HomeMy WebLinkAboutE-3.04GENERAL POWER PLAN NOTES:
1. EXACT LOCATION OF MECHANICAL, PLUMBING, KITCHEN, FURNITURE SYSTEMS, OWNER
FURNISHED EQUIPMENT, ETC. THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON
THE MECHANICAL, PLUMBING, AND/OR ARCHITECTURAL DRAWINGS. COORDINATE EXACT
LOCATIONS WITH RESPECTIVE CONTRACTORS AND/OR VENDORS PRIOR TO ANY
ROUGH -INS.
2. REVIEW AND COORDINATE WITH ALL TRADES' CONTRACT DOCUMENTS TO DETERMINE
SPECIFIC MOUNTING LOCATIONS FOR EQUIPMENT WITH ELECTRICAL CONNECTIONS.
COORDINATE EXACT MOUNTING LOCATIONS WITH THE SPECIFIC TRADE AND ARCHITECT.
3. MINIMUM CONDUCTOR SIZE FOR 277 VOLT BRANCH CIRCUITS SHALL BE 12 -AWG. FOR
277 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150 LINEAR FEET A MINIMUM WIRE
SIZE OF 10 -AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH
CIRCUIT PANELBOARD.
4. MINIMUM CONDUCTOR SIZE FOR 120 VOLT BRANCH CIRCUITS SHALL BE 12 -AWG. FOR
120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 100 LINEAR FEET, A MINIMUM WIRE
SIZE OF 10 -AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH
CIRCUIT PANELBOARD. FOR 120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150
LINEAR FEET, A MINIMUM WIRE SIZE OF 8 -AWG SHALL BE PROVIDED FROM FIRST
JUNCTION/OUTLET BOX TO BRANCH CIRCUIT PANELBOARD.
5. ALL WIRING SHALL BE IDENTIFIED BY PANELBOARD AND CIRCUIT NUMBER(S) IN ALL
CABINETS, JUNCTION BOXES, WIRING TROUGHS, ENCLOSURES, SPLICE OR TERMINATION
POINTS, ETC.
6. A NEW TYPED PANELBOARD DIRECTORY CARD SHALL BE PROVIDED FOR ALL PANELS
INSTALLED OR MODIFIED UNDER THIS CONTRACT. NEW DIRECTORY CARDS SHALL BE
LOCATED ON THE INSIDE DOOR OF ASSOCIATED PANELS.
7. FINALIZE ALL SECURITY DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO
ROUGH -IN.
8. PER N.E.C. ARTICLE 620, ELEVATOR PIT AND MACHINE ROOM LIGHTING SHALL NOT BE
CONNECTED TO THE LOAD SIDE OF GFCI TYPE RECEPTACLE(S).
EXISTING BUILDING FIRE ALARM SYSTEM NOTES:
1. PRIOR TO BID SUBMITTAL, THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE WITH
BUILDING MANAGEMENT AND THE BUILDING APPROVED FIRE ALARM SYSTEM VENDOR TO
VERIFY THE EXISTING SYSTEM, OPERATIONS, COMPONENTS, PANEL LOCATIONS, CABLING,
ROUTING REQUIREMENTS, ETC.
2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT AND THE
FIRE ALARM SYSTEM VENDOR FOR ALL NEW COMPONENTS AND/OR SYSTEM
MODIFICATIONS AS REQUIRED TO ACCOMMODATE RE -USE OF EXISTING AND/OR NEW FIRE
ALARM DEVICES) AND CODE COMPLIANCE OPERATION.
3. FIRE ALARM DEVICE LOCATIONS ARE DIAGRAMMATIC ONLY. THE FIRE ALARM SYSTEM
VENDOR SHALL BE RESPONSIBLE TO VERIFY ALL NEW AND/OR EXISTING DEVICE
SPECIFICATIONS AND CHARACTERISTICS BASED ON EACH SYSTEM DEVICE SPECIFICATIONS.
PROVIDE FINAL DEVICE COUNTS AND LAYOUT DRAWINGS OF DEVICE LOCATIONS TO MEET
ALL STATE AND LOCAL FIRE ALARM CODE REQUIREMENTS.
