HomeMy WebLinkAboutE-3.04GENERAL POWER PLAN NOTES: 1. EXACT LOCATION OF MECHANICAL, PLUMBING, KITCHEN, FURNITURE SYSTEMS, OWNER FURNISHED EQUIPMENT, ETC. THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL, PLUMBING, AND/OR ARCHITECTURAL DRAWINGS. COORDINATE EXACT LOCATIONS WITH RESPECTIVE CONTRACTORS AND/OR VENDORS PRIOR TO ANY ROUGH -INS. 2. REVIEW AND COORDINATE WITH ALL TRADES' CONTRACT DOCUMENTS TO DETERMINE SPECIFIC MOUNTING LOCATIONS FOR EQUIPMENT WITH ELECTRICAL CONNECTIONS. COORDINATE EXACT MOUNTING LOCATIONS WITH THE SPECIFIC TRADE AND ARCHITECT. 3. MINIMUM CONDUCTOR SIZE FOR 277 VOLT BRANCH CIRCUITS SHALL BE 12 -AWG. FOR 277 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150 LINEAR FEET A MINIMUM WIRE SIZE OF 10 -AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH CIRCUIT PANELBOARD. 4. MINIMUM CONDUCTOR SIZE FOR 120 VOLT BRANCH CIRCUITS SHALL BE 12 -AWG. FOR 120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 100 LINEAR FEET, A MINIMUM WIRE SIZE OF 10 -AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH CIRCUIT PANELBOARD. FOR 120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 150 LINEAR FEET, A MINIMUM WIRE SIZE OF 8 -AWG SHALL BE PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH CIRCUIT PANELBOARD. 5. ALL WIRING SHALL BE IDENTIFIED BY PANELBOARD AND CIRCUIT NUMBER(S) IN ALL CABINETS, JUNCTION BOXES, WIRING TROUGHS, ENCLOSURES, SPLICE OR TERMINATION POINTS, ETC. 6. A NEW TYPED PANELBOARD DIRECTORY CARD SHALL BE PROVIDED FOR ALL PANELS INSTALLED OR MODIFIED UNDER THIS CONTRACT. NEW DIRECTORY CARDS SHALL BE LOCATED ON THE INSIDE DOOR OF ASSOCIATED PANELS. 7. FINALIZE ALL SECURITY DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH -IN. 8. PER N.E.C. ARTICLE 620, ELEVATOR PIT AND MACHINE ROOM LIGHTING SHALL NOT BE CONNECTED TO THE LOAD SIDE OF GFCI TYPE RECEPTACLE(S). EXISTING BUILDING FIRE ALARM SYSTEM NOTES: 1. PRIOR TO BID SUBMITTAL, THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE WITH BUILDING MANAGEMENT AND THE BUILDING APPROVED FIRE ALARM SYSTEM VENDOR TO VERIFY THE EXISTING SYSTEM, OPERATIONS, COMPONENTS, PANEL LOCATIONS, CABLING, ROUTING REQUIREMENTS, ETC. 2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT AND THE FIRE ALARM SYSTEM VENDOR FOR ALL NEW COMPONENTS AND/OR SYSTEM MODIFICATIONS AS REQUIRED TO ACCOMMODATE RE -USE OF EXISTING AND/OR NEW FIRE ALARM DEVICES) AND CODE COMPLIANCE OPERATION. 