TO
THIS PROJECT.
2. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION
APPLICABLE TO THIS PROJECT.
C. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES, -
PERFORMANCE CHARTS, ILLUSTRATIONS AND OTHER STANDARD DESCRIPTIVE DATA.
1. CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS,
MODELS, ETC.
2, SHOW EQUIPMENT DIMENSIONS AND MAINTENANCE OR CONSTRUCTION CLEARANCES
REQUIRED.
3. SHOW PERFORMANCE CHARACTERISTICS AND CAPABILITIES.
4. SHOW WIRING DIAGRAMS AND CONTROLS.
5. MATERIAL AND SAFETY DATA SHEETS.
6. THE FULL MANUFACTURE'S MODEL NUMBER OF EACH ITEM.
7, IDENTIFICATION OF COLOR OR FINISHES. .
8. THIS CONTRACTOR'S STAMP, SIGNATURE AND DATA SHALL BE AFFIXED TO EACH
COPY OF THE SHOP DRAWINGS WITH INDICATION OF HIS REVIEW.
3. COPIES OF THE EQUIPMENT DRAWINGS AND ALL OTHER RELATED INFORMATION MUST APPEAR
IN THE OPERATIONS MANUAL LEFT ON SITE AFTER PROJECT COMPLETION.
J. RECORD DRAWINGS
1. DURING CONSTRUCTION THIS CONTRACTOR SHALL MAINTAIN A COMPLETE AND LEGIBLE SET OF
DRAWINGS SHOWING CHANGES AND DEVIATIONS BETWEEN ACTUAL CONSTRUCTION AND THE
ENGINEER'S DRAWINGS.
2. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE, THIS CONTRACTOR
SHALL MAKE ANY FINAL CORRECTIONS TO THE DRAWINGS AND CERTIFY THE ACCURACY OF
EACH PRINT WITH THIS CONTRACTOR'S STAMP AND SIGNATURE THEREON. THIS COPY OF THE
RECORD DRAWINGS SHALL BE PLACED IN A DRAWING TUBE AND MARKED "RECORD DRAWINGS -
DO NOT REMOVE FROM PREMISES' AND SHALL BE KEPT WITH THE OPERATIONS MANUAL.
K. OPERATIONS MANUAL
1. THREE COPIES OF THE OPERATIONS AND MAINTENANCE MANUAL FOR ALL EQUIPMENT
FURNISHED FOR THE PROJECT SHALL BE COLLECTED AND INSERTED IN LABELED THREE INCH
(3") THREE (3) RING BINDERS.
2. OPERATIONS AND MAINTENANCE MANUALS SHALL BE ASSEMBLED AS FOLLOWS:
A. SECTION 1
1. TITLE OF PROJECT
2. LOCATION OF PROJECT
3. NAME AND ADDRESS OF OWNER
4. NAME AND ADDRESS OF ENGINEER
5, NAME AND ADDRESS OF THIS CONTRACTOR.
B. SECTION 2
1. SHOP DRAWINGS OF ALL APPROVED EQUIPMENT.
C. SECTION 3
1. A LISTING OF ALL EQUIPMENT WARRANTIES INDICATING THE EQUIPMENT MODEL
NUMBER, SERIAL NUMBER, START AND ENDING DATE OF THE WARRANTY, ETC.
D. SECTION 4
1. COPIES OF ALL AIR AND WATER BALANCE REPORTS.
3. EACH SECTION SHALL BE SEPARATED BY A PASTEBOARD TABBED DIVIDER.
4. ALL INFORMATION SHALL BE ARRANGED IN AS MANY BINDERS AS NECESSARY,
5. OPERATION AND MAINTENANCE MANUAL AND DRAWING TUBE SHALL BE SENT TO THE
ENGINEER.
L. INSPECTIONS, FINAL REPORTS AND GUARANTEE
1. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL INFORM THE LOCAL
AND STATE AUTHORITIES AND THE OWNER TO ARRANGE FOR FINAL INSPECTIONS
OF THIS WORK.
2. THIS CONTRACTOR SHALL FURNISH TO THE OWNER ALL CERTIFICATES OF INSPECTION
AND FINAL INSPECTION APPROVAL AT THE COMPLETION OF THIS PROJECT.
3. THIS CONTRACTOR SHALL SUBMIT TO THE OWNER UPON COMPLETION OF THIS WORK
A LETTER CERTIFYING THAT THIS WORK IS IN ACCORDANCE WITH ALL APPLICABLE STATE
AND LOCAL LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY
REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND
STANDARDS.
4. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT, WORK, ETC., UNDER
THIS CONTRACT FOR ONE (1_) YEAR AFTER THE ACCEPTANCE OF ALL SYSTEMS INSTALLED
BY THIS CONTRACTOR UND RR THIS CONTRACT, THIS CONTRACTOR SHALL MAKE GOOD,
REPAIR OR REPLACE AT THIS CONTRACTORS OWN EXPENSE, ANY DEFECTIVE WORK,
MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED FORM THE DATE OF ACCEPTANCE,
IN WRITING. EXTENDED WARRANTIES ARE AS SPECIFIED WITH THE INDIVIDUAL EQUIPMENT.
5. UNDER THE ONE (1) YEAR GUARANTEE PERIOD THIS CONTRACTOR SHALL BE RESPONSIBLE
FOR ANY DAMAGE TO THE PREMISES CAUSED BY DEFECTS IN ANY WORKMANSHIP OR
ANY EQUIPMENT FURNISHES AND/OR INSTALLED BY THIS CONTRACTOR.
M. SLEEVES
1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN
THE INSTALLATION, EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL
OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT
PENETRATE THE FLOOR, WHICH SHALL EXTEND TWO INCHES (2") ABOVE THE FLOOR.
2. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE
STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY
PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING,
SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM.
N, FIRE STOPPING
1. ALL OPENINGS THROUGH FIRE RATED WALLS AND10R FLOORS FOR CONDUITS SHALL BE
FIRE SEALED IN ACCORDANCE WITH NFPA 101 WIITH CALCIUM SILICATE, SILICONE RTV" FOAM,
3M FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE RATING. PROVIDE
SLEEVES AS REQUIRED BY ALL APPLICABLE CODES OR OWNER REQUIREMENTS. (INCLUDING FACTORY
MUTUAL FIELD VERIFY ALL EXISTING PENETRATIONS THROUGH FIRE WALLS AND/OR FLOORS AND
SEAL A REQUIRED IN ACCORDANCE WITH NFPA 101 AS LISTED ABOVE.
0. PHASING REQUIREMENTS
1. THIS CONTRACTOR SHALL INCLUDE IN HIS BID ALL NECESSARY SERVICES REQUIRED TO KEEP
THE OPERATING PHASE OF THE OWNER'S HVAC, PLUMBING OR FIRE PROTECTION, SYSTEMS EIC.,
IN OPERATION. THIS CONTRACTOR SHALL SCHEDULE SHUT DOWNS OF THE OWNER'S HVAC,
PLUMBING, FIRE PROTECTION OR ELECTRICAL SYSTEMS ONE WEEK PRIOR TO THE SHUT DOWN.
SECTION 15145 - HANGERS AND SUPPORTS
A. RELATED WORK
1. MECHANICAL INSULATION: SECTION 15250
B. MANUFACTURES
1. BI -LINE
2. FEE AND MASON
3. GRINNELL
4. MICHIGAN HANGER COMPANY
C. INSTALLATION
1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS,
C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR
THE COMPLETE INSTALLATION OF WORK.
2. HANGERS SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE, OR MASONRY,
BUT NOT TO EQUIPMENT OR PIPING. HANGING FROM METAL DECK SHALL NOT BE
PERMITTED. HANGERS SHALL BE ATTACHED TO THE UPPER CHORD OF THE BAR JOIST.
WHERE INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT DUCTWORK OR PIPING, THIS
CONTRACTOR SHALL INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE
LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS DOORS TO FIRE DAMPERS,
VALVES, EQUIPMENT, ETC. HANGER TYPES AND INSTALLATION METHODS SHALL BE
SUBJECT TO ALL APPLICABLE CODES AND THE LANDLORD. REQUIREMENTS. VERIFY ANY
LANDLORD REQUIREMENTS PRIOR TO BIDDING.
3. HANGERS OR SUPPORTS FOR EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL NOT BE
SUPPORTED FROM THE LANDLORD'S CEILING, SOFFITS, NEUTRAL PIERS, PIPING,
DUCTWORK, METAL ROOF DECK, LATERAL BRACING, BRIDGING, ELECTRICAL CONDUITS, ETC.
4. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER
DIAMETER OF INSULATION. INSTALL SIX INCH (6" LONG SPLIT CIRCLE GALVANIZED
SADD E BETW T )
L EEN HE HANGER AND THE PIPE INSULATION. REFER TO TH
E DRAWINGS
FOR PIPE HANGER DETAILS.
5. HANGERS AND PIPING OF'DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED.
6. PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY THE OWNER OR CODE.
END OF SECTION 15145
SECTION 15241 - VIBRATION ISOLATION
A. RELATED WORK
1. HANGERS AND SUPPORTS: SECTION 15145
2. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800
B. MANUFACTURES
1. AMBER/BOOTH COMPANY
2. KORFU D DYNAMICS CORPORATION
3. MASON INDUSTRIES, INCORPORATED
4. PEABODY NOISE CONTROL, INCORPORATED
5. KINETICS NOISE CONTROL, INCORPORATED
C. INSTALLATION
1. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS BETWEEN
VIBRATING EQUIPMENT, FANS, ROOF TOP AIR CONDITIONING EQUIPMENT, EXHAUST
FANS, ETC., AND THE BUILDING STRUCTURE.
2. VIBRATING EQUIPMENT HUNG FROM THE STRUCTURE SHALL BE ISOLATED WITH
RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORT FROM THE FLOOR
OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES.
3. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES.
ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID 'GROUNDING" THE ISOLATOR.
4. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND AT
THE UPPER AND LOWER ATTACHMENTS TO THE STRUCTURES, EQUIPMENT,ETC.
5. CONSULT MANUFACTURER FOR FURTHER APPLICATION AND INSTALLATION DATA.
END OF SECTION 15241
SECTION 15250 MECHANICAL INSULATION
A. RELATED WORK
1. HANGERS AND SUPPORTS: SECTION 15145
2. PLUMBING: SECTION 15400
3. HYDRONIC/REFRIGERANT PIPING: SECTION 15500
4. HEATING, VVENTILATION AND AIR CONDITIONING: SECTION 15800
B. PRODUCTS
1. BLANKET INSULATION W'iTH ALUMINUM FOIL FACING
A. CERTAIN TEED CORPORATION.
B. KNAUF FIBERGLASS
C. MANVILLE
D. OWENS-CORING FIBERGLASS CORPORATION
2. FLEXIBLE ELASTOMERIC
A, ARMSTRONG WORLD INDUSTRIES
B. PITTSBURGH CORNING PRODUCTS
C. RUBATEX CORPORATION
---
CITY OF CARMEL/CLAY TOWNSHIP
Dept. of Community Services -- Building & Code Enforcement
One Civic Square I" Floor; Carmel, IN 46032
PLAN AUTHENTICATION CERTIFICATIONS AND AGREEMENT
As the authorized agent responsible for obtaining a permit or permits', I certify that these plans
are IDENTICAL to those released for construction by the Indiana Depart. of Fire & Building
Services. I also understand that if it is determined that these plans are not identical, a STOP
WORK ORDER will be served, s requ' ed and the Ordinances referenc, bellow.
'r ��l 55 � u� (A S 6E Ctrj
A horized Signature Printed Name
'Required under Chapter 7, Section 10 of the Carmel City Code, entitled "Building Code' and Section 29.4.2
and Section 29.4.3 entitled "Administration". Required by Carmel / Clay Township Zoning Ordinance, Section
31.1 entitled "Violations and Penalties".
S:Permi is / Forms /AuthentStickerl 1-01
C. INSULATION SCHEDULES
TYPE OF DUCTWORK
FORM THICKNESS JACKET
INTERIOR SUPPLY, RETURN,
RELIEF AND OUTSIDE AIR DUCTWORK
BLANKET
1-1/2"
-
INTERIOR EXPOSED SUPPLY, RETURN,
-
1/2"
-
INTERIOR HYDRONIC (35' - 99')
BOARD
1"
-
RELIEF AND OUTSIDE AIR DUCTWORK
1„
-
INTERIOR HYDRONIC (100' - 250')
ALL DUCTWORK RISERS
3/4"
-
INTERIOR REFRIGERANT
(LIQUID AND SUCTION ONLY)
TO ROOF MOUNTED EQUIPMENT
BLANKET
1-1/2"
-
(SEE NOTE 3 BELOW)
-
EXTERIOR EXPOSED REFRIGERANT
(LIQUID AND SUCTION ONLY)
1/2" - 1-1/4"
TYPE OF PIPING
PIPE SIZE THICKNESS JACKET
INTERIOR DOMESTIC HOT WATER
1/2" - 4"
1/2"
-
SANITARY DRAINS AND TRAPS
EXPOSED AT FIXTURES FOR THE
DISABLED (SEE NOTE 1 BELOW)
-
1/2"
-
INTERIOR HYDRONIC (35' - 99')
1/2" - 1-1/4"
3/4'
-
1-1/2" - 4"
1„
-
INTERIOR HYDRONIC (100' - 250')
1/2" - 2"
3/4"
-
INTERIOR REFRIGERANT
(LIQUID AND SUCTION ONLY)
1/2" -
3/4"
-
,1--1/4"
1-1 2' - 4"
/
1
-
EXTERIOR EXPOSED REFRIGERANT
(LIQUID AND SUCTION ONLY)
1/2" - 1-1/4"
3/4"
ALUM.
1-1 /2" - 4"
1 "
ALUM.
SANITARY DRAINS LOCATED IN
THE CEILING SPACE OF OTHER
TENANTS
ALL SIZES
1/2"
-
INTERIOR DOMESTIC COLD WATER
1/2" - 4"
1/2"
-
EXTERIOR EXPOSED NATURAL GAS
(SEE NOTE 2 BELOW)
1/2" - 1--1/4"
3/4"
ALUM.
1-1 /2" - 4"
1 "
ALUM.
INTERIOR CONDENSATE DRAIN
ALL SIZES
-
-
EXTERIOR CONDENSATE DRAIN
3/4" - 4"
i-1/2"
ALUM.
1. PIPING INSULATION IS BASED UPON FLEXIBLE ELASTOMERIC TYPE.
2. ALL INSULATION SHALL MEET LOCAL CODE REQUIREMENTS AND UL FLAME SPREAD AND
SMOKE DEVELOPED RATINGS.
NOTES:
1. TRUEBRO MODEL 102W "HANDI LAV GUARD" INSULATION KIT SHALL BE USED UNDER
ADA LAVATORIES,
2. CORROSION -RESISTANT POLYETHYLENE COATING MAY BE SUBSTITUTED.
END OF SECTION 15250
SECTION 15300 - FIRE PROTECTION
SECTION 15400 - PLUMBING
A. RELATED WORK
1. VALVES: SECTION 15100
2. HANGERS AND SUPPORTS: SECTION 15145
3. MECHANICAL INSULATION: SECTION 15250
4. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800
B. EQUIPMENT AND MATERIALS
1. REFER TO THE DRAWINGS FOR PLUMBING FIXTURE SPECIFICATIONS.
2. SANITARY WASTE AND VENT PIPING SHALL BE AS FOLLOWS:
A. SERVICE WEIGHT CAST IRON PIPE, VENT PIPING ABOVE THE FLOOR TWO INCHES (2")
OR SMALLER MAY BE GALVANIZED STEEL. PVC PIPING SHALL BE ALLOWED AS A
SUBSTITUTE WHEN PERMITTED BY THE LOCAL CODES, AND BUILDING DEPARTMENT OFFICIALS
AND IT DOES NOT AFFECT OTHER TRADES. PROVIDE DIELECTRIC SEPARATION BETWEEN
DISSIMILAR METALS.
3. CONDENSATE DRAIN PIPING SHALL BE AS FOLLOWS:
A. TYPE "L' DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY SOLDERED JOINTS AND
WROUGHT COPPER FITTINGS WITH DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS.
B. ALL CONDENSATE DRAIN PENETRATIONS SHALL BE MADE WITHIN THE ROOF CURB OF THE
ROOF TOP AIR CONDITIONING UNIT. TERMINATE CONDENSATE DRAINS AT CODE APPROVED
TERMINATION POINTS. CONDENSATE DRAINS SHALL NOT TERMINATE ABOVE THE ROOF LEVEL.
4. DOMESTIC HOT AND COLD WATER PIPING SHALL BE AS FOLLOWS:
A. TYPE "K" ANNEALED TEMPERED COPPER TUBE FOR PIPE SIZES TWO INCH (2") AND SMALLER
BELOW GRADE. BRAZE ALL JOINTS. DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS.
B. TYPE "L" DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY SOLDERED JOINTS AND WROUGHT
FITTINGS FOR ALL OTHER PIPING. DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS.
5. NATURAL GAS PIPING SHALL BE AS FOLLOWS:
A. BLACK STEEL, SCHEDULE 40, ASTM A-120, WITH MALLEABLE THREADED FITTINGS FOR TWO
INCH (2") AND SMALLER AND WELDED JOINTS FOR TWO AND ONE-HALF INCH (2-1/2")
AND LARGER.
6. INSTALL WATER HAMMER ARRESTORS ON EACH HOT AND COLD WATER SUPPLY TO EACH
FIXTURE. WATER HAMMER ARRESTORS SHALL BE SIMILAR JAY R. SMITH "HYDROTROL" SERIES
5000 OR EQUAL. REFER TO THE PLUMBING DRAWINGS FOR SHOCK ABSORBER SCHEDULE,
7. BACKFLOW PREVENTERS SHALL BE AS FOLLOWS:
A. BRONZE BODY WITH THREADED ENDS, 150 PSIG MINIMUM WORKING PRESSURE UNLESS
NOTED OTHERWISE, CORROSION RESISTANT INTERIOR COMPONENTS AND STRAINER ON INLET.
8. ESCUTCHEONS SHALL BE CHROME PLATED, SIZE AS REQUIRED AND PLACED AT ALL PIPE
PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, ETC., IN ALL FINISHED AREAS.
9. INSTALL FIXTURE CARRIERS OR SUPPORT FOR ALL WALL MOUNTED PLUMBING FIXTURES.
FIXTURE CARRIERS OR SUPPORTS SHALL BE AS FOLLOWS:
A. JAY R. SMITH MANUFACTURING COMPANY
B. JOSAM COMPANY
C. WADE DIVISION; TYLER PIPE
D. ZURN INDUSTRIES, INCORPORATED; HYDROMECHANICS DIVISION
C. INSTALLATION
1. VALVE LOCATIONS SHALL BE AS FOLLOWS: ..
A. PROVIDE A SHUT OFF VALVE IN THE SUPPLY PIPING TO EACH FIXTURE.
PROVIDE A MINIMUM 24' X 24" ACCESS DOOR WHERE REQUIRED FOR
VALVE ACCESS.