4. PROVIDE ALL NEW EQUIPMENT AND DEVICES AS REQUIRED FOR A COMPLETE AND CODE
COMPLIANT SYSTEM. THE ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM VENDOR
SHALL BE RESPONSIBLE TO PROVIDE ALL SERVICES REQUIRED TO PROVIDE A "COMPLETE
AND OPERATIONAL SYSTEM" PER ALL LOCAL MUNICIPALITY AND STATE CODE
REQUIREMENTS. THIS INCLUDES BUT IS NOT LIMITED TO: PRODUCING FIRE ALARM PLAN
DRAWINGS AND SPECIFICATIONS FOR PERMITTING, SHOP DRAWINGS, AND INSTALLATION.
ALL DOCUMENTS MUST INCLUDE ALL SIGNALING CIRCUIT LOADS, VOLTAGE DROPS, WIRING
DIAGRAMS WIRE SIZE, BATTERY CALCULATIONS, ETC. PER MUNICIPAL CODE OF THE CITY
OF INDIANAPOLIS, AND STATE OF INDIANA CODE REQUIREMENTS.
K
K
TO RACK (#6 AWG)
TO RACK (#6 AWG)
TO RACK (#6 AWG)
TO BUILDING "TMGB" IN MAIN TELEPHONE CLOSET (#6 AWG)
Oil 1110
NEMA COPPER LUGS. SIZED PER
CONDUCTOR SIZE INDICATED ON
DRAWINGS. (TYPICAL)
GROUND BAR ASSEMBLY - 1/4"x 2"x 12" NEMA BAR
CHATSWORTH #13622-012 COMPLETE WITH INSULATORS
AND MOUNTING BRACKETS.
ALONG "TTB" IN TELECOM ROOM
GROUND BAR DETAIL "TGB"
SCALE: NOT TO SCALE
NOTES:
1. VERIFY EXACT MOUNTING LOCATION OF TGB WITH
IT DEPARTMENT PRIOR TO ANY ROUGH -IN.
TO EXISTING POWER
AS REQUIRED
3/4"C TO ACCESS FACR 3/4"C TO FACP (FIRE ALARM CONTROL PANEL)
CONTROL PANEL JB
I:y9l1111111110
CARD READER/ELECTRIC STRIKE DETAIL
CR FLUSH MOUNTED BACK BOX ON SECURE SIDE OF DOOR FOR CARD READER.
MOUNT PER ADA REQUIREMENTS.
TO JB FACR FIRE ALARM CONTROL RELAY FOR DOOR RELEASE.
JBJUNCTION BOX 8" X 10" W/COVER, ON SECURE SIDE OF SPACE 6" ABOVE
ACCESSIBLE CEILING.
DB ES I ELECTRIC STRIKE CONCEALED WITHIN DOOR FRAME.
CR ES
O MD MOTION DETECTOR
pB "REQUEST TO EXIT" PUSHBUTTON - FLUSH MOUNTED ON NON -SECURE SIDE
OF DOOR, MOUNTED PER ADA REQUIREMENTS.
• Integrated
l� Engineering
Consultants, Inc.
9700 ROCKSIDE RD. SUITE #290
CLEVELAND, OH 44125
(P): 216.901.6711
(F): 216.901.6712
www.iec-inc.cc
No.11400468 -
•; • -
SCALE:
Electrical Power Plan ,/ SS ALE:
PANEL "CR"
208Y/120V-3�-0
Enlarged Telecom Room 403 Power Plan SCALE:
1/4" = 1'-0" 1 2J
RELEASED IFOR CONSTRICTION
Subject to aompdiianice with ®III regofatiens
of State and (Feel Endes
ICltp of Caimal
ntro DATE: 02/23/18
14a11010.1t41IN
COFFEE MAKER LIH-1
30-277V-1�
P4/41
P4/39 i
5
MICROWAVES(2) I REFRIGERATOR
Enlarged HIVE 414A Power Plan SCALE:
1/4" = 1'-0' 131
ELECTRICAL CODED NOTES: XX
O WIRE INTO EXISTING TOILET ROOM RECEPTACLE CIRCUIT.
O 4" EMT CONDUIT WITH PULLSTRING AND INSULATING BUSHING AT BOTH ENDS.