3. FIRE ALARM DEVICE LOCATIONS ARE DIAGRAMMATIC ONLY. THE FIRE ALARM SYSTEM VENDOR SHALL BE RESPONSIBLE TO VERIFY ALL NEW AND/OR EXISTING DEVICE SPECIFICATIONS AND CHARACTERISTICS BASED ON EACH SYSTEM DEVICE SPECIFICATIONS. PROVIDE FINAL DEVICE COUNTS AND LAYOUT DRAWINGS OF DEVICE LOCATIONS TO MEET ALL STATE AND LOCAL FIRE ALARM CODE REQUIREMENTS. 4. PROVIDE ALL NEW EQUIPMENT AND DEVICES AS REQUIRED FOR A COMPLETE AND CODE COMPLIANT SYSTEM. THE ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM VENDOR SHALL BE RESPONSIBLE TO PROVIDE ALL SERVICES REQUIRED TO PROVIDE A "COMPLETE AND OPERATIONAL SYSTEM" PER ALL LOCAL MUNICIPALITY AND STATE CODE REQUIREMENTS. THIS INCLUDES BUT IS NOT LIMITED TO: PRODUCING FIRE ALARM PLAN DRAWINGS AND SPECIFICATIONS FOR PERMITTING, SHOP DRAWINGS, AND INSTALLATION. ALL DOCUMENTS MUST INCLUDE ALL SIGNALING CIRCUIT LOADS, VOLTAGE DROPS, WIRING DIAGRAMS WIRE SIZE, BATTERY CALCULATIONS, ETC. PER MUNICIPAL CODE OF THE CITY OF INDIANAPOLIS, AND STATE OF INDIANA CODE REQUIREMENTS. K K TO RACK (#6 AWG) TO RACK (#6 AWG) TO RACK (#6 AWG) TO BUILDING "TMGB" IN MAIN TELEPHONE CLOSET (#6 AWG) Oil 1110 NEMA COPPER LUGS. SIZED PER CONDUCTOR SIZE INDICATED ON DRAWINGS. (TYPICAL) GROUND BAR ASSEMBLY - 1/4"x 2"x 12" NEMA BAR CHATSWORTH #13622-012 COMPLETE WITH INSULATORS AND MOUNTING BRACKETS. ALONG "TTB" IN TELECOM ROOM GROUND BAR DETAIL "TGB" SCALE: NOT TO SCALE NOTES: 1. VERIFY EXACT MOUNTING LOCATION OF TGB WITH IT DEPARTMENT PRIOR TO ANY ROUGH -IN. TO EXISTING POWER AS REQUIRED 3/4"C TO ACCESS FACR 3/4"C TO FACP (FIRE ALARM CONTROL PANEL) CONTROL PANEL JB I:y9l1111111110 CARD READER/ELECTRIC STRIKE DETAIL CR FLUSH MOUNTED BACK BOX ON SECURE SIDE OF DOOR FOR CARD READER. MOUNT PER ADA REQUIREMENTS. TO JB FACR FIRE ALARM CONTROL RELAY FOR DOOR RELEASE. JBJUNCTION BOX 8" X 10" W/COVER, ON SECURE SIDE OF SPACE 6" ABOVE ACCESSIBLE CEILING. DB ES I ELECTRIC STRIKE CONCEALED WITHIN DOOR FRAME. CR ES O MD MOTION DETECTOR pB "REQUEST TO EXIT" PUSHBUTTON - FLUSH MOUNTED ON NON -SECURE SIDE OF DOOR, MOUNTED PER ADA REQUIREMENTS. • Integrated l� Engineering Consultants, Inc. 9700 ROCKSIDE RD. SUITE #290 CLEVELAND, OH 44125 (P): 216.901.6711 (F): 216.901.6712 www.iec-inc.cc No.11400468 - •; • - SCALE: Electrical Power Plan ,/ SS ALE: PANEL "CR" 208Y/120V-3�-0 Enlarged Telecom Room 403 Power Plan SCALE: 1/4" = 1'-0" 1 2J RELEASED IFOR CONSTRICTION Subject to aompdiianice with ®III regofatiens of State and (Feel Endes ICltp of Caimal ntro DATE: 02/23/18 14a11010.1t41IN COFFEE MAKER LIH-1 30-277V-1� P4/41 P4/39 i 5 MICROWAVES(2) I REFRIGERATOR Enlarged HIVE 414A Power Plan SCALE: 1/4" = 1'-0' 131 ELECTRICAL CODED NOTES: XX O