B. PROVIDE A GAS COCK IN THE SUPPLY PIPING TO EACH PIECE OF
EQUIPMENT REQUIRING GAS SERVICE.
2. PROVIDE A DIRT LEG AND UNION CONNECTION TO EACH PIECE OF EQUIPMENT
REQUIRING GAS SERVICE.
3. PITCH GAS PIPING AT A UNIFORM GRADE OF 1/4" IN FIFTEEN FEET (15'-0")
UPWARD IN THE DIRECTION OF FLOW.
4. GAS PIPING INSTALLED IN RETURN AIR PLENUMS SHALL BE SLEEVED AND VENTED
OR WELDED IN ACCORDANCE WITH UTILITY COMPANY REGULATIONS, LOCAL CODES
A. RELATED WORK
AND ALL APPLICABLE NFPA CODES.
1. BASIC MECHANICAL REQUIREMENTS: SECTION 15010
5. PROVIDE FLOOR DRAINS AND CLEAN -OUTS PER CODE REQUIREMENTS.
B. SUMMARY OF WORK
NO SCALE
D.
TEST OF SYSTEMS
1. THE FIRE PROTECTION CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT,
MSF
PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES NECESSARY
1. PRIOR TO THE INSTALLATION OF THE SANITARY PIPING SYSTEM SNAKE THE
FOR AND REASONABLY IMPLIED, AND INCIDENTAL T0, THE FURNISHING, INSTALLATION,
SANITARY SYSTEM A MINIMUM OF FIFTY FEET (50'-0") AND REPORT ANY BLOCKAGE.
COMPLETION AND TESTING OF ALL THE WORK FOR A COMPLETE FIRE PROTECTION
SYSTEM AS SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS. THESE
2. TEST WATER PRESSURE TO INSURE MINIMUM PSI MATCHES MOST DEMANDING
CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
EQUIPMENT SUPPLIED.
A. A COMPLETE FIRE PROTECTION SYSTEM AS REQUIRED BY NFPA, LOCAL CODES,
OWNER'S CRITERIA AND THE OWNER'S INSURANCE CARRIER INCLUDING
3. STERILIZE WATER SYSTEM PIPING IN ACCORDANCE WITH ALL CODE REGULATIONS.
SPRINKLER PIPING, TAPS, RISERS, LATERALS, BRANCHES, VALVES, ALARMS, SPRINKLER
4. TEST THE WATER PIPING SYSTEM AT 100 PSIG FOR FOUR (4 HOURS OR AS REQUIRED
HEADS, ETC., FIRE PUMPS AND ALL RELATED COMPONENTS NECESSARY FOR A
BY THE LANDLORD, UTILITY COMPANY REGULATIONS OR BY CODE REQUIREMENTS.
COMPLETE INSTALLATION AS SPECIFIED HEREIN.
B. DESIGN DRAWINGS, HYDRAULIC CALCULATIONS, SUBMITTALS AND APPROVALS.
5. TEST THE SANITARY WASTE, VENT AND DRAIN PIPING BY A TEN FOOT (10') WATER
C. TESTS AND TEST CERTIFICATES.
COLUMN FOR ONE HOUR OR AS REQUIRED BY THE UTILITY COMPANY
REGULATIONS OR BY CODE REQUIREMENTS.
D. FIRE EXTINGUISHER(S).
6. TEST AND PURGE THE GAS PIPING SYSTEM AS PER THE REQUIREMENTS OF THE
C. GENERAL REQUIREMENTS
UTILITY COMPANY REGULATIONS, LOCAL CODES AND APPLICABLE NFPA CODES.
1. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER
END OF SECTION 15400
AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN
THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR
i�
WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE
SECTION 15530 - REFRIGERANT PIPING
SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK,
AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE
PROVIDE AS PAST OF THIS CONTRACT. A.
RELATED WORK
2. ALL WORK BY THE FIRE PROTECTION CONTRACTOR SHALL BE INSTALLED SO AS TO BE
1. HANGERS AND SUPPORTS: SECTION 15145
READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS
2. MECHANICAL INSULATION: SECTION 15250
CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE
OF THE EQUIPMENT
3. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800
AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES.
3. RELOCATION OF ANY EXISTING FIRE PROTECTION PIPING, EQUIPMENT, VALVES, B,
REFRIGERANT EQUIPMENT AND MATERIALS
SPRINKLER HEADS, ETC., TO FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED
IN THE BID PROPOSAL. THE FIRE PROTECTION CONTRACTOR SHALL NOT REMOVE OR
1. REFRIGERANT PIPING SHALL BE AS FOLLOWS:
RELOCATE ANY LANDLORD EQUIPMENT, PIPING, ETC., WITHOUT PRIOR WRITTEN APPROVAL
A. TYPE "L" HARD DRAWN COPPER TUBING (ASTM B88). TUBING SHALL BE CLEAN, CAPPED
FROM THE LANDLORD.
AND NITROGEN CHARGED.
4. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED, FULLY SUPERVISED
AND INSTALLED ACCORDING TO NFPA 13. SUPERVISION WILL INCLUDE VALVE TAMPER
2. REFRIGERANT PIPING FITTINGS SHALL BE AS FOLLOWS:
SWITCHES AND WATER FLOW INDICATORS WHICH SHALL TRANSMIT CONDITIONS TO
A. WROUGHT COPPER OR CAST BRONZE (_ANSI B16.22). ALL COPPER TO COPPER JOINTS
THE MASTER FIRE ALARM PANEL.
SHALL BE BRAZED WITH SILOS -5 ALLOY.
5. THIS CONTRACTOR SHALL ASSUME FINANCIAL RESPONSIBILITY FOR COMPLIANCE OF ALL
3. REFRIGERANT PIPING SPECIALTIES SHALL BE FURNISHED AS PART OF THE CONDENSING
CODES AND REGULATIONS OF GOVERNING STANDARDS AND AGENCIES.
UNIT BY THE CONDENSING UNIT MANUFACTURER. REFER TO AIR COOLED CONDENSING
6. ALL SPRINKLER PIPING SHALL BE INSTALLED CONCEALED, AVOIDING INTERFERENCE WITH
UNIT DX COIL PIPING DETAIL FOR REFRIGERANT PIPING SPECIALTIES FURNISHED BY THIS
CONTRACTOR.
LIGHTS, DUCTWORK, PIPING, ETC. THE FIRE PROTECTION CONTRACTOR SHALL
.
PREPARE COORDINATED SHOP DRAWINGS INDICATING THE LOCATIONS OF ALL SPRINKLER C.
INSTALLATION
HEADS, SPRINKLER PIPING, LIGHTS AND DIFFUSERS; GRILLES, REGISTET;S, ETC., PRIOR TO
INSTALLATION OR MODIFICATION.
1. SUCTION LINES SHALL HAVE ADEQUATE LIFT TRAPS AND/OR DOUBLE SUCTION RISERS TO
7. PROPERLY COMPLETED AND SIGNED TEST CERTIFICATES SHALL BE FURNISHED TO THE
MEET THE REQUIREMENTS OF FIELD CONDITIONS AND UNIT MANUFACTURES RECOMMENDATIONS.
OWNER, AUTHORITIES HAVING JURISDICTION, THE OWNER'S INSURANCE CARRIER, ETC.
UNIT MANUFACTURER SHALL VERIFY ALL REFRIGERANT PIPING SIZES BEFORE INSTALLATION AND
-. :p THE INSTALLATION HAS BEEN MADE TO THE UNIT MANUFACTURES SPECIFICATIONS AND
8. CONCEALED SPRINKLER HEADS SHALL BE INSTALLED IN CEILINGS BELOW 8'-O" . RECOMMENDATIONS.
D. QUALITY ASSURANCE
2. BRAZE ALL REFRIGERANT PIPING JOINTS WITH SILOS -5 STARTING AT THE INDOOR UNIT
AND WORKING TOWARD THE OUTDOOR UNIT. THE SEALS ON THE OUTDOOR UNIT SHALL BE
1. ALL MATERIALS AND DEVICES USED ARE TO BE NEW AND ARE TO BE LISTED FOR USE BY
BROKEN LAST. A NITROGEN BLEED SHALL BE USED DURING ALL BRAZING AND ANY TIME
THE UNDERWRITERS LABORATORIES, INCORPORATED" AND SHALL BEAR THEIR LABEL WHENEVER
"LABEL
THE SYSTEM IS OPEN. ALL OPEN LINES SHALL BE CAPPED AND SEALED WHENEVER THIS
SERVICE' IS A REQUIREMENT OR IS AVAILABLE,
CONTRACTOR IS NOT ON THE PREMISES,
2. THE FIRE PROTECTION SYSTEM SHALL COMPLY WITH ALL REGULATING AGENCIES, ORGANIZATIONS, D.
TEST OF SYSTEM
PUBLICATIONS, ETC.
E. SHOP DRAWINGS
1. PRESSURE TEST FOR LEAKAGE OF SYSTEM WITH AN INERT GAS UP TO 245 PSI. SEAL
ANY LEAKING JOINTS AND RETEST UNTIL THE SYSTEM IS LEAK FREE. CHARGE THE SYSTEM
1. THE FIRE PROTECTION CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS AND
WITH 25 PSI OF THE SYSTEM REFRIGERANT AND INERT GAS MIXTURE UP TO 245 PSI
MAXIMUM AND RETEST SYSTEM WITH A HALIDE LEAK DETECTOR. SEAL ANY LEAKING JOINTS
CALCULATIONS OF THE NECESSARY WORK REQUIRED. SUBMIT ALL REQUIRED COPIES TO
THE STATE FIRE MARSHALL FOR APPROVAL PRIOR TO THE SUBMISSION TO THE OWNER.
AND RETEST UNTIL THE SYSTEM IS LEAK FREE. CRANK CASE HEATERS SHALL BE ENERGIZED
TWENTY FOUR (24) HOURS PRIOR TO COMPRESSOR ACTIVATION TO ENSURE ALL REFRIGERANT
2. DRAWINGS SUBMITTED TO THE OWNER SHALL BEAR THE "APPROVAL" OR "RELEASE" STAMP
IS OUT OF THE COMPRESSOR.
FROM THE
SUBMITTED
SO ATE FIREAMARSHALLIASHALL A SO BE ATR THIS IMECOMMENiS
2, UPON COMPLETION OF TESTING, THE REFRIGERANT PIPING SYSTEM SHALL BE INSPECTED BY
3. APPROVAL FROM THE OWNER'S INSURANCE CARRIER AND GOVERNING AGENCIES SHALL BE
OBTAINED
THE AUTHORITY HAVING JURISDICTION AS REQUIRED. AFTER SYSTEM APPROVAL BY THE
GOVERNING AUTHORITY THIS CONTRACTOR SHALL INSTALL ALL REFRIGERANT PIPING INSULATION.
PRIOR TO FABRICATION, INSTALLATION, MODIFICATION, ETC., OF THE FIRE PROTECTION
SYSTEM BY THIS CONTRACTOR.
END OF SECTION 15530
4. THE FIRE PROTECTION CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ALL WORK
PERFORMED ON THE FIRE PROTECTION SYSTEM PRIOR TO RECEIVING SAID APPROVALS. NO
SECTION 15800 - HEATING, VENTILATION AND AIR CONDITIONING
ADDITIONAL COMPENSATION SHALL BE AWARDED TO THE FIRE PROTECTION CONTRACTOR FOR
WORK DONE PRIOR TO THE RECEIPT OF SAID APPROVALS IF WORK PERFORMED IS NOT IN A.
RELATED WORK
COMPLIANCE WITH SAID APPROVALS,
F. EQUIPMENT AND MATERIALS
1. HANGERS AND SUPPORTS: SECTION 15145
2. VIBRATION ISOLATION: SECTION 15241
1. FIRE PROTECTION PIPING MATERIALS SHALL BE AS FOLLOWS:
3. MECHANICAL INSULATION: SECTION 15250
4. HYDRONIC PIPING: SECTION 15510
A. SCHEDULE 40, BLACK STEEL PIPE, ASTM A-53 FOR FERROUS PIPING, WELDED AND
5. REFRIGERANT PIPING: SECTION 15530
SEAMLESS, ANSI B-36-10-70 FOR WROUGHT IRON STEEL PIPE.
,
6. TEMPERATURE CONTROL: SECTION 15900
B. CAST IRON OR MALLEABLE IRON SCREWED FITTINGS FOR PIPES TWO INCHES (2")
7. TESTING, ADJUSTING AND BALANCING: SECTION 15990
AND SMALLER. SCREWED OR CAST IRON FLANGED JOINTS FOR PIPES LARGER THE
TWO INCHES (2"). B.
EQUIPMENT AND MATERIALS
C. GALVANIZED OR BLACK MALLEABLE IRON WITH BRASS SEAT SCREWED UNIONS FOR
PIPES TWO INCHES (2") AND SMALLER.
1. ROOFTOP AIR CONDITIONING UNITS SHALL BE AS FOLLOWS:
A. REFER TO THE DRAWINGS FOR ROOFTOP AIR CONDITIONING UNIT SCHEDULE. ALL UNITS
D. VICTAULIC TYPE COUPLINGS ARE ACCEPTABLE WHERE APPROVED BY CODE AND THE
SHALL BE FURNISHED WITH AN EXTENDED FIVE (5) YEAR COMPRESSOR WARRANTY.
OWNER.
E. FIRE PROTECTION PIPING MANUFACTURES
B. ROOF TOP AIR CONDITIONING UNIT MANUFACTURERS
1. CARRIER AIR CONDITIONING; DIVISION OF CARRIER CORPORATION
1. ALLIED TUBE AND CONDUIT CORPORATION
2. MC QUAY INTERNATIONAL
2. BERGER INDUSTRIES
3. JONES AND LAUGHLIN
3. TRANE (THE) COMPANY; DIVISION OF AMERICAN STANDARD, INCORPORATED
4. U.S. STEEL
4. BRYANT AIRCONDITIONING
5. REPUBLIC
C. ALL UNITS SHALL BE FURNISHED WITH A MINIMUM SIXTEEN INCH (16") HIGH ROOF
F. FIRE PROTECTION FITTING MANUFACTURES
CURB BY THE UNIT MANUFACTURER. UNIT MANUFACTURER SHALL ALSO PROVIDE ALL
1. CRANE
NECESSARY VIBRATION ISOLATION EQUIPMENT TO ISOLATE ALL MOVING EQUIPMENT FROM
2. GUSTIN-BACON
THE BUILDING STRUCTURE.
3. ITT GRINNELL-GRUVLOK
4. STOCKHAM
D, ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES,
5. VICTAULIC
ACCESSORIES, ETC. PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS
SHOWN
2. SPRINKLER HEADS SHALL BE AS FOLLOWS:
AND CALLEb FOR ON THE DRAWINGS AND SPECIFIED HEREIN.
A. ALL SPRINKLER HEADS SHALL BE NEW AND RATED FOR 165' F. OR AS REQUIRED BY
THE
E. THE ROOFTOP AIR CONDITIONING EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE
LANDLORD, THE OWNERS INSURANCE CARRIER OR THE AUTHORITY HAVING JURISDICTION.
WITH THE UNIT MANUFACTURERS REQUIREMENTS. MAINTAIN ALL UNIT MANUFACTURER
B. SPRINKLER LOCATED IN A FINISHED CEILING AREA SHALL BE PENDANT MOUNTED ON
REQUIRED CLEARANCES.
CONCEALED PIPING.
C. SPRINKLER HEADS SHALL BE AS FOLLOWS:
F. OUTSIDE, RELIEF AND RETURN AIR DAMPERS SHALL BE OPPOSED BLADE TYPE AND LOW
1. OFFICE: RECESSED PENDANT TYPE, BRIGHT CHROME WITH BRIGHT CHROME ESCUTCHEON,
LEAKAGE.
2. WAREHOUSE & SERVICE GARAGE (NO CEILING): UPRIGHT PENDANT TYPE, ROUGH BRASS.
2. VARIABLE AIR VOLUME (VAV)/FAN POWERED VARIABLE AIR VOLUME (FPVAV) BOXES SHALL BE
3. SPRINKLER HEADS SHALL HAVE A MINIMUM ORIFICE SIZE OF 1/2 OR 17/32 AND
BE AS FOLLOWS:
SHALL BE UL LISTED.
D. THE FIRE PROTECTION CONTRACTOR SHALL VERIFY THE SPRINKLER HEAD REQUIREMENTS
A. REFER TO THE DRAWINGS FOR VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME
PRIOR TO BIDDING.
BOX SCHEDULE.
E. PROVIDE SPARE HEADS AS REQUIRED BY NFPA,
B. VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME BOX MANUFACTURERS:
F. SPRINKLER HEAD MANUFACTURES
1. CARRIER AIR CONDDITIONING; DIVISION OF UNITED TECHNOLOGIES
1. CENTRAL SPRINKLER CORPORATION
2. TITUS PRODUCTS DIVISION
2. GRINNELL FIRE PROTECTION SYSTEMS COMPANY, INCORPORATED
3. TRANE (THE) COMPANY; DIVISION OF AMERICAN STANDARD, INCORPORATED
3. RELIABLE AUTOMATIC SPRINKLER COMPANY, INCORPORATED
4. ENVIRONMENTAL TECHNOLOGIES
4. VIKING CORPORATION
C. ALL EQUIPMENT SHALL] BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES,
G. HANGERS AND SUPPORTS
ACCESSORIES, ETC., PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS
SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN.
1. ALL HANGER AND SUPPORT COMPONENTS SHALL BE PER NEPA.
2. HANGER AND SUPPORT SPACING SHALL BE PER NFPA.
D. THE VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME BOX SHALL BE INSTALLED
3. WHEN MECHANICAL GROOVES OR PUSH ON FITTINGS ARE USED, HANGERS AND SUPPORTS
IN STRICT ACCORDANCE WITH THE UNIT MANUFACTURES REQUIREMENTS.
MAINTAIN ALL UNIT MANUFACTURERS REQUIRED CLEARANCES.
SHALL NOT EXCEED THE MAXIMUM SPACING RECOMMENDED BY THE MANUFACTURE.
H. TEST OF SYSTEM
E. CONTROLS SHALL BE PROVIDED BY THIS CONTRACTOR.
1. THE FIRE PROTECTION CONTRACTOR SHALL FLUSH AND TEST TH(E FI��R//E PROTECTION SYSTEM
F. PROVIDE CONTROLS ACCURATE TO 1.5' F. AND ADJUSTABLE FROM 65' F. TO 85' F.
NFPASTANDARDS. TEOSTHAND PRESSU RESULTSOSHALL I COMPLY OWITHQNFPA. OR PER
ED
G. PROVIDE DUCT PRESSURE POWERED CONTROLS, DESIGNED TO OPERATE WITH DUCT
2. ALL TESTS SHALL BE MADE IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE
PRESSURES FROM 1.0" W.G. TO 5.0" W.G.