H
3#10, #10(G), 3/4"1
CR/22,24
L Y E R
LEW
AJM
30/2
CR/2,4 CR/6,8
FLOOR
60/2
Client Approval:
20/2 20/2
Date:
3#6, #10(G), 3/4"
CR/3
CR/10,12
20/2
CR/14,16
SINGLE DOOR SECURITY DETAIL
2O/2
SCALE: NONE
CR
CR/18,2
20/2
NOTES:
Issue For Permit: 01/29/18
�
1. CARD READER PROVIDED BY LIBERTY MUTUAL'S SECURITY VENDOR. ELECTRIC STRIKE
:12R/1
Revision
PROVIDED BY DOOR HARDWARE VENDOR.
P4/37
2. THE ELECTRICAL CONTRACTOR/FIRE ALARM VENDOR IS RESPONSIBLE FOR ALL FIRE ALARM
%
HARDWIRE: 2 -POLE 60A INPUT BREAKER P4/25 27
P4/ P4/29 P4/35
RELATED WORK TO PROVIDE A COMPLETE OPERATIONAL DOOR PER ALL STATE AND LOCAL
TGB
HARDWIRE TERMINAL BLOCK 3W+G P4/33
CODE REQUIREMENTS.
/
(L -L -N -G) TO CHASSIS. L4/18
3. COORDINATE WITH LIBERTY MUTUAL'S SECURITY VENDOR PRIOR TO ANY ROUGH -IN THE
EXACT REQUIREMENTS FOR ALL CONDUITS, DEVICE BACK BOX SIZES, LOCATIONS, MOUNTING
HEIGHTS, ETC. COORDINATE WITH FIRE ALARM CONTRACTOR AND VENDOR FOR FIRE ALARM
INTERFACE POINTS AS REQUIRED.
42" 42" U 14291 42" 4
Enlarged Telecom Room 403 Power Plan SCALE:
1/4" = 1'-0" 1 2J
RELEASED IFOR CONSTRICTION
Subject to aompdiianice with ®III regofatiens
of State and (Feel Endes
ICltp of Caimal
ntro DATE: 02/23/18
14a11010.1t41IN
COFFEE MAKER LIH-1
30-277V-1�
P4/41
P4/39 i
5
MICROWAVES(2) I REFRIGERATOR
Enlarged HIVE 414A Power Plan SCALE:
1/4" = 1'-0' 131
ELECTRICAL CODED NOTES: XX
O WIRE INTO EXISTING TOILET ROOM RECEPTACLE CIRCUIT.
O 4" EMT CONDUIT WITH PULLSTRING AND INSULATING BUSHING AT BOTH ENDS.
H
E
L
L Y E R
LEW
AJM
Approved by:
IS=
ARCH ITECTU RE
INTERIOR DESIGN
2 1 1 South 12th St.
P h i l a. , PA 1 9 1 0 7
21 5.922.7066
THE GENERAL CONTRACTOR IS RESPONSIBLE
TO VERIFY ALL DIMENSIONS ON SITE AND
CONFIRM SUCH DIMENSIONS AGAINST ACTUAL
SITE CONDITIONS. THE GENERAL CONTRACT—
OR SHALL COORDINATE ALL WORK AND
RELATED TRADES, AND SHALL NOTIFY THE
ARCHITECT OF ANY INTERFERENCE OF
MECHANICAL, ELECTRICAL, OR PLUMBING
WORK WITH THE ARCHITECTURAL WORK AND
OF ANY CONFLICTS OR DISCREPANCIES IN
DIMENSIONS AGAINST ON SITE CONDITIONS
PRIOR TO PROCEEDING WITH THE WORK OR
PROCUREMENT OF MATERIALS.
Project:
Liberty
Mutual.
INSURANCE
450 East 96th St
4th Floor
Indianapolis IN 46240
Project No: 047.41
Drawing:
Electrical
Power Plan
No. E— 3.04
Drawn by:
M E B
Checked by:
AJM
Approved by:
AJM
Client Approval:
Date:
Issue Date:
01/26/18
Issue For Permit: 01/29/18
No.
Date
Revision
Scale: 1/8" =
1'-0"
Drawing:
Electrical
Power Plan
No. E— 3.04