WIRE INTO EXISTING TOILET ROOM RECEPTACLE CIRCUIT. O 4" EMT CONDUIT WITH PULLSTRING AND INSULATING BUSHING AT BOTH ENDS. H 3#10, #10(G), 3/4"1 CR/22,24 L Y E R LEW AJM 30/2 CR/2,4 CR/6,8 FLOOR 60/2 Client Approval: 20/2 20/2 Date: 3#6, #10(G), 3/4" CR/3 CR/10,12 20/2 CR/14,16 SINGLE DOOR SECURITY DETAIL 2O/2 SCALE: NONE CR CR/18,2 20/2 NOTES: Issue For Permit: 01/29/18 � 1. CARD READER PROVIDED BY LIBERTY MUTUAL'S SECURITY VENDOR. ELECTRIC STRIKE :12R/1 Revision PROVIDED BY DOOR HARDWARE VENDOR. P4/37 2. THE ELECTRICAL CONTRACTOR/FIRE ALARM VENDOR IS RESPONSIBLE FOR ALL FIRE ALARM % HARDWIRE: 2 -POLE 60A INPUT BREAKER P4/25 27 P4/ P4/29 P4/35 RELATED WORK TO PROVIDE A COMPLETE OPERATIONAL DOOR PER ALL STATE AND LOCAL TGB HARDWIRE TERMINAL BLOCK 3W+G P4/33 CODE REQUIREMENTS. / (L -L -N -G) TO CHASSIS. L4/18 3. COORDINATE WITH LIBERTY MUTUAL'S SECURITY VENDOR PRIOR TO ANY ROUGH -IN THE EXACT REQUIREMENTS FOR ALL CONDUITS, DEVICE BACK BOX SIZES, LOCATIONS, MOUNTING HEIGHTS, ETC. COORDINATE WITH FIRE ALARM CONTRACTOR AND VENDOR FOR FIRE ALARM INTERFACE POINTS AS REQUIRED. 42" 42" U 14291 42" 4 Enlarged Telecom Room 403 Power Plan SCALE: 1/4" = 1'-0" 1 2J RELEASED IFOR CONSTRICTION Subject to aompdiianice with ®III regofatiens of State and (Feel Endes ICltp of Caimal ntro DATE: 02/23/18 14a11010.1t41IN COFFEE MAKER LIH-1 30-277V-1� P4/41 P4/39 i 5 MICROWAVES(2) I REFRIGERATOR Enlarged HIVE 414A Power Plan SCALE: 1/4" = 1'-0' 131 ELECTRICAL CODED NOTES: XX O WIRE INTO EXISTING TOILET ROOM RECEPTACLE CIRCUIT. O 4" EMT CONDUIT WITH PULLSTRING AND INSULATING BUSHING AT BOTH ENDS. H E L L Y E R LEW AJM Approved by: IS= ARCH ITECTU RE INTERIOR DESIGN 2 1 1 South 12th St. P h i l a. , PA 1 9 1 0 7 21 5.922.7066 THE GENERAL CONTRACTOR IS RESPONSIBLE TO VERIFY ALL DIMENSIONS ON SITE AND CONFIRM SUCH DIMENSIONS AGAINST ACTUAL SITE CONDITIONS. THE GENERAL CONTRACT— OR SHALL COORDINATE ALL WORK AND RELATED TRADES, AND SHALL NOTIFY THE ARCHITECT OF ANY INTERFERENCE OF MECHANICAL, ELECTRICAL, OR PLUMBING WORK WITH THE ARCHITECTURAL WORK AND OF ANY CONFLICTS OR DISCREPANCIES IN DIMENSIONS AGAINST ON SITE CONDITIONS PRIOR TO PROCEEDING WITH THE WORK OR PROCUREMENT OF MATERIALS. Project: Liberty Mutual. INSURANCE 450 East 96th St 4th Floor Indianapolis IN 46240 Project No: 047.41 Drawing: Electrical Power Plan No. E— 3.04 Drawn by: M E B Checked by: AJM Approved by: AJM Client Approval: Date: Issue Date: 01/26/18 Issue For Permit: 01/29/18 No. Date Revision Scale: 1/8" = 1'-0" Drawing: Electrical Power Plan No. E— 3.04