OF THE INSURANCE INTEREST. A COMPLETE WRITTEN REPORT OF THE TEST
RESULTS SHALL BE SENT TO THE OWNER OR ARCHITECT WITHIN TEN (10) DAYS OF THE
H. FAN POWERED VARIABLE AIR VOLUME BOX FILTERS SHALL BE ONE INCH (1 ") 30% EFFICIENT
COMPLETION OF THE TESTS STATING THE RESULTS OF THE TEST AND THE NAME OF THE
REPRESENTATIVES
THROWAWAY TYPE WITH MOUNTING CLIPS AND FRAMES FOR HOLDING DISPOSAL MEDIA.
PRESENT DURING THE TEST PRIOR TO FINAL ACCEPTANCE.
3. ANY ALTERATIONS OR REPAIRS SHALL BE MADE IMMEDIATELY AND THE TESTS SHALL BE
RERUN TO PROVE FINAL SECURITY OF THE SYSTEM.
END OF SECTION 15300
1. ALL UNITS SHALL HAVE CERTIFIED SOUND DATA RATINGS AT OR BELOW AN NC LEVEL
OF 35.
3. DUCTWORK SHALL BE AS FOLLOWS:
A. ONE INCH (1 ") THICK FOIL FACED FIBERGLASS DUCT BOARD SHALL BE USED IN LIEU OF
GALVANIZED SHEET METAL DUCTWORK WHEN PERMITTED BY ALL APPLICABLE CODES.
B. VERIFY ALL EXISTING CONDITIONS PRIOR TO THE FABRICATION OF SHEET METAL DUCTWORK.
C. ALL DUCTWORK DIMENSIONS ARE INSIDE CLEAR DIMENSIONS.
D. FABRICATE ALL RECTANGULAR DUCTWORK WITH GALVANIZED SHEET METAL STEEL IN
ACCORDANCE WITH SMANCA, "HVAC DUCT CONSTRUCTION STANDARDS AND ALL REQUIRED
APPLICABLE CODES.
E. FABRICATE ALL ROUND DUCTWORK WITH GALVANIZED SHEET METAL STEEL IN
ACCORDANCE WITH SMANCA, "HVAC DUCT CONSTRUCTION STANDARDS" AND ALL REQUIRED
APPLICABLE CODES, FOR SIZES FOURTEEN INCHES (14") OR LARGER USE SPIRAL
LOCKSEAM CONSTRUCTION. SIZES LESS THAN FOURTEEN INCHES (14'') OR SMALLER MAY
BE SNAP -LOCK CONSTRUCTION. ALL SNAP -LOCK SEAMS SHALL BE SEALED AS SPECIFIED
HEREIN. ROUND FITTINGS SHALL BE GALVANIZED STEEL WITH SPOT WELDED AND BONDED
CONSTRUCTION.
F. ROUND SPIRAL DUCTWORK MAY BE USED IN PLACE OF RECTANGULAR DUCTWORK WHEN
CEILING HEIGHTS PERMIT AND EQUIVALENT FREE AREA IS MAINTAINED. ALL SUPPLY AND
RETURN AIR DUCTWORK WITHIN TEN FEET (10'-0") OF THE AIR CONDITIONING UNIT SHALL
BE RECTANGULAR DUCTWORK AND INTERNALLY INSULATED.
G. DUCTWORK CLASSIFICATION SHALL BE AS FOLLOWS:
A. LOW PRESSURE
1. SUPPLY AND RELIEF AIR DUCTWORK: 2" W.G. POSITIVE
2. RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK: 2" W.G. NEGATIVE
B, MEDIUM PRESSURE
1. SUPPLY AIR DUCTWORK: 3" W.G. POSITIVE
H. INSTALL TURNING VANES IN ALL SUPPLY AIR RIGHT ANGLE ELBOWS.
1. INSTALL ALL DUCTWORK SUPPORTS IN ACCORDANCE WITH SMACNA STANDARDS, AND ALL
APPLICABLE CODES. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY APPLICABLE CODES.
J. DUCTWORK TRANSITIONS SHALL NOT EXCEED THIRTY DEGREE (30') SLOPE UNLESS NOTED
OTHERWISE.
K. PROVIDE ACCESS TO ALL MANUAL VOLUME DAMPERS, MOTORIZED DAMPERS, FIRE DAMPERS,
CONTROLS, ETC., THAT REQUIRE SERVICE OR INSPECTION. MINIMUM ACCESS PANEL SIZE
SHALL BE 24" X 24". SUPPLY AIR DIFFUSERS AND RETURN AND EXHAUST AIR GRILLES OR
REGISTERS WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS.
L. PROVIDE CONICAL OR "BELL -MOUTH" TAKE -OFFS FROM MAIN DUCTWORK TO BRANCH
DUCTWORK.
4. FLEXIBLE CONNECTIONS SHALL BE AS FOLLOWS:
A. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT ALL CONNECTIONS B EEN VIBRATING
EQUIPMENT AND DUCTWORK OR CASINGS. PROVIDE FLEXIBLE CONNEC IONS WHERE
DUCTWORK CROSSES BUILDING EXPANSION JOINTS.
B. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE COAT FLAMEPROOF
FABRIC. PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR MOVEM T AND PREVENT
THE TRANSMISSION OF VIBRATION.
5. FLEXIBLE DUCTWORK SHALL BE AS FOLLOWS:
A. FLEXIBLE DUCTWORK SHALL BE ONE INCH _(1 ") INSULATED CLASS 1 A, D RATED FOR THE
OPERATING PRESSURE OF THE SYSTEM, DUUCTWORK CONSTRUCTION M TERIAL SHALL BE
IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES.
VERIFY ALL REQUIREMENTS PRIOR TO BIDDING.
B. FLEXIBLE DUCTWORK MANUFACTURERS
1. GENFLEX #SLR -25C
2. NORFLEX
3. OWENS CORNING INL=-25
4. THERMAFLEX #G- M
5. WIREMOLD
C. FLEXIBLE DUCTWORK SHALL NOT EXTEND OVER THREE FEET (3'--0" IN LENGTH AT ANY
ONE (1) LOCATION, AND SHALL NOT BE USED AS A REPLACEMENT FOR ELBOWS.
6. MANUAL VOLUME DAMPERS SHALL BE AS FOLLOWS:
A. LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH
DUCTWORK TO THE SUPPLY AIR DIFFUSER.
B. MANUAL VOLUME DAMPERS MANUFACTURERS
1. AMERICAN WARMING AND VENTILATING, INCORPORATED
2. LOUVERS AND DAMPERS, INCORPORATED FC
3. NAILOR HART �/ C��®
5. RUSIO NAL CONTROLLED AIR ,�r��,`C.a o o ,
,
„- i 4 VL
C. OPERATING HANDLES ON ALL DAMPERS SHALL BE A MINIMUM EIGHTEEN INCHES (18) LCiRG. QF ,.
7. FIRE DAMPERS SHALL BE AS FOLLOWS: `� 10 0� O�V
A. PROVIDE FIRE DAMPERS AS SHOWN AND CALLED FOR ON THE DRAWINGS, SPECIFIED
REQUIRE BY APPLICABLE CODE.
B. FIRE DAMPER MANUFACTURERS
1. AMERICAN WARMING AND VENTILATING, INCORPORATED
2. LOUVERS AND DAMPERS, INCORPORATED
3. NAILOR HART
4. NATIONAL CONTROLLED AIR
5. RUSKIN
C. ALL FIRE DAMPERS SHALL BE UL LABELED.
D. THIS CONTRACTOR SHALL PROVIDE ALL NECESSARY LINTELS, FRAMING, SLEEVES, ETC., AS
REQUIRED FOR FIRE DAMPER INSTALLATION.
E. REFER TO THE FIRE DAMPER DETAIL ON THE DRAWINGS.
8. DIFFUSERS, REGISTER AND GRILLES SHALL BE AS FOLLOWS:
A. REFER TO THE DRAWINGS FOR THE DIFFUSER, REGISTER AND GRILLE SCHEDULE.
B. DIFFUSERS, REGISTER AND GRILLE MANUFACTURERS
1: ANEMOSTAT
2. PRICE
3. TITUS
9. ?OOF/EQUIPMENT CURB AND PIPE SUPPORT CURB SHALL BE AS FOLLOWS:
F,. THIS CONTRACTOR SHALL PROVIDE ALL THE NECESSARY CURBING AND FRAMING AS
REQUIRED TO INSTALL ALL ROOF MOUNTED EQUIPMENT AND PIPING ABOVE THE ROOF AS
DESCRIBED, IMPLIED OR SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN.
ROOF/PIPE CURB HEIGHT SHALL BE A MINIMUM OF SIXTEEN INCHES ��(16" ABOVE ROOFING
MEMBBRANE. ALL CURBS MUST BE INSTALLED SO THAT THE TOP IS DEAD LEVEL.
ALL ROOF CURBS SHALL BE FULL PERIMETER.
END OF SECTION 15800
SECTION 15900 - TEMPERATURE CONTROL
A. RELATED WORK
1. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800
B. EQUIPMENT AND MATERIALS
1. THIS CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE TEMPERATURE CONTROL SYSTEM
TO AUTOMATICALLY CONTROL THE HEATING, VENTILATION, AND AIR CONDITIONING EQUIPMENT AND
OTHER COMPONENTS AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN.
FAILURE TO MENTION ANY SPECIFIC DEVICE DOES NOT RELIEVE THE MECHANICAL CONTRACTOR
OF THE RESPONSIBILITY FOR THE FURNISHING OR INSTALLATION OR PROVIDING THE DEVICES OR
ITEMS NECESSARY IN ORDER TO ACHIEVE THE INTENT OF THE DRAWING OR SPECIFICATIONS,
2. ALL CONTROL WIRING SHALL BE TWENTY FOUR VOLT (24 V.) AND SHALL BE FURNISHED AND
INSTALLED BY THIS CONTRACTOR. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH
ALL APPLICABLE CODES. ALL CONTROL WIRING SHALL BE IN CONDUIT,
3. ZERO TO ONE HUNDRED PERCENT (O - 100%) OUTSIDE AIR ECONOMIZER CONTROL SHALL
CONSIST OF LOW LEAKAGE OUTSIDE, RETURN AND EXHAUST AIR DAMPERS, MOTOR AND
ADJUSTABLE ENTHALPY CONTROLLER MOUNTED IN THE OUTSIDE AIR STREAM OF EACH UNIT. AN
ENTHALPY CONTROLLER SHALL BE PROVIDED TO SENSE THE DRY BULB TEMPERATURE AND RELATIVE
HUMIDITY OF THE OUTSIDE AIR FOR USE IN THE COOLING CYCLE. THE ENTHALPY CONTROLLER
SHALL PREVENT THE COMPRESSOR OPERATION WHEN THE OUTSIDE AIR AND HUMIDITY CAN
SATISFY THE COOLING LOAD. THE OUTSIDE AND RELIEF AIR DAMPER MOTORS SHALL BE OF
THE MODULATING SPRING TYPE TO CLOSE WHENEVER THE UNIT IS IN UNOCCUPIED MODE.
SECTION 15990 -TESTING, ADJUSTING AND BALANCING
A. REL ATED WORK
1. HYDRONIC PIPING: SECTION 15510
2. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800
B. GENERAL REQUIREMENTS
1. TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE MADE BY A SEPARATE AND
INDEPENDENT CONTRACTOR WHO IS CURRENTLY A LICENSED ASSOCIATED AIR BALANCING COUNCIL
�AABC) OR A NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB) BALANCING CONTRACTOR.
Ivo OTTHER BALANCE REPORTS SHALL BE ACCEPTED OR REVIEWED. ALL BALANCING WORK
SHALL BE DONE IN ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY.
PAYMENT OF ALL COSTS FOR THE TESTING AND BALANCING SHALL BE INCLUDED IN THE
MECHANICAL CONTRACTORS BID.
2. ALL TESTING, ADJUSTING AND BALANCING AND REPORTS MUST BE COMPLETED AND SUBMITTED
TO THE ENGINEER PRIOR TO THE FINAL ACCEPTANCE OF THE SYSTEMS.
3. THE MECHANICAL CONTRACTOR SHALL BE PRESENT FOR THE AIR BALANCE TO VERIFY
ACCESSIBILITY TO ALL DEVICES, VERIFY ALL OPERATING SEQUENCES AND INSTALL NEW FILTERS
PACE WITH THE OUTSIIDE AIR DAMPERSBIN�THE MINIMUM OPOSITION,AIUNBLESSNNOTED OT ERWISE.
4. AIR AND WATER QUANTITIES SHALL BE BALANCED TO WITHIN (+ -) TEN PERCENT (10%)
OF THE INDICATED QUANTITY AS SHOWN AND CALLED FOR ON THE DRAWINGS. ANY
R'QUIRED CHANGES IN SHEAVES BELTS, PULLEYS OR THE ADDITION OF DAMPERS REQUIRED
TO ACHIEVE SPECIFIED FLOW RATES SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR
AT NO ADDITIONAL COMPENSATION TO THE OWNER.
5. THE BALANCE REPORT SHALL BE ON THE AABC NATIONAL STANDARD REPORT FORMS OR
THE NEBB CERTIFIED REPORT FORMS AS PUBLISHED IN THEIR MOST CURRENT EDITIONS
HND SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION: (WHERE APPLICABLE)
A. AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF SEPARATE AND INDEPENDENT
BALANCING CONTRACTOR.
B. A COPY OF A CERTIFICATE OF CONFORMANCE WITH NATIONAL STANDARDS FOR THIS
PROJECT.
C. INSTRUMENTATION LIST WITH LAST CALIBRATION DATES.
D. MAKE AND MODEL NUMBER OF ALL HVAC EQUIPMENT TESTED.
E. CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY
PITOT TUBE DUCT TRAVERSE AT EACH UNIT,
F. MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR
EACH LEG.
G. MOTOR AND FAN RPMS, SHEAVE SIZES, AND BELT SIZES,
H. OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AND VOLUMES SHALL BE
MEASURED AT FULL COOLING WITH MINIMUM OUTSIDE AIR. RETURN AND RELIEF SHALL
BE BALANCED AND MEASUREMENTS RECORDED BY PITOT DUCT TRAVERSE AT FULL
ECONOMIZER AND POWER EXHAUST.
I. WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE AND
PRESSURE READINGS.
J. MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT.
K. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHEN DUCTED).
6. ALL CONTROL SEQUENCES SHALL BE TESTED (INTERLOCKED EQUIPMENT, SMOKE DETECTORS,
SMOKE EVACUATION, ECONOMIZER, ETC.) AND OPERATING STATUS RECORDED IN THE REPORT.
7. THREE (3) COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED TO THE ENGINEER
FOR AP ROVAL. THE OWNER OR ARCHITECT SHALL RETURN ONE (_1) APPROVED BALANCE
REPORT TO THE MECHANICAL CONTRACTOR. THIS BALANCE REPORTT SHALL APPEAR
IN THE OPERATIONS MANUAL.
8. THE BALANCING CONTRACTOR SHALL MAK A RETURN INSPECTION OF THE SYSTEM DURING
THE NEXT SEASON (HEATING OR COOLING CYCLE.
END OF SECTION 15990
FROST
ENGINEERS
920 N. Shadeland Ave., Suite G -I IA
Indianapolis, Indiana 46219
Phone 317.359.0901
Fax 317.359.0902
mfrost@frostengineers.,6om
Seal
,`` %J111Jtllf,11��
��,,, P, S. F,q� '
��� G 1 S7*tk s%' iii
�� No. ��
2 * *
:60910220: CC =
.. CTATC nC _ ft
Revision
Project No.
DD04001
Date
4-13-04
Scale
NO SCALE
----
�.
Checked By
MSF
,'';
I I_�
=_i_
rfl
_ __
�-
; �
_
1-1
�.�,'
i�
-
(�i
F_
_ -_
L�_�
\
~i
)__
,_T_I
-
,:.
- -
(�1.
=1.
�--
->,
==-
r.
-
l.%
�;
---
Seal
,`` %J111Jtllf,11��
��,,, P, S. F,q� '
��� G 1 S7*tk s%' iii
�� No. ��
2 * *
:60910220: CC =
.. CTATC nC _ ft
Revision
Project No.
DD04001
Date
4-13-04
Scale
NO SCALE
Drawn By
MSF
Checked By
MSF
9rtA T k
MECHAMCAL
3PECIRCATIONS
OhmW�
MO
FROST
ENGINEERS
920 N. Shadeland Ave., Suite G-11 A
Indianapolis, Indiana 46219
Phone 317.359.0901
Fax 317.359.0902
mfrost@frostengineers.com
1 V �
RG 1
r
G 10
1000 r P 0
OFFICE 325 >:
10
10 12
° x SDBD -1 W
10"91 r = 325 CFM o
o x
BD BD N coD
CL
325 CFM
x 0
s ( �
PQ ® w
RG -1
U1 w
T
;;Ow LL U
w LLZ
A 0�
HEAT PUMP O
HEAT PUMP EXISTING 42,000 BTUH rw 0
N EXISTING 28,000 BTUH 00 CL
" MECHANICAL PLAN Wco M
SCALE: ,/
MECHANICAL PLAN — DEMO S L : 4" = 1'-0" >- " Z
a UJ LU SCALE: 1/4" = 1'-0"he
Z
0
NOTES:
OREMOVE DUCT WORK TO THIS POINT
ORELOCATE EXISTING THERMOSTAT
A.) METALLIC FLEXIBLE DUCTWORK SHALL BE ATTACHED
USING A MINIMUM OF THREE (3) #8 SHEET METAL
SCREWS EQUALLY SPACED AROUND THE DUCTWORK
CIRCUMFERENCE. DUCTWORK LARGER THAN 12"
SHALL HAVE A MINIMUM OF FIVE (5) 18 SHEET
METAL SCREWS. SCREWS SHALL BE LOCATED
AT LEAST 1/2" FROM THE DUCTWORK END.
B.) NON-METALLIC FLEXIBLE DUCTWORK SHALL BE SECURED
TO THE SLEEVE OR COLLAR USING A DRAW BAND.
IF THE DUCTWORK COLLAR EXCEEDS 12". THE DRAW
BAND MUST BE POSRIONED BEHIND A BEAD ON THE
METAL COLLAR.
C.) INSULATION AND VAPOR BARRIERS PRESENT ON
FACTORY -FABRICATED DUCTWORK SHALL BE FITTED
OVER THE CORE CONNECTION AND SHALL BE
SUPPLEMENTALLY SECURED WITH A DRAW BAND.
D.) FLEXIBLE DUCTWORK SEALING SHALL BE A CLASS "B"
SEAL FOR LOW PRESSURE DUCTWORK.
E.) SUPPORT SYSTEM SHALL. NOT DAMAGE
OR CAUSE OUT OF ROUND SHAPE.
F.) ALL DUCTWORK SHALL BE PROVIDED WITH
SEISMIC RESTRAINTS WHERE REQUIRED BY
CODE OR THE LANDLORD. REFER TO THE
"SEISMIC RESTRAINT MANUAL: GUIDELINES
FOR MECHANICAL SYSTEMS DATED 1991. AS
PUBLISHED BY THE SHEET METAL AND AIR
CONDITIONING CONTRACTORS NATIONAL
ASSOCIATION, INC. FOR REQUIREMENTS.
G.) REFER TO MECHANICAL SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
SPIN -IN FITTING, BELLMOUTH
WHERE POSSIBLE.
INSULATED FLEXIBLE DUCTWORK.
MAXIMUM 3'-0" LENGTH AND NO
90' BENDS.
SUPPLY AIR DIFFUSER
COLLAR WITH VOLUME DAMPER
AND LOCK
12" MINIMUM
INSULATED FLEXIBLE DUCTWORK
SQUARE TO ROUND FITTING BY
DIFFUSER MANUFACTURER. REFER
TO DIFFUSER, REGISTER AND GRILLE
SCHEDULE FOR PROVIDED ACCESSORIES.
CEILING
DIFFUSER, REGISTER AND GRILLE SCHEDULE
TAG NO.
PATTERN
NECK SIZE
FACE SIZE
MODULE SIZE
FRAME STYLE
MATERIAL
FINISH
CFM RANGE
ACCESSORIES
MANUFACTURER
MODEL NO.
NOTES
RG -1
-
240X24"
24"X24"
-
TYPEI3
ALUMINUM
WHITE
0 - 1,500
-
TITUS
50 F
2
SD -1
T -4 -WAY
10"o
24"X24"
24"X24"
TYPE
ALUMINUM
WHITE
250 - 400
-
TTAUS
SA
-
NOTES:
1. REFER TO MECHANICAL DRAWINGS FOR DIFFUSER DISCHARGE ARRANGEMENT PATTERN.
2. 1" X 1" X 1" GRID SIZE
Seal
*. No.
w � :60910220:
STATE OF
;i F ��'' �h!0 I ANS•' �� ��:
Revision
Project No. I DD04001
Date 1 4-13-04
Scale 1/4 n = 1 #-0"
Drawn By MSF
Checked By MSF
Sheet Title
MECHANICAL
PLANS
Sheet No.
M1
SECTION 16010 - BASIC ELECTRICAL REQUIREMENTS
A. DEFINITIONS ANO TERMS
1. THE WORD "OWNER" SHALL MEAN ANY REPRESENTATIVE OF HIS PARTY DULY
AUTHORIZED TO ACT IN HIS BEHALF IN THE EXECUTION OF ANY WORK.
2. THE WORD "CONTRACTOR" SHALL MEAN THE PERSON, FIRM OR CORPORATION
ENTERING INTO A CONTRACT OR AGREEMENT WITH THE OWNER TO CONSTRUCT
AND COMPLETE THE WORK AS SHOWN ON THE DRAWINGS AND SPECIFIED
HEREIN.
3. THE WORD "ARCHITECT OR ENGINEER" SHALL MEAN REPRESENTATIVES
THEIR REPRESENTATIVES ACTING AS THE OWNER APPOINTED AGE
4. THE WORD "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE PROJECT
SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION AND SIMILAR
SUBSEQUENT REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND CALLED
ON THE DRAWINGS AND SPECIFIED HEREIN.
5. THE WORD "INSTALL" SHALL MEAN OPERATIONS AT THE PROJECT SITE, INCLUDING,
BUT NOT LIMITED TO, UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING,
ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING,
CLEANING, AND SIMILAR REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND
ON THE DRAWINGS AND SPECIFIED HEREIN.
6. THE TERM "PROVIDED" SHALL BE INTERPRETED AS MEANING "FURNISHED AND
INSTALLED" BY THIS CONTRACTOR WITH THE EXCEPTION WHERE ITEMS ARE
PROVIDED BY THE OWNER" WHICH MEANS "FURNISHED ONLY" AND INSTALLED
BY THIS CONTRACTOR, UNLESS NOTED OTHERWISE. REFER TO THE
RESPONSIBILITY SCHEDULES FOR ADDITIONAL INFORMATION.
B. SUMMARY OF WORK
1. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT,
PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES
NECESSARY FOR AND REASONABLY IMPLIED, AND INCIDENTAL TO, THE
FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK
FOR ALL INSTALLED SYSTEMS AS SHOWN AND CALLED FOR ON THE
DRAWINGS AND SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS.
THESE CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
A. A COMPLETE ELECTRICAL DISTRIBUTION SYSTEM INCLUDING THE
INSTALLATION OF PANELBOARDS, SAFETY AND DISCONNECT SWITCHES,
MOTOR STARTERS, LIGHTING CONTACTORS AND TRANSFORMER. IT IS
THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INCLUDE
IN HIS BID THE NECESSARY SERVICE EQUIPMENT OR TO OBTAIN SERVICE FROM
THE LOCAL UTILITY COMPANY. THIS CONTRACTOR SHALL ALSO INCLUDE IN THE
BID ALL NECESSARY MATERIALS REQUIRED TO COMPLETE THE SYSTEM
INCLUDING, BUT NOT LIMITED TO, FEEDERS, BRANCH CIRCUITS, JUNC_i ION
BOXES, OUTLET BOXES, WIRING DEVICES, COVERPLATES, CONDUITS, ETC.
B. METERING AND CURRENT TRANSFORMERS AS REQUIRED BY THE DRAWINGS
OR SPECIFIED HEREIN, THE UTILITY COMPANY REGULATIONS.
C. THE WIRING OF MECHANICAL EQUIPMENT AS OUTLINED ON THE DRAWINGS
OR SPECIFIED HEREIN. WORK SHALL INCLUDE ALL STARTERS, DISCONNECTS,
AND POWER WIRING OF MECHANICAL EQUIPMENT EXCEPT UNLESS NOTED
OTHERWISE. ALL LOW VOLTAGE (24 VOLT) TEMPERATURE CONTROL WIRING
SHALL BE BY THE MECHANICAL CONTRACTOR UNLESS NOTED OTHERWISE.
D. THE INSTALLATION OF LIGHT FIXTURES AND LAMPS AS SHOWN AND CALLED
FOR ON THE DRAWINGS OR SPECIFIED HEREIN, INCLUDING ALL DEVICES,
EQUIPMENT, ETC., REQUIRED FOR MOUNTING.
E. A CONDUIT SYSTEMFOR TELEPHONE/DATA INCLUDING THE TERMINAL BOARD,
BRANCH CONDUITS, OUTLET BOXES, PULL WIRES, GROUND CONDUCTORS, ETC.,
AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN.
F. A COMPLETE EMERGENCY AND EXIT LIGHTING SYSTEM AS SHOWN AND CALLED
FOR ON THE DRAWINGS OR SPECIFIED HEREIN.
G. TEMPORARY SERVICE AS SPECIFIED HEREIN AND ITS REMOVAL.
H. ALL FINAL CONNECTIONS TO SIGNS, LIGHTING, OWNER PROVIDED EQUIPMENT, ETC.,
AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN.
I. THE INSTALLATION AND WIRING OF SPEAKERS, CONDUIT, ETC., FOR A SOUND
SYSTEM AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN.
J. ALL SMOKE/FIRE ALARM WIRING, DEVICES, CONDUITS, ETC., AS REQUIRED TO
MEET ALL FEDERAL, STATE AND LOCAL APPLICABLE CODES AND
INSURANCE AND FIRE DEPARTMENT REQUIREMENTS AS SHOWN AND CALLED FOR
ON THE DRAWINGS OR SPECIFIED HEREIN.
K. THE INSTALLATION OF CONDUITS STUBBED ABOVE THE CEILING FOR HVAC AND/OR
LIGHTING CONTROL PANELS AND ANY ADDITIONAL CONDUIT FOR HVAC EQUIPMENT
CONTROL WIRING WHERE PLENUM RATED CABLES ARE NOT PERMITTED.
2. WORK NOT INCLUDED OR TO BE PROVIDED BY THIS CONTRACTOR SHALL BE AS FOLLOWS:
A. LOW VOLTAGE (24 VOLT) TEMPERATURE CONTROL WIRING FOR HVAC EQUIPMENT.
B. TELEPHONE DEVICES AND WIRING UNLESS NOTED OTHERWISE ON THE DRAWINGS.
C. DATA LINE WIRING.
C. GENERAL REQUIREMENTS
1. THIS CONTRACTOR SHALL VERIFY THE EXTENT OF ALL EXISTING CONDITIONS,
UTILITY CONNECTION POINTS, EQUIPMENT PROVIDED BY OTHERS, ETC., AS
SHOWN AND CALLED FOR ON THE DRAWINGS AND REPORT ANY DISCREPANCIES
TO THE ENGINEER PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF
KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE
REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. NO
ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE
OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE
REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE
OF KNOWLEDGE OF EXISTING CONDITIONS BY VISITING THE SITE PRIOR TO BIDDING
DOES NOT RELIEVE THIS CONTRACTOR OF RESPONSIBILITY IN WORK OR WORKMANSHIP.
2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER
AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN
THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR
WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE
SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK,
AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE
PROVIDED AS PART OF THIS CONTRACT.
3. ALL WORK BY THIS CONTRACTOR SHALL BE INSTALLED SO AS TO BE READILY
ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS
CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE
OF THE EQUIPMENT AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES.
4. ALL ROOF CUTTING, PATCHING AND FLASHING SHALL BE BY THE OWNER'S
ROOFING CONTRACTOR OR OWNER'S APPROVED ROOFING CONTRACTOR AT THIS
CONTRACTOR'S EXPENSE, COORDINATE ALL ROOF PENETRATIONS,
5. THIS CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL OR SUPPORTS
TO SUPPORT ANY INSTALLED EQUIPMENT AS SHOWN AND CALLED FOR ON THE
DRAWINGS OR IN THE SPECIFICATIONS. THIS CONTRACTOR SHALL COORDINATE ALL
ADDITIONAL STEEL OR SUPPORT LOCATIONS WITH THE OWNER PRIOR TO BIDDING
AND INSTALLATION.
6. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF
OF THE FLOOR FOR ALL INSTALLED CONDUIT, SLEEVES, ETC., AS SHOWN AND
CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. COORDINATE ALL FLOOR
CUTS WITH THE OWNER. CUTTING AND PATCHING
SHALL BE HELD TO A MINIMUM.
7. ALL SWITCH GEAR, CIRCUIT BREAKERS AND DISCONNECTS IN SWITCH GEAR,
PANELBOARDS, TRANSFORMERS, TIME CLOCKS, THERMAL OVERLOAD FAN
SWITCHES, EQUIPMENT CONTROL SWITCHES, SAFETY SWITCHES, MOTOR
STARTERS, AND SIMILAR ITEMS SHALL BE IDENTIFIED BY NAME, FUNCTION,
AND/OR CONTROL. N NAMEPLATES SHALL BE AT LEAST 1" X 3" WITH
CHARACTERS NOT LESS THAN 1/4". THEY SHALL BE MADE UP OF PLASTIC -
LAMINATED TAGS AND CHARACTERS ENGRAVED TO ENGRAVER'S STANDARD
THICKNESS AND LETTER STYLE WITH WHITE CORE AND BLACK BACKGROUND.
NAMEPLATES SHALL BE FASTENED WITH POP RIVETS OR SCREWS.
8. PROVIDE TYPED DIRECTORIES IN PANELBOARDS TO DEPICT ACTUAL EQUIPMENT
CONNECTED TO INDIVIDUAL BREAKERS/SWITCHES.
D. CODES, FEES AND MISCELLANEOUS COSTS
1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE
CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS,
REQUIREMENTS AND UTILITY COMPANY REGULATIONS.
2. IN CASES OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, STATE
LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER REQUIREMENTS,
UTILITY COMPANY REGULATIONS AND THE CONTRACT DOCUMENTS, THE MOST
STRINGENT SHALL GOVERN. THIS CONTRACTOR SHALL PROMPTLY NOTIFY THE
ENGINEER IN WRITING OF ANY SUCH DIFFERENCE.
3. NON-COMPLIANCE: SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT
COMPLY WITH THE REQUIREMENTS OF APPLICABLE BUILDING CODES, STATE LAWS,
LOCAL ORDINANCES, INDUSTRY STANDARDS, UTILITY COMPANY
REGULATIONS OR THE CONTRACT DOCUMENTS, THIS CONTRACTOR SHALL BEAR ALL
COSTS ARISING FOR THE CORRECTION OF NON -COMPLYING ITEMS.
4. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL FEDERAL AND STATE LAWS,
LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND
APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. THOSE
REQUIREMENTS ARE TO BE CONSIDERED A MINIMUM AND ARE TO BE EXCEEDED WHEN
SO INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. THIS CONTRACTOR SHALL
INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES AND STANDARDS AND ANY
CHANGES OR MODIFICATIONS TO THE DRAWINGS OR SPECIFICATIONS AS REQUIRED BY
THE CODES SHALL BE INCLUDED IN THE BID. NO ADDITIONAL COMPENSATION SHALL
BE AWARDED TO THE CONTRACTOR FOR FAILURE OF CODE INQUIRY OR COMPLIANCE.
5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PAYMENT OF
ALL FEES, NECESSARY DRAWINGS AND ARRANGING AND PAYING FOR ALL INSPECTIONS,
TESTS, ETC., WHICH MAY BE REQUIRED BY ANY AUTHORITY OR UTILITY COMPANY IN
CONNECTION WITH THE FURNISHING OR INSTALLATION OF ANY OF HIS RESPECTIVE WORK.
E. WORK AND -WORKMANSHIP
1. ALL MATERIALS AND EQUIPMENT SHALL BE OF THE HIGHEST QUALITY IN EVERY RESPECT.
ALL MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, OF THE LATEST
DESIGN AND FREE OF DEFECTS.
2. WORKMANSHIP SHALL BE BY SKILLED WORKMEN OF HIGHEST STANDARD IN STRICT
ACCORDANCE WITH ALL APPLICABLE MANUFACTURERS PRINTED SPECIFICATIONS, PERFORMED
UNDER SUPERVISION OF COMPETENT FOREMAN AT ALL TIMES.
3. THE OWNER AND THE ARCHITECT HAVE FULL POWER TO CONDEMN OR REJECT ANY WORK,
MATERIALS OR EQUIPMENT NOT IN ACCORDANCE WITH THESE SPECIFICATIONS AND DRAWINGS
OR ARE NOT IN CONFORMANCE WITH THE MANUFACTURES SPECIFICATIONS OR DRAWINGS
WHICH WERE APPROVED BY THE OWNER OR ARCHITECT.
4. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE REMOVED AND REPLACED TO THE
SATISFACTION OF THE OWNER OR ARCHITECT AT THIS CONTRACTORS EXPENSE. WORK
OR EQUIPMENT THAT IS REJECTED SHALL BE SO STATED IN WRITING BY THE OWNER
OR THE ARCHITECT.
5. SUCH DECISIONS AS THE OWNER OR THE ARCHITECT MAY MAKE WITH RESPECT TO
QUESTIONS CONCERNING THE QUALITY, FITNESS OF MATERIALS, EQUIPMENT AND
WORKMANSHIP SHALL BE BINDING UPON THE PARTIES THERETO,
F. DEVIATIONS FROM DRAWINGS
1. THE DRAWINGS SHOW THE INTENDED ARRANGEMENT OF ALL CONDUITS, LIGHT FIXTURES,
PANELBOARDS, EQUIPMENT AND APPURTENANCES. THEY SHALL BE FOLLOWED AS
CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL
PERMIT.
2. THIS CONTRACTOR SHALL INVESTIGATE STRUCTURAL AND FINISH CONDITIONS
AFFECTING HIS WORK AND SHALL PROVIDE ANY FITTINGS, OFFSETS AND ACCESSORIES
REQUIRED TO ACCOMMODATE SAID CONDITIONS IN THE BID PROPOSAL.
3. WHERE TRADE NAMES AND MANUFACTURES ARE USED ON THE DRAWINGS OR
SPECIFIED HEREIN, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE
BASE BID. MANUFACTURES CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS
TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY THE OWNER OR
THE ENGINEER PRIOR THROUGH SHOP DRAWING OR SUBMITTAL PROCESS, TO
ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO
REMOVAL AND REPLACEMENT AT THIS CONTRACTORS EXPENSE.
4. THE DRAWINGS INDICATE AN INSTALLED SYSTEM BASED UPON SELECTED MANUFACTURERS
OF EQUIPMENT, ELECTRICAL SERVICES, SIZE, CONFIGURATIONS, ETC., ARE CONSISTENT
WITH THE MANUFACTURER'S RECOMMENDATIONS. OTHER MANUFACTURERS ARE ENCOURAGED
TO FURNISH EQUIPMENT FOR THIS PROJECT; HOWEVER, IT SHALL BE THIS CONTRACTORS
RESPONSIBILITY TO ASSURE THAT THE EQUIPMENT IS CONSISTENT WITH THE DESIGN BASE.
NO ADDITIONAL COMPENSATION SHALL BE AWARDED FOR REVISIONS, MODIFICATIONS, ETC.,
TO ELECTRICAL SERVICES, WIRING, BREAKERS, SPACE, CLEARANCE, CONDUIT, PANELBOARDS,
ETC., REQUIRED BY OTHER MANUFACTURES.
5. THE LOCATION OF OUTLETS, PANELBOARDS, ELECTRICAL EQUIPMENT, ETC., AS SHOWN AND
CALLED FOR ON THE DRAWINGS IS APPROXIMATE AND THE OWNER OR THE LANDLORD SHALL
HAVE THE RIGHT TO RELOCATE ANY SAID EQUIPMENT, RECEPTACLES, LIGHT FIXTURES, ETC.,
UPON THEIR REQUEST AT NO ADDITIONAL COMPENSATION TO THIS CONTRACTOR.
G. HANGERS AND _SUPPORTS
1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, WIRE,
UNISTRUT, C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC.,
NECESSARY FOR THE INSTALLATION OF WORK.
2. HANGERS AND SUPPORTS SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE
OR MASONRY, BUT NOT TO OR FROM OTHER CONDUIT, PIPING, EQUIPMENT, DUCTWORK,
SOFFIT, NEUTRAL PIERS, PIPING DUCTWORK, METAL ROOF DECK,
LATERAL BRACING, BRIDGING, OR CONDUIT. HANGERS SHALL BE ATTACHED TO THE UPPER
CHORD OF THE BAR JOIST. HANGING FROM THE METAL DECK IS NOT PERMITTED. WHERE
INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT CONDUIT, THIS CONTRACTOR SHALL
INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY
DO NOT INTERFERE WITH ACCESS DOORS TO FIRE DAMPERS, VALVES, JUNCTION BOXES,
ACCESS DOORS, EQUIPMENT, ETC. HANGER TYPES AND INSTALLATION METHODS SHALL
BE SUBJECT TO ALL APPLICABLE CODES.
H. OCCUPATIONAL SAFETY AND HEALTH ACT
1. ALL WORK SHALL BE COMPLY WITH THE CURRENT REQUIREMENTS OF THE U.S.
DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, ENTITLED
OCCUPATIONAL SAFETY AND HEALTH STANDARDS; NATIONAL CONSENSUS STANDARDS
AND ESTABLISHED FEDERAL STANDARDS.
I. COORDINATION BETWEEN CONTRACTORS
1. BEFORE THE COMMENCEMENT OF ANY WORK, THIS CONTRACTOR SHALL EXAMINE
ALL THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS
COMPONENTS OF THE INSTALLED SYSTEMS, MATERIALS, CONDUIT, EQUIPMENT, ETC.,
WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES
AND CONFLICTS.
2. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO LEAVE THE REQUIRED, NECESSARY
ROOM FOR OTHER TRADES. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO
THIS CONTRACTOR FOR FAILURE TO COORDINATE WITH OTHER TRADE CONTRACTORS
TO AVOID OTHER TRADE INTERFERENCES, CONFLICTS, RELOCATION OF PANELBOARDS,
CONDUIT, EQUIPMENT, ETC., FOUND ENCROACHING ON SPACE REQUIRED BY OTHERS.
3. THIS CONTRACTOR SHALL PROVIDE COMPLETE INFORMATION AND COOPERATION TO
THE OTHER CONTRACTORS AND TRADES PERTAINING TO HIS WORK TO ACCOMPLISH
COORDINATION OF THE COMPLETED PROJECT.
J. EQUIPMENT DRAWINGS
1. THIS CONTRACTOR SHALL PROVIDE EQUIPMENT DRAWINGS OF PROVIDED EQUIPMENT
AS SPECIFIED HEREIN.
2. THE FOLLOWING ITEMS ARE A MINIMUM REQUIREMENT FOR EACH EQUIPMENT DRAWING
SUBMITTAL:
A. SHEET SIZE 8-1/2" X 1 1 ".
B. MANUFACTURE'S STANDARD SCHEMATIC DRAWINGS:
1. MODIFY DRAWINGS TO DELETE INFORMATION THAT IS NOT APPLICABLE TO
APPLICABLE TO THIS PROJECT.
2. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION
C. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES,
PERFORMANCE CHARTS, ILLUSTRATIONS AND OTHER STANDARD DESCRIPTIVE DATA.
1, CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS,
REQUIRED.
2. SHOW EQUIPMENT DIMENSIONS AND MAINTENANCE OR CONSTRUCTION CLEARANCES
3. SHOW PERFORMANCE CHARACTERISTICS AND CAPABILITIES.
4. SHOW WIRING DIAGRAMS AND CONTROLS.
5. MATERIAL AND SAFETY DATA SHEETS.
6. THE FULL MANUFACTURE'S MODEL NUMBER OF EACH ITEM.
7. IDENTIFICATION OF COLOR OR FINISHES.
8. THIS CONTRACTOR'S STAMP, SIGNATURE AND DATA SHALL BE AFFIXED TO EACH
3. COPIES OF THE EQUIPMENT DRAWINGS AND ALL OTHER RELATED INFORMATION MUST APPEAR
IN THE OPERATIONS MANUAL LEFT ON SITE AFTER PROJECT COMPLETION.
K. RECORD DRAWINGS
1. DURING CONSTRUCTION THIS CONTRACTOR SHALL MAINTAIN A COMPLETE AND LEGIBLE SET OF
DRAWINGS SHOWING CHANGES AND DEVIATIONS BETWEEN ACTUAL CONSTRUCTION AND THE
ENGINEER'S DRAWINGS.
2. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE, THIS CONTRACTOR
SHALL MAKE ANY FINAL CORRECTIONS TO THE DRAWINGS AND CERTIFY THE ACCURACY OF
EACH PRINT WITH THIS CONTRACTOR'S STAMP AND SIGNATURE THEREON. THIS COPY OF THE
RECORD DRAWINGS SHALL BE PLACED IN A DRAWING TUBE AND MARKED "RECORD DRAWINGS -
DO NOT REMOVE FROM PREMISES" AND SHALL BE KEPT WITH THE OPERATIONS MANUAL,
L. OPERATIONS MANUAL
1. ONE COPY OF AN OPERATIONS AND MAINTENANCE MANUAL FOR ALL EQUIPMENT FURNISHED
(3) RING BINDER. SHALL BE COLLECTED AND INSERTED IN A LABELED THREE INCH (3") THREE
2. OPERATIONS AND MAINTENANCE MANUALS SHALL BE ASSEMBLED AS FOLLOWS:
A. SECTION 1
1. TITLE OF PROJECT
2. LOCATION OF PROJECT
3. NAME AND ADDRESS OF OWNER
4. NAME AND ADDRESS OF ENGINEER
5. NAME AND ADDRESS OF THIS CONTRACTOR.
B. SECTION 2
1. SHOP DRAWINGS OF ALL APPROVED EQUIPMENT,
C. SECTION 3
1. A LISTING OF ALL EQUIPMENT WARRANTIES INDICATING THE EQUIPMENT MODEL
NUMBER, SERIAL NUMBER, START AND ENDING DATE OF THE WARRANTY, ETC.
3. EACH SECTION SHALL BE SEPARATED BY A PASTEBOARD TABBED DIVIDER.
4. ALL INFORMATION SHALL BE ARRANGED IN AS MANY BINDERS AS NECESSARY.
5. OPERATION AND MAINTENANCE MANUAL AND DRAWING TUBE SHALL BE LEFT WITH THE
STORE MANAGER.
M. TESTS, ADJUSTMENTS, INSTRUCTIONS AND CLEANING
1. ALL CONNECTIONS AT PANELS AND SWITCHES ARE TO BE MADE, ALL SPICES
COMPLETE, ALL FUSES IN PLACE, AND ALL CIRCUITS CONTINUOUS FROM POINT
OF SERVICE CONNECTION TO ITS FINAL DESTINATION, AND ALL COVERS AND
PLATES INSTALLED PRIOR TO THE TIME OF FINAL INSPECTION BY THE OWNER'S
CONSTRUCTION MANAGER.
2. TEST FOR GROUNDS, SHORT CIRCUITS AND PROPER FUNCTION OF ALL EQUIPMENT
AFTER INSTALLATION IS COMPLETE. FAULTS IN THE INSTALLATION SHALL BE
CORRECTED AT THIS CONTRACTORS EXPENSE.
3. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION
SHALL BE TESTED AND PROVED FREE OF UNWANTED GROUNDS AND OTHER
DEFECTS.
4. ALL OVERLOAD DEVICES, INCLUDING EQUIPMENT, FURNISHED UNDER OTHER
CONTRACTS, SHALL BE SET AND ADJUSTED TO SUIT THE LOAD CONDITIONS.
5. TEST AND MAKE CORRECTIONS/ADJUSTMENTS FOR PHASE BALANCING.
6. AFTER ALL TESTS AND ADJUSTMENTS HAVE BEEN MADE, THIS CONTRACTOR SHALL
FULLY INSTRUCT THE REPRESENTATIVES OF THE OWNER IN ALL DETAILS OF
OPERATION AND MAINTENANCE OF THE EQUIPMENT INSTALLED UNDER THIS
CONTRACT. INSTRUCTION SHALL BE FURNISHED UNTIL THE OWNER IS
SATISFIED. FURNISH THE OWNER WITH TWO INSTRUCTION MANUALS ON EACH
SYSTEM. INSTRUCTION MANUALS SHALL CONTAIN ALL SHOP DRAWINGS,
MANUFACTURERS INSTALLATION AND OPERATION INSTRUCTION, GUARANTEES,
MAINTENANCE SCHEDULE, ETC.
7. AT THE END OF THE PROJECT, THIS CONTRACTOR SHALL CLEAN ALL EQUIPMENT,
INCLUDING LIGHT FIXTURES, TO THE SATISFACTION OF THE OWNER. ALL
DUST, DIRT, DEBRIS, AND FOREIGN MATTER SHALL BE REMOVED FROM ALL
EQUIPMENT.
N. INSPECTIONS, FINAL REPORTS AND GUARANTEE
1. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL INFORM THE LOCAL
AND STATE AUTHORITIES AND THE OWNER TO ARRANGE FOR FINAL INSPECTIONS
OF THIS WORK.
2. THIS CONTRACTOR SHALL FURNISH TO THE OWNER ALL CERTIFICATES OF INSPECTION
AND FINAL INSPECTION APPROVAL AT THE COMPLETION OF THIS PROJECT.
3. THIS CONTRACTOR SHALL SUBMIT TO THE OWNER UPON COMPLETION OF THIS WORK
A LETTER CERTIFYING THAT THIS WORK IS IN ACCORDANCE WITH ALL APPLICABLE STATE
AND LOCAL LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY
REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND
STANDARDS.
4. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT, WORK, ETC., UNDER
THIS CONTRACT FOR ONE (1) YEAR AFTER THE ACCEPTANCE OF ALL SYSTEMS INSTALLED
BY THIS CONTRACTOR UNDER THIS CONTRACT. THIS CONTRACTOR SHALL MAKE GOOD,
REPAIR OR REPLACE AT THIS CONTRACTORS OWN EXPENSE, ANY DEFECTIVE WORK,
MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED FORM THE DATE OF ACCEPTANCE,
IN WRITING. EXTENDED WARRANTIES ARE AS SPECIFIED WITH THE INDIVIDUAL EQUIPMENT,
5. UNDER THE ONE (1) YEAR GUARANTEE PERIOD THIS CONTRACTOR SHALL BE RESPONSIBLE
FOR ANY DAMAGE TO THE PREMISES CAUSED BY DEFECTS IN ANY WORKMANSHIP OR
ANY EQUIPMENT FURNISHES AND/OR INSTALLED BY THIS CONTRACTOR.
0. SLEEVES
1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN
THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL
OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT
PENETRATE THE FLOOR, WHICH SHALL EXTEND TWO INCHES (2") ABOVE THE FLOOR.
2. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE
STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY
PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING,
SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM.
P. FIRE STOPPING
1. ALL OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS FOR CONDUITS SHALL BE
FIRE SEALED IN ACCORDANCE WITH NFPA 101 WITH CALCIUM SILICATE, SILICONE "RTV" FOAM,
3M FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE RATING. PROVIDE
SLEEVES AS REQUIRED BY ALL APPLICABLE CODES OR LANDLORD REQUIREMENTS.
END OF SECTION 16010
SECTION 16111 - CONDUIT
A. THIS CONTRACTOR SHALL PROVIDE ALL CONDUITS SERVING ALL EQUIPMENT
INCLUDING BUT NOT LIMITED TO, LIGHTING, RECEPTACLES, HEATING, AIR
CONDITIONING, PLUMBING EQUIPMENT, TELEPHONE, SPEAKERS, AND ELECTRICAL
EQUIPMENT.
B. ALL CONDUITS SHALL BE GALVANIZED IMC OR MC UNLESS OTHERWISE
SPECIFIED IN SPECIFICATIONS OR ON DRAWINGS. ALL CONDUIT IS TO BE UL
LABELED. MC CONNECTORS SHALL BE STEEL COMPRESSION OR SET SCREW
TYPE. CONDUIT UNDER SLAB ON GRADE SHALL BE RIGID STEEL.
C. MINIMUM SIZES OF CONDUIT SHALL BE 1/2" FOR INDIVIDUAL LIGHTING
FIXTURES CONNECTIONS OR TO INDIVIDUAL LIGHT SWITCHES (IF ACCEPTABLE
BY THE LANDLORD AND LOCAL CODE OFFICIALS) AND 3/4" FOR ALL OTHER
LOCATIONS, HVAC CONTROL WIRING, SPEAKER WIRING AND FIRE ALARM WIRING
SHALL BE RUN IN CONDUIT AND SHALL BE A MINIMUM OF 3/4" SIZE, UNLESS
NOTED OTHERWISE ON DRAWINGS. ALL IN AND/OR UNDER FLOOR SLAB CONDUIT
SHALL BE OF MINIMUM 1 " SIZE.
D. SUPPORT ALL CONDUIT, INCLUDING SEISMIC AND SWAY BRACING, IN
ACCORDANCE WITH THE N.E.C. AND LOCAL CODES.
E. GENERALLY, ALL CONDUIT SHALL BE CONCEALED EXCEPT FOR UNFINISHED
AREAS, SUCH AS EQUIPMENT ROOMS. EXPOSED CONDUIT SHALL BE ALLOWED
ONLY AS NOTED ON PLAN. PAINTING OF CONDUITS IN FINISHED AREAS, NOTED
ON DRAWINGS OR SPECIFICATIONS WILL BY GENERAL CONTRACTOR.
F. FLEXIBLE METAL CONDUIT OR MC TYPE CABLE.
1. FLEXIBLE CONDUIT OR MC TYPE CABLE SHALL BE ACCEPTABLE FOR THE
FOLLOWING APPLICATIONS ONLY:
A. FINAL CONNECTIONS TO MOTORS.
B. FINAL CONNECTIONS INTO AND OUT OF THE TRANSFORMER.
C. FINAL CONNECTIONS TO VIBRATING EQUIPMENT.
D. INTERCONNECTIONS BETWEEN ALL LIGHT FIXTURES. (NOT TO INCLUDE
HOME RUN TO PANEL BOARD WHICH MUST BE RIGID.)
E. FINAL CONNECTIONS WHERE RIGID CONDUIT IS NOT PRACTICAL.
F. IN WALLS (FOR LIGHT SWITCHES AND 120 VOLT POWER RECEPTACLES
AND HVAC CONTROL EQUIPMENT.
2. FLEXIBLE METAL CONDUIT OR MC TYPE CABLE MUST BE THE SAME SIZE AS
THE IMC OR MC CONDUIT TO WHICH IT IS CONNECTED. BOTH THE
FLEXIBLE METAL CONDUIT AND ITS FITTINGS ARE TO BE LISTED FOR
GROUNDING. A GREEN GROUNDING CONDUCTOR SHALL BE INSTALLED. ALL
CONNECTORS ARE TO BE OF A NEMA APPROVED TYPE.
3. THE USE OF ROMEX, BX, ETC. IS NOT PERMITTED.
4. CONNECTION TO OUTDOOR EQUIPMENT MUST BE WEATHERPROOF, I.E.
LIQUIDTIGHT OR SEALTIGHT.
5. MAXIMUM LENGTH OF FLEXIBLE METAL CONDUIT SHALL BE 3'-0",
G. PROVED AS A MINIMUM #10 AWG PULL -WIRE IN ALL EMPTY CONDUITS EXCEPT AS
NOTED OTHERWISE ON DRAWINGS.
H. HOME RUNS AND MAIN CONDUIT RUNS ARE TO BE HELD TIGHT TO STRUCTURE
ABOVE OR AS REQUIRED TO ALLOW PROPER SERVICE ACCESS AND OTHER TRADES
WORK. CONDUIT MUST BE TRAPEZED TO ALLOW 3 FEET MINIMUM CLEARANCE
ABOVE CEILING.
1. ALL CONDUIT SHALL BE RUN PARALLEL OR PERPENDICULAR TO COLUMN LINES.
J. ALL CONDUITS MUST BE SIZED PER N.E.C., LOCAL CODES AND LANDLORD
REQUIREMENTS.
K. PVC CONDUIT SHALL NOT BE PERMITTED.
L. CONDUIT SHALL NOT BE INSTALLED IN OR THROUGH ANY DUCTWORK.
M. ANCHOR ALL CONDUITS INSTALLED HORIZONTALLY IN STEEL STUDS TO PREVENT
VIBRATION.
END OF SECTION 16111
SECTION 16120 - WIRING
A. CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS SHALL BE COPPER AND THE
AWG SIZE AND TYPE AS SHOWN ON DRAWINGS. MINIMUM WIRE SIZE #12. THE
CONDUCTORS SHALL BE 600 VOLT INSULATION, TYPE THW, THWN OR THHN.
(CONDUIT SIZE BASED ON THHN AND THWN).
B. MINIMUM WIRE SIZE - 20 AMP BRANCH CIRCUIT SHALL BE AWG LISTED SIZE
PER DISTANCE SHOWN BELOW. DISTANCE SHALL BE MEASURED FROM THE
PANELBOARD CIRCUIT BREAKER TO THE FURTHEST OUTLET.
1. J12 LESS THAN 100 FEET
2. 10 BETWEEN 100-150 FEET
3. 8 BETWEEN 150-250 FEET
4. 6 OVER 250 FEET
NOTE: THE ELECTRICAL CONTRACTOR MAY SUBMIT VOLTAGE DROP CALCULATIONS
OR ACTUAL FIELD READINGS FOR EACH RECEPTACLE CIRCUIT TO THE OWNER
FOR APPROVAL OF SMALLER W!RE SIZE THAN THOSE LISTED ABOVE.
MAXIMUM VOLTAGE DROP SHALL BE 3% PER N.E.C.
C. ON ALL 20 AMP BRANCH CIRCUITS, CONDUCTORS LARGER THAN #10 AWG SHALL
BE REDUCED TO #10 AWG WITHIN 10 FEET OF PANEL BOARD AND DEVICE IN
JUNCTION BOXES ON RATED TERMINAL STRIPS,
D. CONDUCTORS MAY BE STRANDED FOR SIZES #10 AWG AND LARGER. CONDUCTORS
SIZE #12 SHALL BE SOLID (NOT STRANDED).
E. ALUMINUM CONDUCTORS ARE NOT PERMITTED, EXCEPT AT SERVICE ENTRANCE,
WHERE REQUIRED BY LANDLORD. CONDUCTOR CONNECTION MUST BE PER
MANUFACTURER'S REQUIREMENTS.
F. HVAC CONTROL WIRING SHALL BE 8-#16 MULTI -COLORED CABLE WITH 600 V.
INSULATION.
G. ALL WIRING AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE SITE IN
UNBROKEN PACKAGES.
H. ALL WIRING SHALL BE CONDUIT, UNLESS SPECIFICALLY NOTED OTHERWISE
(I.E. LOW VOLTAGE, PLENUM RATED WIRE).
I. THE USE OF SHARED NEUTRALS IS NOT ALLOWED FOR LIGHTING CIRCUITS, SHARED
NEUTRALS FOR POWER CIRCUITS SHALL BE INSTALLED IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE AND LOCAL CODES. ALL OTHER EQUIPMENT REQUIRING A
NEUTRAL CONDUCTOR SHALL HAVE A DEDICATED FULL SIZE NEUTRAL.
J. THE USE OF ROMEX, BX, ETC. IS NOT PERMITTED.
K. WIRE CONNECTORS SHALL BE EQUAL TO "SCOTCH LOCK" FOR #8 AWG WIRE AND
SMALLER AND EQUAL TO T & B "LOCKTIGHT" FOR #6 AWG AND LARGER.
L. ALL WIRING TO BE COLOR -CODED AS FOLLOWS:
120/208 VOLT SYSTEM 277/480 VOLT SYSTEM
NEUTRAL - WHITE NEUTRAL - GRAY
PHASE A OR L1 - BLACK PHASE 1 OR L1 - BROWN
PHASE B OR L2 - REO PHASE B OR L2 - ORANGE
PHASE C OR L3 - BLUE PHASE C OR L3 - YELLOW
GROUND - GREEN GROUND - GREEN
M. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED POWER AND CONTROL
INTERLOCK FOR ALL FIRE SUPPRESSION SYSTEMS.
N. LOW VOLTAGE WIRING FOR SIGNALLING OR CONTROL SYSTEMS OR DEVICES WHICH
ARE ENCLOSED IN PARTITIONS, WALLS, OR ANY WAY MADE INACCESSIBLE BY BUILDING
CONSTRUCTION SHALL BE ENCASED IN A RACEWAY. THE ABOVE RACEWAY NEED NOT
TERMINATE IN A BOX OR FITTING SO LONG AS NORMAL PRECAUTIONS ARE TAKEN
TO PROTECT THE CONDUCTORS AGAINST INJURY OR DAMAGE (N.E.C. 725-38B AND
760-28C). THIS ALSO SHALL INCLUDE COAXIAL CABLE ASSEMBLIES (N.E.C. 820-50).
0. HEATING, VENTILATING & AIR CONDITIONING, PLUMBING, AND FIRE PROTECTION WIRING
1.ELECTRICAL CONTRACTOR SHALL REFER TO MECHANICAL DRAWINGS FOR
FOR ADDITIONAL ELECTRICAL WORK TO BE INCLUDED IN THIS BID.
2. ELECTRICAL CONTRACTOR SHALL DO ALL POWER WIRING, LINE VOLTAGE WIRING,
AND LINE VOLTAGE CONTROL WIRING INDICATED UNDER THE HEATING,
VENTILATION AND AIR CONDITIONING, PLUMBING AND FIRE PROTECTION
SPECIFICATIONS AND DRAWINGS. THIS CONTRACTOR SHALL ALSO DO ALL
INTERCONNECTING LINE VOLTAGE WIRING BETWEEN RELAYS AND SWITCHES AS
REQUIRED.
3, ELECTRICAL CONTRACTOR SHALL PROVIDE AS A MINIMUM, ONE (1) CONDUIT
STUBBED FROM HVAC AND/OR LIGHTING CONTROL PANEL TO 12" ABOVE CEILING
WITH PLASTIC CONDUIT BUSHING TO PREVENT WIRE CHAFFING.
4. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING CONDUIT FOR HVAC
CONTROL WIRING WHERE REQUIRED BY CODE TO BE IN CONDUIT.
5. REFER TO MECHANICAL DRAWINGS FOR AVAILABLE SCHEMATIC WIRING DIAGRAMS
OF EQUIPMENT.
6. ROUTE ELECTRIC POWER AND CONTROL FOR ROOF MOUNTED HVAC EQUIPMENT
THROUGH A SEPARATE ROOF PENETRATION FOR THE ELECTRIC POWER AND
CONTROL CONDUITS. DO NOT ROUTE CONDUIT THROUGH HVAC ROOF MOUNTED
EQUIPMENT CURB. DO NOT DRILL HOLES IN CONDENSATE PAN OR COMPRESSOR
OR CONDENSER SECTION FLOOR.
7. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL SMOKE DETECTORS
AS REQUIRED BY ALL APPLICABLE CODES. VERIFY CONNECTION REQUIREMENTS TO
THE FIRE ALARM SYSTEM PRIOR TO BIDDING. PROVIDE A RESET/TEST AND ALARM
LIGHT FOR ALL INSTALLED SMOKE DETECTORS. VERIFY RESET/TEST AND ALARM LIGHT
LOCATION WITH THE OWNER PRIOR TO INSTALLATION.
P. GENERAL WIRING REQUIREMENTS
1. ALL EQUIPMENT FURNISHED AND INSTALLED UNDER CONTRACTS OTHER THAN THE
ELECTRIC CONTRACT SHALL BE FURNISHED WITH FULL COMPLEMENT OF CONTROL
EQUIPMENT AND CONTROL WIRING DIAGRAMS NECESSARY FOR SATISFACTORY
OPERATION.
2. THE ELECTRICAL CONTRACTOR SHALL COMPLETE ALL ELECTRICAL CONNECTIONS
THROUGH THE DISCONNECT, STARTER AND MOTOR TERMINALS.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER ROTATION OF
ALL THREE PHASE EQUIPMENT.
4. EQUIPMENT FURNISHED BY OTHERS SHALL BE ROUGHED IN WITH CONDUIT AND
BOXES BY MANUFACTURER. INTERNAL WIRING SHALL BE COMPLETED ACCORDING
TO THE MANUFACTURER'S SHOP DRAWINGS OF THE EQUIPMENT BY ELECTRICAL
CONTRACTOR. THIS CONTRACTOR IS TO WIRE TO ALL LINES VOLTAGE CONTROLS
AND CONTROLLERS.
END OF SECTION 16120
SECTION 16131 - JUNCTION AND PULL BOXES
A. THE PLANS INDICATE ONLY SCHEMATIC ROUTINGS FOR CONDUIT RUNS. THIS
CONTRACTOR SHALL PROVIDE ADDITIONAL BOXES WHERE REQUIRED BY FIELD
CONDITIONS OR BY CODE.
B. BOXES AND COVERS SHALL BE GALVANIZED STEEL OF CODE GAUGE SIZE.
C. INSTALL BOXES RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE AND
SUPPORTED INDEPENDENT OF THE CONDUIT SYSTEM
D. ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE
LOCATIONS. THE USE OF JUNCTION BOXES ABOVE DRYWALL CEILING SHALL BE
LIMITED TO LOCATIONS NEAR ACCESS FRAMES USED FOR DIFFUSERS AND RETURN
AIR GRILLES OF ACCESS PANELS AS LOCATED ON PLANS.
E. JUNCTION AND PULL BOXES MUST BE LABELED WITH CIRCUIT NUMBER
IDENTIFICATION AND SYSTEM TYPE ON COVER.
END OF SECTION 16131
SECTION 16134 - OUTLET BOXES
A. ALL OUTLET BOXES SHALL BE GALVANIZED PRESSED STEEL OF THE STANDARD
KNOCKOUT TYPE. NO ROUND OUTLET BOXES SHALL BE PERMITTED, EXCEPT AS
SPECIFICALLY NOTES ON DRAWINGS. CONCEALED BOXES SHALL NOT BE LESS
THAN 4 INCHES SQUARE AND 1 1/2" DEEP, WITH PLASTIC RINGS,
B. ALL KNOCKOUT BOXES, UPON WHICH LIGHTING FIXTURES ARE TO BE INSTALLED,
SHALL BE EQUIPPED WITH 3/4" FIXTURE STUDS.
C. EXTERIOR BOXES SHALL BE CAST RUST -RESISTING METAL WITH GASKETED
COVERS.
D. INSTALL BOXES RIGIDLY FROM BUILDING STRUCTURE AND SUPPORT
INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE SUITABLE BOX
EXTENSIONS TO EXTEND BOXES TO FINISHED FACES OF FLOORS, CEILINGS,
WALLS, ETC. ALL OUTLET BOXES TO HAVE SUITABLE BLOCKING BEHIND THEM
TO MINIMIZE THE DEFLECTION THAT OCCURS WHEN PLUGGING/.UNPLUGGING INTO
THESE DEVICES.
E. UNLESS OTHERWISE NOTED ON DRAWINGS OR OTHERWISE REQUIRED BY NATIONAL
ELECTRICAL CODE, HANDICAP CODES OR LOCAL CODES, OUTLET HEIGHTS SHALL
BE AS FOLLOWS:
1. SWITCH HEIGHT 48" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET.
2. CONVENIENCE OUTLETS
A. SALES - HORIZONTALLY IN BASEBOARD BENEATH CABINETS, AS SHOWN
ON DRAWINGS, OR AS REQUIRED BY LOCAL CODES.
B. NON -SALES - 18" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET.
3. TELEPHONE OUTLETS SHALL BE LOCATED AS NOTED ON DRAWINGS.
END OF SECTION 16134
SECTION 16140 - WIRING DEVICES
A. THIS CONTRACTOR SHALL FURNISH AND INSTALL SWITCHES AND RECEPTACLES AS
SHOWN ON THE DRAWINGS AND AS NECESSARY FOR A COMPLETE INSTALLATION.
COLOR OF DEVICES AND PLATES SHALL BE SELECTED BY THE ARCHITECT. THE
DEVICES SHALL BE OF THE TYPES AND RATINGS LISTED, OR EQUALS BY ARROW -
HART, GENERAL ELECTRIC OR PASS & SEYMOUR. WEATHERPROOF G.F.I.
RECEPTACLES SHALL BE INSTALLED WHERE SHOWN ON DRAWINGS OR AS REQUIRED
BY CODE.
1. SINGLE POLE SWITCHES: 20 A - 125 V HUBBELL - 1221
2. THREE WAY SWITCHES: 20 A - 125 V HUBBELL - 1223
3. FOUR WAY SWITCHES: 20 A - 125 V HUBBELL - 1224
4. DUPLEX RECEPTACLES: 20 A - 125 V HUBBELL - 5362
5. ISOLATED GROUND RECEPTACLES: 20 A - 125 V HUBBELL - IG5362
6. FLOOR OUTLET BOX: STEEL CITY #841
7. FLOOR OUTLET BRASS COVER: STEEL CITY #P-64-1 OR P -64-D7, ADD
"AL" FOR ALUMINUM
8. GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLES: 20 A-125 V
HUBBELL-CF5352
9. DIMMERS: LUTRON
10, MOTOR STARTERS: SQUARE D
11. EXHAUST FAN TIMER: MARK TIME
12. LIGHTING TIMERS: PARAGON 7007-0 (24 HOUR - 7 DAY TYPE)
B. ALL DEVICE COVERPLATES SHALL BE PASS AND SEYMOUR SERIES "RP" OR
EQUAL.
END OF SECTION 16140
SECTION 16155 - MOTOR STARTERS
A. MANUAL MOTOR STARTERS WITH OVERLOAD PROTECTION MAY BE USED FOR
FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REQUIRE AUXILIARY CONTROL.
THREE PHASE STARTERS SHALL BE PROVIDED WITH OVERLOAD DEVICE IN EACH
PHASE MATCHED TO MOTOR NAMEPLATE RATING. MAGNETIC MOTOR STARTERS
SHALL BE ELECTRICALLY HELD (MINIMUM SIZE #1) AND BE USED FOR ALL
SINGLE PHASE AND THREE PHASE MOTORS RATED ABOVE 1/2 HP OR THAT
REQUIRED AUXILIARY CONTROL, PROVIDE CONTROL DEVICES (AUXILIARY
CONTACTS, TRANSFORMERS, ETC.) IN STARTERS AS REQUIRED FOR INTERLOCKS.
COORDINATE WITH MECHANICAL CONTRACTORS. COMBINATION STARTERS SHALL
CONTAIN FUSIBLE SWITCHES AND ONLY USED WHERE INDICATED ON DRAWINGS.
B. MANUFACTURER SHALL BE SQUARE "D" OR EQUAL.
END OF SECTION 16155
SECTION 16160 PANELBOARDS
A. ALL PANELBOARDS SHALL BE FACTORY ASSEMBLED OF THE BOLTED CIRCUIT
BREAKER TYPE WITH SOLID COPPER BUSSING, FULL SIZED COPPER NEUTRAL,
100% GROUND BUSSING, AND OVERALL HINGED/LOCKABLE DOOR. ALL CIRCUIT
BREAKERS SHALL BE OF THE QUICK -MAKE AND QUICK -BREAK DESIGN, THERMAL -
MAGNETIC TYPE, TRIP FREE AND TRIP -INDICATING. ALL PANELS SHALL BE
DEAD FRONT AND FLUSH OR SURFACE MOUNTED AS SHOWN AND SHALL BE
FURNISHED WITH A TYPEWRITTEN DIRECTOR CARD OF THE CIRCUITS AND AN
ENGRAVED NAMEPLATE.
B. CIRCUIT BREAKER PANELBOARDS SHALL HAVE FULL LENGTH NON-TAPERED BUS
BARS ARRANGED AND DRILLED FOR SEQUENCE PHASING.
C. ALL PANELS SHALL HAVE DOORS FLUSH WITH THE TRIM, EQUIPPED WITH LOCKS,
AND KEYED ALIKE. ALL MULTI -POLE BREAKERS SHALL BE COMMON TRIP.
D. ALL PANELBOARDS PHASE AMPERAGE SHALL BE BALANCED TO WITHIN 7 PERCENT
MAX. TO MIN. REARRANGE NON -LIGHTING BRANCH CIRCUITS AS REQUIRED AND
NOTE CHANGES ON RECORD DRAWINGS. LIGHTING PANEL CIRCUIT BREAKERS
MUST BE INSTALLED AND WIRED EXACTLY AS SHOWN ON DRAWINGS.
E. PANELS SHALL BE AS INDICATED ON THE DRAWINGS. ALL BRANCH CIRCUIT
BREAKERS (C/B) SHALL BE RATED 20 AMPERES SINGLE POLE MINIMUM, EXCEPT
AS NOTED OR REQUIRED BY LOCAL CODES.
F. PROVIDE LOCKOUT CLIPS ON NIGHT LIGHT, TIME CLOCK CONTROLLED, LIFE
SAFETY, AND ALL OTHER CIRCUIT BREAKERS WHERE INDICATED ON PANEL
SCHEDULE. PROVIDE 5 ADDITIONAL CLIPS TO BE INSTALLED AS DIRECTED BY
THE OWNER.
G. PROVIDE ONE SPARE 1" CONDUIT FOR EACH SIX SPACES OR SPARE CIRCUIT
BREAKERS IN EACH RECESSED MOUNTED PANEL. MINIMUM 1 SPARE CONDUIT PER
PANEL. RUN CONDUIT TO A LOCATED JUST ABOVE CEILING.
H. ALL CIRCUIT BREAKERS FEEDING LIGHTING LOADS SHALL BE LISTED AND SHALL
BE MARKED "SWD" (SWITCHING DUTY). REFER TO ELECTRICAL RISER DIAGRAM
AND DRAWINGS FOR ADDITIONAL INFORMATION
I. CIRCUIT BREAKERS SERVING HEATING, VENTILATION, AND/OR AIR
CONDITIONING (HVAC) EQUIPMENT SHALL BE RATED AND MARKED "HACR", IF
FUSING IS NOT PROVIDED AT PIECE OF HVAC EQUIPMENT. FIELD VERIFY
EXACT "HACR" BREAKER REQUIREMENTS WITH HVAC EQUIPMENT NAMEPLATE AND
MANUFACTURER'S REQUIREMENTS PRIOR TO INSTALLATION.
J. IN SERVICE ENTRANCE APPLICATIONS, PANELS, SHALL BEAR THE
MANUFACTURER'S LABEL INDICATING THE EQUIPMENT IS RATED FOR SUCH
APPLICATION IN ACCORDANCE WITH THE N.E.C. AND AS INDICATED ON DRAWINGS.
K. PANELBOARDS MUST BE MOUNTED ON MINIMUM 3/4" A/D PLYWOOD AND PAINED TO
A COLOR TO MATCH THE SURROUNDING WALLS OR A COLOR AS REQUIRED BY
LOCAL CODE. PLYWOOD SHALL EXTEND 1 FOOT MINIMUM BEYOND EDGE OF
EQUIPMENT.
L. PANELBOARDS SHALL HAVE A MINIMUM SHORT CIRCUIT CURRENT RATING AND LUG
CONNECTIONS AS FOLLOWS:
1. 120/208 VOLT PANELBOARDS: 10,000 A.I.C.
2. 277/480 VOLT PANELBOARDS: 14,000 A.I.C.
3. FUSIBLE DISTRIBUTION PANELBOARDS: 100,000 A.I.C.
M. VERIFY ACTUAL A.I.C. SHORT CIRCUIT CURRENT REQUIREMENTS WITH
UTILITY COMPANY PRIOR TO ORDERING EQUIPMENT.
N. ALL LUG CONNECTIONS TO BE 75"C
0. PANELS SHALL BE MANUFACTURED BY SQUARE "D" OR EQUAL.
END OF SECTION 16160
SECTION 16170 - SAFETY AND DISCONNECT SWITCHES
A. SAFETY AND DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, QUICK -MAKE,
QUICK -BREAK FUSED OR NON -FUSIBLE WITH RATINGS AND SIZES AS NOTED ON
PLANS AND REQUIRED BY CODES.
B. SWITCHES SHALL BE WEATHERPROOF IN OUTDOOR LOCATIONS OR AS REQUIRED BY
LOCAL CODES.
C. DISCONNECT SWITCHES THAT ARE INSTALLED AT HEATING, VENTILATING AND
AIR CONDITIONING (HVAC) EQUIPMENT SHALL BE FUSED IF NOT PROTECTED
WITH A "HACR" BREAKER IN ACCORDANCE WITH THE EQUIPMENT'S NAMEPLATE
AND MANUFACTURER'S REQUIREMENTS PER THE NATIONAL ELECTRICAL CODE,
STATE AND LOCAL CODES.
D. AT SERVICE ENTRANCE, DISCONNECT SHALL BEAR MANUFACTURER'S LABEL
INDICATING THE EQUIPMENT IS UL RATED FOR APPLICATION IN ACCORDANCE
WITH ALL CODES.
E. MANUFACTURER SHALL BE SQUARE "D" OR EQUAL.
END OF SECTION 16170
SECTION 16450 - GROUNDING
A. PROVIDE COMPLETE WIRED GROUNDING CONDUCTOR SYSTEM, #12 AWG MINIMUM,
SIZED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE
NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES, THE LANDLORD'S
TENANT CRITERIA AND AS NOTED IN THE SPECIFICATIONS AND AS INDICATED
ON THE DRAWINGS.
B. ALL CONDUIT, INCLUDING FLEXIBLE CONDUIT, SHALL BE GROUNDED WITH A
GREEN GROUNDING CONDUCTOR,
C. GROUNDING CONNECTIONS MADE TO THE WATER PIPING SYSTEM SHALL BE
COORDINATED WITH THE PLUMBING CONTRACTOR AND BONDING JUMPERS SHALL BE
INSTALLED PER CODES AND AS INDICATED ON DRAWINGS,
D. ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. USE A BONDING
JUMPER BETWEEN THE OUTLET BOX AND THE DEVICE GROUNDING TERMINAL.
METAL -TO -METAL CONTRACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS
NOT ACCEPTABLE AS A BOND FOR EITHER SURFACE MOUNTED BOXES OR FLUSH
TYPE BOXES. ALL JUNCTION BOXES, OUTLET BOXES, AND PULL BOXES SHALL
BE BONDED TO THE CONDUIT SYSTEM.
E. RUN A SEPARATE ISOLATED GROUNDING CONDUCTOR, #12 AWG MINIMUM, IN EACH
CONDUIT FEEDING THE HVAC CONTROL PANEL, AND OTHER COMPUTERIZED EQUIPMENT
AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS, BOND THE GROUNDING CONDUCTOR
TO THE CONDUIT, WHERE ENTERING AND LEAVE THE CONDUIT. THE GROUNDING
CONDUCTOR SHALL BE SIZED PER CODE, GREEN COLORED, COPPER WIRE.
F. ALL ENCLOSURES AND NON-CURRENT CARRYING METAL PARTS ARE TO BE
GROUNDED. CONDUIT SYSTEM IS TO BE ELECTRICALLY CONTINUOUS. ALL LOCK
NUTS MUST CUT THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES.
WHERE ENCLOSURES AND NON-CURRENT CARRYING METAL PARTS ARE ISOLATED
FROM THE CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED CLAMPS.
ALL GROUND CLAMPS SHALL BE "PENN -UNION" OR EQUAL, SIMILAR TO "GPL"
TYPE.
END OF SECTION 16450
SECTION 16477 - FUSES
A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY FUSES
FOR A COMPLETE INSTALLATION.
B. FUSES FOR FEEDER CIRCUITS AND PANELBOARDS SHALL BE U.L. CLASS RKI FAST -
ACTING TYPE.
C. FUSES FOR MOTOR OVERCURRENT AND TRANSFORMER PROTECTION SHALL BE DUAL
ELEMENT, U.L. CLASS RKI TIME DELAY TYPE.
D. FUSES MANUFACTURES:
1. BUSSMANN DIVISION
2. GENERAL ELECTRIC COMPANY
3. GOULD, INC.
4. LITTELFUSE, INC.
END OF SECTION 16477
SECTION 16500 - LIGHTING FIXTURES AND LAMPS
A. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL LIGHTING FIXTURES AND
LAMPS AS SHOWN ON THE DRAWINGS. ALL FIRE RATED ENCLOSURES FOR
ELECTRICAL LIGHTING FIXTURES, SPEAKERS, EQUIPMENT, ETC., SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
B. ALL RECESSED INCANDESCENT FIXTURES SHALL BE PROVIDED WITH APPLICABLE
THERMAL PROTECTION.
C. WHERE FLUORESCENT FIXTURES ARE SPECIFIED, THEY SHALL BE PROVIDED WITH
HIGH POWER FACTOR RAPID START BALLASTS, U.L. LISTED, C.B.M. CERTIFIED
AND E.T.L. APPROVED.
D. THIS CONTRACTOR SHALL FURNISH ADDITIONAL AUXILIARY SUPPORT STEEL
HANGER WIRED ADEQUATELY SIZED TO SUPPORT THE WEIGHT OF THE FIXTURE
FASTENED TO THE BUILDING STRUCTURE (MINIMUM TWO PER FIXTURE) FOR ALL
FIXTURES IN LAY -IN CEILINGS AND OTHER FIXTURES AS REQUIRED BY THE
LOCAL CODE OFFICIALS.
E. THIS CONTRACTOR SHALL VERIFY THE MODEL NUMBERS AND QUANTITY OF ALL
LIGHT AND FIXTURES PROVIDED BY THE OWNER. CONTACT THE OWNER'S
CONSTRUCTION MANAGER IMMEDIATELY IF THE MODELS DIFFER FROM THOSE
LISTED ON THE LIGHTING FIXTURE SCHEDULE OR IF THEY DO NOT HAVE PROPER
THERMAL PROTECTION.
F. PROVIDE APPLICABLE FIRE RATED DRYWALL BOXES OVER RECESSED FIXTURES IN
FIRE RATED CEILINGS AS REQUIRED BY CODES. FIELD COORDINATE AS
REQUIRED TO AVOID CONFLICTS.
END OF SECTION 16500
SECTION 16740 -TELEPHONE DATA AND COMPUTER WIRING
A. PROVIDE A SYSTEM OF CONDUIT RACEWAYS, OUTLET BOXES, PULL WIRES, AND
TERMINAL BOARDS AS SHOWN ON THE DRAWINGS UNLESS OTHERWISE NOTED ON
PLANS. TELEPHONE SWITCHING APPARATUS, CONDUCTORS, INSTRUMENTS,
MISCELLANEOUS EQUIPMENT AND APPURTENANCES ARE NOT PART OF THIS
CONTRACT AND WILL BE PROVIDED AND INSTALLED BY THE OWNER.
B. OUTLET BOXES TO BE 4" SQUARE MINIMUM WITH SINGLE FOR DEVICE COVER AND
TELEPHONE PLATE WITH CONDUIT DROP AND PULL WIRE TO ABOVE CEILING.
C. ALL PULL WIRES ARE TO BE LABELED FOR PURPOSE DESIGNATED.
D. NO OTHER CIRCUITS ARE TO BE RUN IN SAME CONDUIT FEEDING ISOLATED
GROUND RECEPTACLES.
E. PROVIDE A 3/4" THK X 36" X 72" ACX PLYWOOD BOARD MOUNTED VERTICALLY
AT 12" A.F.F. FOR MOUNTING TELEPHONE EQUIPMENT. PLYWOOD SHOULD BE
PAINTED WITH HIGH QUALITY GRAY OIL BASE PAINT ON BOTH SIDES, FRONT,
AND BACK.
END OF SECTION 16740
ig
�4t �
)7q- nrlia FROST
ENGINEERS
920 N. Shadeland Ave., Suite G-11 A
Indianapolis, Indiana 46219
Phone 317.359.0901
Fax 317.359.0902
mfrost@frostengineers.com
H
W
ov
004O
PQ
w
��PQ
A
Z
CODO
w
PQ
a
a
0
H
Seal
0,`%III I I 1111
%%SFRos
'
"
15T4Pi
�. Iqt'••
,�
V p
No. '-
- *i:6:0i
Revision
Project No.
DD04001
Date
4-13-04
Scale
NO SCALE
Drawn By
MSF
Checked By
MSF
Sheet T k
ELECiAICAL
SPECIFICA71ONS
Sheet No.
POWER PLAN
SCALE: 1/4" = 1'- o" -
NOTES:
REMOVE RECEPTACLE AND WIRING BACK TO PANEL OR JUNCTION BOX,
FILL, SPACKLE AND PAINT WALL TO LIKE NEW.
REMOVE DATA/TELEPHONE BOX AND WIRING.
FILL, SPACKLE AND PAINT WALL TO LIKE NEW.
C
C
Q
C
C
C
C
POWER PLAN
SCALE: 1/4" = 1'-0"
NOTES:
1 RECEPTACLE TO REMAIN UNCHANGED,
2 EXISTING RECEPTACLE TO REMAIN, RECIRCUIT AS NOTED,
DO NOT ABANDON ANY WIRE.
3 NEW RECEPTACLE. CIRCUIT AS NOTED,
4 PROVIDE NEW DATA OUTLET.
ELECTRIC PANEL SCHEDULE
SYMBOL
PANEL : 1 C (EXISTING) LUGS : 125
120/208 VOLT 1 PHASE 3 WIRE MAIN BREAKER MLO
4--13-04
CKT
NO.
DESCRIPTION
BRKR
SIZE
POLE
KW
MSF
POLE
BRKR
SIZE
DESCRIPTION
CKT
NO.
PHASE A
PH+4SE B
1
RECEPTACLES SUITE 120
20
1
0.8
-
FOUR PLEX OUTLET +15 ABOVE FINISHED FLOOR. TYPICAL
-
-
SPACE
2
3
UNDETERMINED
20
1
1.5
-
-
-
SPACE
4
5
UNDETERMINED
20
1
11.5
0.6
1
20
RECEPTACLES SUITE 120
6
7
RECEPTACLES SUITE 120
20
1
0.6
1.5
1
20
UNDETERMINED
8
9
UNDETERMINED
20
1
1,5
1.5
1
20
UNDETERMINED
10
11
RECEPTACLES SUITE 120
20
1
0.8
1.5
1
20
UNDETERMINED
12
13
SUITE 120 WATER HEATER
20
1
1.5
-
-
-
SPACE
14
15
RECEPTACLES SUITE 120
20
1
0.6
0.4
1
20
NIGHT/EMERG SUITE 120
16
17
RECEPTACLES SUITE 120
20
1
1.2
1.1
1
20
UGH71NG SUITE 120
18
191
REFRIGERATOR SUITE 120
20
1
0.7
1.1
1
20 1
LIGHTING SUITE 120 120
TOTAL KW : 18.4
9.7
8.7
TOTAL AMPS : 88.5
ELECTRICAL PANEL REQUIREMENTS
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TYPED PANEL DIRECTORY IDENTIFYING ALL CIRCUITS.
2. THE ELECTRICAL CONTRACTOR SHALL BALANCE THE THREE PHASES WITHIN 10% OF EACH OTHER.
3. ALL BREAKERS SHALL BE BOLT -ON,
4. PANELBOARD SHAD_ BE SQUARE D.
5. PANEL.BOARD SHALL BE SERVICE ENTRANCE RATED.
ELECTRICAL PANEL KEY NOTES
O PROVIDE "DO NOT TURN OFF!" LABEL AND LOCK—ON CUPS FOR CIRCUIT BREAKER.
EXISTING CIRCUIT FOR OTHER SUITE TO REMAIN.
O NEW BREAKER REQUIRED.
PANEL IC IS LOCATED IN SECOND FLOOR MECHANICAL ROOM.
23
23
3
D@
D
30
ELECTRICAL SYMBOLS
SYMBOL
DESCRIPTION
4--13-04
ELEC ICAL PANEL, FIELD RIFY LOCATION. SEE ELECTRICAL RISER DIAGRAM
IS�79
FOR MORE INFORMATION AND WORK RESPONSIBILITY
C*
SWITCH D=DIMMER M=MOTION SENSOR
MSF
sw
DUPLEX OUTLET +150 E FINISHED FLOOR, TYPICAL UNLESS NOTED
OTHERWISE OUTLETS SHALL NOT BE IN MIRRORS, ADJUST LOCATIONS
ACCORDINGLY VERIFY CHANGES WITH TMW OR ARCHITECT.
GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. .
GA
WP=WEATHER PROOF COVER
FOUR PLEX OUTLET +15 ABOVE FINISHED FLOOR. TYPICAL
Cn
UNLESS NOTED OTHERWISE. NO MORE THAN 3 PER CIRCUIT.
FLOOR MOUNTED DUPLEX AND DATA OUTLET.
Z
JUNCTION BOX
TELDWINIE/BATA BOX MOUNTED AT 15" AFF WITH CONDUIT TO ABOVE CEILING.
>10
PROVIDE PULL STRING.
AFROST
ENGINEERS
920 N. Shadeland Ave., Suite G-1 I
Indianapolis, Indiana 46219
Phone 317.559.0901
Fax 317.359.0902
mfrost@frostengineers.com
Seal
`,\111111 fill.,
*: No. : *=
-� 60910220.
STATE OF
lee
ZONAL
Milt%
Revision
Project No.
DD04001
Date
4--13-04
Scale
1/4" = 1'-0"
Drawn By
C*
Checked By
MSF
sw
LL.1
I ---
�J
CL
Cn
LU
Z
0
<
>10
LL
p ,i -
iw
--_
—
L! 1
l
m
—j -
0
L
Seal
`,\111111 fill.,
*: No. : *=
-� 60910220.
STATE OF
lee
ZONAL
Milt%
Revision
Project No.
DD04001
Date
4--13-04
Scale
1/4" = 1'-0"
Drawn By
MSF
Checked By
MSF
srven nk
POWER PLANS
Sheet No.
Ag-. FROST
ENGINEERS
920 N. Shadeland Ave., Suite G-11 A
Indianapolis, Indiana 46219
Phone 317.359.0901
Fax 317.359.0902
mfrost@frostengineers.com
Hyl a�-IF
1c -2o �
O O Ff F C CON ;r-;
NL 101 w he U J C\1
108 w, F-
1 C-20 PD
1C-16 1C- 0 vd
-0 O
Q 2 1C 1s 104 0
W ®U®
3 > L, L
W �L Z
Z M
0 �- 0
N N 00
LIGHTING PLAN — DEMO LIGHTING PLAN Cn 0)>- . z
SCALE: = 1
4 -0
1 " '" W U
/ SCALE: 1 /4" = 1'-0"
OSe I—
NOTES: E"4
OREMOVE LIGHT AND WIRING BACK TO PANEL OR JUNCTION BOX,
CLEAN FIXTURE AND TURN OVER TO OWNER FOR REUSE.
OREMOVE EXISTING SWITCH AND WIRING.
FILL, SPACKLE AND PAINT WALL TO LIKE NEW.
LIGHT FIXTURE SCHEDULE
SYMBOL
MANUFACTURER
CATALOG #
DESCRIPTION
MOUNTING
VOLTS
NOTES
LAMPS
DAY-BRITE
2P4GA332R-365L-
120-1/3EB
3 TUBE, 18 CELL, 2' X 4'
FLUORESCENT PARALOUVER
LAY -IN
120
FIXTURES MARKED NL FOR NIGHTLIGHT USE
CHECK WITH MM FOR EXISTING
(3) 38 W T8
GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. .
rfl�GF1
WP=WEATHER PROOF OVER
FOUR PLEX OUTLET +15 ABOVF FINISHED FLOOR, TYPICAL
STOCK OF LIGHTS
UNLESS NOTED OTHERWISE NO MORE THAN 3 PER CIRCUIT.
LITHONIA
LHQM SW 3R 120
COMBINATION EXIT/EMERG,
WITH BATTERY PACK
SURFACE
120
LLD
ELECTRICAL SYMBOLS
SYMBOL
DESCRIPTION
ELECTRICAL PANEL, FIELD VERIFY LOCATION. SEE ELECTRICAL RISER DIAGRAM
®
FOR MORE INFORMATION AND WORK RESPONSIBILRY
SWITCH D=DIMMER M=MOTION SENSOR
DUPLEX OUTLET +150 ABOVE FINISHED FLOOR, TYPICAL UNLESS NOTED
OTHERWISE OUTLETS SHALL NOT BE IN MIRRORS, ADJUST LOCATIONS
ACCORDINGLY VERIFY CHANGES WITH TMW OR ARCHITECT.
GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. .
rfl�GF1
WP=WEATHER PROOF OVER
FOUR PLEX OUTLET +15 ABOVF FINISHED FLOOR, TYPICAL
UNLESS NOTED OTHERWISE NO MORE THAN 3 PER CIRCUIT.
FLOOR MOUNTED DUPLEX AND DATA OUTLET.
•
O
OJUNCTION
J
BOX
TELEPHONE/DATA BOX MOUNTED AT 15' AFF WITH CONDUIT TO ABOVE CEILING.
PROVIDE PULL STRING.
Seal
S. Fq,'�.,�
-� 60910220. w
STATE OF `
�inu
Revision
Project No. DD04001
Date 4-13-04
Scale 1/4" = 1'-0"
Drawn By MSF
Checked By MSF
Sheet Title
LIGI-17"ING PLANS
Sheet No.
E2
� GENERAL NOTES
1, SEE KEYSTONE OFFICE PARK BUILDING STANDARDS FOR ALL GENERAL INFORMATION.
2. ALL DEMISING WALLS BETWEEN TENANT SUITES AND COMMON AREAS TO BE 3 5/8'
METAL STUDS W/ 5/8' GYP. EITHER SIDE FROM FLOOR TO UNDERSIDE OF DECK
ABOVE. 3 1/2' INSULATION TO BE INSTALLED BETWEEN STUDS.
3. ALL DOOR ROUGH OPENINGS SHALL BE FRAMED 6' FROM ADJACENT WALL CORNER
UNLESS OTHERWISE NOTED,
4. PROVIDE WOOD BLOCKING IN NEW WALLS FOR ALL WALL HUNG ITEMS INCLUDING
MILLWORK, WALLSTOPS, CABINETRY, ETC, ALL WOOD BLOCKING MUST BE FIRE
TREATED. ALL WALL HUNG ITEMS THAT ARE TO BE HUNG ON EXISTING WALLS
SHALL BE FASTENED TO EXISTING STUD FRAMING.
5. ALL PLAN DIMENSIONS ARE TAKEN FROM FACE OF NEW GYPSUM PARTITION
OR FACE OF EXISTING CONSTRUCTION UNLESS OTHERWISE NOTED,
6. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD CHECKING ALL
DIMENSIONS AND MEASUREMENTS, IF JOB CONDITIONS PREVENT OBTAINING
DIMENSI❑NS OR RESULTS AS SHOWN OR SPECIFIED, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR INFORMING DESIGN/APPLICATIONS, INC. BEFORE ANY
CONSTRUCTI❑N IS STARTED.
7, EACH CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AS INDICATED ON THE
DRAWINGS AND REPORT ANY DISCREPANCY THAT MAY OCCUR TO THE GENERAL
CONTRACTOR, ANY IRREGULARITIES SHALL BE REPORTED TO DESIGN/APPLICATIONS,
INC., FROM THE GENERAL CONTRACTOR,
8. SHOP DRAWINGS OR CATALOG CUTS MUST BE SUBMITTED TO DESIGN/APPLICATIONS,
INC. FOR APPROVAL, ON ALL MATERIALS OR ITEMS IF THE CONTRACTOR CHOOSES
TO DEVIATE FROM THAT SHOWN ON THE DRAWINGS OR IF THE DRAWING DOES
NOT INDICATE A SPECIFIC MANUFACTURER OR MODEL NUMBER,
9. GENERAL CONTRACTOR SHALL EXPEDIATE PREPARATION AND SUBMITTAL OF ALL
SHOP DRAWINGS TO ALLOW SUFFICIENT TIME FOR FOR CHECKING, FABRICATION,
AND/OR ORDERING AND DELIVERY OF MATERIALS & EQUIPMENT.
10. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OVERSEEING THAT ALL
MATERIALS AND LABOR SHALL BE IN ACCORDANCE WITH THE BEST QUALITY
STANDARDS OF THE RESPECTED TRADE, THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR OVERSEEING THAT ALL WORK SHALL BE IN ACCORDANCE WITH
THE STATE UNIFORM BUILDING CODES AND STANDARDS FOR ALL GENERAL
CONSTRUCTION, MECHANICAL, AND ELECTRICAL WORK AND LOCAL AND FEDERAL
CODES AND STANDARDS.
11, ALL DETAILS, MATERIALS, AND INSTALLATIONS OF SAME ARE SUBJECT TO APPROVAL
BY DESIGN/ APPLICATIONS, INC. AND FINAL APPROVAL BY THE OWNER.
12. ALL EXISTING BLINDS TO BE CLEANED, ANY DAMAGED BLINDS SHALL BE REPAIRED
OR REPLACED IF REQUIRED.
13, NEW WOOD STAINED SILLS ARE TO MATCH EXISTING IN BUILDING W/ OVER
HANG OF 3/4'.
DESIGN/BUILD NOTES:
1. FIRE PROTECTION CONTRACTOR TO BE RESPONSIBLE FOR LOCATING SPRINKLER
HEADS AS REQUIRED BY NFPA AND FILING THE APPROPRIATE DRAWINGS WITH
THE CITY AND STATE OFFICIALS. FIRE PROTECTION CONTRACTOR RESPONSIBLE
FOR SMOKE DETECTION DEVICES.
2. MECHANICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR FIGURING
CFM NUMBERS ON SUPPLY DIFFUSERS, AND FOR LOCATING RETURN AIR OUTLETS.
3. MECHANICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR LOCATING
THERMOSTATS AND COORDINATING LOCATION WITH OWNER AND TENANT'S FURNITURE.
4. ELECTRICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR PROVIDING
LIFE -SAFETY DEVICES WHERE REQUIRED BY CODE. SUCH AS EXIT SIGNS, HORNS,
STROBES AND SPEAKERS.
5. ELECTRICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR ALL
CIRCUITING OF OUTLETS AND LIGHT FIXTURES.
6. ELECTRICAL DESIGN/BUILD CONTRACTOR TO BE RESPONSIBLE FOR EMERGENCY
LIGHTING IN SPACE: EMERGENCY BATTERY PACKS OR NIGHT LIGHTS CONNECTED TO
EMERGENCY POWER SOURCE IS REQUIRED IF SPACE CONTAINS 100 PERSONS OR
MORE.
7. WHERE MULTIPLE SWITCHES ARE REQUIRED, PROVIDE ONE COVER PLATE.
N
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
WALL LEGEND
EXISTING WALL TO REMAIN
EXISITING WALL TO BE REMOVED
DEMOLITION NOTES:
1. CONT'R TO REMOVE ALL EXISTING CARPET AND BASE.
2. CONT'R TO SALVAGE ALL DOORS AND FRAMES FOR REUSE.
3. REMOVE ALL EXISTING ORBIT STYLE KNOBS ON DOORS AND REPLACE WITH NEW LEVER STYLE.
SEE DOOR HARDWARE NOTES FOR DETAILS.
1\
0
3'W CHERR
STAINED W
TRIM
00
FIN
S.C. WOOD
DOOR, CHERRY
STAINED
�o
DOOR TYPES
SCALE: 1/4' = F-0'
3"W CHERRY
STAINED WOOD
TRIM
4 4 -
FRAME TYPES
�3�
D2
3.C. WOOD
IOOR, CHERRY
STAINED
3/8' TEMPERED
GLASS •�
3" 3'
F2
D3
>" W SIDELITE
/8' TEMPERED
LASS "
00
ANODIZED
ALUMINUM FRA
ANODIZED
LUMINUM FRAME
1/2' TEMPERED
3LASS
S-6"
SCALE: 1/4' = V-0'
NOTES: 1. DOOR FRAME TRIM: BUTZ LUMBER, BLC 364, OAK, 3/4" X 3". STAINED ST -1.
2. F2 TO HAVE KAWNEER OR EQUAL, 3/4"X3/4"X1/8" EXTRUDED CLEAR ANODIZED ALUMINUM
U CHANNEL TOP & BOTTOM. CLEAR SYLICONE CAULK WHERE GLASS MEETS WALL.
WINDOW IS DRYWALL WRAPPED. BOTTOM @ 2'AFF, TOP HT 8'-4", MEETS DOOR NOT FRAME.
DOOR SCHEDULE
No.
DOOR
LEGEND
FRAME
17 EXISTING
\\ EXISTING
SALVAGE
DDDR AND FRAME TO REMAIN
DOOR AND FRAME 1'0 BE REMOVED
FOR REUSE
MATERIA
DEMOLITION NOTES:
1. CONT'R TO REMOVE ALL EXISTING CARPET AND BASE.
2. CONT'R TO SALVAGE ALL DOORS AND FRAMES FOR REUSE.
3. REMOVE ALL EXISTING ORBIT STYLE KNOBS ON DOORS AND REPLACE WITH NEW LEVER STYLE.
SEE DOOR HARDWARE NOTES FOR DETAILS.
1\
0
3'W CHERR
STAINED W
TRIM
00
FIN
S.C. WOOD
DOOR, CHERRY
STAINED
�o
DOOR TYPES
SCALE: 1/4' = F-0'
3"W CHERRY
STAINED WOOD
TRIM
4 4 -
FRAME TYPES
�3�
D2
3.C. WOOD
IOOR, CHERRY
STAINED
3/8' TEMPERED
GLASS •�
3" 3'
F2
D3
>" W SIDELITE
/8' TEMPERED
LASS "
00
ANODIZED
ALUMINUM FRA
ANODIZED
LUMINUM FRAME
1/2' TEMPERED
3LASS
S-6"
SCALE: 1/4' = V-0'
NOTES: 1. DOOR FRAME TRIM: BUTZ LUMBER, BLC 364, OAK, 3/4" X 3". STAINED ST -1.
2. F2 TO HAVE KAWNEER OR EQUAL, 3/4"X3/4"X1/8" EXTRUDED CLEAR ANODIZED ALUMINUM
U CHANNEL TOP & BOTTOM. CLEAR SYLICONE CAULK WHERE GLASS MEETS WALL.
WINDOW IS DRYWALL WRAPPED. BOTTOM @ 2'AFF, TOP HT 8'-4", MEETS DOOR NOT FRAME.
DOOR SCHEDULE
No.
DIMENSIONS
DOOR
FRAME
HDWR.
REMARKS
MATERIA
FINISH
TYPE
MATERIA
FINISH:]SET
Ol
3' -0'x8' -4'x1 3/4'
D2
WOOD VENEER
CHERRY
STAINED
Fl
MAPLE
CHERRY
STAINED
#1
REUSE EXISTING ENTRY DOOR AT SUITE 130.
02
3' -0'x8' -4'x1 3/4'
D3
N
F3
r =r
>
#2
' n
rn
03
3' -0'x8' -4'x1 3/4'
DI
oo
0
00
FI
O om
C-4
00
0
#2
0
04
EXIST
EXIST
EXIST
�
o
Q
o
—
EXIST
05
2'-6'x8'-4'xl 3/4'
D1
d)
00
c
Fi
z
#2
O
06
3' -0'x8' -4'x1 3/4'
DI
F1
O W
#2
07
3' -0'x8' -4'x1 3/4'
DI
W O
W
F2
n
O
#2
08
3' -0'x8' -4'x1 3/4'
Dl
a_
n-,
F2
W
#2
NOTES: CHERRY STAIN IS TO MATCH STAIN IN EXISTING BUILDINGS AT KEYSTONE OFFICE PARK.
REUSE EXISTING DOORS WHERE APPLICABLE, TOUCH UP TO LIKE NEW.
HARDWARE SETS:
HARDWARE S T #1 HARDWARE SET #2
2 PR. BUTT HINGES 2 PR. BUTT HINGES
I LOCK SET/THUMB TURN I PASSAGE
I DOORSTOP I DOORSTOP
I SET SILENCERS I SET SILENCERS
SGHLAGE D SERIES, SPARTA SATIN BRASS ELECTRIFIED
LOGKSETS: D&O-PD-EU-5PA-6O6 TO BE INSTALLED
H/ ELEGTRIFIED HINGE OF 4 1/2 X4 1/2, ALL LOGKS TO
BE KEYED TO PRIMUS LOGKS.
ALL DOOR HARDWARE TO COMPLY WITH AMERICANS WITH
DISABILITIES ACT ACCESSABILITY GUIDELINES AND THE
REQUIREMENTS OF UBC CHAPTER 11, 1997 BUILDING CODE.
W-1
2 1/2" METAL
STUD FRAMING
® 16" O.C.
5/8" GYPSUM
WALLBOARD
EACH SIDE
WALL TO EXTEND TO
UNDER SIDE OF
FINISHED CEILING.
WALL TYPES
3 5/8" METAL
STUD FRAMING
@ 16" O.C.
5/8" GYPSUM
WALLBOARD
EACH SIDE
SOUND -ATTENUATING
BATTS INSIDE WALL
& 2 FT EITHER SIDE
ADVVE FINISHED CEiLiNG.
WALL TO EXTEND TO
UNDER SIDE OF
FINISHED CEILING.
NO SCALE
NOTE: ALL WALLS TO BE W-1 UNLESS NOTED OTHERWISE.
W-3 IS TO BE 3 EQUAL PANELS OF STORE FRONT 1/2" TEMPERED GLASS
W-3 WITH ANODIZED ALUMINUM FRAMES. SYSTEM TO INCLUDE STORE FRONT DOOR.
ALL HEIGHTS TO 9'-9" OR EQUAL TO OTHER DOOR HEIGHTS IN OFFICE.
3" 3"
N
OVERALL FLOOR PLAN
SCALE: NONE
N
ARCHITECTURAL PLAN
SCALE: 1/8" = 1'-0"
WALL LEGEND
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION.
SEE WALL TYPES FOR DETAILS.
W
DOOR LEGEND
EXISTING DOOR AND FRAME TO REMAIN
�O NEW DOOR AND FRAME. REFER
TO DOOR SCHEDULE ON THIS SHEET.
t j
ARCHITECTURAL NOTES:
O CONT'R TO SUPPLY & INSTALL FLOOR TO CEILING STOREFRONT WALL (10'-0" WIDE) W/
1 THREE EQUAL PANELS. INCLUDE 1/2' TEMPERED GLASS, FRAMING SYSTEM TO BE
BRUSHED ANODIZED ALUMINUM.
O SUPPLY & INSTALL 3'-0" PREMANUFACTURED BASE CABINETS, CHERRY STYLE W/ PLASTIC
LAMINATE COUNTER TOP, END AND BACK SPLASH.
SUPPLY & INSTALL 5'-6" PREMANUFACTURED BASE CABINETS, CHERRY STYLE W/ PLASTIC
O LAMINATE COUNTER TOP, END AND BACK SPLASH. SUPPLY SINGLE BOWL STAINLESS STEEL SINK W/
ADA COMPLIANT LEVER FAUCET. ALLOW FOR HOT AND COLD WATER.
OSUPPLY & INSTALL WATER LINE FOR ICE MAKER IN TENANT SUPPLIED REFRIGERATOR.
Z_
o
W
N
00
n
W
O
cll�
O
Q0Q0
Q
C'C5
^_
W
C__
Q
N
o
r =r
>
z
' n
rn
�
w�
z
oo
0
00
O om
C-4
00
0
0
UU)
N
00
z
�
o
Q
o
—
O
d)
00
c
z
U
Z_
o
W
N
00
n
W
O
cll�
O
Q0Q0
Q
W
W
Q
U
W �cy
o
wC/�
z
O
w�
z
z
00
O om
0
0
UU)
w
z
�
o
—
O
z
U
O
z
O W
W O
W
n
O
a_
n-,
W
I—
U
W
W
C�d=
W
U
Q:�
Q
Q
Revisions:
own.,,�,
o
i
110.4285
WATE OF
3
t�O 1A�..�
ss4f, f �,•
Issue:
CONST.
DOC.
Date:
MARCH 31 ,
04
Sheet:
Al D1-01
EXISTING
SCALE: 1/8" = 1'-0"
EXISTING
- --r- �' nl - - -
;-----I----
-f--7 —1h
I i 111 I 11 Irl — — --
I I III L� �J I 11 I
I i III I 11 II I
i I III i 11 I I
I I III I 1 Ic—=.p I
I I III i 11 1
11
I 11 II a� I i i
i it II I I I
11 � — 1 ii II I I jyi
REFLECTED CEILING PLAN
REFLECTED CEILING NOTFS--
1. ALL EXISTING LIGHT FIXTURES ARE TO BE REMOVED.
2. ALL EXISTING CEILING TILE IS TO BE REMOVED.
3. REMOVE CEILING GRID AS SHOWN TO MEET NEW LAYOUT REQUIREMENTS.
REFLECTED CEILING LEGEND
NEW 2'X2' GRID & TILE GTOM ACOUSTIC SUPPLY
GRID: ARMSTRONG PRELUDE XL. XL8323 WHITE, 15/16"W
TILE: CLEOTEX, CASMERE 2'X2'X3/4", PCM454, W/TAGULAR REVEAL.
I I
L i - EXISTING 4'X2' TILE TO BE REMOVED,
I I
I I
NEW 2'X4' 18 CELL PARABOLIC FIXTURES, 3000 KELVIN BULB
PROPERTY MGM'T HAS 15 IN STOCK, CONT'R TO MATCH REMAINDER.
NEW NITE LITE, TO MATCH 2'X4' FIXTURE AS NOTED ABOVE.
M NEW SWITCH, DECORA WHITE ROCKER STYLE AT 48" AFF ON CENTER.
NEW EXIT SIGNAGE
D° NEW 2'X2' SUPPLY DIFFUSER, VERIFY STYLE W/ PROPERTY MGM'T.
r -1
PROPOSED REFLECTED CEILING
SCALE: 1/8" = 1'-0"
REFLECTED CEILING NOTES.-
1.
OTES:
1. FINISHED CEILING HEIGHT IS 9'-0" AFF.
2. ALL SPRINKLER HEADS TO BE LOCATED, PROVIDE FULLY RECESSED STYLE W/ COVERS
TO MATCH NEW BUILDING STANDARD.
3. ELECTRICIAN RESPONSIBLE FOR ALL FIRE/LIFE SAFETY DEVICE LOCATIONS.
Im
PLAN W
3'VENT
1/2' V.
SINK
��1NOCP�IpN>
TYPICAL INASTF. 8, VENT
DIAGRAM AT
NO SCALE
BREAK ROOMS
ELECTRICAL PLAN
SCALE: 1/8" = 1'-0"
ELECTRICAL LEGEND
=@E EXISTING DUPLEX RECEPTACLE
NEW DUPLEX RECEPTACLE
NEW QUADRAPLEX RECEPTACLE
NEW GROUNDED DUPLEX RECEPTACLE
b NEW DATA/COMMUNICATIONS DROP
►4E EXISTING DATA/COMMUNICATIONS DROP
® NEW FLUSH FLOOR MOUNTED DUPLEX
RECEPTACLE & DATA OUTLET
ELECTRICAL NOTES:
1. ALL DUPLEX RECEPTACLE PLUGS, COVER PLATES & ROCKER SWITHES TO BE WHITE DECORA STANDARD.
2. ANY DUPLEX RECEPTACLES, DATA BOXES OR BLANK COVER PLATES NOT SHOWN IN EXISTING WALLS
ARE TO BE REMOVED. FILL, SPACKLE AND PAINT WALL TO LIKE NEW.
IV
OVERALL PLAN cT
SCALE: NONE
N
FINISH PLAN
SCALE: 1/8" = 1'-0"
FINISHES:
CARPET:
CPT -1 COLOR TO BE DETERMINED
CARPET BASE:
B-1 4 1/2" HIGH CARPET BASE W/ 1"W X 1-1/2" H WOOD TRIM CHERRY STAINED
(ST -1). COLOR TO BE DETERMINED
PAINT/WALLCOVERING•
PT -1 COLOR TO BE DETERMINED
ST -1 CHERRY STAIN TO MATCH EXISTING IN COMMON AREAS OF EXISTING
KEYSTONE OFFICE PARK BUILDINGS.
NEW WALLS TO RECEIVE 1 COAT PRIMER, 2 COATS CASHMERE FINISH MINIMUM.
EXISTING WALLS TO RECEIVE TWO COATS CASHMERE FINISH MINIMUM.
COLOR SUBMITTAL SAMPLE REQUIRED PRIOR TO PAINTING.
PLASTIC LAMINATE:
PL -1 COLOR TO BE DETERMINED
CEILING TILE/GRID:
CT -1 TILE: 2'X2'X3/4" CELOTEX, CASHMERE PCM -454, W/ TAGULAR REVEAL.
GRID: ARMSTRONG PRELUDE XL, XL8323-WHITE 15/16".
ii
• CAI. .� f%'<F ..
FINISH
LEGEND
W
o
FLOORING TYPE
## BASE TYPE
## WALL TYPE
N
FINISHES:
CARPET:
CPT -1 COLOR TO BE DETERMINED
CARPET BASE:
B-1 4 1/2" HIGH CARPET BASE W/ 1"W X 1-1/2" H WOOD TRIM CHERRY STAINED
(ST -1). COLOR TO BE DETERMINED
PAINT/WALLCOVERING•
PT -1 COLOR TO BE DETERMINED
ST -1 CHERRY STAIN TO MATCH EXISTING IN COMMON AREAS OF EXISTING
KEYSTONE OFFICE PARK BUILDINGS.
NEW WALLS TO RECEIVE 1 COAT PRIMER, 2 COATS CASHMERE FINISH MINIMUM.
EXISTING WALLS TO RECEIVE TWO COATS CASHMERE FINISH MINIMUM.
COLOR SUBMITTAL SAMPLE REQUIRED PRIOR TO PAINTING.
PLASTIC LAMINATE:
PL -1 COLOR TO BE DETERMINED
CEILING TILE/GRID:
CT -1 TILE: 2'X2'X3/4" CELOTEX, CASHMERE PCM -454, W/ TAGULAR REVEAL.
GRID: ARMSTRONG PRELUDE XL, XL8323-WHITE 15/16".
ii
• CAI. .� f%'<F ..
V)
�z
wQ
U n
W
LL
W
�z
n1
Q
_U
►- z
U
W -
� W
W U
Revisions:
00
W
o
�
N
::D
�D
(J�
_;t
Q
n.
Q
W
z
U
GZS
Q
�
o
C�
(f
N
f�
��
>
Vim-
�
z0
0
0
00
�
0
o
0
o
Q
`
z
N
00
0
�
o
z
n
V)
�z
wQ
U n
W
LL
W
�z
n1
Q
_U
►- z
U
W -
� W
W U
Revisions:
Flo, 4285
STATE OF
Vol '%0-)
I
sue:
CONST. DOC.
F
RCH 31 , 04
U
W
ry
W
0
n
W
W
Q
Sheet:RCPI
E1 %F1 -0
1
00
W
o
�
N
::D
�D
(J�
_;t
Q
n.
Q
W
z
U
Q
�ry
o
LL
(f
z
0
W
=
z0
J
00-)
0
LLl
Q
z
w
�
o
z
n
Flo, 4285
STATE OF
Vol '%0-)
I
sue:
CONST. DOC.
F
RCH 31 , 04
U
W
ry
W
0
n
W
W
Q
Sheet:RCPI
E1 %F1 -0
1